Adaptive Power Module SPEC (369583) - Lutron Electronics€¦ ·  · 2017-01-04DIN Rail Power...

9
® SPECIFICATION SUBMITTAL Page Job Name: Job Number: Model Numbers: Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller 369583e 1 12.14.16 Adaptive Power Module The Adaptive Power Module family is a group of modular products for the control of lighting loads. This document describes the following product: Adaptive Power Module (model LQSE-4A-D) Features • Adaptive Power Modules can be used in a HomeWorks QS system. • Automatically selects leading edge or trailing edge dimming for incandescent/halogen, electronic/magnetic low voltage and neon / cold cathode light sources. • Controls dimmable CFL/LED loads. Refer to Lutron P/N 048478 on www.lutron.com for compatibility with dimmable CFL / LED light sources. • RTISS Equipped technology compensates for incoming line-voltage variations (up to ± 2% change in frequency/ second) such as changes in Root Mean Square (RMS) voltage, frequency shifts, harmonics and line noise. LQSE-4A-D Notes: 1 See "Output Zone Ratings" in “Specifications” section, for specific load types ratings. H M L LQSE-4A-D DIN Rail Power Module 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 CCI 500 W Max 800 W Max 500 W Max 500 W Max Zone 2 Zone 1 Zone 3 Zone 4 Input Hi Temp Prog Power Opt1 Opt2 Opt3 Def Option System Example • RTISS-TE operates on the trailing edge of the AC sine wave. This allows for true instantaneous voltage compensation. • Unit is 12 DIN modules (216 mm) wide. • Provides air gap off (when all zones are off). • Integral protection for common temporary over- current and over-voltage conditions. • LEDs on front of unit provide diagnostic information. • Includes QS link for seamless integration of lights and controls. MUX COM MUX QS Def Opt1 Opt2 0-10 V Power Module LQSE-4T10-D 230 V~ 50/60 Hz 50 mA www.lutron.com +44.(0)20.7680.4481 1 2 3 4 Zone 1 Zone 2 Zone 3 Zone 4 Option L N μ Opt3 CCI CCI COM Input Hi Temp Program Power H M L Up H M L LQSE-4A-D DIN Rail Power Module 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 CCI 500 W Max 800 W Max 500 W Max 500 W Max Zone 2 Zone 1 Zone 3 Zone 4 Input Hi Temp Prog Power Opt1 Opt2 Opt3 Def Option QS Link HomeWorks QS Power Module Adaptive Power Module GRAFIK Eye QS QS Contact Closure Interface HomeWorks QS Panel seeTouch QS Wallstation Emergency Contact Closure Input Up to 100 total QS devices 220–240 V~ Control Power 800 W Adaptive load 1 500 W Adaptive load 1 500 W Adaptive load 1 500 W Adaptive load 1

Transcript of Adaptive Power Module SPEC (369583) - Lutron Electronics€¦ ·  · 2017-01-04DIN Rail Power...

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller

369583e 1 12.14.16

Adaptive Power ModuleThe Adaptive Power Module family is a group of modular products for the control of lighting loads. This document describes the following product: Adaptive Power Module (model LQSE-4A-D)

Features

•AdaptivePowerModulescanbeusedina HomeWorks QS system.

•Automaticallyselectsleadingedgeortrailingedge dimming for incandescent/halogen, electronic/magnetic low voltage and neon / cold cathode light sources.

•ControlsdimmableCFL/LEDloads.RefertoLutronP/N 048478 on www.lutron.com for compatibility with dimmableCFL/LEDlightsources.

•RTISSEquippedtechnologycompensatesforincomingline-voltagevariations(upto±2%changeinfrequency/second)suchaschangesinRootMeanSquare(RMS)voltage,frequencyshifts,harmonicsandlinenoise.

LQSE-4A-D

Notes: 1 See"OutputZoneRatings"in“Specifications”section,forspecificloadtypesratings.

H

M

L

LQSE-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

CCI

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

System Example

•RTISS-TEoperatesonthetrailingedgeoftheACsine wave. This allows for true instantaneous voltage compensation.

•Unitis12DINmodules(216 mm) wide.•Providesairgapoff(whenallzonesareoff).•Integralprotectionforcommontemporaryover-

current and over-voltage conditions.•LEDsonfrontofunitprovidediagnosticinformation.•IncludesQSlinkforseamlessintegrationoflights

and controls.

MU

X

CO

M

MU

X

QS

Def

Opt1

Opt2

0-10 V Power ModuleLQSE-4T10-D230 V~ 50/60 Hz 50 mAwww.lutron.com +44.(0)20.7680.4481

1 2 3 4Outputs 230 V~ 10 AX each

Zone 1 Zone 2 Zone 3 Zone 4

Option

L N

µ

Z096

Opt3

CC

I

CCI

CO

M

0,5 N•mAll Others

8 mm1,2 N•mMains Only

Input

Hi Temp

Program

Power

H

M

L

Zones0-10 V-50 mA

Up

H

M

L

LQSE-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

CCI

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

QS Link

HomeWorks QS Power Module

Adaptive Power Module

GRAFIKEye QS

QSContactClosureInterface

HomeWorks QS Panel

seeTouch QS Wallstation

EmergencyContactClosureInput

Upto100total QS devices

220–240 V~ ControlPower

800 W Adaptive load1

500 W Adaptive load1

500 W Adaptive load1

500 W Adaptive load1

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller

369583e 2 12.14.16

SpecificationsAdaptive Power Module

Power

•220–240V~50/60Hz•10Amaximumtotalinputcurrent•LightningstrikeprotectionmeetsANSI/IEEEstandard62.31-1980.Canwithstandvoltagesurgesofupto 6 000 V and current surges of up to 3 000 A.

Standards

•IEC/EN60669-2-1•CEmarked•LutronQualitySystemsregisteredtoISO9001.2008

Environment

•SeeMounting onpage4forthermalspecifications•Relativehumidity:lessthan90%non-condensing•Forindooruseonly

Output Zone Ratings

•No Deratingisrequiredifalltheconditionsbelowaremet: –Calibrationpointmaximumis70ºC –Roomambienttemperatureisbetween0ºCand30ºC –Panelambienttemperatureisbetween0ºCand50ºC

•100 W Deratingisrequiredonallzonesforasinglemoduleinasinglenon-ventilatedDINenclosureif: – The room ambient temperature is between 30ºCand40ºC.

•200 W Deratingisrequiredonallzonesformultiple rownon-ventilatedDINenclosureif: – Theroomambienttemperatureisbetween30ºCand40ºC.

Output Zone Ratings (continued)

•Eachzonehasnominimumloadrequirement.

•Automaticallyselectsleading-edgeortrailing-edgedimmingorcanalsobemanuallyconfiguredforaspecificloadtype.

•Internalrelayprovidesanairgapoffwhenallzonesare off.

•Oneloadtypeperzone.

•Outputmustnotbeusedtocontrolreceptacles.

• Output must be directly connected to the load. ContactLutronforapplicationswithloadsidebreakers.

•Runaseparateneutralforeachloadcircuit.Acommon neutral connection is not recommended.

•MaximumwirelengthbetweentheEnergiSavrNodeunit and the load must be less than 30.5 m.

•UnitmaybepoweredbyGroundFaultInterrupter(GFI)orResidualCurrentCircuitBreakerwithOverload(RCBO)protectedcircuitifrequired.Loadcircuitwiring(from breaker to unit to load) must be run in its own non-metallic conduit, or nuisance tripping may occur.

•Forapplicationsrequiring0–10 V- control, use Ten VoltInterface(GRX-TVI)ortheQSNE-4T10-D.

•Forapplicationsrequiringhigherwattageratings,useapowerbooster(NGRX-PB,NGRX-ELVI,NGRX-FDBI).

Each zone is rated for the following wattage and load typesA, B:

Load TypeZone 1 Rating Zone 2, 3 and 4 Rating (per zone)

No Derating100 W Derating

200 W Derating No Derating

100 W Derating

200 W Derating

Incandescent/Halogen 800 W 700 W 600 W 500 W 400 W 300 W

Electronic Low Voltage 800 W 700 W 600 W 500 W 400 W 300 W

Magnetic Low VoltageD 800 VA (600 WC) 700 VA (525 WC) 600 VA (450 WC) 500 VA (375 WC) 400 VA (300 WC) 300 VA (225 WC)

Neon/ColdCathodeD 800 VA (600 WC) 700 VA (525 WC) 600 VA (450 WC) 500 VA (375 WC) 400 VA (300 WC) 300 VA (225 WC) A AdditionalloadtypeoptionsareavailableintheQuantumsoftwaresuite,somemayrequireaninterface.ContactLutronfordetails. B RefertoLutronP/N048478onwww.lutron.comforcompatibilitywithdimmableCFL/LEDlightsources. C Actual lamp wattage. D OnlyuseironcoretransformersintendedforusewithanelectronicswitchordimmerperClause8.3ofIEC/EN60669-2-1

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller

369583e 3 12.14.16

Specifications (continued)

Terminals (Torque,wiregauge&typeratings)

•Mainswiring:0.6N•m 1.0 mm² to 4.0 mm²

(single wire, solid or stranded) 1.0 mm² to 1.5 mm² (two wires, solid or stranded)

• Zonewiring: 0.6N•m 1.0 mm² to 4.0 mm²

(single wire, solid or stranded)

• CCIwiring: 0.6N•m 0.5 mm² to 4.0 mm² (single wire, solid or stranded)

• QSLink: 0.6N•m 0.5 mm² to 4.0 mm²

(single wire, solid or stranded) 0.5 mm² to 1.0 mm²

(two wires, solid or stranded)

Out of Box Functionality

This section describes the default functionality when theunitisfirstinstalled.

Emergency Contact Closure Input (CCI)

•WhentheCCIisopen,theEnergiSavrNodeQSunit will enter Emergency Mode, which will turn on all loads to their emergency level and disable control oflocalzonesandQSdevices.

•WhentheCCIisclosedorjumpered,EnergiSavrNodeQSunitzoneswillreturntothesettingsorlev-els they were at prior to entering emergency mode. Note:Unitwillprocessanysensoreventsreceivedwhileinemergencymodeafteritexitsemergencymode.

Normal Mode Operation

•Bydefaulteachzoneissettoanunassigned/Non-Dimloadtype.Eachzonewillswitchloadonoroffuntilitisconfiguredviaunitprogramming.Onceconfigured,theloadtypecannotbechangedbackto unassigned / Non-Dim.

•Zoneandraise/lowerbuttonsontheunitcanbe used to:

– turn loads on and off. – dim loads up and down.•InputandsensorstatusLEDs(‘Occ’,‘Photo’,‘IR’,and‘Switch’)verifyconnectionstodrycontact switches and sensors.

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller

369583e 4 12.14.16

H

M

L

LQSE-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

CCI

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

Mounting

•SeeLutronP/N048466atwww.lutron.comformore information on mounting and installation in panels with integratedDINrail.

•MountinIP20(minimum)ratedconsumerpanelorbreakerpanelwithintegratedDINrail.

•Mountunitinorientationshown.•Unitmaybemountedbyunlockingthefourmountingclipsonthebackoftheunit.ClipsmustbelockedonceunittosecurelyattachedtheunittotheDINrail.

•Mountinanaccessibleandserviceablelocation.•Unitgeneratesheat,maximum75BTUs/Hour•Mountunitsuchthatalltheconditionsbelowaremet: –Roomambienttemperatureisbetween0ºCand30ºC – Temperature inside mounting panel, within 20 mm of

unit,isbetween0ºCand50ºC –Calibrationpointmaximum:70ºC

Unlocked

4 mounting clips on unit

Locked

H

M

L

LQSE-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

CCI

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

Mechanical Dimensions

Front View

90 m

m

216 mm

Left Side View

Calibration point

90 m

m

55 mm

70 mm

76 mm

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller

369583e 5 12.14.16

Overview of Wiring Terminals

QS Link

Mains Input

Load Neutrals

Emergency-Contact Closure

Input

LQSE-4A-D

Phase Adaptive OutputsMains Wiring

Zone 1

Zone 4

Zone 2

Zone 3

H

M

L

LQSE-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

CCI

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

LL N N N N N DL1 DL2 DL3 DL4

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller

369583e 6 12.14.16

H

M

L

LQSE-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

CCI

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

LL N N N N N DL1 DL2 DL3 DL4

Verify Wiring

LQSE-4A-D

•Unitshipswithbypassconnectorpre-installedforloadwiringverification.Bypassconnectorisusedtoapplypower to loads to ideintify any load or wiring faults prior to wiring loads to unit.

•Loadwiringmustbeverifiedbeforewiringloadstounit.

•Toverifywiring: 1. Turn off power. 2. Wire loads to provided connector. 3. Apply power, ensure the desired loads are

powered and properly wired. 4. Turn off power and wire loads to DL terminals

on unit.

a

b

c

Neutral

Live

Earth Distribution

Panel(220–240 V~)

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller

369583e 7 12.14.16

Wiring from Distribution to Adaptive Power Module

•TurnoffallcircuitbreakersorisolatorsfeedingtheAdaptive Power Module at distribution panel.

•Runlive,neutral,andearth( ) wires from a 220-240 V~50/60HzfeedtotheDINRailPowerModule unit.

•Runaseparateneutralforeachloadcircuit.A common neutral connection is not recommended.

Mains Wiring and IEC PELV Separation

•Followappropriatelocalandnationalcodestoavoidviolatingrequiredseparationguidelines.

Dim Live (220-240 V~)

Neutral

H

M

L

LQSE-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

CCI

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

Zone 1 Example

Mains Voltage Wiring

H

M

L

LQSE-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

CCI

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

L N N N N N DL1 DL2 DL3 DL4

Load

Earth

Neutral

LiveDistribution

Panel(220–240 V~)

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller

369583e 8 12.14.16

IEC PELV Emergency Contact Closure Input

•ContactClosureInput(CCI)wiringis IECPELV/NEC®Class2. Followallapplicablenationalandlocalcodesforproper circuit separation and protection.

•Turnoffallbreakersorisolatorsfeedingthe Energi Savr Node QS unit at distribution panel be-fore servicing unit.

•TheCCIisalocalcontrolonlyandcannotcontrolother Energi Savr Node QS units over the QS link. Amaximumof32EnergiSavrNodeQSunitsmaybe connected in parallel to an Emergency or Manual override device if the event is intended to affect multiple devices.

•Wheninemergencymode,allzoneoutputswillbeat their programmed emergency light level (configurableforeachzone,defaultis100%). All sensors and controls are locked out.

•Emergencycontactclosureinputisnormallyclosed(NC).TheEnergiSavrNode QS unit is shipped with ajumperpre-installed.

Note: The Energi Savr Node QS unit will default to EmergencyModeiftheCCIisleftopen.IfnoEmergencyContactClosureInputisrequired,pleaseleavethewirejumperintheCCIterminals.

H

M

L

LQSE-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

CCI

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

H

M

L

QSNE

-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

InputS1 S2 S3 S4 CCI

SwitchOccPhotoIR

Type

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

H

M

L

QSNE

-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

InputS1 S2 S3 S4 CCI

SwitchOccPhotoIR

Type

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

CCICommon

Wiring: Emergency Contact Closure Input

CCI COM

Note: Shown with pre-installedjumper.

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller

369583e 9 12.14.16

Wiring: QS LinkQS Link IEC PELV Wiring

•LinkcommunicatesusingIEC PELV/NECRClass 2wiring.•TurnoffallbreakersorisolatorsfeedingtheAdaptive

Power Module at distribution panel before servicing unit.•Followallapplicablenationalandlocalcodesforproper

circuit separation and protection.•Wiringmaybedaisychainedort-tapped.•TotallengthofQSlinkmustnotexceed600m.•Forlengthsunder150m,usetwo1,0mm2

conductors for control power (24 V-,COM).•Forlengthsover150m,usetwo4,0mm2 conductors

for control power (24 V-,COM).•Useone,twisted-shieldedpairof1,0mm2 conductors fordatalink(MUX,_).

H

M

L

LQSE-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

CCI

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

H

M

L

LQSE-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

CCI

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

(1) COM

(2) Do Not Connect Teminal 21

(3) MUX

(4) MUX

seeTouch QSwallstations

seeTouch QSwallstations

QSE-CI-DMX

QSE-CI-DMX

Daisy-Chain Wiring Example

T-Tap Wiring Example

1 UnitdoesnotconsumeorsupplyPDUson the QS link. Do not connect the 24 V- wire to unit. Note: 24 V- wire must bypass the unit if other devices on the link consume PDUs.

)Lutron,Lutron,HomeWorks,RTISSEquipped,GRAFIKEye,seeTouch,andQuantumareregistered trademarks of Lutron Electronics Co.,Inc.registeredintheU.S.andothercountries.

RTISS-TE,EnergiSavrNodearetrademarksofLutronElectronicsCo.,Inc.