The models AC 46, AC 56 & AC 86 are
equipped with a special PC Board that
operates like a
“Cleaning/Maintenance Reminder”.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
When condensingtemperature is morethen 60°C, thecondenser sensor senda signal to theCleaning/MaintenanceRemind Board to…….
AC 46-56-86AC 46-56-86
0
10
70
40
30
20
80
60
50
>60ºC
MAINTENANCEMAINTENANCE
…..activate/energize
the RED Light with
machine still in
operation.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
This is the signal to
clean the air cooled
condenser filter by
taking it out from
the front panel.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
In case the RED
Light is blinking
slow (0,5” ON -
3” OFF) with
machine still in
operation….
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
…. it’s the signal to
perform the
cleaning/de-scaling of
the water system.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCEThe time between
cleaning/de-scaling
can be changed
according to the
quality of the water
used as per setting of
the two Dip Switches
of the PC Board....
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
….as per attached
chart.
AC 46-56-86AC 46-56-86
DIP SW 1 DIP SW 2 TIME
ON ON 1 MONTH
OFF ON 3 MONTHS
ON OFF 6 MONTHS
OFF OFF 12 MONTHS
MAINTENANCEMAINTENANCEThe most important program on the maintenance of the cubers isthe cleaning/sanitizing to be done on regular base, as detailed herebelow:
• Sanitizing: Every month
• Cleaning: Every sixor when cleaning remind board signals it.
On next slides will be shown the procedure for cleaning andsanitizing.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCETOOLS REQUIRED
• Medium PhillipsScrewdriver
• Medium Flat Screwdriver
• Pair of safety gloves
• Bucket
• Different types of brush
• Approved Cleaner/Sanitizer
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
Remove the front…. ….and top panel.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
Wait till the end of
the defrost/harvest
cycle then Switch
OFF the machine
at Push Button
Master Switch.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
Scoop out all ice cubes storedinto the bin so to prevent itscontamination then...
….take out the S.S. spring holdingthe soft plastic plug to the bottomof the water sump ….
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
….and remove
the soft plastic
plug by pulling
it down so to
drain out all
water from the
water sump.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
Unloose the two
thumb screws
holding the
curtain assy to
the
evaporator/sump
chamber and ….
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
…. take out the
curtain with its
own plastic
bracket.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCEGrasp the
spray platen
assy on the
center spray
jet and lift it
up so to have
access to the
water sump.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
Turn
counterclockwise
the spray platen
seat and …..
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
… remove it
from its
bottom hole.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
Disconnect
the plastic
hose from the
water pump
outlet port.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
Prepare the cleaningsolution by diluting ina plastic bucket twoliters of lukewarmwater (max 40ºC) with200 cc ofSCOTSMAN IceMachine Cleaner.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCEPrepare, in asuitable basin, asecond cleaningsolution by dilutingfour liters oflukewarm water(max 40ºC) with400 cc ofSCOTSMAN IceMachine Cleaner.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCEPoor into thecleaning solutionall parts previouslyremoved from thewater system i.e.:
• Spray platen
• Curtain assy
• Spray platen seat
• Soft Plastic plug
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
Leave them into
the cleaning
solution for about
10 minutes then,
with an help of a
plastic brush,
remove all scale
deposit then….
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
….wash them under
tap water.
When finish, install
again all removed parts
following the
procedure on reverse.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
Remove the evaporator coverthen….
….slowly pour onto the evaporatorthe cleaning solution.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
With the help of
a brush dissolve
the most
resistant and
remote scale
deposits in the
plastic platen.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
Switch ON the
machine at Push
Button Master
Switch.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCEWith the water pump in operation the cleaning solution in kept incirculation through the entire water system.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
Let the unit remain in
the freezing mode for
about 20 minutes then
move the Cleaning
Switch on the Cleaning
position (II) for about
four-five minutes
till…...
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE……all the ice cubes produced with the cleaning solution arereleased down from the evaporator.
AC 46-56-86AC 46-56-86
BINTSTAT
COMPRESSOR
MOTORWATERHOT
GASVALVE
WATERINLETVALVE
BY-PASSSWITCH
EVAPORATORTHERMOSTAT
PUMPFAN
3
2
46
SWITCHMASTER
SAFETYREMINDBOARD
CONDENSER
& ALARM SWITCHRE-SET BUTTON
SENSOR
MAINTENANCEMAINTENANCE
Flush out the cleaning solutionfrom the sump by removing thesoft plastic plug then….
…. pour onto the evaporator cavitythree liters of fresh water to rinsethe molds and the platen.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
Turn again the CleaningSwitch on Operatingposition (I) so to leavethe water pumpcirculating the freshwater and rinse thewater system
Do it twice so to be sure no more trace of descaling/cleaningsolution remains into the sump.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
Pour on the upper side of theevaporator 2 liters of freshwater with 10-15 drops ofScotsman Antialgae Solutionthen….
…. turn again the CleaningSwitch in Operating Position (I)so to have the water pumpcirculating the sanitationsolution for 10 minutes.
NOTE. Do not mix delimer with sanitizingsolution to avoid the generation of a veryaggressive acid.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
Flush out the sanitizing solution from thesump then….
…. turn the CleaningSwitch to CleaningPosition (II) for 2-3minutes….
…. and then again inOperating Position (I).
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
Place again theevaporator cover andthe service panelspreviously removed.
At completion of the freezing and harvestcycle make sure of proper texture andclearness of the ice cubes and that they donot have any acid taste.
ATTENTION. In case the ice cubes are cloudy-white and have acid taste, melt them
immediately by pouring on them some warmwater so to prevent that anybody can use them.
AC 46-56-86AC 46-56-86
MAINTENANCEMAINTENANCE
Wipe clean and rinse the inner surface of the storage bin.Wipe clean and rinse the inner surface of the storage bin.
REMEMBER. To prevent theaccumulation of undesirable
bacteria it is necessary to sanitizethe interior of the storage bin with a
sanitizing solution every week.
AC 46-56-86AC 46-56-86
SERVICEANALYSISSERVICESERVICE
ANALYSISANALYSIS
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSIS
This is a ScotsmanIce Cube.
It must be clear, solidwith a smalldepression on itsbottom rim of about3-4 mm.
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSIS
This ice cube is clear, solidbut it has a deep depressionon its bottom rim due to a tooshort freezing cycle.
It is necessary to extend thelength of the freezing cycleby turning the…..
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSIS
….. Evaporator
Thermostat a little bit
clockwise.
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSIS
This is a typical ice cubeclear on its upper left sideand white and corroded onits bottom right side.
The reason is that the waterdoesn’t reach in correctlythe inside of some of the tincooper molds.
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSIS
Probably one ormore of thespray jets of thespray platen ispartially lookedby scale/dirt andthe water is nolonger sprayedas a completeinverted watercone.
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSISTo overcamethe problem itis necessaryfirst to find outwhich of thesix spray jetsdoesn’t spraywater in thecorrect waythen removethe completespray platenfrom the sumpand ….
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSIS
….unloose the two
screws securing
the plastic spray
cover to clean it or
replace it with a
new one.
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSIS
When refit it onthe spray platenbe careful incorrectly installthe O ringbetween thespray cover andits bottom seat.
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSIS
This is a typical ice cube; clearon its upper side and white andcorroded on its bottom side.
The water is sprayed in thecorrect way and under the rightpressure only during the firstportion of the freezing cyclewhile on the second half the levelof the water in the sump is notenough to assure the proper sprayof the water pump (cavitation).
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSISAC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSIS
The reason is the too low water level into the sump during theharvest cycle that could be related to:
• Too low water inlet pressure• Clogged water filter
• Clogged water inlet strainer
• Clogged water flow control
• Water leak through the front curtain
• Water leak through the overflow stand pipe
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSIS
The reason is the too low water level into the sump during theharvest cycle that could be related to:• Too low water inlet pressure
• Clogged water filter• Clogged water inlet strainer
• Clogged water flow control
• Water leak through the front curtain
• Water leak through the overflow stand pipe
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSISThe reason is the too low water levelinto the sump during the harvest cyclethat could be related to:
• Too low water inlet pressure
• Clogged water filter
• Clogged water inlet strainer• Clogged water flow control
• Water leak through the front curtain
• Water leak through the overflow standpipe
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSIS
The reason is the too low water level into the sump during theharvest cycle that could be related to:• Too low water inlet pressure
• Clogged water filter
• Clogged water inlet strainer
• Clogged water flow control• Water leak through the front curtain
• Water leak through the overflow stand pipe
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSISThe reason is the too low water level into the sump during theharvest cycle that could be related to:
• Too low water inlet pressure
• Clogged water filter
• Clogged water inlet strainer
• Clogged water flow control
• Water leak through the frontcurtain• Water leak through the overflowstand pipe
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSISAC 46-56-86AC 46-56-86
• Too low water inletpressure• Clogged water filter• Clogged water inlet strainer• Clogged water flow control• Water leak through thefront curtain
• Water leak through thesoft plastic plug
The reason is the too low water level into the sump during theharvest cycle that could be related to:
SERVICE ANALYSISSERVICE ANALYSIS
This ice cube is clear, solidbut it is oversized.
It is necessary to reduce thelength of the freezing cycleby turning the EvaporatorThermostat Knob…..
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSIS
….. a little bit
counter-clockwise.
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSIS
These ice cubes areboth clear, solid butsome are oversizedand some other areundersized.
If so the possiblereason is an incorrectcharge of refrigerantin the system (toolow).
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSISLooking the upper side ofthe evaporator after 15-20minutes in the freeze theserpentine is properlyfrosted mainly on the firstportion of the same (inletof refrigerant) while on thesecond portion (outlet) thefrost is very thin (noexchange of heat betweenrefrigerant - already invapor state - and sprayedwater).
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSISCheck the operatingpressures of the refrigerantsystem connecting thegauges on hi and low servicevalve.
The operating pressures atthe end of the freezing cyclewith unit at 21ºC ambientmust be:
Hi pressure (air):Hi pressure (air): 8 bar8 bar(110 PSI)(110 PSI)
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSISCheck the operating pressuresof the refrigerant systemconnecting the gauges on hiand low service valve.
The operating pressures at theend of the freezing cycle withunit at 21ºC ambient must be:
Hi pressure (air): 8 bar(110 PSI)
Hi pressure (water): 8-9 barHi pressure (water): 8-9 bar(110-125 PSI)(110-125 PSI)
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSISCheck the operating pressuresof the refrigerant systemconnecting the gauges on hiand low service valve.
The operating pressures at theend of the freezing cycle withunit at 21ºC ambient must be:
Hi pressure (air): 8 bar(110 PSI)
Hi pressure (water): 8-9 bar(110-125 PSI)
Low pressure:Low pressure: 0-0,10-0,1bar (0-2 PSI)bar (0-2 PSI)
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSIS
The unit is OFF
with RED
LIGHT ON
steady.
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSIS
This means that
condensing
temperature rises
up to more then
70ºC.
AC 46-56-86AC 46-56-86
0
10
70
40
30
20
80
60
50
>70ºC
SERVICE ANALYSISSERVICE ANALYSIS
To restart the
operation of the
machine it is
necessary to
push and release
the reset RED
button.
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSISThe possible reasons are:
• Fan motor (air cooledversion) inoperative• No water to the water cooledcondenser (water cooledversion)
• Hi pressure control (watercooled version) inoperative
• Water inlet solenoid valve tocondenser inoperative
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSISThe possible reasons are:
• Fan motor (air cooled version)inoperative
• No water to the watercooled condenser (watercooled version)• Hi pressure control (watercooled version) inoperative
• Water inlet solenoid valve tocondenser inoperative
CLOSEDCLOSED
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSISThe possible reasons are:
• Fan motor (air cooled version)inoperative
• No water to the water cooledcondenser (water cooledversion)
• Hi pressure control (watercooled version) inoperative• Water inlet solenoid valve tocondenser inoperative
AC 46-56-86AC 46-56-86
SERVICE ANALYSISSERVICE ANALYSISThe possible reasons are:
• Fan motor (air cooled version)inoperative
• No water to the water cooledcondenser (water cooledversion)
• Hi pressure control (watercooled version) inoperative
• Water inlet solenoid valveto condenser inoperative
AC 46-56-86AC 46-56-86
A SCOTSMAN EUROPEA SCOTSMAN EUROPE presentation presentationAuthor: R. CerianiAuthor: R. Ceriani
AC 46-56-86AC 46-56-86