Advanced Universal Harmonic FilterAdvancdvaancnced …admeng.ca/files/AHUF Brochure 05-2012.pdf ·...
Transcript of Advanced Universal Harmonic FilterAdvancdvaancnced …admeng.ca/files/AHUF Brochure 05-2012.pdf ·...
LINEATOR TMTMPatentedPatented
Revolutionary New Reactor DesignRevolutionary New Reactor DesigRevolutionary New Reactor DesignnRevolutionary New Reactor Design
Advanced Universal Harmonic FiilltterAdvanced Univeersal Harmonic FilterAdvanced Universal Harmonic FilterAdvanced Universal Harmonic Filternced Universal Harmonic FilterAdvanced Universal Harmonic Filter
The most energyThe most energyefficciieent harrmmoonniiccsoluuttiioon forr VVSDDD sssoluuuttiioon forr VVSSDDDD`̀ss
The most energy efficient harmonic solution for VSD`s
Freeess uupp ssyysstteemmp c y y restoringgccaappaaciitty bby restoringgVSDD to neeeaaaaaaaaaarrrr uuuuuuuunityyyyyyy
ppppppoooooowwwwweeeeeeerrrrr fffffffffaaaaaaacccccccctttttttooooooooorrrr
Frees up systemcapacity by restoring
VSD to near unitypower factor
MMMMMMeeeeeeeeeeeettttttssssss hhhhhhaaaaaarrrrrrmmmmmmmooooooonnnniiiicccccc llllllliiiimmmmiiiittttssfffffooooorrrrr bbbbooooootttthhhh llllaaaaannnndddd aaaannnnnndddddd mmmaaaarrrriiinnneee
VVVVSSD applicccationss
Meets harmonic limitsfor both land and marine
VSD applications
Lowww ccaappaaccciiiiittttttiiiivvvvveeeeeeerrrrrreeeeeeaaaaaaaccccctttttaaaaaaaaaannnnnnnnccccccccceeeeeeee eeeeeeeeeennnnnnnnsssssssuuuuuuuuurrrrrreeeeeeeeeeesssss
gggeeeeeeeeeennnnnnnnnneeeeeerrrraaaaaattttooooorrrr cccccccccccoooooooommmmmmmmppppppppppppaaaaattttttiiiiibbbbbbiiilllliittttyyyy
Low capacitivereactance ensures
generator compatibility
International Inc.R
‘Wide Spectrum Harmonic Filter’ for treatment of all harmonicsgenerated by 3-phase diode or thyristor bridge rectifiers
ggssss
Total Demand Distortion (TDD) of the current at the LINEATOR input terminals will not exceed the limits as defined in Table 10.3 of IEEE Std 519
Power factor 0.95 leading to 0.98 lagging over the normal operating range (40 to 100% load)
Will not resonate with other power system components or attract line side harmonics
Suppresses overvoltages caused bycommutation notching, capacitor switching and other fast changing loads
Removal of harmonics improves overall system power factor
Reduces conducted RF interference generated by VSD
Models available for AC Drives and DC Drives or other controlled rectifiers
FeaturesFeatures
18-PulsePerformancefrom standard6-Pulse VariableSpeed Drives
18-PulsePerformancefrom standard6-Pulse VariableSpeed Drives
Up to 3% moreenergy efficientthan 18-Pulsesolutions
Up to 3% moreenergy efficientthan 18-Pulsesolutions
Will meet IEEE 519standard for bothcurrent andvoltage distortion
Will meet IEEE 519standard for bothcurrent andvoltage distortion
ABS Type Approved for marine applications
ABS Type Approved for marine applications
The evolution of microproccessor based power electronic Variable Speed Drives (VSD) has progressed very rapidly over the past 20 years. With this growth has come concern over the level of current harmonics generated by these nonlinear loads. Harmonic currents increase losses, overheat electrical equipment and interact with the distribution system impedances causing voltage distortion which can have a detrimental effect on all equipment connected to the system.
Present methods of harmonic treatment (line reactors, multi- pulse systems, tuned or broadband passive filters, active filters and active-front-end drives) are often very large, unreliable, moderately effective, inefficient or too expensive.
The LINEATOR Advanced Universal Harmonic Filter (AUHF) is a revolutionary advance in the area of passive harmonic mitigation. No other device on the market can meet the stringent limits of IEEE Std 519 at an equivalent efficiency, size and cost.
When your application calls for a truly cost effective harmonic solution, the LINEATOR AUHF is the logical choice. It provides Engineers with a standard off-the-shelf solution for what used to be a very challenging engineering problem.
Wide Spectrum Harmonic Filter treats all major harmonics generated by VSD’s and other 3-phase rectifier loads
Suitable for application on multiple VSD’s provided only VSD’s are connected
Guaranteed to meet IEEE Std 519 for both current and voltage distortion at the input terminals of the LINEATOR
Compatible with engine driven generators thanks to the extremely low capacitive reactance, even at no load
Saves energy by reducing upstream harmonic losses while operating at >99% efficiency
Low capacitive reactance also eliminates the need for capacitor switching contactors (contactors are available upon request)
Advanced UniversalHarmonic Filter (AUHF)
. Oil and Gas industry. Water and Waste Water. Irrigation systems. HVAC systems. Mining operations. Marine vessels. Printing presses. Elevators and escalators . Pulp and paper processing
Other applications include:. Induction furnaces. Industrial rectifiers. Welding operations
The LINEATOR is a purely passive device consisting of a revolutionary new inductor combined with a relatively small capacitor bank. It's innovative design achieves reduction of all the major harmonic currents generated by VSD's and other similar 3-phase, 6-pulse rectifier loads. The resulting ITHD is reduced to <8% and often as low as 5%. Although referred to as a filter, the LINEATOR exhibits none of the problems that plague conventional filters.
Harmonic Distortion ReductionThe filtering effectiveness of a trap filter is dependent upon the amount of harmonics present at untuned frequencies as well as the residual at the tuned frequency. To obtain performance better than 15% ITHD, multiple tuned branches are often required. Other broadband filters require relatively large capacitor banks (2 to 3 times more than Lineator) to achieve reasonable performance.
Harmonics from other sourcesAs a parallel connected device, the conventional trap filter has no directional properties. It therefore, can easily be overloaded by attracting harmonics from upstream non-linear loads. The LINEATOR, on the other hand, will present a high impedance to line side harmonics eliminating the possibility of inadvertent importation and overloading.
System ResonanceAt frequencies below its tuned frequency, a conventional filter will appear capacitive. This capacitance has the potential of resonating with the power systems natural inductance. When a filter is tuned to a higher order harmonic, such as the 11th, it could easily resonate at a lower harmonic frequency, such as the 5th or 7th. The natural resonance frequency of the LINEATOR is below that of any predominant harmonic, therefore inadvertent resonance is avoided.
Capacitive Reactance and Leading Power FactorThe large capacitor banks in trap filters and competing broadband filters present a high capacitive reactance to the system, especially under light loads. On weak power systems, this can raise voltages or cause excitation control problems in generator applications. To address this, some filter manufacturers offer mechanisms for switching out the capacitors under light loads, increasing cost and complexity. This is not necessary for the LINEATOR because even under no load conditions, it’s capacitive reactance (kVAR) remains below 15% of its kVA rating. This ensures compatibility with engine generators, without the need to switch out capacitors.
Competitor FilterkVAR Curve (Typical)
LINEATOR AUHFkVAR Curve (Typical)
AcceptableOperating
Range
Generator Reactive Power Capability Curve
Apply LINEATOR anywhereVariable Speed Drives and6-Pulse Rectifiers are used
Apply LINEATOR anywhere Variable Speed Drives and 6-Pulse Rectifiers are used
LINEATOR over otothher Passive FiltersAdvantages of the LINEATOR over other Passive Filters
As background voltage distortion increases, the harmonic mitigating performance of the 18-Pulse VSD degrades much quicker than the 6-Pulse / LINEATOR combination. This demonstrates that the LINEATOR AUHF will not attract harmonic currents as other non-linear loads distort the applied voltage waveform. LINEATOR is the only harmonic solution that guarantees performance even in heavily distorted environments.
The 6-Pulse VSD / LINEATOR combination has 2% to 3% higher efficiency than the 18-Pulse solution over the entire operating range. (Efficiency shown is for a system that includes motor/gen set load, VSD, and harmonic mitigation equipment). When compared to an 18-Pulse VSD, a 400HP AUHF/VSD will save more than $3,000 in annual operating costs when averaging 75% loading at $0.07/kWHr.
The unique design of the AUHF produces extremely low losses. It’s operating efficiency therefore is much higher than competitive filters. The graphs below show typical losses and efficiencies for AUHF and two competitors. (AUHF is available in sizes up to 3500HP. Since competitor maximum sizes are only 600HP and 900HP, the chart range has been set at 1000HP)
There is little degradation in harmonic mitigating performance of the 6-Pulse / LINEATOR combination as voltage imbalance increases. The 18-Pulse solution, on the other hand, degrades dramatically because harmonic cancellation due to phase shifting becomes much less effective with 3-phase voltage imbalance.
Outperforms 18-P Solutions
Compare Performance!Compare Performance!The LINEATOR outperforms all other forms of VSD harmonic solutions. By choosing the LINEATOR you have selected a filter that:
• performs in Real World environments even with background voltage distortion and voltage imbalance
• lowers operating costs by being highly efficient
• is compatible with engine generators and incorporates a low capacitive reactance design
• has a simple and compact design to reduce footprint and ensure reliability
• can be computer modeled to provide up front assurance of meeting harmonic limit standards such as IEEE Std 519, ABS and other marine certifying bodies
• is factory performance tested under actual VSD loading
VSD Input Current Waveform and Spectrum with no reactor.
VSD Input Current Waveform and Spectrum with AC reactor.
VSD Input Current Waveform and Spectrum with LINEATOR AUHF.
Efficiency ComparisonnEfficiency Comparison Improves VSD PerformanceImproves VSD Performance
95%
96%
97%
98%
99%
100%
0 500 1000
Effic
ienc
y at
FL
Filter Size (HP)
Harmonic Filter Comparison - Efficiency
Lineator AUHF Competitor1 Competitor2
0
1000
2000
3000
4000
5000
6000
0 500 1000
FL L
osse
s (W
)
Filter Size (HP)
Harmonic Filter Comparison - Typical Losses
Lineator AUHF Competitor1 Competitor2
PerformancePerformance
ITHD = 81%
ITHD = 29%
ITHD = 4.6%
The Harmonics & Energy (H&E) Lab at MIRUS International Inc. provides the unique ability to test our products under ‘real world’ non-linear load conditions. We also conduct compatibility testing with all major VSD manufacturers' products to ensure a trouble-free installation.
Every LINEATOR is factory tested under VSD load to ensure our performance guarantee is met. No other manufacturer provides this level of testing whether they offer a passive filter, multi-pulse or active solution.
y yununder VSVSVSDD D load to eeensure ooour pepepp rfrfrforormam nce guuarararananantetetee e isi mmmeeet. No otototthehehher rr r mamamam nunuufaf ctururerer pprorovidedess ththththisissleeevevevvel l ofofofof t t t tesesestititingnggg ww heeththere they offer aa papapapasssssssivivivive e e e fifif ltltlterere , , mumultti-i-pup lslse e or active sosososoluluuutitititionononon..
MIRUS guarantees that the LINEATOR AUHF will perform as advertised to reduce harmonic distortion caused by AC Variable Speed Drives and other non-linear loads equipped with 3-phase, 6-pulse, diode bridge rectifiers. A properly selected and installed LINEATOR will:
Reduce Current Total Harmonic Distortion (ITHD), measured at the LINEATOR input terminals at full load, to:(i) <8% when background voltage
distortion is <5% and voltage imbalance is <3%
(ii) <5% when short circuit ratio (Isc/IL), as defined by IEEE Std 519, is <20 and when background voltage distortion is <0.5% and voltage imbalance is <1%
(iii) Reduce Current Total Demand Distortion (ITDD), measured at the LINEATOR input terminals over its entire operating range, to levels defined in Item (i) above. ITDD is defined as the ratio of ITHD divided by the full load current (peak demand current) of the LINEATOR.
(iv) Minimize the contribution to Voltage Harmonic Distortion of all VSD’s equipped with the LINEATOR to <5% total and <3% for individual harmonics, as defined by IEEE Std 519-1992.
(v) NOT become overloaded by other upstream harmonic sources.
(vi) NOT resonate with other power system components.
(vii) NOT have compatibility problems with engine generator sets properly sized for the load.
'Performance Guarantee'MIRUS offers proprietary software called Simulation of LINEATOR / VFD (SOLV). SOLV is a powerful and unique computer simulation program that will calculate current and voltage distortion levels based on your load requirements.
By simply entering some basic information about your source and VSD system, you can generate very useful reports such as, an IEEE 519 Compliance Report. In addition to the accurate reports, you can print a single line representation of your system along with voltage and current waveforms and spectrums.
MIRUS' SOLV will help you find the right solution for your VSD application without the need of a costly harmonic study. It can be downloaded at mirusinternational.com
Simulation ooff LINEATOR / VFDSimulation of LINEATOR / VFDSOLVSOLV&H&E LAB TMTMTMTM
General Specificatioonns:General Specifications:Rating Tables: (type ‘D’ Lineator)Rating Tables: (type ‘D’ Lineator)
Typical LINEATOR ApplicationsTypical LINEATOR Applications
HP / kW RATING: Available for motor/drive system sizes up to 3500HP / 2600kWVOLTAGE: Standard voltages up to 690V, 3-phaseFREQUENCY: 50 or 60HzOVERLOAD CAPABILITY: Suitable for overload of 150% for 60 seconds every 10 minutesHARMONICS TREATED: 5th, 7th, 11th, 13th, ...K-FACTOR SUITABILITY: Up to 20INPUT K-FACTOR: Reduced to <1.5INPUT CURRENT DISTORTION: <8% at full loadNO LOAD CAPACITIVEREACTANCE (kVAR) LEVELS: 5 to 75HP 15 to 20% 100 to 3500HP 10 to 15%EFFICIENCY: >99%ELEVATION: 3300ft [1000m] above sea levelVENTILATION: Convection air cooledENCLOSURE: NEMA 3R [IP23] Paint: Polyester powder coated Color: ANSI 61 GreyOPTIONS: Nema 3R [IP23] Enhanced ABS, DNV or Lloyds Certification
HP kW 208V 220/240V 380/400V 415/440V Output Case Weight Case Weight Case Weight Case Weight kW Style lbs [kg] Style lbs [kg] Style lbs [kg] Style lbs [kg] 5 4 14 13 8 7 4.5 SU1 65 [30] SU1-E 75 [34] 58 [26] 68 [31] 7.5 5.5 20 18 11 10 6.3 76 [35] 86 [39] SU1 67 [30] SU1-E 77 [35] 10 7.5 27 24 14 13 8.5 80 [36] 80 [36] 78 [35] 88 [40] 15 11 40 36 21 19 13 SU2 117 [53] SU2-E 127 [58] 90 [41] 100 [45] 20 15 53 48 28 25 17 138 [63] 148 [67] 118 [54] SU2-E 128 [58] 25 18.5 66 60 35 32 21 154 [70] 164 [74] SU2 130 [59] 140 [64] 30 22 79 72 42 38 25 189 [86] SU3-E 199 [90] 142 [65] 152 [69] 40 30 105 95 55 51 34 SU3 253 [115] 263 [119] 154 [70] 164 [74] 50 37.5 131 119 69 63 42 275 [125] 333 [151] 186 [84] SU3-E 196 [88] 60 45 158 143 83 76 51 315 [143] MT2-E 337 [153] SU3 218 [99] 228 [103] 75 55 196 178 103 95 63 325 [148] 399 [181] 304 [138] 314 [142] 100 75 260 236 137 125 84 MT2 442 [201] 516 [235] 323 [147] MT2-E 414 [188] 125 90 323 294 170 156 104 468 [213] MT3-E 542 [246] MT2 345 [156] 434 [197] 150 110 388 353 204 187 125 553 [251] 627 [285] 365 [166] MT3-E 469 [213] 200 150 274 250 168 415 [189] 514 [234] 250 185 340 312 209 MT3 578 [262] MT4-E 600 [273] 300 200 410 374 251 585 [266] 670 [305] 350 250 475 436 292 MT4 800 [363] 1006 [456] 400 315 565 520 349 825 [374] LT1-E 1031 [467] 500 400 720 660 443 915 [415] 1121 [508] 600 450 810 740 499 LT1 1098 [499] LT2-E 1176 [535] 700 500 940 865 579 1700 [771] 1839 [834] 800 560 1075 985 662 LT2 1882 [854] 1954 [886] 900 630 1200 1100 736 1920 [871] LT3-E 2054 [931] 1000 710 1335 1220 818 1950 [884] 2084 [945] 1100 800 1470 1340 900 2465 [1118] 2564 [1163] 1200 900 1610 1470 987 LT3 2568 [1167] 2958 [1245] 1300 970 1735 1585 1064 2718 [1236] 3408 [1549] 1400 1000 1870 1710 1145 2858 [1299] HT2-E 3548 [1613] 1500 1120 2000 1835 1228 3598 [1635] 3690 [1677] 1600 1200 2145 1965 1316 3748 [1703] 3840 [1745] 1800 1350 2410 2210 1481 HT2 3848 [1749] 4376 [1943] 2000 1450 2670 2440 1636 3978 [1808] 4506 [2048] 2300 1700 3065 2810 1882 4075 [1850] HT3-E 4600 [2088] 2500 1850 3335 3050 2045 4650 [2111] 4750 [2157] 2800 2100 3750 3435 2303 HT3 5000 [2270] 5100 [2315] 3000 2250 4020 3680 2468 5225 [2372] 3500 2600 4265 3905 2618 5550 [2520]
Motor Size Lineator Rating 208V (50 or 60Hz), 240V (50Hz) 400, 440V (50Hz) Input Amps (3-Phase) Standard Enclosure Enhanced Enclosure Standard Enclosure Enhanced Enclosure
HP kW 460/480V 575/600V 660/690V Output Case Weight Case Weight Case Weight Case Weight kW Style lbs [kg] Style lbs [kg] Style lbs [kg] Style lbs [kg] 5 4 7 5 5 4.5 58 [26] 68 [31] 57 [26] 67 [30] 7.5 5.5 9 7 6 6.3 SU1 67 [30] SU1-E 77 [35] 67 [30] SU1-E 77 [35] 10 7.5 12 10 8 8.5 78 [35] 88 [40] SU1 77 [35] 87 [39] 15 11 17 14 12 13 90 [41] 100 [45] 86 [39] 96 [44] 20 15 23 18 16 17 118 [54] 128 [58] 98 [45] 128 [58] 25 18.5 29 23 20 21 130 [59] SU2-E 140 [64] 125 [57] SU2-E 135 [61] 30 22 34 28 24 25 SU2 142 [65] 152 [69] 137 [62] 147 [67] 40 30 46 37 32 34 154 [70] 164 [74] SU2 149 [68] 159 [72] 50 37.5 57 45 40 42 186 [84] 196 [89] 184 [83] 196 [89] 60 45 69 55 48 51 218 [99] SU3-E 228 [103] 206 [94] SU3-E 216 [98] 75 55 85 68 59 63 SU3 304 [138] 314 [142] 298 [135] 308 [140] 100 75 113 90 79 84 323 [147] 333 [151] SU3 315 [143] 325 [147] 125 90 141 112 98 104 345 [156] MT2-E 419 [191] 345 [156] MT2-E 419 [191] 150 110 169 135 118 125 MT2 365 [166] 439 [200] MT2 365 [166] 439 [200] 200 150 226 180 158 168 415 [189] MT3-E 489 [222] 415 [189] MT3-E 489 [222] 250 185 281 225 196 209 MT3 578 [262] 640 [290] MT3 578 [262] 640 [290] 300 200 337 270 235 251 585 [266] MT4-E 695 [316] 585 [266] MT4-E 695 [316] 350 250 395 315 275 292 800 [363] 1006 [456] 780 [354] 1006 [456] 400 315 470 375 325 349 MT4 825 [374] 1031 [467] MT4 805 [365] 1031 [467] 500 400 595 475 415 443 915 [415] LT1-E 1121 [508] 915 [415] LT1-E 1121 [510] 600 450 670 535 470 499 LT1 1398 [634] 1476 [ 670] LT1 1398 [634] 1476 [670] 700 500 780 625 545 579 1700 [771] LT2-E 1839 [834] 1650 [748] LT2-E 1740 [789] 800 560 890 715 620 662 1882 [854] 1954 [886] 1805 [819] 1852 [842] 900 630 990 795 690 736 LT2 1920 [871] 2054 [931] LT2 1882 [854] 2054 [932] 1000 710 1100 880 770 818 1950 [884] LT3-E 2084 [945] 1915 [869] LT3-E 2064 [936] 1100 800 1210 970 845 900 2465 [1118] 2564 [1163] 2331 [1057] 2515 [1141] 1200 900 1330 1060 925 987 LT3 2568 [1167] 2958 [1245] LT3 2465 [1121] 2855 [1298] 1300 970 1430 1145 1000 1064 2718 [1236] 3408 [1549] 2609 [1186] 2999 [1363] 1400 1000 1540 1235 1075 1145 2858 [1299] HT2-E 3548 [1613] 2782 [1265] HT2-E 3172 [1442] 1500 1120 1650 1325 1155 1228 3598 [1635] 3690 [1677] 3540 [1606] 3620 [1642] 1600 1200 1770 1415 1235 1316 3748 [1703] 3840 [1745] 3702 [1679] 3800 [1724] 1800 1350 1990 1595 1390 1481 HT2 3848 [1749] 4376 [1943] HT2 3798 [1723] 3875 [1758] 2000 1450 2200 1765 1535 1636 3978 [1808] 4506 [2048] 3945 [1789] 4250 [1928] 2300 1700 2530 2030 1765 1882 4075 [1850] HT3-E 4600 [2088] 4015 [1821] HT3-E 4340 [1969] 2500 1850 2755 2205 1920 2045 4650 [2111] 4750 [2157] 4600 [2087] 4750 [2155] 2800 2100 3100 2480 2160 2303 HT3 5000 [2270] 5100 [2315] HT3 4945 [2243] 5100 [2313] 3000 2250 3320 2660 2315 2468 5225 [2372] 5180 [2350] 3500 2600 3855 3085 2685 2618 5550 [2520] 5490 [2490]
Motor Size Lineator Rating 480V (60Hz), 600V / 690V (50Hz) 600V / 690V (60Hz) Input Amps (3-Phase) Standard Enclosure Enhanced Enclosure Standard Enclosure Enhanced Enclosure
InputInput
Input
VSD System with Bypass*
Multiple VSD System
VSD
VSD VSD
MOTOR MOTOR
StandaloneVSD System
VSD
LINEATORAUHF
TM LINEATORAUHF
TM
LINEATORAUHF
TM
* When the VSD requires a bypass, the LINEATOR must also be bypassed as shown.
1. For type ‘T’ Lineator use enclosure and weights from the next size up.
MOTOR MOTOR
MOTOR
VSD
[1][1]
A1 B1 C1A2 B2 C2
A3 B3 C3
DimensionsDimensions
FRONT VIEW RIGHT SIDE VIEW
F 1.00TYP .
1.00TYP .
CD
E
B
A
‘MT3’, ‘MT4’, ‘LT’ ENCLOSURE
‘E0P’ PANEL MOUNT‘HT’ ENCLOSURE ‘E0’ OPEN STYLE ‘E0M’ MODULAR
5to
3500
208240400440480600690
(VAC)
AdvancedUniversalHarmonicFilter
5060
DDiode Bridge
RectifierT
Thyristor BridgeRectifier
E0No Enclosure
(250 to 3500HP)EOP
Panel Mount(5 to 200HP)
EOMModular
(250 to 3500HP)E1
Nema 3R [IP23]Ventilated
(5 to 3500HP)
AUHF HPE
Nema 3R[IP23]
Enhanced
Model MotorHorsepower
LineVoltage
Frequency LoadType
EnclosureType
Optional
VVV Hz L En O- - - - - -
Ordering InformationOrdering Information
GA
B C
E F
DH
FRONT VIEW BACK VIEWRIGHT SIDE VIEW
7.75
2.25
3.5
A
6.50 Typ.
B CD
E FFRONT VIEW RIGHT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW
A3 B3 C3
A2 B2 C2
A1 B1 C1
Cap. Fuse
Cap. Fuse
Cap. Fuse
Cap. Fuse
Cap. Fuse
Cap. Fuse
A3 B3 C3Cap. Fuse
Cap. Fuse
Cap. Fuse
Cap. Fuse
Cap. Fuse
Cap. Fuse
FRONT VIEW FRONT VIEWRIGHT SIDE VIEW CAPACITOR BOARD(Supplied loose)
A1 B1 C1A2 B2 C2
A3 B3 C3
Standard Enhanced A B C D E F G H SU1 SU1-E 23.50 [597] 11.25 [286] 8.75 [222] 11.25 [286] 8.00 [203] 9.00 [229] 13.00 [330] 9.00 [229] SU2 SU2-E 29.50 [749] 13.25 [336] 10.25 [260] 12.75 [324] 9.00 [229] 10.00 [254] 19.00 [483] 11.00 [279] SU3 SU3-E 34.00 [864] 20.25 [514] 13.25 [336] 16.00 [406] 17.50 [445] 13.00 [330] 20.00 [508] 18.00 [457] MT2 MT2-E 38.00 [965] 21.50 [546] 19.50 [495] 23.50 [597] 17.00 [432] 17.50 [445] 25.00 [635] MT3 MT3-E 45.00 [1143] 26.00 [661] 21.00 [534] 25.00 [635] 21.50 [546] 19.00 [483] MT4 MT4-E 51.50 [1308] 32.00 [813] 25.50 [648] 29.50 [749] 23.50 [597] 23.50 [597] LT1 LT1-E 59.00 [1499] 39.50 [1003] 30.00 [762] 34.00 [864] 24.00 [610] 32.00 [813] LT2 LT2-E 66.00 [1677] 44.00 [1118] 34.00 [864] 38.00 [965] 26.00 [660] 36.00 [915] LT3 LT3-E 75.00 [1905] 48.50 [1232] 39.00 [991] 43.00 [1092] 27.50 [699] 41.00 [1041] HT2 HT2-E 78.00 [1981] 58.50 [1486] 51.00 [1295] 56.25 [1428] 52.50 [1333] 50.75 [1289] HT3 HT3-E 84.00 [2134] 68.50 [1740] 59.00 [1499] 64.50 [1638] 62.50 [1587] 58.75 [1492]
CASE STYLE DIMENSIONS - inches [mm]
‘SU’ ENCLOSURE ‘MT1’, ‘MT2’ ENCLOSURE
H
A G
CD
B
E F
FRONT VIEW BACK VIEWRIGHT SIDE VIEW
1. ‘D’ type AUHF is suitable for standard diode bridge and diode/SCR precharged front-end VSD’s.2. ‘T’ type AUHF is suitable for DC drives, Current Source Inverters and other controlled rectifier loads.
[1]
[2]
Mirus International Inc. All specifications subject to change without notice.C
AUHF-PS01-A1Effective: August 2007
R
To discuss how MIRUS can help youmeet your power quality challenges,contact us at our head office:
MIRUS International Inc.31 Sun Pac Blvd.Brampton, OntarioCanada L6S 5P6
Tel: (905) 494-1120Fax: (905) 494-1140Toll-Free: 1-888-TO MIRUS (888-866-4787)
www.mirusinternational.com
Real-world performancefor real-world loads.Real-world performancefor real-world loads.
Harmonic and Energy SolutionsHarmonic and Energy Solutions
Expect better. Call us.
International Inc.R
MIRUS International Inc. 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6
TYPICAL SPECIFICATION THE LINEATOR™ Advanced Universal Harmonic Filter (AUHF)
MIrus International Inc. [2010-01-06] 1-888-TO MIRUS www.mirusinternational.com AUHF-TS001-A2
PART 1 – GENERAL
1.1 All PWM AC Variable Frequency Drives of [ 30 ] hp and above shall be equipped with harmonic mitigation equipment to prevent power system problems resulting from high levels of harmonic distortion. .1 The harmonic mitigation equipment and all of its components shall be manufactured and tested in accordance with
the latest applicable standards of UL, CSA and NEMA. .2 Demonstration of compatibility between the harmonic mitigation equipment and the VFD must be available upon
request. .3 Harmonic mitigation equipment shall be warranted to be free of defects in materials and workmanship for a period of
3 years from the date of shipment. .4 Factory Performance Testing: Manufacturer must be capable of factory testing for harmonic mitigating performance
and energy efficiency under actual variable frequency drive loads. A detailed description of the program and a sample test report must be provided at time of quotation.
.5 Subject to compliance with all of the contract documents and specifications, the acceptable product and manufacturer is: LINEATOR™ AUHF, by MIRUS International Inc. (905) 565-6900, Toll Free: (888) 866-4787
PART 2 - PRODUCT
2.1 Key Requirements: .1 The harmonic mitigation equipment shall treat all of the characteristic low frequency harmonics generated by a 3-
phase, diode bridge rectifier load (5th, 7th, 11th, 13th, etc.). .2 The characteristic harmonics shall be suppressed without the need for individual tuning or the requirement to phase
shift against other harmonic sources. .3 Harmonic mitigation shall be by passive inductor/capacitor network. Active electronic components shall not be used. .4 Power factor shall be .98 lagging to .95 leading in operating range from full to half load. .5 To ensure compatibility with engine generators, the harmonic mitigation equipment must never introduce a capacitive
reactive power (KVAR), which is greater than 20% of its kVA rating. .6 The harmonic mitigation equipment shall not resonate with system impedances or attract harmonic currents from
other harmonic sources. .7 The harmonic mitigation equipment in combination with the Variable Frequency Drive shall meet all requirements as
outlined in the 1992 edition of IEEE std 519 for individual and total harmonic voltage and current distortion. The Point of Common Coupling (PCC) for all voltage and current harmonic calculations and measurements shall be the input terminals to the harmonic mitigation equipment.
.8 Total Harmonic Voltage Distortion (THVD) shall meet the requirements of Table 10.2 of IEEE std 519 by not exceeding 5% and by limiting the individual harmonic voltage distortion to less than 3%. These limits shall apply while operating on either utility supply or generator supply when applicable. The harmonic mitigation equipment vendor shall not be responsible for pre-existing voltage distortion caused by other harmonic sources.
.9 Total Demand Distortion (TDD) of the current at the input terminals of the harmonic mitigation equipment shall not exceed the limits as defined in Table 10.3 of IEEE std 519. For Isc/IL ratio < 20, TDD must be less than 5%. For all other Isc/IL ratios, the TDD must not exceed 8% even when Table 10.3 allows for more relaxed limits. For single-phase applications, the TDD must not exceed 12%.
.10 The full load efficiency of the harmonic mitigation equipment / VFD combination shall be greater than 96%. The harmonic mitigation equipment itself shall have efficiency no less than 99%.
2.2 Basic Requirements:
.1 All wiring shall be copper.
.2 Insulation class: 220°C system. Temperature rise: 130°C
.3 Anti-vibration pads shall be used between the reactor or transformer core and the enclosure.
.4 Ventilated, sprinkler proof NEMA-3R enclosure.
2.3 Options: .1 Submit for approval before shipment certified production test results with serial numbers for harmonic mitigation
performance and energy efficiency under actual variable frequency drive loading. PART 3 - EXECUTION
3.1 Installation .1 The harmonic mitigation equipment shall be handled, stored and installed in accordance with the manufacturer's
recommended installation practices as found in the installation, operation, and maintenance manual. Installation shall comply with all applicable codes.
3.2 Acceptance .1 [OPTION] Harmonic compliance shall be verified with onsite field measurements of both the voltage and current
harmonic distortion at the input terminals of the harmonic mitigating equipment with and without the equipment operating. A recording type Fluke 41 or equivalent harmonics analyzer displaying individual and total harmonic currents and voltages must be utilized.
MIRUS International Inc. 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6
TECHNICAL DATA THE LINEATOR™
Advanced Universal Harmonic Filter (AUHF) Enclosed
© Mirus International Inc. [2011-03-08] 1-888-TO MIRUS www.mirusinternational.com AUHF-S001-C6Page 1 of 2
GENERAL SPECIFICATIONS: RATING For motor/drive system sizes
5HP(4kW) to 3500HP(2600kW) INPUT CURRENT
DISTORTION < 8% @ Full Load
VOLTAGE Standard voltages up to 690V EFFICIENCY > 99% FREQUENCY 60Hz (50Hz available) ELEVATION ≤ 3300ft [1000m] above sea level OVERLOAD CAPABILITY Suitable for overload of 150% for 60
seconds every 10 minutes VENTILATION Convection air cooled
AMBIENT TEMPERATURE ≤ 104 Deg F [40 Deg C] HARMONICS TREATED All harmonics 5th and higher WINDING MATERIAL Copper K-FACTOR SUITABILITY Up to 20 (Reduced to <1.5 on input
of AUHF) ENCLOSURE Type: TYPE-3R, Colour: ANSI 61 Grey
Paint: Polyester powder coated Wall Mtg Capability: 5 to 200HP
MAXIMUM CAPACITIVE REACTIVE CURRENT @ N.L.
< 20% of rated input current OPTIONS: TYPE-3R Enhanced Outdoor Ventilated Enclosure, Fan Cooling (150-3500HP), Hinged Doors (150-3500HP)
Motor Size Lineator Rating (3-Phase) 480V (60Hz) 600V (60Hz), 690V (50-60Hz)
HP kW Input Amps Standard Enclosure Enhanced Enclosure Standard Enclosure Enhanced Enclosure
460/ 480V
575/ 600V
660/ 690V Output Case Weight Case Weight Case Weight Case Weight
60Hz 60Hz 50/60Hz kW Style lbs [kg][1] Style lbs [kg][1] Style lbs [kg][1] Style lbs [kg][1] 5 4 7 5 5 4.5
SU1 58 [26]
SU1-E68 [31]
SU1
57 [26] SU1-E
67 [30]7.5 5.5 9 7 6 6.3 67 [30] 77 [35] 67 [30] 77 [35]10 7.5 12 10 8 8.5 78 [35] 88 [40] 77 [35] 87 [39]15 11 17 14 12 13 90 [41] 100 [45] 86 [39] 96 [44]20 15 23 18 16 17
SU2
118 [54]SU2-E
128 [58] 98 [45] SU2-E
128 [58]25 18.5 29 23 20 21 130 [59] 140 [64]
SU2
125 [57] 135 [61]30 22 34 28 24 25 142 [65] 152 [69] 137 [62] 147 [67]40 30 46 37 32 34 154 [70] 164 [74] 149 [68] 159 [72]50 37.5 57 45 40 42 186 [84]
SU3-E196 [89] 184 [83]
SU3-E196 [89]
60 45 69 55 48 51SU3
218 [99] 228 [103] 206 [94] 216 [98]75 55 85 68 59 63 304 [138] 314 [142]
SU3 298 [135] 308 [140]
100 75 113 90 79 84 323 [147] 333 [151] 315 [143] 325 [147]125 90 141 112 98 104 345 [156] SU4-E 419 [191] 345 [156] SU4-E 419 [191]150 110 169 135 118 125 SU4 365 [166] 439 [200] SU4 365 [166] 439 [200]200 150 226 180 158 168 415 [189] MT3-E 489 [222] 415 [189] MT3-E 489 [222]250 185 281 225 196 209 MT3 578 [262] 640 [290] MT3 578 [262] 640 [290]300 200 337 270 235 251 585 [266] MT4-E 695 [316] 585 [266] MT4-E 695 [316]350 250 395 315 275 292
MT4 800 [363] 1006 [456]
MT4 780 [354] 1006 [456]
400 315 470 375 325 349 825 [374]LT1-E
1031 [467] 805 [365] LT1-E
1031 [467]500 400 595 475 415 443 915 [415] 1121 [508] 915 [415] 1121 [510]600 450 670 535 470 499 LT1 1398 [634] 1476 [670] LT1 1398 [634] 1476 [670]700 500 780 625 545 579 1700 [771] LT2-E 1839 [834] 1650 [748] LT2-E 1740 [789]800 560 890 715 620 662
LT2 1882 [854] 1954 [886]
LT2 1805 [819] 1852 [842]
900 630 990 795 690 736 1920 [871]LT3-E
2054 [931] 1882 [854]LT3-E
2054 [932]1000 710 1100 880 770 818 1950 [884] 2084 [945] 1915 [869] 2064 [936]1100 800 1210 970 845 900
LT3 2465 [1118] 2564 [1163]
LT3 2331 [1057] 2515 [1141]
1200 900 1330 1060 925 987 2568 [1167] 2958 [1245] 2465 [1121] 2855 [1298]1300 970 1430 1145 1000 1064 2718 [1236]
HT2-E3408 [1549] 2609 [1186]
HT2-E2999 [1363]
1400 1000 1540 1235 1075 1145 2858 [1299] 3548 [1613] 2782 [1265] 3172 [1442]1500 1120 1650 1325 1155 1228
HT2
3598 [1635] 3690 [1677]
HT2
3540 [1606] 3620 [1642]1600 1200 1770 1415 1235 1316 3748 [1703] 3840 [1745] 3702 [1679] 3800 [1724]1800 1350 1990 1595 1390 1481 3848 [1749]
HT3-E
4376 [1943] 3798 [1723]
HT3-E
3875 [1758]2000 1450 2200 1765 1535 1636 3978 [1808] 4506 [2048] 3945 [1789] 4250 [1928]2300 1700 2530 2030 1765 1882 4075 [1850] 4600 [2088] 4015 [1821] 4340 [1969]2500 1850 2755 2205 1920 2045
HT3 4650 [2111] 4750 [2157]
HT3 4600 [2087] 4750 [2155]
2800 2100 3100 2480 2160 2303 5000 [2270] 5100 [2315] 4945 [2243] 5100 [2313]3000 2250 3320 2660 2315 2468 5225 [2372] 5180 [2350]3500 2600 3855 3085 2685 2618 5550 [2520] 5490 [2490]
MIRUS International Inc. 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6
TECHNICAL DATA THE LINEATOR™
Advanced Universal Harmonic Filter (AUHF) Enclosed
© Mirus International Inc. [2011-03-08] 1-888-TO MIRUS www.mirusinternational.com AUHF-S001-C6Page 2 of 2
Motor Size Lineator Rating (3-Phase) 208, 240V (60Hz) 400, 440V (50Hz)
HP kW Input Amps Standard Enclosure Enhanced Enclosure Standard Enclosure Enhanced Enclosure
208V 220/ 240V
380/ 400V
415/ 440V Output Case Weight Case Weight Case Weight Case Weight
60Hz 50/60Hz 50Hz 50Hz kW Style lbs [kg][1] Style lbs [kg][1] Style lbs [kg][1] Style lbs [kg][1] 5 4 14 13 8 7 4.5 SU1 65 [30] SU1-E 75 [34]
SU1 58 [26]
SU1-E68 [31]
7.5 5.5 20 18 11 10 6.3 76 [35] 86 [39] 67 [30] 77 [35]10 7.5 27 24 14 13 8.5
SU2 80 [36]
SU2-E80 [36] 78 [35] 88 [40]
15 11 40 36 21 19 13 117 [53] 127 [58]
SU2
90 [41] SU2-E
100 [45]20 15 53 48 28 25 17 138 [63] 148 [67] 118 [54] 128 [58]25 18.5 66 60 35 32 21 154 [70]
SU3-E164 [74] 130 [59] 140 [64]
30 22 79 72 42 38 25SU3
189 [86] 199 [90] 142 [65] 152 [69]40 30 105 95 55 51 34 253 [115] 263 [119] 154 [70]
SU3-E164 [74]
50 37.5 131 119 69 63 42 275 [125]SU4-E
333 [151]SU3
186 [84] 196 [88]60 45 158 143 83 76 51 315 [143] 337 [153] 218 [99] 228 [103]75 55 196 178 103 95 63
SU4 325 [148] 399 [181] 304 [138] 314 [142]
100 75 260 236 137 125 84 442 [201]MT3-E
516 [235] 323 [147] SU4-E 414 [188]125 90 323 294 170 156 104 468 [213] 542 [246] SU4 345 [156] 434 [197]150 110 388 353 204 187 125 553 [251] 627 [285] 365 [166] MT3-E 469 [213]200 150 274 250 168
MT3 415 [189] 514 [234]
250 185 340 312 209 578 [262] MT4-E 600 [273]300 200 410 374 251 585 [266] 670 [305]350 250 475 436 292 MT4 800 [363]
LT1-E1006 [456]
400 315 565 520 349 825 [374] 1031 [467]500 400 720 660 443
LT1 915 [415] 1121 [508]
600 450 810 740 499 1098 [499] LT2-E 1176 [535]700 500 940 865 579 1700 [771] 1839 [834]800 560 1075 985 662 LT2 1882 [854]
LT3-E1954 [886]
900 630 1200 1100 736 1920 [871] 2054 [931]1000 710 1335 1220 818
LT3
1950 [884] 2084 [945]1100 800 1470 1340 900 2465 [1118] 2564 [1163]1200 900 1610 1470 987 2568 [1167]
HT2-E
2958 [1245]1300 970 1735 1585 1064 2718 [1236] 3408 [1549]1400 1000 1870 1710 1145 2858 [1299] 3548 [1613]1500 1120 2000 1835 1228
HT2
3598 [1635] 3690 [1677]1600 1200 2145 1965 1316 3748 [1703] 3840 [1745]1800 1350 2410 2210 1481 3848 [1749]
HT3-E
4376 [1943]2000 1450 2670 2440 1636 3978 [1808] 4506 [2048]2300 1700 3065 2810 1882 4075 [1850] 4600 [2088]2500 1850 3335 3050 2045
HT3 4650 [2111] 4750 [2157]
2800 2100 3750 3435 2303 5000 [2270] 5100 [2315]3000 2250 4020 3680 2468 5225 [2372]3500 2600 4265 3905 2618 5550 [2520]
‘SU1’, ‘SU2’ ,’ SU3’ ENCLOSURE ‘SU4’ ENCLOSURE ‘MT3’, ‘MT4’, ‘LT’ ‘HT’ ENCLOSURE
CASE STYLE ENCLOSURE DIMENSIONS - inches [mm] Standard Enhanced A B C D E F G H
SU1 SU1-E 23.50 [597] 11.25 [286] 8.75 [222] 11.25 [286] 9.00 [229] 8.50 [216] 12.00 [305] 9.00 [228] SU2 SU2-E 29.50 [749] 13.25 [336] 10.25 [260] 12.75 [324] 11.00 [279] 10.00 [254] 16.00 [406] 11.00[279] SU3 SU3-E 34.00 [864] 20.25 [514] 13.25 [336] 16.00 [406] 18.00 [457] 13.00 [330] 20.00 [508] 18.00[457] SU4 SU4-E 40.00 [1016] 22.00 [559] 18.50 [470] 23.00 [584] 20.00 [508] 20.00 [508] MT3 MT3-E 45.00 [1143] 26.00 [661] 21.00 [534] 25.00 [635] 21.50 [546] 19.00 [483] MT4 MT4-E 51.50 [1308] 32.00 [813] 25.50 [648] 29.50 [749] 23.50 [597] 23.50 [597] LT1 LT1-E 59.00 [1499] 39.50 [1003] 30.00 [762] 34.00 [864] 24.00 [610] 32.00 [813] LT2 LT2-E 66.00 [1677] 44.00 [1118] 34.00 [864] 38.00 [965] 26.00 [660] 36.00 [915] LT3 LT3-E 75.00 [1905] 48.50 [1232] 39.00 [991] 43.00 [1092] 27.50 [699] 41.00 [1041] HT2 HT2-E 78.00 [1981] 58.50 [1486] 51.00 [1295] 56.25 [1428] 52.50 [1333] 50.75 [1289] HT3 HT3-E 84.00 [2134] 68.50 [1740] 59.00 [1499] 64.50 [1638] 62.50 [1587] 58.75 [1492]
Notes:
1. Approximate Values. 2. Specifications are subject to change without notice. 3. Lineator sizing is by standard motor horsepower and kW ratings. Each is capable of supplying the larger of the two ratings. 4. Cable entry is from left or right side only unless otherwise indicated. 5. For additional information refer to: Typical Specifications, Internal Layout and Connection Diagrams.
MIRUS International Inc. 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6
SPECIFICATION PWM Variable Frequency Drive (VFD) Typical Harmonic Specification
© Mirus International Inc. [2010-01-06] 1-888-TO MIRUS www.mirusinternational.com MIRUS-S001-B7
PART 1 - GENERAL
1.1 All PWM AC Variable Frequency Drives of [ 30 ] hp and above shall be equipped with harmonic mitigation equipment to prevent power system problems resulting from high levels of harmonic distortion. .1 The harmonic mitigation equipment and all of its components shall be manufactured and tested in accordance with the
latest applicable standards of UL, CSA and NEMA. .2 Demonstration of compatibility between the harmonic mitigation equipment and the VFD must be available upon request. .3 Harmonic mitigation equipment shall be warranted to be free of defects in materials and workmanship for a period of 3
years from the date of shipment. . .4 Factory Performance Testing: Manufacturer must be capable of factory testing for harmonic mitigating performance
and energy efficiency under actual variable frequency drive loads. A detailed description of the program and a sample test report must be provided at time of quotation.
.5 Subject to compliance with all of the contract documents and specifications, the following manufacturers and products are acceptable: .1 MIRUS International Inc. LINEATOR™ Advanced Universal Harmonic Filter (AUHF) .2 MIRUS International Inc. LINEATOR™ Single Phase Universal Harmonic Filter (SUHF) .3 VFD with an 18-pulse rectifier as manufactured by ABB, Allen Bradley, Cutler Hammer, Robicon, or Toshiba.
PART 2 - PRODUCT
2.1 Key Requirements: .1 The harmonic mitigation equipment shall treat all of the characteristic low frequency harmonics generated by a 3-phase,
diode bridge rectifier load (5th, 7th, 11th, 13th, etc.). .2 The characteristic harmonics shall be suppressed without the need for individual tuning or the requirement to phase shift
against other harmonic sources. .3 Harmonic mitigation shall be by passive inductor/capacitor network or internal phase shifting transformer. Active
electronic components shall not be used. .4 Power factor shall be .98 lagging to .95 leading in operating range from full to half load. .5 To ensure compatibility with engine generators, the harmonic mitigation equipment must never introduce a capacitive
reactive power (KVAR) which is greater than 20% of its kVA rating. .6 The harmonic mitigation equipment shall not resonate with system impedances or attract harmonic currents from other
harmonic sources. .7 The harmonic mitigation equipment in combination with the Variable Frequency Drive shall meet all requirements as
outlined in the 1992 edition of IEEE std 519 for individual and total harmonic voltage and current distortion. The Point of Common Coupling (PCC) for all voltage and current harmonic calculations and measurements shall be the input terminals to the harmonic mitigation equipment.
.8 Total Harmonic Voltage Distortion (THVD) shall meet the requirements of Table 10.2 of IEEE std 519 by not exceeding 5% and by limiting the individual harmonic voltage distortion to less than 3%. These limits shall apply while operating on either utility supply or generator supply when applicable. The harmonic mitigation equipment vendor shall not be responsible for pre-existing voltage distortion caused by other harmonic sources.
.9 Total Demand Distortion (TDD) of the current at the input terminals of the harmonic mitigation equipment shall not exceed the limits as defined in Table 10.3 of IEEE std 519. For Isc/IL ratio < 20, TDD must be less than 5%. For all other Isc/IL ratios, the TDD must not exceed 8% even when Table 10.3 allows for more relaxed limits. For single-phase supply applications, the TDD must not exceed 12%.
.10 The full load efficiency of the harmonic mitigation equipment / VFD combination shall be greater than 96%. The harmonic mitigation equipment itself shall have efficiency no less than 99%.
2.2 Basic Requirements: .1 All wiring shall be copper. .2 Insulation class: 220°C system. Temperature rise: 130°C .3 Anti-vibration pads shall be used between the reactor or transformer core and the enclosure. .4 Ventilated, sprinkler proof NEMA-3R enclosure.
2.3 Other Requirements: .1 [OPTION] Submit for approval before shipment certified production test results with serial numbers for harmonic
mitigation performance and energy efficiency under actual variable frequency drive loading.
PART 3 - EXECUTION
3.1 Installation .1 The harmonic mitigation equipment shall be handled, stored and installed in accordance with the manufacturer's
recommended installation practices as found in the installation, operation, and maintenance manual. Installation shall comply with all applicable codes.
3.2 Acceptance .1 [Option] Harmonic compliance shall be verified with onsite field measurements of both the voltage and current harmonic
distortion at the input terminals of the harmonic mitigating equipment with and without the equipment operating. A recording type Fluke 41 or equivalent harmonics analyzer displaying individual and total harmonic currents and voltages must be utilized.
General Specifications: LLL RROTOTATAEANNNII RA OE RN A RR -- 11QQQ33 TMLINEATOR - 1Q3 TM
Nema 3R Enhanced
Tel:(905) 494-1120 Fax:(905) 494-1140Toll Free: 1-888-TO MIRUSEmail: [email protected]: www.mirusinternational.com
Mirus International Inc. All specifications subject to change without notice.C
Available for motor/drive systemsizes up to 150HP / 110kW
Standard voltages up to 600V
60Hz (50Hz available)
3rd, 5th, 7th, 9th,11th, 13th,...
Up to 20
Reduced to < 1.5
< 12% @ Full Load
> 99%
Convection air cooled
Copper
NEMA 3R Grey(SU1, 2 & 3 suitable for Wall Mount)
HP / kW RATING
VOLTAGE
FREQUENCY
HARMONICS TREATED
K-FACTOR SUITABILITY
INPUT K-FACTOR
INPUT CURRENT DISTORTION
EFFICIENCY
VENTILATION
ELEVATION
WINDING MATERIAL
ENCLOSURE
OPTIONS
MIRUS International Inc.31 Sun Pac Blvd.Brampton, OntarioCanada L6S 5P6
1. Approximate Values
SUHF-PS01-A5Effective: March 2011
< 3300ft [1000m] above sea level_AMBIENT TEMPERATURE
< 104 Deg F [40 Deg C]_
International Inc.
Case StyleSU2SU3SU4MT3MT4
W in.[mm]10.25 [260]13.25 [336]18.50 [470]26.00 [661]32.00 [813]
D in.[mm]12.75 [324]16.00 [406]23.00 [584]25.00 [635]29.50 [749]
H in.[mm]29.50 [749]34.00 [864]
40.00 [1016]45.00 [1143]51.50 [1308]
Mtg. Hole Center W11.00 [279]18.00 [457]20.00 [508]21.50 [546]23.50 [597]
Mtg. Hole Center D10.00 [254]13.00 [330]20.00 [508]19.00 [483]23.50 [597]
DIMENSIONS
5to
150
240480600
(VAC)
Single PhaseUniversalHarmonic
Filter
60 DDiode Bridge
RectifierT
Thyristor BridgeRectifier
E0PNo Enclosure
E1Nema 3RVentilated
SUHF HP
ORDERING INFORMATION
ENema 3REnhanced
Model
Typical Application
LINEATOR - 1Q3LLLLLL RROOTOTOTTTATATAAEAENNNNNNIIIII RRREAEAA OOOEEE RRNN - 111QQQ3QQ33Application with Lineator-1Q3TM
MotorHorsepower
LineVoltage
Frequency LoadType
EnclosureType
Optional
VVV Hz L En O- - - - - -
Input Current
0
50
100
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Harmonic #A
mps
Input Voltage
0%
5%
10%
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Harmonic #
% fu
nd
Ithd = 109%
Vthd = 5.8%
Input Current
0
50
100
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Harmonic #A
mps
Input Current
0
50
100
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Harmonic #A
mps
Input Voltage
0%
5%
10%
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Harmonic #
% fu
nd
Input Voltage
0%
5%
10%
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Harmonic #
% F
und
amen
tal
Input Current
0
50
100
1 3 5 7 9 11 13 15 18 17 18 19 21 23 25 27
Harmonic #
Am
ps
Vthd = 2.0%
Input Voltage
0%
5%
10%
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Harmonic #
% f
un
d
Ithd = 9.8%
Input Current
0
50
100
1 3 5 7 9 11 13 15 18 17 18 19 21 23 25 27
Harmonic #
Am
ps
Input Current
0
50
100
1 3 5 7 9 11 13 15 18 17 18 19 21 23 25 27
Harmonic #
Am
ps
Input Voltage
0%
5%
10%
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Harmonic #
% f
un
d
Input Voltage
0%
5%
10%
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Harmonic #
% F
un
dam
enta
l
60HP
VFD
30 HP480V
Excess ripple current requiresdrive derating of 2x
1Q3 reduces ripple current which may allow for less derating when approved by VFD manufacturer
Unbalanced3-wire
Balanced3-phase, 3-wire
40HP
VFD
30HP1Q3
Balanced1-phase, 2-wire
30 HP480V
at input of VFD at input of 1Q3
* All LINEATOR 1Q3 units are shipped complete with a capacitor bank switching contactor and control system that automatically switches the filter capacitors off whenever the VFD is in the idle-no load ready-to-run mode.
Motor Size Lineator Rating 240V (60Hz) 480V (60Hz) 600V (60Hz)
HP kW Input Amps (1ph/60Hz)
Standard Enclosure
Enhanced Enclosure
Standard Enclosure
Enhanced Enclosure
Standard Enclosure
Enhanced Enclosure
Output Case Weight[1] Case Weight[1] Case Weight[1] Case Weight[1] Case Weight[1] Case Weight[1]
240VAC 480VAC 600VAC kVA Style lbs [kg] Style lbs [kg] Style lbs [kg] Style lbs [kg] Style lbs [kg] Style lbs [kg] 5 4 23 12 9 7.5
SU2
81 [37]
SU2-E
84 [38]
SU2
74 [34]
SU2-E
77 [35]
SU2
71 [32]
SU2-E
74 [33]
7.5 5.5 33 17 13 11 93 [42] 96 [44] 84 [38] 87 [39] 80 [36] 83 [38]
10 7.5 45 23 18 14 111 [50] 114 [52] 99 [45] 102 [46] 94 [42] 97 [44]
15 11 68 34 26 20
SU3
159 [72]
SU3-E
165 [75] 119 [54] 122 [55] 112 [51] 115 [52]
20 15 90 45 35 27 189 [86] 195 [88]
SU3
168 [76]
SU3-E
174 [79]
SU3
158 [72]
SU3-E
164 [75]
25 18.5 111 56 44 34 213 [97] 219 [99] 188 [85] 194 [88] 177 [80] 183 [83]
30 22 137 68 52 40 273 [124] 279 [127] 238 [108] 244 [111] 222 [101] 228 [103]
40 30 180 90 70 51 333 [151] 339 [154] 288 [131] 294 [133] 268 [121] 274 [124]
50 37.5 202 110 87 63
SU4
389 [176]
SU4-E
397 [180] 318 [144] 324 [147] 295 [134] 301 [136]
60 45 255 130 105 75 413 [187] 421 [191]
SU4
358 [162]
SU4-E
366 [166]
SU4
333 [151]
SU4-E
341 [155]
75 55 300 152 130 93 461 [209] 469 [213] 398 [180] 406 [184] 369 [168] 377 [171]
100 75 420 210 175 118 MT3
563 [255] MT3-E
593 [269] 458 [208] 466 [211] 424 [192] 432 [196]
125 90 520 260 220 145 659 [299] 689 [312] MT3
568 [258] MT3-E
598 [271] MT3
527 [239] MT3-E
557 [252]
150 110 590 295 260 175 MT4 847 [384] MT4-E 884 [401] 688 [312] 718 [326] 636 [288] 666 [302]
R
R
MIRUS International Inc. TYPICAL SPECIFICATION LINEATOR-1Q3™ Single Phase Universal Harmonic Filter (SUHF)
PART 1 - GENERAL
1.1 Single phase to quasi 3-phase harmonic filter for 3-phase PWM AC Variable Frequency Drives being supplied with single phase voltage. .1 The harmonic mitigation equipment and all of its components shall be manufactured and tested in accordance with
the latest applicable standards of UL, CSA and NEMA. .2 Demonstration of compatibility between the harmonic mitigation equipment and the VFD must be available upon
request. .3 Harmonic mitigation equipment shall be warranted to be free of defects in materials and workmanship for a period of
12 months from the date of start-up or 18 months from the date of shipment. .4 Factory Performance Testing: Manufacturer must be capable of factory testing for harmonic mitigating performance
and energy efficiency under actual variable frequency drive loads. A detailed description of the program and a sample test report must be provided at time of quotation.
.5 Subject to compliance with all of the contract documents and specifications, the acceptable product and manufacturer is: LINEATOR-1Q3™ SUHF, by MIRUS International Inc. (905) 565-6900, Toll Free: (888) 866-4787
PART 2 - PRODUCT
2.1 Key Requirements: .1 The harmonic mitigation equipment shall treat all of the characteristic low frequency harmonics generated by a 3-
phase, diode bridge rectifier load when supplied with single phase voltage (3rd, 5th, 7th, 9th, 11th, 13th, etc.). Total Harmonic Current Distortion shall be reduced by more than 10x when compared to a VFD without harmonic treatment and shall be less than 12% when measured at the input terminals of the harmonic mitigation equipment under full load operation.
.2 The characteristic harmonics shall be suppressed without the need for individual tuning or the requirement to phase shift against other harmonic sources.
.3 Harmonic mitigation shall be by passive inductor/capacitor network. Active electronic components shall not be used.
.4 Power factor shall be .98 lagging to .95 leading in operating range from full to half load.
.5 To ensure compatibility with engine generators, the harmonic mitigation equipment must never introduce a capacitive reactive power (KVAR), which is greater than 20% of its kVA rating.
.6 The harmonic mitigation equipment shall not resonate with system impedances or attract harmonic currents from other harmonic sources.
.7 The full load efficiency of the harmonic mitigation equipment / VFD combination shall be greater than 96%. The harmonic mitigation equipment itself shall have efficiency no less than 99%.
2.2 Basic Requirements:
.1 All wiring shall be copper.
.2 Insulation class: 220°C system. Temperature rise: 130°C
.3 Anti-vibration pads shall be used between the reactor or transformer core and the enclosure.
.4 Ventilated, sprinkler proof NEMA-3R enclosure.
2.3 Other Requirements: .1 [OPTION] Submit for approval before shipment certified production test results with serial numbers for harmonic
mitigation performance and energy efficiency under actual variable frequency drive loading. PART 3 - EXECUTION
3.1 Installation .1 The harmonic mitigation equipment shall be handled, stored and installed in accordance with the manufacturer's
recommended installation practices as found in the installation, operation, and maintenance manual. Installation shall comply with all applicable codes.
3.2 Acceptance .1 [OPTION] Harmonic compliance shall be verified with onsite field measurements of both the voltage and current
harmonic distortion at the input terminals of the harmonic mitigating equipment with and without the equipment operating. A recording type Fluke 41 or equivalent harmonics analyzer displaying individual and total harmonic currents and voltages must be utilized.
31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6
1-888-TO MIRUS www.mirusinternational.com SUHF-TS001-A1© Mirus International Inc. [2010-04-20]
MIRUS International Inc. 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6
TECHNICAL DATA THE LINEATOR-1Q3™
Single Phase Universal Harmonic Filter (SUHF) [60Hz]
© Mirus International Inc. [2011-03-08] 1-888-TO MIRUS www.mirusinternational.com SUHF-S001-A6
Motor Size Lineator Rating 240V (60Hz) 480V (60Hz) 600V (60Hz)
HP kW Input Amps (1ph/60Hz)
Standard Enclosure
Enhanced Enclosure
Standard Enclosure
Enhanced Enclosure
Standard Enclosure
Enhanced Enclosure
Output Case Weight[1] Case Weight[1] Case Weight[1] Case Weight[1] Case Weight[1] Case Weight[1]
240VAC 480VAC600VAC kVA Style lbs [kg] Style lbs [kg] Style lbs [kg] Style lbs [kg] Style lbs [kg] Style lbs [kg] 5 4 23 12 9 7.5
SU2
81 [37]
SU2-E
84 [38]
SU2
74 [34]
SU2-E
77 [35]
SU2
71 [32]
SU2-E
74 [33]
7.5 5.5 33 17 13 11 93 [42] 96 [44] 84 [38] 87 [39] 80 [36] 83 [38]
10 7.5 45 23 18 14 111 [50] 114 [52] 99 [45] 102 [46] 94 [42] 97 [44]
15 11 68 34 26 20
SU3
159 [72]
SU3-E
165 [75] 119 [54] 122 [55] 112 [51] 115 [52]
20 15 90 45 35 27 189 [86] 195 [88]
SU3
168 [76]
SU3-E
174 [79]
SU3
158 [72]
SU3-E
164 [75]
25 18.5 111 56 44 34 213 [97] 219 [99] 188 [85] 194 [88] 177 [80] 183 [83]
30 22 137 68 52 40 273 [124] 279 [127] 238 [108] 244 [111] 222 [101] 228 [103]
40 30 180 90 70 51 333 [151] 339 [154] 288 [131] 294 [133] 268 [121] 274 [124]
50 37.5 202 110 87 63
SU4
389 [176]
SU4-E
397 [180] 318 [144] 324 [147] 295 [134] 301 [136]
60 45 255 130 105 75 413 [187] 421 [191]
SU4
358 [162]
SU4-E
366 [166]
SU4
333 [151]
SU4-E
341 [155]
75 55 300 152 130 93 461 [209] 469 [213] 398 [180] 406 [184] 369 [168] 377 [171]
100 75 420 210 175 118 MT3
563 [255] MT3-E
593 [269] 458 [208] 466 [211] 424 [192] 432 [196]
125 90 520 260 220 145 659 [299] 689 [312] MT3
568 [258] MT3-E
598 [271] MT3
527 [239] MT3-E
557 [252]
150 110 590 295 260 175 MT4 847 [384] MT4-E 884 [401] 688 [312] 718 [326] 636 [288] 666 [302]
GENERAL SPECIFICATIONS:
HP / kW RATING Available for motor/drive system sizes up to 150HP / 110kW VOLTAGE
Standard voltages up to 600V FREQUENCY 60Hz (50Hz available) HARMONICS TREATED 3th, 5th, 7th, 9th, 11th, 13th,… K-FACTOR SUITABILITY Up to 20 INPUT K-FACTOR Reduced to <1.5 INPUT CURRENT DISTORTION
<12% @ Full Load EFFICIENCY > 99% @ Full Load ELEVATION ≤ 3300ft [1000m] above sea level AMBIENT TEMPERATURE ≤ 104 Deg F [40 Deg C] VENTILATION Convection air cooled WINDING MATERIAL Copper ENCLOSURE Type: NEMA-3R Paint: Polyester powder coated Colour: ANSI 61 Grey
OPTIONS: Nema 3R Enhanced
‘SU1’,‘SU2’,‘SU3’ ENCLOSURE DIM. - in. [mm] ‘SU4’, ENCLOSURE DIM. – in. [mm]
CASE A B C D E F G H SU2 29.50 [749] 13.25 [336] 10.25 [260] 12.75 [324] 11.00 [279] 10.00 [254] 16.00 [406] 11.00 [279]
SU3 34.00 [864] 20.25 [514] 13.25 [336] 16.00 [406] 18.00 [457] 13.00 [330] 20.00 [508] 18.00 [457]
SU4 40.00 [1016] 22.00 [559] 18.50 [470] 23.00 [584] 20.00 [508] 20.00 [508]
‘MT3’, ‘MT4’ ENCLOSURE DIM. - inches [mm]
CASE A B C D E F MT3 45.00 [1143] 26.00 [661] 21.00 [534] 25.00 [635] 21.50 [546] 19.00 [483] MT4 51.50 [1308] 32.00 [813] 25.50 [648] 29.50 [749] 23.50 [597] 23.50 [597]
Notes: 1. Approximate Values. 2. For additional information refer to: Typical Specifications, Internal Layout and Connection Diagrams. 3. For Thyristor Diode Bridge models, larger sizes and/or other enclosure types contact Mirus. 4. All LINEATOR 1Q3 units are shipped complete with a capacitor bank switching contactor and control system
that automatically switches the filter capacitors off whenever the VFD is in the idle-no load ready-to-run mode. 5. Specifications are subject to change without notice.