AHRI Standard 1240 I-P Add 1

download AHRI Standard 1240 I-P Add 1

of 17

Transcript of AHRI Standard 1240 I-P Add 1

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    1/17

     

    2014 Standard for

    Performance Rating of ActiveChilled Beams

    AHRI Standard 1240 (I-P) with Addendum 1 

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    2/17

     

    AHRI STANDARD 1240 (I-P)-2014 WITH ADDENDUM1, PERFORMANCE RATING OF ACTIVE CH ILLED

    BEAMS  

    September 2015

     Note: This addendum is not ANSI approved and is currently going through the process to become so.

    Addendum 1 (dated September 2015) of AHRI Standard 1240 (I-P)-2014, “Changes to AHRI Standard 1240 (I-P)-2014” is

     provided as follows. The following changes have been incorporated (deletions are shown by strikethroughs, additions are

    shown by shading) into the already published 2014 version of AHRI Standard 1240 (I-P) to avoid confusion.

    The changes include:

    1)  First paragraph of Section 3 was updated.

    All terms in this document will follow the standard industry definitions in the ASHRAE Wikipedia website

    (http://wiki.ashrae.org/index.php/ASHRAEwiki) Terminology website (https://www.ashrae.org/resources--

     publications/free-resources/ashrae-terminology), unless otherwise defined in this section.

    2)  Section 3.3 was updated.

    3.3 Octave Band . A band of sound covering a range of frequencies such that the highest is twice the lowest. The Octave

    Bands used in this standard are those defined in ANSI/ASA Standard S1.11.

    3)  CFM was updated to SCFM throughout document as the units for Primary Air. Example;

    7.1  Standard Ratings. Standard Ratings shall be established at the Standard Rating Conditions specified in Section 7.2

    and shall be expressed in terms of Btu per hour (Btu/h) rounded to the nearest 50 Btu/h and in terms of the flow of Primary

    Air in cubic feet per minute (scfm) rounded off to the nearest 2 scfm.

    4)  Sections 7.4.2 –  7.4.5 were updated.

    7.4.2 Water pressure drop shall be no greater than 105%110% of the rating or 1 foot of fluid above the rating,

    whichever is greater.

    7.4.3 Water coil capacity shall be within ±5% greater than or equal to 95% of the rating.

    7.4.4 Primary air flow rate shall be within ±5% less than or equal to 105% of the rating.

    7.4.5 Induced air flow rate shall be within ±10% greater than or equal to 90% of the rating.

    5)  Section 8.2 was updated to include two additional Primary Air pressure drops. Section 8.2.3 was moved to Section 8.2.6.

    Sections 8.2.3, 8.2.4 and 8.2.6 through 8.2.11 were moved under the newly created Sections 8.2.4, 8.2.5, and 8.2.6.

     Numbering of Section 8.2.5 was updated to 8.2.3.

    8.2 Standard Ratings.  Standard Ratings shall consist of at least the following information, obtained at Standard Rating

    Conditions:

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    3/17

     

    8.2.1  Primary air flow rate, scfm (Standard Air)

    8.2.2  Primary air temperature, 75°F - Isothermal to reference air temperature

    8.2.3  Primary Air pressure drop, 0.5 inches H2O

    8.2.4  Water coil capacity, reported, Btu/h

    8.2.53  Entering water temperature, cooling: 57°F

    8.2.6  Leaving water temperature, reported value °F

    8.2.7  Water flow rate, gpm, adjusted to achieve mean water temperature differential of 14.5°F relative to

    Reference Air Temperature

    8.2.8  Water pressure drop, reported, inches H2O

    8.2.9  Supply Air throw distance, 100 fpm with Supply Air at isothermal conditions relative to the test room to be

    determined using ANSI/ASHRAE Standard 70. Air volume to be at manufacturer supplied value for Primary Air.

    8.2.10  Sound generation (combined radiated and discharge sound) by Octave Bands 2 to 7. Air volume to be at

    manufacturer’s supplied value for Primary Air.  

    8.2.11  Induced air flow rate, cfm

    8.2.4  Minimum primary air pressure drop, reported value, rounded to 0.1 inches H2O. At this condition, also

    include the following information:

    8.2.4.1 Water coil capacity, reported, Btu/h

    8.2.4.2  Induced air flow rate, scfm

    8.2.4.3  Leaving water temperature, reported value, °F

    8.2.4.4  Water flow rate, gpm, adjusted to achieve mean water temperature differential of 14.5°F relative

    to reference air temperature

    8.2.4.5  Water pressure drop, reported, feet H2O

    8.2.4.6  Supply air throw distance, 100 fpm with Supply Air at isothermal conditions relative to the test

    room to be determined using ANSI/ASHRAE Standard 70. Air volume to be at manufacturer supplied

    value for Primary Air.8.2.4.7  Sound generation (combined radiated and discharge sound) by Octave Bands 2 to 7. Air volume to

     be at manufacturer’s supplied value for Primary Air.  

    8.2.5  Maximum primary air pressure drop, reported value, rounded to 0.1 inches H2O. At this condition, alsoinclude the following information:

    8.2.5.1 Water coil capacity, reported, Btu/h

    8.2.5.2  Induced air flow rate, scfm

    8.2.5.3  Leaving water temperature, reported value °F

    8.2.5.4  Water flow rate, gpm, adjusted to achieve mean water temperature differential of 14.5°F relative

    to reference air temperature

    8.2.5.5  Water pressure drop, reported, feet H2O 8.2.5.6  Supply air throw distance, 100 fpm with Supply Air at isothermal conditions relative to the test

    room to be determined using ANSI/ASHRAE Standard 70. Air volume to be at manufacturer supplied

    value for Primary Air.

    8.2.5.7  Sound generation (combined radiated and discharge sound) by Octave Bands 2 to 7. Air volume to

     be at manufacturer’s supplied value for Primary Air.  

    8.2.6  Primary Air pressure drop, 0.5 inches H2O. At this condition, also include the following information:

    8.2.6.1 Water coil capacity, reported, Btu/h

    8.2.6.2  Induced air flow rate, scfm

    8.2.6.3  Leaving water temperature, reported value °F

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    4/17

     8.2.6.4  Water flow rate, gpm, adjusted to achieve mean water temperature differential of 14.5°F relative

    to reference air temperature

    8.2.6.5  Water pressure drop, reported, feet H2O 8.2.6.6  Supply air throw distance, 100 fpm with Supply Air at isothermal conditions relative to the test

    room to be determined using ANSI/ASHRAE Standard 70. Air volume to be at manufacturer supplied

    value for Primary Air.

    8.2.6.7  Sound generation (combined radiated and discharge sound) by Octave Bands 2 to 7. Air volume to

     be at manufacturer’s supplied value for Primary Air.  

    6)  Added Normative Reference to ANSI/ASA Standard S1.11-2014 in Appendix A

    A1.4  ANSI/ASA Standard S1.11-2014 , Electroacoustics - Octave-band and Fractional-octave-band Filters - Part

    1: Specifications (a nationally adopted international standard , Acoustical Society of America, Suite 300, 1305 Walt

    Whitman Road, Melville, NY 11747-4300, U.S.A.

    7)  Updated Normative Reference for ASHRAE Terminology site in Appendix A

    A1.4 ASHRAEwiki, Terminology, http://wiki.ashrae.org/index.php/ASHRAEwiki,  2014, American Society of

    Heating, Refrigerating and Air-Conditioning Engineers, Inc., 1791 Tullie Circle, N.E., Atlanta, GA 30329, U.S.A. 

    A1.5 ASHRAE Terminology, https://www.ashrae.org/resources--publications/free-resources/ashrae-terminology,

    2014, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 1791 Tullie Circle, N.E.,

    Atlanta, GA 30329, U.S.A.

    8)  Added Appendix C –  Method of Testing Water Pressure Drop - Normative

    APPENDIX C. METHOD OF TESTING WATER PRESSUREDROP - NORMATIVE 

    C1.1 The temperatures and pressures of water entering and leaving the chilled beam shall be measured by the apparatus as

    illustrated in Figure C1. The connecting piping shall be the same size as the chilled beam supply and return connections.

    C1.2 Temperature measuring instruments shall be placed so as to measure the temperature of the water entering (t l1) andleaving (tl2) the coil. The liquid lines shall be insulated at and adjacent to the temperature measuring instruments. Suitable

    insulation having an R-value of 4.5 ft2•°F•hr/Btu or greater shall be applied from the unit  under test to at least 6 in. upstream

    of the inlet temperature sensor and 6 in. downstream of the outlet temperature sensor. Temperature sensor stems shall be

    insulated. To minimize possible temperature stratification, appropriate mixers, such as "static mixers," shall be inserted in the

    inlet and outlet liquid lines upstream from the temperature measuring instruments. Alternatively, two close-coupled 90°

    elbows just upstream of the temperature measuring instruments can serve as mixers provided that the water velocity at the

    mixing section is not below 1 ft/s.

    http://wiki.ashrae.org/index.php/ASHRAEwikihttp://wiki.ashrae.org/index.php/ASHRAEwiki

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    5/17

     

    Figure C1. Measuring Apparatus for Water Pressure Drop

    C1.3  Suitable means shall be provided for determining the liquid absolute pressure entering the coil (P l1) and the liquid

     pressure drop through the coil and measurement apparatus (Δplts) as shown in Figure C1. The piezometer rings shall be

    located and constructed in accordance with the dimensions shown in Figure C1. Pressure taps may be used in lieu of

     piezometer rings. The test setup measurement of pressure drop between piezometer rings or pressure taps shall be reduced by

    the pressure drop of the total length of pipe between the piezometer rings or pressure taps and the coil (Δp lma). The piping

    loss shall be determined by calibration of the measurement apparatus.

    The pressure drop in the test measurement apparatus, including any pipe between the coil and the measuring devices, at the

    test flow shall be calculated and subtracted from the measurement. This piping loss shall be determined by calibration of thetest apparatus or by calculation of pressure drop based on type of material used for the pipe.  

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    6/17

     Price $10.00 (M) $20.00 (NM) ©Copyright 2014, by Air-Conditioning, Heating, and Refrigeration InstitutePrinted in U.S.A. Registered United States Patent and Trademark Office 

    IMPORTANT

    SAFETY RECOMMENDATIONS  

    AHRI does not set safety standards and does not certify or guarantee the safety of any products, components or

    systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly

    recommended that products be designed, constructed, assembled, installed and operated in accordance with

    nationally recognized safety standards and code requirements appropriate for products covered by thisstandard/guideline.

    AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry

     practices. AHRI does not certify or guarantee that any tests conducted under its standards/guidelines will be

    non-hazardous or free from risk. 

     Note:

    This is a new standard.For SI ratings, see AHRI Standard 1241 (SI)-2014.

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    7/17

     

    TABLE OF CONTENTS 

    SECTION PAGE

    Section 1. Purpose ............................................................................................................................................................ 1

    Section 2. Scope ............................................................................................................................................................... 1

    Section 3. Definitions ....................................................................................................................................................... 1

    Section 4. Classifications ................................................................................................................................................. 2

    Section 5. Standard Equipment .......... .......... ........... .......... ........... .......... ........... .......... ........... .......... .......... ........... .......... . 3

    Section 6. Test Requirements ........... ........... .......... ........... .......... ........... .......... .......... ........... .......... ........... .......... ........... .. 3

    Section 7. Rating Requirements .......... ........... ........... .......... ........... .......... .......... ........... .......... .......... ........... ........... ......... 3

    Section 8. Minimum Data Requirements for Published Ratings .......... ........... .......... ........... .......... ........... .......... ........... .. 4

    Section 9. Marking and Nameplate Data ........... .......... ........... .......... .......... ........... .......... ........... .......... ........... .......... ...... 6

    Section 10. Conformance Conditions........ ........... .......... ........... .......... ........... .......... .......... ........... .......... ........... .......... ...... 6

    TABLES

    Table 1. Sound Power Level Rating Tolerances ........... .......... ........... .......... .......... ........... .......... ........... .......... ........... .. 4

    APPENDICES

    Appendix A. References –  Normative .................................................................................................................................. 7

    Appendix B. References –  Informative ................................................................................................................................ 7

    Appendix C. Method of Testing Water Pressure Drop - Normative .......... ........... .......... ........... .......... ........... .......... .......... . 9

    FIGURES FOR APPENDICES

    Figure C1. Measuring Apparatus for Water Pressure Drop ........... .......... ........... .......... .......... ........... .......... ........... ......... 9

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    8/17

      AHRI STANDARD 1240 (I-P)-2014

    1

    PERFORMANCE RATING OF ACTIVE CHILLED BEAMS

    Section 1. Purpose

    1.1   Purpose.  The purpose of this standard is to provide, for Active Chilled Beams: definitions; classifications; standard

    equipment; testing requirements; rating requirements; minimum data requirements for published ratings; marking and

    nameplate data; and conformance conditions.

    Section 2. Scope

    2.1 This standard applies to Active Chilled Beams as defined in Section 3, including Multi-service Active Chilled

    Beams and Room Air Induction Units.

    2.2  Exclusions. 

    2.2.1 This standard does not apply to Active Chilled Beams employing volatile-refrigerant coils, condensing coils,

    or steam coils.

    2.2.2 This standard does not apply to Passive Chilled Beams.

    Section 3. Definitions

    All terms in this document will follow the standard industry definitions in the ASHRAE Wikipedia website

    (http://wiki.ashrae.org/index.php/ASHRAEwiki) Terminology website (https://www.ashrae.org/resources--publications/free-

    resources/ashrae-terminology), unless otherwise defined in this section.

    3.1   Active Chilled Beam. An air induction and diffusion device which introduces conditioned air for the purposes of

    temperature and/or humidity control. Primary Air is delivered through a series of Nozzles, which induces and conditions

    Secondary Air through a unit mounted coil.

    3.1.1   Multi-service Active Chilled Beam. A chilled beam that incorporates space services other than cooling suchas lighting. This type of Active Chilled Beam is usually customized to meet specific project requirements.

    3.1.2   Room Air Induction Unit . A type of Active Chilled Beam that requires more than 1.5 in. H 2O of inlet static

     pressure to operate.

    3.2   Air-induction Process. The process by which a jet of Primary Air induces Secondary Air through the coil.

    3.2.1  Primary Air. Air delivered through the Nozzle(s) of an Active Chilled Beam.  

    3.2.2  Secondary Air. Air induced through coil of an Active Chilled Beam.

    3.2.3  Supply Air . Supply air is the mixture of Primary Air and Secondary Air that is discharged to the space by the

    Active Chilled Beam.

    3.2.4  Nozzle. An air flow opening in the Plenum which discharges a jet of Primary Air via the Air-induction

    Process.

    3.2.5  Plenum. An air compartment under positive pressure, and consisting of inlet(s) and Nozzle(s) for Primary Air.

    Also referred to as a Plenum chamber  

    3.2.6  Induction Ratio. The ratio of the volumetric flow rate of Secondary Air to Primary Air.

    3.2.7  Air Outlet and Inlet. Openings for the delivery or induction of air.

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    9/17

    AHRI STANDARD 1240 (I-P)-2014

    2

    3.2.7.1  Supply Air Outlet . An opening for the delivery of supply air from the Active Chilled Beam unit.

    3.2.7.2  Induced Air Inlet. An opening through which Secondary Air is induced into the Active Chilled

    Beam.

    3.2.8 Standard Air.  Air weighing 0.075 lb per cu ft., which approximates dry air at 70F and at a barometric

     pressure of 29.92 inches of mercury.

    3.2.9   Reference Air Temperature. Average air temperature of the induced air on the inlet side of the cooling coil(s),

    measured as prescribed in ANSI/ASHRAE Standard 200.

    3.3 Octave Band . A band of sound covering a range of frequencies such that the highest is twice the lowest. The Octave

    Bands used in this standard are those defined in ANSI/ASA Standard S1.11.

    3.4  Passive Chilled Beam.  A cooled element or coil, fixed in, above or under a ceiling that sensibly cools through

    natural convection using buoyancy driven air flow. The cooling media in the coil is water.

    3.5  Product Line. A family of units of common basic design, consisting of a set of Models, and a progression of Sizes.

    3.5.1  Model. The style or structure of the Active Chilled Beam relative to the configuration of coils, Nozzles, and

    Air Outlets and Inlets as typified by the discharge pattern common to all Sizes. A given Model may have different Nozzle arrangements, Air Outlets and Inlets, coil configurations and Sizes.

    3.5.2  Size. A measurement relative to the nominal length and width of the coil.

    3.6  Published Rating. A statement of the assigned values of those performance characteristics, under stated rating

    conditions, by which a unit may be chosen to fit its application. These values apply to all units of a particular Model and Size

     produced by the same manufacturer.

    3.6.1   Published Ratings shall include Standard Ratings, properly identified as such, and should, in addition, include

    application ratings.

    3.6.2 Standard Ratings. A rating based on tests performed at Standard Rating Conditions.

    3.6.3  Application Rating.  A rating at other than Standard Rating Conditions; such other rating conditions are

    referred to as Application Rating Conditions.  

    3.7  Sensible Cooling Capacity.  Capacity associated with a reduction in dry-bulb temperature, Btu/h.

    3.8 "Shall" or "Should". "Shall" or "should" shall be interpreted as follows:

    3.8.1 Shall.  Where "shall" or "shall not" is used for a provision specified, that provision is mandatory if

    compliance with the standard is claimed.

    3.8.2 Should.  "Should" is used to indicate provisions which are not mandatory but which are desirable as good

     practice.

    3.9  Sound Power Level . Ten times the logarithm to the base ten of the ratio of the sound power radiated by the source to

    a reference sound power, expressed in decibels (dB). The reference sound power used in this standard is 1 picowatt (pW).

    3.10 Throw. Horizontal or vertical axis distance an airstream travels after leaving an air outlet before the stream velocity

    is reduced to a specific terminal value.

    Section 4. Classifications

    4.1  Active Chilled Beams are classified according to the following Product Lines:

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    10/17

      AHRI STANDARD 1240 (I-P)-2014

    3

    4.1.1 Single or Multiple Discharge Openings.

    4.1.2  Method of Secondary Air Intake.

    4.1.2.1  Direct Type –  where the Induced Air Inlet is located in the room (Secondary Air is induced from

    the conditioned space).

    4.1.2.2  Indirect Type –  where the Induced Air Inlet is located outside the room (Secondary Air is induced

    from the conditioned space via the return air Plenum).

    4.1.3 The Ability to Form Condensation on the Coil.

    4.1.3.1  Non-condensing

    4.1.3.2  Condensing

    4.1.4   Mounting Type. 

    4.1.4.1  Exposed mount or surface mount

    4.1.4.2  Modular (ceiling or drywall integrated)

    4.1.5  Operating Inlet Static Pressure. 

    4.1.5.1  Less than or equal to 1.5 in. H2O of inlet static pressure.

    4.1.5.2  More than 1.5 in. H2O of inlet static pressure.

    Section 5. Standard Equipment

    5.1   Equipment . An Active Chilled Beam shall include the following as standard equipment:

    5.1.1  Plenum

    5.1.2  Nozzle(s)

    5.1.3  Cooling, or cooling and heating, coil(s)

    5.1.4  Static pressure port(s)

    5.1.5  Supply Air Outlet(s)

    5.1.6  Induced air opening

    Section 6. Test Requirements

    6.1  Active Chilled Beams, as described in Section 5, shall be tested for rating in accordance with the provisions set forth

    in ANSI/ASHRAE Standard 200.

    Section 7. Rating Requirements

    7.1  Standard Ratings. Standard Ratings shall be established at the Standard Rating Conditions specified in Section 7.2

    and shall be expressed in terms of Btu per hour (Btu/h) rounded to the nearest 50 Btu/h and in terms of the flow of Primary

    Air in cubic feet per minute (scfm) rounded off to the nearest 2 scfm.

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    11/17

    AHRI STANDARD 1240 (I-P)-2014

    4

    7.2 Standard Rating Conditions.  Standard Ratings shall be determined from tests, using the methods of testing set forth

    in ANSI/ASHRAE Standard 200.

    7.3  Application Rating Conditions.  Application ratings shall permit selection of units for at least a range of conditions

    commonly encountered, and should be based on corresponding ranges of the parameters listed in Section 8.

    7.4 Tolerances. To comply with this standard, Published Ratings shall be based on data obtained in accordance with the

     provisions of Section 8 of this standard, and shall be such that any production Chilled Beams, when tested, will meet these

    ratings within the following tolerances:

    7.4.1 Water flow rate shall be greater than or equal to 95% of the rating.

    7.4.2 Water pressure drop shall be no greater than 105%110% of the rating or 1 foot of fluid above the rating,

    whichever is greater.

    7.4.3 Water coil capacity shall be within ±5% greater than or equal to 95% of the rating.

    7.4.4 Primary Air flow rate shall be within ±5% less than or equal to 105% of the rating.

    7.4.5 Induced air flow rate shall be within ±10% greater than or equal to 90% of the rating.

    7.4.6 Discharge air throw distance shall be within 20% or 1 foot of the rating whichever is greater.

    7.4.7 Sound Power Levels shall not exceed the published values in each Octave Band by more than the rating

    tolerance shown in Table 1.

    Table 1. Sound Power LevelRating Tolerances 

    Octave BandCenter

    Frequencies, Hz

    RatingTolerance,

    dB

    125 6

    250 4

    500 31000 3

    2000 3

    4000 3

    Section 8. Minimum Data Requirements for Published Ratings

    8.1   Published   Ratings. Published Ratings shall consist of Standard Ratings. Application Ratings may be published in

    addition to Standard Ratings. Wherever Application Ratings are published or printed, they shall include or be accompanied

     by the Standard Rating, clearly designated as such. Application Ratings shall include the information contained in Section

    8.3 and shall clearly define the pertinent conditions as indicated in Section 8.4.

    8.2 Standard Ratings.  Standard Ratings shall consist of at least the following information, obtained at Standard RatingConditions:

    8.2.1  Primary air flow rate, scfm (Standard Air)

    8.2.2  Primary air temperature, 75°F - Isothermal to reference air temperature

    8.2.3  Primary Air pressure drop, 0.5 inches H2O

    8.2.4  Water coil capacity, reported, Btu/h

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    12/17

      AHRI STANDARD 1240 (I-P)-2014

    5

    8.2.53  Entering water temperature, cooling: 57°F

    8.2.6  Leaving water temperature, reported value °F

    8.2.7  Water flow rate, gpm, adjusted to achieve mean water temperature differential of 14.5°F relative toReference Air Temperature

    8.2.8  Water pressure drop, reported, inches H2O

    8.2.9  Supply Air throw distance, 100 fpm with Supply Air at isothermal conditions relative to the test room to bedetermined using ANSI/ASHRAE Standard 70. Air volume to be at manufacturer supplied value for Primary Air.

    8.2.10  Sound generation (combined radiated and discharge sound) by Octave Bands 2 to 7. Air volume to be atmanufacturer’s supplied value for Primary Air.  

    8.2.11  Induced air flow rate, cfm

    8.2.4  Minimum primary air pressure drop, reported value, rounded to 0.1 inches H2O. At this condition, alsoinclude the following information: 

    8.2.4.1 Water coil capacity, reported, Btu/h

    8.2.4.2  Induced air flow rate, scfm8.2.4.3  Leaving water temperature, reported value, °F8.2.4.4  Water flow rate, gpm, adjusted to achieve mean water temperature differential of 14.5°F relativeto reference air temperature8.2.4.5  Water pressure drop, reported, feet H2O8.2.4.6  Supply air throw distance, 100 fpm with Supply Air at isothermal conditions relative to the testroom to be determined using ANSI/ASHRAE Standard 70. Air volume to be at manufacturer suppliedvalue for Primary Air.8.2.4.7  Sound generation (combined radiated and discharge sound) by Octave Bands 2 to 7. Air volume to be at manufacturer’s supplied value for Primary Air.  

    8.2.5  Maximum primary air pressure drop, reported value, rounded to 0.1 inches H2O. At this condition, alsoinclude the following information: 

    8.2.5.1 Water coil capacity, reported, Btu/h8.2.5.2  Induced air flow rate, scfm8.2.5.3  Leaving water temperature, reported value °F8.2.5.4  Water flow rate, gpm, adjusted to achieve mean water temperature differential of 14.5°F relativeto reference air temperature8.2.5.5  Water pressure drop, reported, feet H2O8.2.5.6  Supply air throw distance, 100 fpm with Supply Air at isothermal conditions relative to the testroom to be determined using ANSI/ASHRAE Standard 70. Air volume to be at manufacturer suppliedvalue for Primary Air.8.2.5.7  Sound generation (combined radiated and discharge sound) by Octave Bands 2 to 7. Air volume to be at manufacturer’s supplied value for Primary Air.  

    8.2.6  Primary Air pressure drop, 0.5 inches H2O. At this condition, also include the following information:  

    8.2.6.1 Water coil capacity, reported, Btu/h8.2.6.2  Induced air flow rate, scfm8.2.6.3  Leaving water temperature, reported value °F8.2.6.4  Water flow rate, gpm, adjusted to achieve mean water temperature differential of 14.5°F relativeto reference air temperature8.2.6.5  Water pressure drop, reported, feet H2O8.2.6.6  Supply air throw distance, 100 fpm with Supply Air at isothermal conditions relative to the testroom to be determined using ANSI/ASHRAE Standard 70. Air volume to be at manufacturer suppliedvalue for Primary Air.

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    13/17

    AHRI STANDARD 1240 (I-P)-2014

    6

    8.2.6.7  Sound generation (combined radiated and discharge sound) by Octave Bands 2 to 7. Air volume to be at manufacturer’s supplied value for Primary Air.  

    8.3   Published Application Ratings.  Published Application Ratings shall consist of at least the following information:

    8.3.1  Primary Air flow rate, scfm (Standard Air)

    8.3.2  Primary Air temperature, °F

    8.3.3  Dew point temperature of room and Primary Air, °F

    8.3.4  Primary Air pressure drop, inches H2O

    8.3.5  Room air temperature (induced to the beam), cooling: °F

    8.3.6  Water coil sensible capacity, Btu/h

    8.3.7  Entering water temperature, cooling: °F

    8.3.8  Leaving water temperature, °F

    8.3.9  Water flow rate, gpm

    8.3.10  Water pressure drop, inches H2O

    8.3.11  Supply Air throw distance, 100 fpm with Supply Air at isothermal conditions relative to the test room to bedetermined using ANSI/ASHRAE Standard 70. Air volume to be at manufacturer supplied value for Primary Air.

    8.3.12  Supply Air temperature, °F

    8.3.13  Sound generation (combined radiated and discharge sound) by Octave Bands 2 to 7.

    8.3.14  Total Sensible Cooling Capacity, Btu/h

    8.3.15  Sensible water coil energy per unit volume of Primary Air, Btu/scfm

    8.3.16  Induced air flow rate, scfm

    8.3.17 Some optional published Application Ratings may include:

    8.3.17.1  Induction Ratio

    8.4  Published Rating Data. Published Ratings shall include drawings indicating essential dimensions, including:

    8.4.1  The length, height, and width of the unit

    8.4.2  Nozzle type

    8.4.3  Size and locations of inlet(s) for Primary Air

    8.4.4  Size and location of piping

    As a minimum, Published Ratings shall include all Standard Ratings. All claims to ratings within the scope of this standard

    shall include the statement “Rated in accordance with AHRI Standard 1240 (I-P)”. All claims to ratings outside the scope of

    this standard shall include the statement “Outside the scope of AHRI Standard 124 0 (I-P)”. Wherever Application Ratings

    are published or printed, they shall include a statement of the conditions at which the ratings apply.

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    14/17

      AHRI STANDARD 1240 (I-P)-2014

    7

    Section 9. Marking and Nameplate Data

    9.1  Model Identification. The nameplate on each Active Chilled Beam shall include sufficient Model and Size

    identification to correlate with published data, literature and any other advertising issued by the manufacturer.

    9.2  Marking and Nameplate Data.  As a minimum, the nameplate shall display the manufacturer’s name, Model

    designation, and electrical characteristics.

     Nameplate voltages for 60 Hz systems shall include one or more of the equipment nameplate voltage ratings shown in Table

    1 of ANSI/AHRI Standard 110. Nameplate voltages for 50 Hz systems shall include one or more of the utilization voltages

    shown in Table 1 of IEC Standard 60038.

    Section 10. Conformance Conditions

    10.1  Conformance. While conformance with this standard is voluntary, conformance shall not be claimed or implied for

     products or equipment within the standard’s  Purpose (Section 1) and Scope (Section 2) unless such product claims meet all

    the requirements of the standard and all of the testing and rating requirements are measured and reported in complete

    compliance with the standard. Any product that has not met all the requirements of the standard cannot reference, state, or

    acknowledge the standard in any written, oral, or electronic communication.

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    15/17

    AHRI STANDARD 1240 (I-P)-2014

    8

    APPENDIX A. REFERENCES  – NORMATIVE 

    A1  Listed here are all standards, handbooks and other publications essential to the formation and implementation of the

    standards. All references in this appendix are considered as part of the standard.

    A1.1 ANSI/AHRI Standard 110-2012,  Air-Conditioning, Heating and Refrigerating Equipment Nameplate

    Voltages, 2012, Air-Conditioning, Heating, and Refrigeration Institute, 2111 Wilson Boulevard, Suite 500,Arlington, VA 22201, U.S.A..

    A1.2  ANSI/ASHRAE Standard 70-2006 , Method of Testing the Performance of Air Outlets and Air Inlets, 2006,

    American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 1791 Tullie Circle, N.E., Atlanta,

    GA 30329, U.S.A.

    A1.3  ANSI/ASHRAE Standard 200-2015 , Methods of Testing Chilled Beams, 2014, American Society of Heating,

    Refrigerating and Air-Conditioning Engineers, Inc., 1791 Tullie Circle, N.E., Atlanta, GA 30329, U.S.A.

    A1.4  ANSI/ASA Standard S1.11-2014 , Electroacoustics - Octave-band and Fractional-octave-band Filters - Part

    1: Specifications (a nationally adopted international standard , Acoustical Society of America, Suite 300, 1305 Walt

    Whitman Road, Melville, NY 11747-4300, U.S.A.

    A1.4 ASHRAEwiki, Terminology, http://wiki.ashrae.org/index.php/ASHRAEwiki,  2014, American Society of

    Heating, Refrigerating and Air-Conditioning Engineers, Inc., 1791 Tullie Circle, N.E., Atlanta, GA 30329, U.S.A. 

    A1.5 ASHRAE Terminology, https://www.ashrae.org/resources--publications/free-resources/ashrae-terminology,

    2014, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 1791 Tullie Circle, N.E.,

    Atlanta, GA 30329, U.S.A.

    A1.6 IEC Standard 60038, IEC Standard Voltages, 2002, International Electrotechnical Commission, 3,

    rue de Varembe, P.O. Box 131, 1211 Geneva 20, Switzerland.

    APPENDIX B. REFERENCES –

     INFORMATIVE B1  Listed here are standards, handbooks, and other publications which may provide useful information and background

     but are not considered essential. References in this appendix are not considered part of the standard.

     None.

    http://wiki.ashrae.org/index.php/ASHRAEwikihttp://wiki.ashrae.org/index.php/ASHRAEwiki

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    16/17

      AHRI STANDARD 1240 (I-P)-2014

    9

    APPENDIX C. METHOD OF TESTING WATER PRESSUREDROP - NORMATIVE 

    C1.1 The temperatures and pressures of water entering and leaving the chilled beam shall be measured by the apparatus as

    illustrated in Figure C1. The connecting piping shall be the same size as the chilled beam supply and return connections.

    C1.2 Temperature measuring instruments shall be placed so as to measure the temperature of the water entering (t l1) and

    leaving (tl2) the coil. The liquid lines shall be insulated at and adjacent to the temperature measuring instruments. Suitable

    insulation having an R-value of 4.5 ft2•°F•hr/Btu or greater shall be applied from the unit  under test to at least 6 in. upstream

    of the inlet temperature sensor and 6 in. downstream of the outlet temperature sensor. Temperature sensor stems shall be

    insulated. To minimize possible temperature stratification, appropriate mixers, such as "static mixers," shall be inserted in the

    inlet and outlet liquid lines upstream from the temperature measuring instruments. Alternatively, two close-coupled 90°

    elbows just upstream of the temperature measuring instruments can serve as mixers provided that the water velocity at the

    mixing section is not below 1 ft/s.

    Figure C1. Measuring Apparatus for Water Pressure Drop

  • 8/18/2019 AHRI Standard 1240 I-P Add 1

    17/17