    Technical Site Selection ReportABB, Faridabad AG2 Location

  • 8/22/2019 ABB Faridabad

    2/37

  • 8/22/2019 ABB Faridabad

    3/37

    ABB AG2 site, 5 nearest possible Industrial/commercial plot/properties identified by Infotel team

    are recommended for further commercial/technical evaluation after field survey by site selectionteam. The details of these recommended sites are as given below.

    Location Co-ordinates

    Site NameABB FARIDABAD AG2

    Location as per Design - 2827' 22.732" N 7718' 25.849" E

    Sl.

    No.Site Address

    Location Distance

    from Design

    Location

    Remarks

    Latitude Longitude

    1

    Plot No. 1523, A Block

    Market, Green Field,

    Faridabad.

    2827' 53.4" N 7718' 3.42" E1126 m

    Site suitable for AG2

    2

    Plot No. 1529, A Block

    Market, Green Field,

    Faridabad.

    2827' 53.34" N 7718' 1.62" E

    1152 mSite suitable for AG2

    3

    Plot No. 644, B Block

    Market, Green Field,

    Faridabad. 121003

    2827' 42.96" N7717' 43.02" E

    1320 mSite suitable for AG2

    4

    SCO 63, Huda market

    Sec 31, Adjoining Pristine

    Mall, Faridabad-121001

    2826'41.3"N 7718'58.6"E

    1558 mSite suitable for AG2

    5

    Plot 181, double story

    Sec 31. Adjoining Pristinemall, Faridabad -121001

    2826'45.6"N 7718'57.4"E

    1432 m Site suitable for AG2

  • 8/22/2019 ABB Faridabad

    4/37

    Plot No -1523 Green Field Market Faridabad

  • 8/22/2019 ABB Faridabad

    5/37

    10.00 Ft Road

    63.30 ft30.00 Ft Road

    28.50 Ft

    30 Ft Road

  • 8/22/2019 ABB Faridabad

    6/37

    Front View Left View

    Right View Road View

  • 8/22/2019 ABB Faridabad

    7/37

    Term sheet/Checklist for AG2 facilitiesSl.

    No.

    Description / Requirement

    1 Location of Facility

    Complete Postal Address

    with Pin Code

    Plot No. 1523, A Block Market, Green Field,

    Faridabad.

    Location Coordinates

    Longitude 7718' 3.42" E

    Latitude 2827' 53.4" N

    Contact Person S.N. Arora

    Phone/Mobile No. of

    Contact person

    9810183093

    2 Does the Property belong to

    Reliance?

    No

    if Yes Is property Owned by

    Reliance?

    No

    Is property taken on

    Lease by Reliance?

    No Lease Period From..

    To ..

    if No Is property available on

    Sale?

    Yes

    Is property available on

    Lease?

    No Lease Period (required

    for 20 years)

    From..

    To ..

    3 Space Available for Infotel Facilities

    Does available

    property have

    Open space ?

    Yes

  • 8/22/2019 ABB Faridabad

    8/37

    Minimum Requirement for

    Open Space

    a) If Covered/Built-up Area

    not available

    i. 1600 sq ft , minimum 25 ft

    wide

    b) If Covered/Built-up Area is

    also available

    i. 400 sq ft - for Manhole,

    earth pits, DGs and

    transformer if emergency

    power (DG) is not available.

    ii. 250 sq ft - for Manholes,

    earth pits plus if DG power is

    available.

    if yes

    1804.05 Sqft

    (28.5 x63.3)

    The site is

    available on sale.

    Corner Plot

    having area 1800

    Sqft Space for

    MH, EP, GBM

    and DG are

    available. Plot

    requires Approx

    2 m filling. The

    site is 1.1 Km

    from designed

    coordinates.

    Does available

    property have

    covered/built-up

    space?

    No

    Minimum Requirement for

    Covered/Built-up space

    400 sq ft, minimum 10 ft

    width

    if yes

    4 Is Covered space air

    conditioned?

    No

    Minimum Requirement

    8 ton cooling capacity.

    Only Precision AC is

    acceptable

    Controlled Temperature

    (maximum) 25 deg C

    if yes NA

    5 Power Requirement

    Minimum Requirement

    a) If non AC covered/built-in

    space or only open space

    available

    Normal Power (grid) : 3-

    Ph, 415 V

    Power

    Availab

    le

    No

    If yes Normal Power(grid), kW

    Emergency Power (DG), KW NA

  • 8/22/2019 ABB Faridabad

    9/37

    Connected Load : 64

    kW

    Operating Load : 50

    kW

    Redundant Emergency

    Power (DG): 3-Ph, 415V, 13

    kW

    b) If covered/built up space

    available is also having

    precision air conditioning

    Normal Power (grid) : 3-

    Ph, 415 V

    Connected Load : 38

    kW

    Operating Load : 38

    kW

    Redundant EmergencyPower (DG): 3-Ph, 415 V, 1

    kW

    6 Other Requirements

    Access for

    Personnel

    24x7 accesses available? Yes

    Independent Entry

    Possible?

    Yes

    Access for

    Equipment

    Vehicular access available

    (min 3m road)?

    Yes

    Independent Entry for

    Infotel Possible?

    Yes

    Access to

    Fiber and

    Electrical

    cables

    Space for cable routing to

    Infotel facility available

    (required for 20 fiber

    cables each in 40 mm

    duct and three phase

    power supply)?

    Yes

    Security

    for

    facilities

    Facility has 24x7

    securities? No

    Can it be extended to

    Infotel?No

    Potable

    Water

    Will 250 let potable water

    be available for use by

    No

  • 8/22/2019 ABB Faridabad

    10/37

    Infotel personnel?

    Toilet

    Facilities

    Are toilet facilities

    available for use by

    Infotel personnel?

    No

    Earthling

    Facilities

    Is it possible to share

    existing earthling system

    with Infotel (for Lightning,

    electrical/equipment, DC

    (for electronic

    equipment), DG neutral

    etc.) if available?

    No

  • 8/22/2019 ABB Faridabad

    11/37

    Plot No. 1529, A Block Market, Green Field,

    Faridabad.

  • 8/22/2019 ABB Faridabad

    12/37

    10.00 Ft Road

    63.30

    28.50 Ft

  • 8/22/2019 ABB Faridabad

    13/37

    Main view inside view

  • 8/22/2019 ABB Faridabad

    14/37

    Term sheet/Checklist for AG2 facilitiesSl.

    No.

    Description / Requirement

    1 Location of Facility

    Complete Postal

    Address with Pin

    Code

    Plot No. 1529, A Block Market, Green

    Field, Faridabad.

    Location Coordinates

    Longitude 7718' 1.62" E

    Latitude 2827' 53.34" N

    Contact Person S.N. Arora

    Phone/Mobile No. of

    Contact person

    9810183093

    2 Does the Property

    belong to Reliance?

    No

    if Yes Is property Owned by

    Reliance?

    No

    Is property taken on

    Lease by Reliance?

    No Lease Period From..

    To ..

    if No Is property available

    on Sale?

    Yes

    Is property available

    on Lease?

    No Lease Period

    (required for 20years)

    From..

    To ..

    3 Space Available for Infotel Facilities

    Does available

    property have Open

    space?

    Yes

    Minimum Requirement for

    Open Space

    a) If Covered/Built-up Area

    not available

    i. 1600 sq ft , minimum 25

    ft wide

    b) If Covered/Built-up Area

    is also available

    i. 400 sq ft - for Manhole,

    earth pits, DGs and

    if yes

    1804.05 Sqft

    (28.5 x63.3)

    The site is available

    on sale. Plot area

    1800 Sqft Space for

    MH, EP, GBM and

    DG is available.

    Plot requires

    Approx 2 m filling.

    The site is 1.1 Km

    from designed

    coordinates.

  • 8/22/2019 ABB Faridabad

    15/37

    transformer if emergency

    power (DG) is not available.

    ii. 250 sq ft - for Manholes,

    earth pits plus if DG power

    is available.

    Does available

    property have

    covered/built-up

    space?

    No

    Minimum Requirement for

    Covered/Built-up space

    400 sq ft, minimum 10 ft

    width

    if yes

    4 Is Covered space air

    conditioned?

    No

    Minimum Requirement

    8 ton cooling capacity.

    Only Precision AC is

    acceptableControlled Temperature

    (maximum) 25 deg C

    if yes NA

    5 Power Requirement

    Minimum Requirement

    a) If non AC covered/built-in space

    or only open space available

    Normal Power (grid) : 3-Ph, 415 V

    Connected Load : 64 kW

    Operating Load : 50 kW

    Redundant Emergency Power

    (DG): 3-Ph, 415V, 13 kW

    b) If covered/built up space

    available is also having precision air

    conditioning

    Normal Power (grid) : 3-Ph, 415 V

    Connected Load : 38 kW

    Power

    Available

    N0

    If yes Normal Power(grid), kW

    Emergency Power (DG), kW NA

  • 8/22/2019 ABB Faridabad

    16/37

    Operating Load : 38 kW

    Redundent Emergency Power

    (DG): 3-Ph, 415 V, 1 kW

    6 Other RequirementsAccess for Personnel 24x7 access available? Yes

    Independent Entry

    Possible?

    Yes

    Access for Equipment Vehicular access

    available (min 3m

    road)?

    Yes

    Independent Entry for

    Infotel Possible?

    Yes

    Access to Fiber and

    Electrical cables

    Space for cable routing

    to Infotel facility

    available (required for

    20 fiber cables each in

    40 mm duct and three

    phase power supply)?

    Yes

    Security for facilities Facility has 24x7

    securities?

    No

    Can it be extended to

    Infotel?

    No

    Potable Water Will 250 lt potablewater be available for

    use by Infotel

    personnel?

    No

    Toilet Facilities Are toilet facilities

    available for use by

    Infotel personnel?

    No

    Earthing Facilities Is it possible to share

    existing earthing

    system with Infotel(for Lightning,

    electrical/equipment,

    DC (for electronic

    equipment), DG

    neutral etc.) if

    available?

    No

  • 8/22/2019 ABB Faridabad

    17/37

    Plot N0-644 B Block Mkt Green Field Faridabad-

    121003

  • 8/22/2019 ABB Faridabad

    18/37

  • 8/22/2019 ABB Faridabad

    19/37

    60.00 ft

    24.00 Ft

    30 Ft Road

  • 8/22/2019 ABB Faridabad

    20/37

    Front View Left view

    Right View

    Term sheet/Checklist for AG2 facilitiesSl.

    No.

    Description / Requirement

    1 Location of Facility

    Complete Postal

    Address with Pin

    Code

    Plot No-644 B Block Mkt Green Field

    faridabad-121003

    Location Coordinates

    Longitude 7717' 43.02" E

    Latitude 2827' 42.96" N

    Contact Person Rajveer Yadav

    Phone/Mobile No. of

    Contact person

    9811424208

  • 8/22/2019 ABB Faridabad

    21/37

    2 Does the Property

    belong to Reliance?

    No

    if Yes Is property Owned by

    Reliance?

    No

    Is property taken on

    Lease by Reliance?

    No Lease Period From..

    To ..

    if No Is property available

    on Sale?

    Yes

    Is property available

    on Lease?

    No Lease Period

    (required for 20

    years)

    From..

    To ..

    3 Space Available for Infotel Facilities

    Does available

    property haveOpen space?

    Yes

    Minimum Requirement for Open

    Space

    a) If Covered/Built-up Area not

    available

    i. 1600 sq ft, minimum 25 ft wide

    b) If Covered/Built-up Area is also

    available

    i. 400 sq ft - for Manhole, earth

    pits, DGs and transformer if

    emergency power (DG) is not

    available.

    ii. 250 sq ft - for Manholes, earth

    pits plus if DG power is available.

    if yes

    1440 Sqft

    (24 x 60)

    The site is

    available on sale.

    Plot area 1440

    Sqft Space for MH,

    EP, GBM and DG is

    available. Plot

    requires Approx 1

    m filling. The site

    is 1.3 Km from

    designed

    coordinates.

    Does available

    property have

    covered/built-

    up space?

    No

    Minimum Requirement for

    Covered/Built-up space400 sq ft, minimum 10 ft width

    if yes

    4 Is Covered space air

    conditioned?

    No

  • 8/22/2019 ABB Faridabad

    22/37

    Minimum Requirement

    8 ton cooling capacity.

    Only Precision AC is acceptable

    Controlled Temperature

    (maximum) 25 deg C

    if yes NA

    5 Power Requirement

    Minimum Requirement

    a) If non AC covered/built-in

    space or only open space

    available

    Normal Power (grid) : 3-Ph,

    415 V

    Connected Load : 64 kW

    Operating Load : 50 kW

    Redundant Emergency Power(DG): 3-Ph, 415V, 13 kW

    b) If covered/built up space

    available is also having precision

    air conditioning

    Normal Power (grid) : 3-Ph,

    415 V

    Connected Load : 38 kW

    Operating Load : 38 kW

    Redundant Emergency Power

    (DG): 3-Ph, 415 V, 1 kW

    Power

    Available

    No

    If yes Normal Power(grid), kW

    Emergency Power (DG), kW NA

    6 Other Requirements

    Access for Personnel 24x7access available? Yes

    Independent Entry Possible? Yes

    Access for Equipment Vehicular access available (min

    3m road)?

    Yes

    Independent Entry for Infotel

    Possible?

    Yes

    Access to Fiber and

    Electrical cables

    Space for cable routing to Infotel

    facility available (required for 20

    fiber cables each in 40 mm duct

    and three phase power supply)?

    Yes

    Security for facilities Facility have 24x7 security? No

    Can it be extended to Infotel? No

  • 8/22/2019 ABB Faridabad

    23/37

    Potable Water Will 250 lt potable water be

    available for use by Infotel

    personnel?

    No

    Toilet Facilities Are toilet facilities available for

    use by Infotel personnel?

    No

    Earthing Facilities Is it possible to share existing

    earthing system with Infotel (for

    Lightning, electrical/equipment,

    DC (for electronic equipment),

    DG neutral etc.) if available?

    No

    Sco-63 Huda Market Sec-31 Faridabad

  • 8/22/2019 ABB Faridabad

    24/37

  • 8/22/2019 ABB Faridabad

    25/37

    38

    17.5

    Front View Right View

  • 8/22/2019 ABB Faridabad

    26/37

    Left View Right View

    Term sheet/Checklist for AG2 facilities

    Sl.

    No.

    Description / Requirement

    1 Location of Facility

    Complete Postal Address

    with Pin Code

    SCO 63, Huda Market Sec 31, Adjoining Pristine

    Mall, Faridabad-121001

    Location Coordinates

    Longitude 7718'58.6"E

    Latitude 2826'41.3"N

    Contact Person Mr. Manchanda

    Phone/Mobile No. of

    Contact person

    9350646304

  • 8/22/2019 ABB Faridabad

    27/37

    2 Does the Property belong to

    Reliance?

    Yes

    if Yes Is property Owned by

    Reliance?

    RIL Recommended Vendor

    Is property taken on Lease

    by Reliance?

    No Lease Period From.. To

    ..

    if No Is property available on

    Sale?

    No

    Is property available on

    Lease?

    Yes Lease Period (required

    for 20 years)

    From.. To

    ..

    (Available on

    lease)

    3

    Space Available for Infotel FacilitiesDoes

    available

    property

    have

    Open

    space?

    Yes

    Minimum Requirement for

    Open Space

    a) If Covered/Built-up Area

    not available

    i. 1600 sq ft , minimum 25 ft

    wide

    b) If Covered/Built-up Area

    is also available

    i. 400 sq ft - for Manhole,

    earth pits, DGs and

    transformer if emergency

    power (DG) is not available.

    ii. 250 sq ft - for Manholes,earth pits plus if DG power is

    available.

    if yes

    162 Sq Ft.

    (12.5x13)

    Open space for DG

    162 Sqft available on

    back side.

    Does

    available

    property

    have

    covered/

    built-up

    space?

    Yes

  • 8/22/2019 ABB Faridabad

    28/37

    Minimum Requirement for

    Covered/Built-up space

    400 sq ft, minimum 10 ft

    width

    if yes

    665 Sqft

    17.5x38

    The site is available

    on Lease. Total

    Covered area725 Sqft

    suitable for AG2.

    Space for MH, EP

    available. Open space

    for DG 162 Sqft

    available on back

    side. The site is 1.56

    Km from designed

    coordinates.

    4 Is

    Covered

    space air

    conditioned?

    No

    Minimum Requirement

    8 ton cooling capacity.

    Only Precision AC is

    acceptable

    Controlled Temperature

    (maximum) 25 deg C

    if yes Cooling Capacity available, tons NA

    5 Power Requirement

    Minimum Requirement

    a) If non AC covered/built-in

    space or only open space

    available

    Normal Power (grid) : 3-

    Ph, 415 V

    Connected Load : 64

    kW

    Operating Load : 50

    kW

    Redundent EmergencyPower (DG): 3-Ph, 415V, 13

    kW

    b) If covered/built up space

    available is also having

    precision air conditioning

    Normal Power (grid) : 3-

    Ph, 415 V

    Connected Load : 38

    PowerAvailable

    Yes CommercialPower

    available

    If yes Normal Power(grid), kW 50 Kw

    Emergency Power (DG), KW NA

  • 8/22/2019 ABB Faridabad

    29/37

    kW

    Operating Load : 38

    kW

    Redundent Emergency

    Power (DG): 3-Ph, 415 V, 1

    kW

    6 Other Requirements

    Access for

    Personnel

    24x7 access available? Yes

    Independent Entry Possible? Yes

    Access for

    Equipment

    Vehicular access available (min

    3m road)?

    Yes

    Independent Entry for InfotelPossible? Yes

    Access to

    Fiber and

    Electrical

    cables

    Space for cable routing to Infotel

    facility available (required for 20

    fiber cables each in 40 mm duct

    and three phase power supply)?

    Yes

    Security for

    facilities

    Facility have 24x7 security? No

    Can it be extended to Infotel? NA

    Potable

    Water

    Will 250 lt potable water be

    available for use by Infotel

    personnel?

    Yes

    Toilet

    Facilities

    Are toilet facilities available for

    use by Infotel personnel?

    Yes

    Earthing

    Facilities

    Is it possible to share existing

    earthing system with Infotel (for

    Lightning, electrical/equipment,

    DC (for electronic equipment),

    DG neutral etc.) if available?

    No

  • 8/22/2019 ABB Faridabad

    30/37

    Plot No -181 Double Story Sec -31 Faridabad

  • 8/22/2019 ABB Faridabad

    31/37

  • 8/22/2019 ABB Faridabad

    32/37

    46'

    19'

  • 8/22/2019 ABB Faridabad

    33/37

    Front View Right View

    Inside View Left View

  • 8/22/2019 ABB Faridabad

    34/37

    Term sheet/Checklist for AG2 facilities

    Sl.

    No.

    Description / Requirement

    1 Location of Facility

    Complete Postal

    Address with Pin Code

    Plot 181, double story sec 31. adjoining pristine mall,

    Faridabad -121001

    Location Coordinates

    Longitu

    de

    7718'57.4"E

    Latitude

    2826'45.6"N

    Contact Person Mr. Manchanda

    Phone/Mobile No. of

    Contact person

    9350646304

    2 Does the Property belong to

    Reliance?

    Yes

    if Yes Is property Owned by

    Reliance?

    RIL Recommended Vendor

    Is property taken on

    Lease by Reliance?

    No Lease Period From.. To

    ..

    if No Is property available on

    Sale?

    Yes

    Is property available on

    Lease?

    No Lease Period

    (required for 20

    years)

    From.. To

    ..

    (Available on lease)

    3 Space Available for Infotel Facilities

    Does available property have

    Open space ?

    Yes

  • 8/22/2019 ABB Faridabad

    35/37

    Minimum

    Requirement for

    Open Space

    a) If Covered/Built-

    up Area not

    available

    i. 1600 sq ft ,

    minimum 25 ft

    wide

    b) If Covered/Built-

    up Area is also

    available

    i. 400 sq ft - for

    Manhole,

    earthpits, DGs andtransformer if

    emergency power

    (DG) is not

    available.

    ii. 250 sq ft - for

    Manholes,

    earthpits plus if DG

    power is available.

    if yes874 Sqft

    (46x 19)

    The site is

    available onsale. Total plot

    area 900 Sqft .

    As per FAR

    (19'*35') can be

    constructed on

    G. floor. We

    can construct as

    per our

    requirement.

    Space for MH,

    EP, DG is

    available. Thesite is 1.56 Km

    from designed

    coordinates.

    Does available property have

    covered/built-up space?

    No

    Minimum

    Requirement for

    Covered/Built-up

    space

    400 sq ft,

    minimum 10 ft

    width

    if yes Built-up Area

    Available, Sq ft

    NA

    4 Is Covered

    space air

    conditioned?

    No

    Minimum

    Requirement

    8 ton cooling

    capacity.

    Only Precision

    AC is acceptable

    Controlled

    Temperature

    if yes Cooling Capacity available,

    tons

    NA

  • 8/22/2019 ABB Faridabad

    36/37

    (maximum) 25

    deg C

    5 Power

    RequirementMinimum

    Requirement

    a) If non AC

    covered/built-in

    space or only

    open spaceavailable

    Normal Power

    (grid) : 3-Ph, 415

    V

    Connected Load :

    64 kW

    Operating Load :

    50 kW

    Redundent

    Emergency Power

    (DG): 3-Ph, 415V,

    13 kW

    b) If

    covered/built up

    space available is

    also having

    precision air

    conditioning

    Normal Power

    (grid) : 3-Ph, 415V

    Connected Load :

    38 kW

    Operating Load :

    38 kW

    Redundent

    Power Available No

    If yes Normal Power(grid), kW NA

    Emergency Power (DG), kW NA

  • 8/22/2019 ABB Faridabad

    37/37

    Emergency Power

    (DG): 3-Ph, 415 V,

    1 kW

    6 Other Requirements

    Access for

    Personnel

    24x7 access available? Yes

    Independent Entry

    Possible?

    Yes

    Access for

    Equipment

    Vehicular access

    available (min 3m

    road)?

    Yes

    Independent Entry for

    Infotel Possible?

    Yes

    Access to Fiber

    and Electrical

    cables

    Space for cable routing

    to Infotel facility avialble

    (required for 20 fiber

    cables each in 40 mm

    duct and three phase

    power supply)?

    Yes

    Security for

    facilities

    Facility has 24x7

    security?

    No

    Can it be extended to

    Infotel?

    NA

    Potable Water Will 250 lt potable water

    be available for use by

    Infotel personnel?

    No

    Toilet Facilities Are toilet facilities

    available for use by

    Infotel personnel?

    No

    Earthing

    Facilities

    Is it possible to share

    existing earthing systemwith Infotel (for

    Lightning,

    electrical/equipment,

    DC (for electronic

    equipment), DG neutral

    etc.) if available?

    No