Actuators By themselves, valves cannot control a process. Manual valves require an operator to...

87
Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that must be operated remotely and automatically require special devices to move them. These devices are called actuators. Actuators may be pneumatic, hydraulic, or electric solenoids or motors 1 BEE4523 Chapter 3 : Actuator NH

Transcript of Actuators By themselves, valves cannot control a process. Manual valves require an operator to...

Page 1: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

ActuatorsBy themselves, valves cannot control a process.   Manual valves require an operator to position them to control a process variable. Valves that must be operated remotely and automatically require special devices to move them. These devices are called actuators. Actuators  may be  pneumatic, hydraulic, or electric solenoids or motors

1BEE4523 Chapter 3 : ActuatorNH

Page 2: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

2BEE4523 Chapter 3 : ActuatorNH

Actuators

1 Electrical actuator2 Pneumatic3 Hydraulic4 Fluid valve

Page 3: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

3BEE4523 Chapter 3 : ActuatorNH

Electrical Actuator

Page 4: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

4BEE4523 Chapter 3 : ActuatorNH

Electrical Actuator

2 types of electrical actuators :

• Solenoid

• Electrical Motors

Dc Motor

Ac Motor

Stepping motor

Page 5: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

5BEE4523 Chapter 3 : ActuatorNH

Solenoid

• Solenoid : converts an electrical

signal into mechanical motion,

usually rectilinear

• Used when a large, sudden force

must be applied to perform some

job

Page 6: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

6BEE4523 Chapter 3 : ActuatorNH

Solenoid

• Consist of a coil n plunger (freestanding / spring

loaded)

• Coil will have voltage or current rating in dc or ac

Page 7: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

7BEE4523 Chapter 3 : ActuatorNH

Solenoid

Page 8: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

8BEE4523 Chapter 3 : ActuatorNH

Solenoid

• Solenoid used to change the gears of a two-

position transmission

• Used SCR to activate solenoid coil

Page 9: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

Electric Solenoid Actuators A typical electric solenoid actuator is shown in Figure 38.  It consists of a coil, armature, spring, and stem.The coil is connected to an external current supply.   The spring rests on the armature to force it downward.  The armature moves vertically inside the coil and transmits its motion through the stem to the valve. When current flows through the coil, a magnetic field forms around the coil.  The magnetic field attracts the

9BEE4523 Chapter 3 : ActuatorNH

Page 10: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

armature toward the center of the coil.   As the armature moves upward, the spring collapses and the valve opens.  When the circuit is opened and current stops flowing to the coil, the magnetic field collapses. This allows the spring to expand and shut the valve.A major advantage of solenoid actuators is their quick operation.   Also, they are much easier to install   

10BEE4523 Chapter 3 : ActuatorNH

Page 11: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

  than pneumatic or hydraulic   actuators. However,   solenoid   actuators   have    two disadvantages. First, they have only two positions:   fully open and fully closed.   Second, they don’t produce much force, so they usually only operate relatively small valves.

11BEE4523 Chapter 3 : ActuatorNH

Page 12: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

12BEE4523 Chapter 3 : ActuatorNH

Figure 38    Electric Solenoid Actuator

Page 13: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

13BEE4523 Chapter 3 : ActuatorNH

Electrical Motors

• Electrical motors : accept electrical

input and produce a continuous rotation

as a result

• Motor styles and sizes vary as demands

for rotational speed (rpm), starting

torque, rotational torque, etc

Page 14: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

14BEE4523 Chapter 3 : ActuatorNH

DC Motor

• Rotation of dc motor :

produced by the

interaction of two

constant magnetic fields

• Employs permanent

magnet (PM) to form one

of the magnetic fields

• 2nd magnetic field formed

by current through coil of

wire within PM

Page 15: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

15BEE4523 Chapter 3 : ActuatorNH

DC Motor

• Coil of wire

(armature) : free

to rotate

• Coil is connected

to current source

through slip rings

and brushes

(commutator)

• Slip rings are split

so that current

reverses direction

as the armature

rotates

Page 16: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

16BEE4523 Chapter 3 : ActuatorNH

DC Motor

Page 17: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

17BEE4523 Chapter 3 : ActuatorNH

DC Motor

Page 18: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

18BEE4523 Chapter 3 : ActuatorNH

DC Motor

Page 19: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

19BEE4523 Chapter 3 : ActuatorNH

DC Motor

• Torque will drive

the N armature

from the N PM &

the S armature

from the S PM

• Armature rotate

counterclockwise

• Rotation will

continuous

Page 20: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

20BEE4523 Chapter 3 : ActuatorNH

DC Motor

• Many dc motors use electromagnet instead of

PM to provide static field

• Field coil : coil used to produce static field

• Wound field motor : dc motor to produce

static field

• Current can be provided by placing the coil in

series or parallel (shunt) or else with two

windings (compound) with the armature

Page 21: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

21BEE4523 Chapter 3 : ActuatorNH

Series field

• Large starting

torque

• Difficult to speed

control

• Good for starting

heavy, where

speed control is

not important

Page 22: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

22BEE4523 Chapter 3 : ActuatorNH

Shunt field

• Smaller starting

torque

• Good speed

control

• Good for

application

where speed is

to be controlled

Page 23: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

23BEE4523 Chapter 3 : ActuatorNH

Compound field

• The best

features of

both series &

shunt

• Large starting

torque

• Good speed

control

Page 24: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

24BEE4523 Chapter 3 : ActuatorNH

AC Motor

• Principle of ac motor : involves the

interaction between 2 magnetic

fields

• Both fields varying with the voltage

• Force between fields is a function of

rotor angle and current phase

Page 25: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

25BEE4523 Chapter 3 : ActuatorNH

Synchronous ac motor

• AC voltage applied to field coils (stator)

• Armature (rotor) is PM or dc electromagnet

• Rotor follows

stator

• Speed of rotation:

rpmp

fns

120

Page 26: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

26BEE4523 Chapter 3 : ActuatorNH

Induction ac motor

• Rotor is neither PM nor dc electromagnet

• Current induced from stator coils

• Ac field of stator

produces

magnetic field

changing through

closed loop of

rotor

Page 27: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

27BEE4523 Chapter 3 : ActuatorNH

Stepping Motor

• Stepping motor : rotating machine that

completes a full rotation by sequencing

through a series of discrete rotational

steps

• Rotational rate : determined by the

number of steps per revolution and the

rate at which the pulses are applied

Page 28: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

28BEE4523 Chapter 3 : ActuatorNH

Stepping motor

• 90° per step

• Rotor is PM driven by set of electromagnets

• Switches : transistors, SCRs or TRIACs

• Switch sequencer will direct the switches through a sequence of positions as the pulses received

Page 29: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

29BEE4523 Chapter 3 : ActuatorNH

Stepping motor

• Pulse will change S2 from C to D

• Poles of electromagnet reversing fields

• Pole N/S orientation is different

• Rotor repelled and attracted, moves to new position

• Next pulse will change S1 from A to B – same kind of pole reversal and rotation of rotor

Page 30: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

30BEE4523 Chapter 3 : ActuatorNH

Stepping motor

• Next pulse will change S2 from D to C– same kind of pole reversal and rotation of rotor

• Next pulse will change S1 from B to A– same kind of pole reversal and rotation of rotor, send back system to original position

• Continuous sequence as pulse come in

Page 31: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

31BEE4523 Chapter 3 : ActuatorNH

Example 1

A stepper motor has 10° per step

and must rotate at 250 rpm.

Calculate the required input pulse

rate, in pulses per second.

Page 32: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

Electric Motor Actuators Electric motor actuators vary widely in their design and applications.    Some electric motor actuators are designed to operate in only two positions (fully open or fully closed).  Other electric motors can be positioned between the two positions.   A typical electric motor actuator is shown in Figure 39.   Its major parts include an electric motor, clutch and gear box assembly, manual hand wheel, and stem connected to a valve.

32BEE4523 Chapter 3 : ActuatorNH

Page 33: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

The motor moves the stem through the gear assembly.   The motor reverses its rotation to either open or close the valve.  The clutch and clutch lever disconnects the electric motor from the gear assembly and allows the valve to be operated manually with the hand wheel. Most electric motor actuators are equipped with limit switches, torque limiters, or both.   Limit switches de-energize the electric motor when the valve has reached a specific position.   Torque Rev. 0 Page 59 IC-07

33BEE4523 Chapter 3 : ActuatorNH

Page 34: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

Limiters de-energize the electric motor when the amount of turning force has reached a specified value. The  turning  force  normally  is  greatest  when  the  valve  reaches  the  fully  open  or  fully closed position.  This feature can also prevent damage to the actuator or valve if the valve binds in an intermediate position.

34BEE4523 Chapter 3 : ActuatorNH

Page 35: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

35BEE4523 Chapter 3 : ActuatorNH

Figure 39    Electric Motor Actuator

Page 36: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

36BEE4523 Chapter 3 : ActuatorNH

Pneumatic

Page 37: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

37BEE4523 Chapter 3 : ActuatorNH

Pneumatic

• Pneumatic : based on concept of pressure

as force per unit area

• Net force acts on diaphragm ;

NforceF

mareadiaphragmA

Padifferencepressurepp

ppAF

:

:

:2

21

21

Page 38: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

38BEE4523 Chapter 3 : ActuatorNH

Direct Pneumatic

• Condition in low

signal-pressure state

• Spring, S maintains

diaphragm and

connected control

shaft in position

• Pressure on opposite

side is maintained at

atmospheric

pressure by open

hole, H

Page 39: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

39BEE4523 Chapter 3 : ActuatorNH

Direct Pneumatic

• Increasing control

pressure applies

force on diaphragm

• Forcing diaphragm

and connected shaft

down against spring

force

• Maximum control

pressure and travel

of shaft

Page 40: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

40BEE4523 Chapter 3 : ActuatorNH

Pneumatic

• Shaft position is linearly related to applied control pressure

• Shaft position;

mNconstantspringk

mareadiaphragmA

Papressuregaugeappliedp

mtravelshaftx

pk

Ax

/:

:

:

:

2

Page 41: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

41BEE4523 Chapter 3 : ActuatorNH

Reverse Pneumatic

• Moves shaft in

opposite sense

from direct

actuator

• Obeys same

operating principle

• Shaft is pulled by

application of

control pressure

Page 42: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

42BEE4523 Chapter 3 : ActuatorNH

Example 2

A force of 400 N must be applied to open

valve. Determine the diaphragm area if a

control gauge pressure of 70 kPa (~10

psi) must provide this force.

Page 43: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

Pneumatic Actuators A simplified diagram of a pneumatic  actuator is shown in figure  35. It operates by a combination of force created by air and spring force. The actuator positions a control valve  by transmitting its motion through the stem. A rubber diaphragm separates the actuator housing into two air chambers. The upper chamber receives supply air  through an opening in the top of the housing.

43BEE4523 Chapter 3 : ActuatorNH

Page 44: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

The bottom chamber contains a spring that forces the diaphragm against mechanical stops in the upper chamber.  Finally, a local indicator is connected to the stem to indicate the position of the valve. The position of the valve is controlled by varying supply air pressure in the upper chamber.  This results in a varying force on the top of the diaphragm.   Initially, with no supply air, the spring forces the diaphragm upward against the mechanical stops and holds the valve fully open.   As supply air pressure is increased

44BEE4523 Chapter 3 : ActuatorNH

Page 45: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

from zero, its force on top of the diaphragm begins to overcome the opposing force of the spring.  This causes the diaphragm to move downward and the control valve to close.With increasing supply air  pressure,  the  diaphragm  will  continue  to  move downward and compress the spring until the control valve is fully closed.  Conversely, if supply air pressure is decreased, the spring will begin to force the  diaphragm upward  and  open  the control valve.  Additionally, if supply pressure is held constant at

45BEE4523 Chapter 3 : ActuatorNH

Page 46: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

some value between zero and maximum, the valve will position at an intermediate position.    Therefore, the valve can be positioned anywhere between fully open and fully closed in response to changes in supply air pressure. A positioner is a device that regulates the supply air pressure to a pneumatic actuator.   It does this by comparing the actuator’s demanded position with the control valve’s actual position.  The demanded position is transmitted by a pneumatic or electrical control signal from a controller to the

46BEE4523 Chapter 3 : ActuatorNH

Page 47: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

positioner.  The pneumatic actuator in Figure 35 is shown in Figure 36 with a controller and positioner added. The controller generates an output signal that represents the demanded position.   This signal is sent to the positioner.   Externally, the positioner consists of an input connection for the control signal, a supply air input connection, a supply air output connection, a supply air vent connection, and a feedback linkage.   Internally, it contains an intricate network of electrical transducers, air lines, valves, linkages, and

47BEE4523 Chapter 3 : ActuatorNH

Page 48: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

necessary adjustments.   Other positioners may also provide controls for local valve positioning and gauges to indicate supply air pressure and control air pressure (for pneumatic controllers).  From an operator’s viewpoint, a description of complex internal workings of a positioner is not needed.   Therefore, this discussion will be limited to inputs to and outputs from the positioner. In Figure 36, the controller responds to a deviation of a controlled variable from set point and varies the control output signal accordingly to

48BEE4523 Chapter 3 : ActuatorNH

Page 49: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

correct the deviation. The control output signal is  sent  to  the  positioner,  which  responds  by  increasing  or decreasing the  supply  air  to  the actuator.   Positioning of the actuator and control valve is fed back to the positioner through the feedback linkage.  When  the  valve  has  reached  the  position  demanded  by  the  controller,  the positioner stops the change in supply air pressure and holds the valve at the new position.  This, in turn, corrects the controlled variable’s deviation from set point.

49BEE4523 Chapter 3 : ActuatorNH

Page 50: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

For example, as the control signal increases, a valve inside the positioner admits more supply air to the actuator.  As a result, the control valve moves downward.  The linkage transmits the valve position information back to the positioner.   This forms a small internal feedback loop for the actuator.   When the valve reaches the position that correlates to the control signal, the linkage stops supply air flow to the actuator.  This causes the actuator to stop.  On the other hand, if the control  signal  decreases,  another  

50BEE4523 Chapter 3 : ActuatorNH

Page 51: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

  This causes the valve to move upward and open. When the valve has  opened to the proper position, the inside the positioner opens and allows  the  supply  air pressure to decrease by venting the supply air.positioner stops  venting  air  from  the actuator and stops movement of the control valve. An  important  safety  feature  is  provided  by  the  spring in an actuator. It can be designed to position a control valve in a safe position if a loss of supply air occurs. On a loss of supply air, the actuator in Figure 36 will

51BEE4523 Chapter 3 : ActuatorNH

Page 52: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

fail open.   This type of arrangement is referred to as "air-to-close, spring-to-open"  or  simply  "fail-open."   Some valves fail in the closed position.   This type of actuator is referred to as "air-to-open, spring-to-close" or "fail-closed."   This "fail-safe" concept is an important consideration in nuclear facility design

52BEE4523 Chapter 3 : ActuatorNH

Page 53: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

53BEE4523 Chapter 3 : ActuatorNH

Figure 36    Pneumatic Actuator with Controller and Positioner

Page 54: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

54BEE4523 Chapter 3 : ActuatorNH

Hydraulic

Page 55: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

55BEE4523 Chapter 3 : ActuatorNH

Hydraulic

• Hydraulic : used when large forces are

required

• Hydraulic pressure ;

21

1

11

:

:

:

/

mareapistonforcingA

NforcepistonappliedF

Papressurehydraulicp

AFp

H

H

Page 56: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

56BEE4523 Chapter 3 : ActuatorNH

Hydraulic

• Basic idea same as

pneumatic

• Except

incompressible fluid

used to provide

pressure

• Pressure will be very

large by adjusting

area of forcing piston

Page 57: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

57BEE4523 Chapter 3 : ActuatorNH

Hydraulic

allows the lifting of a heavy load with a small force

Page 58: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

58BEE4523 Chapter 3 : ActuatorNH

Hydraulic

• Pressure is transferred equally throughout the liquid

• Force on working piston;

• Working force in terms of applied force;

22

2

:

:

mareapistonworkingA

NpistonworkingonforceF

ApF

w

Hw

11

2 FA

AFw

Page 59: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

59BEE4523 Chapter 3 : ActuatorNH

Automobile Hydraulic Lift

• A hydraulic lift for automobiles is an example of a force multiplied by hydraulic press, based on Pascal's principle. The fluid in the small cylinder must be moved much further than the distance the car is lifted.

Page 60: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

60BEE4523 Chapter 3 : ActuatorNH

Pascal’s Principle

Page 61: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

61BEE4523 Chapter 3 : ActuatorNH

Example 3

Determine:

(a)The working force resulting from 200 N

applied to a 1 cm radius forcing piston if

the working piston has a radius of 6 cm

(b)The hydraulic pressure

Page 62: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

62BEE4523 Chapter 3 : ActuatorNH

Example 4

If the lift cylinder were 25 cm in diameter

and the small cylinder were 1.25 cm in

diameter, determine the force on the fluid

in the small cylinder to lift a 6000 N car.

Page 63: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

Hydraulic Actuators Pneumatic actuators are normally used to control processes requiring quick and accurate response, as they do not require a large amount of motive force.   However, when a large amount of force is required to operate a valve (for example, the main steam system valves), hydraulic actuators are normally used.   Although hydraulic actuators come in many designs, piston types are most common.

63BEE4523 Chapter 3 : ActuatorNH

Page 64: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

A typical piston-type hydraulic actuator is shown in Figure 37.  It consists of a cylinder, piston, spring, hydraulic supply and returns line, and stem. The piston slides vertically inside the cylinder and separates the cylinder into two chambers. The    upper chamber contains the spring and the lower chamber contains hydraulic oil. The hydraulic supply and return line is connected to the lower chamber  and allows   hydraulic   fluid   to flow to and from the lower chamber of   the   actuator. The stem   transmits    the motion of the piston to a valve

64BEE4523 Chapter 3 : ActuatorNH

Page 65: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

Initially, with no hydraulic fluid pressure, the spring force holds the valve in the closed position. As fluid enters the lower chamber, pressure in the chamber increases.   This pressure results in a force on the bottom of the piston opposite  to the force  caused by the  spring. When  the hydraulic  force  is  greater  than  the  spring  force, the piston begins  to  move  upward,  the  spring compresses, and the  valve begins  to  open. As the hydraulic pressure  increases, the  valve continues to open.  Conversely, as hydraulic

65BEE4523 Chapter 3 : ActuatorNH

Page 66: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

oil is drained from the cylinder, the hydraulic force becomes less than the spring  force, the  piston moves downward, and the valve  closes.  By regulating  amount  of oil  supplied  or  drained  from  the  actuator, the  valve  can  be  positioned between fully open and fully closedThe principles of operation of a hydraulic actuator are like those of the pneumatic actuator.  Each uses some motive force to overcome spring force to move the valve.   Also, hydraulic actuators can be designed to fail-open or fail-closed to provide a fail-safe feature.

66BEE4523 Chapter 3 : ActuatorNH

Page 67: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

67BEE4523 Chapter 3 : ActuatorNH

Figure 37    Hydraulic Actuator

Page 68: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

68BEE4523 Chapter 3 : ActuatorNH

Fluid valve

Page 69: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

69BEE4523 Chapter 3 : ActuatorNH

Control-valve principles

• Flow rate in process control : volume per unit time

• If a given fluid is delivered through a pipe, the volume flow rate ;

smvelocityflowv

mareapipeA

smrateflowQ

AvQ

/:

:

/:2

3

Page 70: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

70BEE4523 Chapter 3 : ActuatorNH

Control-valve principles

• To regulate flow rate of fluids through pipes

• Placing variable-size restriction in flow path

• Stem and plug move up and down

• Opening size between plug and seat changes, thus changing flow rate

Page 71: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

71BEE4523 Chapter 3 : ActuatorNH

Control-valve principles

• There will be a drop in pressure and flow rate varies with square root of pressure drop

• The volume flow rate ;

Padifferencepressureppp

PasmconstantalityproportionK

smrateflowQ

pKQ

:

//:

/:

12

2/13

3

Page 72: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

72BEE4523 Chapter 3 : ActuatorNH

Control-valve types

• Control-valve characteristic :

different types of control valves

depends on relationship between

valve stem position and flow rate

through valve

Page 73: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

73BEE4523 Chapter 3 : ActuatorNH

Control-valve types

• Control

valve using

pneumatic

actuator

• To drive

stem and

open or

close valve

Page 74: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

74BEE4523 Chapter 3 : ActuatorNH

Control-valve types

• Types determined by shape of plug and

seat

• Stem and plug move with respect to seat

• Shape of plug determines the amount of

actual opening valve

Page 75: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

75BEE4523 Chapter 3 : ActuatorNH

Control-valve types

1. Quick opening

• Used predominantly for full ON/full

OFF control applications

• Small motion of valve stem, max

possible flow rate

• Allow 90% max flow rate, 30% travel

of stem

Page 76: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

76BEE4523 Chapter 3 : ActuatorNH

Control-valve types

2. Linear

• Flow rate varies linearly with stem position

• Ideal situation, valve determines pressure drop;

mpositionstemmaximumS

mpositionstemS

smrateflowmaximumQ

smrateflowQ

S

S

Q

Q

:

:

/:

/:

max

3max

3

maxmax

Page 77: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

77BEE4523 Chapter 3 : ActuatorNH

Control-valve types

3. Equal percentage

• Percentage change in stem position produces equivalent change in flow-equal percentage

• Not shut off the flow completely in its limit of stem travel

rateflowminimumQ

rateflowmaximumQ

Q

QR

:

:

min

max

min

max

max/max

SSRQQ

• Rangeability;

• Flow rate;

Page 78: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

78BEE4523 Chapter 3 : ActuatorNH

Control-valve types

• Three

types of

control

valves

open

differently

as function

of stem

position

Page 79: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

79BEE4523 Chapter 3 : ActuatorNH

Control-valve sizing

• Correction factor (valve flow coefficient), Cv : allow

selection of proper size of valve to accommodate flow rate

• Measured as the number of U.S. gallons of water per minute

that flow through full open valve with pressure differential 1 lb

per square inch

• Liquid flow rate (in U.S. gallons per minute);

gravityspecificliquidS

psivalveacrosspressurep

S

pCQ

G

Gv

:

:

Page 80: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

80BEE4523 Chapter 3 : ActuatorNH

Control-valve sizing

• Control-valve

flow

coefficients for

different size

valves

Valve size (inches) Cv

¼ 0.3

½ 3

1 14

1½ 35

2 55

3 108

4 174

6 400

8 725

Page 81: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

81BEE4523 Chapter 3 : ActuatorNH

Example 5

Alcohol is pumped through a pipe of

10 cm diameter at 2 m/s flow

velocity. Calculate the volume flow

rate

Page 82: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

82BEE4523 Chapter 3 : ActuatorNH

Example 6

A pressure difference of 1.1 psi occurs

across a constriction in a 5 cm diameter

pipe. The constriction constant is 0.009

m3/s/kPa1/2. Determine:

(a) The flow rate in m3/s

(b) The flow velocity in m/s

Page 83: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

83BEE4523 Chapter 3 : ActuatorNH

Example 7

An equal percentage valve has a

maximum flow of 50 cm3/s and a

minimum of 2 cm3/s. If the full

travel is 3 cm, calculate the flow at

a 1cm opening.

Page 84: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

84BEE4523 Chapter 3 : ActuatorNH

Example 8

Calculate:

(a) The proper Cv for a valve that must

allow 150 gal of ethyl alcohol per

minute with a specific gravity of 0.8

at maximum pressure of 50 psi

(b) The required valve size

Page 85: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

Summary The important information in this chapter is summarized below.Valve Actuator Summary Pneumatic actuators  utilize  combined  air and  spring  forces  for  quick  accurate responses for almost any size valve with valve position ranging from 0-100%.  

85BEE4523 Chapter 3 : ActuatorNH

Page 86: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

Hydraulic actuators use fluid displacement to  move  a  piston  in  a  cylinder positioning  the  valve  as  needed  for  0-100%  fluid  flow. This type actuator is incorporated when a large amount of force is necessary to operate the valve.  

86BEE4523 Chapter 3 : ActuatorNH

Page 87: Actuators By themselves, valves cannot control a process. Manual valves require an operator to position them to control a process variable. Valves that.

Solenoid actuators are  used  on  small  valves  and  employ an electromagnet  to move the stem which allows the valve to either be fully open or fully closed. Equipped with limit switches and/or torque limiters, the electric motor actuator has the capability of 0-100% control and has not only a motor but also a manual hand wheel, and a clutch and gearbox assembly. End of text.

87BEE4523 Chapter 3 : ActuatorNH