Air Conditioning Carisma CRSO High Pressure Fan Coil...

40
NEW MB control board for Modbus communication protocol Compliant with ERP 2013 Regulation (EU) No. 327/2011 Air Conditioning Carisma CRSO High Pressure Fan Coil Units Quality management systems ISO 9001 – Cert. n° 0545/5 www.eurovent-certification.com www.certiflash.com

Transcript of Air Conditioning Carisma CRSO High Pressure Fan Coil...

Page 1: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

NEW

MB control board

for Modbus

communication protocol

Compliant with ERP 2013 Regulation (EU) No. 327/2011

Air ConditioningCarisma CRSO High Pressure Fan Coil Units

Air Conditioning

Carisma CRSO High Pressure Fan Coil Units

CRSO

- E

X -

04/1

4

COD

. A4

6901

00

C/04

/14

Sabiana s.p.a. • via Piave, 53 • 20011 Corbetta • Milano • Italy • phone +39.02.97203.1 r.a. / +39.02.97270429 / +39.02.97270576fax +39.02.9777282 / +39.02.9772820 • www.sabiana.it • [email protected]

Quality management systemsISO 9001 – Cert. n° 0545/5

www.eurovent-certification.comwww.certiflash.com

Page 2: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

INTRODUCTION

In line with innovative trends and modern industrial design,the Carisma CRSO fan coil range meets today’s demandingrequirements of performance, size, acoustics, low energy,ease of installation and maintenance. The Carisma CRSOfan coil unit has been designed around a platform of models,versions and accessories, all of which have been independentlytested and certified by Eurovent.

All Carisma CRSO fan coils with centrifugal fans are equippedwith electric motors which reduce electrical consumptioncomparative to previous models, with 5 speed motors asstandard offering greater flexibility in the selection of products.

New market trends have also led to an extension of the fourpipe model which now has a two row LTHW battery givingimproved outputs at lower flow and return temperatures.

A full range of control options is available including the Freepatented wireless control offering greater flexibility in theinstallation of units, with the highest precision in monitoringand maintaining the desired comfort conditions.

The Carisma CRSO model is complemented with a fullrange of accessories: various types of adjustment valves,additional electric heater, auxiliary condensatepump, air inlet/outlet diffusers for fittedinstallations.

• Available pressure • Fan absorption • Water pressure drop • Sound power

• Heating emission (2 pipe units) at the following conditions: - Entering water temperature +50°C - Entering air temperature +20°C - Waterflowrateasforthecoolingconditions

• Heating emission (4 pipe units) at the following conditions: - Water temperature +70°C E.W.T. +60°C L.W.T. - Entering air temperature +20°C

• Cooling total emission at the following conditions: - Water temperature +7°C E.W.T. +12°C L.W.T. - Entering air temperature +27°C dry bulb +19°C wet bulb

• Cooling sensible emission at the following conditions: - Water temperature +7°C E.W.T. +12°C L.W.T. - Entering air temperature +27°C dry bulb +19°C wet bulb

Sabiana take part to the Eurovent program of fan coil performance certification.The official figures are published in the web sitewww.eurovent-certification.com and in the web site www.certiflash.com.The tested performances are:

The descriptions and illustrations provided in this publication are not binding: Sabiana reserves the right,whilst maintaining the essential characteristics of the types described and illustrated, to make,

at any time, without the requirement to promptly update this piece of literature, any changes that it considersuseful for the purpose of improvement or for any other manufacturing or commercial requirements.

CONTENTS• Presentation Page 3

• Construction features Page 3

• Dimension, Weight, Water content Page 4

• EUROVENT Certification Page 6

• Main performance and technical characteristics Page 7

• Cooling emission tables Page 8

• Heating emission tables Page 12

• Correction factors table Page 14

• Operation limits Page 16

• Water pressure drop Page 17

• Accessories Page 18

• Wall electronic controls Page 24

• FreeSabiana wireless control system Page 30

• Controls and units MB version Page 32

• Management system for a network of fan coils Page 36

• PSM-DI and Sabianet electronic boards Page 38

Page 3: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

3

Carisma

CasingMade from 1 mm galvanized steel insulated with polyolefin (PO) foam(class M1).

FilterPolypropylene cellular fabric regenerating filter.The filter frame of galvanized steel is inserted into special plasticsliding guides fastened to the internal structure for easy insertionand removal of the filter.

Fan assemblyThe fans have aluminium or plastic blades directly keyed onthe motor with double aspiration and they are dynamically andstatically balanced during manufacture in order to have an extremelyquiet operation.

Electric motorThe motor is wired for single phase and has five speeds with capacitor.The motor is fitted on sealed for life bearings and is secured on anti-vibration and self-lubricating mountings.Internal thermal protection with automatic reset, protection IP 20, class B.

CoilIt is manufactured from drawn copper tube and the aluminium fins aremechanically bonded onto the tube by an expansion process. Thecoil has two 1/2 inch BSP internal connections and 1/8 inchBSP air vent and drain.The coil is not suitable for use in corrosive atmosphere or inenvironments where aluminium may be subject to corrosion.The connections are on the left hand side looking from theair outlet of the unit (see picture).On request or on site the connections can be movedto the other side.

Condensate collection trayMade from plastic (ABS UL94 HB) with an “L”-shaped plastic fitted onthe inner casing; the tray is insulated with polyolefin (PO) foam (class M1).The outside diameter of the condensate discharge pipe is 15mm.

Accessories and ControlsSee pages 18 - 24.

Range includes 4 air flow rates (from 375 to 2220 m3/h),each equipped with 3 or 4 row coil and with the possibilityto add a 1 or 2 row coil for 4 pipe systems.It is the most comprehensive range, perfect to meet allair-conditioning requirements of work environments likeoffices, shops, restaurants and hotel rooms featuringducted installations with available pressure up to 80 Pa.

Compliant with ERP 2013 Regulation (EU) No. 327/2011

Carisma CRSO version with centrifugal fan

Construction features

Presentation

Page 4: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

4

CRSO version Carisma

Ø 1/2" F

M

37

O

N U

Ø 15ext.

G H

230

WATER

INLET

WATER OUTLET

Ø 1/2" F

P

R

S

321

Ø 15ext.

HG

230

U

WATER OUTLET

WATER

INLET

133

125

4471

153

F150 10

17

D

12 12

GH

Ø 15 ext.230

119 *

E*

153

1711

9 *

7144

125

133

F10

D

E*12 12

511

D22 22

29100

12 12

G

H

Ø 15 ext.

230

Vertical Installation

Horizontal Installation

Dimensions, Weight, Water content

Heating additional coil (1 or 2 rows)3 or 4 row coils

Auxiliary condensate tray (optional)

Coil connections on the left

COIL CONNECTIONS

Supply frame dimension = E x 119 mm*

Supply frame dimension = E x 119 mm*

Page 5: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

5

CRSO version Carisma

600

X

Y

43,2

4,2

0,9

31,9

2,8

0,6

1,2

21,6

2,2

0,5

1,0

10,9

1,3

0,3

0,6

Ro

ws

Ro

ws

3 426,1

27,6

28,5

27,4

28,9

219,1

20,3

21,0

20,1

21,3

147,7

50,0

49,5

51,8

30,4

32,2

33,3

31,9

33,7

443,3

45,6

45,1

47,4

327,3

29,1

30,2

28,8

30,6

223,5

25,0

25,9

24,8

26,3

117,3

18,5

19,2

18,3

19,5

1689

645

669

218

205

145

260

460

185

105

475

65

260

820

41570

1526

1550

248

235

170

270

450

210

110

465

95

290

1790

31119

1075

1099

248

235

170

270

450

210

110

465

95

290

1250

2904

860

884

248

235

170

270

450

210

110

465

95

290

1035

34

+1+2

Model

Weight without packagingWeight with packaging

3

3+1

3+2

4

4+1

Model

D

E

F

G

H

M

N

O

P

R

S

U

X

Y

Model

PACKAGING

Dimension, Weight, Water content

Dimension (mm)

Weight (kg)

Water content (litres)

Page 6: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

6

CRSO version Carisma

(E) =Euroventcertifiedperformance.

(*) =Thesoundpressurelevelsare9dB(A)lowerthanthesoundpowerlevels andapplytothereverberantfieldofa100m3roomandareverberationtimeof0.5sec..

194535

5,954,395,558,9

13,514052594350

2115550

6,875,166,3311,517,214856624753

31285

607,405,626,7913,119,515858644955

9069224

247040

2,942,172,8511,23,88246523743

352550

3,192,373,0813,04,39049544045

458060

3,422,573,2814,74,89751574248

9069222

224040

1,581,141,669,05,34044523543

328550

1,811,311,8711,56,64647543845

431060

1,931,411,9812,97,35550574148

9066363

276040

4,443,364,1411,46,210751574248

388550

4,923,804,5713,77,412154604551

496060

5,204,054,8215,18,113457634854

9066368

CRSO 13+1 CRSO 23+1 CRSO 33+1 CRSO 43+1Model

m3/hPakWkWkWkPakPaW

dB(A)dB(A)dB(A)dB(A)

Speed(E)Airflow(E)Availablepressure(E)Coolingtotalemission(E)Coolingsensibleemission(E)Heating(E)DpCooling(E)DpHeating(E)Fan(E)Soundpoweroutlet(E)Soundpowerinlet+radiated(E)Soundpressureleveloutlet(*)Soundpressurelevelinlet+radiated(*)Plenumcode(E)

194535

5,954,397,298,96,814052594350

2115550

6,875,168,6211,59,214856624753

31285

607,405,629,4113,110,815858644955

9069224

247040

2,942,173,5710,68,38246523743

352550

3,192,373,9212,39,89049544045

458060

3,422,574,2513,911,49751574248

9069222

224040

1,581,141,919,06,94044523543

328550

1,811,312,2211,59,04647543845

431060

1,931,412,3912,910,35550574148

9066363

276040

4,443,365,6311,49,010751574248

388550

4,923,806,3613,711,012154604551

496060

5,204,056,7915,111,913457634854

9066368

CRSO 13 CRSO 23 CRSO 33 CRSO 43Model

m3/hPakWkWkWkPakPaW

dB(A)dB(A)dB(A)dB(A)

Speed(E)Airflow(E)Availablepressure(E)Coolingtotalemission(E)Coolingsensibleemission(E)Heating(E)DpCooling(E)DpHeating(E)Fan(E)Soundpoweroutlet(E)Soundpowerinlet+radiated(E)Soundpressureleveloutlet(*)Soundpressurelevelinlet+radiated(*)Plenumcode(E)

194535

6,514,687,8511,811,014052594350

2115550

7,595,549,3915,613,814856624753

31285

608,226,0510,3018,017,015858644955

9069224

247040

3,272,323,9018,114,38246523743

352550

3,572,554,3021,217,19049544045

458060

3,852,774,6924,320,19751574248

9069222

224040

1,741,232,065,44,24044523543

328550

2,011,432,417,05,64647543845

431060

2,151,542,607,96,45550574148

9066363

276040

4,803,526,009,78,010751574248

388550

5,363,996,8311,99,312154604551

496060

5,684,257,3113,210,513457634854

9066368

CRSO 14 CRSO 24 CRSO 34 CRSO 44Model

m3/hPakWkWkWkPakPaW

dB(A)dB(A)dB(A)dB(A)

Speed(E)Airflow(E)Availablepressure(E)Coolingtotalemission(E)Coolingsensibleemission(E)Heating(E)DpCooling(E)DpHeating(E)Fan(E)Soundpoweroutlet(E)Soundpowerinlet+radiated(E)Soundpressureleveloutlet(*)Soundpressurelevelinlet+radiated(*)Plenumcode(E)

EUROVENT Certification www.eurovent-certification.comwww.certiflash.com

COOLING

Enteringairtemperature+27°C d.b. +19°C w.b.Watertemperature + 7°C E.W.T.+12°C L.W.T.

HEATING

Enteringairtemperature +20°CEnteringwatertemperature +50°C

Waterflowrateasforthecoolingconditions

2 pipe units. Thefollowingstandardratingconditionsareused:

COOLING

Enteringairtemperature+27°C d.b. +19°C w.b.Watertemperature + 7°C E.W.T.+12°C L.W.T.

HEATING

Enteringairtemperature+20°CWater temperature + 70°C E.W.T. + 60°C L.W.T.

4 pipe units. Thefollowingstandardratingconditionsareused:

Page 7: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

7

CRSO version Carisma

(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec..

CRSO 13+1 CRSO 23+1 CRSO 33+1 CRSO 43+1Model

m3/hkWkWkWkPakPaW

dB(A)dB(A)

SpeedAir flowCooling total emissionCooling sensible emissionHeatingDp CoolingDp HeatingFanSound power LwSound pressure (*)

3752,221,643,6216,68,9414738

4102,361,763,9118,510,2465041

4702,591,964,3721,812,5545344

5402,842,184,8925,715,3655647

5953,022,355,2828,717,6765950

3752,501,823,9810,45,4414738

4102,681,964,3111,76,2465041

4702,962,194,8614,17,7545344

5403,272,465,4816,89,5655647

5953,502,665,9519,011,1765950

3752,221,642,2516,69,2414738

4102,361,762,3918,510,3465041

4702,591,962,6121,812,0545344

5402,842,182,8525,714,1655647

5953,022,353,0428,715,8765950

5803,422,575,5013,97,3884536

6653,752,866,1516,48,9954738

7654,123,196,8919,411,01075142

8704,483,537,6322,613,21205445

10405,014,058,7627,716,91405950

5803,852,776,0624,312,3884536

6654,273,106,8329,215,2954738

7654,723,477,7135,019,01075142

8705,163,848,5941,223,01205445

10405,834,439,9751,230,11405950

5803,422,573,2813,94,8884536

6653,752,863,5816,45,7954738

7654,123,193,9219,46,71075142

8704,483,534,2522,67,71205445

10405,014,054,7627,79,41405950

7454,383,317,1911,16,1974940

9505,164,028,7814,98,71215445

11505,854,6610,2318,711,51435950

13206,385,1911,4021,913,91646354

14156,685,4712,0423,815,41746455

7454,733,477,649,55,0974940

9505,644,229,4313,07,31215445

11506,444,9111,0816,59,81435950

13207,065,4712,4119,512,01646354

14157,405,7813,1321,213,31746455

7454,383,314,0811,16,0974940

9505,164,024,7914,98,01215445

11505,854,665,4018,710,01435950

13206,385,195,8921,911,71646354

14156,685,476,16

23,812,71746455

10006,214,599,909,65,01634940

13607,695,8812,7814,17,91915546

17058,947,0215,3518,511,02186051

19809,847,8817,3122,013,62376455

222010,598,6118,9125,116,02566657

10006,814,9110,4012,97,01634940

13608,566,3413,5719,411,41915546

170510,077,6316,4326,016,12186051

198011,168,5918,6131,220,12376455

222012,059,4120,4035,923,72566657

10006,214,595,769,614,51634940

13607,695,887,0414,120,81915546

17058,947,028,1418,527,02186051

19809,847,888,9522,032,02376455

222010,598,619,6325,136,62566657

1 2 3 4 5

1 2 3 4 5

1 2 3 4 5

1 2 3 4 5

1 2 3 4 5

1 2 3 4 5

1 2 3 4 5

1 2 3 4 5

1 2 3 4 5

1 2 3 4 5

1 2 3 4 5

1 2 3 4 5

CRSO 13 CRSO 23 CRSO 33 CRSO 43Model

m3/hkWkWkWkPakPaW

dB(A)dB(A)

SpeedAir flowCooling total emissionCooling sensible emissionHeatingDp CoolingDp HeatingFanSound power LwSound pressure (*)

CRSO 14 CRSO 24 CRSO 34 CRSO 44Model

m3/hkWkWkWkPakPaW

dB(A)dB(A)

SpeedAir flowCooling total emissionCooling sensible emissionHeatingDp CoolingDp HeatingFanSound power LwSound pressure (*)

Main performance and technical characteristics

COOLING

Entering air temperature + 27°C d.b. + 19°C w.b.Water temperature + 7°C E.W.T. + 12°C L.W.T.

AVAILABLE PRESSURE: 0 Pa

HEATING

Entering air temperature + 20°CEntering water temperature + 50°C

Water flow rate as for the cooling conditions

2 pipe units. The following standard rating conditions are used:

COOLING

Entering air temperature + 27°C d.b. + 19°C w.b.Water temperature + 7°C E.W.T. + 12°C L.W.T.

AVAILABLE PRESSURE: 0 Pa

HEATING

Entering air temperature + 20°CWater temperature + 70°C E.W.T. + 60°C L.W.T.

4 pipe units. The following standard rating conditions are used:

Page 8: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

8

CRSO version Carisma

54321543215432154321

54321543215432154321

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

595540470410375104087076566558014151320115095074522201980170513601000

595540470410375104087076566558014151320115095074522201980170513601000

3,253,052,782,542,385,424,844,454,053,687,216,916,335,594,7311,4310,639,668,316,69

2,322,161,951,751,643,963,473,152,832,555,325,064,573,963,288,407,726,915,824,57

55952547943741093183276569663312401188108996181419661829166214301151

32,829,324,921,018,831,826,022,318,815,927,325,321,617,212,828,825,321,316,211,0

2,922,742,512,292,154,844,333,983,633,316,446,175,664,994,2310,219,518,647,456,01

2,192,041,831,651,543,783,302,992,682,405,114,854,363,763,108,037,366,565,504,30

502472431393370833745685624569

11081061973859728

17561636148712811034

26,924,120,517,315,525,921,218,215,413,022,220,517,514,010,423,420,617,313,39,0

2,262,121,931,761,653,773,363,082,802,545,024,804,383,853,267,957,386,685,734,61

2,011,861,671,491,383,483,022,712,422,164,724,463,983,402,787,416,765,984,963,83

389365333303284649577530481438863825754663560

136812701149985792

16,815,012,710,79,6

16,413,311,49,68,1

14,012,911,08,76,4

14,812,910,88,25,5

1,701,591,441,301,222,852,512,292,071,883,793,613,282,862,406,005,544,994,243,38

1,701,591,441,301,222,852,512,292,071,883,793,613,282,862,406,005,544,994,243,38

292273247224210489432395357323651621564492413

1032

953858729581

10,08,87,46,25,59,87,86,65,54,68,47,76,55,13,78,87,66,34,73,1

2,902,732,492,272,144,824,313,963,613,296,416,145,634,974,2210,179,468,607,405,98

2,202,041,831,651,543,783,302,992,682,415,114,844,363,763,118,047,376,575,514,31

4994694283913688297416826225661102105696885472517491628147912731028

26,824,020,317,315,425,821,118,115,413,022,120,417,513,910,423,320,517,313,29,0

2,572,412,202,011,894,283,823,513,192,915,695,444,984,393,729,028,387,616,545,27

2,101,951,751,571,463,633,152,852,542,284,904,644,163,572,947,707,046,265,224,07

442415379346325736657603549500979936856755640

1551144213091124907

21,419,116,213,812,320,716,914,512,210,317,716,413,911,18,3

18,716,413,810,57,1

1,971,841,671,521,433,292,922,672,422,204,384,183,813,342,816,946,425,804,963,97

1,931,781,581,411,313,292,882,582,302,044,384,183,803,242,636,946,425,694,713,62

339317288262246566502460417378754719655574483

11931105998852683

13,111,79,88,37,4

12,810,38,87,46,2

11,010,18,56,74,9

11,610,18,46,34,2

1,461,361,231,111,042,452,161,961,771,603,273,112,812,452,045,174,764,273,612,86

1,461,361,231,111,042,452,161,961,771,603,273,112,812,452,045,174,764,273,612,86

251234211191178422371338304275562535484421351889819735621492

7,66,75,64,64,17,55,95,04,23,46,45,94,93,82,76,75,84,83,52,3

CRSO

13

CRSO

13

CRSO

23

CRSO

23

CRSO

33

CRSO

33

CRSO

43

CRSO

43

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

Qv

Qv

m3/h

m3/h

Speed

Speed

Mod.

Mod.

Cooling emission of 3 row coil

Cooling emission of 3 row coil

Entering air temperature: 27°C – R. H.: 50% – Available pressure: 0 Pa

Entering air temperature: 26°C – R. H.: 50% – Available pressure: 0 Pa

WT: 7/12 °C

WT: 7/12 °C

WT: 8/13 °C

WT: 8/13 °C

WT: 10/15 °C

WT: 10/15 °C

WT: 12/17 °C

WT: 12/17 °C

PcPsPcPs

48%

R.H. WT:

46%

Legend

WT = Water temperature

Pc = Cooling total emission

Ps = Cooling sensible emission

Qw = Water flow

Dp(c) = Water pressure drop

Speed = Fan speed

MAX = High speed

MED = Medium speed

MIN = Low speed

Qv = Air flow

Correction factors for different R.H.

0,951,000,901,00

0,941,000,881,00

7/12°C 8/13°C1,001,001,001,00

1,001,001,001,00

10/15°C 12/17°C

Page 9: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

9

CRSO version Carisma

54321543215432154321

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

595540470410375104087076566558014151320115095074522201980170513601000

2,562,412,192,001,884,273,813,493,182,905,685,434,964,383,719,008,367,586,515,25

2,101,951,751,571,463,623,152,852,552,284,904,634,163,582,947,707,046,265,234,07

4414143783443247346556015474989769348537536381548143713041120904

21,419,116,213,712,320,716,914,512,210,317,716,413,911,18,218,716,413,810,57,1

2,262,121,931,761,653,763,353,072,792,545,014,784,373,843,247,937,366,675,714,60

2,011,861,661,491,383,473,002,712,412,164,694,443,973,402,787,386,735,964,953,84

388364331302284647576528480436861823752661558

136512661147983790

16,915,112,810,89,6

16,513,311,49,68,1

14,113,011,08,86,4

14,913,010,98,25,6

1,711,601,451,311,232,862,532,312,091,893,813,633,302,882,426,035,575,024,273,40

1,711,601,451,311,232,862,532,312,091,893,813,633,302,882,426,035,575,024,273,40

294274249225211492435397359325656625567496416

1038959864734585

10,29,07,56,35,6

10,08,06,85,74,78,57,86,65,23,89,07,86,54,83,2

1,241,161,040,940,872,241,881,671,501,353,172,962,592,161,724,884,373,783,052,40

1,241,161,040,940,872,241,881,671,501,353,172,962,592,161,724,884,373,783,052,40

214199179161150385324287257231545510446371296840752650525412

5,75,04,13,43,06,34,63,73,12,56,15,44,23,02,06,15,03,82,61,7

CRSO

13CRSO

23CRSO

33CRSO

43

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)Qv

m3/hSpeedMod.

Cooling emission of 3 row coil

Entering air temperature: 25°C – R. H.: 50% – Available pressure: 0 Pa

WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C

PcPsPcPs

48%

R.H. WT:

46%

Legend

WT = Water temperature

Pc = Cooling total emission

Ps = Cooling sensible emission

Qw = Water flow

Dp(c) = Water pressure drop

Speed = Fan speed

MAX = High speed

MED = Medium speed

MIN = Low speed

Qv = Air flow

Correction factors for different R.H.

0,951,000,901,00

0,941,000,881,00

7/12°C 8/13°C1,001,001,001,00

1,001,001,001,00

10/15°C 12/17°C

Page 10: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

10

CRSO version Carisma

54321543215432154321

54321543215432154321

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

595540470410375104087076566558014151320115095074522201980170513601000

595540470410375104087076566558014151320115095074522201980170513601000

3,783,533,192,882,696,275,545,064,574,128,007,646,966,095,1013,0612,0810,899,257,32

2,632,442,181,951,814,393,823,453,092,775,695,404,864,193,459,278,497,566,324,90

6516075494964631078953870786709137613141197104787622462078187315921259

21,919,316,113,411,858,346,739,733,027,424,422,419,014,910,841,436,029,922,314,6

3,393,172,872,602,435,645,004,574,133,737,156,836,225,464,5811,6710,809,758,306,60

2,492,302,051,841,704,143,603,252,912,605,405,124,593,953,248,808,047,145,944,60

583544493446418970861787711642

123011741070938789

20071858167714281136

17,815,813,211,09,8

48,038,732,927,422,819,818,315,412,28,9

33,729,324,418,212,1

2,612,432,201,991,864,373,863,523,182,885,515,264,784,193,509,018,327,496,375,05

2,232,051,831,621,503,753,242,902,582,304,924,654,153,542,887,977,256,405,284,05

448418378342320751664606548495948905822720603

1549143112891095869

11,09,78,16,86,0

30,024,020,417,014,212,311,39,57,55,4

20,918,115,011,27,4

1,921,791,611,451,353,252,852,592,332,104,113,913,543,072,566,706,175,534,663,67

1,921,791,611,441,333,252,852,592,302,044,113,913,543,072,566,706,175,534,663,57

331308277250233559491446402362707673609529440

1152

1061950801631

6,35,64,63,83,417,513,811,69,68,07,26,65,54,33,112,210,58,66,34,1

3,373,152,852,582,415,624,984,544,103,717,126,806,195,434,5611,6110,749,708,266,56

2,492,302,061,841,714,153,613,262,912,615,415,134,603,963,258,818,057,155,964,62

58054149044441596685678170663712241169106593478419961848166814201128

17,815,713,111,09,747,938,532,727,222,619,818,215,412,18,933,529,124,218,112,0

2,982,782,522,282,134,974,404,023,643,296,296,005,464,794,0210,279,508,577,295,79

2,362,181,941,731,613,943,413,082,742,455,154,884,373,743,068,387,646,765,614,33

512479433392367856757692626566

10811032940824691

1767163514731253996

14,212,510,58,77,7

38,330,726,121,818,215,714,512,29,67,0

26,823,319,314,49,5

2,252,101,901,711,603,793,343,042,742,484,794,564,143,613,027,817,216,485,484,34

2,111,941,721,531,413,573,072,752,442,174,704,433,943,352,727,586,886,064,983,81

388361326294275652575523472426824785712621519

134312401114943746

8,57,56,25,24,6

23,318,515,713,010,89,58,87,45,74,2

16,214,011,68,65,6

1,641,521,361,231,142,782,432,201,971,773,523,353,022,612,165,735,264,703,943,09

1,641,521,361,231,142,782,432,201,971,773,523,353,022,612,165,735,264,703,943,09

281261235211196478418379340305606576520449372986905808678531

4,74,13,42,82,513,210,48,77,15,95,45,04,13,22,39,27,96,44,73,0

CRSO

14

CRSO

14

CRSO

24

CRSO

24

CRSO

34

CRSO

34

CRSO

44

CRSO

44

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

Qv

Qv

m3/h

m3/h

Speed

Speed

Mod.

Mod.

Cooling emission of 4 row coil

Cooling emission of 4 row coil

Entering air temperature: 27°C – R. H.: 50% – Available pressure: 0 Pa

Entering air temperature: 26°C – R. H.: 50% – Available pressure: 0 Pa

WT: 7/12 °C

WT: 7/12 °C

WT: 8/13 °C

WT: 8/13 °C

WT: 10/15 °C

WT: 10/15 °C

WT: 12/17 °C

WT: 12/17 °C

PcPsPcPs

48%

R.H. WT:

46%

Correction factors for different R.H.

0,951,000,901,00

0,941,000,881,00

7/12°C 8/13°C1,001,001,001,00

1,001,001,001,00

10/15°C 12/17°C

Legend

WT = Water temperature

Pc = Cooling total emission

Ps = Cooling sensible emission

Qw = Water flow

Dp(c) = Water pressure drop

Speed = Fan speed

MAX = High speed

MED = Medium speed

MIN = Low speed

Qv = Air flow

Page 11: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

11

CRSO version Carisma

54321543215432154321

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

595540470410375104087076566558014151320115095074522201980170513601000

2,972,772,512,272,124,964,394,013,623,286,275,985,454,774,0010,239,478,537,265,77

2,362,181,941,731,613,943,423,082,752,455,164,884,373,753,078,377,646,775,624,34

510477432390365853754690623563107810289378206881759162914671248992

14,112,510,48,77,738,230,726,121,818,115,714,412,29,67,026,723,219,214,49,5

2,602,432,191,981,854,363,853,513,172,875,505,254,774,173,498,998,307,486,355,04

2,232,061,831,631,513,753,242,912,592,314,914,644,153,542,897,967,246,405,294,07

447418377341319749662604546493946903821717601

1546142812861092866

11,19,88,26,86,0

30,124,120,517,114,212,411,49,67,55,5

21,018,315,111,37,4

1,941,801,621,461,363,272,872,612,352,124,143,943,573,102,586,756,215,574,703,70

1,941,801,621,441,333,272,872,602,302,044,143,943,573,102,566,756,215,574,693,57

333310279252235563494450405364713678613533443

11611068957808636

6,55,74,73,93,4

17,914,111,99,98,27,46,75,64,43,1

12,410,78,86,54,2

1,381,281,141,020,952,352,051,851,651,483,152,942,582,201,815,074,543,953,302,56

1,381,281,141,020,952,352,051,851,651,483,152,942,582,201,815,074,543,953,302,56

237220196176163405352318284254541506444378311872781680568440

3,53,02,52,01,89,87,66,35,24,24,43,93,12,31,67,46,04,73,42,2

CRSO

14CRSO

24CRSO

34CRSO

44

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)

kW kW l/h kPa

Pc Ps Qw Dp(c)Qv

m3/hSpeedMod.

Cooling emission of 4 row coil

Entering air temperature: 25°C – R. H.: 50% – Available pressure: 0 Pa

WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C

PcPsPcPs

48%

R.H. WT:

46%

Correction factors for different R.H.

0,951,000,901,00

0,941,000,881,00

7/12°C 8/13°C1,001,001,001,00

1,001,001,001,00

10/15°C 12/17°C

Legend

WT = Water temperature

Pc = Cooling total emission

Ps = Cooling sensible emission

Qw = Water flow

Dp(c) = Water pressure drop

Speed = Fan speed

MAX = High speed

MED = Medium speed

MIN = Low speed

Qv = Air flow

Page 12: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

12

CRSO version Carisma

595540470410375104087076566558014151320115095074522201980170513601000

595540470410375104087076566558014151320115095074522201980170513601000

6,896,375,695,094,7111,439,958,998,017,1615,7414,9013,3611,479,3624,7022,6120,0916,6912,90

59354848943740598385677368961513541281114998780521241945172714351109

27,523,919,515,913,926,420,617,113,911,424,121,817,913,69,424,921,317,212,37,7

5,284,894,373,913,628,767,636,896,155,5012,0411,4010,238,787,1918,9117,3115,3512,789,90

45442137633631275465659252847310359808807556181626148913201099851

17,615,312,510,28,9

16,913,211,08,97,3

15,413,911,58,76,1

16,013,611,07,95,0

4,484,143,713,323,087,426,465,835,214,66

10,179,648,667,446,09

16,0114,6513,0210,848,38

386356319285264638555502448401875829745640524

137712591120932721

13,311,69,57,86,8

12,89,98,36,85,5

11,610,58,76,64,6

12,010,28,36,03,8

3,683,403,042,722,536,085,294,794,283,838,327,897,096,105,00

13,0911,9910,688,896,89

316293262234217523455412368329715678609524430

11261031918765593

9,58,36,85,54,99,17,15,94,83,98,27,46,14,73,38,57,35,94,22,7

4,223,903,493,122,897,006,105,504,914,399,649,128,197,015,74

15,1213,8412,2910,237,90

725671600536497

12051049946845754

1658156914081206986

26012380211317591358

42,036,529,924,421,240,531,526,221,417,436,833,427,420,814,538,232,526,318,911,8

3,423,162,832,532,345,674,944,463,983,567,807,396,625,694,66

–––––

588544487434403976850766685612

134212701139979801–––––

29,325,520,917,014,928,222,018,314,912,225,623,219,114,510,1

–––––

7,757,146,325,605,1712,9711,1610,028,867,8617,1316,2014,4512,289,9526,6624,2421,4317,6713,52

6676145444814441115960861762676147413931243105685622932084184315201163

17,214,811,99,68,346,735,729,323,519,020,818,815,311,47,837,131,325,017,710,9

5,955,484,864,313,989,978,597,716,836,0613,1312,4111,089,437,6420,4018,6116,4313,5710,40

512471418370342857739663587521112910679538116571754160014131167894

11,19,57,76,25,4

30,123,019,015,212,313,312,09,87,35,0

23,720,116,111,47,0

5,064,654,123,653,388,487,306,555,805,16

11,1210,519,387,996,49

17,2915,7613,9411,538,82

435400355314290729628564499443956904806687558

148713551199991759

8,47,25,84,74,1

22,917,514,411,69,4

10,09,17,45,53,8

17,915,212,28,65,3

4,153,823,393,012,786,966,015,394,784,259,118,607,686,555,32

14,1612,9011,419,457,25

357328291259239599517464411365783740660563458

12181110982813623

6,05,24,23,42,9

16,412,610,38,36,77,26,55,33,92,7

12,710,88,66,23,8

4,744,373,873,433,177,946,836,135,424,81

10,509,938,857,526,09

16,3014,8513,1310,828,27

816752665590545

136711761054932827

1807170815231293104728042555225818611422

26,322,718,214,712,771,654,644,936,029,031,928,823,417,511,956,747,938,427,116,7

3,863,543,142,792,576,455,554,984,413,918,508,047,176,094,94

13,2212,0410,638,796,71

663610540479442

1109955857758673

1462138212331048849

22742070182815121154

18,515,912,710,38,950,138,331,525,220,422,220,116,312,28,339,633,426,719,011,7

54321543215432154321

54321543215432154321

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

Qv

Qv

m3/h

m3/h

Speed

Speed

WT: 70/60 °C

WT: 70/60 °C

WT: 60/50 °C

WT: 60/50 °C

WT: 55/45 °C

WT: 55/45 °C

WT: 50/40 °C

WT: 50/40 °C

WT: 50/45 °C

WT: 50/45 °C

WT: 45/40 °C

WT: 45/40 °C

Heating emission of 3 row coil

Heating emission of 4 row coil

Entering air temperature: 20°C – Available pressure: 0 Pa

Entering air temperature: 20°C – Available pressure: 0 Pa

MAX = High speedMED = Medium speedMIN = Low speed

Legend WT = Water temperaturePh = EmissionQw = Water flow

Dp(c) = Water pressure dropQv = Air flowSpeed = Fan speed

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

CRSO

13

CRSO

14

CRSO

23

CRSO

24

CRSO

33

CRSO

34

CRSO

43

CRSO

44

Mod.

Mod.

Page 13: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

13

CRSO version Carisma

MAX = High speedMED = Medium speedMIN = Low speed

Legend WT = Water temperaturePh = EmissionQw = Water flow

Dp(c) = Water pressure dropQv = Air flowSpeed = Fan speed

CRSO

1CRSO

2CRSO

3CRSO

4

Heating emission of 1 row additional coil

Heating emission of 2 row additional coil

Entering air temperature: 20°C – Available pressure: 0 Pa

Entering air temperature: 20°C – Available pressure: 0 Pa

595540470410375104087076566558014151320115095074522201980170513601000

3,773,553,242,962,795,965,324,904,484,097,687,346,725,955,0811,9311,1110,078,737,13

3243052792552405124574213853526606315785124371026956866751613

22,620,317,214,613,113,711,19,68,27,018,216,814,411,58,752,045,838,329,620,6

3,403,202,932,682,525,374,794,414,033,686,926,626,065,374,5910,7810,029,117,886,44

293275252230217462412379347317595570521462394927862783678554

19,117,114,512,411,211,59,48,16,95,8

15,414,212,19,77,3

44,038,632,525,017,4

3,042,852,612,392,254,764,253,923,583,286,165,895,404,794,089,638,958,147,045,76

261245224205194409366337308282530507464412351829770700605495

15,814,112,010,39,29,47,76,75,74,8

12,711,710,08,06,0

36,632,027,020,814,5

2,672,512,292,101,984,173,733,433,142,875,405,184,744,193,598,477,887,166,215,08

230216197180170359320295270247465445407361308729678616534437

12,811,49,78,37,47,56,25,34,53,9

10,29,48,06,44,9

29,525,921,816,811,7

2,302,161,981,811,713,573,192,942,692,474,644,454,083,623,097,316,816,195,364,38

197186170156147307274253232212399383351311266629586532461377

9,98,97,66,45,85,84,74,13,53,07,97,36,25,03,8

23,020,217,013,19,2

1,931,821,661,521,432,972,662,462,252,063,893,733,413,032,596,175,735,214,513,70

166156143131123256229211193177335321294261223531493448388318

7,46,65,64,84,34,33,53,02,62,25,85,4

4,63,72,817,315,112,79,86,9

54321543215432154321

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

PhQv

m3/hSpeedMod.

WT: 80/70 °C WT: 75/65 °C WT: 70/60 °C WT: 65/55 °C WT: 60/50 °C WT: 55/45 °C

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

CRSO

1CRSO

2CRSO

3

5955404704103751040870765665580141513201150950745

4,594,293,883,513,297,606,736,155,565,0410,269,798,927,796,52

394369334302283654579529478433882842767670561

6,05,34,53,73,320,216,213,811,59,646,242,435,928,120,4

3,963,703,353,042,846,585,825,324,824,358,908,497,736,765,66

341318288261244566501458414375765730665581487

4,74,23,52,92,6

15,812,710,89,07,5

36,433,428,222,216,1

3,333,112,822,552,395,554,924,504,063,687,527,196,545,724,79

286268242219206478423387349317647618562492412

3,53,12,62,21,9

11,99,58,16,85,7

27,425,221,316,712,2

2,692,522,292,071,944,534,013,673,323,006,165,875,344,683,92

232217197178167389345315285258530505460402337

2,42,21,81,51,48,46,75,74,84,0

19,417,915,111,88,6

2,572,412,171,971,854,273,783,453,122,835,775,505,004,383,67

442414374339317734651594537486992946860753631

7,97,05,84,94,3

26,421,318,115,112,660,855,847,037,026,9

2,061,931,751,591,493,493,102,842,572,334,774,564,153,633,06

178166151137128300266244221200410392357312263

1,51,41,11,00,95,34,33,73,12,612,511,59,77,75,6

543215432154321

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

Ph

kPa

Dp(c)

l/h

Qw

kW

PhQv

m3/hSpeedMod.

WT: 65/55 °C WT: 60/50 °C WT: 55/45 °C WT: 50/40 °C WT: 45/40 °C WT: 45/35 °C

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

Page 14: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

14

CRSO version Carisma

7665544641140120107958817416414412297256237219191164

7563534540137117104928517116114111894248224208182156

7362514439133114101898316715713711491238212197174151

7160494238

129110978680

16215213311088

227201187165143

7058484136

124105938276

15614612810684

216190177157136

6856463935

119101907973

15014012210181

204179168148127

6554443833

11497867569

1431331159677

193170158139122

63524236–

10992817065

1351251089173

183161148130115

605040––

1038676––

1271191018568

173151139123108

595540470410375104087076566558014151320115095074522201980170513601000

5655074373783409958257106105351375128011159056852130190016501330985

5304754033443029507806655604951325123010708606402030182015851300975

495435365305260900730620515455

127011701020810600

1930174015201260955

455395327265220845680572470410

12001105960760550

1825165014501215935

410348285225178782630530430370

11201030890700505

1720155013801160900

355300237180137720575480380320

1040950810640460

1600145012951090870

297245187135–

650515430330270945860730570400

1495134012001000820

230185130

––

575450360––

845780650500340

137512201100910750

0 10 20 30 40 50 60 70 80

0 10 20 30 40 50 60 70 80

54321543215432154321

54321543215432154321

Speed

Speed

Available pressure (Pa)

Available pressure (Pa)

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

CRSO

1CRSO

2CRSO

3CRSO

4

CRSO

1CRSO

2CRSO

3CRSO

4

Mod.

Mod.

Air flow (m3/h)depending on speed and requested available pressure

Power absorption (Watt)depending on air flow and available pressure

Page 15: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

15

CRSO version Carisma

1,001,001,001,001,001,001,001,001,001,001,001,001,001,001,001,001,001,001,001,00

0,970,970,960,960,950,980,970,960,960,960,980,980,980,970,960,980,980,980,990,99

0,940,930,920,910,890,950,940,930,910,920,970,960,960,950,920,950,960,960,980,99

0,910,890,870,850,810,930,910,890,870,880,940,940,940,920,890,930,930,940,960,98

0,860,840,820,780,730,890,870,850,820,820,920,910,910,890,850,900,910,920,940,96

0,810,780,750,700,640,850,840,810,780,770,880,870,870,840,800,870,880,890,920,95

0,740,710,660,610,540,810,790,760,720,700,840,830,820,800,760,830,840,860,890,93

0,660,620,570,50

–0,760,740,710,660,630,800,780,770,740,690,800,800,820,840,90

0,560,510,45

––

0,700,670,63

––

0,740,740,720,680,620,760,760,780,800,85

1,001,001,001,001,001,001,001,001,001,001,001,001,001,001,001,001,001,001,001,00

0,960,960,950,940,930,970,960,950,940,940,980,980,980,970,940,970,970,980,980,99

0,920,910,900,880,860,940,930,910,890,890,950,950,950,930,900,940,940,950,970,98

0,880,860,830,810,770,900,880,860,830,840,930,920,920,890,860,910,910,920,950,97

0,830,800,770,730,680,860,840,810,780,780,890,880,880,850,800,870,880,890,920,95

0,760,730,690,640,570,820,790,770,730,720,850,840,830,800,750,830,840,860,890,93

0,680,650,600,540,470,770,740,710,660,640,800,790,780,750,700,790,800,820,850,91

0,600,550,500,43

–0,710,680,650,590,570,750,730,720,690,630,750,750,780,800,87

0,490,450,38

––

0,650,610,57

––

0,690,680,660,620,560,700,700,730,750,81

0 10 20 30 40 50 60 70 80

0 10 20 30 40 50 60 70 80

54321543215432154321

54321543215432154321

Speed

Speed

Available pressure (Pa)

Available pressure (Pa)

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

MAXMEDMIN

CRSO

1CRSO

2CRSO

3CRSO

4

CRSO

1CRSO

2CRSO

3CRSO

4

Mod.

Mod.

Correction factors for Total cooling emission

Correction factorsfor Sensible cooling emission and Heating emission

Page 16: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

16

CRSO version Carisma

230/150Hz

W

A

CRSO 1 CRSO 2 CRSO 3 CRSO 4Model

100

750

CRSO 13150

1000

CRSO 23200

2000

CRSO 33300

3000

CRSO 43Lowest

Highest

Model

150

1000

CRSO 14150

1500

CRSO 24300

2250

CRSO 34400

3300

CRSO 44Lowest

Highest

Model

50

350

CRSO 1100

500

CRSO 2100

750

CRSO 3100

750

CRSO 4Lowest

Highest

Model

100

350

CRSO 1100

500

CRSO 2100

750

CRSO 3–

CRSO 4Lowest

Highest

Model

Operation limits

Highest water inlet temperature............................... + 85 °C

Lowest water inlet temperature................................ + 5 °C

for entering water temperatures below + 5°C, contact “SABIANA” technical department

Highest working pressure........................................ 1000 kPa (10 bars)

Motor electrical data (max. absorption)

76

0,33

140

0,64

174

0,81

256

1,22

Water flow limits for 3 row coil (l/h)

Water flow limits for 4 row coil (l/h)

Water flow limits for 1 row additional coil (l/h)

Water flow limits for 2 row additional coil (l/h)

Page 17: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

17

CRSO version Carisma

3-4

100 800600400300200 1000806050

1

40

30

20

9876

5

60

4

3

2

10

50

2

1

3

100 800600400300200 1000806050

1

40

30

20

9876

5

60

4

3

2

10

50

2

3

4

1

1

40

30

20

98

7

6

5

50

4

3

2

10

100 800600400300200 1500 20001000

14

34

2444

100 800600400300200 1500 200010001

40

30

20

98

7

6

5

50

4

3

2

10

33

43

23

13

Dp - kPa Dp - kPa

Dp - kPa Dp - kPa

Waterflow (l/h)

Waterflow (l/h)

Waterflow (l/h)

Waterflow (l/h)

K 0,94 0,90 0,86 0,82 0,78 0,74 0,70

20 30 40 50 60 70 80°C

K 1,14 1,08 1,02 0,96 0,90

°C 40 50 60 70 80

The water pressure drop figuresrefer to a mean water temperature of 10°C;for different temperatures, multiplythe pressure drop figures by the correction factors K.

The water pressure drop figuresrefer to a mean water temperature of 65°C;for different temperatures, multiplythe pressure drop figures by the correction factors K.

3 row coil 4 row coil

1 row additional coil 2 row additional coil

Water pressure drop

Page 18: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

18

Carisma

40

30

20

1098765

4

3

2

1100 200 300 400 600 800 1000 2000 3000 4000

Kvs 2

Kvs 2,5

Kvs 1,6

Kvs 3,5

Kvs 4Dp - kPa

Waterflow (l/h)

Accessories for CRSO version

Control valve kit:3 way valve, ON-OFF,with electric motor and mounting kitwith micrometric lockshield valve.

VBPmain coil 3 way valve

Control valve kit:3 way valve, ON-OFF,with electric motor and mounting kitwith micrometric lockshield valve.

VBAadditional coil 3 way valve

9060472H

9060472H

9060472H

9060475H

9060475H

9060475H

15

15

15

1/2” F

1/2” F

1/2” F

2

2

2

15

15

15

1/2”

1/2”

1/2”

1,6

1,6

1,6

120

135

135

195

200

200

240

235

235

340

330

330

1 – 234

Mod.CodeMicrometric lockshield valveDimensions (mm) Valve

FITTED NOT FITTEDDN (Ø) KvsA B C D DN (Ø) Kvs

9066561H

9060471H

9060471H

9069202H

9066560H

9060474H

9060474H

9069200H

15

15

15

20

1/2” F

1/2” F

1/2” F

3/4” F

2

2

2

3,5

15

20

20

20

1/2”

3/4”

3/4”

3/4”

1,6

2,5

2,5

4

25

25

50

50

85

85

120

120

190

190

185

185

290

290

290

290

105

105

105

105

1234

Mod.CodeMicrometric lockshield valveDimensions (mm) Valve

FITTED NOT FITTEDDN (Ø) KvsA B C D E DN (Ø) Kvs

Dimensions ± 10 mm

Dimensions ± 10 mm

Page 19: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

19

Carisma

40

30

20

1098765

4

3

2

1100 200 300 400 600 800 1000 2000 3000 4000

Kvs 1,7 Kvs 2,8

Kvs 2,5

Kvs 1,6 Kvs 4Dp - kPa

Waterflow (l/h)

Accessories for CRSO version

3 way valve, (ON-OFF)with electric motor and mounting kit.Valve with flat connectionwithout micrometric lockshield valve.

VSsimplified kit for 3 way valve

Dimensions ± 10 mm

Control valve kit:2 way valve, ON-OFF,with electric motor and mounting kit.

V22 way valvefor main and additional coil

Dimensions ± 10 mm

9060476H 9060478H15 1/2” 1,7

Dimensions (mm)

H

Main additional

149

150

176

176

180

181

175

175

438

438

422

422

186

186

210

210

456

456

440

440

A C D E

CodeValve

FITTED NOT FITTEDDN (Ø) Kvs

Code

9060476H

9060477H

9060477H

9069203H

9060478H

9060479H

9060479H

9069201H

15

20

20

25

1/2”

3/4”

3/4”

1”

1,7

2,8

2,8

4

Valve

FITTED NOT FITTEDDN (Ø) Kvs

Main additional

1234

Mod.

9060483H 9060480H15 1/2” 1,6

CodeValve

FITTED NOT FITTEDDN (Ø) Kvs

Code

9066571H

9060484H

9060484H

9069205H

9066570H

9060481H

9060481H

9069204H

15

20

20

20

1/2”

3/4”

3/4”

3/4”

1,6

2,5

2,5

4

Valve

FITTED NOT FITTEDDN (Ø) Kvs

Dimensions (mm) Main additional

CMain additional

152

152

177

177

270

268

270

270

185

185

210

210

330

330

327

329

116

124

124

124

A1 A2 B1 B2

1234

Mod.

Page 20: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

20

CarismaAccessories for CRSO version

1 PHASE 230VElectric heater with integral:safety thermostat and relay control.

BEL electric heater

CRSo 43500

9038026

CRSo 32500

9066617

1500

9066607

1000

9066597

2000

9066615

1250

9066605

750

9066595

CRSo 21500

9066613

900

9066603

600

9066593

CRSo 1Size

Watt

Code

BSV extension condensate collection tray to cover valve assembly(for vertical units)

Code 6060400

BSO extension condensate collection tray to cover valve assembly(for horizontal units)

6060402

LEFT

BSO-SX

6060403

RIGHT

BSO-DX

Code

ConneCtion Side

type

190

100

DRPV-C condensate pump(for vertical units)

1234

HeigHt

foR veRtiCal floW (m) 5 m 10 m

WateR floW (l/h) depending on tHe lengtH of HoRizontal floW

7,6

5,6

4,0

3,2

7,2

5,2

3,7

2,9

fitted not fitted

DRPV-C-M DRPV-C-S

9066297 9066296

type

Code

Page 21: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

21

CarismaAccessories for CRSO version

SCR plastic condensate drain pipe with fast connection(allows correct condensate drain)

Code 6060420

FRD straight inlet flange

Can be used together with GRAG air inlet grid.Made of galvanized steel.

BA C D G

9060721

9038002

9060724

9038007

Code

FRD - 3/4

FRD - 4S

FRD - 8/9

FRD - 8S

type

590

790

990

1440

669

884

1099

1549

39,5

47

54,5

54,5

216

246

246

246

16

46

46

46

CRSo 1CRSo 2CRSo 3CRSo 4

Size

9069071

9069072

9069073

9069074

Code

CRSo 1CRSo 2CRSo 3CRSo 4

Size

KAF frontal intake kit

Bottom closing panel and filter sliding guides.

DRPO-C fitted condensate pump(for horizontal units)

1234

HeigHt

foR veRtiCal floW (m) 5 m 10 m

WateR floW (l/h) depending on tHe lengtH of HoRizontal floW

7,6

5,6

4,0

3,2

7,2

5,2

3,7

2,9

DRPO-C

9066295

type

Code

Page 22: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

22

CarismaAccessories for CRSO version

Made of galvanized steel.

FMD straight outlet flange

E

-

-

-

248

9066373

9069232

9066378

9069234

CodeBA C D

FMD - 3/4

FMD - 4S

FMD - 8/9

FMD - 8S

type

590

790

990

1440

667

882

1097

1547

38,5

46

53,5

53,5

152

179

179

152

CRSo 1CRSo 2CRSo 3CRSo 4

Size

To be used with FRD straight inlet flange.Made of anodized aluminium.

GRAG air inlet grid

GRAP air inlet grid

To be used with FR 90 90° inlet flange.Made of anodized aluminium.

FR 90 90° inlet flange

Can be used together with GRAP air inlet grid.Made of galvanized steel.

BA C D G

9060711

9038001

9060714

9038006

Code

FR90 - 3/4

FR90 - 4S

FR90 - 8/9

FR90 - 8S

type

590

790

990

1440

669

884

1099

1549

39,5

47

54,5

54,5

216

246

246

246

11

41

41

41

CRSo 1CRSo 2CRSo 3CRSo 4

Size

deSCRiption B

9060761

9060762

9060763

9038041

Code

GRAP - 3/4

GRAP - 5/6

GRAP - 7/9

GRAP - S4

type

Grid 600x150

Grid 800x150

Grid 1000x150

Grid 1450x150

575

775

975

1425

CRSo 1CRSo 2CRSo 3CRSo 4

Size

deSCRiption B

9060765

9060766

9060767

9038042

Code

GRAG - 3/4

GRAG - 5/6

GRAG - 7/9

GRAG - S4

type

Grid 600x200

Grid 800x200

Grid 1000x200

Grid 1450x200

575

775

975

1425

CRSo 1CRSo 2CRSo 3CRSo 4

Size

Page 23: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

23

CarismaAccessories for CRSO version

D

313

270

347,5

360

9066463

9038050

9066468

9038051

Code

N° 2

N° 3

N° 3

N° 4

SpigotS

CRSo 1CRSo 2CRSo 3CRSo 4

Size BA C

PRC - 3/4

PRC - 4S

PRC - 8/9

PRC - 8S

type

166

160

190

223

645

860

1075

1525

218

248

248

248

Made of galvanized steelinsulated with polyethylene lining.

All the plenums are suppliedwith spigots for the connection of flexible ducts.

PRC air inlet spigot plenum

Double louvre grid to be fitted to the duct,to the FMD straight outlet flangeor to the FM 90 90° outlet flange.Made of anodized aluminium.

BMA air outlet grid

B

9060751

9060752

9060753

9038040

Code

BMA - 3/4

BMA - 5/6

BMA - 7/9

BMA - 8S

type

575

775

975

1425

CRSo 1CRSo 2CRSo 3CRSo 4

Size

Made of galvanized steelinsulated with polyethylene lining.

All the plenums are suppliedwith spigots for the connection of flexible ducts.

PMC spigot diffuser

D

313

270

347,5

360

9066363

9069222

9066368

9069224

Code

N° 2

N° 3

N° 3

N° 4

SpigotS

CRSo 1CRSo 2CRSo 3CRSo 4

Size BA C

PMC - 3/4

PMC - 4S

PMC - 8/9

PMC - 8S

type

166

160

190

223

645

860

1075

1525

218

248

248

248

Made of galvanized steelinsulated with polyethylene lining.

FM 90 90° outlet flange

E

-

-

-

248

BA C D

9066383

9069242

9066388

9069244

Code

FM90 - 3/4

FM90 - 4S

FM90 - 8/9

FM90 - 8S

type

590

790

990

1440

667

882

1097

1547

38,5

46

53,5

53,5

152

179

179

152

CRSo 1CRSo 2CRSo 3CRSo 4

Size

Page 24: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

24

Carisma

ON

-OF

F s

witc

h

ON

-OF

F s

witc

h fo

r el

ectr

ic h

eate

r

Man

ual 3

spe

ed s

witc

h

Man

ual/A

utom

atic

3 s

peed

sel

ectio

n

Sum

mer

/Win

ter

switc

h

Rem

ote

cent

raliz

ed S

umm

er/W

inte

r sw

itch

or b

y an

aut

omat

ic c

hang

e-ov

erfit

ted

on t

he w

ater

pip

e

Aut

omat

ic S

umm

er/W

inte

r sw

itch

with

neu

tral

zon

e fo

r 4

pipe

inst

alla

tion

with

2 v

alve

s

Roo

m t

herm

osta

t fo

r fa

n co

ntro

l (O

N-O

FF

)

Roo

m t

herm

osta

t fo

r 1

valv

e co

ntro

l (2

pipe

inst

alla

tion)

Roo

m t

herm

osta

t fo

r 2

valv

e co

ntro

l (4

pipe

inst

alla

tion)

Sim

ulta

neou

s th

erm

osta

tic c

ontr

ol o

f th

e va

lves

and

fan

Roo

m t

herm

osta

t fo

r ch

illed

wat

er v

alve

(S

UM

ME

R)

and

elec

tric

hea

ter

(WIN

TE

R)

cont

rol

(in w

inte

r on

ly t

he h

eate

r is

wor

king

)

Roo

m t

herm

osta

t fo

r fa

n an

d el

ectr

ic h

eate

r co

ntro

l

Inst

alla

tion

of e

lect

roni

c lo

w t

empe

ratu

re C

UT

-OU

T t

herm

osta

t (T

ME

)

Inst

alla

tion

of b

imet

allic

low

tem

pera

ture

CU

T-O

UT

the

rmos

tat

(TM

M)

9063023

9063021

9060174

9060165

9060173

9060164

9060161

9066330

9060160

TMO-T-AU-IAQ

TMO-T-IAQ

T2T

TMO-DI

TMO-503-SV2

TMO-T-AU

TMO-T

CR-T

MO-3V

Co

ntR

ol

ope

Ra

tio

nS

Co

ntR

ol

iden

tifi

Ca

tio

n

Co

nt

Ro

l C

od

eS

Electrical diagrams are shown on the installation, use and maintenance manual

Control functions

Electronic controls

The CRSO units can be controlled using the remote controls above;in the standard version, the motor speeds connected to the main terminal block, are:

- for sizes 1, 2 and 3 motor speeds 2, 3 and 4 are connected while the wires for speeds 1 and 5 are connected to a two-pole support terminal block.

- for size 4 motor speeds 1, 2 and 3 are connected while the wires for speeds 4 and 5 are connected to a two-pole support terminal block.

Page 25: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

25

CarismaWall electronic controls

• ON-OFF switch and 3 speed switch.• Without thermostatic control.• It allows to control the low temperature cut-out thermostat (TMM).

identifiCation Code

MO-3V 9060160

Dimensions: 133x93x37 mm

• ON-OFF switch.• Manual or automatic 3 speed switch.• Summer/Winter switch.• Electronic room thermostat for fan or valve control (ON-OFF).• Simultaneus thermostatic control of the valves and fan.• It allows to control the low temperature cut-out thermostat (TME).• It allows to control the chilled water valve (ON-OFF) and the electric heater (BEL) only in case that hot water is not used in winter (otherwise please use TMO-T-AU-IAQ control with on/off switch for the electric heater).• It allows to control the summer/winter cycle with a centralized and remote switch or with an automatic change-over fitted on the water pipe (for 2-tube installations only).

N.B.: with 4 pipe installations and continuous chilled and hot water supply, it allows the automatic summer winter change-over in accordance to the room temperature (-1°C = Winter, +1°C = Summer, Neutral Zone 2°C).

identifiCation Code

TMO-T-AU 9060164

Dimensions: 133x93x37 mm

• ON-OFF switch.• Manual 3 speed switch.• Summer/Winter switch.• Electronic room thermostat for fan or valve control (ON-OFF).• It allows to control the low temperature cut-out thermostat (TME).• It allows to control the chilled water valve (ON-OFF) and the electric heater (BEL) only in case that hot water is not used in winter (otherwise please use TMO-T-IAQ control with on/off switch for the electric heater).• It allows to control the summer/winter cycle with a centralized and remote switch or with an automatic change-over fitted on the water pipe (for 2-tube installations only).

identifiCation Code

TMO-T 9060161

Dimensions: 133x93x37 mm

• ON-OFF switch.• Manual 3 speed switch.• Manual Summer/Winter switch.• Electronic room thermostat for fan or valve control (ON-OFF).• It allows to control the low temperature cut-out thermostat (TMM).• It allows to control the chilled water valve (ON-OFF) and the electric heater (BEL) only in case that hot water is not used in winter (otherwise please use TMO-T-IAQ control with on/off switch for the electric heater).

identifiCation Code

CR-T 9066330

Dimensions: 133x93x37 mm

Page 26: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

26

CarismaWall electronic controls

2 pipes units only.

• ON-OFF switch.• 3 speed switch.• Manual Summer/Winter switch.• Thermostatic control on the fan.• Thermostatic control on the valve and continuous fan operation.• Simultaneous thermostatic control of the valve and fan.• Cannot be used with speed switch (master-slave).

identifiCation Code

T2T 9060174

Dimensions: 128x75x25 mm

To be installed on the wall or in the DIN 503 box.• Manual or automatic speed switch.• Manual or centralized Summer/Winter switch.• Electronic thermostat for fan control (ON-OFF).• Electronic thermostat for valve control (ON-OFF).• Simultaneus thermostatic control of the valves and fan.• It allows to control the low temperature cut-out thermostat (TME).• It allows to control the chilled water valve (ON-OFF) and the electric heater (BEL) only in case that hot water is not used in winter.• It allows to control the fan and the electric heater.• It allows to control up to 10 units with SEL-DI speed switch.

N.B.: with 4 pipe installations and continuous chilled and hot water supply, it allows the automatic summer/ winter change-over in accordance to the room temperature (-1°C = Winter, +1°C = Summer, Neutral Zone 2°C).

identifiCation Code

TMO-DI 9060165

Dimensions on the wall: 133x93x27 mmDimensions in the DIN 503 box: 133x93x18 mm

The TMO-503-SV2 control for fan coils with valves, is designed to be installed in a DIN 503 wall box.It is easy to use, it has a big and clear display, and a great precision.The control is supplied integral with the external frame, but it is possible to use frames of the mostknown brand on the market (BTicino, Vimar, AVE, Gewiss).The highest working electric absorbtion is 200 W.If the fan coil has an higher absorbtion or more units are connected to the same control, the speedswitch SEL-CR must be installed (on size 4 the SEL-CR switch must be installed).

• Manual or automatic speed switch.• Manual Summer/Winter switch.• Electronic thermostat for valves control (ON-OFF).• Simultaneus thermostatic control of the valves and fan.• It allows to control the low temperature cut-out thermostat, included with the control.

N.B.: with 4 pipe installations and continuous chilled and hot water supply, it allows the automatic summer/ winter change-over in accordance to the room temperature (-1°C = Winter, +1°C = Summer, Neutral Zone 2°C).

identifiCation Code

TMO-503-SV2 9060173

Dimensions: 118x87x8 mm

Page 27: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

27

CarismaWall electronic controlsfor units with electric heater

To be installed on the wall or in the DIN 503 box.• Manual or automatic speed switch.• Manual or centralized Summer/Winter switch.• Electronic thermostat for fan control (ON-OFF).• Electronic thermostat for valve control (ON-OFF).• Simultaneus thermostatic control of the valves and fan.• It allows to control the low temperature cut-out thermostat (TME).• It allows to control the chilled water valve (ON-OFF) and the electric heater (BEL) only in case that hot water is not used in winter.• It allows to control the fan and the electric heater.• It allows to control up to 10 units with SEL-DI speed switch.

N.B.: with 4 pipe installations and continuous chilled and hot water supply, it allows the automatic summer/ winter change-over in accordance to the room temperature (-1°C = Winter, +1°C = Summer, Neutral Zone 2°C).

identifiCation Code

TMO-DI 9060165

• ON-OFF switch.• Manual or automatic 3 speed switch.• Summer/Winter switch.• Electric heater ON-OFF switch.• Electronic room thermostat for fan or valve control (ON-OFF).• Simultaneus thermostatic control on the valves and fan.• It allows to control the low temperature cut-out thermostat (TME).• It allows to control the chilled water valve (ON-OFF) and the electric heater (BEL) only in case that hot water is not used in winter.• It allows to control the summer/winter cycle with a centralized and remote switch or with an automatic change-over fitted on the water pipe (for 2-tube installations only).

N.B.: with 4 pipe installations and continuous chilled and hot water supply, it allows the automatic summer/ winter change-over in accordance to the room temperature (-1°C = Winter, +1°C = Summer, Neutral Zone 2°C).

identifiCation Code

TMO-T-AU-IAQ 9063023

• ON-OFF switch.• Manual 3 speed switch.• Summer/Winter switch.• Electric heater ON-OFF switch.• Electronic room thermostat for fan or valve control (ON-OFF).• It allows to control the low temperature cut-out thermostat (TME).• It allows to control the chilled water valve (ON-OFF) and the electric heater (BEL) only in case that hot water is not used in winter.• It allows to control the summer/winter cycle with a centralized and remote switch or with an automatic change-over fitted on the water pipe (for 2-tube installations only).

identifiCation Code

TMO-T-IAQ 9063021

Dimensions: 133x93x37 mm

Dimensions: 133x93x37 mm

Dimensions on the wall: 133x93x27 mmDimensions in the DIN 503 box: 133x93x18 mm

Page 28: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

28

Carisma

2 63 41 5

7 1198 1210

• Speed switch (Slave).• It allows to control up to 8 units with only one centralized wall control (1 speed switch for each unit).• For controls CR-T, TMO-T, TMO-T-AU and TMO-503-SV2.

identifiCation Code

SEL-CR 9066311

Speed switches

• Speed switch (Slave) for TMO-DI• It allows to control up to 10 units with only one TMO-DI centralized wall control.

identifiCation Code

SEL-DI 9060139

Page 29: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

29

Carisma

RED

BROWN

RED

BLACK

To be fitted between the coil fins; when connecting the control,the TME probe cable must be separated from the power supply wires.To be used with the following controls:TMO-T, TMO-T-AU, TMO-DI and corresponding IAQ controls.It stops the fan whenthe water temperature is lower than 38°Cand it starts the fan when is higher than 42°C.

TME low temperature cut-out thermostat

Wall electronic control accessoriesfor CRSO version

To be installed in contact with the hot water circuit.To eliminate cold air blow.Installed by the installing engineer.To be used with the MO-3V and CR-T controls.For units working on heating only.It stops the fan whenthe water temperature is lower than 30°Cand it starts the fan when is higher than 38°C.

TMM low temperature cut-out thermostat

Automatic summer/winter switchto be installed in contact with the water circuit.For 2-tube installations only(not to be used with 2 way valve).To be used with the following controls:TMO-T, TMO-T-AU, TMO-DI.

Change-Over CH 15-25

Code 3021091

Code 9053048

Code 9053049

Page 30: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

30

Carisma

Control unit with support

Power unit

Probe with support

FreeSabiana wireless control system

FreeSabiana

Free Sabiana is an innovative, fully wireless, electronic system for use withfan coil units, based on radio communication.

This technology provides installation flexibility and a more accuratemeasurement of the room temperature. The probe can be moved untilthe most suitable position is found, without the worry of changes in theroom layout and of its furniture and also without mounting it on a wall.If a new fan coil unit is added, no electrical wiring for the control system is

required: just define the control unit and the probe which regulates it. The improved measurement accuracy is aresult of the possibility to position the probe near the user location: this enables to keep the temperature exactlyat the required value with more energy savings compared with a traditional measurement system.

Transmission is based on communication protocol IEE802.15.4, the most suitable way to transmit a relatively lowamount of information with very low consumption and high reliability.

The system has been certified by a leading independent body, officially recognized by the EU authorities and itssale has been authorized in all the EU and EFTA countries.

Main components

Free Sabiana includes 3 main components:

Power unit fitted on the unit

Power unit not fitted on the unit

deSCRiption

Free-Upm 9060571

Free-Ups 9060570

identifiCation Code

Temperature probe

deSCRiption

Free-Sen 9060573

identifiCation Code

Remote control

deSCRiption

Free-Com 9060572

identifiCation Code

A remote control which features a button panel andLCD display and can be wall-mounted or positionedon a dedicated table support.It enables the control of all the operating variables ofthe fan coil units in different configurations. The controlis battery powered.The temperature and the operating speed of the fancoil unit are set with two large buttons featuring userfriendly graphics.

A power unit to be installed on the fan coil (fan coilinterface).It controls the fan and the valves of the fan coil. Thepower unit is connected to the electric supply.The power unit receives the information required tocontrol the fan coil both from the remote control andlocally, such as the temperature of the coil.

A room temperature probe, which can be wall-mounted or positioned on a dedicated table support.It is a battery powered device, able to measure the airtemperature in the spot where it is positioned, generatingtemperature information which is communicated to theother devices.

Page 31: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

31

CarismaFreeSabiana wireless control system

The power unit controlsthe fan and the valves of the fan coil.The power unit receives the informationrequired to control such unitsboth from the remote control and locally.

This device is able to measurethe temperature of the air in the spotwhere it is positioned and to transmit itby means of radio communication tothe other devices in the system.It is battery powered and can befreely positioned in the area

to be air-conditioned.

Main features of the remote control

Main features of the temperature probe

❍ Fan on/off at a set speed❍ Fan speed change (fan on/off)❍ Water valve/s on/off (1 valve for 2 tube system - 2 valves for 4 tube system)

❍ Fan speed change operating the water valve/s❍ Control of the electric heater as main heating unit or as integration to the battery supplied with hot water❍ Control of the operation of the electrostatic filter (in parallel to the fan)

❍ Management of the dead zone function for 4-tube systems❍ Available functional inputs: • Consent for remote on/off • Consent for remote Summer/Winter switch (centralized)

• Consent for the activation of the Energy Saving function with setting change • Minimum probe • Probe for season change

It enables the following main actions:

❍ Measured environment temperature❍ Transmission signal❍ Clock❍ Battery status

Display:

❍ Fan coil on/off switching❍ Fan speed selection (high - medium - low - automatic)❍ Summer/winter operation selection❍ Valve on/off❍ Real time clock setting❍ Temperature setting❍ Daily switch on/off setting (timer function)❍ Enable/disable the timer function❍ Activation of the (optional) electrostatic filter❍ Activation of the (optional) electric heater

The control enables:

On-off statusSummer operationWinter operationAutomatic season changeElectric heaterElectrostatic filterRoom temperature(with decimal accuracy)

Fan operating speedRequired/measured temperatureTimerClockTransmission signalBattery level

Main information displayed:

12 10 11 138

1 2 3 7 4 5 6

9

1

2

3

4

5

6

7

8

9

10

11

12

13

Main features of the power unit to be installed on the fan coil

Page 32: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

32

Carisma

The MB electronic board, to be mounted on the fan coil internal unit, is setto carry out different functions and adjustment modes, in order to meetthe installation requirements. These modes are selected by settingthe configuration dip switches on the board.

• 2/4 pipe system.

• Fan ON/OFF thermostatic control.

• Valve ON/OFF thermostatic control and continuous ventilation.

• Valve and simultaneous ventilation ON/OFF thermostatic control.

• Fan operation control depending on the coil temperature (cut-out T3 probe fitted), which can be activated only in heating mode or heating and cooling mode.

• Automatic switch of the operating mode by means of T2 water probe (optional) applied on the 2 pipe system.

• Seasonal switch by means of remote contact.

• ON/OFF of the fan coil by means of the remote contact (window or clock contact).

• Electric heater control.

By activating the cut-out T3 probe function, the fan is stopped in winter when the coil temperature is lower than 32°Cand started when the temperature reaches 36°C. In summer mode, the fan stops when the temperature inside thecoil exceeds 22°C and starts when it drops below 18°C.

The following connections are located on the power board:

• Receiver for infra-red remote control.

• T-MB wall mounted control.

• RS 485 serial connection to manage several fan coils in Master/Slave configuration or to create a supervisory network.

All the Carisma CRSO units can be supplied with a wide range of controls, which allows managing one single unitor several units by using the Modbus RTU - RS 485 communication protocol. Units can be managed according to theMaster/Slave logic (up to 20 units) or by supervisory components. The system consists in a MB board and a seriesof controls, such as the T-MB wall control, the RT03 infra-red remote control, the PSM-DI multifunction control andthe Sabianet supervisory program.

MB electronic board fitted on the unit

MB electronic board supplied with separate packaging

deSCRiption

MB-M 9066332

MB-S 9066333

identifiCation Code

MB electronic board

Controls and units MB version

Page 33: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

33

Carisma

InstaLLatIon exampLe

wIth Infra-red remote controL

Wall control with display that allows controlling one or more units in Master/Slave mode. The control is equipped with internal sensor to detect the roomtemperature, which can be defined as a priority compared to the return airsensor on the fan coil. The T-MB control features the following functions:

• Switch the appliance ON and OFF.

• Temperature set.

• Modify the set point (when used as a +/- 3° variation of the set point configured from Sabianet supervisory program or PSM-DI).

• Set the fan speed (low, medium, high or autofan).

• Set the operation mode (fan only, cooling, heating; auto for 4 pipe systems with mode selection depending on the air temperature).

• Time setting.

• Weekly ON/OFF program.

• Display and change of the fan coil operation parameters.

The infra-red remote control allows setting by a remote position the fan coil operation parameters.The RT03 infra-red remote control features the following functions:

• Switch the appliance ON and OFF.

• Temperature set.

• Set the fan speed (low, medium, high or autofan).

• Set the operation mode (fan only, cooling, heating; auto for 4 pipe systems with mode selection depending on the air temperature).

• Time setting.

• 24 hours ON/OFF program.

Wall control (to be used with MB board only)

deSCRiption

T-MB 9066331E

identifiCation Code

T-MB wall control

RT03 infra-red remote control

RT03 3021203RT03 infra-red remote control supplied with separate packaging(to be used with MB board only)

RS-RT03 9066337RT03 infra-red remote control with receiver supplied with separate packaging(to be used with MB board only)

RS 9066338Receiver for RT03 infra-red remote control supplied with separate packaging(to be used with MB board only)

deSCRiption identifiCation Code

Controls and units MB version

Page 34: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

34

CarismaA group of Carisma CRSO units with MB electronic board can be connected via a serial link and can consequentlybe managed at the same time by just one T-MB wall control or RT03 infra-red remote control. Using the specialjumper present on the MB board, one unit must be configured as the master, and all the others as slaves. It is clearthat the remote control must be pointed at the receiver on the master unit. To avoid problems, it is recommendedto install and connect the receiver only on the master unit.

One control for each unitOne control for more units (20 units max.)(maxImum totaL Length of the connectIon cabLe = 800 m)

One control for each unit(maxImum Length of the connectIon cabLe = 20 m)

One control for more units (20 units max.)(maxImum totaL Length of the connectIon cabLe = 800 m)

The T2 sensor can be combined with MB boards to be placed on the water supply pipe upstream 3 way valves(not to be used with 2 way valve).

The T2 sensor must be used as described below:

- Change-Over for 2-pipe system for the automatic switch of the operating mode. If water temperature is lower than 20°C, cooling mode is set; on the other hand, if water temperature exceeds 30°C, heating mode is set.

- It can be used on units with electric heater and hot water supply. The T2 priority probe activates the electric heater or water valve, depending on the water temperature detected. If water temperature exceeds 34°C, the water valve ON-OFF control is activated; on the other hand, if water temperature is lower than 30°C, the electric heater is activated.

identifiCation Code

T2 9025310

T2 accessory for units with MB electronic board

With RT03 infra-red remote control

With T-MB wall control

Controls and units MB version

Page 35: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

35

Carisma

Multifunction control panel (to be used with MB board only)

deSCRiption

PSM-DI 3021293

identifiCation Code

PSM-DI multifunction control panel

Controls and units MB version

Another option available for the serial communication betweenthe units is the possibility to connect up to 60 Carisma CRSO units in series and manage them with just one wall mounted PSM-DI controller. The wall mounted controller can be usedto set the operating mode for each individual unit connected,display the operating conditions of each individual unit, andset the ON/OFF time sets for each day of the week (theprogram can be set for all the units and for a maximum oftwo groups of units).If more than 60 units need to be connected, two or morecontrollers must be used. Each unit must have a MB board.The PSM-DI control is used to manage a series of fan coils,up to a maximum of 60 units (the maximum length of the RS 485connection cable must not exceed 800 m), from one single controlpoint.

The PSM-DI control communicates via a serial line with all the units connected, with the possibility of controllingthem all together or individually. In fact, the unique address of each individual fan coil means that all the units canbe called at the same time, or the individual unit called, to perform the following functions:

- display the current operating mode, the fan speed, the set point;

- display the room temperature measured on the individual unit;

- turn all the units ON and OFF at the same time or alternatively each unit individually;

- change the operating mode (fan only, heating, cooling, automatic changeover);

- change the set point;

- modify the values and operation parameters of the fan speed.

Each function can then be sent to all the units connected, or alternatively to each individual unit.

Different set points or operating modes can be set for each individual unit.

The PSM-DI panel can also be used for the time management of the units over the week. Four ON times and fourOFF times can be set on the units for each day of the week. A different Temperature set that will be considered asOperation set for all connected appliances, can be set for each event. If the Temperature set is not entered for theindividual event, it must be set during programming for each individual unit or for the entire network.

Units without receiver or with receiver can be connected within the network: the former can receive instructions onlyfrom the PSM-DI wall mounted panel; while the latter can receive information from both the wall mounted panel(PSM-DI) and infra-red remote control. Use the infra-red remote control to force ON mode of the individual unit,if ON/OFF daily time programming has been set. The unit will regain the settings from the PSM-DI panel duringexecution of successive start-up program.

The PSM-DI panel cannot be usedtogether with the Sabianet management program (see next page).

Note: set the configuration Dip Switches of each fan coil as illustrated in the remote control use manual, based on the required solutions.

Note: the RS 485 network’s overall length must not exceed 700/800 metres.

Page 36: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

36

CarismaManagement systemfor a network of fan coils

Hardware/software supervisory system (to be used with MB board only)

deSCRiption

Sabianet 9079118

identifiCation Code

Sabianet program for managing a network of Sabiana MB fan coils

“MO

NIT

OR

ING

” S

CR

EE

N

Sabianet is a centralised control system for networks of Sabiana MBfan coils, based on software that runs on LINUX™.The Sabianet software offers a practical and economical solution formanaging the units, with the simple click of the mouse.The main characteristics include simplicity of use, an extremely completeand functional weekly program, and the possibility to access the historicaloperating data for each individual unit connected.

The program exploits all the potential of our units with remote controls, representing anaddition to the latter.

The Sabianet program is a control tool that can be used as a replacement for the remotecontrol, or in parallel, however the settings made using Sabianet can have priority over those madeusing the remote control.

The program can be used to:

- Create uniform groups (groups of units on individual floors, in offices or rooms).

- Save weekly programs configured for different types of operation (summer, winter, mid seasons, closing periods etc.); these can then be recalled and activated with a simple click of the mouse. Weekly on/off cycles can be set for individual units or groups of units.

- Set the operating conditions for each individual unit or groups of units (operating mode, fan speed, temperature setting).

- Set the set point limits for each individual unit or groups of units.

- Switch each individual unit or groups of units ON or OFF.

The main program screen can display and interact with the entire network of units. An individual unit, a group ofunits or the entire network can be called so as to make modifications to the operating mode and the set point. Theuser can then check the operating status of each individual unit, read the room temperature, the coil temperatureand the operating status of the condensate drain pump or any alarms.

Page 37: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

37

CarismaManagement systemfor a network of fan coils

The icon of the terminal unitprovides the following information:

- Unit name ( C01000001)

- Set temperature ( TSET )

- Room temperature ( TA )

- Unit status: ON or OFF

- Mode: • Summer • Auto

• Winter • Fan only

- Fan speed: • Low • High

• Medium • AutoFan

“EV

EN

T M

AN

AG

EM

EN

T”

SC

RE

EN

Time bands are available for each day of the week. The time and the type of operation to be performed by the unitcan be set for each band. The time and the operating parameters can then be displayed before being sent to theunit and implemented.

The “Weekly Program” can be used to set the unit operating parameters for each day of the week. Up to 20 differentweekly programs can be set.

The “MONITORING” SCREEN shows the units thatare connected to the network and scanned by the program.

Displaying a unit

Page 38: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

38

Carisma

USB-RS 485

Outputsfor system

Powerinput

CONVERTER

RS 485

Outputsfor system

Powerinput

Outputsfor system

Powerinput

MC2 Jumperto be closed.

End of network.

Carisma CRSOunit

Carisma CRSOunit

Carisma CRSOunit

SABIANET

60 units max. (*)

Management systemfor a network of fan coils

PC Sabianet Software

Connectionof a Carisma CRSO networkwith MB electronic board

(*) In the event of more than 60 units, add one or more Router-S (see below).

RS 485 serial connection cable

Shielded cable to be used:Belden 9841, RS-485, 1x2x24 AWG SFTP, 120 Ohm

SIOS is a board equipped with 8 relays with potential free contact to control the activationor deactivation of remote electric utilities. Moreover, the board has 8 digital inlets todisplay the actuators or external consents, such as motor or other. The SIOS boardscan be connected:

- inside a network managed by Sabianet;

- to a PSM-DI panel (one SIOS for each PSM-DI panel).

The Router-S is an electronic board that:

- allows creating networks with more than 60 units (minimum 2 Router-S are required) or to divide the network (per floor, building, etc.);

- it allows creating a Master/Slave sub-network to be controlled as an indipendent group.

The Router-S can be used only inside a network managed by Sabianet.

The number of Router-S to be used is: - up to 60 units: no Router-S - from 61 to 120 units: 2 Router-S - every 60 subsequent units: 1 additional Router-S

identifiCation Code

SIOS 3021292

identifiCation Code

Router-S 3021290

PSM-DI and Sabianet electronic boards for HPO units

Page 39: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

INTRODUCTION

In line with innovative trends and modern industrial design,the Carisma CRSO fan coil range meets today’s demandingrequirements of performance, size, acoustics, low energy,ease of installation and maintenance. The Carisma CRSOfan coil unit has been designed around a platform of models,versions and accessories, all of which have been independentlytested and certified by Eurovent.

All Carisma CRSO fan coils with centrifugal fans are equippedwith electric motors which reduce electrical consumptioncomparative to previous models, with 5 speed motors asstandard offering greater flexibility in the selection of products.

New market trends have also led to an extension of the fourpipe model which now has a two row LTHW battery givingimproved outputs at lower flow and return temperatures.

A full range of control options is available including the Freepatented wireless control offering greater flexibility in theinstallation of units, with the highest precision in monitoringand maintaining the desired comfort conditions.

The Carisma CRSO model is complemented with a fullrange of accessories: various types of adjustment valves,additional electric heater, auxiliary condensatepump, air inlet/outlet diffusers for fittedinstallations.

• Available pressure • Fan absorption • Water pressure drop • Sound power

• Heating emission (2 pipe units) at the following conditions: - Entering water temperature +50°C - Entering air temperature +20°C - Waterflowrateasforthecoolingconditions

• Heating emission (4 pipe units) at the following conditions: - Water temperature +70°C E.W.T. +60°C L.W.T. - Entering air temperature +20°C

• Cooling total emission at the following conditions: - Water temperature +7°C E.W.T. +12°C L.W.T. - Entering air temperature +27°C dry bulb +19°C wet bulb

• Cooling sensible emission at the following conditions: - Water temperature +7°C E.W.T. +12°C L.W.T. - Entering air temperature +27°C dry bulb +19°C wet bulb

Sabiana take part to the Eurovent program of fan coil performance certification.The official figures are published in the web sitewww.eurovent-certification.com and in the web site www.certiflash.com.The tested performances are:

The descriptions and illustrations provided in this publication are not binding: Sabiana reserves the right,whilst maintaining the essential characteristics of the types described and illustrated, to make,

at any time, without the requirement to promptly update this piece of literature, any changes that it considersuseful for the purpose of improvement or for any other manufacturing or commercial requirements.

CONTENTS• Presentation Page 3

• Construction features Page 3

• Dimension, Weight, Water content Page 4

• EUROVENT Certification Page 6

• Main performance and technical characteristics Page 7

• Cooling emission tables Page 8

• Heating emission tables Page 12

• Correction factors table Page 14

• Operation limits Page 16

• Water pressure drop Page 17

• Accessories Page 18

• Wall electronic controls Page 24

• FreeSabiana wireless control system Page 30

• Controls and units MB version Page 32

• Management system for a network of fan coils Page 36

• PSM-DI and Sabianet electronic boards Page 38

Page 40: Air Conditioning Carisma CRSO High Pressure Fan Coil Unitscomatec-groupe.com/files/Carisma_CRSO_UK_cat_A...6 CRSO version Carisma (E) = Eurovent certified performance. (*) = The sound

NEW

MB control board

for Modbus

communication protocol

Compliant with ERP 2013 Regulation (EU) No. 327/2011

Air ConditioningCarisma CRSO High Pressure Fan Coil Units

Air Conditioning

Carisma CRSO High Pressure Fan Coil Units

CRSO

- E

X -

04/1

4

COD

. A4

6901

00

C/04

/14

Sabiana s.p.a. • via Piave, 53 • 20011 Corbetta • Milano • Italy • phone +39.02.97203.1 r.a. / +39.02.97270429 / +39.02.97270576fax +39.02.9777282 / +39.02.9772820 • www.sabiana.it • [email protected]

Quality management systemsISO 9001 – Cert. n° 0545/5

www.eurovent-certification.comwww.certiflash.com