A001-MNC Siemens Chiller
Transcript of A001-MNC Siemens Chiller
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
© KKT KRAUS Kälte- und Klimatechnik GmbH page 1
KKT WaterChiller forMAGNETOM Avanto 1.5T - A Tim SystemMAGNETOM Espree 1.5T - A Tim SystemMAGNETOM Trio 3T - A Tim SystemMAGNETOM Verio 3T - A Tim System
KSC 215-L-U/S (US Market)
KSC 215-L-S (R.O.W. Market)
Siemens AG - Healthcare Sector
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
page 2 © KKT KRAUS Kälte- und Klimatechnik GmbH
The illustrations of products of the Siemens company
are shown with friendly permission by Siemens AG - Healthcare Sector.
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
© KKT KRAUS Kälte- und Klimatechnik GmbH page 3
List of Contents
Page 5 Description of KKT WaterChiller
Page 6 Nameplate KSC 215-L-U/S
Page 7 Technical Data KSC 215-L-U/S
Page 8 Nameplate KSC 215-L-S
Page 9 Technical Data KSC 215-L-U/S
Page 10 Dimensions KSC 215 (inch)
Page 11 Dimensions KSC 215 (mm)
Page 12 Key: Cold Water/Glycol Diagram
Page 13 Cold Water/Glycol Diagram
Page 14 Key: Refrigerant Diagram/Compact Design
Page 15 Refrigerant Diagram/Compact design
Page 16 WaterChiller Installation I
Page 17 WaterChiller Installation II
Page 18 IFP (Manufacturer Kutting)
Page 19 IFP (Manufacturer Kutting)
Page 20 Overvolting Protection
Page 21 Overview of WaterChiller Transfer Station/Remote Control Panel
Page 22 Transport
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
page 4 © KKT KRAUS Kälte- und Klimatechnik GmbH
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
© KKT KRAUS Kälte- und Klimatechnik GmbH page 5
The KKT WaterChillers are designed, developed and produced as a compact system for the MAGNETOM Avanto/Espree/TaTs/Verio. KKT WaterChillers are suitable for outdoor installations. Power supplies of 380V - 480V/50-60Hz. UL approved version is 480V/60Hz. Ambient temperatures up to 118.4 °F [48 °C]. Produced and testet in accordance with Siemens AG - Healthcare Sector specifi cations.
frontal operation•
mainly Siemens products in the switch box•
totally integrated automation with display (Siemens S7)•
operator panel•
separate fault alarm•
switch box heater/fans•
UPS operation - optional extra, available through our customer •
service department (low starting current)
no fuses (only automatic fuses/circuit• breakers)
wired on clamps•
cooling circuit including pump, regulation valve, fi lter strainer, •
shut-off fi ttings, automatic air vent, fi ll and outlet valves and
pressure gauges
expansion receiver, safety valve•
fl ow control•
overheating protection •
2 separate cooling circuits 50/50 %•
partial/emergency cooling possible with one compressor•
high quality safety and control instruments•
R 134a „Ozon Safe Refrigerant“•
Description of KKT WaterChiller - Outdoor Version
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
page 6 © KKT KRAUS Kälte- und Klimatechnik GmbH
Nameplate KSC 215-L-U/S
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
© KKT KRAUS Kälte- und Klimatechnik GmbH page 7
Technical DataWaterChiller Typ KSC 215-L-U/S outdoor usedesigned for MAGNETOM Avanto/Espree/TaTS/Verio
Standard Device Standard Note Construction Nominal cooling capacity (Btu/hr [kW]) 205,000 [60.0] Refrigeration medium R 134a Quantity of compressors 2 Compressor capacity (HP [kW]) 18.2 [13.4] Fabr.: DWM Type: ZR 16 Volume of condenser airfl ow (m³/s [m³/h]) 10.0 [36,000] Number of axial fans (piece) 4 Condenser fan motor (HP [kW]) 1.54 [1.15] Max. ambient air temperature (°F [°C]) +118 [+48] Min. ambient air temperature (°F [°C]) -4.0 [-20] Cooling medium PCW/AFN PKW/AFN AFN = 35 - 38% mono ethylene glycol rate
Min. cooling medium out (°F [°C]) +66.2 [+19.0] Max. cooling medium out (°F [°C]) +71.6 [+22.0] Temperature stabilty (K) ±0.5 Min. volume of cooling medium (gpm [l/min]) 34.34 [130.0] Ext. pump pressure (psig [bar]) 58.0 [4.0] Pump power (HP [kW]) 4.0 [3.0] Noise level (dB[A]) 61 abt. 32.8 ft [10m] distance/ 118°F [48°C] 55 abt. 32.8 ft [10m] distance/ 90°F [32°C] 50 abt. 32.8 ft [10m] distance/ 70°F [21°C]
Power supply (V/Ph/Hz) 480/3/60 tolerance -14/+10%V/±1 Hz Control voltage (VDc) 24 Full load amps (A) 58.5 Form of protection IP 54 Internal piping volume (gals. [l]) 4.49 [17.0] Plumbing 2” Shipping weight (lbs [kg]) 3,490 [1,583] Operation weight (lbs [kg]) 2,425 [1,100]
WarningThe 35 - 38% Glycol rate does not depend on the local ambient temperature!
Do not use Propylene Glycol or automotive antifreeze.
Never mix different types or brands of Glycol.
R 134a120.47 inch
3,060 mm
37.80 inch960 mm
72.0
5 in
ch1,
830
mm
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
page 8 © KKT KRAUS Kälte- und Klimatechnik GmbH
Nameplate KSC 215-L-S
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
© KKT KRAUS Kälte- und Klimatechnik GmbH page 9
Technical Data
WaterChiller Typ KSC 215-L-S outdoor usedesigned for MAGNETOM Avanto/Espree/TaTs/Verio
Standard Device Standard Note Construction Nominal cooling capacity (Btu/hr [kW]) 205,000 [60.0] Refrigeration medium R 134a Quantity of compressors 2 Compressor capacity (HP [kW]) 21.7 [16.0] Fabr.: DWM Type: ZR 19 Volume of condenser airfl ow (m³/s [m³/h]) 10.0 [36,000] Number of axial fans (piece) 4 Condenser fan motor (HP [kW]) 1.54 [1.15] Max. ambient air temperature (°F [°C]) +118 [+48] Min. ambient air temperature (°F [°C]) -4.0 [-20] Cooling medium PCW/AFN PKW/AFN AFN = 35 - 38% mono ethylene glycol rate
Min. cooling medium out (°F [°C]) +66.2 [+19.0] Max. cooling medium out (°F [°C]) +71.6 [+22.0] Temperature stabilty (K) ±0.5 Min. volume of cooling medium (gpm [l/min]) 34.34 [130.0] Ext. pump pressure (psig [bar]) 58.0 [4.0] Pump power (HP [kW]) 4.0 [3.0] Noise level (dB[A]) 61 abt. 32.8 ft [10m] distance/ 118°F [48°C] 55 abt. 32.8 ft [10m] distance/ 90°F [32°C] 50 abt. 32.8 ft [10m] distance/ 70°F [21°C] Power supply (V/Ph/Hz) 380-480/3/50 tolerance -14/+10%V/±1 Hz Control voltage (VDc) 24 Full load amps (A) 55.0 Form of protection IP 54 Internal piping volume (gals. [l]) 4.49 [17.0] Plumbing 2” Shipping weight (lbs [kg]) 3,600 [1,633] operation weight (lbs [kg]) 2,535 [1,150]
WarningThe 35 - 38% Glycol rate does not depend on the local ambient temperature!
Do not use Propylene Glycol or automotive antifreeze.
Never mix different types or brands of Glycol.
R 134a120.47 inch
3,060 mm
37.80 inch960 mm
72.0
5 in
ch1,
830
mm
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
page 10 © KKT KRAUS Kälte- und Klimatechnik GmbH
Dimensions KSC 215 (inch)
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
© KKT KRAUS Kälte- und Klimatechnik GmbH page 11
Dimensions KSC 215 (mm)
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
page 12 © KKT KRAUS Kälte- und Klimatechnik GmbH
safety relief valve (water)
automatic air vent
back flow preventer
manual air vent
filling and draining cock
shut-off valve
TA regulating valve
filter strainer
advanced cooling system (Siemens)
evaporator
air receiver with automaticair vent
TT
PI
temperature sensor
pressure gauge
expansion receiver
flow meter
high pressure pump
FS
H
H
interface panel
overflow valve
ACS
IFP
Key: Cold Water/Glycol Diagram
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
© KKT KRAUS Kälte- und Klimatechnik GmbH page 13
Cold Water/Glycol Diagram
C6134_08-11-04
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
page 14 © KKT KRAUS Kälte- und Klimatechnik GmbH
Key: Refrigerant Diagram
Schrader valve
moisture indicator
inspection gauge with
refrigerant dehydrator
no return valve
vibration absorber
refrigerant shut-off valve
evaporator
receiver
with cap
PZAHH
suction gas line
liquid line
hot gas line
high pressur cut out
low-/high pressure sensor
compressor
condenser with fan
Rotalock valve
hot gas bybass valve
PTHPTL
R134a
TC
electronic expansion valve
variable speed control
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
© KKT KRAUS Kälte- und Klimatechnik GmbH page 15
Refrigerant Diagram
System 1
System 2
condenser 2 condenser 1
el.
PTH
P ZA HH
el.
PTH
PTHPTL
PTHPTL
PZA HH
M M MM
PTL
PTL
TT
TT
TC
TC
evaporator 1
evaporator 2
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
page 16 © KKT KRAUS Kälte- und Klimatechnik GmbH
WaterChiller Installation I
min.3,260mm
concrete bed
adjusted according to local codes.
keep free for service
operator control panel
37.80inch
Dimensions for the concrete bed should be
keep free
min.1,000mm
960mm
min.1,160mm
min.1,000mm
3,060mm
min.200mmmin.8.00inch
~1,830mm
air outlet
Always keep unobstructed
min.40.00inch
min.40.00inch
min.4.00inchmin.100mm
120.47inch
min.128.47inch
~72.05inch
min.45.80inch
sound absorbant mat
min.400mm
min.15.75inch
min.400mm
min.15.75inch
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
© KKT KRAUS Kälte- und Klimatechnik GmbH page 17
WaterChiller Installation II
installation example C
installation example B
installation example A
free access for servicing
free access for servicing
Air outlet must be kept free!
min.
40
inch
min.1000mm
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
page 18 © KKT KRAUS Kälte- und Klimatechnik GmbH
IFP - Manufacturer
For further information contact Siemens Customer Support.
Connector Fittingslocated inside KKT WaterChiller
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
© KKT KRAUS Kälte- und Klimatechnik GmbH page 19
IFP - Manufacturer
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
page 20 © KKT KRAUS Kälte- und Klimatechnik GmbH
Overvoltage Protection
X8 Chiller Cabinet
X81 ACC Roof
Overvoltage Protector
Grounding Wire
Data Transfer Cable(164 ft/50 m)
Filter out
Filter in
Grounding Wire Connection
Main BoxGrounding Bus
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
© KKT KRAUS Kälte- und Klimatechnik GmbH page 21
Overview of WaterChillerTransfer Station/Remote Control Panel
= delivered with chiller
= not scope of delivery KKT
2
data transfer cable
main power
recommended
interface station
2
for water pipes
< 45m/148ft
> 45m/148ft consult KKT
pipe dimensions
technic room
one way distance
indoor
outdoor
2 1/2"/65mm*
ASC SiemensXGE 42-LR 1 1/2"
2"
2"
KSC 215-L...
IFP
1
= scope of delivery KKT1
3
4
= delivered with chiller
15 x AWG 26,
4
3
2"/50mm*< 25m/82ft
4
164ft50m
Cu-pipe with insulation
protectorovervoltagedata transfer cable
data transfer cable
mains box
ACC
X81 X80
data transfer cable
X810IFP
15 x AWG 26,23ft7m
ground
* use only long turn ellbows
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
page 22 © KKT KRAUS Kälte- und Klimatechnik GmbH
Transport
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
© KKT KRAUS Kälte- und Klimatechnik GmbH page 23
H:\Marketing\Drucksachen\Prospekte\Geraete\KSC 215_11-2008
page 24 © KKT KRAUS Kälte- und Klimatechnik GmbH
Technical development may cause changes of confi guration.
KKT KRAUS GermanyKälte- und Klimatechnik GmbHIndustriestraße 23 a • D-91207 Lauf
Phone +49 9123 174-01Fax +49 9123 174-174E-Mail [email protected] www.kkt-kraus.com
KKT KRAUS USA Corp.1351 Brummel Ave.Elk Grove • IL 60007
Phone +1 847 734 1600Fax +1 847 734 1601Toll Free +1 866 517 6867
Certifi ed according DIN EN ISO 9001