A Posteriori Modelling of the Growth Phase of Dalmarnock Fire Test One

download A Posteriori Modelling of the Growth Phase of Dalmarnock Fire Test One

of 9

Transcript of A Posteriori Modelling of the Growth Phase of Dalmarnock Fire Test One

  • 7/24/2019 A Posteriori Modelling of the Growth Phase of Dalmarnock Fire Test One

    1/9

  • 7/24/2019 A Posteriori Modelling of the Growth Phase of Dalmarnock Fire Test One

    2/9

    et al.[14]found temperature proles, smoke layer heights and gas

    species concentrations in a 10 10 5 m compartment predictedby FDSv4 to be in good agreement with experimental data for the

    burning of pool res (heptane or toluene) and single cribs (PMMA

    or wood). The measured mass loss rate of the fuel was used to

    calculate the HRR, which was then input into the model.

    Theevaluationof the entire process ofre modelling, in which the

    mathematical model is only a component, is an important taskfor the

    advancement ofre safety engineering. The state of the art of re

    modelling is reected not only in the mathematical models capa-

    bilities, but also on how it is implemented throughout the different

    stages ofre modelling[9].The assumptions made by the user, the

    collection of data for input and the selection of the parameter valuesare crucialcomponents leading to the creation of the inputle.Thisis

    particularly important when advanced and complex computational

    tools areused (e.g. CFDand evacuationmodelling). Under the current

    state of the art, there are many ill-dened and uncertain parameters

    within the models which cannot be rigorously and uniquely deter-

    mined. Thus, there is plenty of space for uncertainty and doubt to

    unravel, and for curvetting and arbitrary parameter value selection

    to take place. This is summarised best in the words attributed to the

    German scientist Carl Friedrich Gauss (1777e1855): Give me four

    parameters, and I will draw anelephant for you; withveI willhave him

    raise and lower his trunk and his tail.

    This paper reports a series of CFD simulations (with FDSv4) con-

    ducted a posteriori to reproduce the large-scale Dalmarnock Fire Test

    One thatinvolved several real burningitems leading to a complex respread process. The HRR of the growth phase was not measured. But

    because the compartment was densely instrumented, it provides

    a veryrich set ofdata thatcouldbe usedto aid dening the HRR of the

    re source and uncertain parameters to reproduce the main features

    of the re. A key difference between previous modelling studies of

    large-scale tests and the present work is that the heavily instru-

    mented full-scale Dalmarnock Fire Tests provides for the rst time

    measurements at sufcient spatial resolution to be suitable for

    comparison witheld models at the grid size level.

    2. Dalmarnock Fire Test One

    Detailed information about the experimental set-up and the

    chain of events that occurred during the Test One can be found

    elsewhere[15,16], but a short summary is given here. Test One was

    held in a two-bedroom single family at, with the living room

    set-up as the main experimental compartment. This compartment

    was 3.50 m by 4.75 m wide and 2.45 m high and made of concrete

    walls. It had two-pane windows as shown inFig. 1. While the main

    source of fuel was a two-seat sofa stuffed with exible poly-

    urethane foam, the compartments also contained two ofce work

    desks with computers, each with its own foam-padded chair, three

    tall wooden bookcases, a short plastic cabinet, three small wooden

    coffee tables, a range of paper items and two tall plastic lamps. A

    plastic waste paper basket lled with crumpled newspaper and

    300e500 ml of heptane was the ignition source. The re spread to

    a blanket on the sofa hanging into the basket, igniting the seatingarea of the sofa. After about 275 s the bookshelf next to the sofa

    ignitedand was rapidly engulfed in re. Within 25 s afterignition of

    the bookshelf the compartment reached ashover conditions (see

    Table 1for a time line of the events).

    Fig. 2shows the HRR, the average temperature of the hot layer

    and the vertical distribution of temperatures along one specic

    thermocouple rack measured in Test One. A detailed presentation

    of the data can be found in[15,16]. The HRR in the re tests was

    estimated by the principle of oxygen depletion, using the

    measurements from the gas velocity probes at all the ventilation

    openings and assuming total O2 consumption[16]. An estimation

    for the post-ashover re results in about 3 MW before the rst

    window breakage, and about 5 MW after the second breakage as

    shown inFig. 2. During the growth phase the assumption of totalO2 consumption does not hold, as the re is not ventilation

    controlled, thus the evolution of the HRR during re growth is

    unknown.

    Fig. 1. Room layout with location of furniture and sensors [15,16].

    Table 1

    Time line of main events during Dalmarnock Test One [15,16].

    Event Time from ignition (s)

    Ignition 0

    Cushions ignite 9

    Bookcase ignites 275

    Fire engulfs bookcase (ashover) 300

    Compartment window breakage (NW Pane) 800

    Compartment window breakage (SW Pane) 1100

    Extinction 1140

    W. Jahn et al. / Building and Environment 46 (2011) 1065e10731066

  • 7/24/2019 A Posteriori Modelling of the Growth Phase of Dalmarnock Fire Test One

    3/9

    Prior to Test One, laboratory experiments were conducted in

    order to determine the HRR curves for the sofa and the book-

    shelves inside the furniture calorimeter (using an exact replica of

    those used in Test One) [15]. A second series of laboratory

    experiments was conducted after Test One in order to analyse

    variations to the ignition protocol[17]. These two sets of experi-

    ments were the only direct source of information on the HRR in

    Test One.

    Fig. 3shows the evolution of the HRR of the sofa and the effect of

    variations to the ignition source. The experiment conducted prior to

    Test One (referred to as Set 1) consisted of a sofa with two cushions,

    and a waste paper basket located next to the sofa. Accelerant was

    poured into the paper basket and the basket was ignited. The re

    then spread over the armrest to the sofa and was stopped about

    800 s after ignition when approximately one third of the sofa had

    been burnt. In the experiments conducted after Test One (referred to

    as Set 2), the exact ignition protocol of Dalmarnock Test One was

    replicated, which was like Set 1 but including a blanket that had

    been placed over the armrest of the sofa, and the accelerant

    distributed between basket and blanket. The presence of the blanket

    in Set 2 allowed the re to bypass the armrest re barrier and led to

    a faster growth rate involving the cushions. The re growth rate for

    Set 2 is equivalent to a t-squared re with growth constant 1.6 W/s2

    (a mediumre [18]).The constantin Set 1 is 0.5 W/s2 (corresponding

    to a slow re[18]). The two tests show that the uncertainty in the

    growth rate of the sofa re during the early stages is signicant and

    varies between a slow and a medium re.

    Fig. 3suggests two patterns in the burning behaviour; an initial

    peak that rapidly decreases is followed by a growing re that

    resembles a t-squared curve. A similarbehaviour can be seen forSet

    2. It is conjectured that the initial peak corresponds to the waste

    paper basket, accelerant and the blanket (in the case of Set 2), while

    the t-squared re corresponds to the sofa itself.

    By measuring ame heights from visual recordings, it can be

    established that the sofas HRR in Set 1 grew slower than the

    observed re in Test One. Flashover in Test One occurred at 300 s.

    According to Set 1, this is only 100 s after the period when the basket

    re dominated the HRR. Comparison of the re development using

    the video available of both resconrms this. At the initial laboratory

    experiment no blanket was used, so that the re could not spread

    across thearmrest to the cushions as fast. The re in Dalmarnock Test

    One spread quickly from the basket over the armrest to the sofa,

    whereas in Set 1, the ames took considerably longer to spread over

    the armrest.

    3. A priori vs. a posteriori modelling

    Before the Dalmarnock Tests were carried out, a round-robin

    study of blind predictions [9] was conducted in order to explore the

    a priori predictive capabilities ofre modelling in realistic scenarios.

    The aim of the exercise was to forecast the re development as

    accurately as possible and compare the results. Comparison of the

    modelling results showed a large scatter and considerable disparity

    among the predictions, and between predictions and experimental

    measurements. Thescatter of the simulations was much largerthan

    the error and variability expected in the experiments. The studyemphasized on the inherent difculty of modelling re dynamics in

    complex re scenarios like Dalmarnock, and showed that the

    accuracy of blind prediction ofre growth (i.e. evolution of the heat

    release rate) is poor.

    The present work revisits the modelling of the Dalmarnock Fire

    Test One, this time using the large set of measurements available.

    That is, the work is conducted a posteriori. Many different simula-

    tions are conducted and many parameters are adjusted and read-

    justed until acceptable agreement is reached. Work is focused only

    on the growth phase of the Dalmarnock Fire Test One.

    a b c

    Fig. 2. Measurements from the Dalmarnock Test One: a) estimated HRR (using oxygen consumption), b) average temperature of the hot layer in the main compartment (corrected

    for radiation) and c) vertical temperature distribution in front of the compartment door at 600 s[15,16](rack 4, seeFig. 1).

    a b

    Fig. 3. Measured HRR for variations to the ignition source and equivalent t-squared res: a) measured in the laboratory prior to Test One including sofa and waste basket (Set 1);

    and b) after Test One including the sofa, waste basket and blanket (Set 2).

    W. Jahn et al. / Building and Environment 46 (2011) 1065e1073 1067

  • 7/24/2019 A Posteriori Modelling of the Growth Phase of Dalmarnock Fire Test One

    4/9

    As mentioned before, during the growth phase of Test One

    the evolution of the HRR is unknown. Moreover, the laboratory

    experiments of the sofa and similar ignition sources show signi-

    cant uncertainty. Indeed, this is one of the most important issues

    addressed in this article. The challenge is to be able to reproduce

    the HRR such that the re environment (temperature and smoke)

    is simulated correctly. The work solves a large and complex inverse

    problem by trial and error.

    4. Computational model

    The code Fire Dynamics Simulator v4.07 [19,20], one of the most

    commonly used re CFD codes, is used here. FDS solves a form of

    the NaviereStokes equations adequate for low-speed thermally

    driven ows. While large eddies are solved directly, turbulences at

    subgrid scale are modelled using Smagorinskys approach[21].

    FDS is a tool still under active development, and improved

    versions are released with some frequency. At the time this paper

    goes to press, FDSv5 had been released and FDSv6 is expected

    soon. But research has a characteristic time that seems to be longer

    that the time between version releases of FDS. This means that by

    the time a research project has been completed and conclusionshave been reached, newest versions might be available. While not

    all of the ne results of this paper might apply directly to FDSv5 or

    FDSv6, the merit of the study is that the bulk of the conclusions

    relate to the signicant amount of papers in the technical litera-

    ture where FDSv4 was used, and to current re safety engineering.

    This last is particularly important for infrastructure designed,

    approved and built, and to forensic ndings agreed on with the aid

    of FDSv4.

    The computational domain used reproduces in detail the main

    Dalmarnock compartment (Fig. 4) and includes the vent openings

    (two-pane windows to the exterior), the nearby kitchen (with

    another window to the exterior) and the hallway connecting to

    the apartment entry. It was considered that the other rooms of

    the apartment did not contribute signicantly to the re dynamics

    and therefore were not included. The fuel load in the main

    compartment was reduced to the fuel elements involved in the

    growth phase; the sofa, the ignition source and two bookshelves in

    the corner behind the sofa. The other fuel items, the computers,

    coffee table, chairs and desks contributed to the re only after

    ashover, and therefore are outside the scope of this work.

    The compartment walls and ceiling were modelled as 10 cm

    thick concrete, and the compartment ooras covered with a carpet.

    Open boundary conditions were used at the exterior of the

    compartment at some distance from the building facades.

    FDS models combustion based on a mixture fraction approach

    [19] with a single-step instantaneous reaction chemistry. While the

    Dalmarnock Fire Test One contained several dozen different

    fuels burning at the same time, FDSv4 only allows for one single

    fuel. Thus, as an overall representative, propane was assumed as

    fuel (FDS default fuel) with combustion reaction:

    C3H8 5O2/3CO2 4H2O (1)The time variation of the HRR is imposed as a ramp of the fuel

    injection, while there area is assumed constant at 2/3 of theseating

    area of the sofa. Because there area affects the air entrainment into

    the ame, in principle, it should be changed in time as well. This has

    been shown in previous sensitivity studies with FDSv4 [22].However, the uncertainty in the actual rate of change of the re area

    is large. Therefore, it has not been considered here for the sake of

    simplicity but its effects can be investigated in future studies

    together with other uncertain combustion, turbulence and radiation

    parameters within FDS.

    The grid size is one of the most critical parameters in numerical

    simulations.In the scope of this work a large number of simulations

    had to be run in order to converge toward good agreement with the

    measured data and it was therefore necessary to use a sufciently

    coarse grid allowing for an efcient use of computational resources.

    However, too coarse a grid could induce signicant numerical

    errors in the solution. It has been proposed[23,24]that to resolve

    the re plume properly, the ratio between the characteristic re

    diameter, D*, and the gridsize shouldbe atleast5 to10, where D* is

    dened as:

    Fig. 4. Computational domain and fuel items used in the FDS simulations.

    W. Jahn et al. / Building and Environment 46 (2011) 1065e10731068

  • 7/24/2019 A Posteriori Modelling of the Growth Phase of Dalmarnock Fire Test One

    5/9

    D*

    Q$

    rN

    cpTNffiffiffigp

    2=5: (2)

    During the growth phase, the peak of the HRR is 300 kW, and

    the characteristic diameter of the sofa is around 0.6 m. Hence the

    grid size should be smaller than 11 cm for an adequate plume

    resolution. This value is used as an order of magnitude reference. In

    order to select an adequate grid size, simulation were run with

    a wide range of different grid sizes: 5 cm, 10 cm, 15 cm and 20 cm

    edge cubes. The 10 cm grid size resulted in 120,000 cells, and the

    number of cells in other grids scales with the inverse of the cube of

    the grid size. The HRR was prescribed according to the laboratory

    experiment Set 1.

    Fig. 5 shows the temperature vs. height distribution at two

    different locations in the experimental compartment, one near the

    burning sofa, and one near the window away from there. See Fig.1

    for rack locations. The time of comparison is 140 s, and data are

    averaged in time (10 s) in order tolterout inconsistent uctuations.

    The simulations using coarser grids (15 and 20 cm) actually showed

    better agreement when compared to the measured data, both

    qualitatively and quantitatively than the ner grids (5 and 10 cm).

    Near the re (Fig. 5a), the 20 cm and 15 cm grids are in agreement

    between them and reproduce well the lower zone temperatures andthe smoke layer height, but overpredict the temperatures of the

    smoke layer by 17%. The 10 cm grid underpredicts the smoke layer

    height by around 15%, but is in good agreement regarding the smoke

    layer temperature. The 5 cm grid underpredicts the measurements

    by more than 35% at all heights. Away from the re (Fig. 5b), the 10,

    15 and 20 cm grids are in reasonable agreement to the measure-

    ments, while the 5 cm grid shows divergence both quantitatively

    (>30%) and qualitatively.

    Based on this grid dependency study, the 10 cm grid was chosen

    because it showed good comparison to the experiments, allowed

    for fast computations and complied with the recommendation

    associated to the characteristic re diameter [23,24]. Given the

    present results, there are no good reasons to choosea different grid,

    but most validation studies by the FDS developers had been con-ducted with similar grid sizes to this.

    We cannot explain why the coarser grids in this case provide

    lower global errors. While it is generally accepted for numerical

    integration that a smaller grid yields more accurate results, FDS

    results are known to dependsignicantly onthe size of thenumerical

    grid due to the LES approximation[25,24]. A possible explanation is

    that the LES Smagorinsky constant used by default in FDS was cali-

    brated to predict smoke movement in a very large enclosure and

    away from the ames [26]. This is a very different scenario to theDalmarnock Test One and the constant might need recalibration.

    All other parameters not discussed here were left with the

    default values in FDSv4.

    5. Hot layer average temperatures

    Two distinct levels of detail are analysed. This section predicts

    the average hot layer temperature while the next section looks at

    the distribution of local eld temperature and wall heat uxes.

    Comparison at detailed level requires a good agreement at aver-

    aged level rst.

    As seen in the Set 1 and Set 2 experiments, the blanket signi-

    cantly modies the HRR. A possible HRR of the blanket alone can

    be estimated assuming quadratic growth and decay phases. Theblanket, made of cotton, weighed 1 kg, hence the total combustible

    energystored in the blanket including 100 ml of accelerant can be

    estimated to be around 21 MJ [22], assuming a heat of combustion

    of 16.5 MJ/kg for the cotton. The resulting peak HRR would be

    150 kW. This is not negligible compared to the measured HRR of

    the sofa in the early stages, and should therefore be included

    in the input HRR for the model. Fig. 6shows the reconstructed HRR

    of the blanket alone and its addition to the HRR of Set 1. The

    a b

    Fig. 5. Comparison of results with different grid sizes at 140 s: a) distribution at the north wall next to the bookshelf (rack 1); and b) distribution near the window (rack 17).

    Fig. 6. Addition of the blanket to the HRR measured in Set 1 (Measured sofare) to

    obtain Set 1b (combined re).

    W. Jahn et al. / Building and Environment 46 (2011) 1065e1073 1069

  • 7/24/2019 A Posteriori Modelling of the Growth Phase of Dalmarnock Fire Test One

    6/9

    resulting HRR is referred to as Set 1b. Note that here the data is

    shifted by 150 s compared to Fig. 3, sothat the ignitionoccurs at0 s.

    The predicted hot layer average temperature using different

    HRR and comparison to measurements are shown in Fig. 7.For the

    Set 1 (Fig. 7a), the simulated hot layer temperature rise agrees with

    the measurements during the rst 100 s. The predicted average

    temperatures after t 100 s are lower that measured (up to 50%error). For Set 1b (Fig. 7b), the simulated hot layer temperatures are

    in good agreement with the measured temperatures (within theinstrumental uncertainty) until 200 s into the re. After that, the

    simulated temperature decreases in contrast to the measured

    temperature which rises continually until ashover. For Set 2

    (Fig. 7c), the average hot layer temperature is overpredicted by

    about 50% between 25 s and 100 s, and by about 35% between 150 s

    and 250 s.

    Overall, it is seen that Set 1 results in unrealistically low average

    temperatures for the hot layer, but Set 1b and Set 2 provide predic-

    tions closer to the measurements. Thus, it is concluded that Set 1b

    provides a lower bound to the HRR curve during the growth phase,

    while Set 2 is an upper bound. This range captures the intrinsic

    uncertainty ofre growth in real complex scenarios and alsoincludes

    experimental variability. The uncertainty in the average temperature

    predictions using these HRRbounds is between0 and50%. It conrms

    that to predict temperatures with reasonable agreement, the HRR

    must be well characterized.

    6. Comparison of local measurements

    The density of measurements in Test One presents an oppor-

    tunity to assess eld level simulations.Fig. 8shows the tempera-

    ture vs. height distributions at different locations (three vertical

    thermocouple racks) in the experimental compartment using the

    two bounding HRR curves Set 1b and Set 2. Two different times,

    150 s (HRR plateau) and 200 s (rapid HRR rise), are chosen arbi-

    trarily for illustration purposes. In general the simulations are inreasonable agreement with the measurements, although it can be

    seen that the further away from the burning sofa the better the

    agreement between measurements and simulations.

    As expected the lower and upper HHR bounds result in upper and

    lower bounds for the smoke temperatures. It is observed that the

    thickness of the hot layer is not signicantly affected by the HRR

    within the bounds, but the upper HHR leads to higher temperatures

    in smoke. Within the cold layer, the simulations underpredict the

    temperature even for the upper HHR bound. This indicates that the

    Dalmarnock FireTest had a less well dened hot layer thanpredicted.

    At thermocouple rack 7, roughly 1.5 m from the re, the

    temperatures are underpredicted by 20e200% at 150 s (Fig. 8a)

    when using both the lower HRR bound (Set 1b) or the upper HRR

    bound (Set 2). At rack 11, near the centre of the compartment, and

    150 s into the re (Fig. 8b) the simulations with both input HRR

    curves are in good agreement with the measured data lying within

    Fig. 7. Predicted average hot layer temperatures; a) Set 1; b) Set 1b and c) Set 2.

    Fig. 8. Temperature vs. height distribution at different locations in the compartment at 150 s (a, b and c) and 200 s (d, e and f). Thermocouple rack 7 (a, d) is located near the re,

    rack 11 (b, e) is located near the centre of the compartment, and rack 19 (c, f) is located near the window. See Fig. 1for rack location.

    W. Jahn et al. / Building and Environment 46 (2011) 1065e10731070

  • 7/24/2019 A Posteriori Modelling of the Growth Phase of Dalmarnock Fire Test One

    7/9

    the experimental error in the hot layer, but underpredicting the

    temperatures in the cold layer by about 40%. At rack 19, near the

    window, and 150 s (Fig. 8c), the lower HRR bound produces

    temperatures that lie within the experimental error in the hotlayer,

    while the upper HRR bound results in overprediction by about 30%.At 200 s the hot layer temperatures at rack 7 are slightly over-

    estimated (although close to the experimental error, Fig. 8d) when

    using the upper HRR bound, and underestimated by around 35%

    when using the lower HRR bound. The cold layer temperatures are

    underestimated by 50e100% for both input HRR curves. At rack 11

    temperatures simulated with the lower HRR bound are under-

    predicted by less than 20% in the hot layer (Fig. 8e), having similar

    shape to the measured distribution. With the upper HRR bound as

    input, the temperatures are overpredicted by about 25% in the hot

    layer, but underpredicted by about 35% in the cold layer, thus indi-

    cating higher temperature differences between hot and cold layer.

    Near the window, at rack 19 (Fig. 8f), the temperatures (specially in

    the hot layer) are in good agreement with the lower HRR bound as

    input, although the predicted hot layer height is around 0.5 mhigher than that observed. But the upper HHR bound overpredicts

    the hot layer temperature by 40%, which is in accordance to the

    overprediction by around 40% of the hot layer average temperature

    resulting from the upper HRR bound at 200 s (Fig. 7c).

    In addition to gas phase temperatures, the simulated wall

    temperatures and wall heat uxes are compared to the measure-

    ments in Fig.9 at two different times. Theux for both measurement

    and predictions is the total incident heat arriving to the location.

    Using the lower HRR bound, the wall temperature is underpredicted

    by about 20% at 150 s, and within (or very close to) the experimental

    error range at 200 s. For the upper HRR bound, the simulated wall

    temperature lieswithin the experimental error at both times. Butthis

    apparently best agreement of the upper HRR bound for wall

    temperatures contradicts the corresponding results for the wall heat

    uxes. While the lower HRR bound produces heat uxes in the hot

    layer close to the experimental error at 150 s, the upper HRR bound

    overpredicts heatuxes in the hot layer by20% and the cold layer by

    100%. Fig. 9 shows that at 200 s the predicted wall heatux with the

    lower HRR bound is in reasonable agreement with the measure-ments, both qualitatively and quantitatively. The upper HRR bound

    overpredicts of the heat uxes by 60e150%.

    Fig. 10shows the comparison of the distribution of heat uxes

    on the ceiling along two perpendicular directions at two different

    times. The simulated heat ux to the ceiling agrees with the

    measured heat ux when using the lower HRR bound (within 20%

    error). Using the upper HRRbound, the heat uxes tothe ceiling are

    consistently overpredicted (20e100%). The betterpredictions of the

    ceiling heat ux compared to the wall heat ux (seeFig. 9) for the

    lower HRR bound could be explained by the fact that the radiation

    from the ame to the ceiling is reduced by the presence of the

    smoke layer. The inaccuracies when modelling the ame could

    have a smaller effect on the ceiling heat ux.

    The difculty of modelling the near eld of the re on one hand,and the relatively good agreement of the results away from there

    on the other, is consistent throughout this paper and with previous

    work[9].

    7. Conclusions

    This work presents a detailed account of the a posteriori

    modelling of Dalmarnock Test One. A very large pool of scenario

    descriptions and measurements is used together with possible

    HRR curves. Simulations were then compared against detailed

    measurements, and uncertain input parameters were adjusted in

    order to t the results. It was shown that even with full access to

    the measurements, it is not easy to satisfactorily reproduce the

    course of the

    re. Although averaged quantities were in reasonable

    Fig. 9. Wall temperature vs. height (a and c) and Heat ux vs. height (b and d) distribution on the wall of the re compartment against the kitchen at times 150 s (a and b) and 200 s

    (c and d).

    W. Jahn et al. / Building and Environment 46 (2011) 1065e1073 1071

  • 7/24/2019 A Posteriori Modelling of the Growth Phase of Dalmarnock Fire Test One

    8/9

  • 7/24/2019 A Posteriori Modelling of the Growth Phase of Dalmarnock Fire Test One

    9/9