SACE Emax LV Air Circuit Breaker –
Range - Emax
© A
BB
SA
CE
- 2
SACE Emax
SACE EMAX:SACE EMAX:THE THIRD MILLENIUM IS IN THE AIRTHE THIRD MILLENIUM IS IN THE AIR
© A
BB
SA
CE
- 3
SACE Emax - History
1960 1970 1980 1990 1996
OTOMAX G30 NOVOMAX
MEGAMAX
EMAX
© A
BB
SA
CE
- 4
SACE Emax
The ABB SACE L.V. Quality System conforms to the International Standard ISO 9001
ISO 9001
ISO 14001
© A
BB
SA
CE
- 5
SACE Emax
Electrical characteristics
Technical and design characteristics
Microprocessor-based trip units
Terminals - Accessories - Versions
Applications
© A
BB
SA
CE
- 6
SACE Emax: Electrical characteristic
Currents (definitions)
Icu = RATED ULTIMATE SHORT CIRCUIT BREAKING CAPACITY
Ics = RATED SERVICE SHORT CIRCUITBREAKING CAPACITY
Icw = RATED SHORT-TIME WITHSTAND CURRENT
© A
BB
SA
CE
- 7
SACE Emax: Electrical characteristics
DIVERSIFIED BREAKING CAPACITIES RANGERATED ULTIMATE BREAKING CAPACITIES (Icu)
Selective circuit-breakers
B = BASE Icu = 40 kA
N = NORMAL Icu = 65 kA
S = STANDARD Icu = 75 kA
H = HIGH Icu = 100 kA
V = VERY HIGH Icu = 150 kA
Current-limiting circuit-breakers
L = CURRENT LIMITING Icu = 130 kA
E1N – 50 kA
© A
BB
SA
CE
- 8
SACE Emax: Electrical characteristics
Rated Voltage Ue = 690V a.c.
Rated uninterrupted current Iu = 800 - 6300 A
Rated ultimate breaking capacity Icu = 40-150kA
Rated insulation voltage Ui = 1000 V
Rated impulse withstand voltage Uimp = 12 kV
Frequency F = 50 - 60 Hz
© A
BB
SA
CE
- 9
Performance levels B N B N L N S H S H H V
[A] 800 800 1600 1000 1250 2500 1000 800 4000 3200 4000 3200[A] 1000 1000 2000 1250 1600 3200 1250 1000 4000 5000 4000[A] 1250 1250 1600 1600 1250 6300 5000[A] 1600 1600 2000 2000 1600 6300[A] 2500 2000[A] 3200 2500[A] 3200
Breaking capacityIcu @ 415 V AC [kA] 42 50 42 65 130 65 75 100 75 100 100 150Ics @ 415 V AC [kA] 42 50 42 65 130 65 75 85 75 100 100 125
Making capacity
Icm @ 415 V AC [kA] 88.2 105 88.2 143 286 143 165 220 165 220 220 330
Rated withstand currentIcw @ 1 s [kA] 42 50 42 55 10 65 75 75 75 100 100 100Icw @ 3 s [kA] 36 36 42 42 - 65 65 65 75 75 85 85
Utilisation category B B B B A B B B B B B B
Rated current Iu
E6E1 E2 E3 E4
SACE Emax: Electrical characteristics
© A
BB
SA
CE
- 1
0
FIXED
WITHDRAWABLE
VERSIONS
SACE Emax: Technical characteristics
TYPES
THREE - POLE
FOUR - POLE
50% and 100% rated up to 6300A
© A
BB
SA
CE
- 1
1
SACE Emax: Technical and design characteristics
Icw (1s) up to 75 kA with rate current In = 1250 - 1600 - 2000 - 2500 - 3200 A
Icw (1s) up to 100 kA with rated current In = 3200 - 4000 - 5000 - 6300 A
Icw (3s) up to 75 kA with rated current In = 1250-1600-2000-2500-3200-4000-5000-6300 A
A new construction concept for peak level
performance
© A
BB
SA
CE
- 1
2
SACE Emax: Technical characteristics
- Double the number of contact points
- No mechanical junctions in live parts
Reduced Contact Wear
Long Electrical Life
© A
BB
SA
CE
- 1
3
SACE Emax: Technical characteristics
- Single pole construction concept
© A
BB
SA
CE
- 1
4
SACE Emax: Technical characteristics
- Metal supporting structure
- Double insulation between auxiliary circuits and power circuits
- Pre-wired electrical accessories connected from the front of the breaker
© A
BB
SA
CE
- 1
5
SACE Emax: Technical characteristics
- Breaking chamber visible for inspection
- Simplified changing of current transformer set
© A
BB
SA
CE
- 1
6
SACE Emax: Technical characteristics
Completeness of range
800A
6300A
© A
BB
SA
CE
- 1
7
SACE Emax: Technical characteristics
- Reduced volumes
- Only 4 mounting points
Building of compact switchboards
© A
BB
SA
CE
- 1
8
SACE Emax: Technical characteristics
Sheet steel supporting structure
Earthing contacts (one for E1, E2, E3,
two for E4, E6)
Safety shutters (Protection class IP20)
Isolating base for the terminals
Terminals (RH, RV,F)
Auxiliary contacts (conn/test/disconn)
Sliding contacts
Fixing points (4 for E1,2,3 and 6 for
E4,6)
1
2
3
4
5
6
7
8
7
2
8
3
4
5
6
1
© A
BB
SA
CE
- 1
9
SACE Emax: Technical characteristics
© A
BB
SA
CE
- 2
0
SACE Emax: Overcurrent releases
New generation of microprocessor-based overcurrent releases
© A
BB
SA
CE
- 2
1
SACE Emax: Overcurrent releases
Three versions available for the entire series
Complete range of protection functions (L, S, I, G)
Complete range of protection functions + Accessory functions
PR111PR111
PR112PR112
Complete range of protection functions + Accessory functionsPR113PR113
© A
BB
SA
CE
- 2
2
SACE Emax: Overcurrent releases
Available functions:
Protection (L, S, I, G)
Self - protection
Test
Load control
© A
BB
SA
CE
- 2
3
Available functions:
SACE Emax: Overcurrent releases
Self - control (Watchdog System)
Alarms
Measurements
Controlling and monitoring
© A
BB
SA
CE
- 2
4
SACE Emax: Overcurrent releases
Selectivity for all installation needs
Self-powered unit for protection function only
Interchangeability
© A
BB
SA
CE
- 2
5
SACE Emax: Overcurrent releases
COMPLETE RANGE OF PROTECTION FUNCTIONS (L, S, I, G)
VERSIONS AVAILABLE : - PR111/ L I- PR111/ L S I- PR111/ L S I G
SELF SUPPLIED DEVICE
POSSIBILITY TO TEST THE TRIP UNIT WITH EXTERNAL DEVICE
AVAILABLE IEC AND UL LISTED
PR111PR111
© A
BB
SA
CE
- 2
6
SACE Emax: Overcurrent releases
1
7
6 3
2 13
12
8
4
5
15 16
20
11
9
10
18 17
19
1 6 7
SACE PR111/P OVERCURRENT RELEASE
© A
BB
SA
CE
- 2
7
SACE Emax: Overcurrent releases
SACE PR111/P OVERCURRENT RELEASE
Thresholds and tripping times
FUNCTIONCurrent
thresholdsteps Tripping time Curves Cut-out relation t = f(I)
L I1 =0,4 1In 8 t1=3 18s (6xI1) 4 no t = k/I2
S I2 =1 10In 7 t2=0,05 0,5s (8xI2) 4 yes t = k/I2 e t = k
I I3 =1,5 12In 7 instantaneous - yes t = k
G I4 =0,4 1In 7 t3=0,1 0,8s 4 yes t = k/I2
© A
BB
SA
CE
- 2
8
COMPLETE RANGE OF PROTECTION FUNCTIONS (L, S, I, G)
VERSIONS AVAILABLE: - PR112/P L S I
- PR112/P L S I G
- PR112/PD L S I LON Protocol
- PR112/PD L S I G LON Protocol
- PR112/PD LSI ModBus RTU Protocol
- PR112/PD LSIG ModBus RTU Protocol
PR112PR112
SACE Emax: Overcurrent releases
© A
BB
SA
CE
- 2
9
SACE Emax: Overcurrent releases
MEASUREMENT FUNCTIONS: ammeter, contact wear, n° operations
SELF-POWERED DEVICE
SELF-PROTECTION AGAINST OVERTEMPERATURE
CONTROLLING AND MONITORING
MICROPROCESSOR SELF-DIAGNOSIS (WATCHDOG)
CERTIFICATED BY RINA, DNV,BV,GL,ABS
5 LANGUAGES DISPLAY
NEUTRAL SETTING BY DISPLAY
LOAD CONTROL AVAILABLE BY PR010/K
CONTACT K51/pl CONFIGURABLE
PR112PR112
© A
BB
SA
CE
- 3
0
SACE Emax: Overcurrent releases
SACE PR112/P AND PR112/PD OVERCURRENT RELEASES
9 10 11 12 1313
14
16 5 4 37 2
© A
BB
SA
CE
- 3
1
SACE Emax: Overcurrent releases
SACE PR112 OVERCURRENT RELEASE
Thresholds and tripping times
FUNCTION steps relation t = f(I)
L I1 =0,4 1In 0,01 t1=3 144s (3xI1) 3s no t = k/I2
S I2 =0,6 10 In 0,1 t2=00,75s (10xI2) 0,01s yes t = k/I2 e t = k
I I3 =1,5 15In 0,1 instantaneous - yes t = k
G I4 = 0,2 1In 0,02 t3=0,1 1s 0,05s yes t = k/I2 e t = k
Currentthreshold
Tripping time Steps Cut-out
© A
BB
SA
CE
- 3
2
VERSIONS AVAILABLE:
- PR113/P L S I G
- PR113/PD - M L S I G Modbus RTU
COMMUNICATION LINE
- RS485 with other Protocols
PR113 with LON protocol will available in future
PR113PR113
SACE Emax: Overcurrent releases
© A
BB
SA
CE
- 3
3
STANDARD RANGE OF PROTECTION FUNCTIONS (L, S, I, G)
(More current and time setting steps in functions)
NEW PROTECTIONS AVAILABLE:
V Minimum / Maximum / Residual voltage
F Unbalanced phase
P Inverse power flow
D Directional
NEUTRAL SETTINGNEUTRAL SETTING: 50% - 100% - 150% - 200%
PR113PR113
Protections
SACE Emax: Overcurrent releases
© A
BB
SA
CE
- 3
4
SACE PR113/P AND PR113/PD OVERCURRENT RELEASES
10 11
1
16
6 5 4
9
238 7
12 13 14 15
17
SACE Emax: Overcurrent releases
© A
BB
SA
CE
- 3
5
Ammeter
Voltages
Power (P - Q - A)
Harmonic distortion (20th)
PR113PR113
Measurements
Contact wear
N° Operations
Energy
5 Languages Graphic Display5 Languages Graphic Display NEW !!!
SACE Emax: Overcurrent releases
© A
BB
SA
CE
- 3
6
PR113PR113
Measurements
© A
BB
SA
CE
- 3
7
SACE Emax: Overcurrent releases
SACE PR111 & PR112 accessories
- SACE PR010/T Test Unit
- SACE PR010/K Signaling unit
- PR110/B Battery unit
© A
BB
SA
CE
- 3
8
SACE Emax: Overcurrent releases
SACE PR112 accessory unitSACE PR010/T
PROTECTION FUNCTION TESTING
TRIP TEST
PROGRAMMING FUNCTION
READING PARAMETERS FUNCTION
© A
BB
SA
CE
- 3
9
SACE Emax: Overcurrent releases
SACE PR112 accessory unitSACE PR010/K
EXTERNAL SIGNALING UNIT
- overload alarm function L- protection L tripped
- protection S tripped - protection I tripped - protection G tripped
- overtemperature (T=85°C)
LOAD CONTROL
- disconnection of two different loads- disconnection/connection of the same load
© A
BB
SA
CE
- 4
0
SACE Emax: Automatic Transfer Switch
© A
BB
SA
CE
- 4
1
What is ATS010:
• Automatic transfer switch device
• Microprocessor based
• All series of circuit-breakers
(Isomax, Tmax, Emax)
ATSG
1 2
LOAD
SACE Emax: Automatic Transfer Switch
© A
BB
SA
CE
- 4
2
SACE Emax: Terminals
Complete series of terminals
Modular design
Transformation kits available
© A
BB
SA
CE
- 4
3
SACE Emax: Terminals
Fixed version
Withdrawable version
© A
BB
SA
CE
- 4
4
SACE Emax: Accessories
A single range of accessories for the entire series
© A
BB
SA
CE
- 4
5
SACE Emax: Electrical accessories
Shunt Opening, Shunt Closing, Undervoltage releases
Circuit-breakers SOR Total
F1 - F2a.c.
MEGAMAXd.c.
F3 - F6a.c.
d.c.
EMAX E1 - E6 a.c./d.c.
12
2
SCR UVR
© A
BB
SA
CE
- 4
6
SACE Emax: Electrical accessories
- Opening/Closing release unified (YO/YC)
- Undervoltage release (YU)
© A
BB
SA
CE
- 4
7
SACE Emax: Electrical accessories
Shunt closing release (YC)
Undervoltage release (UVR)
Shunt closing release (YO)
Auxiliary releases
© A
BB
SA
CE
- 4
8
SACE Emax: Electrical accessories
- Time-delay device forundervoltage release
- SACE SOR Test Unit
© A
BB
SA
CE
- 4
9
SACE Emax: Electrical accessories
- Motor operator for automatic loading of closing springs
- Mechanical indication of Overcurrent release tripped
© A
BB
SA
CE
- 5
0
SACE Emax: Electrical accessories
Motor operator for automatic loadingof closing springs
© A
BB
SA
CE
- 5
1
SACE Emax: Electrical accessories
- Electrical indication of overcurrent release tripped
- Electrical signalling of circuit-breaker open/closed
© A
BB
SA
CE
- 5
2
SACE Emax: Electrical accessories
- Electrical signaling of circuit-breaker connected/test/disconnected position
- Contact for signaling closing springs loaded
© A
BB
SA
CE
- 5
3
SACE Emax: Electrical accessories
- Current transformer for external neutral
- External toroid for transformer star-centre (Source Ground Return)
© A
BB
SA
CE
- 5
4
SACE Emax: Mechanical accessories
- Operation counter
- Lock in open position (padlock or key lock devices)
© A
BB
SA
CE
- 5
5
SACE Emax: Mechanical accessories
- Lock in connected / test / disconnected position (padlock and key lock devices)
- Accessory for lock in disconnected /disconnected for test position
© A
BB
SA
CE
- 5
6
SACE Emax: Mechanical accessories
- Mechanical lock for compartment door
- Padlock device for safety shutters
© A
BB
SA
CE
- 5
7
SACE Emax: Mechanical accessories
- IP54 protective cover for door
- Protection for opening and closing push-buttons
© A
BB
SA
CE
- 5
8
SACE Emax: Electrical accessories
Current transformer set
© A
BB
SA
CE
- 5
9
SACE Emax: Mechanical accessories
Mechanical interlocks kits
© A
BB
SA
CE
- 6
0
SACE Emax: Mechanical accessories
1 2
1 2 3
G
1 32
G
1 2
Type A
Type B
Type C
Type D
O =Open Circuit-Breaker - I = Closed Circuit-Breaker
1 2 31 2 3
1 32
G
1 32
© A
BB
SA
CE
- 6
1
SACE Emax: Derived versions
• Switch-disconnector
• Isolating truck
• Earthing switch with making capacity
• Earthing truck
MS
CS
MTP
MT
MTCS MTP
© A
BB
SA
CE
- 6
2
SACE Emax: Special versions
For aggressive ambience (SO2)
For anti-seismic installations
For Navy
1000 V A.C.
1000 V D.C. (Switch disconnector only)
© A
BB
SA
CE
- 6
3
Special versionEMAX / E Ue=1000 V a.c.
SACE Emax: Special versions
E2B/E E2N/E E3H/E E4H/E
Iu [A] 1600 2000 1250 1600 2000 1250 1600 2000 2500 3200 3200 4000
Ue [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Icu [kA] 20 20 30 30 30 50 50 50 50 50 65 65
Ics [kA] 20 20 30 30 30 50 50 50 50 50 65 65
Icw [kA] 20 20 30 30 30 50 50 50 50 50 65 65
© A
BB
SA
CE
- 6
4
SACE Emax: “RETROFITTING”
Kits for simplified replacement of oldcircuit-breakers in the following series
SACE OtomaxSACE Novomax G30
With SACE Emax circuit-breakers
© A
BB
SA
CE
- 6
5
SACE Emax: Applications
POWER CENTER
© A
BB
SA
CE
- 6
6
SACE Emax: Applications
Generator/Motor protection
Transformer protection
Capacitor protection
Switching sets
Marine plants
© A
BB
SA
CE
- 6
7
SACE Emax: Applications
Automated installations
Installations characterized by high short circuit currents
Installations with special selectivity needs
Use in polluted environments
© A
BB
SA
CE
- 6
8
SACE Emax
SACE EMAX:SACE EMAX:THE THIRD MILLENIUMTHE THIRD MILLENIUM
IS IN THE AIRIS IN THE AIR