F5707.01-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: TUBELITE, INC. SERIES/MODEL: E4500 TYPE: Storefront Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC F5707.01A 1/2" Laminated glass, Glass temperature 75°F 35 32 F5707.01B 1/4" Monolithic glass 28 27 Reference should be made to Intertek-ATI Report No. F5707.01-113-11 for complete test specimen description. This page alone is not a complete report. Flanking limit tests and reference specimen tests are available upon request. 130 Derry Court York, PA 17406 p. 717.764.7700 f. 717.764.4129 www.archtest.com www.intertek.com/building

Transcript of Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900...

Page 1: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test

F5707.01-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT

ASTM E90

Rendered to:

TUBELITE, INC.

SERIES/MODEL: E4500

TYPE: Storefront

Summary of Test Results

Data File No. Glazing (Nominal Dimensions) STC OITC

F5707.01A 1/2" Laminated glass, Glass temperature 75°F 35 32

F5707.01B 1/4" Monolithic glass 28 27

Reference should be made to Intertek-ATI Report No. F5707.01-113-11 for complete test specimen description. This page alone is not a complete report. Flanking limit tests and reference specimen tests are available upon request.

130 Derry CourtYork, PA 17406

p. 717.764.7700f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 2: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test

Acoustical Performance Test Report

TUBELITE, INC. 4900 Langdon Road, Suite 500

Dallas, Texas 75241 Report No F5707.01-113-11 Test Date 02/29/16 Report Date 03/16/16 Specimen Construction Date 02/29/16 Project Scope Architectural Testing, Inc., a subsidiary of Intertek ("Intertek-ATI"), was contracted to conduct a sound transmission loss test. The complete test data is included as Appendix B of this report. The client provided the test specimen. Test Methods Testing for this project was conducted in accordance with the following standards. The equipment listed in the attachments meets the requirements of the following standards. ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements ASTM E413-10, Classification for Rating Sound Insulation ASTM E1332-10a, Standard Classification for Rating Outdoor-Indoor Sound Attenuation ASTM E2235-04 (2012), Standard Test Method for Determination of Decay Rates for Use in Sound Insulation Test Methods

Test Procedure All measurements were conducted in the HT test chambers at Intertek-ATI located in York, Pennsylvania. The sensitivity of the microphones was checked before measurements were conducted. The transmission loss values were obtained for a single direction of measurement. Two background noise sound pressure level and five sound absorption measurements were conducted at each of five microphone positions. Two sound pressure levels were made simultaneously in the receive and source rooms at each of five microphone positions.

The air temperature and relative humidity conditions were monitored and recorded during all measurements.

130 Derry CourtYork, PA 17406

p. 717.764.7700f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 3: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test

F5707.01-113-11-R0 Page 2 of 6

Specimen Installation A sound transmission loss test was initially performed on a filler wall. The specimen plug was removed from the filler wall assembly. The specimen was placed on a foam isolation pad in the test opening. Duct seal was used to seal the perimeter of the specimen to the test opening on both sides. The interior side of the specimen, when installed, was approximately 1/4" from being flush with the receive room side of the filler wall. A stethoscope was used to check for any abnormal air leaks around the test specimen prior to testing. Test Calculations Transmission loss (TL) at each 1/3 octave frequency is the average source room sound pressure level minus the average receive room sound pressure level, plus, 10 times the log of the specimen area divided by the sound absorption of the receive room with the sample in place. STC Rating To obtain the Sound Transmission Class (STC), read the TL of the contour curve at 500 Hz. The sum of the deficiencies below the contour curve must not exceed 32. The maximum deficiency at any one frequency must not exceed 8. OITC Rating The Outdoor-Indoor Transmission Class (OITC) is calculated by subtracting the logarithmic summation of the TL values from the logarithmic summation of the A-weighted transportation noise spectrum stated in ASTM E1332. Specimen Descriptions

Frame

Size 78-3/4" by 78-1/8"

Thickness 4-1/2"

Corners Butted

Fasteners Screws

Seal Method N/A

Material Aluminum

Reinforcement N/A

Thermal Break Material N/A

Daylight Opening Size 37-3/8" by 75-3/16"

N/A-Not Applicable

Page 4: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test

F5707.01-113-11-R0 Page 3 of 6

Specimen Descriptions (Continued)

Glazing Option A

Measured Overall Glass Thickness 0.475"

Spacer Type N/A

Sheet

Measured Thickness 0.227", 0.064", 0.184"

Muntin Pattern N/A

Material Laminated

Laminate Material PVB

Glazing Method Exterior

Glazing Material Roll-in glazing gasket

Glazing Bead Material Aluminum

Glazing Option B

Measured Overall Glass Thickness 0.227"

Spacer Type N/A

Sheet

Measured Thickness 0.227"

Muntin Pattern N/A

Material Client did not specify

Laminate Material N/A

Glazing Method Exterior

Glazing Material Roll-in Glazing Gasket

Glazing Bead Material Aluminum

* - Stated per Client/Manufacturer, N/A-Not Applicable

Page 5: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test

F5707.01-113-11-R0 Page 4 of 6

Specimen Descriptions (Continued)

Components

Type Quantity Location

Weatherstrip

No weatherstrip

Hardware

No hardware

Drainage

No drainage

Test Option Total Weight (lbs) Average Weight (lbs/ft2)

A 269 6.30

B 159 3.72

Comments Drawings of the test specimen are included in Appendix D. The specimen was returned per the client's request.

Page 6: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test

F5707.01-113-11-R0 Page 5 of 6

Intertek-ATI will service this report for the entire test record retention period. Test records, such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation, will be retained by Intertek-ATI for the entire test record retention period. The test record retention period ends four years after the test date. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen tested. This report is intended to help in the client’s quality assurance program, but it does not represent a continuous or exhaustive evaluation of the specimen tested or of other products or materials that were not evaluated. The statements and data provided herein do not constitute approval, disapproval, certification, or acceptance of performance or materials. This report may not be reproduced, except in full, without the written approval of Intertek-ATI. For INTERTEK-ATI: Daniel B. Mohler Todd D. Kister Technician - Acoustical Testing Laboratory Supervisor – Acoustical Testing DBM:jmcs

Attachments (pages): This report is complete only when all attachments listed are included.

Appendix A: Equipment description (1) Appendix B: Complete test results (4) Appendix C: Photographs (1) Appendix D: Drawings (4)

Page 7: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test

F5707.01-113-11-R0 Page 6 of 6

Revision Log

Rev. # Date Page(s) Revision(s)

R0 03/16/16 N/A Original Report Issue

This report produced from controlled document template ATI 00272, revised 08/31/15.

Page 8: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test

Data Acquisition Unit National Instruments PXI-1033

Description ATI NumberDate of

Calibration

Data Acquisition card 65127 04/14 *

Microphone and Preamplifier 64902 12/15

F5707.01 -113-11

Appendix A

Instrumentation:

Instrument Manufacturer Model

Source Room

MicrophonePCB Piezotronics 378B20

Source Room

MicrophonePCB Piezotronics 378B20

64905 12/15

64903 12/15

378B20

12/15Source Room

MicrophonePCB Electronics 378B20 Microphone and Preamplifier 65103

Source Room

MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64906

Source Room

MicrophonePCB Piezotronics

12/15

Receive Room

MicrophonePBC Piezotronics 378B20 Microphone and Preamplifier 64907 12/15

Microphone and Preamplifier

Receive Room

MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64908 12/15

Receive Room

MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64909 12/15

Receive Room

MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64910 12/15

Receive Room

MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64911 12/15

Receive Room

Environmental IndicatorComet T7510 Receive Room 64915 03/16

Source Room

Environmental IndicatorComet T7510 Source Room 64914 03/16

Microphone Calibrator Norsonic 1251 Pistonphone Calibrator 65105 04/15

*- Note: The calibration frequency for this equipment is every two years per the manufacturer's recommendation.

Test Chamber:

Volume Description

Receive Room 234 m3 (8291.3 ft3)

Rotating vane and stationary diffusers Temperature and humidity controlledIsolation pads under the floor

Microphone and Preamplifier

Vibration break between source and receive rooms3.05 m (10 ft) high

Source Room 206.6 m3 (7296.3 ft3)Stationary diffusers only

Temperature and humidity controlled

Maximum Size Description

N/A-Not Applicable

TL Test Opening4.27 m (14 ft) wide by

ATI 00760 Page 1 of 1 Revised: 01/22/15

Page 9: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test

F5707.01-113-11-R0

Appendix B

Complete Test Results

Page 10: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test

STC Rating (Sound Transmission Class)

Deficiencies (Sum of Deficiencies)

OITC Rating (Outdoor-Indoor Transmission Class)

0

0.31 0

5000

27

2500 5.2

4000

Notes: 1) Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.

2) Specimen TL levels listed in red indicate the lower limit of the transmission loss.

3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied

ATI 00760 Revised 09/18/15

32

45 43.4

35

8.8 15.7

Page 1 of 2

0.29

92 41 44.4 0.32

94

49

-

3150 6.2 10.0

7.3 12.3

94

95 57 34.9

51 38.5

41.1

92

7.4

0.22 7

0.22 4

0.16 1

102 67 32.2

1250 9.1 6.7 97 61 33.2

0.29 3

8.3

2000 5.7

0.14 6

1600 7.4 7.0

16.1 5.9 100 62 36.3 0.42

1

1000 10.9 6.1 96 59 35.2

1

1800

0.23

500 19.6 5.8 96 60 33.9 0.16

0.35 1

630 18.0 5.7 100 64 34.9

0.44 2

315 26.8 5.3 99 68 29.8

0.64 0

400 23.2 5.7 96 62 32.4

0.48 0

200 40.2 4.4 106 77 29.1

1.41 0

250 34.2 4.9 106 75 29.4

0.78 0

125 34.1 4.4 105 75 30.1

5.0 104 84 21.0

100 33.3 5.0 104 74 30.9

2.94 -

160 41.9 4.6 105 75 29.9

80 32.1

Data File No. F5707.01A

Client Tubelite, Inc.

Description

(Hz) (dB) (m²) (dB) (dB)

1.43 -

SPL SPL

AIRBORNE SOUND TRANSMISSION LOSSASTM E 90

Test Date 02/29/16

Specimen Area 3.97 m² Receive Temp. 21.9 °C Source Temp.

Source Receive

Receive Humidity 51% Source Humidity 49%

Limit Deficiencies

Number

(dB)

Series/Model: E4500, Storefront with 1/2" laminated, Glass temperature 75°F

21.1 °C

Confidence of

Technician

FreqBackground

AbsorptionSpecimen

TL

95%

Daniel B. Mohler

SPL

Page 11: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test

21.9 °C Source Temp. 21.1 °C

Data File No.

Receive Humidity 51%

F5707.01A

Source Humidity

3.97 m² Receive Temp.

Test Date 02/29/16

AIRBORNE SOUND TRANSMISSION LOSSASTM E 90

ATI 00760 Revised 09/18/15

Description Series/Model: E4500, Storefront with 1/2" laminated, Glass temperature 75°F

Specimen Area

Client Tubelite, Inc.

49%Technician Daniel B. Mohler

Page 2 of 2

0

10

20

30

40

50

60

70

80

90

100

31.5 63 125 250 500 1000 2000 4000 8000

Sou

nd

Tra

nsm

issi

on

Lo

ss (

dB

)

Frequency (Hz)

Airborne Sound Transmission Loss

Specimen TL

Contour Curve

Page 12: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test

STC Rating (Sound Transmission Class)

Deficiencies (Sum of Deficiencies)

OITC Rating (Outdoor-Indoor Transmission Class)

3

0.31 0

5000

15

2500 5.3

4000

Notes: 1) Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.

2) Specimen TL levels listed in red indicate the lower limit of the transmission loss.

3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied

ATI 00760 Revised 09/18/15

27

57 32.0

28

9.0 16.1

Page 1 of 2

0.29

92 50 35.5 0.34

94

62

-

3150 6.2 10.1

7.4 12.5

94

95 64 27.9

65 24.2

28.8

92

7.4

0.22 0

0.20 4

0.15 8

102 68 31.7

1250 10.1 6.6 97 60 34.3

0.33 0

8.4

2000 6.0

0.12 0

1600 7.7 7.0

16.9 5.9 100 65 32.9 0.46

0

1000 12.6 6.0 96 60 33.9

0

0800

0.23

500 21.6 5.8 96 65 29.6 0.20

0.33 0

630 19.5 5.6 100 68 30.6

0.40 0

315 27.8 5.5 99 73 24.9

0.72 0

400 25.0 5.7 96 67 27.8

0.49 0

200 39.6 4.5 106 82 24.1

1.32 0

250 34.2 5.1 105 80 24.7

0.83 0

125 35.3 4.6 105 79 25.5

4.9 104 88 15.5

100 33.5 5.3 104 77 26.7

3.02 -

160 40.9 4.8 105 80 24.0

80 34.2

Data File No. F5707.01B

Client Tubelite, Inc.

Description

(Hz) (dB) (m²) (dB) (dB)

1.57 -

SPL SPL

AIRBORNE SOUND TRANSMISSION LOSSASTM E 90

Test Date 02/29/16

Specimen Area 3.97 m² Receive Temp. 22.1 °C Source Temp.

Source Receive

Receive Humidity 48% Source Humidity 47%

Limit Deficiencies

Number

(dB)

Series/Model: E4500, Storefront with 1/4" monolithic glass

21.4 °C

Confidence of

Technician

FreqBackground

AbsorptionSpecimen

TL

95%

Daniel B. Mohler

SPL

Page 13: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test

22.1 °C Source Temp. 21.4 °C

Data File No.

Receive Humidity 48%

F5707.01B

Source Humidity

3.97 m² Receive Temp.

Test Date 02/29/16

AIRBORNE SOUND TRANSMISSION LOSSASTM E 90

ATI 00760 Revised 09/18/15

Description Series/Model: E4500, Storefront with 1/4" monolithic glass

Specimen Area

Client Tubelite, Inc.

47%Technician Daniel B. Mohler

Page 2 of 2

0

10

20

30

40

50

60

70

80

90

100

31.5 63 125 250 500 1000 2000 4000 8000

Sou

nd

Tra

nsm

issi

on

Lo

ss (

dB

)

Frequency (Hz)

Airborne Sound Transmission Loss

Specimen TL

Contour Curve

Page 14: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test

F5707.01-113-11-R0

Appendix C

Photographs

Receive Room View of Installed Test Specimen

Source Room View of Installed Test Specimen

Page 15: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test

F5707.01-113-11-R0

Appendix D

Drawings

Page 16: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test
dmohler
Oval
dmohler
Oval
dmohler
Oval
dmohler
New Stamp
dmohler
Callout
Heights were adjusted 5/8" shorter for the test.
Page 17: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test
dmohler
New Stamp
dmohler
Oval
dmohler
Oval
dmohler
Oval
dmohler
Oval
Page 18: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test
dmohler
New Stamp
dmohler
Oval
dmohler
Oval
dmohler
Oval
Page 19: Acoustical Field Test Report - Tubelite · Acoustical Performance Test Report . TUBELITE, INC. 4900 Langdon Road, Suite 500 . Dallas, Texas 75241 . Report No F5707.01-113-11 . Test
dmohler
New Stamp
dmohler
Oval
dmohler
Oval