AIRCOOLED HEAT EXCHANGER - CALCULATION RESULTS
Fans
Number of Fans 2 -
Fan Size 11 ft
Power per Fan 15 kW
Overall size
Bundle Face Area 30.5 m2
Total Plot Area 40 m2
Back Print
GEA Aircooled Systems (Pty) Ltd., July 2004 - 2007
All rights reserved
Design Requirements
Inlet Temperature 90 deg C
Required Outlet Temperature 48 deg C
Duty 0.6 MW
Ambient Temperature 38 deg C
Barometric Pressure 101.3 kPa
DescriptionViscous Fluid
Cooling
Operating Point
Exhaust Air Temperature 42.33 deg C
Inlet Face Velocity 3.98 m/s
Airside Pressure Drop 160 Pa
Geometry
Number of Bays 1 -
Number of Bundles 2 -
Tube Length 7.82 m
Number of Tubes per Bundle 123 -