BHS1.com The BHS Electrical Distribution System (EDS) provides flexible power distribution to all 480 V / 3 ph components in an Operator Aboard Battery Extractor System including the Battery Extractor, chargers, and Battery Wash Equipment. The EDS is a stand mounted, high-density system that is customized using track busway that can be tapped at any location with a simple turn-n-lock connection. Electrical Distribution System Accessories

Transcript of Accessories Electrical Distribution System BHS Electrical Distribution System ... Particular...

Page 1: Accessories Electrical Distribution System BHS Electrical Distribution System ... Particular Requirements for Busbar Trunking systems ... Underwriters Laboratories Standard, UL 857

BHS1.com

The BHS Electrical Distribution System (EDS) provides flexible power distribution to all 480 V / 3 ph components in an Operator Aboard Battery Extractor System including the Battery Extractor, chargers, and Battery Wash Equipment. The EDS is a stand mounted, high-density system that is customized using track busway that can be tapped at any location with a simple turn-n-lock connection.

Electrical Distribution SystemAccessories

Page 2: Accessories Electrical Distribution System BHS Electrical Distribution System ... Particular Requirements for Busbar Trunking systems ... Underwriters Laboratories Standard, UL 857

BHS1.com

Equipment Comparison

• 2JunctionBoxes• Modifiableandexpandable• Installcostsapproximatelyathirdoftraditionalsystems,andcostsavingsincreaseasthe

EDSsystemgrows

• 100fusedbladedisconnects• 100runsofconduit(1toeachcharger)• Multiplerunsofwireway• Costlyanddifficulttomodify

TheEDSrunsthelengthofthebatterysystemstandsandeasilyaccommodatesgrowth.Themaintenance-freedesignsavesspace,andtheuniqueconnectionmethodeliminatesinterruptionsinpower,providingreliablepowerdistribution.Whetherconnectingsectionsoftrackbuswayorconnectingmodularunitsintothetrackbusway,aturn-n-lock“compression-fit”connectionisusedtolockeverythinginplace.

Operator Aboard Battery Extractor System with EDS:

Operator Aboard Battery Extractor System with Traditional Wiring:

Electrical Distribution SystemAccessories

TheBHSElectricalDistributionSystem(EDS)providesafavorableoptionforpoweringanOperatorAboardBatteryExtractorSystem,inplaceoftraditionalalternativesthatutilizeadisarrayofcables.ThestreamlineddesignoftheEDSallowsforeasymodificationorexpansiontothesystemduetotheinnovativeconnectionofthecomponents.

EDS, Sixteen outlets pictured

Traditional Wiring

Page 3: Accessories Electrical Distribution System BHS Electrical Distribution System ... Particular Requirements for Busbar Trunking systems ... Underwriters Laboratories Standard, UL 857

BHS1.com

EDS Equipment Components

Track BuswayTrackbuswayconsistsoffourconductorsallowingforamaximumcapacityof800A.Eachcompositecopper-aluminumconductorishousedinacontinuousinsulator,andtheextrudedaluminumcasecanbeusedasa100%groundpath.Thecontinuousplug-indesignallowsfortwistinplug-inunitstobeinstalledanywherealongthelengthofthetrackbusway.

• Availablein5’and10’(1.5mand3m)lengthsections• Accommodatesupto800A/600Vacordc• Aluminumhousing• Compositecopper-aluminumconductors• Shortcircuitcapacityof50kA• 60Hz/50Hzfrequencyrating

Dual Outlet Units with 20 A (or 30 A) Breakers

Joint Kit

Installation Tool

End Power Feed Unit

End Power Feed Unit• Theendpowerfeedunitconnectstotheendofanybuswaysectionandsuppliespower• 24”x20”x20”(610mmx508mmx508mm)steeljunctionbox,withremovablesides,

connectedtoa1’(305mm)sectionofbusway

Available Units:

1. 800ACapacity–24”x20”x20”(610mmx508mmx508mm)steeljunctionboxwithlugconnectionsforparallelrunsofMCM600Cuwire,andissizedtoallowfor(2)4”(102mm)conduitstobeinstalledtothebox

2. 400ACapacity–16”x12”x10”(406mmx305mmx254mm)steeljunctionboxwithlugconnectionsforMCM500,andissizedtoallowfora4”(102mm)conduittobeinstalledtothebox

Circuit Breaker Units• Usedtotapoffpowerfromthebusway• Plugheadisreversibletofaceinoppositeposition• Lockedintopositionwithasingleboltonmountingtab

Available Units:

1. Dualoutletunitswith20Abreakers(NemaL16-20)

2. Dualoutletunitswith30Abreakers(NemaL16-30)

3. Hardwiredbreaker

-Accommodates480V/3phpowersupply

-IdealforusewithanOperatorAboardBatteryExtractororWashEquipment

Track Busway

Joint Kit & Installation ToolAjointkitisrequiredateachjointwhenconnectingadjacentsectionsoftrackbusway.Ajointkitincludesahousingcouplerpair(two12-screwcouplers)andbusconnectorset(silver-platedcopperbladessecuredtoinsulatingmountingplate).

Aninstallationtoolisusedforinstallationofthe‘busconnector’electricaljointbetweentwoadjacentsectionsoftrackbusway.Theinstallationtoolisusedinconjunctionwiththejointkittocreateasecureelectricalconnection.

Page 4: Accessories Electrical Distribution System BHS Electrical Distribution System ... Particular Requirements for Busbar Trunking systems ... Underwriters Laboratories Standard, UL 857

P.O.Box28990•St.Louis,MO63132USA•1.800.BHS.9500•Fax:314.423.6444•Email:[email protected]•Web:BHS1.comSpecificationsaresubjecttochangewithoutnotice.©2013–2014BatteryHandlingSystemsInc.St.Louis,MODataSheet:PL-380001/14

Product Specifications

Standards & Certifications

Maximum Voltage 600V

Ampacity 800A

Frequency 50or60Hz

Conductors Qty4(PhasesA,B,CandNeutral)

Rated Short Circuit Capacity 50kA

Ambient Operating Temp 40°C/104°F60°C/140°F–0.8AmpRatingMultiplier

Grounding AluminumCasing,100%GroundingPath

Voltage Drop (1)voltper50ft(15m)

Housing Material ExtrudedAluminum

Conductor NickelplatedAluminumandCopper

Housing Exterior Dimensions 5’or10’(L)x6.4”(W)x5.05”(H)1.5mor3m(L)x162.6mm(W)x128.3mm(H)

Thebuswayisdesignedandmanufacturedtothefollowingstandards:1. LowVoltageDirective(73/23/EEC)includingAmendment(93/68/EEC)

2. LowVoltageSwitchgearandControlgearAssemblies,Part1:TypeTestedAssemblyandPartiallyTypeTestedAssemblies,IEC60439-1:1999

3. LowVoltageSwitchgearandControlgearAssemblies,Part2:ParticularRequirementsforBusbarTrunkingsystems(busways),IEC60439-2:2000

4. UnderwritersLaboratoriesStandard,UL857–ThecommonUL,CSA,andANCEStandardforBuswaysthatisderivedfromthefiftheditionofCSAStandardsC22.2No.27,thetwelftheditionofUL857,andthesecondeditionofNMX-J-148-1998-ANCE.

5. ETLClassifiedto(US/Canada)UL857

6. NationalElectricCode(NEC)–Article368-Busways

7. NEMAAB1,MoldedCaseCircuitBreakersandMoldedCaseSwitches

8. NEMAKS-1,EnclosedandMiscellaneousDistributionEquipmentSwitches(600VAC)

9. NFPA70–NationalFireProtectionAgency

Charger ShutdownTheoptionalchargershutdownconnectstotheBHSBatteryRoomVentilationSystem(BRVS)ortoaHydrogenGasDetector(HGD)inordertodisablethechargers.Ifanexcessiveamountofhydrogen(morethan2%)isdetectedinthearea,thepowersupplytothechargersthroughtheEDSwillautomaticallybeinterrupted.Bydisablingthechargers,theproductionofhydrogengasisstopped.ReferenceliteraturePL-3900 Battery Room Ventilation SystemformoreinformationontheBRVSandHGD.