ABB Limited Rated voltages 245 - 550 kV Rated current 4000 A Rated breaking current up to 50 kA LTB E SF 6 circuit-breaker with Auto-Puffer™ for outdoor installation

Transcript of ABB€Limited · For export enquiries E-mail: [email protected] Internet: Publ...

Page 1: ABB€Limited · For export enquiries E-mail: pt-exports.inabb@in.abb.com Internet: Publ 1HYB800001-048 Rev.A PLEASE NOTE! ABB Ltd. is working to continuously improve the products.

ABB Limited

Rated voltages 245 - 550 kV

Rated current 4000 A

Rated breaking current up to 50 kA

LTB ESF6 circuit-breaker withAuto-Puffer� for outdoorinstallation

Page 2: ABB€Limited · For export enquiries E-mail: pt-exports.inabb@in.abb.com Internet: Publ 1HYB800001-048 Rev.A PLEASE NOTE! ABB Ltd. is working to continuously improve the products.

circuit-breaker with for

LTB E is an type circuit-breaker designed for system voltages 245 -550 kV and for rated short-circuit currents upto 50 kA. The design incorporates animproved interrupter based onexperience gained from previous interrupterdesigns.

The energy required for interrupting short-circuit currents is taken partly from the arcitself, thereby reducing the energy requiredfrom the operating mechanism by more than50 percent compared with a conventionalpuffer type circuit-breaker.

The low energy requirements result in a de-sign optimized for the low operating forceswhich in turn results in higher reliability.

All single pole operated circuit-breakers areequipped with one operating mechanism perpole. Circuit-breakers with one breaking unitper pole can be operated with one operatingmechanism per breaker.

The LTB E circuit-breaker complies with theinternational standards IEC and ANSI.

Main features and advantages

The LTB circuit-breaker family satisfies thehighest demands. It is based on latest develop-ments in dielectric dimensioning and arcresearch. Advantages are as follows:

� Restrike-free interruption of capacitive currents due to optimized contact design and movement.

� Low overvoltages when switching inductive currents due to optimum quenching at current zero.

� High dielectric strength even at atmospheric

� Long maintenance intervals due to separate current

� The circuit-breakers have passed type tests according to IEC.� Mechanical endurance tests have been performed to 10 000 operations.� Before delivery each circuit-breaker must pass routine tests in accordance with IEC and ANSI.� For each breaker a routine test report is issued showing actual test results.

Testing

The breaker pole constitutes a sealed unit, whichincludes one or two breaking unit(s), support andoperating insulators, and pole linkage housing. Tothe latter the tripping spring is attached.

To ensure the quality of the gas, each breakeris provided with a filter for moisture absorption.

Design

Auto-Puffer�

Auto-Puffer�

Auto-Puffer�

SF6

SF6

SF6

SF6

outdoor installation

SF6 pressure due to optimized contact gap.

� High security against gas leakage due todouble X-rings in all dynamic seals and doubleO-rings in static seals, verified during morethan 30 years of field operation at varying

climatic conditions. (SF6 gas loss much less than 1

percent/year.)

paths for continuous and arcing currents,respectively.

� Reliable components due to all parts optimized,aided by advanced computer technology, forelectrical and mechanical stresses.

� High seismic withstand capability due to optimizedpole and structure.

� Low noise level due to low mechanical energyrequired for operation.

� Easy installation and commisioning. Each circuit-breaker is pre-tested and shipped to erection site inform of a few pre-assembled units.

� Optional synchronized switching due tosynchronizing relay type Switchsync�.

� Optional supervisory control due to conditionmonitoring type Switchguard� / Switchcontrol�.

Page 3: ABB€Limited · For export enquiries E-mail: pt-exports.inabb@in.abb.com Internet: Publ 1HYB800001-048 Rev.A PLEASE NOTE! ABB Ltd. is working to continuously improve the products.

Technical Data

LTB245E1 420E2 420E2 550E2

Values complying with IEC 62271-100 (50 Hz), other values on request.

Number of breaks per poleRated voltagePower frequency withstand voltage (1 min):� To earth� Across open poleLightning Impulse Withstand Level (LIWL):� To earth� Across open poleSwitching Impulse Withstand Level (SIWL):� To earth� Across open poleMimimum creepage distanceRated normal currentRated breaking currentFirst pole to clear factorMaking current / peakDuration of short-circuitClosing timeOpening timeTotal break timeDead timeRated operating sequence

kV

kVkV

kVkV

kVkVmm/kVAkA

kAsmsmsmsms

1245

460460

10501050

--254000401.310034017±240300O - 0.3 sec - CO - 3 min - COAlt: CO - 15 sec - CO

2362

520450

11751175(+205)

950800(+295)254000501.312537018±240300

2420

520610

14251425(+240)

1050900(+345)254000501.312537018±240300

The circuit-breaker is operated by motor chargedspring operating mechanism, which is installed in acompact splash-proof and corrosion resistanthousing, attached to the structure.

� Three BLK 222�s are used for single pole operation at 245 kV.

� One BLG 1002A is used for three pole operation at 245 kV.

� Three BLG 1002A�s are used for single-pole operation at 420 kV.

The LTB E circuit-breaker poles are transported ascomplete units filled with gas to a slightoverpressure. Circuit-breaker poles with twobreaking units per phase are supplied as twoseparate units: breaker-head and support insulator.The circuit-breaker is routine tested in the factory.

Erection work at site can be done in less than oneday.

Filling of gas to specified working pressure isdone by using the following pressurizing equipment:

� One special control valve, for connection to the gas bottle, and a gas-filled hose with connectors.

� Gas filling can be done without gas being released into the atmosphere.

� No gas treatment is necessary before gas filling.

Operating mechanism Transport and erection

SF6

SF6

SF6

SF6

2550

620800

15501550(+315)

1175900(+450)254000501.312537018±240300

Page 4: ABB€Limited · For export enquiries E-mail: pt-exports.inabb@in.abb.com Internet: Publ 1HYB800001-048 Rev.A PLEASE NOTE! ABB Ltd. is working to continuously improve the products.

Dimensions

LTB 245E1 LTB 245E1

LTB 420 - 550E21-pole operation with BLG 1002A

J Circuit breaker

Type LTB 420E2

Type LTB 550E2

F

3105

4135

G

1914

1914

H

4882

4882

J

6541

7571

Dimensions (mm)

1-pole operation with BLK 222 3-pole operation with BLG 1002A