Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts
description
Transcript of Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts
![Page 1: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/1.jpg)
INDOOR AIR QUALITY ASSESSMENTMassachusetts Department of Public Health
Bureau of Environmental HealthIndoor Air Quality Program
Agassiz Community School20 Child Street
Jamaica Plain, Massachusetts
![Page 2: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/2.jpg)
Outline
• IAQ background• General IAQ assessment
– Dates Visited• July 14, 2008• December 11, 2008 • January 21, 2009• April 22, 2009
• Health Effects Discussion• Recommendations• Questions
![Page 3: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/3.jpg)
Common Factors Associated with IAQ Problems
• Ventilation• Microbial Growth
– Mold• Point Sources of
Environmental Irritants
![Page 4: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/4.jpg)
Conditions that Influence Indoor Air Quality
• Poor Design• Poor Maintenance• Occupant Induced
![Page 5: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/5.jpg)
Poor DesignExamples:
• Inadequate or Nonexistent HVAC Systems
• Poor Construction/Design
• Right Design/Wrong Climate
• Over-Designed/Multiple Moving Parts
Conditions that Influence Indoor Air Quality
![Page 6: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/6.jpg)
Poor Maintenance Examples:• Lack of Attention to Maintenance of
HVAC System
• HVAC System Operations & Management
• Failure to Maintain Building Envelope/Water Penetration
Conditions that Influence Indoor Air Quality
![Page 7: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/7.jpg)
Occupant-InducedExamples:
• Environmental Tobacco Smoke
• VOC-containing Art/Office Supplies
• Blockage of HVAC Vents
• Poorly Stored Chemicals
Conditions that Influence Indoor Air Quality
![Page 8: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/8.jpg)
Aerial View of School
![Page 9: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/9.jpg)
![Page 10: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/10.jpg)
1990s Repairs
• Replacement of duct boards-taped ducts• Replacement of air handling units• Replacement of HVAC system chiller• Roof replaced
– No slope– No additional roof drains
![Page 11: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/11.jpg)
Environmental Measurements
![Page 12: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/12.jpg)
Indoor Air Quality Ventilation
Parameter typically measured to ascertain ventilation equipment function:
• Carbon Dioxide Levels: ≥ 800 ppm indicates inadequate ventilation600-800 ppm acceptable air exchange< 600 ppm is preferable in elementary schools
![Page 13: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/13.jpg)
Carbon Dioxide Measurements
• Above 800 ppm in 6 of 71* areas surveyed, indicating adequate ventilation in majority of the areas surveyed (December 11, 2008)
* It is important to note that several classrooms had open windows and/or were empty/sparsely populated
Indoor Air Quality Ventilation
![Page 14: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/14.jpg)
Additional Parameter Typically Measured To Ascertain Ventilation Equipment Function:
• Temperature:
Comfort Range: 70 o F to 78 o F
• Relative Humidity:
Comfort Range: 40% to 60%
Indoor Air Quality Ventilation
![Page 15: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/15.jpg)
Temperature Measurements: • 68o F to 74o F
Relative Humidity Measurements: 12% to 25%
Indoor Air Quality Ventilation
December 11, 2008
![Page 16: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/16.jpg)
Low Relative Humidity
Relative Humidity < 20 %
• is found frequently during the winter indoors in New England during cloudless, below- freezing weather conditions
• dry eyes, mucous membranes, throat irritation
• exacerbate preexisting skin rashes
• leads to increased
– aerosolization of dusts
– evaporation of VOCs
![Page 17: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/17.jpg)
HVAC Equipment
Heat exchanger
![Page 18: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/18.jpg)
Classroom supply vent
![Page 19: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/19.jpg)
Classroom exhaust vent
![Page 20: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/20.jpg)
Classroom exhaust vent near door
![Page 21: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/21.jpg)
Classroom FCU
![Page 22: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/22.jpg)
FCU settings
![Page 23: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/23.jpg)
Occluded filter, note that filter is sitting in FCU and off floor
![Page 24: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/24.jpg)
Items placed in front of FCU
![Page 25: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/25.jpg)
Point source pollution parameters:
• Carbon monoxidelevels of fresh air introduced to a building should not exceed the NAAQS* level of 9 ppm in an eight-hour average.
• Airborne particles Levels for particulate matter with a diameter of 2.5 μm or less (PM2.5) should be maintained below the NAAQS* level of 35 μg/m3 over a 24-hour average
*The NAAQS were adopted by reference in the BOCA National Mechanical Code of 1993, which is now an HVAC standard included in the Massachusetts State Building Code.
Indoor Air QualityPoint Source Irritants
![Page 26: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/26.jpg)
Carbon monoxide:• ND in all areas surveyed
Particulate Matter (PM2.5):• Outdoors/Background: 17 μg/m3 • 7 - 15 μg/m3
Indoor Air QualityPoint Source IrritantsDecember 11, 2008
![Page 27: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/27.jpg)
Wall/Window Frame Temperature Analysis
• Building occupants report temperature extremes
– Building is unable to cool in the summer
– Building in the winter is:• Too cold in classrooms on the exterior walls• Too warm in rooms in the core of the building
![Page 28: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/28.jpg)
Surface Temperature Survey January 21, 2009
• Using a laser thermometer, the temperature of the following building components were measured inside the building:
– Window frames– Exterior door frames (where present)– Exterior walls– Walls dividing classrooms– Hallway walls
![Page 29: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/29.jpg)
Surface Temperature Survey January 21, 2009
• Assumption: If properly insulated, temperatures of building components inside classrooms should be near the room air temperature.
• Set point for the thermostat at the ACS is 68o F
• Therefore the temperature of window frames, exterior door frames, exterior walls, walls dividing classrooms and hallway walls should be in a range of 63o F to 73o F (+/- 5o F)
![Page 30: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/30.jpg)
Surface Temperature Survey Results January 21, 2009
– Window frames 0oF to 103oF
– Exterior door frames 0o F to 26o F
– Exterior walls 20o F to 63o F
– Walls dividing classrooms 35o F to 67o F
– Hallway walls 37o F to 69o F
![Page 31: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/31.jpg)
Thermal Bridge
• Thermal bridge is created when materials that are poor insulators come in contact, allowing heat to flow through the path created.
• Repeating thermal bridges - where bridges occur following a regular pattern, such that made by wall ties penetrating a cavity wall.
![Page 32: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/32.jpg)
Insulation
• R Rating-A measure of the capacity of a material, such as insulation, to impede heat flow, with increasing values indicating a greater capacity
• The higher the R-value, the greater the insulating effectiveness.
![Page 33: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/33.jpg)
Thermal Bridge
• If an object transverses the insulation (e.g., a steel bar), heat loss will occur, lowering temperature
• It is as if the insulation is not in place
![Page 34: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/34.jpg)
Repeating Thermal Bridges
![Page 35: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/35.jpg)
Note Wire and Space in Wall
![Page 36: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/36.jpg)
Windows are Single Pane with Non-insulated Window Frames
![Page 37: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/37.jpg)
Supply and return heating system pipes connected from FCU to ceiling instead of along walls
![Page 38: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/38.jpg)
Example of typical univent supply and return heating system pipes configured to provide heat for windows and walls, note radiator register flanking the univent
Granville Village School, Granville, MA
![Page 39: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/39.jpg)
Understanding Dew Point
• When warm, moist air passes over a cooler surface, condensation can form. Condensation is the collection of moisture on a surface at or below the dew point.
• The dew point is the temperature that air must reach for saturation to occur. If a building material/component has a temperature below the dew point, condensation will accumulate on that material.
• Over time, condensation can collect and form water droplets.
![Page 40: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/40.jpg)
Understanding Dew Point
• American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE), if relative humidity exceeds 70%, mold growth may occur due to wetting of building materials
• It is recommended that porous material be dried with fans and heating within 24 to 48 hours of becoming wet (US EPA, 2001, ACGIH, 1989)
• If porous materials are not dried within this time frame, mold growth may occur
• Water damaged porous materials cannot be adequately cleaned to remove mold growth
![Page 41: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/41.jpg)
Calculation for Dew Point January 21, 2009
• Temperature indoors 68o F• Relative Humidity 46% outdoors• Dew Point 46o F
• On this day, 41 windows were below the dew below the dew point point
• Therefore, a major contribution to wood rot on sills is likely due to condensation, with periodic moistening by rainwater penetration
![Page 42: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/42.jpg)
Microbial GrowthConditions Needed to Grow Mold
• spores• nutrients• temperature >45o F• water (moisture)
– Material should be dried within 24 - 48 hours of becoming moistened
![Page 43: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/43.jpg)
Components of a Mold Colony That Can Be Allergenic
• Mold*• Spores*• Mycotoxins• Mycelia Fragments• Mold Volatile Organic Compounds
* killed by fungicides/sporicides
![Page 44: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/44.jpg)
Why Does Mold Growth Occur Indoors?
• Water is either entering or failing to exit the building interior.
• Materials that can support mold growth are stored/placed in an area that can become moistened for an extended period (> 24 hours).
– Example: storing books in a basement prone to condensation generation in the summer
• condensation
![Page 45: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/45.jpg)
Materials Unlikely To Grow Mold With an Adequate Moisture Source
• Cement• Cinderblock• Brick• Steel and other metal• Floor tiles• Hard Plastic
• If mold appears, the mold growth medium is settled onto the surface of the material
• Remediation recommendation = Cleaning of surface
![Page 46: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/46.jpg)
Materials Likely to Grow Mold with an Adequate Moisture Source
• carpet• ceiling tiles• drapery• gypsum wallboard• paper• books• particle board/plywood• cardboard• potting soil• fiberglass insulation• soft plastic• soft wood
• Each material contains carbon, which serves as the food source for mold
• Remediation recommendation = Removal of the material if moistened for an extended period of time
![Page 47: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/47.jpg)
FCU insulation losing adherence to surfaces, resulting in condensation
![Page 48: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/48.jpg)
Condensation on surface of FCU
![Page 49: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/49.jpg)
FCU in stairwell with floor stained from water leaking
![Page 50: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/50.jpg)
Cooling Coil
FCU cooling coil and debris in drip pan
Drip Pan
![Page 51: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/51.jpg)
Auxiliary drain pan, note debris in pan, lack of insulation on copper drain pipe elbow, rust on cabinet components and water staining on floor of cabinet
![Page 52: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/52.jpg)
Filter sitting on floor due to missing brackets
![Page 53: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/53.jpg)
Water damaged stained window frame wood
![Page 54: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/54.jpg)
Staining from rainwater, note damaged window frames
![Page 55: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/55.jpg)
Damaged window frame
![Page 56: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/56.jpg)
Breach in window frame where wooden sill was removed
![Page 57: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/57.jpg)
Spaces between stone panels
![Page 58: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/58.jpg)
Water drip stains down wall
![Page 59: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/59.jpg)
Stained/lifting floor tiles
![Page 60: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/60.jpg)
Standing water on floor beneath filing cabinet
![Page 61: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/61.jpg)
Plug in floor, note staining indicating water leakage
![Page 62: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/62.jpg)
Signs of water pooling against the building
![Page 63: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/63.jpg)
Clogged roof drain
![Page 64: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/64.jpg)
Accumulated water on roof below slope
![Page 65: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/65.jpg)
Efflorescence around Plaster Patch, corresponds to pooling water noted in previous slide
![Page 66: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/66.jpg)
Accumulated materials on roof, note plant growth
![Page 67: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/67.jpg)
Lifted repair sections on roof
![Page 68: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/68.jpg)
Example of open seam between sink countertops and walls
![Page 69: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/69.jpg)
Dehumidifier
Dehumidifier operating with the window open
![Page 70: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/70.jpg)
Other Concerns
![Page 71: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/71.jpg)
Ionizer button
Air purifier with ionizer
![Page 72: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/72.jpg)
Air purifier using HEPA filter with no ionizer
![Page 73: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/73.jpg)
Exposed fiberglass insulation
![Page 74: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/74.jpg)
Tennis Balls on Chair Legs
![Page 75: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/75.jpg)
Rodent infestation
• Rodents can be a source of disease and infestation can result in indoor air quality related symptoms due to materials in their wastes.
• Mouse urine and feces contain a protein that is a known sensitizer (US EPA, 1992).
• A sensitizer is a material that can produce symptoms (e.g. rhinitis and skin rashes) in sensitive individuals.
![Page 76: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/76.jpg)
Rodent infestation
• A three-step approach is necessary to eliminate rodent infestation:
• removal of the rodents
• cleaning of waste products from the interior of the building
• reduction/elimination of pathways/food sources
that are attracting rodents such as toasters/toaster ovens in classrooms
![Page 77: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/77.jpg)
Rodent attractorPaper mâché
• Paper mâché paste is a liquid adhesive usually made using flour and water.
• It closely resembles wallpaper paste. It can be used as a paste for paper mâché projects and also decoupage, collage, and book binding.
• One classroom floor had substantial paper mâché residue on its floor
![Page 78: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/78.jpg)
Green Material is Bait on Floor
Bait traps in AHU room
Rodent attractorBait Trap Inappropriately Placed
![Page 79: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/79.jpg)
Noise in gymnasium
• Reports concerning the noise in the gymnasium that is created by the HVAC system.
• Factors increasing noise in gymnasium– The AHU is hung from the ceiling of the gymnasium.– The AHU and its ductwork are not externally insulated. – Ductwork does not appear to be internally insulated.
• In this configuration, the HVAC system ductwork amplifies noise from the AHU fan and motors. Insulation on the ductwork would dampen the vibrations and reduce noise.
![Page 80: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/80.jpg)
Health Concerns
![Page 81: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/81.jpg)
Health EffectsInterview Results
• All school personnel were offered opportunity to be interview by DPH staff. 15 agreed to be interviewed.
• The predominant symptoms in this category were sinus congestion/infection and colds.
![Page 82: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/82.jpg)
Health EffectsInterview Results
General Indoor Air Quality
• variation in temperature (some individuals reported the building being too hot while others reported it being too cold)
• variation in humidity (some individuals reported that the air is too dry while others reported that it is too moist)
• water damage• poor ventilation• mold• pests• dust• general building deterioration
![Page 83: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/83.jpg)
Health Effects Medical Record Reviews
• Of the 15 employees interviewed, 5 consented to have their medical records reviewed and returned signed medical record release consent forms.
• Despite repeated requests, MDPH staff were not able to obtain one set of medical records for one individual.
• According to BEH’s physician, several of the IAQ conditions observed may contribute to eye or respiratory irritation; these include – low levels of humidity,– presence of particulates and dusts– VOCs – conditions conducive to attracting rodents– mold/moisture in areas prone to water damage
![Page 84: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/84.jpg)
Health Effects Medical Record Reviews
• The five cases reviewed show one commonality, rhinosinusitis (a condition involving inflammation in one or more of the paranasal sinuses) symptoms.
• Typically, rhinosinusitis is the result of irritation, allergic reaction, or infection.
![Page 85: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/85.jpg)
Health Effects Discussion
• The symptoms reported among participants of this health investigation are generally those most commonly experienced in buildings with less than optimal indoor air quality.
• The symptoms most frequently reported by individuals at the ACS were respiratory/irritant effects including allergies, headaches, sinus congestion or sore, hoarse or dry throat as well as headaches.
• The diagnosis of rhinosinusitis among the 5 individuals whose medical records were reviewed may be impacted by some conditions observed in the building
![Page 86: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/86.jpg)
RecommendationsShort and Long-Term
![Page 87: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/87.jpg)
Short-Term Recommendations
• Remove/replace original, water-damaged wood sills from the base of all windows if wood is water stained or materially degrading.
• Operate both supply and exhaust ventilation continuously during periods of school occupancy to maximize air exchange.
• Clean accumulated debris from FCU drip pans on a regular schedule.
• Install filter racks on FCUs to hold filters in place.
![Page 88: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/88.jpg)
Short-Term Recommendations
• Remove obstructions from FCU air intakes and diffusers.
• Operate FCUs during periods of school occupancy to facilitate airflow in classrooms.
• Close classroom doors to maximize air exchange.
• Consider adopting a balancing schedule of every 5 years for all mechanical ventilation systems, as recommended by ventilation industrial standards (SMACNA, 1994).
• Remove rodent bait traps from HVAC system mechanical rooms.
![Page 89: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/89.jpg)
Short-Term Recommendations
• Use the principles of integrated pest management (IPM) to rid this building of pest. Activities that can be used to eliminate pest infestation may include the following activities:– Refrain from using recycled food containers. Seal recycled
containers in a tight fitting lid to prevent rodent access
– Ensure that areas where paper mache is practiced are thoroughly cleaned after such activities.
– Remove non-food items that rodents are consuming– Store foods in tight fitting containers.– Avoid eating at workstations. In areas were food is consumed,
periodic vacuuming to remove crumbs is recommended.
![Page 90: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/90.jpg)
Short-Term Recommendations
• Principles of IPM (cont.):– Regularly clean crumbs and other food residues from toasters,
toaster ovens, microwave ovens coffee pots and other food preparation equipment.
– Examine each room and the exterior walls of the building for means of rodent egress and seal appropriately. Holes as small as ¼” is enough space for rodents to enter an area. If doors do not seal at the bottom, install a weather strip as a barrier to rodents.
– Reduce harborages (cardboard boxes) where rodent may reside.
![Page 91: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/91.jpg)
Short-Term Recommendations
• To control for dusts, a HEPA filter equipped vacuum cleaner in conjunction with wet wiping of all surfaces is recommended.
• Avoid the use of feather dusters.
• Drinking water during the day can help ease some symptoms associated with a dry environment (throat and sinus irritations).
![Page 92: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/92.jpg)
Short-Term Recommendations
• Change filters for air-handling equipment (e.g., AHUs, FCUs and air purifiers) as per the manufacturer’s instructions or more frequently if needed. Vacuum interior of units prior to activation to prevent the aerosolization of dirt, dust and particulates. Ensure filters fit flush in their racks with no spaces in between allowing bypass of unfiltered air into the unit.
• Ensure leaks are repaired. Remove/replace water damaged ceiling tiles. Examine the areas above and around for mold growth. Disinfect areas of water leaks with an appropriate antimicrobial.
![Page 93: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/93.jpg)
Short-Term Recommendations
• Remove dirt/debris from roof/drains to ensure proper drainage and to prevent plant growth. Consider methods to prevent water from pooling at the base of the sloped stairwell roof.
• Consider regrading the apron of the building to prevent water pooling/penetration through the building’s foundation and slab.
• Move plants away from FCUs in classrooms. Avoid over-watering and examine drip pans periodically for mold growth. Disinfect with an appropriate antimicrobial where necessary.
![Page 94: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/94.jpg)
Short-Term Recommendations
• Keep windows closed during hot, humid weather to maintain indoor temperatures and to avoid condensation problems when air conditioning is activated.
• Clean and maintain humidifiers and dehumidifiers as per the manufacturers’ instructions.
• Seal areas around sinks to prevent water-damage to the interior of cabinets and adjacent wallboard. Inspect wallboard for water damage and mold growth, repair/replace as necessary. Disinfect areas with an appropriate antimicrobial, as needed. Consider replacing with single piece molded countertops.
![Page 95: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/95.jpg)
Short-Term Recommendations
• Refrain from using plug-in air fresheners or other air deodorizers.
• Clean and maintain aquariums and terrariums to prevent mold growth and associated odors.
• Store cleaning products properly and out of reach of students. Ensure spray bottles are properly labeled. All cleaning products used at the facility should be approved by the school department with MSDS’ available at a central location.
![Page 96: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/96.jpg)
Short-Term Recommendations
• Relocate or consider reducing the amount of materials stored in classrooms to allow for more thorough cleaning of classrooms. Clean items regularly with a wet cloth or sponge to prevent excessive dust build-up.
• Clean personal fans/heaters, air diffusers, return vents and exhaust vents periodically of accumulated dust.
• Clean chalk and dry erase trays to prevent accumulation of materials.
• Clean upholstered furniture and pillows on the schedule recommended in this report. If not possible/practical, consider removal from classrooms.
![Page 97: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/97.jpg)
Short-Term Recommendations
• Replace latex-based tennis balls with latex-free tennis balls or alternative “glides”.
• Consider adopting the US EPA document, “Tools for Schools”, to maintain a good indoor air quality environment in the building (US EPA, 2000). This document can be downloaded from the Internet at: http://www.epa.gov/iaq/schools/index.html.
• Refer to resource manuals and other related indoor air quality documents for further building-wide evaluations and advice on maintaining public buildings. These materials are located on the MDPH’s website at: http://mass.gov/dph/indoor_air.
![Page 98: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/98.jpg)
Long-Term Recommendations
• An evaluation of FCUs should be done to ascertain whether this HVAC system component can be repaired to prevent condensation generation. If not repairable, consideration should be given to replacing FCUs.
• Consider plans for repairing the roof and installing additional drainage.
![Page 99: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/99.jpg)
Long-Term Recommendations
• Consider having a building engineer evaluate the building envelope in order to ascertain whether the exterior wall of classrooms can be improved to prevent thermal bridges and more controlled heating and cooling of the ACS. Activities to consider include, but are not limited to the following: – Installing an interior wall with insulation over the existing
classroom exterior walls. Ensure proper integration with the new window systems planned for installation in 2009. It may also include separation of interior walls from the exterior walls to disrupt the likely temperature bridge that exists.
![Page 100: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/100.jpg)
Long-Term Recommendations
• Consider having a ventilation engineer examine the existing heat exchange system for adequacy of design.
• Consider having exterior walls re-pointed and waterproofed to prevent water intrusion. This measure should include a full building envelope evaluation.
• Examine the feasibility of insulating the FCUs and duct work in the gymnasium to reduce noise.
• Consider plans for having an energy audit conducted.
![Page 101: Agassiz Community School 20 Child Street Jamaica Plain, Massachusetts](https://reader035.fdocuments.net/reader035/viewer/2022062323/56816331550346895dd3b273/html5/thumbnails/101.jpg)
MDPH IAQ Assessment Staff
Michael A. Feeney, R.Ph., J.D., C.H.O.
Director, Indoor Air Quality ProgramBureau of Environmental Health
Massachusetts Department of Public Health
Tel. No. (617) 624-5757
Website: http://mass.gov/dph/indoor_air