Active Power Filter with Relay Current Regulator andCommon DC Link for Compensation of Harmonic
Distortion in Power GridsMaksim Habibullin, Igor Pavlov, Viktor Mescheryakov, Stanimir Valtchev
To cite this version:Maksim Habibullin, Igor Pavlov, Viktor Mescheryakov, Stanimir Valtchev. Active Power Filter withRelay Current Regulator and Common DC Link for Compensation of Harmonic Distortion in PowerGrids. 5th Doctoral Conference on Computing, Electrical and Industrial Systems (DoCEIS), Apr2014, Costa de Caparica, Portugal. pp.427-434, �10.1007/978-3-642-54734-8_47�. �hal-01274805�
Active Power Filter with Relay Current Regulator and
Common DC Link for Compensation of Harmonic
Distortion in Power Grids
Maksim Maratovich Habibullin1, Igor Sergeevich Pavlov
1, Viktor
Nikolaevich Mescheryakov1, Stanimir Valtchev
2
1
Lipetsk State Technical University, Moskovskaya 30, 398600 Lipetsk, Russia [email protected], [email protected]
2 Campus de Campolide, 1099-085 Lisboa, Portugal
Abstract. The growing number of consumers representing non-linear loads has
led to an increase in the level of harmonics and poor power quality. It is not
news to apply active power filtering (APF), but the drawback is the lower
efficiency and complexity. The described here active power filter control
system is simpler and more efficient. It is based on a relay current regulator and
its converter uses the existing DC bus of the rectifier. The theoretical basis of
the APF is described. A model of the proposed APF (with its suggested control
system and the common DC link) is simulated in Matlab. The result of this
simulation demonstrates that the level of the Total Harmonic Distortion (THD)
of the input current is less than 3 %. The input current matches the phase of the
input (mains) voltage: i.e. the consumption of reactive power from the grid is
minimized. The simulation is confirmed by experimental study of the relay
current controller. The corresponding results are provided.
Keywords: Non-linear load, Quality of electric energy, Total harmonic
distortion, Relay current control, DC-link, Active power filter.
1 Introduction
1.1 Power Quality
Less than twenty years ago the harmonic components of current and voltage in the
electric alternating current were negligible and their impact on the grid could be
ignored. Currently, in most countries the level of harmonic components in power
grids has increased in several times. The tendency for further growth is here to stay
[1]. The high level of harmonic components should be considered seriously because it
has a negative impact both on the grid and its users.
The reason for the growth of the harmonic current and voltage is the growing
number of electricity customers that use non-linear load, both in the industrial and
domestic sectors. The main negative effect of the non-linear load consists in the
specific nature of the harmonics in the consumed current from the grid. The harmonic
components frequencies can be so high that they provoke electromagnetic disturbance
but the low frequency harmonics are also a problem because their filtering requires
large reactive elements. Currently, 60 % of the electrical consumption is due to the
426 M. M. Habibullin et al.
nonlinear load and now the requirements for power supply quality from the grid is
one of the main tasks of the electrical energy industry [2].
The existence of higher harmonic contents in the grid current results in significant
economic damages. These include the additional losses in rotating electrical
machines, the loss in transformers, vibration in electric machine systems, single-phase
ground short circuit, capacitor breakdowns, insulation aging, disruption and failure of
high-precision measuring instruments, protective gears, control systems and
microprocessor-based systems, interference and distortion of signals in
telecommunication networks and systems. In addition, the nonlinear load has high
level of reactive energy circulation; hence the losses in the energy transport system
rise, as well as the overloading of generators, transformers and transmission lines.
Oscillations of system voltage are then more probable. In general, the quality of the
supplied energy goes downward [3].
1.2 Outlining the Research Question and its Motivation
The harmonic components in the power network variables are produced in the
consumer environment and they are originated by the load characteristics. This means
that the consumers must themselves control the influence exercised by their
equipment onto the grid.
The most characteristic behavior of the power grid working on active-inductive
load has been modeled in Matlab in order to analyze the influence of a nonlinear load
application. The above mentioned load is connected to a three-phase classical
uncontrolled semiconductor bridge rectifier. The adopted for this simulation
parameters, are: U 380= V, f 50= Hz, LR 4.5= Ohm, LL 10= mH, dC 30= mF.
The simulation results are presented in Fig. 1 (a, b).
(a) (b)
Fig. 1. (a) Waveforms of phase A current (solid line) and phase A voltage (dotted line); (b)
Spectral contents of the phase A current, THDi = 34.27.
As it is seen in Fig. 1 (a), the current and the voltage waveforms show a certain
phase difference. The load requires reactive power from the supplying network and
the THDi is higher than normally is [4]. The usually applied equipment to correct the
electric power quality parameters of the consumed power have been the passive
power filters of high order harmonics, the compensating capacitor batteries and
synchronous compensators. Based on the achievements in power electronics, it
Active Power Filter and Common DC Link for Harmonic Distortion in Power Grids
427
became possible to solve this issue by means of active power filters (APF) [5], [6],
[7]. The APF that is currently applied consists of a voltage converter (with fully
controlled power switches) and a capacitor battery in a dedicated DC link. However,
the most non-linear consumers, having a rectifier incorporated, already possess a
capacitor in their output DC link. It is suggested therefore that a new type of APF will
use this already existing DC link: the converter of the filter is connected to the DC
output voltage tank. This will reduce the number of circuit elements and simplify the
control system of the APF [8]. The chosen control system is based on the relay (bang-
bang) current controller. This control system is characterized by simplicity, stable
performance, high speed and high accuracy [9], [10], [11].
The APF is supposed to operate as a step-up converter, i.e. the output voltage (the
output filter’s DC link voltage) will be always higher than the voltage applied to the
APF converter (the damaged voltage that is necessary to correct). The main task in the
development of this APF is the construction of the control system based on the
balance of the power consumed by the nonlinear load from the AC supply and the
power injected into the DC link. The other task is the control of the voltage level at
the output of the APF converter in order to correspond to the consumed power.
2 Relationship to Collective Awareness Systems
The increase in the number and the power of non-linear loads is due to the rapid
development of the modern electronics. From the point of view of the economy, the
power electronics made the energy use more efficient. Unfortunately the electronic
devices applied in the energy sector have led to quality problems of the power grid.
Those problems our society needs to solve by the effort of both the energy producers
and the electric power consumers.
In the industry, the modern static power converters and the frequency controllers
for motor drives made possible by the high-power IGBT transistors and other
emerging devices to facilitate the control of the induction motors, the cheapest and
most common type of electric motors. The application of electronic devices brought
certain effects in the general electric network: massively the controlled AC drives
have been upgraded by introducing a frequency controlled converters in already
existing power system and this distorted the consumed current.
In the domestic applications the switching power supplies increased dramatically
in number. The switched power converter is highly efficient but the massive use of it
created problems. For example, the millions of laptops, tablet PCs and mobile phones,
the necessary servers, routers, etc., all of these electronic devices operate at a constant
voltage supply, but they are connected to the AC mains. The converters from the AC
to DC in the millions of devices and other equipment represent a non-linear load. As a
final result, the quality parameters of the AC grid deteriorated.
In fact, it is not possible to avoid the non-linear load in the energy system. A
promising solution to this problem is the use of APF in order to compensate the
damage made to the grid parameters. This filtering is also a must for the
interconnections between the numerous generators and consumers in the future smart
grids. If a simple and reliable solution like the proposed one will be adopted, the
manufacturers of electronic equipment will produce massively equipment that will be
more easily made compact and cheap.
428 M. M. Habibullin et al.
The consumers connected to the mains will be able to have their nonlinear
influence compensated: the APF will be cheaper and more acceptable to be used in
massive number to compensate for harmonic distortion. This will contribute to the
development of Collective Awareness Systems, where the price of the nonlinear load
compensation will be equally divided between the consumers and the producers of
electric energy.
3 Theoretical bases
The schematic diagram of the proposed APF is shown in Fig. 2 (a). A transformer is
used as the matching element between the APF converter output (here it is an
inverter) and the electric grid.
(a)
AU
BU
CU
Di
LA
*i
LB
*i
LC
*i
LAi
LBi
LCi CU
(b)
Fig. 2. APF: (a) its connection to the load and grid; (b) its control system.
The operation of the suggested APF control system is planned to compensate for
the difference L
I∆ between the real L
I and the ideal L
*I load current that passes
through the system in any instant of time [8]:
L L L
*I I I∆ = − . (1)
The “Ideal” current, flowing from the mains, is defined by the power that the DC
consumer requires.
The active power 1P at the input should correspond to that DC power, and 1P is:
1 k1 kL k
k 1
P 3 U I cos∞
=
= ⋅ ⋅ ⋅ ϕ∑ , (2)
where kLI is the current drawn from the grid by the uncontrolled rectifier,
k1U is the AC input voltage,
kϕ is the phase shift between the voltage and current (in fact, the first harmonic
of the input current is the only harmonic contributing to the DC output power!).
The reactive power 1Q at the input is:
1 k1 kL k
k 1
Q 3 U I sin∞
=
= ⋅ ⋅ ⋅ ϕ∑ . (3)
The apparent power 1S at the uncontrolled rectifier input is:
FA
i
3LL
AU
BU
CU L
Ai L
Bi L
CiF
Bi F
Ci
Di
DC
LL
LR
CU
Active Power Filter and Common DC Link for Harmonic Distortion in Power Grids
429
2 21 1 1S P Q= + . (4)
According to the required (and expected) result from the filtering, it is assumed
that the phase angle between the current and the voltage will be zero ( 0ϕ = ). Then
the total power at the input of the scheme is:
1
1 1 1 L
Q 0;
S P 3 U I .
=
= = ⋅ ⋅ (5)
The power 2P that is expected to be consumed by the load is:
2 u 1 dP k U I= ⋅ ⋅ , (6)
where uk 1.35= is the DC/AC voltage ratio of the full bridge rectifier,
and dI is the DC current drawn by the load.
The power balance between 1P and 2P will be:
1 2P P P= + ∆ , (7)
where P∆ represents the total losses in the APF, the rectifier and the transformer.
In general, the lost part P∆ can be represented as a function of the current dI
multiplied by the coefficient Pk∆ . Then the balance of power is:
1 L u 1 d P d3 U I k U I k I∆⋅ ⋅ = ⋅ ⋅ + ⋅ . (8)
The peak value of the “ideal” current consumed from the grid is:
L
* d Pu
1
I kI k
U3
∆ = +
. (9)
The instantaneous values of the “ideal” phase currents are:
* d PLA u
1
* d PLB u
1
* d PLC u
1
I ki (t) k sin( t);
U3
I ki (t) k sin( t 120 );
U3
I ki (t) k sin( t 120 ).
U3
∆
∆
∆
= + ⋅ ω
= + ⋅ ω + °
= + ⋅ ω − °
(10)
As a general outlook, the APF control circuit is shown in Fig. 2 (b). The relay
current control (RCC) is configured by adjusting the hysteresis value in order to
determine the precision by which to process the signal from the current sensors. The
difference between the “ideal” and real current is delivered to the RCC together with
the signal from the DC current feedback iD. The RCC block calculates and compares
continuously the instantaneous “ideal” load currents and the real load currents. The
control signals for the converter (it is an inverter in Fig. 2 are generated by RCC.
These signals are aimed to form the APF output current instantaneous value. The
instantaneous values of APF output currents are supplied to a step-up transformer.
The secondary of the transformer supplies the missing instantaneous current
continuously and thus compensates for the non-sinusoidal waveforms of the
consumed current in the load. As a result, the current that the grid supplies to the
430 M. M. Habibullin et al.
whole circuit, becomes sinusoidal with a reasonable precision. The physical basis of
this current waveform shaping, as in all the active filter circuits, is the temporary
energy storage implemented by passive reactive devices. The particular difference in
this method is the use of the output voltage: the filter capacitor or the battery, and not
constructing a separate DC link as it is usually done.
4 Simulation Results Following the described operation principle of this APF, a computer model has been
developed in Matlab. The connection to the nonlinear load corresponds to the shown
in Fig. 2 (a). The simulation parameters are: U 380= V, f 50= Hz, LR 4.5= Ohm,
LL 0.1= mH, dC 30= mF, 3LL 0.1= mH. The results shown in Fig. 3 demonstrate
the current, supplied to the uncontrolled rectifier, having a sinusoidal form and a
phase coincident with the mains voltage phase. As a result, no reactive power is
consumed from the grid and the level of harmonic distortion of the current (THDi) is
close to ideal. This is illustrated by Fig. 3 (b) where THDi = 2.43%.
Fig. 3. Current in the phase A of the uncontrollable rectifier: (a) Graphically compared (solid
line) to the phase A voltage (dashed line); (b) The spectral composition of the current.
5 Experimental Results
The APF control system (RCC) was experimented in a real implementation. The
parameters of the experimental study are: U 24= V, f 50= Hz, R 0 20= − Ohm,
L 0.1= mH. In Fig. 4 a general view of the construction is shown.
The power module is “Mitsubishi PS22054” connected to a ”Mitsubishi 1200V
DIP IPM (PS2205X) EVALUATION BOARD”, used for debugging converter
circuits. The module “Piccolo TMDX28069USB” of Texas Instruments” is a DSP
controller, used here as the RCC. The module “CSLA1CH” of Honeywell is a linear
current sensor (for measurement of the current in the load circuit). The waveforms
were observed by oscilloscope “HANTEK DSO8060” and the values were measured
by multimeter “MASTECH M890F”. The power supply was a regulable block
supplying 24 V at a maximum current of 2A) is connected to converter input. A
single-phase load is experimented being a combination of a resistor and an inductive
coil, connected to the power converter output.
(a)
(b)
Active Power Filter and Common DC Link for Harmonic Distortion in Power Grids
431
Fig. 4. General view of set up to research RCC.
The mathematical model of the RCC based APF control system as shown in Fig. 2
(b) was first implemented as a simulation in Matlab 8.1 and then was loaded to the
DSP controller. The RCC control was supposed to maintain a sinusoidal current at a
frequency 50 Hz and amplitude of 1.2 A. This task and the width of the hysteresis gap
of the RCC were programmed in the DSP controller and the program was not changed
during the experiment. The current feedback obtained from the current sensor placed
in series with the load was introduced to the DSP controller too (analogue input). The
signal processing speed is 3 MSPS. The “bang-bang” operation produced by the RCC
control resulted in driving signals applied to the power converter of the APF. The
signals depend on the programmed task, the width of the hysteresis gap and the signal
from the current feedback. The driving signals from the DSP controller were sent to
the power converter switches (through drivers). The correct waveforms from the
experiments are shown in Fig. 5 (a, b).
(a) (b)
Fig. 5. Operation of the RCC: (a) Waveform and numerical value of the load current; (b) closer
view of the signal of the load current sensor.
As it is verified from the waveform in Fig. 5 (a, b) and the multimeter readings,
the load current (DC) is corresponding to the sinusoidal input current from the grid at
a correct magnitude, phase and frequency. The variation of the load (resistance of the
variable resistor) across a range of values left the waveforms always correctly
432 M. M. Habibullin et al.
corresponding to the frequency, phase and amplitude required from the energy qualiy
point of view.
6 Conclusions and Future Work According to the results from the theoretical analysis, mathematical modelling, and
experiments, the proposed APF based on the power rectifier filter capacitor as a DC
link is designed and verified. The APF control based on RCC and limited calculation
based on "ideal" load current was investigated. According to the simulation results,
the uncontrolled rectifier combined with the new APF system is an effective means of
compensation for harmonic current distortion and reactive power. For the
experimental verification the APF set-up has been designed, and it confirmed the
good performance of the simple “bang-bang” RCC control of the APF. The
application of the proposed APF control system to non-linear power converters will
improve the electromagnetic compatibility of the “naturally” nonlinear consumers and
the power grids. It will have a positive influence on the power system and its
customers. It provides increased reliability and energy efficiency. This will be
especially important for the future smart grids construction. Further work on the APF
will be in experimental studies of “uncontrolled rectifier – APF” to improve the
construction and control system of the proposed APF.
References
1. Nejdawi, I.M., Emanuel, A.E., Pileggi, D.J.: Harmonic Trend in the USA: A Preliminary
Survey. Transactions on Power Delivery. Vol. 14, № 4, pp. 1488--1494 (1999)
2. Bojarskaja, N.P., Dovgun V.P.: The influence of the harmonic content of the currents and
voltages on energy efficiency. Vestnik KrasGAU. №4, pp.130--134 (2010)
3. Zhezhelenko, I. V.: The higher harmonics in power systems of industrial enterprises. 2nd
ed. rev. and additional. Jenergoatomizdat, Moscow (1984)
4. IEEE Std 519--1992, IEEE Recommended Practices and Requirements for Harmonic
Control in Electrical Power Systems, New York, NY: IEEE
5. Moran, L., Dixon, J., Espinoza, J., Wallace, R.: Using active power filters to improve
power quality. In: 5th Brazilian Power Electronics Conference, COBEP (1999)
6. Sandeep G J S M, Rasoolahemmed Sk.: Importance of Active Filters for Improvement of
Power Quality. Int. J. of Engineering Trends and Technology, 4(4), pp. 1164--1171 (2013)
7. Meshherjakov, V.N., Koval', A.A.: The active filter-compensating devices for systems
controlled dc drive. LSTU, Lipetsk (2008)
8. Meshherjakov, V.N., Bezdenezhnyh, D.V., Habibullin, M.M.: The active harmonic filter
adapted to the alternating current. In: The 9th All-Russian conference of young scientists.
Managing large systems, с.164--167, Lipetsk (2012)
9. Kazmierkowski, M. P., Malesani, L.: Current control techniques for three-phase voltage
source PWM converters: A survey. IEEE Trans. Ind. Electron. 45(5), pp. 691--703 (1998)
10. Chen, D., Xie, S.: Review of the control strategies applied to active power filters. In: IEEE
International Conference on Electric Utility Deregulation, Restructuring and Power
Technologies (DRPT2004), pp. 666-670 (2004)
11. Xiaobo, F., Dairun, Z., Qian, S.: Hysteresis Current Control Strategy for Three-phase
Three-wire Active Power Filter. Automation of Electric Power Systems. Vol. 31, № 18, pp.
57--61 (2007).