ABB (Entrelec) Surge Protectors

Transcript of ABB - Relay Specialties, Inc. (Entrelec) Surge Protectors . ... - Protection in common mode and in...

ABB

(Entrelec)

Surge Protectors

SURGE PROTECTOR SYMBOLS

622

SPS 6/24 0020 369.14SPS 3/220 0020 293.21

NF10016 010103

Characteristics

Part number Type P/N Type P/N

Accessories, marking, wire size : see Accessories section.

Approvals (Contact Entrelec)

Surge protection unitSPS 3/220

3 A - 220 V AC/DC

Spacing 48.5 mm 1.91"

surge in common mode surge in differential mode

1060 V 1080 V

700 V 750 V

500 V 650 V

450 V 600 V

430 V 530 V

Surge protection unitSPS 6/24

6 A - 24 V AC/DC

Spacing 48.5 mm 1.91"

Protection modules

Surge protection unitsSeries 20 000

DIN 1 - 3

surge in common mode surge in differential mode

318 V 376 V

202 V 252 V

112 V 142 V

57 V 94 V

21 V 68 V

Designed for use on low voltage networks in an industrial environment, Entrelec SPS products are compatible with isolated orimpedance grounded neutral networks.Doubled terminals, wire size of each terminal 2,5 mm2 14 AWG.

Wave flow currentTest carried out with hybrid generator6 kV / 3 kA impedance 2 ΩHigh wire size connection(1.2 / 50 µs - 8 / 20 µs wave)

5 surges of 3 kA

10 surges of 2.5 kA

20 surges of 2 kA

100 surges of 1 kA

103 surges of 600 A

104 surges of 250 A

Peak voltage on output in differential mode in volts

623

SPS 6/110 0020 292.20 SPS 6/220 0020 291.27

NF10017 010103

Accessories, marking, wire size : see Accessories section.

Approvals (Contact Entrelec)

Characteristics

Part number Type P/N Type P/N

Wave flow currentTest carried out with hybrid generator6 kV / 3 kA impedance 2 ΩHigh wire size connection(1.2 / 50 µs - 8 / 20 µs wave)

5 surges of 3 kA

10 surges of 2.5 kA

20 surges of 2 kA

100 surges of 1 kA

103 surges of 600 A

104 surges of 250 A

surge in common mode surge in differential mode

1340 V 1080 V

800 V 700 V

600 V 500 V

550 V 450 V

520 V 420 V

surge in common mode surge in differential mode

1350 V 980 V

1060 V 780 V

900 V 650 V

850 V 600 V

800 V 550 V

Designed for use on low voltage networks in an industrial environment, Entrelec SPS products are compatible with isolated orimpedance grounded neutral networks.Doubled terminals, wire size of each terminal 2,5 mm2 14 AWG.

Peak voltage on output in differential mode in volts

Surge protection unitSPS 6/220

6 A - 220 V AC/DC

Surge protection unitSPS 6/110

6 A - 110 V AC/DC

Protection modules

Surge protection unitsSeries 20 000

DIN 1 - 3Spacing 48.5 mm 1.91" Spacing 48.5 mm 1.91"

624

SPS 10/3 x 380 0020 368.13

NF10018 010103

Characteristics

Part number Type P/N Type P/N

Accessories, marking, wire size : see Accessories section.

Approvals (Contact Entrelec)

Surge protection unitSPS 10/3 x 380

10 A - 3 x 380 V AC

Spacing 48.5 mm 1.91"

Protection modules

Surge protection unitsSeries 20 000

DIN 1 - 3

Designed for use on low voltage networks in an industrial environment, Entrelec SPS products are compatible with isolated orimpedance grounded neutral networks.Doubled terminals, wire size of each terminal 2,5 mm2 14 AWG.

Wave flow currentTest carried out with hybrid generator6 kV / 3 kA impedance 2 ΩHigh wire size connection(1.2 / 50 µs - 8 / 20 µs wave)

5 surges of 3 kA

10 surges of 2.5 kA

20 surges of 2 kA

100 surges of 1 kA

103 surges of 600 A

104 surges of 250 A

surge in common mode surge in differential mode

920 V 1420 V

840 V 1260 V

700 V 1180 V

594 V 960 V

495 V 720 V

Peak voltage on output in differential mode in volts

625

Page

627

626

628

627

626

627

628

627

626

627

NF10020 010103

ANALOG

ANALOG

TELEPHONE

TELEPHONE

NETWORKS

NETWORKS

SERIAL

LINKS

Entrelec productsEntrelec productsNetworks or ApplicationsNetworks or Applications

APPLICATION OF "DATA"

PRODUCTS

APPLICATION OF "DATA"

PRODUCTS

RS232C (V24) DATA PU3-200 12V 0008 030.01

DATA PU1-200 12V 0008 032.27

RS422-485 (V11) DATA PU5-200 5V 0008 041.00

Current loop DATA PU3-200 24V 0008 037.24

DATA PU1-200 24V 0008 033.20

Profibus (500 kBits/S) DATA PU3-200 5V 0008 029.04

Interbus-S DATA PU5-200 5V 0008 041.00

DATA PU4-200 240V 0008 040.13

Loop 0/4-20 mA DATA SP BE/C

0-10 V DATA PU1-200 12V 0008 032.27

DATA PU3-200 12V 0008 030.01

SERIAL

lINKS

626

PRT 0008 001.01 PRT 0008 001.01

NF10024

DATA PU1-200 5 V DC 0008 031.26DATA PU1-200 12 V DC 0008 032.27DATA PU1-200 24 V DC 0008 033.20DATA PU1-200 48 V DC 0008 034.21

010103

DATA PU2-200 0008 035.22DATA PU2-200 0008 036.23

BJS9 0177 583.12BJS9 0177 584.13

BJS9 0177 583.12BJS9 0177 584.13

Surge protection unitDATA PU1 - 200

5 to 48 V DC

Spacing 9 mm .354"

Surge protection unitDATA PU2 - 200

110 to 240 V AC

Spacing 9 mm .354"Protection modulesSurge protection unitsSeries 8 000

DIN 1 - 3

Front connection

Input Output Input Output

Front connection

Rated voltage Vn

Max. voltage VC

Max. current INMax. upstream fuseWave flow current

(test conducted with a 20 kV / 10 kA hybrid generator)(1.2 / 50 µs - 8 / 20 µs wave)

Response frequency - 1 dB

Serial / Line resistancePeak voltage on output = protection

level Vp 6 kV / 3 kA1 kV / µs

Tightening torque on front connection (Nm)Degree of protection

TEMPERATUREAmbient temperature

StorageOperating

5 V DC 12 V DC 24 V DC 48 V DC7 V DC 15 V DC 28 V DC 55 V DC

0.2 A0.2 A

5 x 10 kA surges10 x 2.5 kA surges20 x 2 kA surges100 x 1 kA surges103 x 600 A surges104 x 250 A surges

1 MHz / 150 Ω

10 Ω

< 25 V < 60 V < 100 V < 200 V< 10 V < 20 V < 40 V < 80 V

0.4 min. / 0.6 max.IP20

- 40°C to + 80°C- 20°C to + 50°C

110 to 130 V AC 220 to 240 V AC150 V AC 265 V AC

0.2 A0.2 A

5 x 5 kA surges10 x 2.5 kA surges20 x 2 kA surges100 x1 kA surges

103 x 600 A surges104 x 250 A surges

1 MHz / 150 Ω

10 Ω

< 400 V < 800 V< 280 V < 500 V

0.4 min. / 0.6 max.IP20

- 40°C to + 80°C- 20°C to + 50°C

- The use of a PRT and BJS jumper bar will provide an easyjumping method for ground connections. The PRT provides4 screw terminal connections for ground connections.

Front connection

- The use of a PRT and BJS jumper bar will provide an easyjumping method for ground connections. The PRT provides4 screw terminal connections for ground connections.

8 poles16 poles

- Protection of an active wire in relation to ground between"ZONE 1" and "ZONE 2"

- DC voltage.- Cascade protection in common mode by discharger,

power resistor, zener.- Ground connection on front using a simple jumper bar.

- Protection of an active wire in relation to ground between"ZONE 1" and "ZONE 2"

- AC voltage.- Cascade protection in common mode by discharger in series

with varistor, power resistor, zener.- Ground connection on front using a simple jumper bar.

Characteristics

Part numbers Type P/N Type P/N

Accessories, marking, wire size : see Accessories section.

Approvals (Contact Entrelec)

Front connection

110 to 130 V AC220 to 240 V AC

8 poles16 poles

627

PRT 0008 001.01PRT 0008 001.01

NF10025

DATA PU3-200 5 V DC 0008 029.04DATA PU3-200 12 V DC 0008 030.01DATA PU3-200 24 V DC 0008 037.24DATA PU3-200 48 V DC 0008 038.05

010103

BJS9 0177 583.12BJS9 0177 584.13

BJS9 0177 583.12BJS9 0177 584.13

DATA PU4-200 0008 039.06DATA PU4-200 0008 040.13

110 to 130 V AC220 to 240 V AC

Surge protection unitDATA PU3 - 200

5 to 48 V DC

Protection modulesSurge protection unitsSeries 8 000

DIN 1 - 3

Spacing 9 mm .354"

Surge protection unitDATA PU4 - 200

110 to 240 V AC

Input Output

Frontconnection

Spacing 9 mm .354"

Input Output

8 poles16 poles

- Protection of two active wires in relation to ground between"ZONE 1" and "ZONE 2".

- DC voltage.- Protection in common mode and in differential mode by

discharger, power resistor, zener.- Ground connection on front using a simple jumper bar.

Frontconnection

- Protection of two active wires in relation to ground between"ZONE 1" and "ZONE 2".

- AC voltage.- Protection in common mode and in differential mode by

discharger in series with varistor, power resistor, zener.- Ground connection on front using a simple jumper bar.

Rated voltage Vn

Max. voltage VC

Max. current INMax. upstream fuseWave flow current

(test conducted with a20 kV / 10 kA hybrid generator)(1.2 / 50 µs - 8 / 20 µs wave)

Response frequency - 1 dB

Serial / Line resistancePeak voltage on output = protection

level Vp 6 kV / 3 kA1 kV / µs CM1 kV / µs DM

Tightening torque on front connection (Nm)Degree of protection

TEMPERATUREAmbient temperature

StorageOperating

5 V DC 12 V DC 24 V DC 48 V DC7 V DC 15 V DC 28 V DC 55 V DC

0.2 A0.2 A

5 x 10 kA surges10 x 2.5 kA surges20 x 2 kA surges100 x1 kA surges

103 x 600 A surges104 x 250 A surges

1 MHz / 150 Ω

10 Ω

< 25 V < 60 V < 100 V < 200 V< 10 V < 20 V < 40 V < 80 V< 20 V < 40 V < 80 V < 160 V

0.4 min. / 0.6 max.IP20

- 40°C to + 80°C- 20°C to + 50°C

110 to 130 V AC 220 to 240 V AC150 V AC 265 V AC

0.2 A0.2 A

5 x 5 kA surges10 x 2.5 kA surges20 x 2 kA surges100 x1 kA surges

103 x 600 A surges104 x 250 A surges

1 MHz / 150 Ω

10 Ω

< 400 V < 800 V< 280 V < 500 V< 560 V < 1000 V

0.4 min. / 0.6 max.IP20

- 40°C to + 80°C- 20°C to + 50°C

Front connectionFront connection

Accessories, marking, wire size : see Accessories section.

Approvals (Contact Entrelec)

Characteristics

Part number Type P/N Type P/N

- The use of a PRT and BJS jumper bar will provide an easyjumping method for ground connections. The PRT provides4 screw terminal connections for ground connections.

- The use of a PRT and BJS jumper bar will provide an easyjumping method for ground connections. The PRT provides4 screw terminal connections for ground connections.

8 poles16 poles

628

DATA PU5-200 5 V DC 0008 041.00

PRT 0008 001.01

NF10026 010103

BJS9 0177 583.12BJS9 0177 584.13

Surge protection unitDATA PU5 - 200

5 V DC

Protection modulesSurge protection unitsSeries 8 000

DIN 1 - 3

Spacing 9 mm .354"

- The use of PRT and BJS jumper bar will provide an easyjumping method for ground connections. The PRT provides 4screw terminal connections for ground connections.

8 poles16 poles

- Protection of two active wires in relation to ground between"ZONE 1" and "ZONE 2" - DC voltage.

- Protection in common mode and in differential mode bydischarger, power resistor, zener.

- Ground connection on front using a simple jumper bar.- Addition of a 6.8 V transorb in differential mode for 5 V

application (RS 422/485).

InputOutput

Frontconnection

Rated voltage Vn

Max. voltage VC

Max. current INMax. upstream fuseWave flow current

(test conducted with a 20 kV / 10 kAhybrid generator)(1.2 / 50 µs - 8 / 20 µs wave)

Response frequency - 1 dB

Serial / Line resistancePeak voltage on output = protection

level Vp 6 kV / 3 kA1 kV / µs CM

1 kV / µs DMTightening torque on front connection (Nm)Degree of protection

TEMPERATUREAmbient temperature

StorageOperating

24 V in CM 5 V in DM28 V in CM 5.8 V in DM

0.2 A0.2 A

5 x 10 kA surges10 x 2.5 kA surges20 x 2 kA surges100 x 1 kA surges103 x 600 A surges104 x 250 A surges

1 MHz / 150 Ω

10 Ω

< 13.4 V< 40 V< 10 V

0.4 min. / 0.6 max.IP20

- 40°C to + 80°C- 20°C to + 50°C

Front connection

Characteristics

Part number Type P/N

Accessories, marking, wire size : see Accessories section.

Approvals (Contact Entrelec)

Type P/N

629

NF10027

PU1 12 V DC 0010 620.02PU1 24 V DC 0010 621.27PU1 48 V DC 0010 622.20PU1 60 V DC 0010 623.21

010103

PU3 12 V DC 0010 627.25PU3 24 V DC 0010 628.06PU3 48 V DC 0010 629.07PU3 60 V DC 0010 630.04

28,51.12"

33,51.32"

62 2.44"

652.

56"

72,5

2.85

"

702.

75"

GEHF

B DA C

Protection modulesSurge protection unitsSeries 10 000

DIN 1 - 3

Characteristics

Part number Type P/N Type P/N

Accessories, marking, wire size : see Accessories section.

Approvals (Contact Entrelec)

Surge protection unitPU1

12 to 60 V DCSpacing 23 mm .906"

- Double Π protection of an active wire in relation to ground.- Cascade protection in common mode by discharger, mov,

varistor, mov, zener.- High energy protection :

. control voltages

. PLC outputs.

Surge protection unitPU3

12 to 60 V DCSpacing 23 mm .906"

Input Output

- Double Π protection of two active wires in relation to ground.- Protection in common mode by discharger, mov, varistor.- Protection in differential mode by varistor, mov, zener.- High energy protection :

. control voltages

. PLC outputs.

Input Output

Rated voltagee ± 10%

Rated current

Wave flow current(test conducted with a6 kV / 3 kA hybrid generator)(1.2 / 50 µs - 8 / 20 µs wave)

Max. voltage for a disturbing input voltageof 1 kV/µs :

U A-DU D-groundU A-ground

Transmission frequency

Response time for an outputvoltage on :

A-B/D-CD-ground

TEMPERATUREAmbient temperature

StorageOperating

12 V DC 24 V DC 48 V DC 60 V DC

1 A

10 kA

≤ 1.7 V rated

20 kHz / 50 Ω

0.1 ns

- 40°C to + 80°C- 20°C to + 60°C

12 V DC 24 V DC 48 V DC 60 V DC

1 A

10 kA

≤ 1.7 V rated≤ 2 V rated

20 kHz / 50 Ω

0.1 ns100 ns

- 40°C to + 80°C- 20°C to + 60°C

center of rail

630

IECNFC DIN UL CSA

IECNFC DIN UL CSA

M 4/9.PE.90

8,5 mm 4 mm 0,4-0,6 Nm IP 20.33" 3.5-5.3 Ib.in NEMA 1

75 V90 V105 V730 V

70 V50 V5 kA

5 A (1s, 50 Hz)≈ 1 pF10 V75 V

0,2-4 mm²0,22-4 mm²

264 mm² / A4

0,5-4 mm²0,5-2,5 mm²

250 V (3) / 400 V (4)4 kV

3

10 mm IP 00.39"

2,5 mm²

17

M 2,5/14.S.H.2

M 4/9.PE.90 0007 028.22

BNS 14.1E

me1 e2 me1 e2

BNS 14.2E

NF10032 010103

M 2,5/14.S.H.2 0199 291.24M 2,5/14.S.H.2 0199 292.25

BNS 14.1E 0199 294.27

BNS 14.2E 0199 297.22

280 V(3) 1275 V (3)350 V(3) 1500 V (3)420 V(3) 1725 V (3)

≤ 1000 V (3) 3500 V (3)

260 V 1150 V (5)180 V 800 V (5)

10 kA (3) 15 kA (3)

10 A (1s, 50 Hz) 5 A (1s, 50 Hz)≤ 5 pF 2 pF≤ 35 V 10 V80 V 80 V

65,52.58"

38 1.50"33 1.30"

64,5

2.54

"

59,7

2.35

"67 2.64

"

AL2 (1) 0163 070.00AL3 (1) 0163 261.00DCG 0163 218.05FC2 0007 865.26BJS9 (1)(2) 0177 583.12BJS9 (1)(2) 0177 584.13EV6D (1)(2) 0168 400.16

AD2,5 0114 205.20

11

Characteristics

Electroniccomponent holderterminal blocksBlocks with gas dischargerCompression clampSolder to solder

DIN 1 - 3

Terminal block with removable plug fitted with gas discharger.Plug available separately.

Color Type P/N Color Type P/N

BAMH th. 9,1 mm 0114 836.00BADLV0 th. 9,0 mm 0199 408.02BAM th. 9,1 mm 0103.002.26PR1Z2 32 x 15 x 1,5 0163 050.04PR3Z2 35 x 7,5 x 1 0174 300.17PR4 35 x 15 x 2,3 0168 500.12PR5 35 x 15 x 1,5 0168 700.22Other rails : See Accessories sectionOther accessories : See Accessories section

Static priming voltage min.nominalmax.

Dynamic priming voltage(1 kV / µs)Max. operating voltage

DCAC

Discharge shock current(8 / 20 µs wave)AC discharge currentCapacity pFResidual voltage with stable arcVoltage with discharge

Rated current ARated wire size

Rated voltage

Wiresize

Screw

Soldered

NominalPulsePollution degree

NominalNominal / Gauge

Accessories Type Part number

Other characteristics Wire stripping Recommended Recommended Protectionlength screwdriver torque

Wire stripping Recommended Recommended Protectionlength screwdriver torque

Type Part number

2 Test socket

3 Test device4 Test plug5 Jumper bar (not preassembled)

6 Sub-assembly for jumper bar(screw+washer+post))

7 IDC JumperR See section on Markers

Marking

Spacing 14 mm .551"

Plug with 1 discharger Plug with 2 dischargers

Note: if the current immediately after triggeringis greater than 1 A (peak), install a protectivedevice able to reduce the fault current

Block only (without plug) :Beige V0Red V0

Plug fittedwith 1 dual discharger, 350 VBeige V0with 2 dischargers, 1500 VRed V0

Characteristics

Solid wireStranded wireSolid wireStranded wire

center of rail

DIA. 2.0 mmDIA. 3.0 mm

greyDIA. 2.0 mm

8 poles16 poles

(1) These accessories can be used on the lower connection only. (2) Use of these accessories requires the user to cut out the partition.(3) Between e1-m or e2-m. (4) Between e1-e2. (5) Voltage for component. For max. voltage, refer to rated voltage of the partition.

M 4/9 block equipped with a 3 mm end plate and a gasdischarger between two decks.

Spacing 9 mm .354"

Grey

max. max.

center of rail

631

NFC DIN UL CSANFC DIN UL CSA

33,3 36,864,6 71,4

D 4/6.PZ.../... D 4/6.PZ.../...

D 4/6.PZ 48/24 24 V AC 0007 034.10

FEM 6 0103 125.15

11

FEM 6 0103 125.15

11

9,5 mm 4 mm 0,5-0,8 Nm IP 00.37" 4.4-7.1 Ib.in

9,5 mm 4 mm 0,5-0,8 Nm IP 00.37" 4.4-7.1 Ib.in

0,2-4 mm²

0,22-4 mm²

0,2-4 mm²

0,22-4 mm²

(pF)

625D 4/6.PZ 24/15D 4/6.PZ 48/24

VRM(V)30

58,1

IRM(µA)

35

DC (V) AC (V)24 1548 24

10/1000 µs 8/20 µsVCL (V) Ipp (A) VCL (V) Ipp (A)

48,4 10,392 6,5 121 59,5

D 4/6.PZ 24/15 24 V DC 0007 035.11D 4/6.PZ 48/24 48 V DC 0007 034.10

T01124 010103

BADL 0199 408.02

35 x 7,5 x 1PR4 35 x 15 x 2,3 0168 500.12

35 x 15 x 1,5

~=

th. 9,0 mmOther end stop : See Accessories sectionPR3Z2 0174 300.17

PR5 0168 700.22Other rails : See Accessories sectionOther accessories : See Accessories section

~=

Characteristics

Type P/N Type P/N

Green body

Spring-loaded rail contact

Green body

Spring-loaded rail contact

Spacing 6 mm .236"Spacing 6 mm .236"

Note : Given for 600 W in 10/1000 µs and 7,2 kW in 8/20 µs.

Electronic componentholder terminal blocksWith transzorbCompression clamp

DIN 3

Breakdown voltageVRB (V) I=1mA

mini. maxi.

DC AC

CapacitanceTypeStand-offvoltage

Leakagecurrent

Maximum surge currentClamping voltage

Characteristics

Accessories

Rated current ARated wire size

Other characteristics

Wire size

1 End section green

R See section on markersmarking method

Rated voltage V

Compression Solid wire

clamp Stranded wire

Type P/N Type P/N

Wire stripping Recommended Recommended Protectionlength screwdriver torque

Wire stripping Recommended Recommended Protectionlength screwdriver torque

th. 2,8 mm th. 2,8 mm

Rated voltage± 20% ± 10%

632

NFC DIN UL CSANFC DIN UL CSA

M 4/9.PZ.../... M 4/9.PZ.../...

AL2 (1) 2 mm 0163 070.00AL3 (1) 3 mm 0163 261.00DCG 0163 218.05FC2 2 mm 0007 865.26BJS9 (1)(2) 8 0177 583.12BJS9 (1)(2) 16 0177 584.13EV6D (1)(2) 0168 400.16

AD2,5 0114 205.20

AL2 (1) 2 mm 0163 070.00AL3 (1) 3 mm 0163 261.00DCG 0163 218.05FC2 2 mm 0007 865.26BJS9 (1)(2) 8 0177 583.12BJS9 (1)(2) 16 0177 584.13EV6D (1)(2) 0168 400.16

AD2,5 0114 205.20

8,5 mm 4 mm 0,4-0,6 Nm IP 20.33" 3.5-5.3 Ib.in NEMA 1

8,5 mm 4 mm 0,4-0,6 Nm IP 20.33" 3.5-5.3 Ib.in NEMA 1

264 mm²

264 mm²

0,5-4 mm²

0,5-4 mm²

0,5-4 mm²

0,5-4 mm²

T01100 010103

BAMH 0114 836.00

35 x 7,5 x 1PR4 35 x 15 x 2,3 0168 500.12

35 x 15 x 1,5PR1Z2 32 x 15 x 1,5 0163 050.04

~=

M 4/9.PZ 5/3 5 V DC 0007 015.15M 4/9.PZ 12/8 12 V DC 0007 016.16M 4/9.PZ 15/12 15 V DC 0007 017.17M 4/9.PZ 24/15 24 V DC 0007 018.20M 4/9.PZ 48/36 48 V DC 0007 020.26M 4/9.PZ 60/48 60 V DC 0007 021.13M 4/9.PZ 130/60 110-130 V DC 0007 022.14

M 4/9.PZ 15/12 12 V AC 0007 017.17M 4/9.PZ 24/15 15 V AC 0007 018.20M 4/9.PZ 35/24 24 V AC 0007 019.21M 4/9.PZ 60/48 48 V AC 0007 021.13M 4/9.PZ 130/60 60 V AC 0007 022.14M 4/9.PZ 187/130 110-130 V AC 0007 023.15M 4/9.PZ 348/240 220-240 V AC 0007 024.16

th. 9,1 mmOther end stops : See Accessories sectionPR30 0173 220.05

PR5 0101 598.26

Other rails : See Accessories sectionOther accessories : See Accessories section

~=

Characteristics

Type P/N Type P/N

Grey body Grey body

M 4/9 block equipped with a 3 mm end plate and a bidirectionalsilicon transient voltage suppressor between two decks.

M 4/9 block equipped with a 3 mm end plate and a bidirectionalsilicon transient voltage suppressor between two decks.

Spacing 9 mm .354"Spacing 9 mm .354"

Note : Given for 1,5 kW in 10/1000 µs and 18 kW in 8/20 µs.

Electronic componentholder terminal blocksWith transzorbSeries 7 000Compression clamp

DIN 1 - 3

5 to 130 V DC 12 to 240 V AC

Characteristics

Accessories

Rated current ARated wire size

Other characteristics

Wire size

Note : (1) These accessories can be used on the lower connection only.(2) Use of these accessories requires the user to cut out the partition.

1 Test socket

2 Test device3 Test plug4 Jumper bar not assembled

5 Sub-assembly for jumper bar(screw + washer + post)

6 IDC jumper

R See section on markersmarking method

Rated voltage V

Compression Solid wire

clamp Stranded

wire

Type P/N Type P/N

Wire stripping Recommended Recommended Protectionlength screwdriver torque

Wire stripping Recommended Recommended Protectionlength screwdriver torque

DIA.DIA.

greyDIA.

polespoles

DIA.DIA.

greyDIA.

polespoles

Capacitance

(pF)22000700051003250220015001100600410240

Type

M 4/9.PZ 5/3M 4/9.PZ 12/8M 4/9.PZ 15/12M 4/9.PZ 24/15M 4/9.PZ 35/24M 4/9.PZ 48/36M 4/9.PZ 60/48M 4/9.PZ 130/60M 4/9.PZ 187/130M 4/9.PZ 348/240

Stand-offvoltageVRM(V)5.813.618.828.240.258.177.8145213376

Leakagecurrent

IRM(µA)1000

555555555

Rated voltageto ± 20%

DC (V) AC (V)5 312 815 1224 1535 2448 3660 48130 60187 130348 240

Max. surge currentClamping voltage

10/1000 µs 8/20 µsVCL (V) Ipp (A) VCL (V) Ipp (A)

10.5 143 13.4 134322.5 67 28.9 62330.6 49 39.3 45845.7 33 59 30564.8 23.2 84 21492 16.3 121 148125 12 162 111234 6.4 301 60344 5 442 47603 3.5 776 33

Breakdownvoltage

(V)min. max.6.45 7.4815.2 17.620.9 24.231.4 36.344.7 51.764.6 74.886.5 100161 187237 275418 484

633

NF10030

DIN-VDE UL CSA NFC-UTE

~=

8

7

109

R

5

1

2

3-4

6

11 M 4/9.PV 5/4 5 V DC 0007 004.23M 4/9.PV 12/8 12 V DC 0007 005.24M 4/9.PV 15/12 15 V DC 0007 006.25M 4/9.PV 24/15 24 V DC 0007 007.26M 4/9.PV 48/35 48 V DC 0007 009.00M 4/9.PV 60/48 60 V DC 0007 010.24M 4/9.PV 130/60 110-130 V DC 0007 011.11

M 4/9.PV 15/12 12 V AC 0007 006.25M 4/9.PV 24/15 15 V AC 0007 007.26M 4/9.PV 35/24 24 V AC 0007 008.07M 4/9.PV 60/48 48 V AC 0007 010.24M 4/9.PV 130/60 60 V AC 0007 011.11M 4/9.PV 165/110 110 V AC 0007 012.12M 4/9.PV 270/130 130 V AC 0007 013.13M 4/9.PV 508/240 220-240 V AC 0007 014.14

010103

65,52.58"

38 1.50"33 1.30"

64,5

2.54

"

59,7

2.35

"67 2.64

"

Spacing 9 mm .354"

M 4/9.PV.../...5 to130 V DC

Wire stripping DIA.length screwdriver

Wire size

Protection in "ZONE 2"

Electroniccomponent holderterminal blocksBlocks with varistorSeries 7 000

DIN 1 - 3

Protection in "ZONE 2"

Grey body

M 4/9 block equipped with a 3 mm end plate and a bidirectionalmetal oxide transient voltage suppressor between two decks.

M 4/9.PV.../...12 to 240 V AC

Spacing 9 mm .354"

Grey body

M 4/9 block equipped with a 3 mm end plate and a bidirectionalmetal oxide transient voltage suppressor between two decks.

Type P/N Type P/N

(1) These accessories can be used on the lower connection only.(2) Use of these accessories requires the user to cut out the partition.

1 Rail 32 x 152 Rail 35 x 7.5 x 13 Rail 35 x 15 x 2.34 Rail 35 x 15 x 1.55 High end stop (all rails)6 Test socket

7 Test device8 Test plug9 Jumper bar (not preassembled)

10 Sub-assembly for jumper bar(screw + washer +post)

11 IDC jumper

R See marking section

PR1 Z2 0163 050.04PR3 G2 0164 800.03PR4 0168 500.12PR5 0168 700.22BAMH th. 9.1 mm 0114 836.00AL2 (1) DIA. 2 mm 0163 070.00AL3 (1) DIA. 3 mm 0163 261.00DCG grey 0163 218.05FC2 DIA. 2 mm 0007 865.26BJS9 (1)(2) 8 poles 0177 583.12BJS9 (1)(2) 16 poles 0177 584.13EV6D (1)(2) 0168 400.16

AD2.5 0114 205.20

8.5 mm 4 mm 0.4-0.6 Nm IP 20.33" 3.5-5.3 Ib.in NEMA 1

0-4 mm² 0-4 mm²

0-4 mm² 0-4 mm²

PR1 Z2 0163 050.04PR3 G2 0164 800.03PR4 0168 500.12PR5 0168 700.22BAMH th. 9.1 mm 0114 836.00AL2 (1) DIA. 2 mm 0163 070.00AL3 (1) DIA. 3 mm 0163 261.00DCG grey 0163 218.05FC2 DIA. 2 mm 0007 865.26BJS9 (1)(2) 8 poles 0177 583.12BJS9 (1)(2) 16 poles 0177 584.13EV6D (1)(2) 0168 400.16

AD2.5 0114 205.20

8.5 mm 4 mm 0.4-0.6 Nm IP 20.33" 3.5-5.3 Ib.in NEMA 1

0-4 mm² 0-4 mm²

0-4 mm² 0-4 mm²

Capacitance(pF)

1200060004000350025001800900550480300220

Peak clamping voltagewith 8/20 µs wave

Vc ( V ) Ip ( A )20 539 553 564 589 5123 5165 25300 25360 25595 251120 25

Varistor voltage at 1 mA DCtest current

min. ( V ) max. ( V )6 11

14.4 21.623 31.1

29.5 36.542 5261 7590 110162 198198 242324 396610 748

Max. impulse current withan 8/20 µs current wave

( A )25050050050050050025002500250025002500

Max. operatingvoltage

DC (V) AC (V)5.5 4.214 1022 1726 2038 3056 4081 60153 115180 140300 230560 420

Type

M 4/9.PV 5/4M 4/9.PV 12/8M 4/9.PV 15/12M 4/9.PV 24/15M 4/9.PV 35/24M 4/9.PV 48/35M 4/9.PV 60/48M 4/9.PV 130/60M 4/9.PV 165/110M 4/9.PV 270/130M 4/9.PV 508/240

Accessories Type P/N

Characteristics

Current ARated wire size

Other characteritics Wire stripping DIA.length screwdriver

Approvals (Contact Entrelec)

Solid wire

Stranded wire

Voltage V

Type P/N

26 304 mm² 2.5 mm²

26 304 mm² 2.5 mm²

CharacteristicsNote : Average power dissipation of transient not to exceed 0.4 W.