AIR CONDITIONERS TS T-Class™ Split System Units R-410A - 50 HZ Bulletin No. 490135 February 2010 Supersedes October 2009 ENGINEERING DATA Nominal Capacity - 7 to 17.6 kW (2 to 5 Ton) Cooling Capacity - 6.4 to 17.6 kW (21 800 to 60 000 Btuh) MODEL NUMBER IDENTIFICATION T S A 048 S 4 N 4 1 T Family T = Product Line Major Design Sequence A= First Generation B = Second Generation Refrigerant Type 4 = R-410A Nominal Cooling Capacity 024 = 7.0 kW (2 tons) 030 = 8.8 kW (2.5 tons) 036 = 10.5 kW (3 tons) 048 = 14.1 kW(4 tons) 060 = 17.6 kW (5 tons) Voltage T = 220/240V-1phase-50hz M = 380/420-3phase-50hz Unit Type S = Split-System Air Conditioner Cooling Efficiency S = Standard Efficiency Part Load Capability N = No part load, single-stage compressor Coil Type 4 = Four-sided Minor Design Sequence 1 = First revision 2 = Second Revision 3 = Third Revision

Transcript of AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ......

Page 1: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

A I R C O N D I T I O N E R S

TST-Class™ Split System Units

R-410A - 50 HZ Bulletin No. 490135

February 2010Supersedes October 2009

E N G I N E E R I N G D ATA

Nominal Capacity - 7 to 17.6 kW (2 to 5 Ton)Cooling Capacity - 6.4 to 17.6 kW (21 800 to 60 000 Btuh)

MODEL NUMBER IDENTIFICATION

T S A 048 S 4 N 4 1 T

Family T = Product Line

Major Design Sequence A= First Generation

B = Second Generation

Refrigerant Type 4 = R-410A

Nominal Cooling Capacity 024 = 7.0 kW (2 tons)

030 = 8.8 kW (2.5 tons) 036 = 10.5 kW (3 tons) 048 = 14.1 kW(4 tons) 060 = 17.6 kW (5 tons)

Voltage T = 220/240V-1phase-50hz M = 380/420-3phase-50hz

Unit Type S = Split-System Air Conditioner

Cooling Efficiency S = Standard Efficiency

Part Load CapabilityN = No part load, single-stage compressor

Coil Type4 = Four-sided

Minor Design Sequence 1 = First revision 2 = Second Revision 3 = Third Revision

Page 2: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

50 hz T-Class Air Conditioners 7 to 17.6 kW / Page 2

FEATURES AND BENEFITS

TESTING

Rated at test conditions included in Air-Conditioning, Heating and Refrigeration Institute (AHRI) Standard 210/240 when operating at rated voltage and air volumes.Units and components within bonded for grounding to meet safety standards for servicing required by Underwriters Laboratories (UL) and the International Electrotechnical Commission (IEC). Units tested by Intertek for conformity assessment on the conditions set out in the New Approach Directives in support of CE marking. The CE (Conformité Européenne) marking certifies that a product has met EU (European Union) consumer safety, health or environmental requirements.International Organization for Standardization (ISO) 9001 Registered Manufacturing Quality SystemAPPLICATIONS

7 through 17.6 kWSingle or three-phase power supply.Vertical air discharge allows concealment behind shrubs at grade level or out of sight on a roof.Matching add-on furnace indoor coils or air handlers provide a wide range of cooling capacities and applications. See Ratings table.See Indoor Coils and Air Handlers sections for data.Units shipped completely factory assembled, piped and wired. Each unit test operated at the factory ensuring proper operation.Installer must set air conditioner, connect refrigerant lines and make electrical connections to complete job.

REFRIGERATION SYSTEM

R-410A RefrigerantNon-chlorine, ozone friendly, R-410A Unit pre-charged with refrigerant. See Specification table.Condenser FanDirect drive fan moves large air volumes uniformly through entire condenser coil for high refrigerant cooling capacity.Vertical air discharge minimizes operating sounds and eliminates damage to lawn and shrubs.Louvered steel top fan guard furnished as standard.Fan service access accomplished by removal of top panel.Copper Tube/Enhanced Fin CoilLennox designed and fabricated coil.Ripple-edged aluminum fins.Copper tube construction.Lanced fins provide maximum exposure of fin surface to air stream resulting in excellent heat transfer.Fin collars grip tubing for maximum contact area.Flared shoulder tubing connections/silver soldering construction.Coil is factory tested under high pressure to ensure leakproof construction.Entire coil is accessible for cleaning.Polyvinyl Chloride (PVC) coated steel wire coil guard furnished.

A

B

C

D

Contents

Dimensions ..................................................................8Expanded Ratings - Single Phase Models .................11Expanded Ratings - Three Phase Models ..................16Features And Benefits ..................................................2Installation Clearances .................................................9Model Number Identification .........................................1Optional Conventional Temperature Control Systems ..7Ratings - Single Phase ...............................................10Ratings - Three Phase ................................................10Sound Data ..................................................................9Specifications - Single Phase ......................................5Specifications - Three Phase .......................................6

B

C

E

F

G

D

Page 3: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

50 hz T-Class Air Conditioners 7 to 17.6 kW / Page 3

REFRIGERATION SYSTEM

R-410A RefrigerantNon-chlorine, ozone friendly, R-410A Unit pre-charged with refrigerant. See Specification table.Condenser FanDirect drive fan moves large air volumes uniformly through entire condenser coil for high refrigerant cooling capacity.Vertical air discharge minimizes operating sounds and eliminates damage to lawn and shrubs.Louvered steel top fan guard furnished as standard.Fan service access accomplished by removal of top panel.Copper Tube/Enhanced Fin CoilLennox designed and fabricated coil.Ripple-edged aluminum fins.Copper tube construction.Lanced fins provide maximum exposure of fin surface to air stream resulting in excellent heat transfer.Fin collars grip tubing for maximum contact area.Flared shoulder tubing connections/silver soldering construction.Coil is factory tested under high pressure to ensure leakproof construction.Entire coil is accessible for cleaning.Polyvinyl Chloride (PVC) coated steel wire coil guard furnished.

A

B

C

D

FEATURES AND BENEFITS

High Capacity Liquid Line DrierFurnished with unit for field installation.Approved for use with R-410A systems.Traps any moisture or dirt that could contaminate the refrigerant system.High Pressure SwitchShuts off unit if abnormal operating conditions cause the discharge pressure to rise above setting.Protects compressor from excessive condensing pressure.Manual reset.OPTIONS

Expansion Valve KitsMust be ordered extra and field installed on certain indoor units. See Ratings Table.Chatleff-style fittings.FreezestatInstalls on or near the vapor line of the indoor coil or on the suction line.Senses suction line temperature and cycles the compressor off when suction line temperature falls below it’s setpoint.Opens at -2°C and closes at 14°CLoss of Charge Switch KitHelps protect the compressor from damage due low refrigerant charge conditions.Single Pole, Single Throw (SPST), normally-closed switch, automatic reset switch mounted on suction line.Refrigerant Line KitsRefrigerant lines (suction & liquid) are shipped refrigeration clean. Lines are cleaned, dried, pressurized and sealed at factory.Suction line fully insulated.Lines are stubbed at both ends.Not available for -060 models. Must be field fabricated.

COMPRESSOR

Scroll CompressorCompressor features high efficiency with uniform suction flow, constant discharge flow and high volumetric efficiency and quiet operation.Compressor consists of two involute spiral scrolls matched together to generate a series of crescent shaped gas pockets between them.During compression, one scroll remains stationary while the other scroll orbits around it.Gas is drawn into the outer pocket, the pocket is sealed as the scroll rotates.As the spiral movement continues, gas pockets are pushed to the center of the scrolls. Volume between the pockets is simultaneously reduced.When pocket reaches the center, gas is now at high pressure and is forced out of a port located in the center of the fixed scrolls.During compression, several pockets are compressed simultaneously resulting in a smooth continuous compression cycle.Continuous flank contact, maintained by centrifugal force, minimizes gas leakage and maximizes efficiency.Scroll compressor is tolerant to the effects of slugging and contaminants. If this occurs, scrolls separate, allowing liquid or contaminants to be worked toward the center and discharged.Low gas pulses during compression reduces operational sound levels.Compressor motor is internally protected from excessive current and temperature.Compressor is installed in the unit on resilient rubber mounts for vibration free operation.Factory installed crankcase heater protects against refrigerant migration that can occur during low ambient operation.OPTIONS

Compressor Sound CoverA reinforced vinyl compressor cover containing a 38 mm thick batt of fiberglass insulation.All open edges are sealed with a 25 mm wide hook and loop fastening tape.

E

Page 4: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

50 hz T-Class Air Conditioners 7 to 17.6 kW / Page 4

CONTROLS

OPTIONS

Compressor Hard Start KitSingle-phase units are equipped with a permanent split capacitor (PSC) compressor motor. This type of motor normally doesn’t need a potential relay and start capacitor.In conditions such as low voltage, this kit may be required to increase the compressor starting torque.Compressor Low Ambient Cut-OffNon-adjustable switch (low ambient cut-out) prevents compressor operation when outdoor temperature is below 2°C.Compressor Time-Off ControlKit prevents compressor short-cycling and allows time for suction and discharge pressure to equalize.Permits compressor start-up in an unloaded condition.Automatic reset with 5 minute delay between compressor shut-off and start-up.Indoor Blower Off Delay RelayDelays the indoor blower-off time during the cooling cycle.See Ratings Tables for usage.Low Ambient KitAir conditioners operate satisfactorily down to 7°C outdoor air temperature without any additional controls.Low Ambient Control Kit can be field installed, allowing unit operation down to -1°C.ThermostatThermostat not furnished with unit and must be ordered extra. See Page 7.Timed-Off ControlKit prevents compressor short-cycling and allows time for suction and discharge pressure to equalize.Permits compressor start-up in an unloaded condition.Automatic reset with 5 minute delay between compressor shut-off and start-up.

FEATURES AND BENEFITS

CABINET

Heavy gauge steel cabinet with five station metal wash process.Powder paint finish provides superior rust and corrosion protection.Painted base section.Control box is conveniently located with all controls factory wired.Corner patch plate allows access to compressor components.Drainage holes are provided in base section for moisture removal.Refrigerant Line Connections, Electrical Inlets, Service ValvesSweat connection suction and liquid lines are located on corner of unit cabinet.Fully serviceable brass service valves prevent corrosion and provide access to refrigerant system. Suction valve can be fully shut off, while liquid valve may be front seated to manage refrigerant charge while servicing system.Refrigerant line connections and field wiring inlets are located in one central area of cabinet for easy access. See dimension drawing.

OPTIONS

Hail GuardsConstructed of louvered, heavy-gauge steel painted to match cabinet.Surrounds unit on all four sides to prevent damage to the coil.Mounting BaseProvides permanent foundation for outdoor units.High density polyethylene structural material is lightweight, sturdy, sound absorbing and will withstand the rigors of the sun, heat, cold, moisture, oil and refrigerant. Will not mildew or rot.Can be shipped singly or in packages of 6 to a carton.Unit Stand-Off KitBlack, high-density polyethylene feet are available to raise unit off of mounting surface away from damaging moisture.Four feet are furnished per order number.

F

G

Page 5: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

50 hz T-Class Air Conditioners 7 to 17.6 kW / Page 5

SPECIFICATIONS - SINGLE PHASE General Data

Model No. TSA024S4 TSA030S4 TSA036S4 TSA048S4 TSA060S4Nominal kW (tonnage) 7.0 (2) 8.8 (2.5) 10.5 (3) 14.1 (4) 17.6 (5)

Connections (sweat)

Liquid line o.d. - in. 3/8 3/8 3/8 3/8 3/8Suction line o.d. - in. 3/4 3/4 7/8 7/8 1-1/8

1 Refrigerant (R-410A) furnished 1.98 kg (4 lbs. 6 oz.)

1.93 kg (4 lbs. 4 oz.)

2.89 kg (6 lbs. 6 oz.)

3.40 kg (7 lbs. 8 oz.)

4.54 kg (10 lbs.)

Outdoor Coil

Net face area m2 (sq. ft.)

Outer coil 1.05 (11.33) 1.23 (13.22) 1.52 (16.33) 1.95 (21.0) 1.73 (18.67)Inner coil - - - - - - - - - - - - 1.67 (17.96)

Tube diameter - in. 5/16 5/16 5/16 5/16 5/16Number of rows 1 1 1 1 2

Fins per meter (per inch) 1024 (26) 1024 (26) 1024 (26) 1024 (26) 866 (22)Outdoor Fan

Diameter - mm. 457 (18) 457 (18) 559 (24) 559 (24) 559 (24)Number of blades 3 4 4 4 4

Motor W (hp) 75 (1/10) 150 (1/5) 185 (1/4) 185 (1/4) 185 (1/4)L/s (cfm) 924 (1958) 944 (2000) 1377 (2917) 1443 (3058) 1416 (3000)Rev/min 842 908 688 696 692

Watts 138 154 250 246 238Shipping Data - kg (lb.) 1 package 56 (123) 60 (133) 81 (178) 88 (194) 99 (218)Electrical Data

Line voltage data - 50 hz - 1 phase 220 / 240V 220 / 240V 220 / 240V 220 / 240V 220 / 240V2 Maximum overcurrent protection (amps) 25 25 35 35 45

3 Minimum circuit ampacity 14.3 16.9 21.7 21.6 26.9Compressor Rated load amps 10.9 12.2 16.0 15.9 20.2

Locked rotor amps 60.0 67.0 87.0 98.0 128.0Condenser Fan Motor

Full load amps 0.7 1.1 1.7 1.7 1.7Locked rotor amps 1.4 2.0 3.1 3.1 3.1

OPTIONAL ACCESSORIES - must be ordered extraCompressor Hard Start Kit 10J42 •

88M91 • • • •Compressor Low Ambient Cut-Off

45F08 • • • • •

Compressor Sound Cover 69J03 • • • • •Compressor Time-Off Control

47J27 • • • • •

Freezestat 3/8 in. tubing 93G35 • • • • •5/8 in. tubing 50A93 • • • • •

Hail Guards 92M87 • •92M88 • •92M93 •

Indoor Blower Off Delay Relay

58M81 • • • • •

Loss of Charge Switch Kit 84M23 • • • • •Low Ambient Kit 34M72 • • • • •Mounting Base 69J06 • • • •

69J07 •Refrigerant Line Sets

L15-41-20, L15-41-30, L15-41-40, L15-41-50

• •

L15-65-30, L15-65-40, L15-65-50

• •

Field Fabricate •Unit Stand-Off Kit 94J45 • • • • •NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage. 1 Refrigerant charge sufficient for 4.6 m (15 ft.) length of refrigerant lines.2 Heating Air Conditioning and Refrigeration type circuit breaker or fuse.3 Refer to local codes to determine wire, fuse and disconnect size requirements

Page 6: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

50 hz T-Class Air Conditioners 7 to 17.6 kW / Page 6

SPECIFICATIONS - THREE PHASEGeneral Data

Model No. TSA036S4 TSA048S4 TSA060S4Nominal kW (tonnage) 10.6 (3) 14.0 (4) 17.6 (5)

Connections (sweat)

Liquid line o.d. - in. 3/8 3/8 3/8Suction line o.d. - in. 7/8 7/8 1-1/8

1 Refrigerant (R-410A) furnished 2.52 kg (5 lbs. 9 oz.) 3.40 kg (7 lbs. 8 oz.) 4.54 kg (10 lbs.)Outdoor Coil

Net face area m2 (sq. ft.)

Outer coil 1.23 (13.22) 1.95 (21.00) 1.73 (18.67)Inner coil - - - - - - 1.67 (17.96)

Tube diameter - in. 5/16 5/16 5/16Number of rows 1 1 2

Fins per meter (per inch) 1024 (26) 1024 (26) 866 (22)Outdoor Fan

Diameter - mm (in.). 457 (18) 559 (22) 559 (22)Number of blades 4 4 4

Motor W (hp) 125 (1/6) 185 (1/4) 185 (1/4)L/s (cfm) 944 (2000) 1443 (3058) 1416 (3000)Rev/min 908 688 692

Watts 154 246 238Shipping Data - kg (lb) 1 package 61 (135) 88 (194) 99 (218)Electrical Data

Line voltage data - 50 hz - 3 phase 380 / 420V 380 / 420V 380 / 420V2 Maximum overcurrent protection (amps) 10 15 20

3 Minimum circuit ampacity 8.0 10.7 14.2Compressor Rated load amps 6.0 7.8 10.6

Locked rotor amps 46.0 51.5 74.0Condenser Fan Motor

Full load amps 0.55 1.0 1.0Locked rotor amps 1.1 2.3 2.3

OPTIONAL ACCESSORIES - must be ordered extraCompressor Crankcase Heater 93M04 • •

93M05 •Compressor Low Ambient Cut-Off 45F08 • • •Compressor Sound Cover 69J03 • • •Compressor Time-Off Control 47J27 • • •Freezestat 3/8 in. tubing 93G35 • • •

5/8 in. tubing 50A93 • • •Hail Guards 92M87

92M88 • •92M93 •

Indoor Blower Off Delay Relay 58M81 • • •Loss of Charge Switch Kit 84M23 • • •Low Ambient Kit 34M72 • • •Mounting Base 69J06 • •

69J07 •Refrigerant Line Sets L15-65-30, L15-65-40,

L15-65-50• •

Field Fabricate •Unit Stand-Off Kit 94J45 • • •NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage. 1 Refrigerant charge sufficient for 4.6 m (15 ft.) length of refrigerant lines.2 Heating Air Conditioning and Refrigeration type circuit breaker or fuse.3 Refer to local codes to determine wire, fuse and disconnect size requirements.

Page 7: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

50 hz T-Class Air Conditioners 7 to 17.6 kW / Page 7

OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS - FIELD INSTALLED

COMMERCIAL TOUCHSCREEN THERMOSTATIntuitive Touchscreen Interface - Two Stage Heating / Two Stage Cooling Conventional or Heat Pump - Seven Day Programmable - Four Time Periods/Day - Economizer Output - Title 24 Compliant - ENERGY STAR® Qualified - Backlit Display - Automatic Changeover

C0STAT02AE1L(14W81)

Sensors For Touchscreen Thermostat1 Remote non-adjustable wall mount 20k temperature sensor ........................ C0SNZN01AE2-

(47W36)1 Remote non-adjustable wall mount 10k averaging temperature sensor ....... C0SNZN73AE1-

(47W37)1 Remote non-adjustable duct mount temperature sensor .............................. C0SNDC00AE1-

(19L22)Outdoor temperature sensor............................................................................ C0SNSR03AE1-

(X4148)Accessories For Touchscreen Thermostat

Locking cover (clear) ....................................................................................... C0MISC15AE1-(39P21)

1 Remote sensors for C0STAT02AE1L can be applied in the following combinations: (1) C0SNZN01AE1-, (2) C0SNZN73AE1-, (2) C0SNZN01AE1- and (1) C0SNZN73AE1-, (4) C0SNZN01AE1-, (3) C0SNZN01AE1- and (2) C0SNZN73AE1.

DIGITAL NON-PROGRAMMABLE THERMOSTATSIntuitive Interface - Automatic Changeover - Simple Up and Down Temperature ControlTwo-stage heating / cooling conventional systems ...................................... C0STAT10AE1L

(13K98)Sensor For Digital Non-Programmable Thermostats AboveRemote wall mounted temperature sensor ...................................................... C0SNZN00AE1-

(26K57)Intuitive Interface - Automatic Changeover - Backlit Display - Simple Up and Down Temperature ControlOne-stage heating / cooling conventional systems ......................................... C0STAT12AE1L

(51M32)Sensor For Digital Non-Programmable Thermostats AboveOutdoor temperature sensor............................................................................ C0SNSR04AE1-

(X2658)Accessories For Digital Non-Programmable Thermostats AboveOptional wall mounting plate............................................................................ C0MISC17AE1-

(X2659)

Page 8: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

50 hz T-Class Air Conditioners 7 to 17.6 kW / Page 8

DIMENSIONS - MM (INCHES)

SIDE VIEW

SUCTION &LIQUID LINE

CONNECTIONS

INLET

AIR

INLET

AIR

DISCHARGE AIR

SIDE VIEW

TOP VIEW

CONDENSERCOIL FAN

COMPRESSOR

INLET AIR

INLET AIR

SUCTION LINECONNECTION

2-3/4 (70)

A

ELECTRICALINLETS

LIQUID LINECONNECTION

TOP VIEW BASE SECTION

COMPRESSOR

COIL DRAIN OUTLETS(Around perimeter of base)

OPTIONAL UNITSTAND-OFF KIT (4)

(Field Installed)

A

OPTIONAL UNITSTAND-OFF KIT (4)

(Field Installed)

2 (51)

3/4(19)

111(4-3/8)

162(6-3/8)

111(4-3/8)

111(4-3/8)

111(4-3/8)

111(4-3/8)

111(4-3/8)

162(6-3/8)

BC

Model No.A B C

mm inches mm inches mm inchesTSA024S4 616 24-1/4 641 25-1/4 616 24-1/4 TSA030S4 616 24-1/4 743 29-1/4 724 28-1/2 TSA036S4 - Single Phase 616 24-1/4 743 29-1/4 724 28-1/2 TSA036S4 - Three Phase 718 28-1/4 743 29-1/4 724 28-1/2 TSA048S4 718 28-1/4 946 37-1/4 921 36-1/4 TSA060S4 718 28-1/4 845 33-1/4 826 32-1/2

Page 9: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

50 hz T-Class Air Conditioners 7 to 17.6 kW / Page 9

INSTALLATION CLEARANCES - MM (INCHES)

SeeNOTES

See NOTES

See NOTES

SeeNOTES

CONTROLBOX

NOTES:Service clearance of 762 mm (30 in.) must be maintained on one of the sides adjacent to the control box.Clearance to one of the other three sides must be 914 mm (36 in.)Clearance to one of the remaining two sides may be 305 mm (12 in.) and the final side may be 152 mm (6 in.).A clearance of 610 mm (24 in.) must be maintained between two units.1219 mm (48 in.) clearance required on top of unit.

SOUND DATA

1 UnitModel No.

Octave Band Sound Power Levels dBA, re 10-12 WattsCenter Frequency - HZ

1 Sound RatingNumber (dB)

125 250 500 1000 2000 4000 8000220/240V - Single Phase ModelsTSA024S4 51.5 62 64.5 68.5 67 60.5 53.5 76TSA030S4 52.5 62 67.5 69 67 61.5 54.5 76TSA036S4 58 68 73.5 75.5 74 69.5 62.5 80TSA048S4 57.5 67 73 74.5 71 64 58.5 80TSA060S4 57 63 69.5 71.5 71 65.5 60.5 80380/420V - Three Phase ModelsTSA036S4 52.5 61 67 69 67 61.5 52.5 80TSA048S4 57.5 67 73 74.5 71 64 58.5 80TSA060S4 57 63 69.5 71.5 71 65.5 60.5 80NOTE - the octave sound power data does not include tonal correction. 1 Tested according to Air-Conditioning, Heating and Refrigeration Institute (AHRI) Standard 270-95 test conditions.

Page 10: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

50 hz T-Class Air Conditioners 7 to 17.6 kW / Page 10

RATINGS - THREE PHASE

ModelNumber

GrossCoolingCapacity

NetCoolingCapacity

Total Power Input

EER(Energy EfficiencyRating)

COP(Coefficient of Perfomance)Output/Input

Indoor Unit Model Number

Expansion Device Required

kW Btuh kW BtuhTSA036S4 10.0 34 200 9.4 32 200 3.28 9.85 2.89 BCRMB9937S005 37L51TSA036S4 9.9 33 600 9.4 32 200 3.07 10.50 3.08 CX34-36B/C-6F Factory InstalledTSA036S4 10.0 34 000 9.6 32 600 3.07 10.60 3.11 CR33-30/36B-F 37L51TSA036S4 9.8 33 500 9.4 32 000 3.07 10.40 3.05 CH33-36B-2F 37L51TSA048S4 14.2 48 300 13.3 45 500 4.42 10.30 3.02 BCRMC9960S005 91M02TSA048S4 14.0 47 600 13.3 45 500 4.20 10.85 3.18 CX34-44/48C-6F Factory InstalledTSA048S4 13.8 46 900 13.2 45 000 4.19 10.75 3.15 CR33-48C-F 91M02TSA048S4 14.2 48 400 13.6 46 500 4.21 11.05 3.24 CH33-48C-2F 91M02TSA060S4 17.9 61 100 17.0 58 000 5.85 9.90 2.90 BCRMD1960S005 91M02TSA060S4 18.3 62 400 17.6 60 000 5.71 10.50 3.08 CX34-62D-6F Factory InstalledTSA060S4 17.9 61 000 17.1 58 500 5.68 10.30 3.02 CR33-60D-F 91M02TSA060S4 18.0 61 500 17.3 59 000 5.69 10.40 3.05 CH33-60D-2F 91M02Rating test conditions are those included in Air-Conditioning and Refrigeration Institute (ARI) Standard 210/240; 35°C (95°F) outdoor air temperature and 27°C (80°F) db/19°C

(67°F) wb entering evaporator air; minimum external duct static pressure while operating at rated voltage and air volumes.All ratings include the use of a blower time delay relay (TDR). Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or

air handler specifications to determine if relay is needed.

RATINGS - SINGLE PHASE

ModelNumber

GrossCoolingCapacity

NetCoolingCapacity

Total Power Input kW

EER(Energy EfficiencyRating)

COP(Coefficient of Perfomance)Output/Input

Indoor Unit Model Number

Expansion Device Required

kW Btuh kW BtuhTSA024S4 7.0 23 800 6.6 22 600 2.10 10.75 3.15 BCRMA7924S005 Factory InstalledTSA024S4 6.9 23 600 6.6 22 600 2.04 11.10 3.25 CX34-30A/B/C-6F Factory InstalledTSA024S4 6.7 22 800 6.4 21 800 2.03 10.75 3.15 CR33-24B-F 37L51TSA024S4 6.9 23 600 6.6 22 600 2.04 11.10 3.25 CH33-25B-2F 37L51TSA030S4 8.4 28 500 8.0 27 200 2.47 11.00 3.22 BCRMA7924S005 Factory InstalledTSA030S4 8.3 28 300 7.9 27 000 2.45 11.05 3.24 CX34-30A/B/C-6F Factory InstalledTSA030S4 8.7 29 600 8.3 28 400 2.46 11.55 3.38 CR33-30/36B-F 37L51TSA030S4 8.9 30 200 8.5 29 000 2.47 11.75 3.44 CH33-31B-2F 37L51TSA036S4 10.5 35 900 9.9 33 800 3.31 10.20 2.99 BCRMB9937S005 Factory InstalledTSA036S4 10.2 34 900 9.8 33 400 3.10 10.75 3.15 CX34-36B/C-6F Factory InstalledTSA036S4 10.3 35 200 9.9 33 800 3.11 10.90 3.19 CR33-30/36B-F 37L51TSA036S4 10.2 34 800 9.8 33 400 3.10 10.75 3.15 CH33-36B-2F 37L51TSA048S4 14.3 48 600 13.5 46 000 4.52 10.20 2.99 BCRMC9960S005 Factory InstalledTSA048S4 14.1 47 900 13.5 46 000 4.30 10.70 3.14 CX34-44/48C-6F Factory InstalledTSA048S4 13.8 47 200 13.2 45 000 4.29 10.50 3.08 CR33-48C-F 91M02TSA048S4 14.3 48 600 13.6 46 500 4.31 10.80 3.17 CH33-48C-2F 91M02TSA060S4 15.8 53 700 14.8 50 500 4.82 10.50 3.08 BCRMD1960S005 Factory InstalledTSA060S4 16.1 54 800 15.4 52 500 4.67 11.25 3.30 CX34-62D-6F Factory InstalledTSA060S4 15.8 53 800 14.9 51 000 4.65 11.00 3.22 CR33-60D-F 91M02TSA060S4 15.8 54 000 15.1 51 500 4.65 11.10 3.25 CH33-60D-2F 91M02Rating test conditions are those included in Air-Conditioning and Refrigeration Institute (ARI) Standard 210/240; 35°C (95°F) outdoor air temperature and 27°C (80°F) db/19°C

(67°F) wb entering evaporator air; minimum external duct static pressure while operating at rated voltage and air volumes.All ratings include the use of a blower time delay relay (TDR). Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or

air handler specifications to determine if relay is needed.

Page 11: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

50 hz T-Class Air Conditioners 7 to 17.6 kW / Page 11

TSA024S4 Cooling Capacity with BCRMA7924S005Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C315 6.8 1.31 0.75 0.88 0.99 6.3 1.60 0.77 0.91 1.00 5.8 1.94 0.81 0.96 1.00 5.1 2.38 0.86 1.00 1.00390 7.1 1.32 0.79 0.94 1.00 6.6 1.60 0.83 0.98 1.00 6.1 1.95 0.87 1.00 1.00 5.5 2.39 0.94 1.00 1.00470 7.4 1.32 0.84 0.99 1.00 6.9 1.60 0.89 1.00 1.00 6.4 1.96 0.94 1.00 1.00 5.7 2.40 1.00 1.00 1.00

19°C315 7.2 1.32 0.60 0.72 0.84 6.7 1.60 0.62 0.75 0.88 6.1 1.95 0.64 0.78 0.93 5.4 2.39 0.67 0.84 0.99390 7.5 1.32 0.63 0.77 0.91 7.0 1.61 0.65 0.80 0.95 6.4 1.95 0.68 0.85 1.00 5.6 2.40 0.72 0.92 1.00470 7.8 1.32 0.66 0.82 0.98 7.2 1.61 0.69 0.86 1.00 6.6 1.96 0.72 0.92 1.00 5.8 2.40 0.77 0.99 1.00

22°C315 7.6 1.32 0.47 0.58 0.70 7.1 1.61 0.47 0.60 0.72 6.4 1.96 0.49 0.62 0.76 5.7 2.40 0.50 0.66 0.81390 7.9 1.32 0.48 0.62 0.75 7.4 1.61 0.49 0.64 0.78 6.7 1.96 0.51 0.67 0.82 5.9 2.41 0.52 0.71 0.89470 8.2 1.33 0.50 0.65 0.80 7.6 1.61 0.51 0.68 0.83 6.9 1.96 0.52 0.71 0.89 6.1 2.41 0.56 0.76 0.97

EXPANDED RATINGS - SINGLE PHASE MODELSNOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

TSA024S4 Cooling Capacity with CX34-30A/B/CEntering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C330 6.9 1.31 0.76 0.90 1.00 6.4 1.60 0.79 0.93 1.00 5.8 1.94 0.83 0.98 1.00 5.2 2.38 0.89 1.00 1.00380 7.1 1.32 0.79 0.93 1.00 6.5 1.60 0.82 0.98 1.00 6.0 1.95 0.87 1.00 1.00 5.4 2.39 0.93 1.00 1.00425 7.2 1.32 0.82 0.97 1.00 6.7 1.60 0.85 1.00 1.00 6.2 1.95 0.90 1.00 1.00 5.6 2.40 0.97 1.00 1.00

19°C330 7.2 1.32 0.62 0.74 0.86 6.7 1.60 0.63 0.77 0.90 6.2 1.95 0.65 0.80 0.95 5.4 2.39 0.69 0.86 1.00380 7.4 1.32 0.63 0.77 0.90 6.9 1.61 0.65 0.80 0.94 6.3 1.95 0.67 0.84 0.99 5.6 2.40 0.71 0.90 1.00425 7.6 1.32 0.65 0.80 0.94 7.1 1.60 0.67 0.83 0.98 6.4 1.96 0.70 0.88 1.00 5.7 2.40 0.74 0.94 1.00

22°C330 7.6 1.32 0.47 0.60 0.72 7.1 1.61 0.48 0.62 0.74 6.4 1.96 0.49 0.64 0.78 5.7 2.39 0.50 0.67 0.83380 7.8 1.32 0.48 0.62 0.75 7.3 1.61 0.49 0.64 0.77 6.7 1.96 0.50 0.66 0.81 5.9 2.40 0.52 0.70 0.87425 8.0 1.33 0.49 0.64 0.77 7.4 1.61 0.50 0.66 0.81 6.8 1.96 0.51 0.69 0.85 6.0 2.41 0.54 0.73 0.92

TSA024S4 Cooling Capacity with CR33-24B-F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C330 6.6 1.31 0.75 0.88 0.99 6.1 1.59 0.77 0.91 1.00 5.6 1.94 0.81 0.96 1.00 5.0 2.37 0.86 1.00 1.00380 6.8 1.31 0.78 0.92 1.00 6.3 1.60 0.80 0.95 1.00 5.8 1.94 0.84 0.99 1.00 5.2 2.38 0.90 1.00 1.00425 7.0 1.32 0.80 0.95 1.00 6.5 1.60 0.83 0.98 1.00 6.0 1.95 0.88 1.00 1.00 5.4 2.39 0.94 1.00 1.00

19°C330 7.1 1.32 0.61 0.73 0.85 6.6 1.60 0.62 0.75 0.88 5.9 1.94 0.64 0.79 0.93 5.2 2.39 0.67 0.84 0.98380 7.2 1.32 0.62 0.75 0.89 6.7 1.60 0.64 0.78 0.92 6.1 1.95 0.66 0.82 0.97 5.4 2.39 0.70 0.88 1.00425 7.4 1.32 0.64 0.78 0.92 6.8 1.60 0.65 0.81 0.96 6.2 1.95 0.68 0.85 0.99 5.5 2.39 0.72 0.91 1.00

22°C330 7.5 1.32 0.47 0.59 0.70 6.9 1.60 0.48 0.61 0.73 6.3 1.96 0.49 0.63 0.76 5.6 2.40 0.51 0.66 0.81380 7.6 1.32 0.48 0.61 0.73 7.1 1.61 0.49 0.63 0.76 6.5 1.96 0.50 0.65 0.79 5.7 2.40 0.52 0.69 0.86425 7.9 1.32 0.49 0.62 0.76 7.3 1.61 0.50 0.64 0.79 6.6 1.96 0.51 0.67 0.83 5.8 2.40 0.53 0.71 0.89

TSA024S4 Cooling Capacity with CH33-25B-2F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C330 7.1 1.32 0.77 0.91 1.00 6.5 1.60 0.80 0.95 1.00 5.9 1.95 0.84 1.00 1.00 5.3 2.39 0.90 1.00 1.00380 7.3 1.32 0.81 0.96 1.00 6.7 1.60 0.84 0.99 1.00 6.2 1.95 0.88 1.00 1.00 5.5 2.39 0.95 1.00 1.00425 7.5 1.32 0.84 0.99 1.00 6.9 1.60 0.87 1.00 1.00 6.4 1.95 0.92 1.00 1.00 5.7 2.40 0.99 1.00 1.00

19°C330 7.4 1.32 0.62 0.75 0.88 6.9 1.60 0.63 0.78 0.92 6.3 1.95 0.66 0.81 0.97 5.5 2.39 0.69 0.87 1.00380 7.6 1.32 0.64 0.78 0.92 7.1 1.61 0.66 0.81 0.96 6.4 1.96 0.68 0.86 1.00 5.7 2.40 0.72 0.92 1.00425 7.8 1.32 0.66 0.81 0.97 7.2 1.61 0.68 0.85 1.00 6.6 1.96 0.71 0.90 1.00 5.7 2.40 0.75 0.97 1.00

22°C330 7.7 1.32 0.48 0.60 0.73 7.2 1.61 0.48 0.62 0.75 6.6 1.96 0.49 0.64 0.79 5.8 2.40 0.51 0.68 0.85380 8.0 1.32 0.48 0.62 0.76 7.4 1.61 0.49 0.64 0.79 6.7 1.96 0.50 0.67 0.83 5.9 2.41 0.52 0.71 0.90425 8.2 1.33 0.49 0.64 0.79 7.6 1.61 0.50 0.67 0.83 6.9 1.96 0.52 0.70 0.87 6.1 2.41 0.54 0.75 0.94

Page 12: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

50 hz T-Class Air Conditioners 7 to 17.6 kW / Page 12

TSA030S4 Cooling Capacity with BCRMA7924S005 Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C355 8.1 1.56 0.75 0.86 0.98 7.6 1.90 0.76 0.89 1.00 6.9 2.32 0.79 0.94 1.00 6.2 2.83 0.83 0.99 1.00445 8.6 1.58 0.78 0.93 1.00 8.0 1.91 0.81 0.97 1.00 7.3 2.33 0.85 1.00 1.00 6.6 2.85 0.91 1.00 1.00535 8.9 1.59 0.83 0.99 1.00 8.3 1.92 0.86 1.00 1.00 7.6 2.35 0.91 1.00 1.00 6.9 2.86 0.97 1.00 1.00

19°C355 8.6 1.57 0.60 0.72 0.83 8.0 1.91 0.61 0.74 0.86 7.3 2.33 0.63 0.77 0.90 6.5 2.84 0.66 0.81 0.96445 9.0 1.59 0.62 0.76 0.89 8.4 1.93 0.64 0.79 0.93 7.6 2.35 0.67 0.83 0.98 6.8 2.86 0.68 0.88 1.00535 9.3 1.60 0.65 0.81 0.96 8.7 1.94 0.67 0.84 0.99 7.9 2.35 0.70 0.89 1.00 7.0 2.87 0.74 0.95 1.00

22°C355 9.0 1.59 0.46 0.58 0.69 8.4 1.93 0.47 0.60 0.71 7.7 2.35 0.48 0.61 0.74 6.9 2.86 0.50 0.64 0.79445 9.5 1.60 0.48 0.61 0.74 8.8 1.94 0.49 0.63 0.76 8.0 2.36 0.50 0.65 0.80 7.1 2.88 0.51 0.69 0.86535 9.8 1.61 0.49 0.64 0.79 9.1 1.96 0.51 0.66 0.82 8.3 2.37 0.52 0.69 0.86 7.3 2.88 0.54 0.73 0.93

EXPANDED RATINGS - SINGLE PHASE MODELSNOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

TSA030S4 Cooling Capacity with CX34-30A/B/C-6FEntering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C355 8.0 1.67 .74 .87 .99 7.6 1.90 .76 .89 1.00 7.2 2.17 .78 .92 1.00 6.7 2.48 .80 .96 1.00445 8.4 1.68 .79 .94 1.00 7.9 1.91 .81 .97 1.00 7.5 2.18 .84 .99 1.00 7.0 2.49 .87 1.00 1.00535 8.7 1.69 .84 .99 1.00 8.1 1.92 .86 1.00 1.00 7.9 2.19 .89 1.00 1.00 7.4 2.50 .93 1.00 1.00

19°C355 8.4 1.68 .60 .72 .84 8.1 1.91 .61 .74 .86 7.6 2.18 .62 .75 .89 7.0 2.49 .63 .78 .92445 8.8 1.69 .63 .77 .91 8.3 1.93 .64 .79 .93 7.9 2.20 .66 .81 .97 7.4 2.50 .68 .84 .99535 9.1 1.71 .66 .82 .97 8.5 1.94 .67 .84 .99 8.1 2.20 .69 .87 1.00 7.6 2.51 .71 .91 1.00

22°C355 8.9 1.70 .47 .59 .70 8.4 1.93 .47 .60 .71 7.9 2.20 .48 .61 .73 7.4 2.51 .49 .62 .75445 9.3 1.71 .48 .62 .75 8.7 1.94 .49 .63 .76 8.3 2.21 .50 .65 .79 7.7 2.52 .50 .66 .82535 9.6 1.72 .50 .65 .80 8.9 1.96 .51 .66 .82 8.6 2.22 .51 .68 .85 8.0 2.53 .52 .70 .88

TSA030S4 Cooling Capacity with CR33-30/36B-FEntering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C400 8.7 1.58 0.78 0.92 1.00 8.1 1.92 0.80 0.95 1.00 7.3 2.33 0.84 0.99 1.00 6.6 2.85 0.90 1.00 1.00470 9.0 1.59 0.82 0.97 1.00 8.3 1.92 0.85 1.00 1.00 7.6 2.34 0.89 1.00 1.00 6.9 2.86 0.95 1.00 1.00545 9.2 1.59 0.85 1.00 1.00 8.6 1.93 0.89 1.00 1.00 7.9 2.35 0.93 1.00 1.00 7.1 2.87 0.99 1.00 1.00

19°C400 9.1 1.59 0.62 0.75 0.89 8.4 1.93 0.63 0.78 0.92 7.7 2.35 0.66 0.82 0.97 6.8 2.86 0.69 0.87 1.00470 9.4 1.60 0.64 0.79 0.94 8.7 1.94 0.66 0.83 0.97 7.9 2.36 0.69 0.87 1.00 7.0 2.87 0.73 0.92 1.00545 9.6 1.61 0.67 0.83 0.98 8.9 1.94 0.69 0.87 1.00 8.1 2.36 0.72 0.91 1.00 7.1 2.87 0.76 0.97 1.00

22°C400 9.6 1.60 0.47 0.60 0.73 8.9 1.95 0.48 0.62 0.76 8.1 2.37 0.49 0.64 0.80 7.2 2.88 0.51 0.68 0.85470 9.9 1.62 0.49 0.63 0.77 9.1 1.96 0.49 0.65 0.80 8.3 2.37 0.50 0.68 0.84 7.4 2.88 0.53 0.72 0.90545 10.1 1.62 0.50 0.66 0.81 9.3 1.96 0.51 0.68 0.85 8.4 2.38 0.52 0.71 0.89 7.4 2.89 0.55 0.76 0.96

TSA030S4 Cooling Capacity with CH33-31B-2F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C400 8.8 1.58 0.77 0.91 1.00 8.1 1.92 0.80 0.95 1.00 7.4 2.33 0.84 0.99 1.00 6.7 2.85 0.89 1.00 1.00470 9.1 1.59 0.81 0.97 1.00 8.4 1.93 0.84 1.00 1.00 7.7 2.35 0.89 1.00 1.00 6.9 2.86 0.95 1.00 1.00545 9.3 1.60 0.85 1.00 1.00 8.7 1.94 0.88 1.00 1.00 8.0 2.36 0.93 1.00 1.00 7.2 2.88 1.00 1.00 1.00

19°C400 9.3 1.60 0.62 0.75 0.88 8.6 1.94 0.63 0.78 0.92 7.8 2.35 0.65 0.81 0.96 6.9 2.87 0.68 0.87 1.00470 9.6 1.61 0.64 0.79 0.94 8.9 1.95 0.66 0.82 0.97 8.1 2.36 0.68 0.86 1.00 7.1 2.87 0.72 0.92 1.00545 9.8 1.61 0.65 0.83 0.98 9.1 1.95 0.68 0.86 1.00 8.2 2.37 0.71 0.91 1.00 7.2 2.88 0.76 0.98 1.00

22°C400 9.7 1.61 0.47 0.60 0.72 9.0 1.95 0.48 0.62 0.75 8.2 2.37 0.49 0.63 0.79 7.3 2.88 0.50 0.68 0.84470 10.0 1.62 0.48 0.63 0.77 9.3 1.96 0.49 0.65 0.80 8.4 2.38 0.51 0.67 0.84 7.5 2.89 0.52 0.71 0.90545 10.3 1.63 0.50 0.64 0.80 9.5 1.97 0.49 0.67 0.84 8.6 2.38 0.52 0.70 0.89 7.6 2.90 0.54 0.75 0.96

Page 13: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

50 hz T-Class Air Conditioners 7 to 17.6 kW / Page 13

TSA036S4 Cooling Capacity with BCRMB9937S005 Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C455 10.2 1.95 0.75 0.88 0.99 9.4 2.40 0.78 0.91 1.00 8.6 2.94 0.81 0.96 1.00 7.7 3.61 0.86 1.00 1.00570 10.7 1.96 0.80 0.94 1.00 9.9 2.41 0.83 0.98 1.00 9.1 2.94 0.87 1.00 1.00 8.2 3.63 0.94 1.00 1.00685 11.2 1.97 0.85 0.99 1.00 10.4 2.42 0.88 1.00 1.00 9.6 2.96 0.93 1.00 1.00 8.6 3.64 0.99 1.00 1.00

19°C455 10.9 1.97 0.61 0.73 0.85 10.1 2.41 0.62 0.75 0.88 9.1 2.95 0.64 0.79 0.93 8.1 3.62 0.67 0.84 0.99570 11.4 1.98 0.64 0.77 0.91 10.5 2.42 0.66 0.81 0.95 9.5 2.96 0.68 0.85 1.00 8.4 3.63 0.72 0.91 1.00685 11.8 1.98 0.67 0.82 0.97 10.8 2.42 0.69 0.86 1.00 9.8 2.96 0.72 0.91 1.00 8.6 3.64 0.76 0.98 1.00

22°C455 11.5 1.98 0.47 0.59 0.70 10.7 2.42 0.48 0.61 0.73 9.7 2.96 0.49 0.63 0.76 8.6 3.64 0.51 0.66 0.81570 12.0 1.99 0.49 0.62 0.75 11.1 2.43 0.50 0.64 0.78 10.1 2.98 0.51 0.67 0.82 8.9 3.65 0.53 0.71 0.88685 12.5 2.00 0.51 0.65 0.80 11.5 2.44 0.52 0.68 0.84 10.4 2.98 0.53 0.71 0.89 9.1 3.65 0.56 0.76 0.95

EXPANDED RATINGS - SINGLE PHASE MODELSNOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

TSA036S4 Cooling Capacity with CX34-36B/C-6FEntering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C470 10.1 1.95 0.76 0.90 1.00 9.4 2.39 0.79 0.93 1.00 8.5 2.93 0.83 0.98 1.00 7.6 3.61 0.88 1.00 1.00565 10.5 1.96 0.80 0.95 1.00 9.7 2.40 0.83 0.98 1.00 8.9 2.94 0.87 1.00 1.00 8.0 3.62 0.93 1.00 1.00660 10.9 1.97 0.84 0.99 1.00 10.1 2.41 0.87 1.00 1.00 9.3 2.95 0.92 1.00 1.00 8.3 3.63 0.99 1.00 1.00

19°C470 10.7 1.96 0.61 0.74 0.86 9.9 2.40 0.63 0.77 0.90 9.0 2.95 0.65 0.80 0.95 8.0 3.62 0.68 0.85 1.00565 11.1 1.97 0.63 0.78 0.92 10.2 2.41 0.65 0.81 0.96 9.3 2.95 0.68 0.85 1.00 8.2 3.62 0.72 0.91 1.00660 11.4 1.98 0.66 0.82 0.97 10.5 2.42 0.68 0.85 1.00 9.5 2.96 0.71 0.90 1.00 8.4 3.64 0.76 0.97 1.00

22°C470 11.1 1.97 0.47 0.60 0.71 10.3 2.42 0.48 0.61 0.74 9.4 2.96 0.49 0.64 0.78 8.4 3.63 0.51 0.67 0.83565 11.6 1.98 0.48 0.62 0.75 10.7 2.42 0.49 0.64 0.78 9.8 2.97 0.50 0.67 0.82 8.6 3.64 0.52 0.70 0.88660 12.0 1.99 0.50 0.65 0.79 11.0 2.43 0.51 0.67 0.83 10.0 2.97 0.52 0.70 0.88 8.8 3.64 0.54 0.75 0.95

TSA036S4 Cooling Capacity with CR33-30/36B-F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C470 10.2 1.95 0.76 0.90 1.00 9.5 2.40 0.79 0.93 1.00 8.6 2.93 0.83 0.98 1.00 7.7 3.61 0.88 1.00 1.00565 10.6 1.96 0.80 0.95 1.00 9.8 2.40 0.83 0.98 1.00 9.0 2.95 0.88 1.00 1.00 8.0 3.62 0.93 1.00 1.00660 11.0 1.97 0.84 0.99 1.00 10.2 2.41 0.88 1.00 1.00 9.3 2.95 0.93 1.00 1.00 8.4 3.63 0.99 1.00 1.00

19°C470 10.8 1.97 0.61 0.74 0.87 10.0 2.41 0.63 0.76 0.90 9.1 2.94 0.65 0.80 0.95 8.1 3.62 0.68 0.85 1.00565 11.2 1.97 0.63 0.78 0.92 10.3 2.41 0.65 0.81 0.96 9.4 2.96 0.68 0.85 1.00 8.3 3.63 0.72 0.91 1.00660 11.5 1.98 0.66 0.82 0.97 10.6 2.42 0.68 0.86 1.00 9.6 2.96 0.71 0.90 1.00 8.5 3.63 0.76 0.97 1.00

22°C470 11.4 1.98 0.47 0.59 0.71 10.6 2.42 0.48 0.61 0.74 9.6 2.96 0.49 0.63 0.78 8.5 3.64 0.50 0.67 0.83565 11.8 1.99 0.48 0.62 0.75 10.9 2.43 0.49 0.64 0.79 9.9 2.97 0.50 0.67 0.83 8.7 3.64 0.52 0.71 0.89660 12.2 1.99 0.50 0.65 0.80 11.2 2.44 0.51 0.67 0.83 10.1 2.97 0.52 0.70 0.88 8.9 3.65 0.54 0.75 0.95

TSA036S4 Cooling Capacity with CH33-36B-2F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C470 10.1 1.95 0.76 0.90 1.00 9.3 2.39 0.79 0.93 1.00 8.5 2.93 0.82 0.98 1.00 7.6 3.61 0.87 1.00 1.00565 10.5 1.96 0.80 0.95 1.00 9.7 2.40 0.83 0.98 1.00 8.9 2.94 0.87 1.00 1.00 8.0 3.62 0.93 1.00 1.00660 10.8 1.97 0.84 0.99 1.00 10.1 2.41 0.87 1.00 1.00 9.2 2.95 0.92 1.00 1.00 8.3 3.63 0.98 1.00 1.00

19°C470 10.6 1.96 0.61 0.74 0.86 9.8 2.40 0.63 0.76 0.90 9.0 2.94 0.65 0.80 0.94 8.0 3.62 0.68 0.85 1.00565 11.0 1.97 0.63 0.77 0.91 10.2 2.41 0.65 0.80 0.95 9.3 2.95 0.67 0.84 1.00 8.2 3.62 0.71 0.91 1.00660 11.4 1.98 0.66 0.81 0.96 10.5 2.42 0.68 0.85 1.00 9.5 2.96 0.71 0.90 1.00 8.4 3.63 0.75 0.96 1.00

22°C470 11.1 1.97 0.47 0.60 0.71 10.3 2.42 0.48 0.61 0.74 9.4 2.96 0.49 0.64 0.77 8.4 3.63 0.51 0.67 0.83565 11.6 1.98 0.48 0.62 0.75 10.7 2.42 0.49 0.64 0.78 9.7 2.96 0.50 0.66 0.82 8.6 3.64 0.52 0.70 0.88660 12.0 1.99 0.50 0.65 0.79 11.0 2.43 0.51 0.67 0.83 10.0 2.97 0.52 0.70 0.87 8.8 3.64 0.54 0.75 0.94

Page 14: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

50 hz T-Class Air Conditioners 7 to 17.6 kW / Page 14

TSA048S4 Cooling Capacity with BCRMC9960S005 Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C575 13.8 2.85 0.75 0.87 0.98 12.8 3.41 0.77 0.90 1.00 11.6 4.09 0.80 0.95 1.00 10.3 4.93 0.85 1.00 1.00715 14.5 2.89 0.79 0.94 1.00 13.4 3.44 0.82 0.98 1.00 12.3 4.12 0.87 1.00 1.00 11.0 4.97 0.93 1.00 1.00860 15.1 2.91 0.84 0.99 1.00 14.0 3.47 0.88 1.00 1.00 12.9 4.15 0.93 1.00 1.00 11.5 5.00 0.99 1.00 1.00

19°C575 14.7 2.89 0.60 0.72 0.84 13.6 3.45 0.62 0.74 0.87 12.4 4.12 0.64 0.78 0.92 10.9 4.97 0.67 0.83 0.98715 15.4 2.93 0.63 0.77 0.90 14.2 3.48 0.65 0.80 0.94 12.9 4.16 0.68 0.84 0.99 11.3 5.00 0.72 0.91 1.00860 15.9 2.95 0.66 0.81 0.96 14.7 3.50 0.68 0.85 1.00 13.3 4.18 0.72 0.91 1.00 11.6 5.01 0.77 0.97 1.00

22°C575 15.5 2.93 0.47 0.58 0.70 14.4 3.49 0.47 0.60 0.72 13.1 4.17 0.48 0.62 0.75 11.6 5.01 0.50 0.66 0.80715 16.2 2.97 0.48 0.62 0.75 15.0 3.52 0.49 0.64 0.78 13.7 4.20 0.50 0.67 0.82 12.0 5.03 0.52 0.71 0.88860 16.8 2.99 0.50 0.65 0.79 15.5 3.55 0.51 0.67 0.83 14.0 4.22 0.53 0.71 0.88 12.3 5.06 0.55 0.76 0.95

EXPANDED RATINGS - SINGLE PHASE MODELSNOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

TSA048S4 Cooling Capacity with CX34-44/48C-6F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C660 14.0 2.86 0.75 0.88 1.00 12.9 3.41 0.77 0.92 1.00 11.8 4.09 0.81 0.96 1.00 10.4 4.93 0.86 1.00 1.00755 14.4 2.88 0.78 0.92 1.00 13.3 3.43 0.81 0.96 1.00 12.0 4.11 0.85 1.00 1.00 10.8 4.96 0.91 1.00 1.00850 14.7 2.89 0.80 0.95 1.00 13.6 3.44 0.84 0.99 1.00 12.4 4.13 0.88 1.00 1.00 11.1 4.98 0.94 1.00 1.00

19°C660 14.8 2.90 0.60 0.73 0.85 13.7 3.45 0.61 0.75 0.88 12.5 4.13 0.64 0.79 0.93 11.0 4.97 0.67 0.84 0.99755 15.2 2.92 0.62 0.75 0.89 14.1 3.47 0.63 0.78 0.93 12.7 4.15 0.66 0.82 0.97 11.2 4.99 0.70 0.88 1.00850 15.5 2.93 0.63 0.78 0.92 14.3 3.49 0.65 0.81 0.96 13.0 4.16 0.68 0.86 1.00 11.3 4.99 0.72 0.92 1.00

22°C660 15.6 2.94 0.47 0.58 0.70 14.5 3.49 0.47 0.60 0.73 13.2 4.17 0.48 0.62 0.76 11.6 5.02 0.50 0.66 0.81755 16.0 2.96 0.47 0.60 0.73 14.8 3.51 0.48 0.62 0.76 13.5 4.19 0.49 0.65 0.80 11.9 5.03 0.51 0.68 0.86850 16.4 2.97 0.48 0.62 0.76 15.2 3.53 0.49 0.64 0.79 13.7 4.21 0.50 0.67 0.83 12.0 5.04 0.52 0.71 0.90

TSA048S4 Cooling Capacity with CR33-48C-F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C660 13.8 2.85 0.76 0.89 1.00 12.8 3.41 0.78 0.93 1.00 11.6 4.09 0.82 0.97 1.00 10.3 4.93 0.87 1.00 1.00755 14.1 2.87 0.78 0.92 1.00 13.1 3.42 0.81 0.96 1.00 11.9 4.10 0.85 1.00 1.00 10.7 4.95 0.91 1.00 1.00850 14.4 2.88 0.81 0.96 1.00 13.3 3.43 0.84 0.99 1.00 12.3 4.12 0.89 1.00 1.00 11.0 4.97 0.95 1.00 1.00

19°C660 14.6 2.89 0.61 0.73 0.86 13.5 3.44 0.62 0.76 0.89 12.3 4.12 0.65 0.79 0.94 10.9 4.97 0.68 0.85 0.99755 14.9 2.90 0.63 0.76 0.89 13.8 3.46 0.64 0.79 0.93 12.6 4.14 0.67 0.83 0.98 11.1 4.98 0.70 0.89 1.00850 15.2 2.92 0.64 0.78 0.93 14.1 3.47 0.66 0.82 0.97 12.8 4.15 0.69 0.86 1.00 11.3 4.99 0.73 0.93 1.00

22°C660 15.3 2.92 0.46 0.59 0.71 14.2 3.48 0.47 0.61 0.74 13.0 4.16 0.48 0.63 0.77 11.5 5.01 0.50 0.67 0.82755 15.7 2.94 0.47 0.61 0.74 14.6 3.50 0.48 0.63 0.76 13.3 4.18 0.50 0.66 0.80 11.7 5.02 0.51 0.69 0.86850 16.0 2.96 0.48 0.63 0.76 14.9 3.51 0.49 0.65 0.79 13.5 4.19 0.50 0.68 0.84 11.9 5.02 0.53 0.72 0.91

TSA048S4 Cooling Capacity with CH33-48C-2F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C660 14.2 2.87 0.76 0.89 1.00 13.1 3.42 0.78 0.93 1.00 11.9 4.10 0.82 0.97 1.00 10.6 4.94 0.87 1.00 1.00755 14.6 2.89 0.78 0.93 1.00 13.5 3.44 0.81 0.97 1.00 12.2 4.12 0.85 1.00 1.00 11.0 4.97 0.92 1.00 1.00850 14.9 2.90 0.81 0.96 1.00 13.8 3.46 0.84 1.00 1.00 12.6 4.14 0.89 1.00 1.00 11.3 4.99 0.96 1.00 1.00

19°C660 15.0 2.91 0.60 0.73 0.86 13.9 3.46 0.62 0.76 0.89 12.6 4.14 0.64 0.79 0.94 11.1 4.98 0.67 0.85 1.00755 15.4 2.93 0.62 0.76 0.89 14.3 3.48 0.64 0.79 0.94 12.9 4.16 0.66 0.83 0.98 11.4 5.00 0.70 0.89 1.00850 15.8 2.94 0.64 0.79 0.93 14.5 3.50 0.66 0.82 0.97 13.2 4.17 0.69 0.87 1.00 11.5 5.00 0.73 0.93 1.00

22°C660 15.8 2.95 0.47 0.59 0.71 14.7 3.50 0.47 0.60 0.73 13.4 4.18 0.48 0.63 0.77 11.8 5.03 0.50 0.66 0.82755 16.2 2.97 0.47 0.60 0.74 15.0 3.52 0.48 0.62 0.76 13.7 4.20 0.49 0.65 0.81 12.0 5.04 0.51 0.69 0.86850 16.6 2.98 0.48 0.62 0.76 15.4 3.54 0.49 0.65 0.80 13.9 4.22 0.51 0.67 0.84 12.2 5.06 0.53 0.72 0.91

Page 15: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

50 hz T-Class Air Conditioners 7 to 17.6 kW / Page 15

TSA060S4 Cooling Capacity with BCRMD1960S005Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C640 15.3 3.00 0.75 0.87 0.99 14.2 3.60 0.77 0.91 1.00 12.8 4.32 0.81 0.95 1.00 11.4 5.22 0.86 1.00 1.00800 16.1 3.04 0.80 0.94 1.00 14.8 3.63 0.83 0.98 1.00 13.6 4.36 0.88 1.00 1.00 12.2 5.26 0.94 1.00 1.00960 16.7 3.06 0.85 1.00 1.00 15.6 3.67 0.89 1.00 1.00 14.3 4.40 0.94 1.00 1.00 12.8 5.29 1.00 1.00 1.00

19°C640 16.3 3.04 0.60 0.72 0.84 15.1 3.64 0.62 0.75 0.88 13.7 4.36 0.64 0.78 0.92 12.0 5.25 0.67 0.83 0.98800 17.1 3.08 0.63 0.77 0.91 15.8 3.68 0.65 0.81 0.95 14.2 4.40 0.68 0.85 0.99 12.5 5.28 0.72 0.91 1.00960 17.7 3.11 0.67 0.83 0.98 16.2 3.70 0.69 0.87 1.00 14.7 4.42 0.73 0.92 1.00 12.9 5.30 0.78 0.98 1.00

22°C640 17.2 3.09 0.47 0.59 0.70 16.0 3.69 0.48 0.60 0.72 14.5 4.41 0.48 0.62 0.76 12.8 5.29 0.50 0.65 0.81800 18.1 3.13 0.48 0.62 0.75 16.7 3.73 0.49 0.64 0.78 15.2 4.45 0.51 0.67 0.83 13.4 5.33 0.53 0.71 0.89960 18.8 3.16 0.50 0.65 0.81 17.3 3.76 0.51 0.68 0.85 15.6 4.47 0.53 0.72 0.90 13.7 5.35 0.55 0.77 0.96

EXPANDED RATINGS - SINGLE PHASE MODELSNOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

TSA060S4 Cooling Capacity with CX34-62D-6F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C660 15.4 3.00 0.75 0.88 1.00 14.2 3.60 0.77 0.91 1.00 12.9 4.33 0.81 0.96 1.00 11.5 5.21 0.86 1.00 1.00755 15.9 3.02 0.77 0.92 1.00 14.6 3.62 0.80 0.96 1.00 13.3 4.35 0.84 1.00 1.00 11.9 5.24 0.90 1.00 1.00850 16.2 3.04 0.80 0.95 1.00 15.0 3.64 0.84 0.99 1.00 13.7 4.37 0.88 1.00 1.00 12.3 5.27 0.95 1.00 1.00

19°C660 16.2 3.04 0.60 0.72 0.84 15.0 3.64 0.61 0.75 0.88 13.7 4.37 0.64 0.78 0.93 12.1 5.25 0.67 0.83 0.99755 16.6 3.06 0.61 0.75 0.88 15.4 3.66 0.63 0.78 0.92 14.0 4.39 0.66 0.82 0.97 12.4 5.27 0.69 0.88 1.00850 17.1 3.08 0.63 0.78 0.92 15.8 3.68 0.65 0.81 0.96 14.3 4.40 0.68 0.86 1.00 12.6 5.28 0.72 0.92 1.00

22°C660 17.1 3.08 0.46 0.58 0.70 15.9 3.69 0.47 0.60 0.72 14.5 4.41 0.48 0.62 0.76 12.8 5.30 0.49 0.65 0.81755 17.6 3.11 0.47 0.60 0.73 16.3 3.71 0.48 0.62 0.76 14.9 4.43 0.49 0.65 0.80 13.1 5.31 0.51 0.68 0.85850 18.1 3.13 0.48 0.62 0.75 16.7 3.73 0.49 0.64 0.79 15.1 4.45 0.50 0.67 0.83 13.3 5.33 0.52 0.71 0.90

TSA060S4 Cooling Capacity with CR33-60D-F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C660 15.1 2.99 0.75 0.89 1.00 14.0 3.59 0.78 0.92 1.00 12.7 4.32 0.81 0.97 1.00 11.3 5.21 0.87 1.00 1.00755 15.5 3.01 0.78 0.93 1.00 14.4 3.61 0.81 0.96 1.00 13.0 4.33 0.85 1.00 1.00 11.7 5.23 0.91 1.00 1.00850 15.9 3.02 0.81 0.96 1.00 14.7 3.62 0.84 0.99 1.00 13.4 4.35 0.89 1.00 1.00 12.1 5.25 0.95 1.00 1.00

19°C660 16.0 3.03 0.60 0.73 0.85 14.8 3.63 0.62 0.76 0.89 13.5 4.36 0.64 0.79 0.94 11.9 5.24 0.67 0.84 0.99755 16.4 3.05 0.62 0.76 0.89 15.2 3.65 0.64 0.79 0.93 13.8 4.38 0.66 0.83 0.98 12.2 5.26 0.70 0.89 1.00850 16.8 3.06 0.64 0.79 0.93 15.5 3.67 0.66 0.82 0.97 14.0 4.39 0.69 0.87 1.00 12.4 5.28 0.73 0.93 1.00

22°C660 16.8 3.07 0.46 0.59 0.71 15.6 3.67 0.47 0.60 0.73 14.2 4.40 0.48 0.63 0.77 12.6 5.28 0.49 0.66 0.82755 17.2 3.09 0.47 0.61 0.74 16.0 3.69 0.48 0.63 0.76 14.6 4.42 0.49 0.65 0.80 12.9 5.30 0.51 0.69 0.86850 17.6 3.11 0.48 0.63 0.76 16.4 3.71 0.49 0.65 0.80 14.8 4.43 0.50 0.68 0.84 13.1 5.31 0.52 0.72 0.91

TSA060S4 Cooling Capacity with CH33-60D-2F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C660 15.1 2.99 0.74 0.87 0.99 14.0 3.59 0.76 0.90 1.00 12.7 4.31 0.80 0.95 1.00 11.2 5.20 0.85 1.00 1.00755 15.5 3.01 0.77 0.91 1.00 14.4 3.61 0.79 0.94 1.00 13.0 4.33 0.83 0.99 1.00 11.7 5.23 0.89 1.00 1.00850 15.9 3.03 0.79 0.94 1.00 14.7 3.63 0.82 0.98 1.00 13.4 4.35 0.87 1.00 1.00 12.0 5.25 0.93 1.00 1.00

19°C660 16.0 3.03 0.59 0.72 0.83 14.8 3.63 0.61 0.74 0.87 13.5 4.36 0.63 0.77 0.91 11.9 5.24 0.66 0.82 0.98755 16.5 3.05 0.61 0.74 0.87 15.2 3.65 0.63 0.77 0.91 13.8 4.37 0.65 0.81 0.96 12.2 5.27 0.68 0.86 1.00850 16.9 3.07 0.63 0.77 0.91 15.6 3.67 0.64 0.80 0.95 14.1 4.39 0.67 0.84 1.00 12.4 5.27 0.71 0.90 1.00

22°C660 16.9 3.07 0.46 0.58 0.69 15.6 3.67 0.47 0.59 0.71 14.2 4.40 0.48 0.61 0.75 12.7 5.29 0.49 0.64 0.80755 17.4 3.09 0.47 0.59 0.72 16.1 3.69 0.48 0.61 0.75 14.6 4.42 0.49 0.64 0.78 12.9 5.30 0.50 0.67 0.84850 17.8 3.11 0.48 0.61 0.74 16.4 3.72 0.48 0.63 0.78 14.9 4.44 0.50 0.66 0.82 13.1 5.31 0.51 0.70 0.88

Page 16: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

50 hz T-Class Air Conditioners 7 to 17.6 kW / Page 16

TSA036S4 Cooling Capacity with BCRMB9937S005 Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C455 9.9 2.02 0.75 0.88 0.99 9.1 2.45 0.77 0.91 1.00 8.4 2.97 0.80 0.95 1.00 7.5 3.63 0.84 0.99 1.00570 10.3 2.04 0.80 0.95 1.00 9.6 2.46 0.83 0.98 1.00 8.8 2.99 0.86 1.00 1.00 7.9 3.65 0.91 1.00 1.00685 10.7 2.05 0.84 0.99 1.00 10.0 2.48 0.88 1.00 1.00 9.2 3.01 0.92 1.00 1.00 8.3 3.66 0.97 1.00 1.00

19°C455 10.4 2.04 0.61 0.73 0.85 9.7 2.47 0.62 0.75 0.88 8.9 2.99 0.64 0.78 0.92 7.9 3.64 0.67 0.82 0.97570 10.9 2.05 0.64 0.78 0.92 10.1 2.48 0.66 0.81 0.95 9.1 3.01 0.68 0.84 0.99 8.1 3.65 0.71 0.89 1.00685 11.2 2.06 0.67 0.83 0.97 10.3 2.49 0.69 0.86 1.00 9.3 3.01 0.71 0.90 1.00 8.3 3.66 0.75 0.96 1.00

22°C455 11.0 2.06 0.48 0.60 0.71 10.2 2.49 0.48 0.61 0.73 9.3 3.01 0.50 0.63 0.76 8.3 3.66 0.51 0.66 0.80570 11.4 2.07 0.50 0.63 0.76 10.6 2.50 0.50 0.65 0.79 9.6 3.03 0.52 0.67 0.82 8.5 3.68 0.53 0.70 0.88685 11.8 2.08 0.51 0.66 0.81 10.8 2.51 0.52 0.68 0.84 9.8 3.03 0.53 0.71 0.88 8.7 3.69 0.55 0.75 0.94

EXPANDED RATINGS - three PHASE MODELSNOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

TSA036S4 Cooling Capacity with CX34-36B/C-6F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C470 9.8 2.02 0.77 0.90 1.00 9.1 2.45 0.79 0.93 1.00 8.4 2.97 0.82 0.97 1.00 7.5 3.62 0.87 1.00 1.00565 10.2 2.03 0.80 0.95 1.00 9.5 2.46 0.83 0.98 1.00 8.7 2.99 0.87 1.00 1.00 8.0 3.65 1.00 1.00 1.00660 10.5 2.04 0.84 0.99 1.00 9.8 2.47 0.88 1.00 1.00 9.0 3.00 0.92 1.00 1.00 8.0 3.65 1.00 1.00 1.00

19°C470 10.3 2.04 0.62 0.74 0.87 9.6 2.46 0.63 0.77 0.90 8.7 2.99 0.65 0.80 0.94 8.3 3.66 0.97 1.00 1.00565 10.6 2.05 0.64 0.78 0.92 9.8 2.47 0.65 0.81 0.96 9.0 3.00 0.68 0.85 0.99 7.9 3.64 0.67 0.82 0.97660 10.9 2.06 0.66 0.82 0.97 10.1 2.48 0.68 0.86 1.00 9.2 3.01 0.71 0.90 1.00 8.1 3.65 0.71 0.89 1.00

22°C470 10.7 2.05 0.48 0.60 0.72 9.9 2.48 0.48 0.62 0.75 9.1 3.00 0.49 0.64 0.78 8.3 3.66 0.75 0.96 1.00565 11.1 2.06 0.49 0.63 0.76 10.3 2.49 0.49 0.64 0.79 9.4 3.02 0.51 0.67 0.83 8.3 3.66 0.51 0.66 0.80660 11.4 2.07 0.50 0.65 0.80 10.6 2.50 0.51 0.68 0.84 9.6 3.02 0.53 0.70 0.88 8.5 3.68 0.53 0.70 0.88

TSA036S4 Cooling Capacity with CR33-30/36B-F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C470 9.9 2.02 0.77 0.90 1.00 9.2 2.45 0.79 0.93 1.00 8.5 2.97 0.82 0.97 1.00 7.6 3.63 0.87 1.00 1.00565 10.3 2.04 0.81 0.95 1.00 9.6 2.46 0.83 0.98 1.00 8.7 2.99 0.87 1.00 1.00 8.0 3.66 1.00 1.00 1.00660 10.6 2.04 0.85 0.99 1.00 9.8 2.47 0.88 1.00 1.00 9.1 3.00 0.92 1.00 1.00 8.0 3.66 1.00 1.00 1.00

19°C470 10.5 2.04 0.61 0.74 0.87 9.7 2.47 0.63 0.77 0.90 8.9 2.99 0.65 0.80 0.95 8.3 3.66 0.97 1.00 1.00565 10.8 2.05 0.64 0.78 0.92 10.0 2.48 0.65 0.81 0.96 9.1 3.01 0.68 0.85 1.00 7.9 3.64 0.67 0.82 0.97660 11.0 2.06 0.67 0.83 0.97 10.2 2.49 0.69 0.86 1.00 9.3 3.01 0.72 0.90 1.00 8.1 3.65 0.71 0.89 1.00

22°C470 11.0 2.06 0.47 0.60 0.72 10.2 2.49 0.48 0.62 0.75 9.3 3.01 0.49 0.64 0.78 8.3 3.66 0.75 0.96 1.00565 11.3 2.07 0.48 0.62 0.76 10.5 2.50 0.49 0.64 0.79 9.6 3.03 0.50 0.67 0.83 8.3 3.66 0.51 0.66 0.80660 11.6 2.08 0.50 0.66 0.81 10.7 2.50 0.51 0.68 0.84 9.7 3.03 0.52 0.71 0.89 8.5 3.68 0.53 0.70 0.88

TSA036S4 Cooling Capacity with CH33-36B-2F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C470 9.8 2.02 0.76 0.90 1.00 9.1 2.45 0.79 0.93 1.00 8.4 2.97 0.82 0.97 1.00 7.5 3.62 0.86 1.00 1.00565 10.1 2.03 0.80 0.95 1.00 9.4 2.46 0.83 0.98 1.00 8.6 2.99 0.86 1.00 1.00 7.9 3.65 1.00 1.00 1.00660 10.5 2.04 0.84 0.99 1.00 9.7 2.47 0.87 1.00 1.00 9.0 3.00 0.91 1.00 1.00 7.9 3.65 1.00 1.00 1.00

19°C470 10.3 2.04 0.61 0.74 0.87 9.5 2.46 0.63 0.77 0.90 8.7 2.99 0.65 0.80 0.94 8.3 3.66 0.97 1.00 1.00565 10.6 2.05 0.63 0.78 0.92 9.8 2.48 0.65 0.81 0.95 9.0 3.00 0.68 0.84 0.99 7.9 3.64 0.67 0.82 0.97660 10.9 2.06 0.66 0.82 0.97 10.1 2.48 0.68 0.85 1.00 9.2 3.01 0.71 0.89 1.00 8.1 3.65 0.71 0.89 1.00

22°C470 10.7 2.05 0.48 0.60 0.72 9.9 2.48 0.48 0.62 0.74 9.1 3.00 0.49 0.64 0.78 8.3 3.66 0.75 0.96 1.00565 11.0 2.06 0.48 0.62 0.76 10.3 2.49 0.49 0.64 0.79 9.4 3.02 0.51 0.67 0.82 8.3 3.66 0.51 0.66 0.80660 11.4 2.07 0.50 0.65 0.80 10.6 2.50 0.51 0.67 0.83 9.6 3.03 0.52 0.70 0.87 8.5 3.68 0.53 0.70 0.88

Page 17: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

TSA048S4 Cooling Capacity with BCRMC9960S005 Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C575 13.8 2.71 0.75 0.87 0.99 12.7 3.33 0.77 0.91 1.00 11.6 4.02 0.80 0.95 1.00 10.2 4.78 0.86 1.00 1.00715 14.5 2.74 0.79 0.94 1.00 13.4 3.35 0.82 0.98 1.00 12.2 4.05 0.87 1.00 1.00 10.9 4.81 0.94 1.00 1.00860 15.0 2.76 0.84 0.99 1.00 14.0 3.37 0.88 1.00 1.00 12.8 4.07 0.93 1.00 1.00 11.5 4.83 0.99 1.00 1.00

19°C575 14.6 2.74 0.60 0.72 0.84 13.5 3.36 0.62 0.75 0.87 12.3 4.05 0.64 0.78 0.92 10.8 4.81 0.67 0.83 0.98715 15.3 2.77 0.63 0.77 0.90 14.2 3.38 0.65 0.80 0.95 12.9 4.07 0.68 0.84 0.99 11.3 4.83 0.72 0.91 1.00860 15.8 2.78 0.66 0.82 0.97 14.6 3.39 0.69 0.86 1.00 13.2 4.09 0.72 0.91 1.00 11.5 4.84 0.77 0.98 1.00

22°C575 15.4 2.77 0.47 0.59 0.70 14.3 3.38 0.47 0.60 0.72 13.0 4.08 0.48 0.62 0.75 11.5 4.84 0.50 0.66 0.81715 16.1 2.80 0.49 0.62 0.75 14.9 3.40 0.49 0.64 0.78 13.6 4.10 0.50 0.67 0.82 12.0 4.85 0.52 0.71 0.88860 16.7 2.82 0.50 0.65 0.80 15.4 3.42 0.51 0.68 0.83 14.0 4.11 0.53 0.71 0.88 12.3 4.87 0.55 0.76 0.95

EXPANDED RATINGS - three PHASE MODELSNOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

TSA048S4 Cooling Capacity with CX34-44/48C-6FEntering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C660 14.0 2.72 0.75 0.88 1.00 12.9 3.33 0.78 0.92 1.00 11.7 4.03 0.81 0.97 1.00 10.3 4.79 0.87 1.00 1.00755 14.3 2.73 0.78 0.92 1.00 13.2 3.34 0.81 0.96 1.00 12.0 4.04 0.85 1.00 1.00 10.7 4.80 0.91 1.00 1.00850 14.7 2.74 0.80 0.95 1.00 13.5 3.35 0.84 0.99 1.00 12.3 4.05 0.88 1.00 1.00 11.0 4.82 0.95 1.00 1.00

19°C660 14.7 2.75 0.60 0.73 0.85 13.7 3.36 0.62 0.75 0.89 12.4 4.06 0.64 0.79 0.93 10.9 4.81 0.67 0.84 0.99755 15.2 2.76 0.62 0.76 0.89 14.0 3.37 0.64 0.78 0.93 12.7 4.07 0.66 0.82 0.98 11.2 4.82 0.70 0.88 1.00850 15.4 2.77 0.63 0.78 0.92 14.2 3.38 0.66 0.81 0.96 13.0 4.08 0.68 0.86 1.00 11.3 4.83 0.72 0.93 1.00

22°C660 15.5 2.77 0.47 0.59 0.71 14.4 3.38 0.47 0.60 0.73 13.2 4.08 0.48 0.62 0.76 11.6 4.84 0.50 0.66 0.82755 15.9 2.79 0.47 0.60 0.73 14.7 3.40 0.48 0.62 0.76 13.4 4.09 0.49 0.65 0.80 11.9 4.85 0.51 0.69 0.86850 16.2 2.80 0.48 0.62 0.76 15.0 3.41 0.49 0.64 0.79 13.7 4.10 0.50 0.67 0.83 12.0 4.85 0.52 0.71 0.90

TSA048S4 Cooling Capacity with CR33-48C-F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C660 13.7 2.71 0.76 0.89 1.00 12.7 3.33 0.78 0.93 1.00 11.6 4.03 0.82 0.97 1.00 10.2 4.78 0.88 1.00 1.00755 14.1 2.72 0.78 0.93 1.00 13.0 3.34 0.81 0.97 1.00 11.9 4.04 0.85 1.00 1.00 10.6 4.80 0.92 1.00 1.00850 14.4 2.73 0.81 0.96 1.00 13.3 3.35 0.84 0.99 1.00 12.2 4.05 0.89 1.00 1.00 10.9 4.82 0.96 1.00 1.00

19°C660 14.5 2.74 0.61 0.73 0.86 13.5 3.35 0.62 0.76 0.89 12.3 4.05 0.65 0.80 0.94 10.8 4.81 0.68 0.85 1.00755 14.8 2.75 0.63 0.76 0.89 13.8 3.36 0.64 0.79 0.93 12.6 4.06 0.67 0.83 0.98 11.0 4.82 0.71 0.89 1.00850 15.2 2.76 0.64 0.79 0.93 14.0 3.37 0.66 0.82 0.97 12.8 4.07 0.69 0.86 1.00 11.2 4.82 0.73 0.93 1.00

22°C660 15.2 2.76 0.46 0.59 0.71 14.2 3.38 0.47 0.61 0.74 13.0 4.07 0.48 0.63 0.77 11.5 4.84 0.50 0.67 0.82755 15.6 2.78 0.47 0.61 0.74 14.5 3.39 0.48 0.63 0.77 13.2 4.09 0.50 0.66 0.81 11.7 4.84 0.51 0.69 0.87850 15.9 2.79 0.49 0.63 0.76 14.8 3.40 0.49 0.65 0.80 13.5 4.09 0.50 0.68 0.84 11.9 4.85 0.53 0.72 0.91

TSA048S4 Cooling Capacity with CH33-48C-2F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C660 14.2 2.73 0.76 0.89 1.00 13.1 3.34 0.78 0.93 1.00 11.9 4.03 0.82 0.98 1.00 10.5 4.79 0.88 1.00 1.00755 14.5 2.74 0.78 0.93 1.00 13.4 3.35 0.82 0.97 1.00 12.2 4.05 0.86 1.00 1.00 10.9 4.81 0.92 1.00 1.00850 14.9 2.75 0.81 0.97 1.00 13.7 3.36 0.85 1.00 1.00 12.5 4.06 0.89 1.00 1.00 11.2 4.83 0.96 1.00 1.00

19°C660 15.0 2.75 0.60 0.73 0.86 13.9 3.37 0.62 0.76 0.89 12.6 4.06 0.64 0.79 0.94 11.0 4.82 0.68 0.85 1.00755 15.3 2.77 0.62 0.76 0.90 14.2 3.38 0.64 0.79 0.94 12.9 4.07 0.66 0.83 0.99 11.3 4.83 0.70 0.89 1.00850 15.6 2.78 0.64 0.79 0.94 14.4 3.39 0.66 0.82 0.98 13.1 4.08 0.69 0.87 1.00 11.5 4.83 0.73 0.94 1.00

22°C660 15.7 2.78 0.47 0.59 0.71 14.6 3.39 0.47 0.60 0.73 13.3 4.09 0.48 0.63 0.77 11.8 4.85 0.50 0.66 0.82755 16.1 2.80 0.47 0.61 0.74 14.9 3.40 0.48 0.63 0.77 13.6 4.10 0.49 0.65 0.81 12.0 4.86 0.51 0.69 0.87850 16.5 2.81 0.48 0.63 0.77 15.2 3.41 0.49 0.65 0.80 13.9 4.11 0.51 0.68 0.84 12.2 4.87 0.53 0.72 0.91

Page 18: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

TSA060S4 Cooling Capacity with BCRMD1960S005 Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C640 17.3 3.86 0.71 0.83 0.94 16.1 4.58 0.73 0.86 0.97 14.7 5.44 0.76 0.90 1.00 13.0 6.44 0.80 0.95 1.00800 18.3 3.92 0.76 0.89 1.00 16.9 4.64 0.78 0.92 1.00 15.4 5.50 0.82 0.97 1.00 13.7 6.51 0.87 1.00 1.00960 19.0 3.96 0.80 0.95 1.00 17.6 4.69 0.83 0.98 1.00 16.1 5.55 0.88 1.00 1.00 14.4 6.57 0.94 1.00 1.00

19°C640 18.4 3.92 0.58 0.69 0.80 17.1 4.65 0.59 0.71 0.82 15.6 5.51 0.61 0.74 0.86 13.7 6.51 0.64 0.78 0.92800 19.4 3.99 0.61 0.73 0.86 17.9 4.71 0.62 0.76 0.89 16.2 5.57 0.65 0.80 0.94 14.4 6.56 0.68 0.85 0.99960 20.1 4.03 0.64 0.78 0.92 18.6 4.76 0.66 0.81 0.96 16.8 5.61 0.68 0.86 1.00 14.8 6.61 0.72 0.92 1.00

22°C640 19.4 3.99 0.46 0.56 0.66 18.1 4.72 0.46 0.58 0.69 16.5 5.59 0.47 0.59 0.71 14.6 6.58 0.48 0.62 0.76800 20.5 4.05 0.47 0.59 0.71 19.0 4.78 0.48 0.61 0.74 17.2 5.64 0.49 0.63 0.77 15.2 6.64 0.51 0.67 0.83960 21.2 4.10 0.49 0.62 0.76 19.6 4.83 0.49 0.64 0.79 17.8 5.69 0.51 0.67 0.84 15.6 6.69 0.53 0.72 0.90

EXPANDED RATINGS - three PHASE MODELSNOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

TSA060S4 Cooling Capacity with CX34-62D-6FEntering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C660 17.4 3.86 0.72 0.83 0.94 16.2 4.59 0.73 0.86 0.98 14.7 5.44 0.77 0.90 1.00 13.1 6.45 0.80 0.96 1.00755 18.0 3.90 0.74 0.86 0.98 16.7 4.62 0.76 0.90 1.00 15.2 5.48 0.79 0.94 1.00 13.5 6.49 0.84 1.00 1.00850 18.4 3.92 0.76 0.90 1.00 17.1 4.65 0.79 0.93 1.00 15.6 5.51 0.82 0.98 1.00 13.9 6.53 0.88 1.00 1.00

19°C660 18.4 3.92 0.58 0.69 0.80 17.1 4.65 0.59 0.71 0.83 15.6 5.52 0.61 0.74 0.86 13.9 6.52 0.63 0.78 0.92755 18.9 3.96 0.59 0.71 0.83 17.6 4.69 0.61 0.74 0.86 16.0 5.55 0.62 0.77 0.91 14.2 6.55 0.66 0.82 0.97850 19.4 3.99 0.61 0.74 0.86 18.0 4.71 0.62 0.76 0.90 16.4 5.58 0.65 0.80 0.95 14.4 6.57 0.68 0.85 1.00

22°C660 19.3 3.98 0.45 0.56 0.67 18.0 4.72 0.46 0.57 0.69 16.4 5.58 0.47 0.59 0.72 14.6 6.59 0.48 0.62 0.75755 20.0 4.02 0.46 0.58 0.69 18.5 4.75 0.47 0.59 0.71 16.9 5.62 0.47 0.61 0.75 15.0 6.63 0.49 0.64 0.79850 20.4 4.05 0.47 0.59 0.72 18.9 4.78 0.47 0.61 0.74 17.2 5.65 0.48 0.63 0.78 15.3 6.65 0.50 0.67 0.83

TSA060S4 Cooling Capacity with CR33-60D-F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C660 17.1 3.84 0.72 0.84 0.95 15.9 4.56 0.74 0.87 0.98 14.4 5.43 0.77 0.91 1.00 12.7 6.42 0.81 0.97 1.00755 17.6 3.87 0.74 0.87 0.99 16.3 4.60 0.77 0.91 1.00 14.8 5.45 0.80 0.95 1.00 13.1 6.45 0.85 0.99 1.00850 18.0 3.90 0.77 0.91 1.00 16.7 4.62 0.80 0.94 1.00 15.2 5.48 0.83 0.98 1.00 13.5 6.49 0.89 1.00 1.00

19°C660 18.0 3.90 0.58 0.70 0.81 16.7 4.63 0.59 0.72 0.84 15.3 5.49 0.61 0.75 0.88 13.5 6.49 0.64 0.79 0.93755 18.5 3.93 0.60 0.72 0.84 17.2 4.66 0.61 0.75 0.87 15.6 5.52 0.63 0.78 0.92 13.8 6.52 0.66 0.83 0.98850 18.9 3.96 0.61 0.75 0.88 17.6 4.69 0.63 0.77 0.91 16.0 5.55 0.65 0.81 0.96 14.1 6.54 0.69 0.87 1.00

22°C660 18.9 3.96 0.45 0.56 0.67 17.6 4.68 0.46 0.58 0.69 16.0 5.55 0.47 0.60 0.72 14.3 6.56 0.48 0.63 0.76755 19.4 3.98 0.46 0.58 0.70 18.1 4.72 0.46 0.60 0.72 16.5 5.59 0.48 0.62 0.76 14.6 6.59 0.49 0.65 0.80850 19.9 4.02 0.47 0.60 0.73 18.5 4.75 0.47 0.62 0.75 16.8 5.61 0.48 0.64 0.79 14.9 6.61 0.50 0.68 0.84

TSA060S4 Cooling Capacity with CH33-60D-2F Entering

Wet Bulb

Temper-ature

Total Air

Volume

Outdoor Air Temperature Entering Outdoor Coil27°C 35°C 43°C 52°C

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Total Cool Cap.

Comp. Motor Input

Sensible To Total Ratio (S/T)

Dry Bulb Dry Bulb Dry Bulb Dry BulbL/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

17°C660 17.1 3.84 0.71 0.82 0.93 15.9 4.57 0.73 0.85 0.97 14.5 5.42 0.75 0.89 1.00 12.8 6.43 0.79 0.95 1.00755 17.6 3.87 0.73 0.85 0.97 16.4 4.60 0.75 0.88 1.00 14.9 5.46 0.78 0.93 1.00 13.2 6.46 0.83 0.99 1.00850 18.1 3.90 0.75 0.88 1.00 16.7 4.62 0.78 0.92 1.00 15.2 5.48 0.81 0.97 1.00 13.5 6.49 0.86 1.00 1.00

19°C660 18.1 3.90 0.58 0.68 0.79 16.8 4.63 0.59 0.70 0.82 15.4 5.50 0.60 0.73 0.85 13.6 6.50 0.63 0.77 0.91755 18.6 3.94 0.59 0.71 0.82 17.3 4.67 0.60 0.73 0.85 15.8 5.53 0.62 0.76 0.90 14.0 6.54 0.65 0.81 0.96850 19.1 3.97 0.60 0.73 0.85 17.7 4.69 0.62 0.75 0.89 16.1 5.55 0.64 0.79 0.94 14.2 6.55 0.67 0.84 1.00

22°C660 19.0 3.96 0.45 0.56 0.66 17.7 4.70 0.46 0.57 0.68 16.1 5.56 0.46 0.59 0.71 14.4 6.57 0.48 0.61 0.75755 19.6 4.00 0.46 0.57 0.68 18.2 4.73 0.46 0.59 0.70 16.6 5.60 0.47 0.61 0.73 14.7 6.60 0.49 0.64 0.78850 20.1 4.03 0.47 0.59 0.70 18.6 4.76 0.47 0.60 0.73 17.0 5.63 0.48 0.62 0.77 15.0 6.63 0.50 0.66 0.82

Page 19: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

50 hz T-Class Air Conditioners 7 to 17.6 kW / Page 19

Page 20: AIR CONDITIONERS TS - Prime Climate · AIR CONDITIONERS TS T-Class™ Split System Units ... marking certifies that a product has met EU ... (PSC) compressor motor.

NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. ©2010 Lennox Industries, Inc.

Visit us at www.lennox.com

For the latest technical information, www.lennoxcommercial.com

Contact us at 1−800−4−LENNOX

REVISIONS

SpecificationsUpdated electrical data on all except TSA024.Update refrigerant charge on TSA036

Ratings Corrected model numbers for air handlers.

Expanded ratings Updated all.