A0(A60) Fire Damper - STSbunkersts.com/data/goodsImages/14599994322.pdf · FDO - A0(A60) Fire...
Transcript of A0(A60) Fire Damper - STSbunkersts.com/data/goodsImages/14599994322.pdf · FDO - A0(A60) Fire...
FDO - A0(A60) Fire Damper
5
Halton FDO fire dampers are type-approved class A0(A60)
fire dampers for use in marine and offshore ventilation
systems. The FDO can be installed in circular ducts. All
fire dampers have a fusible link and they prevent the
spread of fire within the ventilation ductwork. When the
blade is in the open position, the device does not cause
significant pressure loss, noise or flow disturbance. Fire
dampers are set from outside and can be installed in
any position. An open-closed indicator is visible on the
outside of the damper.
•Type-approved by most recognized classification
societies, class A0 - A60 fire damper when suitably
insulated
•Fixed frame of painted, galvanized or stainless
steel. Blades stainless or galvanized steel. Flanges
available as an option.
•Blade contains seals (effective up to 270 ºC)
•Nominal fuse release temperature 50 ºC, 74 ºC
or 100 ºC. Other temperatures available.
•Very low leakage
•Automatic electrical, pneumatic or spring operation
system available
•Maximum duct pressure for damper construction
5000 Pa and maximum air velocity 15 m/s
FDOA0(A60) Fire Damper
PART MATERIAL FINISHING
Frame Carbon steel Painted or galvanised
Frame Stainless steel EN 1.4301 (AISI304), EN 1.4404 (AISI316L), EN 1.4432 (AISI316L) -
Blades Steel Galvanized
Blades Stainless steel EN 1.4301 (AISI304), EN 1.4404 (AISI316L), EN 1.4432 (AISI316L) -
Maintenance-free bearings Stainless steel EN 1.4404 (AISI316L) -
Shafts Stainless steel EN 1.4404 (AISI316L) -
FDO in picture with flanges (available as an option)
A
B
I
C
ØDE
I
F GG
T
3
Damper BladeAlt. positionof the actuator
H
A
C
I
I
FG G
T
Alt. Positionof the actuator
H
FDO - A0(A60) Fire Damper
6
FDO DIMENSIONS AND MATERIAL THICKNESS
FDO fire dampers meet international standards for
circular ducts (Ø100-500 mm). Sizes Ø100 and Ø125
are not available of stainless steel. Sizes starting from
GENERAL FDO DRAWING (without flanges)
FDO DRAWING (with flanges)
Ø160 can be manufactured with 1 mm division. Flanges
and drilling available as an option and according to ISO
15138 standards. Special flanges and drilling available on
request. Frame material thickness according to SOLAS.
FDO - A0(A60) Fire Damper
V6M
09Y
2015
/Hal
ton
Mar
ine
rese
rves
th
e ri
gh
t to
alt
er p
rod
uct
s w
ith
ou
t n
oti
ce.
7
FDO weight without flanges
Size ØD (mm) KG
100 4125 5160 4,5200 7,5250 9315 12400 17500 22,5
WEIGHTS OF STANDARD HALTON MARINE FDO DAMPERS (KG) without an actuator
Weights stated above do not include flanges or any actuator.Examples of actuator weights: FDO-EL CSQP +3,5 kg, BF230 +3,2 kg, BLF230 +1,7 kg, ExMax or RedMax or InMax +3,5 kg, FDO-PNR AT100 (AISI) +6,2 kg, AT50 (AISI) +3 kg, FDO-SP +1 kg.
FDO Dimensions with flanges (as an option)FDO-EL FDO-PNR FDO-SP
Dampersize
Inside dimensions
Bolt circle
Outside dimensions
Material thickness
Bolt holes
Bolt holes Qty
Housing Lenght
Blade Elodrive CSQP/Schischek
Belimo BF
Air Torque AT 50
Spring
Ø A B C T D E F G H I H I H I H I100 100,8 120 200 3,6 8,5 4 206 - 150 200 115 200 135 105 150 115125 125 150 225 4 8,5 4 206 - 150 200 115 200 135 105 150 115160 160 185 260 3 8,5 4 206 - 150 200 115 200 135 105 150 115200 200 225 300 3 8,5 4 326 - 150 200 115 200 135 105 150 115250 250 280 350 3 12 4 326 - 150 200 115 200 135 105 150 115315 315 355 415 3 12 8 326 - 150 200 115 200 135 105 150 115400 400 450 500 3 12 8 326 40 150 200 115 200 135 105 150 115500 500 560 600 3 12 12 326 90 150 200 115 200 135 105 150 115
FDO Dimensions without flanges (standard)FDO-EL FDO-PNR FDO-SP
Dampersize
Inside dimensions
Outside dimensions
Materialthickness
Housing Lenght
Blade Elodrive CSQP/Schischek
Belimo BF
Air Torque AT50
Air Torque AT100
Spring
Ø A C T F G H I H I H I H I H I100 100,8 108 3,6 200 - 150 200 115 200 145 215 165 215 150 115125 125 133 4 200 - 150 200 115 200 145 215 165 215 150 115160 160 166 3 200 - 150 200 115 200 145 215 165 215 150 115200 200 206 3 320 - 150 200 115 200 145 215 165 215 150 115250 250 256 3 320 - 150 200 115 200 145 215 165 215 150 115315 315 321 3 320 - 150 200 115 200 145 215 165 215 150 115400 400 408 4 320 43 150 200 115 200 145 215 165 215 150 115500 500 508 4 320 93 150 200 115 200 145 215 165 215 150 115
FDO weight with flanges
Size ØD (mm) KG
100 5125 6,5160 6200 9,5250 11315 14,5400 17500 22,5
FDO - A0(A60) Fire Damper
8
Size ØD (mm) Closed blade leakage Casing leakage
100 2 C125 2 C160 3 C200 3 C250 3 C315 3 C400 3 C500 3 C
FDO LEAKAGE CLASS ACCORDING TO STANDARD EN1751
FDO PRODUCT OPTIONS
Halton FDO is available with following actuators:
•FDO-EL: Electrical spring return motor; standard
actuators being 24 V or 230 V or 120 V. The motor
contains built-in open-closed limit switches. Separate
junction box included in the EL-model. A wide range
of eex-proof actuators available, including a one
second closing time function as an option.
•FDO-PNR: Pneumatic rotating actuator
•FDO-SP: Manual spring-actuated damper with fusible
link
DOT: manual override function available for PNR models.
A wide range of accessories available.
OPERATION PRINCIPLE
In the event of a temperature rise in ductwork:
•FDO-EL: fusible link releases and cuts off operating
voltage to the spring return motor, allowing the
spring to close the damper blades. The fire damper
opens automatically when the fuse has been
changed and the operating voltage to the motor is
re-established.
•FDO-PNR: fusible link releases and cuts off
operating pressure to the spring return actuator,
allowing springs to close the damper blades. The
fire damper opens automatically when the fuse
has been changed and the pneumatic air supply is
re-established.
•FDO-SP: fusible link releases allowing the spring to
close the damper blades. When the fuse has been
changed, the fire damper must be reset into open
position manually.
M16
S2 S3 S4 S5 S6S113 14
M20
M16M16
1 2 3 4
M16
EN
D C
LA
MP
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
1
1
11
11
EN
D C
LA
MP
1 2 3 4(-)(+)
(+) (-)
FUSIBLE LINK 74°C14
13
SIHF2 x 0,75 mm²
12
IP 545° 80°
S1 S2 S3 S4 S5 S6BELIMO
21BF24BF230BF120BLF24BLF230
DAMPERCLOSED
DAMPEROPEN
POWER SUPPLY120 V AC
MWHEN DAMPER IS NOT ENERGIZEDCONTACTS S1-S2, S4-S5 ARE CLOSED
2 x 0,75 mm² 6 x 0,75 mm²
13 14
EN
D C
LA
MP
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
1
1
11
11
EN
D C
LA
MP
NL
L N
32 1
FUS
IBLE
LIN
K14
13
SIHF
2 x 0
,75
mm
²
M16 M16M16
M16
M20
IP66
ELODRIVE CSQP-15A1E
21 3
N L1
T-
~+
15A2E10A1E10A2E05A2E05A2E
POWER SUPPLY120/230 V AC
3 x 0,75 mm²
FDO-EL WIRING DIAGRAM with Belimo actuatorFDO-EL WIRING DIAGRAM with Elodrive CSQP
FDO-EL WIRING DIAGRAM with ExMax or RedMax
actuator
3 x 0,75 mm²
WHEN DAMPER IS NOT ENERGIZEDCONTACTS S1-S2, S4-S6 ARE CLOSED
6 x 0,5 mm² 6 x 0,5 mm²
M20 M20
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
15
15
PE -E
ART
HIN
G R
AIL
EN
D C
LA
MP
EN
D C
LA
MP
BK GY BN 2 3 5 1 4 1 2 3 4 5 6PE
(+) (-)(PE) 1 2 3 4
POWER SUPPLY24-230V AC/DCL/+ N/- PE
M20M20M20
FUS
IBLE
LIN
K
BK
GY
BN
DAMPERCLOSED
DAMPEROPEN
2 3 41
PE 2 3 45 1 4 31 2
5°
5 6
85°IP 66
ExMax-15-SF
HEATER
RedMax-15-SF
FUSI
BLE
LIN
K 50
/74/
100°
C
14
13
1 2 3 4
EN
D C
LA
MP
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
PE2 3 5
1 2 3 4 5 6
PE 1 2 3 4
PE
PE
1
1
1 4
EN
D C
LA
MP
(+) (-)
13 14
PE(+) (-)~ ~
PE 2 3 45 1 4 31 2
5°
5 6
85°IP 66
InMax-15-SF
HEATERWHEN DAMPER IS NOT ENERGIZEDCONTACTS S1-S2, S4-S6 ARE CLOSED
6 x 0,5 mm² 6 x 0,5 mm²
M16 M16
M20
M16
M16
SIHF2 x 0,75 mm²
DAMPERCLOSED
DAMPEROPEN24-230 V AC/DC
FDO-EL WIRING DIAGRAM with InMax actuator
FDO-PNR PNEUMATIC DIAGRAM
FDO - A0(A60) Fire Damper
V6M
09Y
2015
/Hal
ton
Mar
ine
rese
rves
th
e ri
gh
t to
alt
er p
rod
uct
s w
ith
ou
t n
oti
ce.
9
SPRING RETURNACTUATOR
VALVESQUICK EXHAUST
VALVEFUSIBLE LINK
3 PORT/2 WAY
1
2
4
8
6
6
6
3
3
9
3 PORT/2 WAYSOLENOID VALVE
PNEU. INLET (5 - 8 BAR)
PIPELINES:POLYAMIDE
OPTION:5
6
6
3
6
6
10
3 PORT/2 WAYMANUAL VALVE
3
LIMIT SWITCHES
OPTION:
3
21 13
22 14 1422
21 13 OPENCLOSED
7
OPTION:
PRESSURE REGULATOR
24/220 V
8
8
8
6
6
FOR A PLASTIC TUBEØ6 MM
SPEED CONTROLLER
1. SPRING RETURN VALVE
2. QUICK EXHAUST VALVE
3. SILENCER
4. FUSIBLE LINK VALVE
5. OPTION: SOLENOID VALVE
6. MALE CONNECTOR
7. DOUBLE NIPPLE
8. PLASTIC TUBE. OPTION: STAINLESS STEEL
9. OPTION: OPEN / CLOSED SWITCHES
10. OPTION: MANUAL VALVE
11. PRESSURE REGULATOR
12. SPEED CONTROLLER
11
12
85°
109
24....230 VAC/DC
OPTION: 50/74/100°CFUSIBLE LINK
Schischek
(+)(-)
IP 665°
JUNCTION BOX
1211 13
~ ~
BLA
CK
BLU
E
BR
OW
N
2 3 5 1 4PE S1 S3S2 S5 S6S4
PE
(BARTEC)
1
M20M20
M20 M20
PE
CLOSED AND OPENEDINFORMATION OUT
1486 732 4 5
PE 32 15 S14 S5S3S2 S4 S6BK BE BN
M20
151 2 3 4 5 6 7 8
S6S5S4S3S2
M 87°
109
THERMAL FUSESM-072-A0-2A (72°C)
OPTION: 50/74/100°CFUSIBLE LINK
AC24V
(+)(-)
IP 54
3°
S1
JUNCTION BOX
11
DC24...48VDAMPERCLOSED
DAMPEROPEN
M16 M16 M16
M20 M16
(+)
(-)
S6S5S4S3S2S1
1 2 3 4
1 2 3 4
2(4)
1(3)
2(4)
1(3)
SIEMENSGGA.126.1E/HAGGA226.1E/HAGGA326.1E/HAGNA126.1E/HAGNA326.1E/HA
AC120VAC230V
1 2 3 4 5 6 7 8
S6S5S4S3S2
M 87°
109
THERMAL FUSESM-072-A0-2A (72°C)
OPTION: 50/74/100°CFUSIBLE LINK
AC24V
(+)(-)
IP 543°
S1
JUNCTION BOX
11
DC24...48VDAMPERCLOSED
DAMPEROPEN
M16 M16 M16
M20 M16
(+)
(-)
S6S5S4S3S2S1
1 2 3 4
1 2 3 4
1 2
1 2
BELIMOBF24 / BF120 / BF230BLF24 / BLF230
AC120VAC230V
FDO - A0(A60) Fire Damper
10