ADDENDUM # 1...072419 EIFS 072726 Fluid Applied Vapor Retarding Membrane Air Barriers 074216...
Transcript of ADDENDUM # 1...072419 EIFS 072726 Fluid Applied Vapor Retarding Membrane Air Barriers 074216...
P.O. BOX 10337 GOLDSBORO, N.C. 27532
PHONE 919-778-4525 FAX 919-778-6850
1
ADDENDUM # 1
December 9, 2020 Project Name: Advanced Manufacturing Center Renovation Owner: Wayne Community College Architect: Moseley Architects SCO ID #: 16-15906-01A From: Daniels & Daniels Construction Company Greg Hedrick [email protected] Message: Bidders are hereby informed that the following additions, deletions, changes and/or clarifications supersede and supplement the Contract Documents for the above referenced projects. It forms a part of the previously issued documents dated November 6, 2020. This Addendum is hereby made a part of the Contract Documents to the same extent as if originally included therein. This Addendum must be acknowledged on the Bid Form provided in the Contract Documents and shall be placed with the Contract Documents. General: 1) The bid date for this project has changed to December 17, 2020. Bids need to be dropped off in a sealed, marked envelope to 3000 Wayne Memorial Drive, Walnut Building Room 104, Goldsboro, NC 27534. EMAILED BIDS WILL NOT BE ACCEPTED. 2) Once bid has been hand delivered at the address provided, each bidder shall leave the room and not return. Daniels & Daniels will initiate a Zoom meeting as directly as possible after 2:00 pm. All bidders may attend via the following link: Join Zoom Meeting https://us02web.zoom.us/j/87380822176?pwd=bk82N3UrL0NGUmpuVGdncHFqcmIxdz09 Meeting ID: 873 8082 2176 Passcode: 259957 One tap mobile +16465588656,,87380822176#,,,,,,0#,,259957# US (New York) +13017158592,,87380822176#,,,,,,0#,,259957# US (Washington D.C) Dial by your location
Advanced Manufacturing Center Renovations/WCC
2
+1 646 558 8656 US (New York) +1 301 715 8592 US (Washington D.C) +1 312 626 6799 US (Chicago) +1 669 900 9128 US (San Jose) +1 253 215 8782 US (Tacoma) +1 346 248 7799 US (Houston) Meeting ID: 873 8082 2176 Passcode: 259957 Find your local number: https://us02web.zoom.us/u/k9j1t9fJ1 3) Bids will be opened and read aloud. Bid tabulation will be developed and made available upon request once all figures and required bid information has been confirmed. Substitution Requests: Subject to requirements of plans and specifications, the Architect has requested if any substitutions are to be made, they follow the project manual for instructions. Revisions to Specifications: 1) Table of Contents ADD Section 233424 – Specialty Exhaust Systems 2) Section 230993 – Sequences of Operations for HVAC Controls See bolded, underlined, and struck-thru text in section 2.8 for revisions. Revisions to Plans: 1) DRAWING A2.1
See clouded areas on A2.1 for revisions 2) DRAWING M0.2
See clouded areas on M0.2 for revisions 3) DRAWING M1.2
See clouded areas on M1.2 for revisions 4) DRAWING M3.1
See clouded areas on M3.1 for revisions 5) DRAWING M5.2
See clouded areas on M5.2 for revisions 6) DRAWING M7.1
See clouded areas on M7.1 for revisions
End of Addendum #1 Attached: Addendum 01 Combined Specifications and Plans (35 pages) Product Substitution Request (1 page)
ADDENDUM 01
ADVANCED MANUFACTURING
CENTER RENOVATION Wayne Community College
Goldsboro, North Carolina
SCO ID: 16-15906-01A
Architect’s Project Number: 539101
Prepared by
MOSELEY ARCHITECTS
911 N. WEST STREET
SUITE 205
RALEIGH, NORTH CAROLINA 27603
DATE OF ISSUE – December 8, 2020
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
December 8, 2020 ADDENDUM NO. 01 Page 1 of 1
GENERAL:
Planholders are requested to insert this Addendum in the front of their Project Manual. Inform all
concerned that the Bidding Documents are modified by this Addendum.
The following modifications and clarifications are hereby made a part of the Bidding Documents and
supersede or otherwise modify the provisions of the published Project Manual and Drawings, dated
December 8, 2020.
Refer to the Drawings, Specification Sections, or other Documents, if any, attached to this Addendum,
which are hereby made a part of this Addendum.
MODIFICATIONS TO THE PROJECT MANUAL:
ADD new Documents in their entirety, noted as Addendum 01, dated December 8, 2020.
TABLE OF CONTENTS
ADD Section 233424 – Specialty Exhaust Systems
SECTION 230993 – SEQUENCES OF OPERATIONS FOR HVAC CONTROLS
See bolded, underlined, and struck-thru text in section 2.8 for revisions
MODIFICATIONS TO THE DRAWINGS:
DRAWING A2.1
See clouded areas on A2.1 for revisions
DRAWING M0.2
See clouded areas on M0.2 for revisions
DRAWING M1.2
See clouded areas on M1.2 for revisions
DRAWING M3.1
See clouded areas on M3.1 for revisions
DRAWING M5.2
See clouded areas on M5.2 for revisions
DRAWING M7.1
See clouded areas on M7.1 for revisions
REFER TO SPECIFICATIONS AND DRAWINGS ATTACHED TO THE END OF THIS
ADDENDUM
END OF ADDENDUM NO 01
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 TABLE OF CONTENTS 001100 - 1
TABLE OF CONTENTS
DIVISON 00 – PROCUREMENT AND CONTRACTING REQIREMENTS
SEALS PAGE
TABLE OF CONTENTS
FORM OF DESIGN BUILD CONSTRUCTION CONTRACT (DB1)
INSTRUCTIONS TO BIDDERS
GENERAL CONDITIONS OF CONTRACT FOR DESIGN BUILD CONSTRUCITON
GUIDELINE FOR MBE PARTICIPATION IN STATE CONSTRUCTION CONTRACTS
DIVISION 01 – GENERAL REQUIREMENTS
011000 Summary
012300 Alternates
012500 Substitution Procedures
013100 Project Management and Coordination
013200 Construction Progress Documentation
013300 Submittal Procedures
014000 Quality Requirements
014200 References
014520 Testing, Adjusting, and Balancing
015000 Temporary Facilities and Controls
016000 Product Requirements
017300 Execution
017419 Construction Waste Management
017700 Closeout Procedures
017839 Project Record Documents
019113 General Commissioning Requirements
DIVISION 02 – EXISTING CONDITIONS
024119 Selective Structure Demolition
028000 Hazardous Materials Remediation
DIVISION 03
033000 Cast-In-Place Concrete
035416 Hydraulic Cement Underlayment
DIVISION 04
042000 Unit Masonry
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 TABLE OF CONTENTS 001100 - 2
DIVISION 05
051200 Structural Steel Framing
061600 Sheathing
054000 Cold Formed Metal Framing
DIVISION 06
061000 Rough Carpentry
064023 Interior Architectural Woodwork
DIVISION 07
072100 Thermal Insulation
072419 EIFS
072726 Fluid Applied Vapor Retarding Membrane Air Barriers
074216 Insulated Core Metal Wall Panels
075424 TPO Roofing – Minor Alterations
076201 Flashing, Sheet Metal and Roofing Accessories
078446 Fire Resistive Joint Systems
079200 Joint Sealants
079500 Expansion Control
DIVISION 08
081113 Steel Doors and Frames
081416 Flush Wood Doors
084113 Aluminum Entrances, Storefront
084523 Fiberglass Sandwich Panel Assemblies
087100 Door Hardware
088000 Glazing
088300 Mirrors
DIVISION 09
092216 Cold Formed Steel Framing - Non-Structural
092900 Gypsum Board
093000 Tiling
095113 Acoustical Panel Ceilings
096513 Resilient Base and Accessories
096519 Resilient Tile Flooring
096724 High Performance Floor Coating System
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 TABLE OF CONTENTS 001100 - 3
DIVISION 9 (Cont.)
099100 Interior Painting
DIVISION 10
101400 Signage
102600 Wall Protection
104313 Defibrillators and Cabinets
104400 Fire Protection Specialties
DIVISION 11 – 14
110000 Misc Equipment
DIVISION 21 – FIRE PROTECTION
Listed on Drawing Sheets
DIVISION 22 – PLUMBING
220500 Common Work Results for Plumbing
220523 General-Duty Valves for Plumbing Piping
220529 Hangers and Supports for Plumbing Piping and Equipment
220553 Identification for Plumbing Piping and Equipment
220700 Plumbing Insulation
221116 Domestic Water Piping
221119 Domestic Water Piping Specialties
221316 Sanitary Waste and Vent Piping
221319 Sanitary Waste Piping Specialties
224000 Plumbing Fixtures
DIVISION 23 – MECHANICAL
230500 Common Work Results for HVAC
230513 Motors for HVAC Equipment
230514 Variable Speed Drives
230517 Sleeves and Sleeve Seals for HVAC Piping
230519 Meters and Gauges for HVAC Piping
230523 General Duty Valves for HVAC Piping
230529 Hangers and Supports for HVAC Piping and Equipment
230548 Vibration Control for HVAC
230553 Identification for HVAC Piping and Equipment
230700 HVAC Insulation
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 TABLE OF CONTENTS 001100 - 4
DIVISION 23 – MECHANICAL (Cont.)
230900 Building Automation System
230993 Sequences of Operations for HVAC Controls
232113 Hydronic Piping
232123 Hydronic Pumps
232300 Refrigerant Piping
233113 Metal Ducts
233300 Air Duct Accessories
233423 HVAC Power Ventilators
233424 Specialty Exhaust Systems – AD-01
233600 Air Terminal Units
233713 Diffusers, Registers, and Grilles
234100 Particulate Air Filtration
238126 Split System Air Handling Units
238216 Hydronic Air Coils
DIVISION 26 – ELECTRICAL
260519 Low-voltage Electrical Power Conductors and Cables
260526 Grounding and Bonding for Electrical Systems
260529 Hangers and Supports for Electrical Systems
260533 Raceways and Boxes for Electrical Systems
260544 Sleeves and Sleeve Seals for Electrical Raceways and Cabling
260553 Identification for Electrical Systems
260923 Lighting Control Devices
261219 Padmounted, Liquid-filled, Medium-voltage Transformers
262413 Switchboards
262416 Panelboards
262726 Wiring Devices
265119 Led Interior Lighting
DIVISION 27 – COMMUNICATIONS
270500 Common Work Results for Communications Systems
271100 Communications Equipment Room Fittings
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 1
SECTION 230993 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Provisions of the Contract and Contract Documents apply to this Section.
1.2 SUMMARY
A. This Section includes control sequences for HVAC systems, subsystems, and equipment.
B. Related Sections include the following:
1. Division 23 Section "Building Automation System” for control equipment, devices and
submittal requirements.
1.3 DEFINITIONS
A. BAS: Building automation system.
B. CO2: Carbon dioxide.
C. DDC: Direct digital control.
D. PPM: Parts per million.
E. RPM: Revolutions per minute.
F. VFD: Variable-frequency drive
1.4 GENERAL REQUIREMENTS OF THIS SECTION
A. Control sequences shall be accomplished in accordance with control drawings and the
sequences specified in this section. It is the intent of this section to utilize sequences included
in pre-programmed controllers when such sequences provide the intended operation.
B. Points may not be deleted without prior approval from the Architect.
C. Every attempt has been made to indicate all required points on the control drawings.
Occasionally an additional point, or points, may be required to accomplish a specified sequence.
The contractor performing work under this section shall understand the work to be implied and
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 2
required by the contract documents. Additional hardware and software required shall be
provided under section “Building Automation System” at no additional cost to the owner.
1. Such points include:
a. Sensors of all types whether or not specified under section “Building Automation
System”
b. Flow measuring stations.
c. Wiring, conduit, and related devices such as relays.
2. Exceptions:
a. Equipment and devices covered under sections other than “Building Automation
System.”
1.5 DISPLAY GRAPHICS:
A. Include system schematic for each system. Indicate all points in system on at least one graphic.
B. Indicate all commanded values and temperatures.
C. Indicate all sensed temperatures.
D. Indicate all alarms.
E. Indicate all status points.
F. Indicate all monitored conditions.
1.6 WARRANTY
A. Provide all services, materials and equipment necessary for the successful operation of the
entire BAS system for a period of one year beginning on the date of Final Acceptance.
1.7 SUBMITTALS
A. Refer to section “Building Automation System.”
PART 2 - SEQUENCES
2.1 SET POINTS: Unless indicated otherwise all set points shall be adjustable from the head end.
2.2 OCCUPIED / UNOCCUPIED
A. The BAS shall institute occupied and unoccupied control sequences based on a time-of-day
schedule furnished by the Owner.
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 3
B. The Owner shall have the capability to program holidays and special functions.
C. The Owner shall have the ability to override occupied and unoccupied operation of each piece
of equipment from the head end.
2.3 OPTIMUM START/STOP:
A. The BAS shall institute optimum start strategies for morning warm up and cool down functions.
Equipment shall start early enough to restore occupied temperature set points 30 minutes prior
to occupancy.
B. The BAS shall institute optimum stop strategies for shutting down units before scheduled
unoccupied operation to allow zones to coast to unoccupied operation without affecting
occupied set points.
2.4 OUTSIDE AIR SENSORS:
A. Temperature: The BAS shall monitor outside air temperature as sensed by the outside air
temperature sensor.
B. Humidity: The BAS shall monitor outside air relative humidity as sensed by the outside air
humidity sensor.
2.5 GENERAL SYSTEM REQUIREMENTS
A. System Failure: The control system shall be installed to fail safe to heating mode.
1. All air handling units shall fail with outside air dampers closed.
2. Night setback shall fail to occupied mode.
3. All interlocked fans shall be de-energized with dampers closed.
2.6 VAV SPLIT AIR HANDLING UNIT SERVING TERMINAL UNITS (AHU-1/CU-1)
A. General: These air handling units include a variable-speed supply fan, hot water pre-heat coil,
and direct expansion cooling coil. A condensing unit is located on grade with modulating and
staged direct expansion cooling. They provide temperature control and humidity control for
terminal units. A separate return fan is provided.
B. Initial Set Points:
1. General:
a. Freezestat: 38F.
b. Enthalpy High Limit: 28.0 BTU/lb
2. Occupied:
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 4
a. Minimum Leaving Air Temperature: 55F.
b. Maximum Leaving Air Temperature: 65ºF.
c. Space Maximum Relative Humidity: 50% RH
d. Unit Pressurization Differential: Refer to Equipment Schedule on Drawings.
3. Unoccupied:
a. Minimum Leaving Air Temperature: 55F.
b. Maximum Leaving Air Temperature: 65ºF.
c. Space Maximum Relative Humidity: 60% RH
d. Unit Pressurization Differential: N/A (Outside air dampers closed/relief fan off)
C. Enable/Disable:
1. Occupied Operation: During occupied hours, the unit shall be enabled, the supply and
return fans shall be started, and dampers shall modulate in accordance with applicable
sequences below.
2. Unoccupied Operation: During unoccupied hours, the unit shall be disabled, the supply
and return fans shall be off, outdoor air damper shall be closed, relief damper shall be
closed, return damper shall be open, the cooling coil control valve shall be closed, and the
preheat coil control valve shall be fully open.
a. Unoccupied Heating: Should the unoccupied space temperature below the
unoccupied heating space temperature set point, the unit shall be started in the
warm-up mode until the space temperature rises 5F below the unoccupied heating
space temperature set point.
b. Unoccupied Cooling: Should the unoccupied space temperature rise above the
unoccupied cooling space temperature set point, the unit shall be started in the
cool-down mode until the space temperature falls 5F below the unoccupied
cooling space temperature set point.
c. Unoccupied Humidity Control: If the space relative humidity rises above the
unoccupied space relative humidity set point (as sensed by the space relative
humidity sensor), the unit shall operate in the cool-down mode until the relative
humidity drops 5% RH below the unoccupied space relative humidity set point.
3. Unoccupied Maintenance Operation: When placed in this mode, the BAS shall operate
as defined in “Unoccupied Maintenance Mode” above.
4. Warm-up Operation: The BAS shall optimize the early start of the unit in warm-up mode
to reach the occupied space heating set point by the occupied time. During warm-up the
supply fan shall be started and controlled by static pressure control, the return fan shall be
started, the return damper shall be open, the relief and outside air dampers shall be
closed, and the preheat coil control valves shall open fully.
5. Cool-down Operation: The BAS shall optimize the early start of the unit in cool-down
mode to reach the occupied space cooling set point by the occupied time. During cool-
down the supply fan shall be started and controlled by static pressure control, the return
fan shall be started, the return damper shall be open, the relief and outside air dampers
shall be closed, and the cooling coil control valve shall open fully.
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 5
D. Startup: Start time shall be based on the BAS optimum start programming in accordance with a
predetermined schedule to be furnished by the Owner and programmed into the BAS. The
outside air damper shall remain closed while the unit operates in warm-up/cool-down mode to
restore occupied set points unless there are cooling economizer conditions. At occupancy time,
the BAS shall begin to modulate the outside air damper in accordance with its sequence of
control.
E. Economizer Mode: Whenever outside air enthalpy is less than return air enthalpy and cooling is
required, economizer operation shall be enabled.
1. Economizer operation shall be available twenty-four hours per day and shall override
unoccupied damper controls.
2. Economizer Mode shall be disabled during dehumidification mode.
F. Supply Fan Control:
1. During unoccupied hours, the fan shall be deactivated. The fan shall be started at its
minimum speed as required to control unoccupied set points.
2. During occupied hours, the BAS shall start the supply fan at its minimum speed. The
required speed shall be determined by the equipment manufacturer and shall be instituted
as the minimum fan speed.
3. Speed Control:
a. A static pressure sensor shall be located at a point two-thirds of the distance from
the supply fan to the end of the longest trunk duct. Locations which result in
extreme variations in static pressure due to terminal box operation shall be
avoided. The static pressure sensor shall function as the control input to the BAS
(and thus to the supply fan VFD) such that a fall in down-duct static pressure will
result in a proportional increase in supply fan speed to maintain set point. The
static pressure set point shall be determined in accordance with “Down-duct Static
Pressure Set Point” below. On a rise in down-duct static pressure, the reverse shall
occur. Initial maximum static pressure set-point shall be 1.0 inches W.G. and shall
be adjustable.
b. Down-duct Static Pressure Set Point: The BAS shall continuously monitor the
damper position of all terminal units. When any damper opens beyond the
maximum set point (initially 95%), the BAS shall reset the down-duct static
pressure set point upward by 5% (adjustable) of the maximum static pressure set
point. This shall occur at 10 minute (adjustable) intervals until no damper is more
than 95% open, or the static pressure set point has been reset upward to the system
maximum setting, or the VFD is at its maximum setting. When all dampers are
opened less than the minimum set point (initially 85%), the BAS shall reset the
down-duct static pressure set-point downward by 5% (adjustable) of the maximum
system static pressure set point. This shall occur at 10 minute (adjustable)
intervals until any damper is more than 85% open, or the VFD is at its minimum
setting.
c. A second static pressure sensor located in the supply fan discharge duct shall
function as a safety input to the BAS. An increase in fan discharge static pressure
above set point (initially 4 inches w.g.) shall cause the BAS to stop the supply fan.
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 6
An alarm shall be sent to the BAS that the unit has been shut down due to fan
over-speed.
4. Drive Malfunction: Should the VFD malfunction as indicated by drive alarm circuit, an
alarm shall be sent to the head end. The fan shall continue to operate unless deactivated
by the VFD protection circuitry.
5. Fan Failure Alarm: Should the supply fan fail (sensed by its current sensing relay), the
unit shall be disabled, and an alarm shall be sent to the head end identifying the unit and
stating that the supply fan has failed.
G. Return Fan Control (F-3):
1. During occupied hours and during economizer operation, the fan shall be started.
a. Speed Control: The BAS shall modulate return fan speed to maintain building
pressurization by tracking the supply airflow less an offset.
b. Minimum Fan Speed: Motor speeds below the manufacturer’s recommended
minimum RPM shall not be permitted.
2. During unoccupied hours, the fan shall be deactivated.
3. Fan Failure Alarm: Should the return fan fail (as sensed by its current sensing relay), an
alarm shall be sent to the head end identifying the unit and stating that the return fan has
failed. Economizer operation shall cease, outdoor air damper shall close, and the return
damper shall open.
4. Drive Malfunction: Should the VFD malfunction as indicated by drive alarm circuit, an
alarm shall be sent to the head end. The fan shall continue to operate unless deactivated
by the VFD protection circuitry.
H. Dehumidification Mode: During occupied or unoccupied operation when the relative humidity
(as sensed by the return duct relative humidity sensor) rises above set point, the unit shall be
placed in dehumidification mode. The BAS shall reset the leaving air temperature set point to
minimum. The unit shall remain in dehumidification mode until the space relative humidity
drops to 5% RH below set point at which time the BAS shall return to normal leaving air
temperature reset control. Refer to applicable paragraphs for operation of valves, dampers, and
fans.
I. Direct Expansion Cooling:
1. During a call for cooling the lead circuit shall be enabled (modulation shall occur
internally with refrigerant APR hot gas bypass valve) to maintain unit leaving air
temperature at set point. If the unit leaving air temperature rises 4°F (adjustable) above
set point after 5 minutes (adjustable) with the lead circuit only, the lag circuit shall be
enabled to increase cooling capacity. If the unit leaving air temperature drops 3°F
(adjustable) below set point after 5 minutes (adjustable), the lag circuit shall be disabled.
If the leaving air temperature continues to drop 3°F (adjustable) below set point after 5
minutes (adjustable), the lead circuit shall be disabled. The lead circuit shall then not be
cycled back on until the leaving air unit leaving air temperature rises 4°F (adjustable)
above set point after 5 minutes (adjustable). This control logic shall be reviewed by the
air handling unit manufacturer and refrigerant modulation APR hot gas bypass valve
manufacturer for approval.
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 7
J. Leaving Air Temperature Reset:
1. Whenever the supply fan reaches its minimum speed, the leaving air temperature set
point shall be increased 1ºF until the leaving air temperature set point is reset up to its
maximum.
2. Whenever the supply fan reaches 50% speed, the leaving air temperature set point shall
be reduced 1ºF until the leaving air temperature set point is reset down to its minimum.
K. Preheat Coil Control Valve: When the supply is started, the preheat coil control valve shall
modulate to maintain the minimum leaving air temperature (as sensed by the temperature sensor
located in the discharge duct) at the minimum leaving air temperature set point. The BAS shall
confirm the DX cooling coil is disabled before modulating the preheat coil control valve.
1. Whenever the supply fan speed reaches its minimum, the preheat coil control valve shall
modulate to increase the leaving air temperature by 1ºF until the leaving air temperature
is reset up to its maximum set point.
2. Whenever the supply fan speed reaches 50% of its RPM range, the cooling coil control
valve shall modulate to reduce the leaving air temperature by 1ºF until the leaving air
temperature is reset down to its minimum set point.
3. Following dehumidification mode, the preheat coil control valve shall remain closed for a
30 minute, adjustable time period to prevent warm air from evaporating moisture off a
wet cooling coil and causing humidification.
L. Return Damper:
1. Unoccupied: Damper shall remain fully open. Damper end switch shall confirm the
damper fully open. If the damper fails to open, an alarm shall be sent to the head end
identifying the unit and stating that the return air damper failed to open.
2. Occupied: The BAS shall modulate return damper as required to provide scheduled
minimum outdoor air (as sensed by the damper air flow measuring system).
3. Economizer: The return damper shall be closed. The damper end switch shall confirm
that the damper is closed. If the damper fails to close, an alarm shall be sent to the head
end identifying the unit and stating that the return damper failed to close.
M. Outdoor Air Damper:
1. Unoccupied: Damper shall remain closed. Damper end switch shall confirm the damper
closed. If damper fails to close, an alarm shall be sent to the head end identifying the unit
and stating that the outdoor damper failed to close.
2. Occupied: The damper shall modulate to its minimum airflow position. Damper end
switch shall confirm the damper open. If damper fails to open, an alarm shall be sent to
the head end identifying the unit and stating that the outdoor damper failed to close. If the
damper fails bring in design outdoor air within +-10% after 5 minutes (adjustable), an
alarm shall be sent to the head end identifying the unit and stating that the unit is not
providing design outdoor air.
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 8
3. Economizer: The damper shall be fully open. Damper end switch shall confirm the
damper open. If damper fails to open, an alarm shall be sent to the head end identifying
the unit and stating that the outdoor damper failed to close.
N. Relief Air Damper:
1. Unoccupied: The BAS shall close the damper.
2. Occupied: The BAS shall close the damper.
3. Economizer: The BAS shall open the damper. If damper fails to open, an alarm shall be
sent to the head end identifying the unit and stating that the relief damper failed to open.
O. Freeze Protection:
1. If the preheat coil discharge air temperature (temperature at the entering face of the
chilled water coil) falls to set point, the unit shall be disabled. This function shall be reset
automatically by the BAS when the temperature reaches 5F above set point.
P. Life Safety: A smoke detector located in the return air duct shall, upon detection of products of
combustion, signal the building fire alarm system and shut down the fans. Refer to floor plans
for quantity. This function shall be manually reset from the unit and shall be so identified on
the head-end graphics. An alarm shall also be provided to the BAS head-end.
Q. System Safety: Whenever the supply fan is stopped or airflow ceases for any reason (as sensed
by the motor status sensing circuit), the supply and relief fans shall be deactivated, power to the
preheat coil control valve shall be removed and the valve shall position open. The outdoor air
damper shall be closed. The relief damper shall be closed. The chilled water valve shall be
closed. In all modes of operation, commanded position values for all control devices such as
dampers and valves shall be readable from the head-end.
R. Filter Change Alarm: The differential pressure across the filters shall be monitored, where if
the differential pressure exceeds 1” wg (adjustable), an alarm is issued to BAS.
2.7 CONSTANT VOLUME SPLIT AIR HANDLING UNIT (AHU-2/CU-2)
A. General: These air handling units include a constant volume supply fan w/VFD, hot water pre-
heat coil, and direct expansion cooling coil. A condensing unit is located on grade with
modulating and staged direct expansion cooling. They provide temperature control and
humidity control for terminal units. A separate return fan is provided.
B. Initial Set Points:
1. General:
a. Minimum Cooling Coil Discharge Temperature: 55ºF (Reset up to 65ºF maximum)
b. Initial Heating Coil Discharge Temperature: 85°F (adjustable)
2. Occupied:
a. Cooling Space Temperature: 75F.
b. Heating Space Temperature: 70F.
c. Space Relative Humidity: 50% RH
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 9
3. Unoccupied:
a. Cooling Space Temperature: 85F.
b. Heating Space Temperature: 55F.
c. Space Relative Humidity: 60% RH
C. Enable/Disable:
1. Occupied Operation: During occupied hours, the unit shall be enabled, the supply fan
shall be started, and dampers shall modulate in accordance with applicable sequences
below.
2. Unoccupied Operation: During unoccupied hours, the unit shall be disabled, the supply
fan shall be off, outdoor air damper shall be closed, the cooling coil control valve shall be
closed, and the preheat coil control valve shall be fully open.
a. Unoccupied Heating: Should the unoccupied space temperature below the
unoccupied heating space temperature set point, the unit shall be started in the
warm-up mode until the space temperature rises 5F below the unoccupied heating
space temperature set point.
b. Unoccupied Cooling: Should the unoccupied space temperature rise above the
unoccupied cooling space temperature set point, the unit shall be started in the
cool-down mode until the space temperature falls 5F below the unoccupied
cooling space temperature set point.
c. Unoccupied Humidity Control: If the space relative humidity rises above the
unoccupied space relative humidity set point (as sensed by the space relative
humidity sensor), the unit shall operate in the cool-down mode until the relative
humidity drops 5% RH below the unoccupied space relative humidity set point.
3. Unoccupied Maintenance Operation: When placed in this mode, the BAS shall operate
as defined in “Unoccupied Maintenance Mode” above.
4. Warm-up Operation: The BAS shall optimize the early start of the unit in warm-up mode
to reach the occupied space heating set point by the occupied time. During warm-up the
supply fan shall be started, the outside air damper shall open, and the preheat coil control
valves shall open fully.
5. Cool-down Operation: The BAS shall optimize the early start of the unit in cool-down
mode to reach the occupied space cooling set point by the occupied time. During cool-
down the supply fan shall be started, the outside air damper shall be open, and the cooling
coil control valve shall open fully.
D. Startup: Start time shall be based on the BAS optimum start programming in accordance with a
predetermined schedule to be furnished by the Owner and programmed into the BAS. The
outside air damper shall remain closed while the unit operates in warm-up/cool-down mode to
restore occupied set points unless there are cooling economizer conditions. At occupancy time,
the BAS shall begin to modulate the outside air damper in accordance with its sequence of
control.
E. Economizer Mode: Whenever outside air enthalpy is less than return air enthalpy and cooling is
required, economizer operation shall be enabled.
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 10
1. Economizer operation shall be available twenty-four hours per day and shall override
unoccupied damper controls.
2. Economizer Mode shall be disabled during dehumidification mode.
F. Supply Fan Control:
1. During unoccupied hours, the fan shall be deactivated. The fan shall be started as
required to control unoccupied set points.
2. During occupied hours, the BAS shall signal the supply fan to start. The supply fan shall
ramp up slowly to design airflow. The required speed shall be determined during balancing
and shall be instituted as the fan speed set point.
3. Drive Malfunction: Should the VFD malfunction as indicated by drive alarm circuit, an
alarm shall be sent to the head end. The fan shall continue to operate unless deactivated
by the VFD protection circuitry.
4. Fan Failure Alarm: Should the supply fan fail (sensed by its current sensing relay), the
unit shall be disabled, and an alarm shall be sent to the head end identifying the unit and
stating that the supply fan has failed.
G. Exhaust Fan (F-1) Control:
1. During occupied hours and during economizer operation, the fan shall be started.
2. During unoccupied hours, the fan shall be deactivated. If AHU-2 is enabled during
unoccupied mode, exhaust fan F-1 shall be started.
3. Fan Failure Alarm: Should the exhaust fan fail (as sensed by its current sensing relay), an
alarm shall be sent to the head end identifying the unit and stating that the exhaust fan has
failed.
H. Dehumidification Mode: During occupied or unoccupied operation when the relative humidity
(as sensed by the space relative humidity sensor) rises above set point, the unit shall be placed
in dehumidification mode. The BAS shall reset the leaving air temperature set point to
minimum. The unit shall remain in dehumidification mode until the space relative humidity
drops to 5% RH below set point at which time the BAS shall return to normal leaving air
temperature reset control. Refer to applicable paragraphs for operation of valves, dampers, and
fans.
I. Space Temperature Control
1. Cooling: On a rise in space temperature above cooling set point (as determined by the
space temperature sensor), the unit shall stage on cooling. On a fall in space temperature,
the reverse shall occur.
2. Heating: On a fall in space temperature below heating set point (as determined by the
space temperature sensor), the unit shall stage on heating. On a rise in space
temperature, the reverse shall occur.
J. Direct Expansion Cooling: The unit manufacturer shall be responsible for the control of the
refrigeration system including the staging of compressors, head pressure control, refrigeration
alarms, etc to maintain temperature control.
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 11
K. Heating Coil Control Valve: In cooling mode, the BAS shall close the heating coil control
valve to prevent simultaneous cooling and heating. Heating coil operation shall only be
available during heating mode.
1. In heating mode, the heating coil control valve shall modulate to control discharge
temperature (as sensed by the temperature sensor downstream of the heating coil). On a
fall in space temperature to 2F below the occupied heating set point, the BAS shall
modulate the heating coil control valve open. The valve shall be fully open to the coil at
2F below set point. On a rise to 1F above set point, the valve shall close.
L. Outdoor Air Damper:
1. Unoccupied: Damper shall remain closed. Damper end switch shall confirm the damper
closed. If damper fails to close, an alarm shall be sent to the head end identifying the unit
and stating that the outdoor damper failed to close.
2. Occupied: The damper shall be fully open. Damper end switch shall confirm the damper
open. If damper fails to open, an alarm shall be sent to the head end identifying the unit
and stating that the outdoor damper failed to close.
3. Economizer: The damper shall be fully open. Damper end switch shall confirm the
damper open. If damper fails to open, an alarm shall be sent to the head end identifying
the unit and stating that the outdoor damper failed to close.
M. Freeze Protection:
1. If the preheat coil discharge air temperature (temperature at the entering face of the direct
expansion cooling coil) falls to set point, the unit shall be disabled. This function shall be
reset automatically by the BAS when the temperature reaches 5F above set point.
N. System Safety: Whenever the supply fan is stopped or airflow ceases for any reason (as sensed
by the motor status sensing circuit), the supply and relief fans shall be deactivated, power to the
preheat coil control valve shall be removed and the valve shall position open. The outdoor air
damper shall be closed. The relief damper shall be closed. The chilled water valve shall be
closed. In all modes of operation, commanded position values for all control devices such as
dampers and valves shall be readable from the head-end.
O. Filter Change Alarm: The differential pressure across the filters shall be monitored, where if
the differential pressure exceeds 1” wg (adjustable), an alarm is issued to BAS.
2.8 WELDING EXHAUST SYSTEM CONTROLS (*AD-01)
A. Description: The welding exhaust system consists of a variable volume inline exhaust fan
equipped with a VFD, motorized outside air dampers located in the space, and hot water
coils at the make-up air louvers in the space.
B. Welding Exhaust Fan (F-2)
1. Enable/Disable: The welding exhaust system shall be enabled and disabled by a
start/stop push button located on the wall within the space. Individual welding
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 12
exhaust hoods are equipped with manual dampers to open the hood exhaust as
needed.
2. Exhaust Fan Control:
a. A static pressure sensor shall be located at a point two-thirds of the distance
from the exhaust fan to the end of the longest trunk duct. Locations which
result in extreme variations in static pressure due to terminal box operation
shall be avoided. The static pressure sensor shall function as the control input
to the BAS (and thus to the supply fan VFD) such that a decrease in down-
duct static pressure will result in a proportional increase in supply fan speed
to maintain set point. On a rise in down-duct static pressure, the reverse shall
occur. Initial maximum static pressure set-point shall be -0.3 inches W.G. and
shall be adjustable.
b. The exhaust fan VFD modulates from minimum to maximum speed and the
motorized bypass damper modulates as required to maintain static pressure
set point of -0.3” w.c.
c. A second static pressure sensor located in the exhaust fan inlet duct shall
function as a safety input to the BAS. An increase in fan discharge static
pressure above set point (initially 4 inches w.g.) shall cause the BAS to stop
the exhaust fan. An alarm shall be sent to the BAS that the unit has been shut
down due to fan over-speed.
d. Drive Malfunction: Should the VFD malfunction as indicated by drive alarm
circuit, an alarm shall be sent to the head end. The fan shall continue to operate
unless deactivated by the VFD protection circuitry.
e. Fan Failure Alarm: Should the supply fan fail (sensed by its current sensing
relay), the unit shall be disabled, and an alarm shall be sent to the head end
identifying the unit and stating that the supply fan has failed.
C. Exhaust Hood Damper:
1. When the welding exhaust system is enabled, the BAS shall open the motorized
damper associated with the fan. Once the damper is confirmed open, the BAS shall
start the associated fan, F-2.
D. Make-Up Air Louvers:
1. When the welding system is exhaust fan is enabled, the motorized make-up air
dampers located in the space shall open.
E. Heating Coils
1. The heating coil control valves shall be modulated open as required to maintain
discharge air temp set point (60°F, adjustable).
2.9 PARALLEL FAN POWERED TERMINAL UNIT WITH HOT WATER HEAT
A. DESCRIPTION: Cooling & heating, ceiling mounted, parallel (intermittently) fan powered,
primary air control, variable air volume terminal unit. The unit contains a characterized damper,
a pitot type flow measuring device with transducer, a fan in parallel with primary air, and a step
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 13
controlled electric heating coil. The velocity of air, as sensed by the flow sensor/transducer
combination using a calculation with a known diameter provides flow (CFM) information to the
BAS. The temperature of the space, as sensed by the space temperature sensor, allows the
controller to determine the required CFM for cooling, when to start the fan, when to start and
where to set the number of steps of electric heat.
B. Set points
1. Occupied Mode:
a. Cooling: 75° F
b. Heating: 70° F
2. Unoccupied Mode:
a. Cooling: 85° F
b. Heating: 55° F
C. Cooling:
1. On a rise in space temperature, as sensed by the space temperature sensor, above the
cooling set point, the BAS shall modulate the terminal unit air valve open in response to
the increase in space temperature until the maximum indicated CFM is reached.
2. On a fall in space temperature, as sensed by the space temperature sensor, the reverse shall
occur until the minimum indicated CFM is reached.
D. Heating:
1. On fall in space temperature, as sensed by the space temperature sensor, to the heating set
point the BAS shall start the terminal unit fan.
2. On a continued fall in space temperature, as sensed by the space temperature sensor, the
BAS shall modulate the hot water valve to maintain space temperature.
3. On a rise in space temperature, as sensed by the space temperature sensor, the reverse shall
occur.
E. Fan:
1. First stage of heat and should be cycled on/off during unoccupied mode to maintain heating
set point.
F. Morning Warm-Up/Cool-Down
1. If zone temperature is below the occupied heating set point, the BAS shall open the air
valve fully, start the terminal unit fan and fully open the hot water control valve.
2. If zone temperature is above the occupied cooling set point, the BAS shall open the air
valve fully.
G. Unoccupied Heating
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 14
1. On fall in space temperature, as sensed by the space temperature sensor, to the unoccupied
heating set point the BAS shall start the terminal unit fan and fully open the hot water
control valve.
2. On a rise in space temperature, as sensed by the space temperature sensor, to five degrees
above the unoccupied space temperature set point, the reverse shall occur.
H. Monitoring points: The following information shall be sent to the BAS by the unitary controller
and subsequently displayed on the head end graphics.
1. Hot water valve position feedback.
2. Air valve position feedback.
3. Measured/calculated primary air flow.
4. Fan status
I. Dead band: A five-degree (5°F) dead band shall be maintained between heating and cooling set
points at all times. This shall not be an adjustable value on the head end graphics.
2.10 SERIES FAN-POWERED TERMINAL UNITS
A. Set points
1. Occupied Mode:
a. Cooling: 75° F
b. Heating: 70° F
2. Unoccupied Mode:
a. Cooling: 85° F
b. Heating: 55° F
B. Unoccupied Mode/Unoccupied Maintenance Mode: The BAS shall close the air valve, close the
hot water coil control valve and stop the fan.
1. Unoccupied Heating: If zone temperature falls below the unoccupied heating set point
(55°F adjustable), the BAS shall start the terminal unit fan at 100% speed and open the
hot water coil control valve.
2. Unoccupied Cooling: If zone temperature rises above the unoccupied cooling set point
(85°F adjustable), the BAS shall start the fan and the associated air handling unit and
open the air valve.
C. Morning Warm-Up/Cool-Down
1. If zone temperature is below the occupied heating set point, the BAS shall open the air
valve, start the terminal unit fan and open the hot water coil control valve.
2. If zone temperature is above the occupied cooling set point, the BAS shall start the
associated air handling unit and open the air valve.
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 15
D. Occupied Mode: The BAS shall start the terminal unit fan and modulate the air valve to
maintain zone temperature at set point. On a fall in zone temperature below heating set point,
the BAS shall modulate the heating coil control valve to maintain zone temperature at set point.
If zone temperature rises above the occupied set point, the BAS shall modulate the air valve
open to maintain the zone temperature set point.
E. Discharge Air Temperature: The BAS shall indicate discharge air temperature at the head end.
2.11 SINGLE DUCT VAV TERMINAL UNITS
A. Set points
1. Occupied Mode:
a. Cooling: 75° F
b. Heating: 70° F
2. Unoccupied Mode:
a. Cooling: 85° F
b. Heating: 55° F
B. Unoccupied Mode: The BAS shall close the air valve and the hot water coil control valve.
1. Unoccupied Heating: If zone temperature falls below the unoccupied heating set point
(55°F adjustable), the BAS shall start the associated air handling unit and open the air
valve. The hot water coil control valve shall open.
2. Unoccupied Cooling: If zone temperature rises above the unoccupied cooling set point
(85°F adjustable), the BAS shall start the associated air handling unit and open the air
valve.
C. Morning Warm-Up/Cool-Down
1. The BAS shall open the air valve. If heating is required, the BAS shall open the hot
water coil control valve to reach occupied set point by the start of occupancy. Once the
occupied heating set point is reached and occupancy begins, the BAS shall operate the
terminal units as required for occupied mode.
D. Occupied/Unoccupied Maintenance Mode: The BAS shall modulate the air valve to maintain
zone temperature at set point. As zone temperature rises, the BAS shall modulate the air valve
open. As zone temperature falls, the BAS shall set modulate the air valve to its minimum
position. If the zone temperature reaches the space occupied heating set point, the BAS shall
modulate the air valve to its heating airflow position and modulate open the heating coil control
valve to maintain the occupied zone heating set point.
E. Discharge Air Temperature: The BAS shall indicate discharge air temperature at the head end.
2.12 FAN (Control Method BAS Schedule – F-4, F-6)
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 16
A. General: These are general duty fans which operate on a time-of-day schedule. Refer to the
Fan Schedule for fan information.
B. Occupied/Unoccupied:
1. Unoccupied Operation: During unoccupied hours the fan shall be off and the damper
shall be closed.
2. Occupied Operation: During occupied hours, the fan shall be on and the damper shall be
open.
C. Start:
1. At the start of occupied operation, the BAS shall open the motorized damper associated
with the fan. Once the damper is confirmed open, the BAS shall start the fan. If the
damper is interlocked with fan operation, then the BAS shall start the fan.
D. Stop:
1. At the beginning of unoccupied operation, the BAS shall stop the fan and close the
associated damper (or just stop the fan if the damper is interlocked).
E. Fan failure alarm:
1. If the fan fails to start (as sensed by its current sensing relay) an alarm shall be sent to the
head end identifying the fan and stating that is has failed to start.
2.13 FAN (Control Method BAS Sensor – F-5)
A. General: Inline exhaust fan that is controlled by a wall-mounted temperature sensor. Refer to
the Fan Schedule for fan information.
B. Set points:
1. Space Temperature: 80°F (adj)
C. Space Temperature Control: When space temperature (as sensed by wall-mounted temperature
sensor) rises above set point, the BAS shall start the fan and open the associated motorized intake
damper. When space temperature (as sensed by wall-mounted temperature sensor) falls below set
point, the BAS shall disable the fan and close the associated motorized damper.
D. Fan failure alarm:
1. If the fan fails to start (as sensed by its current sensing relay), an alarm shall be sent to the
head end identifying the fan and stating that is has failed to start.
2.14 HOT WATER PUMP
A. Pump Start: On a call for heating from any piece of equipment, the BAS shall command the pump
to start.
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 230993 - 17
B. Pump Stop: When no equipment calls for heating for 10 minutes, the BAS shall send a stop
command.
C. Pump Alarms:
1. Should the pump fail to start, as sensed by its current sensing relay, an alarm shall be sent
to the head end identifying the pump and stating that it has failed to start.
D. Hot Water Temperature Monitoring: The BAS shall monitor the hot water supply and return
temperature.
END OF SECTION 230993
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SPECIALTY EXHAUST SYSTEMS 233424 - 1
SECTION 233424 – SPECIALTY EXHAUST SYSTEMS (*AD-01)
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Provisions of the Contract and of the Contract Documents apply to this Section.
1.2 SUBMITTALS
A. Product Data: Include rated capacities, furnished specialties, and accessories for each type of
product indicated and include the following:
1. Certified fan performance curves with system operating conditions indicated.
2. Motor ratings, electrical characteristics, and accessories.
3. Control panel with wiring diagram.
B. Shop Drawings:
1. Fabricated welding exhaust hoods.
2. Detail equipment assemblies and indicate dimensions, weights, loads, required
clearances, and components. Indicate location and size of each field connection.
3. Wiring Diagrams: Power, signal, and control wiring. Differentiate between
manufacturer-installed and field-installed wiring.
C. Maintenance Data: For equipment specified in this section; to include in maintenance manuals.
1.3 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
B. NEMA Compliance: Motors and electrical accessories shall comply with NEMA standards.
C. UL Standard: Fan shall comply with UL 705.
1.4 COORDINATION
A. Coordinate with size and location of structural-steel members.
B. Coordinate duct drop locations with equipment indicated.
PART 2 - PRODUCTS
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SPECIALTY EXHAUST SYSTEMS 233424 - 2
2.1 MANUFACTURERS
A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering
products that may be incorporated into the Work include, but are not limited to, the following:
1. Welding Exhaust Systems
a. Industrial Air Products
b. Plymovent
c. United Air Specialists
2.2 WELDING EXHAUST SYSTEMS
A. General: Fabricated welding exhaust hoods, extractor arms, and welding exhaust fan and
associated controls.
B. Exhaust Fan: Aluminum spark-resistant wheel and wear plate, mounted vertically on steel
supports.
C. Extractor Arms: Telescopic swing exhaust arm with volume damper.
D. Welding Booths: Fabricated welding booth hood as indicated on Drawing M5.2. Hood shall be
16-gauge galvanized steel with manual shut-off dampers.
E. Controls: Custom control enclosure to house fan VFD, static pressure transducer, remote
start/stop contacts, and a dry contact for the emergency shut down. Coordinate with Section
230900.
F. Rigid Round Galvanized Steel Ductwork:
1. Ductwork Straight Sections shall be 26 gauge galvanized steel, spiral lockseam
construction in sizes 3” thru 12” diameter.
G. Rigid Round Galvanized Steel Duct Fittings:
1. Duct Elbows: Duct Elbows shall be smooth radius tube-type, fabricated of 26 gauge
galvanized steel, with a centerline radius equal to 1.5 times the diameter of the elbow.
Elbows shall be utilized for both 45 and 90- degree bends.
2. Duct Tees: Duct Tees shall be tapered-body reducing type, fabricated of 26 gauge
galvanized steel, with 45 degree lateral take-offs.
3. Wye Branches: Wye branches shall be fabricated of 26 gauge galvanized steel, with two
reducing branches at 45 degrees to the fitting outlet.
4. Miscellaneous Duct Adaptors and Transitions: Miscellaneous adaptors and transitions,
including hose adaptors, reducers, rectangular-to-round transitions, and bell-mouths, shall
be fabricated of 26 gauge galvanized steel.
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SPECIALTY EXHAUST SYSTEMS 233424 - 3
H. Galvanized Steel Duct Hardware:
1. Hangers: Hangers shall be pre-drilled, two-piece saddles, fabricated of 14-16 gauge
galvanized steel.
2.3 DUCTWORK HANGERS AND SUPPORTS
A. Hanger Rods: Galvanized, all-thread.
B. Strap and Rod Sizes: Comply with SMACNA's "HVAC Duct Construction Standards - Metal
and Flexible, Third Edition 2005," Table 5-1, "Rectangular Duct Hangers Minimum Size," and
Table 5-2, "Minimum Hanger Sizes for Round Duct."
C. Steel Cables for Galvanized-Steel Ducts: Galvanized steel complying with ASTM A 603.
D. Steel Cable End Connections: Cadmium-plated steel assemblies with brackets, swivel, and
bolts designed for duct hanger service; with an automatic-locking and clamping device.
E. Duct Attachments: Sheet metal screws, blind rivets, or self-tapping metal screws; compatible
with duct materials.
F. Trapeze and Riser Supports:
1. Supports for Galvanized-Steel Ducts: Galvanized-steel shapes and plates.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Verify field conditions prior to installation of exhaust systems and equipment. Install systems
and equipment in accordance with manufacturers’ recommendations, using standard materials
and hardware compatible with the temperatures and operating pressures of the system.
B. Install units with clearances for service and maintenance, as recommended by the manufacturer.
C. Label units according to requirements specified in Division 23 Section "Mechanical
Identification."
3.2 DUCT INSTALLATION
A. Drawing plans, schematics, and diagrams indicate general location and arrangement of duct
system. Duct locations, configurations, and arrangements were used to size ducts and calculate
friction loss for air-handling equipment sizing and for other design considerations. Install duct
systems as indicated unless deviations to layout are approved by Architect in writing.
B. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible, Third
Edition 2005" unless otherwise indicated.
C. Install ducts with fewest possible joints.
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SPECIALTY EXHAUST SYSTEMS 233424 - 4
D. Install factory-fabricated fittings for changes in direction, size, and shape and for branch
connections.
E. Unless otherwise indicated, install ducts vertically or horizontally, and parallel or perpendicular
to building lines.
F. Install ducts close to walls, overhead construction, columns, and other structural and permanent
enclosure elements of building. Maintain clearances for equipment maintenance.
G. Install ducts with a clearance of 1 inch, plus allowance for installation of insulation at specified
thickness.
H. Do not route ducts through transformer vaults, electrical equipment rooms, elevator equipment
rooms or electrical enclosures.
I. Where ducts pass through non-fire-rated interior partitions and exterior walls and are exposed to
view, cover the opening between the partition and duct or duct insulation with sheet metal
flanges of same metal thickness as the duct. Overlap openings on four sides by at least 1-1/2
inches.
J. Protect duct interiors from moisture, construction debris, dust, and other foreign
materials. Comply with SMACNA's "Duct Cleanliness for New Construction Guidelines."
3.3 INSTALLATION OF EXPOSED DUCTWORK
A. Protect ducts exposed in finished spaces from being dented, scratched, or damaged.
B. Maintain consistency, symmetry, and uniformity in the arrangement and fabrication of duct,
fittings, hangers, supports, accessories, and air outlets.
C. Repair or replace damaged sections and finished work that does not comply with these
requirements.
3.4 DUCTWORK HANGER AND SUPPORT INSTALLATION
A. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible, Third
Edition 2005," Chapter 5, "Hangers and Supports."
B. Building Attachments: Unless indicated otherwise, provide concrete inserts, powder-actuated
fasteners, or structural-steel fasteners appropriate for construction materials to which hangers
are being attached.
1. Where practical, install concrete inserts before placing concrete.
2. Do not use powder-actuated concrete fasteners for lightweight-aggregate concrete or for
slabs less than 4 inches thick.
C. Hanger Spacing: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and
Flexible, Third Edition 2005," Table 5-1, "Rectangular Duct Hangers Minimum Size," and
Table 5-2, "Minimum Hanger Sizes for Round Duct," for maximum hanger spacing; install
hangers and supports within 24 inches of each elbow and within 48 inches of each branch
intersection.
D. Hangers Exposed to View: Threaded rod and channel supports.
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SPECIALTY EXHAUST SYSTEMS 233424 - 5
E. Support vertical ducts with channel secured to the sides of the duct with welds, bolts, sheet
metal screws, or blind rivets; support at each floor or at a maximum interval of 18 feet.
F. Install upper attachments to structures. Select and size upper attachments with pull-out, tension,
and shear capacities appropriate for supported loads and building materials where used.
3.5 FIELD QUALITY CONTROL
A. Equipment Startup Checks:
1. Verify that shipping, blocking, and bracing are removed.
2. Verify that unit is secure on mountings and supporting devices.
3. Verify that connections to ducts and electrical components are complete.
4. Verify that proper thermal-overload protection is installed in motors, starters, and
disconnect switches.
5. Verify that cleaning and adjusting of all components is complete.
6. Verify lubrication for bearings and other moving parts.
B. Starting Procedures:
1. Measure and record motor voltage and amperage.
2. Test and adjust controls and safeties. Replace damaged or malfunctioning controls and
components.
C. Operational Test: After electrical circuitry has been energized, start units to confirm proper
motor rotation and system operation. Remove malfunctioning units, replace with new units, and
retest. Verify scheduled airflow at source capture points, and at fume exhaust fans and
collectors. Refer to Section 230593-Testing and Balancing for HVAC, for applicable
procedures and reports.
3.6 DEMONSTRATION
A. Engage a factory-authorized service representative to train Owner's maintenance personnel to
adjust, operate, and maintain exhaust systems.
1. Train Owner's maintenance personnel on procedures and schedules for starting and
stopping, troubleshooting, servicing, and maintaining equipment and schedules.
2. Review data in maintenance manuals.
3. Schedule training with Owner, through Architect, with at least seven days' advance
notice.
ADVANCED MANUFACTURING CENTER RENOVATIONS
WAYNE COMMUNITY COLLEGE
Goldsboro, North Carolina
Architect’s Project No: 593101
SCO ID# 16-15906-01A
Addendum 01 – 12/8/20 SPECIALTY EXHAUST SYSTEMS 233424 - 6
END OF SECTION 233424
UPFEB
FEB
FEB
FEB
FEB
FEB
FEB
FEB
A. PATCH AND REPAIR ANY DAMAGE OR HOLES IN EXISTING PARTITIONS FROM
DEMOLITION WORK. AT MASORY PARTITIONS WHERE MECHANICAL DUCT WORK IS
REMOVED AND NOT REPLACED, SEE DETAIL 5/A2.1 FOR PENETRATION INFILL.
REPAIR WORK SHOULD MATCH THE QUALITY OF EXISTING PARTITIONS AND
PREPARED TO RECIEVE NEW FINISHES.
B. EXTERIOR MASONRY BLOCK WALLS SHALL BE STAINED. COLOR SHALL BE
SELECTED BY ARCHITECT. - ADDITIVE BID ITEM 2
FLOOR PLAN GENERAL NOTES
EXISTING
GREEN APPLE
LAB
140
TOILET
118
EXISTING MEN
115
STORAGE
150
INSTRUCTIONAL
LAB
160
OFFICE
162CONFERENCE
174
LOUNGE
110
WATER JET
133
MATERIAL
PREP/
FABRICATION
130
WELDING
171
WELDING
SHOP
170
EXISTING
WOMEN
116
EXISTING ELEV
EQUIP
117
BREAK
163
9' -
0"
+/- 8' - 0"
ACETYLENE
STORAGE
132A
OXYGEN
STORAGE
132B
A2.2
1
A2.2
2
A4.11
STORAGE
135
JAN
114
RECEIVING
131
CIRCULATION
111
CIRCULATION
112
ELECTRICAL
134
H134H133A
H135A
H118
H110
H162
H171
H160B
H137H150A
P2
P2
P2
M2
M4
2
2
3
M3
3
4
5
4
5
44 54 54 54 5
4
5
4
5
4
5
4 5
4 5
+/-
122' -
3 5
/8"
+/- 122' - 3 5/8"
1
A5.0
1
A5.0
2
A5.0
2
A5.0
A7.1
1
25
9' - 4"
16' -
7"
H160A
H160D
H135B
+/-
10' -
0"
6
H140E
7
EXISTING
STORAGE
141
EXISTING
STORAGE
136
EXISTING ELEC
128
EXISTING
BROOM
CLOSET
129
ALIGN
VESTIBULE
161
+/- 5' - 0"
1' - 8"
5' -
0"
9' - 0"
CIRCULATION
132
ALIGN
1' - 9 1/16"
8
9
A4.1
A4.1 3
A4.1
2
EXTENTS OF WORK AREA
A2.1
1
P2P2
ALIG
N
ALIGN
P2
LINE OF MASONRY
WALL ABOVE
M3
M3
P2
10
P1
H112
A2.1
2
2
17
P2
WITH SINK
4
21
2424
24
24
24
24
9
1
A5.1A3.0.12
A2.1
3
ABOVE
CIRCULATION
111
H114
1
2
AS
3
AS
4
AS
H111B
H111A
6' -
8"
10' - 2"
A4.1
2a
WA1
3 3/8"
11
12
13
14
MECH. EQUIP.
MEZZANINE
280
10
MECHANICAL AND ELECTRICAL
EQUIPMENT NOT SHOWN FOR
CLARITY. REFER TO MECHIANICAL AND
ELETRICAL DRAWINGS FOR LAYOUTS.
15
AD-01
FIRST FLOOR
Roof - Hocutt
28' - 0"
P2
P2
11
11
18
19
19
10' -
0"
20
11
11
22
23
FIE
LD
VE
RIF
Y
EX
IST
ING
PE
NE
TR
AT
ION
EIGH, NCRAL
CHITECTSCP
RA
MOSE
ELY
R
N
EGISTE
RED ARCHITE
CTURAL
CO
RPORAT IO
N
O
RTH OCAR
L I
NA
Y J LOCKWL
AR
B
DE
OO
14206
REG
ISTERED A
T
N
RO
TH CA
A
RALEIGH,
ROL IN
NC
R
CETI
CH
D
MOSELEYARCHITECTS.COM
50149
PROJECT NO:
DATE:
PH
ON
E (
919)
840-0
091
911 N
. W
ES
T S
TR
EE
T, S
UIT
E 2
05 R
ALE
IGH
, N
OR
TH
CA
RO
LIN
A 27603
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
11/06/20
12
/8/2
02
0 1
1:2
6:0
1 A
M FLOOR PLAN AND
DETAILS
WA
YN
E C
OM
MU
NIT
Y C
OL
LE
GE
AD
VA
NC
ED
MA
NU
FA
CT
UR
ING
CE
NT
ER
RE
NO
VA
TIO
N
3000
Way
ne
Mem
ori
al D
r, G
old
sbo
ro, N
C 2
7534
A2.1
SC
O ID
# 1
6-1
59
06
-01
A
593101
NOVEMBER 6, 2020
1/8" = 1'-0"
FIRST FLOOR PLAN
APPLIES TO DRAWINGS A2.1
1 NEW CONCRETE FLOOR SLAB. FINISH LEVEL TO MATCH ADJACENT FINISH
FLOOR - ADDITIVE BID ITEM 3
2 UV CURTAIN STRIPS AT WELDING BOOTHS, TYP
3 CHAIN LINK FENCING AND GATE; 8' - 0" IN HEIGHT
4 REPAIR OR REPLACE LINTELS AS NECESSARY. REMOVE BLOCK AS
REQUIRED TO INSTALL FLASHING. REINSTALL BLOCK WITH WEEP JOINTS AT
REQUIRED SPACING - ADDITIVE BID ITEM 2
5 PAINT EXISTING DOORS AND FRAMES - ADDITIVE BID ITEM 2
6 INSTALL NEW DOOR LEAFS AND HARDWARE AT THIS LOCATION
7 FRAME AROUND EXISTING CONDUIT AND PIPING ALONG MASONRY WALL
8 12' MARKER BOARD - NIC
9 INSTALL COUNTERTOP
10 EXISTING ACCESS LADDER
11 EXISTING MASONRY WALL
12 BACKER ROD AND SEALANT
13 SEALANT
14 GALV CFSF-S; ATTACH USING 1/4" DIA CONCRETE ANCHOR SCREW
15 EXISTING PIPE RAIL
16 NOT USED
17 SEE DETAIL 4/A2.1 FOR BRACING DETAIL
18 CFSF-S CLIP WITH 1/4" DIA CONCRETE SCREW ANCHORS TO ATTACH TO
EXISTING MASONRY WALL
19 3 5/8 CFSF-S BRACE AT 6'-0" ON CENTER
20 3 5/8" CFSF-S AS REQUIRED FOR SUPPORTING SUSPENDED CEILING
21 WATER FOUNTAIN, OFCI
22 20 GAUGE SHEET METAL, ATTACH TO EXISTING WALL. PAINT TO MATCH
WALL WHERE BELOW CEILING
23 ACOUSTIC INSULATION
24 SEE DETAIL 5/A2.1 FOR DUCT PENETRATION PATCHING
25 WIRE MESH PARTITION AND DOORS
0' 8'4' 16'2'
1/8" = 1'-0"
1/4" = 1'-0"A2.1 A2.1
FIRST FLOOR PLAN - ADDITIVE BID ITEM 31
0' 4'2' 8'1'
1/4" = 1'-0"
3" = 1'-0"A2.1 A2.1
DETAIL2
6" 30"18"1'0" 2'
3/4" = 1'-0"
1/4" = 1'-0"A2.1 A2.1
ENLARGED PLAN3
3/4" = 1'-0"A2.1
DETAIL4
A2.1
NO SCALEA2.1
DUCT PENETRATION PATCH DETAIL5
1"0" 2" 4" 8"
3" = 1'-0"
REVISIONS
DATE DESCRIPTION
12/8/20 AD-01
AD-01
CHITECTSCP
RA
MOSE
ELY
N
CO
RPORAT IO
N
O
RTH OCAR
L I
NA
REGIST
ERE
D ENGINE
ERING
EIGH, NCRAL
SEAL
SONP. FORS
Y
037569
TH
JA
CAROLINA
HTRO
N
PR
OFESSIONA
L
ENG INEE
R11/6/20
MOSELEYARCHITECTS.COM
C-3469
PROJECT NO:
DATE:
PH
ON
E (
919
) 8
40
-009
1
911
N. W
ES
T S
TR
EE
T, S
UIT
E 2
05
R
ALE
IGH
, N
OR
TH
CA
RO
LIN
A 27
60
3
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
12
/8/2
02
0 1
1:0
2:2
4 A
M SCHEDULES
WA
YN
E C
OM
MU
NIT
Y C
OL
LE
GE
AD
VA
NC
ED
MA
NU
FA
CT
UR
ING
CE
NT
ER
RE
NO
VA
TIO
N
3000
Way
ne
Mem
ori
al D
r, G
old
sbo
ro, N
C 2
7534
M0.2
SC
O I
D #
16
-15
90
6-0
1A
593101
NOVEMBER 6, 2020
TERMINAL UNIT SCHEDULE
TAG MANUFACTURERMODEL
NUMBER
AIR VALVE COIL
WEIGHT(LBS)
INLETDIAMETER
(IN)MAXIMUM
AIRFLOW (CFM)
MINIMUMAIRFLOW
(CFM)
APD AT MAXAIR FLOW
(IN-WC)
DESIGNAIRFLOW
(CFM)CAPACITY
(BTUH) EAT (°F) LAT (°F)FLOW RATE
(GPM)
FLUIDPRESSURE
DROP(FT WC)
ROWS(NO)
TU1-03 TRANE VCWF 10 870 645 0.22 645 23,500 55 88.6 1.5 6.10 1 29
FAN POWERED TERMINAL UNIT SCHEDULE
TAG MANUFACTURERMODEL
NUMBER
AIR VALVE FAN COIL ELECTRICAL DATA
WEIGHT(LBS)
INLETDIAMETER
(IN)
MAXIMUM AIRFLOW(CFM)
MINIMUM AIRFLOW(CFM)
APD ATMAXIMUM AIR
FLOW(IN WC) FAN SIZE
MOTOR(HP)
AIRFLOW(CFM)
ESP(IN WC)
DESIGNAIRFLOW
(CFM)CAPACITY
(BTUH)EAT(°F)
LAT(°F)
FLOW RATE(GPM)
WATERPRESSURE
DROP(FT WC)
ROWS(NO)
FLA(A)
MCA(A)
MOCP(A)
SERVICE
V PH HZ
TU1-01 TRANE VPWF 12 1,650 1,000 0.18 03SQ 1/3 650 0.25 1,650 49,290 61.0 88.8 4.0 3.57 1 2.4 3.0 15 277 1 60 107
TU1-02 TRANE VPWF 10 1,390 580 0.17 03SQ 1/3 810 0.25 1,390 42,190 63.7 91.7 3.0 2.06 1 2.4 3.0 15 277 1 60 106
TU1-04 TRANE VPWF 10 970 285 0.09 03SQ 1/3 685 0.25 970 34,420 64.2 96.9 2.5 1.45 1 2.4 3.0 15 277 1 60 106
TU1-05 TRANE VPWF 10 1,060 320 0.10 03SQ 1/3 740 0.25 1,060 37,210 64.0 96.7 3.0 2.06 1 2.4 3.0 15 277 1 60 106
TU1-06 TRANE VPWF 10 1,350 410 0.16 03SQ 1/3 940 0.25 1,350 43,780 65.4 95.3 4.0 3.57 1 2.4 3.0 15 277 1 60 106
AIR HANDLING UNIT SCHEDULE
TAG MANUFACTURERMODEL
NUMBER
SUPPLY FAN
OUTSIDE AIRDESIGN
AIRFLOW(CFM)
DX COOLING COIL HYDRONIC HEATING COIL ELECTRICAL DATA
WEIGHT(LBS) NOTES
DESIGNAIRFLOW
(CFM)ESP
(IN WC)
FAN WHEEL
MOTOR SIZE(HP)
TOTALCAPACITY
(BTUH)
SENSIBLECAPACITY
(BTUH)
EAT LAT
SENSIBLECAPACITY
(BTUH)EAT(°F)
LAT(°F)
EWT(°F)
LWT(°F)
WATERFLOWRATE(GPM)
WATERPRESSURE
DROP(FT WC)
SINGLE-POINT DATA SERVICE
DIAMETER(IN) TYPE
FANSPEED(RPM) (°F DB) (°F WB) (°F DB) (°F WB)
UNITFLA(A)
UNITMCA(A)
UNITMOCP
(A) (V) (PH) (HZ)
AHU-1 TRANE CSAA-035 18,000 1.50 25 AF 1407 20 7,250 907,340 572,650 83.0 69.4 54.0 53.4 722,280 18.0 55.0 180 160 72 10.2 24.5 30.6 50.0 480 3 60 3,658 1
AHU-2 TRANE CSAA-012 5,400 1.50 15 FC 1144 7-1/2 5,400 458,970 242,980 95.0 78.0 54.0 53.8 304,530 18.0 70.0 180 160 30 2.9 9.4 11.8 20.0 480 3 60 1,334 2
CONDENSING UNIT SCHEDULE
TAG MANUFACTURER MODEL LOCATIONCAPACITY
(TONS)
NUMBEROF
COMPRESSORS
NUMBEROF
CIRCUITS
AMBIENT AIRTEMPERATURE
(°F)MCA(A)
MOCP(A)
ELECTRICAL DATAWEIGHT
(LBS) NOTES(V) (PH) (HZ)
CU-1 TRANE RAUJ080 ROOF 80 6 2 95 174 200 480 3 60 5,783 1
CU-2 TRANE RAUJ040 ROOF 40 4 2 95 87 100 480 3 60 3,120 -
HOT WATER COIL SCHEDULE
TAG MANUFACTURER MODEL NUMBER LOCATION SIZE
TOTALCAPACITY
(BTUH)
AIR HYDRONIC HEATING COIL
WEIGHT(LBS)
AIR FLOW(CFM)
EAT(°F)
LAT(°F)
FLOW RATE(GPM)
EWT(°F)
WATERPRESSURE
DROP(FT WC)
HC-1 TRANE 5W 171 WELDING 54x21 189,790 3,500 10 60 19.0 180 2.61 58
HC-2 TRANE 5W 171 WELDING 54x21 189,790 3,500 10 60 19.0 180 2.61 58
HC-3 TRANE 5W 171 WELDING 54x21 189,790 3,500 10 60 19.0 180 2.61 58
HC-4 TRANE 5W 171 WELDING 54x21 189,790 3,500 10 60 19.0 180 2.61 58
HC-5 TRANE 5W 171 WELDING 54x21 189,790 3,500 10 60 19.0 180 2.61 58
HC-6 TRANE 5W 171 WELDING 54x21 189,790 3,500 10 60 19.0 180 2.61 58
HC-7 TRANE 5W 171 WELDING 54x21 189,790 3,500 10 60 19.0 180 2.61 58
HC-8 TRANE 5W 171 WELDING 54x21 189,790 3,500 10 60 19.0 180 2.61 58
dofiibI=obdfpqboI=C=afccrpbo=p`ebaribTAG MANUFACTURER MODEL NUMBER MOUNTING STYLE NECK SIZE FACE SIZE MAX NC LEVEL NOTES
S1 PRICE ASCD LAY-IN 6" 24x24 30 -
S2 PRICE ASCD LAY-IN 8" 24x24 30 -
S3 PRICE ASCD LAY-IN 10" 24x24 30 -
S4 PRICE SDGE DUCT-MOUNTED 10x6 12x8 30 1
R1 PRICE 635-TB-L LAY-IN 22x22 24x24 30 -
R2 PRICE 635-F-L SURFACE 40x14 42x16 30 -
E1 PRICE 80-F SURFACE 6x6 8x8 30 -
E2 PRICE 80-F SURFACE 10x10 12x12 30 -
E4 PRICE 80 DUCT-MOUNTED 10x10 12x12 30 -
T1 PRICE 635-TB-L LAY-IN 22x22 24x24 30 -
FAN SCHEDULE
TAG MANUFACTURER MODEL NUMBER SERVING TYPEAIRFLOW
(CFM)ESP
(IN WC)FAN WHEEL
(RPM) DRIVE TYPE SONESCONTROLMETHOD
MOTOR(HP)
ELECTRICAL DATA WEIGHT(LBS) NOTES(V) (PH) (HZ)
F-1 GREENHECK BSQ-180 WELDING AREA INLINE CENTRIFUGAL 5,400 1.00 1527 BELT 23 BAS 3 480 3 60 183 1,2
F-2 INDUSTRIAL AIR PRODUCTS 402-ICB WELDING BOOTHS INLINE CENTRIFUGAL 28,000 3.00 1146 BELT 99 WALL SWITCH 50 480 3 60 2,009 -
F-3 GREENHECK BSQ-240-VG AHU-1 RETURN FAN INLINE CENTRIFUGAL 10,750 0.75 1198 BELT 36 BAS 5 480 3 60 287 1,2
F-4 GREENHECK SQ-95-VG 118, 136, 141 INLINE CENTRIFUGAL 525 0.40 1501 DIRECT 7.7 BAS 1/6 120 1 60 44 1
F-5 GREENHECK SQ-90-VG 150 STORAGE INLINE CENTRIFUGAL 450 0.40 1578 DIRECT 7.6 BAS SENSOR 1/10 120 1 60 44 1
F-6 GREENHECK G-123-VG 130 MATERIAL PREP/FABRICATION ROOF MTD. CENTRIFUGAL 1,650 0.30 1488 DIRECT 13.5 BAS 1/2 120 1 60 43 1,3
PUMP SCHEDULE
TAG MANUFACTURER MODEL NUMBER SERVING LOCATION TYPE
OPERATING DATA
SUCTION SIZE(IN)
DISCHARGESIZE(IN)
IMPELLER SIZE(IN) MOTOR RPM
MOTOR(HP)
ELECTRICAL DATA
FLOW(GPM)
HEAD(FT WC)
EFFICIENCY(%) V PH HZ
HWP-1 BELL & GOSSETT e1510-3BD HOT WATER LOOP MEZZANINE BASE MOUNTED 350.0 50 78.4 4 3 7.750 1770 7.5 480 3 60
NOTES:
1. PROVIDE VARIABLE VOLUME SUPPLY FAN WITH FACTORY INSTALLED VFD AND ECONOMIZER OPERATION.
2. PROVIDE CONSTANT VOLUME SUPPLY FAN WITH FACTORY INSTALLED VFD.
NOTES:
1. PROVIDE RAWALS APR CONTROL VALVE TO MODULATE COOLING CAPACITY DOWN TO 15% ON LEAD CIRCUIT FOR EVAPORATOR COIL LEAVING AIR TEMPERATURE CONTROL.
2. MINIMUM EFFICIENCY OF CONDENSING UNIT: 9.5 EER.
3. MINIMUM EFFICIENCY OF CONDENSING UNIT: 9.8 EER.
NOTES:
1. PROVIDE MOTORIZED BACKDRAFT DAMPERS AND INTERLOCK WITH FAN OPERATION.
2. PROVIDE VFD.
3. PROVIDE CURB ADAPTER.
NOTES:
1. PROVIDE PRIME COAT FINISH FOR FIELD PAINTING. COORDINATE CUSTOM COLOR WITH ARCHITECT.
REVISIONS
DATE DESCRIPTION
12/8/20 *AD-01
*AD-01
S
S
S
SS
S
S
S
S
S
S
S
S
SS S
S
1
2
3 4
4
5
5
5
6
6
EX
36x24
EX
24x12
EX
22
x8
EX 40x16EX 40x20
EX
36x42
EX 36x24EX 36x18
EX 66x20
EX
22
x1
2
EX
22
x1
2
EX
16
x1
2
6
6
6
7 8
9
10
10
10
10
10
10
10
10
10
10
10
10
10 10 10
10
10
11
12
*AD-01
13
CHITECTSCP
RA
MOSE
ELY
N
CO
RPORAT IO
N
O
RTH OCAR
L I
NA
REGIST
ERE
D ENGINE
ERING
EIGH, NCRAL
SEAL
SONP. FORS
Y
037569
TH
JA
CAROLINA
HTRO
N
PR
OFESSIONA
L
ENG INEE
R11/6/20
MOSELEYARCHITECTS.COM
C-3469
PROJECT NO:
DATE:
PH
ON
E (
919
) 8
40
-009
1
911
N. W
ES
T S
TR
EE
T, S
UIT
E 2
05
R
ALE
IGH
, N
OR
TH
CA
RO
LIN
A 27
60
3
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
12
/8/2
02
0 1
1:0
2:2
7 A
M SECOND FLOOR
DEMOLITION PLAN
WA
YN
E C
OM
MU
NIT
Y C
OL
LE
GE
AD
VA
NC
ED
MA
NU
FA
CT
UR
ING
CE
NT
ER
RE
NO
VA
TIO
N
3000
Way
ne
Mem
ori
al D
r, G
old
sbo
ro, N
C 2
7534
M1.2
SC
O I
D #
16
-15
90
6-0
1A
593101
NOVEMBER 6, 2020
1/8" = 1'-0"
SECOND FLOOR DEMOLITION PLAN
KEYNOTES
APPLICABLE TO THIS DRAWING
1 EX 26x70 DOWN. SEE DRAWING M1.1 FOR CONTINUATION. EX 46x36
UP TO EXISTING GRAVITY VENTILATOR ON ROOF. REMOVE EXISTING
MOTORIZED DAMPER AT GRAVITY VENTILATOR.
2 EX 30ø DOWN. SEE DRAWING M1.1 FOR CONTINUATION.
3 EX 40x17 DOWN. SEE DRAWING M1.1 FOR CONTINUATION.
4 EX HOT WATER UNIT HEATER TO REMAIN.
5 REMOVE EXISTING AIR HANDLING UNIT AND ALL ASSOCIATED
CONTROLS.
6 REMOVE EXISTING FAN AND ALL ASSOCIATED CONTROLS.
7 EX 3" HWS & HWR DOWN. SEE DRAWING M1.1 FOR CONTINUTATION.
8 EX 4" HWR DOWN. SEE DRAWING M1.1 FOR CONTINUTATION.
9 EX 4" HWR & EX 2" HWS DOWN. SEE DRAWING M1.1 FOR
CONTINUTATION.
10 PROVIDE PRE-CONSTRUCTION TESTING FOR TERMINAL UNIT PRIOR
TO ANY DEMOLITION WORK. REFER TO SPECIFICATION SECTION
014520 FOR REQUIREMENTS.
11 PROVIDE PRE-CONSTRUCTION TESTING FOR EXHAUST FAN PRIOR TO
ANY DEMOLITION WORK. REFER TO SPECIFICATION SECTION 014520
FOR REQUIREMENTS.
12 EX 26ø DOWN. SEE DRAWING M1.1 FOR CONTINUATION.
13 REMOVE EXISTING MOTORIZED BYPASS DAMPER.
REVISIONS
DATE DESCRIPTION
12/8/20 *AD-01
*AD-01
*AD-01
M
M
M
SDM
MECH. EQUIP.
MEZZANINE
280
AHU-2
BELOW
HWP-1
2
M3.1
F-2
F-3
3
M3.1
F-4
AHU-1
EX 1 1/4" HWS
EX 3/4" HWS
3"
HW
S
4" HWS
4" HWS
32x32
66x20
48x24
34x34
96x96 PLENUM
76x60
36x36
10x12
10x10
1
1
2
3
4
5
6
200x111 PLENUM, FULL SIZE
OF EXISTING LOUVER.
OUTSIDE AIR INTAKE
7
AHU-1
VFD
AHU-2
VFD
F-2
VFD
F-3
VFD
HWP-1
VFD
F-1
VFD
12x12
2" HWS
2" HWR
8888
8888
9
9
10
11
*AD-01
AHU-1
AHU-262x34
96x96 PLENUM
76x60
34x34
4"
HW
S
4"
HW
S
EX 40x34
32x32
36x36
200x111
CONNECT TO
LOUVER
EX EH-5
EX EH-1
2" HWR
3" HWR
HWP-1
4"
HW
S
4"
HW
S
4"
HW
S
1 1
/4"
HW
S
3" HWR
AHU-2
AHU-1
34x34
48x24
34x34
10x10
EX EH-1
EX EH-3
EX EH-7
2" HWS
2" HWR
CHITECTSCP
RA
MOSE
ELY
N
CO
RPORAT IO
N
O
RTH OCAR
L I
NA
REGIST
ERE
D ENGINE
ERING
EIGH, NCRAL
SEAL
SONP. FORS
Y
037569
TH
JA
CAROLINA
HTRO
N
PR
OFESSIONA
L
ENG INEE
R11/6/20
MOSELEYARCHITECTS.COM
C-3469
PROJECT NO:
DATE:
PH
ON
E (
919
) 8
40
-009
1
911
N. W
ES
T S
TR
EE
T, S
UIT
E 2
05
R
ALE
IGH
, N
OR
TH
CA
RO
LIN
A 27
60
3
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
12
/8/2
02
0 1
1:0
2:3
0 A
M ENLARGED PLAN AND
SECTIONS
WA
YN
E C
OM
MU
NIT
Y C
OL
LE
GE
AD
VA
NC
ED
MA
NU
FA
CT
UR
ING
CE
NT
ER
RE
NO
VA
TIO
N
3000
Way
ne
Mem
ori
al D
r, G
old
sbo
ro, N
C 2
7534
M3.1
SC
O I
D #
16
-15
90
6-0
1A
593101
NOVEMBER 6, 2020
1/2" = 1'-0"M2.2.1 M3.1
ENLARGED PLAN - MECHANICAL MEZZANINE1
KEYNOTES
APPLICABLE TO THIS DRAWING
1 4" HWS DOWN. SEE DRAWING M2.1.2 FOR CONTINUTATION.
2 3" HWR DOWN. SEE DRAWING M2.1.2 FOR CONTINUTATION.
3 EX 36x46 UP TO EX RELIEF HOOD ON ROOF. PROVIDE MOTORIZED
DAMPER BELOW ROOF. SEE CONTROLS SCHEMATICD ON DRAWING
M7.1.
4 24x48 UP TO EX RELIEF HOOD ON ROOF.
5 10x10 UP TO EX RELIEF HOOD ON ROOF.
6 12x12 UP TO EX RELIEF HOOD ON ROOF.
7 EX 36x36 UP TO F-6 ON ROOF. PROVIDE NEW MOTORIZED DAMPER AT
ROOF PENETRATION.
8 REFRIGERANT LIQUID AND SUCTION TO CONDENSING UNIT. SIZE PER
MANUFACTURER'S RECOMMENDATIONS.
9 ROUTE CONDENSATE FOR AHU-1 AND AHU-2 TO EXISTING FLOOR
DRAIN. SIZE FOR FULL CONNECTION OF DRAIN.
10 EX 26ø DOWN. SEE DRAWING M2.1.1 FOR CONTINUATION.
11 MOTORIZED BYPASS DAMPER. SEE CONTROLS SCHEMATIC ON
DRAWING M7.1.
1/2" = 1'-0"M3.1 M3.1
SECTION2
1/2" = 1'-0"M3.1 M3.1
SECTION3
REVISIONS
DATE DESCRIPTION
12/8/20 *AD-01
*AD-01
*AD-01
mi^k=sfbt
bibs^qflk=sfbt
5' -
10 3
/4"
8' -
4"
DX
CO
OLIN
G C
OIL
DX
CO
OLIN
G C
OIL
SU
PP
LY
FA
N
HO
T W
AT
ER
HE
AT
ING
CO
IL
FIL
TE
RS
SUPPLY AIR
9' - 7 7/8"
SU
PP
LY
FA
N
HO
T W
AT
ER
HE
AT
ING
CO
IL
FILTERS
RETURN AIR
SUPPLY AIR RETURN AIR
mi^k=sfbt
bibs^qflk=sfbt
3' -
9"
5' -
6 1
/2"
DX
CO
OLIN
G C
OIL
DX COOLING COIL
SU
PP
LY
FA
N
HOT WATER
HEATING COIL
FILTERS
SUPPLY AIR
SU
PP
LY
FA
N
HO
T W
AT
ER
HE
AT
ING
CO
IL
FILTERS
RETURN AIR
SUPPLY AIR RETURN AIR
7' - 7"
MANUAL SHUT-OFF
DAMPERS
16 GA. GALV.
3'-
0"
(2) 48" x 2-1/8" SLOTS
1 2 "
4"
DAMPER LOCK. POSITION
OF DAMPER TO BE SET BY
TAB CONTRACTOR.
mi^k=sfbt
bibs^qflk=sfbt
SHUT-OFF DAMPER
16" DUCT TO DUCT MAIN
12
"
18"
18
"
3'-4"
1,400 CFM
1,400 CFM
SPRING RETURN
SHUT-OFF DAMPER DETAIL
GASKET
AIRTIGHT
BOTH FACES AND CENTER DIVIDING PANEL SHALL
BE 1/8" THICK - SHOP PRIME COAT BOTH FACES
SPOT WELD 4" O.C.
AND SEAL AIRTIGHT
*AD-01
EXISTING LOUVER
EXISTING LOUVER
OUTSIDE AIR
48" x 24" MOTORIZED CONTROL DAMPER (TYP OF 12)
SHEET METAL ENCLOSURE.
COORDINATE PAINT COLOR
WITH ARCHITECT.
HEATING COIL (TYP OF 8)
WALL
SUPPORT
BRACKET
HEATING COIL
SHEET METAL
BLANK-OFF
MOTORIZED
CONTROL
DAMPERS
pb`qflk=sfbt
mi^k=sfbt
AHU-1
SECOND FLOOR
FIRST FLOOR
13,110 CFM
7,290 CFM
8,100 CFM
2,650 CFM
AHU-2
5,400 CFM
WELDING AREA
F-1
ROOF
5,400 CFM
WELDING AREA
CHITECTSCP
RA
MOSE
ELY
N
CO
RPORAT IO
N
O
RTH OCAR
L I
NA
REGIST
ERE
D ENGINE
ERING
EIGH, NCRAL
SEAL
SONP. FORS
Y
037569
TH
JA
CAROLINA
HTRO
N
PR
OFESSIONA
L
ENG INEE
R11/6/20
MOSELEYARCHITECTS.COM
C-3469
PROJECT NO:
DATE:
PH
ON
E (
919
) 8
40
-009
1
911
N. W
ES
T S
TR
EE
T, S
UIT
E 2
05
R
ALE
IGH
, N
OR
TH
CA
RO
LIN
A 27
60
3
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
12
/8/2
02
0 1
1:0
2:3
1 A
M DETAILS
WA
YN
E C
OM
MU
NIT
Y C
OL
LE
GE
AD
VA
NC
ED
MA
NU
FA
CT
UR
ING
CE
NT
ER
RE
NO
VA
TIO
N
3000
Way
ne
Mem
ori
al D
r, G
old
sbo
ro, N
C 2
7534
M5.2
SC
O I
D #
16
-15
90
6-0
1A
593101
NOVEMBER 6, 2020
NO SCALE
AHU-1 LAYOUTAHU-2 LAYOUT
WELDING HOOD EXHAUST DETAILSHEATING COIL WELDING MAKE-UP AIR SYSTEM
1/2" = 1'-0"
AIR HANDLING UNIT DUCT RISER DIAGRAM
REVISIONS
DATE DESCRIPTION
12/8/20 *AD-01
M
M
MM
M
CSRVSD
DX
CO
OLIN
G C
OIL
SUPPLY FAN
BAS
INTERFACE
DRAIN PAN WATER LEVEL
DETECTION DEVICE
SPD
AO
CONDESER SECTION
CSRVSD
RETURN FAN
SPD
AO
RETURN AIR
R
SD
ALM
BI
TS
AI
HE
AT
ING
CO
IL
POS
AO
POS
AI
FO
FIN
AL F
ILT
ER
ATS
AI
ALM
BI
SUPPLY AIR
SP
AI
TS
AI
SUPPLY AIR
SP
AI
DOWN-DUCT STATIC
PRESSURE SENSOR
ATS
AI
OU
TD
OO
R A
IR
POS
AI
DM
AOM
AF
AI
RH
AISPACE HUMIDITY SENSOR
SS
BO
ALM
BI
ALM
BI
RE
LIE
F/E
XH
AU
ST
AIR
M
SS
BO
ALM
BI
ALM
BI
AF
AI
RH
AI
M
DM
AO
DM
AO
POS
AI
POS
AI
RETURN AIR DAMPER
CSRVSD
DX
CO
OLIN
G C
OIL
SUPPLY FAN
BAS
INTERFACEDRAIN PAN WATER LEVEL
DETECTION DEVICE
SPD
AO
CONDESER SECTION
OUTSIDE AIR
HE
AT
ING
CO
IL
POS
AO
POS
AI
FO
FIN
AL F
ILT
ER
ATS
AI
ALM
BI
SUPPLY AIR
SP
AI
TS
AI
ATS
AI
TS
AISPACE TEMPERATURE SENSOR
SS
BO
ALM
BI
ALM
BI
POS
AI
DM
AO
M
FAN MOTOR
EXHAUST AIREXHAUST AIR
M
ALM
BI
CSR
VSD
SPD
AO
SS
BO
ALM
BI
FAN
MOTOR
SS
BO
EXHAUST AIR
ALM
BI
CSR
M
FAN
ROOF
FAN MOTOR
SS
BO
EXHAUST AIREXHAUST AIR
M
ALM
BI
CSR
OR
FAN MOTOR
SS
BO
EXHAUST AIREXHAUST AIR
M
ALM
BI
CSR
TS
AISPACE TEMPERATURE
SU
PP
LY
AIR
UNIT
CONTROL
PANEL
TS
AISPACE TEMPERATURE
PR
IMA
RY
AIR
AF
AO
AF
AI
POS
AO
POS
AI
TS
AI
CONTROL FOR HOT WATER
CONTROL VALVE.
MODULATING
VALVE
HOT WATER COIL
SU
PP
LY
AIR
FAN
UNIT
CONTROL
PANEL
TS
AISPACE TEMPERATURE
RETURN AIR FROM PLENUM
PR
IMA
RY
AIR
AF
AO
AF
AI
SS
BO
POS
AI
POS
AO
TS
AI
HOT WATER HEATING COIL
CONTROL FOR HOT
WATER VALVE
MODULATING VALVE
STS
BI
FAN CONTROL
VFD
ALM
BI
SS
BO
TS
AI
TS
AI
HOT WATER RETURN
TEMPERATURE
HOT WATER SUPPLY
TEMPERATURE
HOT WATER SUPPLY TO SYSTEM
HOT WATER RETURN FROM SYSTEM
HOT WATER SUPPLY FROM CAMPUS LOOP
HOT WATER RETURN TO CAMPUS LOOP
FAN MOTOR
EXHAUST AIREXHAUST AIR
M
ALM
BI
CSR
VSD
SPD
AO
SS
BO
ALM
BI
SP
AI
WELDING BOOTH STATIC
PRESSURE SENSOR
EXHAUST AIR
SS
BOSTART-STOP PUSH BUTTON ON WALL
HOT WATER COIL(TYP OF 8)
VLV
AO
VLV
AI
48" x 24" MOTORIZED DAMPER (TYP OF 12)
M
POS
AI
DM
AO
TS
AI DISCHARGE AIR
TEMPERATURE SENSOR
eb^qfkd=`lfi=tbiafkd=j^hbJrm=^fo=pvpqbj tbiafkd=_llqe=bue^rpq=^fo=pvpqbj
M
GRAVITY
VENTILATOR
ROOF
MDM
AO
POS
AI
NOTE: FAN MANUFACTURER TO PROVIDE CUSTOM CONTROL
ENCLOSURE TO HOUSE FAN VFD, STATIC PRESSURE
TRANSDUCER, REMOTE START/STOP CONTACTS, AND A DRY
CONTACT FOR THE EMERGENCY SHUT DOWN. COORDINATE WITH
BAS CONTRACTOR FOR MONITORING POINTS AND CONTROL.OFF
BOEMERGENCY STOP BUTTON ON WALL
BYPASS DAMPER
DM
AO
POS
AI
CHITECTSCP
RA
MOSE
ELY
N
CO
RPORAT IO
N
O
RTH OCAR
L I
NA
REGIST
ERE
D ENGINE
ERING
EIGH, NCRAL
SEAL
SONP. FORS
Y
037569
TH
JA
CAROLINA
HTRO
N
PR
OFESSIONA
L
ENG INEE
R11/6/20
MOSELEYARCHITECTS.COM
C-3469
PROJECT NO:
DATE:
PH
ON
E (
919
) 8
40
-009
1
911
N. W
ES
T S
TR
EE
T, S
UIT
E 2
05
R
ALE
IGH
, N
OR
TH
CA
RO
LIN
A 27
60
3
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
12
/8/2
02
0 1
1:0
2:3
1 A
M CONTROLS
WA
YN
E C
OM
MU
NIT
Y C
OL
LE
GE
AD
VA
NC
ED
MA
NU
FA
CT
UR
ING
CE
NT
ER
RE
NO
VA
TIO
N
3000
Way
ne
Mem
ori
al D
r, G
old
sbo
ro, N
C 2
7534
M7.1
SC
O I
D #
16
-15
90
6-0
1A
593101
NOVEMBER 6, 2020
PACKAGED VAV AIR HANDLING UNIT SERVING TERMINAL UNITS (AHU-1)PACKAGED CAV AIR HANDLING UNIT (AHU-2)
EXHAUST FAN WITH VFD - CONTROLLEDBY BAS SCHEDULE (F-1)
EXHAUST FAN - CONTROLLED BYBAS SCHEDULE (F-4, F-6)
EXHAUST FAN - CONTROLLED BYBAS SENSOR (F-5)
TERMINAL UNIT WITH MODULATING
CONTROL OF HOT WATER HEAT
PARALLEL FAN POWERED TERMINAL UNIT
WITH MODULATING HOT WATER HEATING COIL
HOT WATER PUMP CONTROLSWELDING EXHAUST SYSTEM CONTROLS
REVISIONS
DATE DESCRIPTION
12/8/20 *AD-01
*AD-01
701 N. Lilac Drive P.O. Box 1452 Minneapolis, MN 55440-1452 T: 763.540.1200 F: 763.540.1437
Terrence Scholz
PRODUCT SUBSTITUTION REQUEST: To: Greg Hedrick, Daniels & Daniels Construction Co., Inc. Project: Wayne CC-Advanced Manufacturing Center Renovations Item: Requesting approval of or equal to product substitution Description: Seamless Resinous/Epoxy Flooring Division: 9 Finishes Section: 09 6724 High-Performance Floor Paragraph/Article: 2.1.A.1 BASF TENNANT COMPANY- ARCHITECTURAL COATINGS REQUEST THE FOLLOWING PRODUCT SUBSTITUTION: Tennant Company Equivalent System: Tennant Performance HTS: Primer: Eco-MPE Build Coat: Eco-MPE Topcoat: Eco-HTS 100 Attached data includes product description, specifications, performance and test data adequate for evaluation of the request. The undersigned certifies that the following paragraphs, unless modified by attachment are correct:
I. The proposed substitution does not affect dimensions shown on drawings. II. The proposed substitution will have no adverse effect on the trades, the construction
schedule, or specified warranty requirements. III. Local support and availability will be available for proposed substitution.
The undersigned further states that the function and quality of the product substitution is equivalent or superior to the specified item. Submitted By: Signature: _____________________________________________ Name: Terrence Scholz Firm: Tennant Company-Architectural Coatings Address: 701 Lilac Drive North, Minneapolis, MN 55440 Date: 12/2/2020 Telephone: 763-513-2182 Attachments: Product Bulletins
Approved Not Approved Approved As Noted More Information Requested
By: Kyle Springer Date: 12/8/20 Remarks: ____________________________________________________________