AEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300 / 600 / 1000 Betriebsanleitung Operating Manual

Transcript of AEG - Conrad · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung...

Page 1: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

AEGPOWER SUPPLYSYSTEMS

Unterbrechungsfreie StromversorgungUninterruptible Power Supply

CompuMaster 300 / 600 / 1000

BetriebsanleitungOperating Manual

Page 2: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

Hints concerning this manual

Responsibility of information

This manual will help you to install and to operate theUninterruptable rower Supply (UPS) CompuMaster 300,CompuMaster 600 or CompuMaster 1000 - generallysimplified called CompuMaster in this manual - properly andsafe according to the assigned use. The manual includes im-portant hints which will be helpful for a use without danger.

Please read this manual carefully before commissioning !

This manual is a constituent part of the CompuMaster. The userof this unit is obliged to provide this manual to all personshandling the CompuMaster , e.g. transport, commissioning,maintaining or other activity.

Validity

These operating instructions comply with the current technicalspecifications of the CompuMaster at the moment of issue. Thecontents do not constitute a subject of contract, but serveinformation purposes only.

AEG reserves the right to make modifications with regard tocontents and technical data in these operating instructionswithout prior notification.

AEG cannot be held liable for any inaccuracies or inapplicableinformation in these operating instructions, as no obligation tocontinuously update the data and maintain their validity hasbeen entered into.

31

Page 3: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

Warranty

Our goods and services are subject to the general conditions ofsupply for products of the electrical industry and our generalsales conditions. We reserve the right to alter any specificationsgiven in these operating instructions, especially with regard totechnical data, operation, weights and dimensions.

AEG will warrant for a period of one year after delivery of therespective unit that all failures caused by faulty material or

-workmanship will be repaired accordingly, provided that theproducts have been-used under normal conditions and byappropriate operation. The a.m. warranty period will be also validfor products being repaired according to this warranty conditionsduring the time of one year. The warranty time will not be pro-longed by repairs.

Claims in connection with supplied goods must be submittedwithin one week of receipt along with the packing slip.Subsequent clai.ms cannot be considered.

AEG will rescind all obligations such as warranty agreements,service contracts etc. entered into by AEG or its representativeswithout notice in the event of maintenance and repairs beingcarried out with anything other than original AEG parts or spareparts purchased by AEG as well as in case of unadequatehandling against instructions of this manual. AEG w-ill not beresponsible for damage outside the used,product caused byinternal failures.

Handling

The realized construction of the CompuMaster allows the userto ctiFy out all necessary steps for erection, commissioningand suitable operation without any internal manipulation.Maintenance and repair of the unit should be performed byqualified skilled personnel.

32

Page 4: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

Illustrations are provided to elucidate and facilitate certain work-steps. If any work possibly involves danger to personnel and theunit, it is highlighted accordingly by pictograms explained inChapter 2, Safety Instructions.

Hotline

Our service department is at your disposal for any questions onthe Hotline number given below:.

.Hotline” : 1p’I AEG Stromversorgungs-Systeme GmbHEmil-Siepmann-S traRe 3 2D - 59581 Warstein

s? (0 29 02) 763 - 100 :FAX (0 29 02) 763 - 1203

Copyright

No part of these operating instructions may be reproduced ortransmitted by any mechanical or electronic means without theexpress prior written permission of AEG.0 Copyright AEG 1996. All rights reserved.

33

Page 5: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

Table of contents

Notes on these operating instructions

Instruction obligation, validity 31Handling, warranty 32Hotline, copyright 33

1 System description 36

2 Safety 382.1 General safety hints 382.2 Safety hints for the

UPS CompWIaster 300 / 600 / 1000 39

3 Technical data 43

4 Commissioning and operation 454.14.24.3

4.44.54.64.6.14.6.24.6.34.6.44.7

Uncasing and testing 45Site conditions 45Principle sketch of connecting pointsand operation/display elements 46Initial start up 47Operation 48Danger signals 49Normal operation 50Battery operation 51Overload conditions 52Troubleshooting 54Communication interface 57UPS management- and shutdown software CompuWatch 58

5 Storage, dismounting and scrapping 595.1 Storage 595.2 Dismounting 595.3 Scrapping 59

35

Page 6: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

1 System description

0 The CompuMaster is an Uninterruptible Power Supply(UPS) for essential loads like PC’s, IT systems andsimilar device, consisting of

- a rectifier (battery charging)- a battery as energy storage device during mains failure

(input supply for the inverter)- an inverter to supply the connected loads when a

mains failure occurs- a static stitch-over circuit to change AC-power supply

from mains to inverter as long as mains is not availableand

- a filter circuit, situated on the mains input

cbzuger

1’1

iwerter

battery

i load

Bloc diagram of a UPS

The UPS has to be connected between mains distributionand the load via standard mains socket.

Under normal operating conditions, i.e. the Compu-Master is supplied by mains, the battery will be fullycharged by the rectifier. Loads connected to the Compu-Master will be supplied with filtered mains voltage.

36

Page 7: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

pm-.---

When mains is not available or in case of decreased mainsvoltage to 85% of nominal value or less the inverter will takeover the supply of the connected loads.

The CompuMaster w-ill supply the load for a time according to thebattery capacity. This autarky time depends in general on theload power. In case of restored mains supply the UPS will switchover the load from inverter to mains operation, i.e. the load willbe supplied by mains again and the battery will be recharged.

In case of a mains blackout the mains input will be automaticallydisconnected by a two-pole-switch to fulfil1 safety requirements ofgerman standards (VDE) and to avoid backfeeding from the inver-ter to the mains.

The availability of the following three protecting functions isguaranteed:

+ Protection against mains blackoutDue to the type of CompuMaster the UPS will provide automati-cally output power up to 3OOVA, 600VA oder IZOOVA for a timebeing sufficient to shut down and switch off the system accor-dingly via shut-down software. The effective autarky time differsindividually and depends in general on the power consumption ofyour connected system load.

+ Protection against mains disturbanceIn case of an input voltage change to less than 85% or more than110% of nominal value, the CompuMaster initialises the change-over to battery operation automatically and supplies the load withAC-voltage to minimize the risk of data loss or damage.

+ Protection against electromagnetical disturbanceDisturbanc.es and problems caused by HF will be reduced by theuse of an EMI filter network

37

Page 8: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

2 Safety regulations

2.1 General safety instructions

Read these operating instructions carefully before initialstart-up of the CompuMaster and pay attention to thesafety instructions in any case !

Use the unit only in a perfect technical state accordingto the intended purpose and subject to the operatinginstructions ! Eliminate failures and any trouble whichcan influence safety of personnel and goods.

The following symbols are used in these operating in-structions to point at possible danger or for any otherreference:

CAUTION !This symbol identifies all working and operationalprocedures requiring absolute compliance to avoid anydanger to personnel.

ATTENTION !This symbol identifies all working and operationalprocedures requiring absolute compliance to preventdanger of hurt to the personnel and any damage, irrepa-rable or otherwise, to the CompuMaster or its comnents.

NOTE !This symbol identifies technical requirements andadditional information requiring the operator’s attention.

38

Page 9: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

i

2.2 Safety hints subject to CompuMastcr 300/400/ 1000

The contents of this chapter are important instructionssubject to the CompuMaster as well as the batteryconcerning erection, operation and maintenance to becomplied with.

The UPS is connected to hazardous voltage. Opening ofthe unit is only allowed to qualified and authorizedpersonnel. Repairs are only allowed to qualified servicepersonnel !

Hazardous voltage may be applied to the output termi-nals as well as mains is not connected, because the UPSwill be still running on it’s internal power supply(battery) !

A/’/ IsDuly earthing of the unit is a must regarding the pro-tection of the personnel !

It is only allowed to connect to and operate the Compu-Master at AC-voltage 230V of a mains distribution withprotective earth by using a VDE-tested or equivalentmains connection cable with protective earth contact(enclosed).

Attention regarding burn (personnel) and fire !The ability of potential high short-circuit currents maylead to melting connectors and firing with the result ofsevere skin burns !

The unit is provided with an acoustic signalling device towarn in case of low battery voltage as well as if the UPSdoes work in an abnormal state (see chapter 4.6, dangersignals).

39

Page 10: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

To keep the UPS in good condition as well as for safeworking with, please pay attention to the followingsafety instructions:

Don’t disassemble the UPS !

The unit is provided for erection inDon’t use the UPS near water or inexcessive humidity !

heated interior.environments with

Never connect mains input terminals to the UPS output !

Please make safe, that no liquids or foreign matter canenter the UPS !

Don’t cover air inlet or outlet of the cabinet ! Please makesafe, that children or other people don’t enter foreignmatter into this cooling openings !

Don’t use the UPS as power supply for householdappliance, e.g. hair drier !

i

Don’t erect the unit near heaters;avoid direkt solar radiation !

The mains wall plug should be situated near the unit:Disconnecting should be possible without problems tosimplify maintaining of the UPS without input voltageavailable !

40 .

Page 11: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

Electric shot hazard ! Despite disconnecting from themains the battery remains still connected to severalcomponents of the UPS, so that the danger of electricshot remains continuously. To avoid unnecessary dangerthe battery-circuit should absolutely be disconnectedprior to maintenance or other business !

A Replacement and maintaining of the battery must be.-.’i’ 4 done by or in attendance of skilled personnel who have

the knowledge about those activities as well as the re-quired preventive actions !

Keep away non-authorized people from batteries !

Replacement of batteries is only allowed by using VRLA-types of the built-in design with the following technicaldata: I 2V/ 7,OAh.

Danger of explosion !Don’t throw batteries into fire. Don’t open batteries andavoid damage, as outcoming electrolyte is toxic andharmful for skin and eyes !

Batteries can cause electric shot and high short-circuitcurrents.

Take the following precautions when handling with bat-teries:

Lay aside wrist-watches, rings and other metal objects !

Use insulated tools only !

41

Page 12: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

For daily use of PC’s or other device the mains switchshould remain in the on-position. It should be avoidedto switch on or off the Computer by using the mainsswitch.

For longer periods without necessity of using the UPSthe mains switch should be set to the off-position. In thecase that the mains distribution will be disconnectedeach evening, the CompuMaster should be switched offtoo to avoid discharging of the battery, because the in-verter will start automatically after mains break down.

To protect the battery aginst damage you never shouldclose the mains switch with disconnected UPS from themains !

The battery will not be charged when the UPS has beenswitched off. Please note chapter 5.1.

42

Page 13: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

3 Technical data

InputRated connection voltageNominal frequencyInput current

230 V50 Hz1,5A2,8 A5,6 A

Connection type

Overvoltage protectionEMI-Filtering

outputNominal load voltageNominal frequencyO u t p u t p o w e r

WaveformLoad connection type

Overload capacity

Overload protection

Autonomy operationSwitch-over timeAutarky time (full load)

AC +lO% -15%_+5%(CompuMaster(CompuMaster

300)600)

(CompuMaster 1000)according to IEC 320cable, connector with earthing contactSpike voltage clamping circuitL-C-Filter aginst EMI

230 V AC50 Hz300 VA (cos cp = 0,67 ind.) / 200 W(CompuMaster 300)600 VA (cos ‘p = 0,67 ind.) / 400 W(CompuMaster 600)1200 VA (cos cp = 0,67 ind) /800 W(CompuMaster 1000)approx. sinewavefemale plug socket accordingto IEC 320HO%,cut off at battery operationElectronic overload monitoringat max. 2OOW / 400W / 800W

< 4,6 ms after mains breakdown- 10 min. (CompuMaster 300)- 4 min. (CompuMaster 600)- 6 min. (CompuMaster 1000)

43

Page 14: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

Battery charging timeBattery type

Efficiency

Physically dataWeight (battery included)-

Dimensions ( W x H x D )(jutting out

connectorsexcluded)

CoolingOperation temperature rangeStorage temperature rangeHumidity

min. 12h to 80%, 48h to 100%VRLA (valve regulated lead acid):1 12V bloc 7,0Ah (300/600VA)2 12V blocs 7,0Ah (1 ZOOVA)90 % 98 % (if mains available)

4,7 kg (CompuMaster 300)4,9 kg (CompuMaster 600)9,3 kg (CompuMaster 1000)1OOmm x 175mm x 185mm(CompuMaster 300 / 600)lOOmmx175mmx36Omm(CompuMaster 1000)Air cooling

5°C to +4O”C-10°C to +4O”Cclass F act. to DIN 40040

max. altitude (at nominal load) up to IOOOm above sea levelEnclosure IP21 act. to DIN 40050Case colour blackInterface Sub-D 9-pole female

44

Page 15: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

4 Erection and operation

4.1 Uncasing and testing

The unit has been fully checked and tested. Althoughpacking and shipping have been prepared carefullyshipping damage is not to be excluded in each case.Please test the incoming goods and shipping containersfor eventually damages, if necessary in presence of thecarrying agent. Note the extend of damages and informyour AEGrepresentative if it is not caused by shipping.Claims in connection with supplied goods must be sub-mitted within one week after receipt along with thepacking slip.

0 Claims caused by shipping must be generally submittedto the carrying agent !

4.2 Site conditions

The CompuMaster is specified for erection and operationin a proper and safe environment. Please carefully lookat sufficient cooling and suitable environmentalconditions.

The CompuMaster is cooled by air. For that reason co-vering of any air- inlet and -outlet should be avoided!The UPS should be operated within an ambient tempera-ture between 15°C and 30°C.

The UPS should be erected in a relatively dust-free roomwithout any content of chemical vapors.

Please check the type plate (rear panel of the Compu-Master) for accordance with the data concerning mainsvoltage and frequency being valuable for your country.

45

Page 16: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

------I_- --- -

4.3 Principle overview of connection points,

operational control and display elements

AEGfi compumastcr xxxx

front view rear side (connections)

Explanations:

1234 -

9IO

11 Load connection via plug-in socket act. to IEC 32012 Mains connection (input) via plug-in socket act. to IEC 32013 Input fuse with integrated spare fuse14 Communication interface (D-Sub9 female - see chapter 4.7)15 Phillips screws (removable cover for battery change)

AEG UPS type identifier ,compuma.ster“apparent power of UPS in VAON-/OFF-switch of UPS (mains switch)

8 Signalisation4 LED ,NORMAL“5 LED &JTONOMY”6 LED ,OVERLOAD“7 LED ,,BATT-LOW”8 LED ,FAULT“ 1

seechapter 4.6(page 49ff.)

Outer case with lock seamBattery cover with technical data of the UPS,serial no. and safety hints

46

Page 17: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

4.4 Initial start-up

Marking of the mains switch (item 3 of pict. on page 46):,,I“ for ,ON” and ,,O” for ,,OFF“

1) Make sure, that the mains switch of UPS is in theOFF-position (item 3 of picture on page 46)

2) Connect the input of UPS (item 12 of pict. on page 46)with the connection cable (female contact) enclosedand plug the connector to a suitable wall plug withearthing contact.

3) Connect the output of the UPS (item 11 of picture onpage 46) to the load. Please use the enclosed secondconnection cable only. The load (e.g. PC) should stillbe switched off.

4) Set the mains switch of UPS to the ON-position.5) The UPS will start with a self test changing automati-

cally to normal operation afterwards. In the case thatthe UPS will be remaining in testing mode, please fol-low the instructions in chapter 4.6 ,,Danger signals“(page 49ff)-

0 If you can’t find any solution concerning the problemoccured, please switch off the equipment completely andcontact your dealer.

6) When the UPS is running in normal operation, pleaseswitch on your load (e.g. PC).

Afterwards the UPS should remain in the ON-position forbattery charging for two days. Thus the battery capacitywill be increased to a normal state.

47

Page 18: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

4.5 Operation

At first the UPS must be connected to a suitable mainswall plug. Then set the mains switch to the ON-position.Following to that procedure output voltage will beavailable. The green LED ,,NORMAL” will be illuminatedor blinking when mains voltage is within nominal range;if not, another LED will be illuminated in connectionwith a sounding danger signal.

In normal operation, i.e. mains voltage is available, theintegrated battery charger will float the battery and theinverter will be set to the stand-by mode by themonitoring. In case of mains blackout as well as with de-creasing mains voltage to 85% or increasing mains volta-ge to 110% the inverter w-ill be set to the stand-alone mo-de supplying the load with AC voltage.

In case of battery undervoltage a danger signal of theUPS will sound for approx. 1 to 3 minutes. Afterwardsthe battery will be disconnected by the UPS.

In this case please switch off the UPS by the mainsswitch asap !

After mains has been restored, the UPS must be switchedon manually by the mains switch for battery charging toovercome the next mains failure.

48

Page 19: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

4.6 Danger signals

Danger signal LED

Normal TVORMALBattery operation AUTONOMYOverload OVERLOADBattery undervoltage BATT-LOWUPS or mains fault FAULT

acoustic signal via integrated signal buzzer!

Explanations to the following used Dictographs:

oc0

33

LED permanently illuminated

LED blinking

LED off

Integrated signal buzzer

49

Page 20: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

4.4.1 Normal operation

I1

-IIILil0

00 03 no sounding

IclLl0

00 no sounding

During normal operation(Battery fully charged):

Under normal conditionsonly LED ,,NORMAL“ isilluminated.

No action required.

During normal operation(Battery being charged):

LED ,,NORMAL” blinking.No action required, but it isrecon-unendated to use theCompuMaster after hatter-ybeing fully charged to besure that the stored energy

will be sufficient for the next mains failure. The charging timewill be in minimum 48 hours.

0 will be blinking.0 no sounding No action required, but

mains voltage might be in

During normal operation(mains undervoltage):

LED ,,NORMAL” will beilluminated. In addition tothat LED ,,AUTONOMY”

an insufficient state (e.g. out of tolerance or exceeding value ofdistortion). This signal has been supplied as supplementaryinformation without any influence concerning the eventualnecessity of automatic change-over to battery operation.

50

Page 21: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

4.6.2 Battery operation

In case of a mains disturbance (e.g. mains blackout)the CompuMaster will be set to battery operationau toma tically.

,

00 sounding

IEl0

BiBi...BiBi...BiBi... I

BiBiBiBi...BiBiBiBi...BiBiBiBi...

Battery operation:

Please finish all your jobsaccordingly and switch offthe PC prior to the automa-tically following action (i.e.disconnecting of battery)and switch off the UPS bythe mains switch.

Battery undervoltage:

The UPS will be switched offwithin 1 to 3 minutes auto-matically. Please finish allyour jobs accordingly andswitch off the PC prior tothe automatically followingaction (i.e. disconnecting ofbattery) and switch off theUPS by the mains switch.

51

Page 22: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

UPS and battery cut-off:

The battery capacity is nomore sufficient. The inverterhas been switched off,output voltage is not yetavailable. Switch off the UPSto avoid further dischargingof the battery!

4.6.3 Overload conditions

In case of overload in connection with the mainsavailable LED ,,NORMAL“ as well as LED ,OVERLOAD“will be blinking. The signal buzzer will sound with aninterruption time of approx. 2 seconds. The connectedloads still will be supplied. It is recommended to finishthis abnormal condition asap to avoid overstressing ofthe battery when a mains failure occurs afterwards. Insuch a case the load supply won’t be guaranteedfurthermore. The load must be reduced till the operatingcondition .NORMAL” is signalled again.

Please make sure generally that overloading also fora short duration will be avoided. Never connect laserprinters or laser fax device to the UPS.

52

Page 23: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

sounding

BiBi...BiBi...BiC..

Normal operation /overload:

C h e c k t h e l o a dStep 1:connected. Depending onthe type of CompuMasterthe value should not exceed:300VA (2OOW), 600VA(4OOW), 1200VA (800W).

R e d u c e t h e t o t a lStep 2:load.

.AI Non-observance of the state ,,OVERLOAD“ can cause totalJ\ : loss of the UPS !

sounding

BiBi...BiBi...BiBi...

Battery operation /overload=

T h e o u t p u t w i l l b eStep 1:switched off immediately.

C h e c k t h e l o a dStep 2:connected. Depending onthe type of CompuMasterthe value shouldn’t exceed:300VA (2OOW), 600VA(4OOW), 1200VA (800W).

Connect the unit according to chapter 4.4, page 47,Step 3:Jnitial start up“.

Following a suitable practiced initial start up normally itshouldn’t be possible getting the problem ,,OVERLOAD“during battery operation.

A Never connect additional loads when output voltage is’ 1

i’ 0 not available !

53

Page 24: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

4.6.4 Troubleshooting

Under normal conditions a self check will be drawn by theCompuMaster itself. By this action charging rectifier andbattery are tested.

When the following symptoms have been detected, theCompuMaster will not supply output voltage at this moment.

0

03,))0 sounding

BiBi...BiBi...BiBi...

0

0 El0

0# 03 $1 sounding

BiBiBiBi...BiBiBiB...iBiBiBiBi...

0

0

IaH0

0 * 63 $) s o u n d i n g

BiBiBiBiBiBiBiBiBiBiBiBi...

Inverter fault:

Finish all your jobs, switchoff the UPS and unplug themains connector from thewall plug Please contactyour dealer.

Charger fault:

Finish all your jobs, switchoff the UPS and unplug themains connector from thewall plug. Please contactyour dealer.

Battery fault:

Finish all your jobs andcontact your dealer forbattery changing.

54

Page 25: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

The last of a.m. faults (battery fault) looks like a discon-nection of the battery, but it has been detected duringnormal operation.

In case of a continuously sounding danger signal after the settingof the mains switch to position ,,I“ and following the UPS selfcheck, it is possible, that no voltage is available at the mains wallplug. Please check this device by connecting another load insteadof the UPS (e.g. a light).

Rem.: the initial start up of the UPS without mains available isnot assigned by the manufacturer with respect to suitablebattery protection !

Switching on withoutmains available:

Switch off the UPS andcheck mains voltage, fre-quency and mains fuse. If

0

aI89sounding

the input voltage is within0

BiBiBiBiBiBiBiBiBiBiiBi...the allowed range pleasefinish all your jobs, switch

off the UPS and unplug the mains connector from the wall plug.Please contact your dealer.

The mains switch must be set to the OFF-position if theCompuMaster is not connected to the mains. If the mainsswitch still remains in the ON-position without mainsavailable the battery will be smoothly discharged. Thiscircumstances can lead to permanent damage if the unitremains more than two days at this state.

55

Page 26: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

In the case that the mains distribution will be switchedoff every evening the same must be done with the UPS toavoid unnecessary battery discharge. Otherwise the in-verter will be started automatically because for the UPSit seems to be a mains failure.

This w-ill lead to a reduction of the usable life of thebattery.

Caused by completely discharged battery (e.g. unithadn’t been switched off by mistake despite a long-lasting mains failure or because of the self-dischargenature of the battery during a longer storage period)unlogical signalling states eventually may occur. Thiscan be normally eliminated without problems and hasno influence on the reliability of the UPS later on.

If the LED ,,BATT.-LOW” is blinking after switching onthe UPS the unit should stay at this state for approx. 3hours with respect to battery charging. Afterwards theUPS must be switched off for approx. 1 minute. Follo-wing this procedure the UPS should be switched onagain. Now only LED “NORMAL” should be blinking.

56

Page 27: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

4.7 Communication interface(Connection of PC’s and signalling device)

The interface of the CompuMaster is designed for use in additionto the shut-down options of AEG.

Interface (SUB-D-plug g-pole)Relais contacts will be si,mulated via RS232interface by usingtransistor technologie. For explanation of pin configuration seethe following table:

pin

1

2

3

.4

5

6

7

8

9L

function

unused

output

unused

common 1

output

input

common 2

unused

unused

mode

mains fault (pins 2-4 closed)

common for pins 2 and 5

battery undervoltage (pins 5-4 closed)

UPS off (+5V DC)

common for pin 6

Operational voltage max. 15V DC (5OmA), inductionfree.This signal is needed at pin 6 for approx. 2s to switch off the UPS

57

Page 28: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

r 1 communication interface:I

El0With ,,High“-potential atpin 6 of the communicationinterface, e.g. initialized

0

al

automatically by AEG soft-0 no sounding ware ,,CompuWatch“, the

load will be disconnected- and the UPS will be shut down. To avoid deep discharge of the

battery caused by the remaining load of the UPS control it isrecommended to switch off the UPS completely by the mainsswitch immediately.

UPS shut down via pin 6 of

UPS management and shut down software ,CompuWatch”

- autom. UPS monitoring

- User Info

- power restored chec- ,emergency“ Shut down

with UPS battery low signal

- logging funktions

b/w representation of user’s menue

The optional software will be available like a disk, CD-ROM ortape for different types of Operating Systems, e.g. Windows 3.x,Windows 95, Windows NT, OS/Z, Novell Netware, IBM AIX,HP-UX, Sun Solaris, . . .

The software will be delivered with detailed setup instructionsdescribed in a german/english version of a manual in additionwith a suitable comunication cable ready for connection.

Please contact your distributor who will help you readily concer-ning the choice of the needed software version.

58

Page 29: AEG - Conrad  · PDF fileAEG POWER SUPPLY SYSTEMS Unterbrechungsfreie Stromversorgung Uninterruptible Power Supply CompuMaster 300/ 600/ 1000 Betriebsanleitung Operating Manual

5 Storage, dismounting and scrapping

5.1 Storage

.A1l

0

Longer storage periods without charging may lead topermanent damage of the battery.

Because of inner chemical activity during storage withina temperatur range from 20°C to 30 O C the self-dischargerate will be approx. 3...6% of nominal capacity permonth. It is recommanded to store VRLA-batteries attemperatures below 20°C because the allowed non-charging period will be much longer.

To preserve full capacity, batteries should be rechargedeach 6 months when stored at 20°C. For a storagetemperature of 0°C the equivalent value would be24 months.

Prior to a longer storage period the CompuMaster shouldbe connected in normal operation without any load to themains for 48 hours to make sure a fully charged battery.

5.2 Dismounting

Dismounting of the CompuMaster is to be made viceversa to the sequence discribed in chapter 4.

5.3 Scrapping

At the end of useful life of the unit please make surea suitable scrapping of all components according tonational / international rules concerning disposal andrecycling with respect to an effective environmentalprotection.

59