Abb ups conceptpower dpa_500(한글)

52
Conceptpower DPA 500 The modular UPS now up to 3 MW

description

Tier IV DataCenter UPS,3-Phase Modular UPS,100kw/Module,500kw/frame,5X6 Frame Expandable 3MW,Made in Swiss,,,,Go to Safety DataCenter

Transcript of Abb ups conceptpower dpa_500(한글)

Page 1: Abb ups conceptpower dpa_500(한글)

Conceptpower DPA 500

The modular UPS – now up to 3 MW

Page 2: Abb ups conceptpower dpa_500(한글)

© ABB

Month DD, YYYY | Slide 2

Page 3: Abb ups conceptpower dpa_500(한글)

© ABB

Month DD, YYYY | Slide 3

최소의 투자비용으로 최고의 효율과 확장성을 제공합니다.

Page 4: Abb ups conceptpower dpa_500(한글)

© ABB

Month DD, YYYY | Slide 4

최고등급의 품질

개별 확장성

모듈방식의 진정한 Online-swap

96%이상의 높은 효율

Zero downtime을 보장

완전한 전력 보안

Page 5: Abb ups conceptpower dpa_500(한글)

© ABB

Month DD, YYYY | Slide 5

내부 Redundancy와 모듈방식의 진정한 Online-swap 기능으로

Zero Downtime을 실현하였습니다.

Page 6: Abb ups conceptpower dpa_500(한글)

The Concept of a Modular UPS

Product Overview

Performance Characteristics

Mechanical Design

The 100 kW Module

Battery Configuration

User Interface, Software and Connectivity

Maintenance and Service

Applications

Conclusions

Conceptpower DPA 500

© ABB Group

Page 7: Abb ups conceptpower dpa_500(한글)

The Concept of a Modular UPS

Product Overview

Performance Characteristics

Mechanical Design

The 100 kW Module

Battery Configuration

User Interface, Software and Connectivity

Maintenance and Service

Applications

Conclusions

Conceptpower DPA 500

© ABB Group

Page 8: Abb ups conceptpower dpa_500(한글)

UPS의 궁극적인 mission:

… 무정전 전원공급으로 중요한 프로세스의 연속성을 확보, 중요부하에 깨끗한 양질의

전원공급, 가용성의 극대화.

주 프로세스의 위험도(중요도)에 따른 기반시설의 기본설계:

주변 전력 인프라에 대한 요구사항을 설정합니다.

요구되는 신뢰성과 가용성을 만족시킬 수 있는 수준을 정합니다.

합리적인 투자의 수준을 정합니다.

Why UPS is important? UPS ?

© ABB Group

UPS is the core of power infrastructure

올바른 UPS를 선택하는 것이 현장설계에서 가장 중요한 부분입니다.

Page 9: Abb ups conceptpower dpa_500(한글)

© ABB Group May 1, 2014 | Slide 9

모든 진정한 Modular system의 장점이 MW 범위까지 가능케

합니다.

대규모 데이터 센터 및 기타 고성능 애플리케이션을 위한 UPS

100 kW steps 의 확장가능한 용량

Conceptpower DPA 500 High power modular UPS

Decentralized Parallel Architecture (DPA™)

모듈방식을 통한 진정한 Redundancy로써 가장 수준 높은 가용성을 확보 할 수 있다.

Page 10: Abb ups conceptpower dpa_500(한글)

Conceptpower DPA 500

© ABB Group

Pay as you grow

성장(증설)에 따른 지불 진정한 모듈형 아키텍처로 용량 확장성 및 향후

업그레이드 가능성을 보장합니다.

Minimize the total cost of ownership

총 소유비용 (TCO)를 최소화

최대 96% 이상의 효율을 보장함은 물론 에너지 손실과

전력비용 감소의 결과로 OpEx(운영비용)을 최소화 할 수

있습니다.

Increase reliability

안정성의 증가 안정적인 이중변환 기술과 모듈의 redundancy 구조는

System Fault를 방지할 수 있게 만듭니다.

Maximize availability

가용성의 극대화

보다 더 쉽고 빠른 서비스: 온라인 상태에서의 안전한

핫스왑 가능한 모듈로써 짧은 MTTR(평균수리시간)이

가용성을 극대화합니다.

Page 11: Abb ups conceptpower dpa_500(한글)

The Concept of a Modular UPS

Product Overview

Performance Characteristics

Mechanical Design

The 100 kW Module

Battery Configuration

User Interface, Software and Connectivity

Maintenance and Service

Applications

Conclusions

Conceptpower DPA 500

© ABB Group

Page 12: Abb ups conceptpower dpa_500(한글)

Conceptpower DPA 500 DPA™ architecture .

© ABB Group

100 kW rated power module

각 모듈은 완전히 독립적으로 운전(작동)이 가능.

ABB’s Decentralized Paralleling Architecture (DPA™)

5 modules in a single DPA 500 frame

단 1.5 m² 크기에 500 kW 급 전력을 확보

모든 모듈은 서로 Full redundant 를 형성

DPA 500 frame completes the system:

각 모듈 별 전용 Bypass input breaker, battery fuse,

output isolation switch가 설치되어 있습니다.

System maintenance bypass switch(Option)를 설치

할 수 있습니다.

Single & dual 입력을 모두 지원합니다.

Top and bottom 의 cable entry 를 모두 지원합니다.

개별 배터리 설치와 Common 배터리 설치를 모두

지원합니다.

May 1, 2014 | Slide 12

Page 13: Abb ups conceptpower dpa_500(한글)

Conceptpower DPA 500 : 100 – 500 kW in one frame

© ABB Group

한 프레임에 1~5모듈을 수직으로 빠르고 쉽게 확장 할 수 있습니다.

May 1, 2014 | Slide 13

Page 14: Abb ups conceptpower dpa_500(한글)

Conceptpower DPA 500 : 100 – 3000 kW in a system

© ABB Group

6개의 프레임을 병렬로 연결하여 총 3MW 전력의 시스템을 구성할 수 있습니다.

고도의 확장성으로 인한 여러가지의 혜택 :

시스템에 용량을 추가하기 쉽다.

가용성과 안정성을 높이기 위해 Redundancy 기능을 추가하기 쉽다.

다양한 크기의 부하 세그먼트를 제공하는 표준화 UPS system 이다.

(실질적인 단위의 표준화 UPS system을 구성하기 쉽다.)

May 1, 2014 | Slide 14

Page 15: Abb ups conceptpower dpa_500(한글)

© ABB Group

Page 16: Abb ups conceptpower dpa_500(한글)

The Concept of a Modular UPS

Product Overview

Performance Characteristics

Mechanical Design

The 100 kW Module

Battery Configuration

User Interface, Software and Connectivity

Maintenance and Service

Applications

Conclusions

Conceptpower DPA 500

© ABB Group

Page 17: Abb ups conceptpower dpa_500(한글)

© ABB Group May 1, 2014 | Slide 17

– Top-of-the-line Performance

IEC/EN 62040-3 VFI-SS-111

on-line double conversion

Module 100 kW

500 kW

5 / 6

System Power 100 kW – 3 MW

Maximum power (N+1) 2.9 MW + 100kW

Output power factor 1.0

up to 96 %

>99 %

1.49 m²

(m² ) up to 335 kW/m²

( ) 975 kg

Module 55 + 54 kg (100 kW)

Input current distortion THDI < 3.5 %

Input power factor (PF) 0.99

Back-feed protection standard in each module

Technical Highlights

Page 18: Abb ups conceptpower dpa_500(한글)

Top-of-the-line Performance

© ABB Group May 1, 2014 | Slide 18

고효율에 도달 - 96% 초과

도표에서 Flat한 커브를 나타내는 것은 낮은 부하 level 에서도 높은 효율에 도달한다는 것을 의미합니다.

25% load 시 95.8% 효율

Page 19: Abb ups conceptpower dpa_500(한글)

The Concept of a Modular UPS

Product Overview

Performance Characteristics

Mechanical Design

The 100 kW Module

Battery Configuration

User Interface, Software and Connectivity

Maintenance and Service

Applications

Conclusions

Conceptpower DPA 500

© ABB Group

Page 20: Abb ups conceptpower dpa_500(한글)

작은 공간을 차지하는 아주 컴팩트 한 디자인

설치 공간 = 1.49 m²; 전력 밀도 (500 kW) = 335 kW/m²

가벼운 무게 프레임(모듈 설치 전) = 430 kg; 모듈을 모두 설치했을 경우 (500kW) = 975 kg

Top / bottom cable entry 및 전면에서 수리 가능

Single & dual 입력을 모두 제공

개별 배터리 설치와 Common 배터리 설치를 모두 지원

Terminal bus-bars 주위에 넉넉한 공간을 확보 – 작업이 용이하며 안전성 확보

Smart한 module의 구조설계로 보다 쉬운 추가설치 및 교체 가능

모듈의 추가설치 및 교체가 쉽도록 Active 모듈과 Passive 모듈로 분리하여 무게를 줄임

active module = 55 kg, passive module = 54 kg

프레임 단위로 MBS 설치 (optional)

Conceptpower DPA 500 Mechanical construction highlights

© ABB Group

Page 21: Abb ups conceptpower dpa_500(한글)

Conceptpower DPA 500 All included

© ABB Group May 1, 2014 | Slide 21

프레임당 최대 5 x 100 kW online hot

swappable DPA UPS modules

각 모듈 별 전용 Bypass input breaker,

battery fuse, output isolation switch

입/출력 Top 또는 Bottom cable entry

(표준제공)

Single 또는 dual 입력 가능(표준제공)

Common 또는 separate battery

connection

Maintenance bypass switch (optional)

Communications interface

각 모듈 별 독립 Display

System display

Page 22: Abb ups conceptpower dpa_500(한글)

Frame - Mechanical Construction Compact and front serviceable

Front Back

May 1, 2014 | Slide 22

1.5 m2 의 설치면적의 Compact 하고 공간을 절약할 수 있는 프레임

전면 부에서 설치 및 서비스 모두 수행 가능 !

Page 23: Abb ups conceptpower dpa_500(한글)

High power density = 335 kW/m2

Frame - Mechanical Construction

크기 (mm)

Width = 1580

Height = 1975

Depth = 940

1.5 m2 footprint!

Frame weight < 500kg

여유공간 (mm)

Front 900 mm

Back 200 mm (air outlet)

Page 24: Abb ups conceptpower dpa_500(한글)

Frame - Mechanical Construction Cable entry

May 1, 2014 | Slide 24

© ABB Group

Bottom entry

Top entry

Page 25: Abb ups conceptpower dpa_500(한글)

Frame - Mechanical Construction Top entry

May 1, 2014 | Slide 25

© ABB Group

Top view

Page 26: Abb ups conceptpower dpa_500(한글)

Frame - Mechanical Construction Bottom entry

May 1, 2014 | Slide 26

© ABB Group

Bottom view

Page 27: Abb ups conceptpower dpa_500(한글)

The Concept of a Modular UPS

Product Overview

Performance Characteristics

Mechanical Design

The 100 kW Module

Battery Configuration

User Interface, Software and Connectivity

Maintenance and Service

Applications

Conclusions

Conceptpower DPA 500

© ABB Group

Page 28: Abb ups conceptpower dpa_500(한글)

Conceptpower DPA 500 – Electrically Double Conversion True Modular UPS

May 1, 2014 | Slide 28

© ABB Group

= =

= =

Bypass input

Critical

Load

Rectifier input

100kW UPS Module

100 kW UPS . :

IGBT rectifier and inverter

Control logic and display

Battery converter

Static bypass switch

Inbuilt back-feed protection

Page 29: Abb ups conceptpower dpa_500(한글)

Module - Mechanical Construction Very compact

May 1, 2014 | Slide 29

© ABB Group

Dimensions, H x W x D = 178(4HU) x 710 x 750 mm

Active Module Weight 55 kg Passive Module Weight 54 kg

- Rectifier, booster, inverter,

- Battery charger

- Logic control

- User interface (DPA mimic diagram +

display)

- Static bypass switch

- Input and output filters

- Back-feed protection

- Output contactor

100 kW module (Active Passive )

.

Page 30: Abb ups conceptpower dpa_500(한글)

Module - Mechanical Construction Front and Back View

May 1, 2014 | Slide 30

© ABB Group

Front Back

견고한 디자인

강하고 실용적인 손잡이

오류 방지 : 모듈의 On-line hot swap이 가능한 스마트 콘넥터는 잘못된

위치에 모듈이 장착되는 오류를 방지해 줍니다.

Page 31: Abb ups conceptpower dpa_500(한글)

The Concept of a Modular UPS

Product Overview

Performance Characteristics

Mechanical Design

The 100 kW Module

Battery Configuration

User Interface, Software and Connectivity

Maintenance and Service

Applications

Conclusions

Conceptpower DPA 500

© ABB Group

Page 32: Abb ups conceptpower dpa_500(한글)

유연한 Battery의 구성

Battery(Block - 12V 단위) 는 40~50blocks 중 선택가능

정확히 일치하는 크기로 Battery 용량을 선택

UPS교체 시 이전에 사용하던 Battery를 재사용 가능

가장 일반적인 Battery 백업시간의

표준 구성 (모듈 별 Battery 구성)

The line-and-match battery cabinet supports

2x50x28Ah 5-6 min @ 100 kW load

3x40x28Ah 8-9 min @ 100 kW load

Longer autonomies supported thanks to the strong

battery charger (up to 60A charging capacity at full

100% nominal load)

Separate와 common battery 적용을

모두 지원

Separate battery 구성은 전체 모듈 각각의 Battery를

설치 함으로써 Full redundancy 기능을 가짐

Common battery 구성은 경제적인 Battery 선택 설치가

가능함으로 설치 비용절감

Conceptpower DPA 500

© ABB Group

Page 33: Abb ups conceptpower dpa_500(한글)

© ABB Group May 1, 2014 | Slide 33

Options Battery cabinet

각 Battery cabinet은 각 100kW모듈에 대해 8-9분의 Backup time으로 구성가능

Page 34: Abb ups conceptpower dpa_500(한글)

Conceptpower DPA 500

© ABB Group

The Concept of a Modular UPS

Product Overview

Performance Characteristics

Mechanical Design

The 100 kW Module

Battery Configuration

User Interface, Software and Connectivity

Maintenance and Service

Applications

Conclusions

Page 35: Abb ups conceptpower dpa_500(한글)

System Display Graphical Touchscreen Display

Month DD, Year | Slide 35

© ABB Group

확실하고 선명한 시스템 개요, 측정치 및 시스템 상태

모듈 단위 별로 측정치 및 상태를 탐색 가능

System level commands

특 징

7‘‘ 터치스크린 조작 패널

대화형 Mimic diagram

컬러 그래픽 디스플레이

Alarm 표시 및 Buzzer 기능

13개국 언어 선택

확장 이벤트 로고 (1000개 이벤트)

Page 36: Abb ups conceptpower dpa_500(한글)

System Display Graphical Touchscreen Display

Month DD, Year | Slide 36

© ABB Group

System status

Time Date

Parallel/single

Access to module

level

Status of system

Quick access to service,

operation and

information menus

Quick access to

mimic diagram

Direct access zones

to specific menus

Page 37: Abb ups conceptpower dpa_500(한글)

System Display

Month DD, Year | Slide 37

© ABB Group

Alarms and events log

UPS measurements

UPS commands UPS information

User setup

Service setup

Page 38: Abb ups conceptpower dpa_500(한글)

Line-and-match battery cabinets

Maintenance bypass switch

:

SNMP cards

Sensor adapters

Relay card

(Wooden box)

Conceptpower DPA 500 Options and accessories

© ABB Group

http://librex.co.uk/media/catalog/product/cache/1/image/5e06319eda06f020e43594a9c230972d/c/d/cd55.jpg_clipped_1_1.jpg

NETWORK INTERFACE CARD, SOFTWARE

AND ENVIRONMENTAL SENSORS

Page 39: Abb ups conceptpower dpa_500(한글)

Connectivity

© ABB Group

May 1, 2014 | Slide 39

LAN

Shutdown service

Several

protocols

Web browser, Remote View, BMS

DATA PROTECTION - CLIENT DATA MONITORING AND MANAGEMENT

E-mails

NETWORK INTERFACE CARD

AND SOFTWARE

ENVIRONMENTAL SENSORS UPS

SMS

Options and possibilities

Page 40: Abb ups conceptpower dpa_500(한글)

The Concept of a Modular UPS

Product Overview

Performance Characteristics

Mechanical Design

The 100 kW Module

Battery Configuration

User Interface, Software and Connectivity

Maintenance and Service

Applications

Conclusions

Conceptpower DPA 500

© ABB Group

Page 41: Abb ups conceptpower dpa_500(한글)

유지보수 및 서비스를 위한 Modula 개념의 혜택

차별화된 품목과 최대한의 Spare parts 재고 보유

표준화된 서비스 매뉴얼 및 방법

Human errors에 대한 리스크를 최소화

ABB의 Online hot swappable modules 과 UPS 서비스 :

모듈을 통째로 Online 상태에서 교체하여 시스템 정지 없이 운전 중 예방 정비

모듈을 통째로 Online 상태에서 교체하여 시스템 정지 없이 운전 중수리

DPA 500 프레임의 기계적 설계는 효율적이고 안전한 서비스를 제공

예방 정비와 서비스를 전면에서 모두 수행 할 수 있음

Smart connectors 는 모듈의 안전한 취급을 보장

Conceptpower DPA 500

© ABB Group

UPS 시스템은 표준화된 서비스 개념을 도입하여 운전자 교육을 표준화 간소화

할 수 있습니다.

Page 42: Abb ups conceptpower dpa_500(한글)

The Concept of a Modular UPS

Product Overview

Performance Characteristics

Mechanical Design

The 100 kW Module

Battery Configuration

User Interface, Software and Connectivity

Maintenance and Service

Applications

Conclusions

Conceptpower DPA 500

© ABB Group

Page 43: Abb ups conceptpower dpa_500(한글)

Conceptpower DPA 500 는 다음을 위해 특별히

설계되었습니다.

Large datacenters

Mid-sized datacenters

Server rooms and other IT applications

Healthcare

Industry automation processes

Other critical applications

Conceptpower DPA 500

© ABB Group

Page 44: Abb ups conceptpower dpa_500(한글)

Conceptpower DPA 500 .

© ABB Group

Modular 개념의 확장성은 여러 가지 종류와 크기의 데이터

센터에 대해 사용자가 다음과 같이 선택할 수 있다 :

각 데이터 센터 또는 각 부하의 종류에 따라 필요한 Solution을

최적화 할 수 있습니다.

간단하고 표준화된 전원보호 개념을 통하여 시스템의 가용성과

에너지 절감효과를 증가시킬 수 있습니다.

간소하고 단순한 서비스 개념으로 오류에 대한 가능성을 최소화

하고 효율적으로 비용을 절감 하며 가용성을 극대화 할 수 있습니다. Small or big

… growing … modular

Page 45: Abb ups conceptpower dpa_500(한글)

Conceptpower DPA 500

.

크고 다양한 여러 가지 어플리케이션에 적용하기

위한 기본적인 블록 개념의 UPS 모듈입니다.

Page 46: Abb ups conceptpower dpa_500(한글)

Datacenter Application – End-of-row

© ABB Group

통상적인 One-rack-row의 전력 수요는 20kW 에서 평균 수 백 kW 까지 변화할 수 있습니다.

Modula UPS 만이 이와 같은 성장 인프라의 전력 수요 변화 에 따른 UPS 용량의 쉽고 빠른

대응(용량 증설) 이 가능합니다.

Page 47: Abb ups conceptpower dpa_500(한글)

Datacenter Application – End-of-row Tier IV

© ABB Group

TIER IV는 분산(de-centralized)

전원보호 개념을 사용하여 구축 :

전력 수요는 500kW 에서 부터 최대

3 MW까지 크게 달라질 수 있습니다.

Modula UPS 만이 이와 같은 변화

하는 인프라의 전력 수요 변화 에 따라

쉽고 빠르게 대응(UPS용량 증설) 이

가능합니다

Page 48: Abb ups conceptpower dpa_500(한글)

Conceptpower DPA 500 – Tier IV

© ABB Group

Stage 1 – 4x300kW (A and B feeds)

Stage 2 – 6x500kW (A and B feeds)

May 1, 2014 | Slide 48

전력 수요는 500kW 에서 부터 최대 3 MW까지 크게 달라질 수 있습니다.

Modula UPS 만이 이와 같은 변화 하는 인프라의 전력 수요 변화 에 따라 쉽고 빠르게

대응(UPS용량 증설) 이 가능합니다

Page 49: Abb ups conceptpower dpa_500(한글)

The Concept of a Modular UPS

Product Overview

Performance Characteristics

Mechanical Design

The 100 kW Module

Battery Configuration

User Interface, Software and Connectivity

Maintenance and Service

Applications

Conclusions

Conceptpower DPA 500

© ABB Group

Page 50: Abb ups conceptpower dpa_500(한글)

Conceptpower DPA 500 Modular UPS

© ABB Group

Right-sizing 조정방법과 확장성의 결합,

쓰는 만큼 지불하는 Pay-as-you-grow solution으로 자본비용을

절감하고 활용도를 증가 시킵니다.

Modula UPS의 혁신적인 기술은 다른 중요한 장비를 위한 공간을

확보하고 최대 전력밀도를 가능케 합니다.

전기 및 물리적 모듈방식은 최소한의 엔지니어링과 빠른 설치를

제공합니다..

동일한 제품과 기본 기술은 각 데이터 센터와 각 부하 구분의 목적에

맞게 적절히 선택 될 수 있다.

모듈 형 구조 설치를 통해 간단하고 표준화된 전원 보호개념 과

서비스 개념을 구현 할 수 있습니다.

On-line hot swappable 모듈 방식은 계획된 또는 계획되지 않은

일정의 Down time을 최소화 할 수 있음을 보증합니다.

자본 투자의 최적화 와 절감

배치 속도의 가속

서비스 및 유지보수의 비용과

복잡성을 감소

운전 비용의 감소

에코모드에서 99% 와 이중변환에서 96% 의 높은 효율은 이전 세대의

UPS와 비교하여 약 40%이상 운영 비용을 줄일 수 있습니다.

가용성의 증가와 부하 가동시간의 결과에 따른 활용도의 증가를 기대

할 수 있습니다.

Page 51: Abb ups conceptpower dpa_500(한글)

Conceptpower DPA 500 –

© ABB Group

고 가용성 – Zero down time

• 내결함성 DPA 아키텍처로 진정한 Redundancy

를 구성

• Online hot Swappable Modules (OSM) 로

빠르고 쉬운 유지보수 및 수리 가능

• 진정한 확장성; 유연한 UPS 전원의 Upgrades 와

Downgrades (100kW 단위)

전체 비용의 최소화 (TCO)

• Modular architecture: 최적화 된 초기 투자

– Pay as you grow (성장에 따른 지불)

• 컴팩트한 크기와 작은 설치 공간

• 높은 이중변환 효율 96% (Eco-Mode >99%)로

에너지 손실을 최소화

• 운전 중 동시에 가능한 쉽고 빠른 유지보수

수평 확장성 : 캐비닛의 병렬 연결로 최대

용량 3 MW 까지 확장 할 수 있다.

수직 확장성 :

하나의 캐비닛에

1모듈에서

5모듈까지 설치할

수 있다.

Page 52: Abb ups conceptpower dpa_500(한글)

© ABB Group May 1, 2014 | Slide 52

서울시 금천구 가산디지털 2로 165 (가산동)

백상스타타워 2차 10층 1007호

Tel:(02)6264-7889, Fax:(02)6264-7886

㈜지엠시스텍