A Healer Reinforcement Approach to Smart Grid

download A Healer Reinforcement Approach to Smart Grid

If you can't read please download the document

description

smart grids ieee

Transcript of A Healer Reinforcement Approach to Smart Grid

  • A Healer Reinforcement Approach to Smart Grid Self-Healing by Redundancy Improvement

    Alireza Shahsavari, Alireza Fereidunian, Hamid Lesani

    f School of Electrical and Computer Engineering, University of Tehran, Tehran, Iran.

    2 Electrical Engineering Faculty, K. N Toosi University of Technology and School of ECE, University of Tehran, Tehran, Iran.

    Abstract- Smart Grid is expected to heal the electricity distribution system to improve its reliability, known as self

    healing capability. Self-healing can be performed in system

    level (like restoration and local generation), in component level,

    or by reinforcing the healer system reinforcement (called as

    healer healing). Smart Grid literature chiefly focuses on the

    two former approaches; while, the latter has gained less

    attention despite merit. A proper healer reinforcement method is expanding redundancy, in both control and protection

    subsystems. The redundancy expansion and the consequent

    self-healed distribution network is anticipated to express lower

    outage times, thus higher reliability and increased social

    welfare. This paper investigates the effect of redundancy

    expansion on reinforcement of the Smart Grid healer, by

    reliability modeling of protection and control subsystems. The

    positive effect of the proposed healer reinforcement approach

    on the overall Smart Grid reliability is shown on RBTS4, and

    the results are discussed then.

    Keywords-Smart Grid, Self-healing, Healer Reinforcement;

    Reliability Modeling; Redundancy Expansion; Non-Dominated

    Solutions.

    NOTATION

    The notation used throughout this paper is reproduced below for quick reference.

    nust. ! Aline

    J Atrans. J Abusbar J Lline J Ltrans. J LBusbar J r.line !)

    r.trans. !)

    r.busbar !)

    In!

    Life cycle of study;

    Number of load points;

    Average annual time that the load point i is out of supply (h/yr);

    Average load per customer in load point i (kW/cust.);

    Number of customers in load point i (kW/cust.); Lines failure rate of section j (f/km.yr);

    Transformers failure rate of section j(f/yr);

    Busbar failure rate of section j (f/yr);

    Length of section j lines (km);

    Number of transformer in section j ;

    Number of bus bars in section j ;

    Average outage time of section per fault in

    section j lines (hIt);

    Average outage time of section per fault in

    section j transformers (hIt);

    Average outage time of section per fault in

    section j busbar (hIt);

    Inflation rate;

    Int wfes

    wfomm

    wfnd

    w[C

    wfPC

    JCRes JCcomm JCind JCPC JCCPC ENS CENS TCENS

    TCR TPJ RB

    Interest rate;

    Residential load coefficient;

    Commercial load coefficient;

    Industrial load coefficient;

    Public customer load coefficient;

    Critical public customer load coefficient;

    Residential customers interruption function;

    Commercial customers interruption function;

    Industrial customers interruption function;

    Public customers interruption function;

    Critical public customers interruption function;

    Energy Not Supplied per year (kWh/yr);

    Cost of Energy Not Supplied per year($ US/yr);

    the Total Cost of Energy Not Supplied during

    life cycle of study;

    Economic Factor;

    the Average Interruption Cost for load point i ($ US/kW);

    Total Cost of Redundancy expansion;

    Total Planning Investment;

    Redundancy expansion Benefit.

    I. INTRODUCTION

    H IGH reliability requirement is considered as the main challenge in modern grids; specifically in electric power distribution systems which are in charge of delivering

    the electrical energy to the consumers. Smart grid satisfies

    this reliability requirement this obstacle by the self-healing

    capability [1].

    A self-healing system uses information, sensing, control

    and communication technologies to handle issues and unwanted events by eliminating or minimizing their

    disadvantageous effect for maximizing reliability [2, 3].

    Self-healing can be performed in system level (like local

    generation and capability of automatic fault detection, isolation, and service restoration), in component level, or by

    healer system reinforcement which we named it as healer

    healing. In [4], we introduced a novel framework for self

    healing methodologies.

    Healer reinforcement method is developed into wide area approaches. A pragmatic approach is improving its

    redundancy, in both control and protection subsystems.

  • From the Sfstem configuration point of view, the

    redundancy improvement leads to achieve a self-healer

    distribution network. The consequent self-healed

    distribution network anticipated to express lower outage

    times, in both frequency and duration of interruptions, thus

    higher reliability and increased social welfare.

    Reliability requirement specifies the degree of

    redundancy enhancement. On the other hand, it is conceivable that overall budget is run over by ting up high degree of ra:lundalt pcths. Thus, it is necessary to do a compromise between reliability requirement and investment

    of redundancy expansion. Economically, the utility cost will

    generally increase as consumers are provided with higher

    reliability. On the other hand, the consumer costs associated

    with supply interruptions will decrease as the reliability

    increases. The total costs to society will therefore be the sum

    of these two individual costs. This total cost exhibits a

    minimum and so an optimum or target level of reliability is

    achieved.

    From the reliability aspect, enhancing the redundancy in

    control subsystem is expected to influence on duration of an

    interruption and by enhancing it in protection subsystem expected to influence on both duration and frequency of an

    interruption. The redundancy enhancement in control

    subsystem decreases SAIDI (System Average Interruption

    Duration Index) and in protection subsystem decreases both

    SAIFI (System Average Interruption Frequency Index) and

    SAIDI.

    All in all, healer reinforcement approach by using of

    redundancy approach possesses some technical and

    economical benefits. For instance, improving overall

    reliability indices and decreasing total cost of energy not supplied. However, it incurs more installation cost

    maintenance. Hence, it is necessary to economically analyz; the healer reinforcement by redundancy approach.

    In [3], reliability models for protection and control

    subsystems are presented and different redundancy schemes

    are checked. However the impact of redundancy expansion

    ?n overall reliability did not discussed. In [4, 5], redundancy

    m some parts of the protective system is examined and

    A.Abbarin and Fotuhi-Firuzabad extended a Markov model

    and examined redundancy and protective components

    effects. In [7], a technical novel framework is introduced for

    redundancy approach in both control and protection

    subsystem.

    This.

    paper .investigates the effect of redundancy

    expansIOn on remforcement of the Smart Grid healer, by reliability modeling of protection and control subsystems. The positive effect of the proposed healer reinforcement approach on the overall Smart Grid reliability is shown on RBTS4. The effect of redundancy expansion is checked in both subsystems individually on RBTS4. Also the economical and technical effects of redundancy expansion on subsystems are investigated and best solution is selected by using non-dominated solution, the results are discussed then. In section 2, by modifying these models different redundant paths have been defined. Next in section 3 reliability achievements of implementing redundanc; approach has been presented and possible redundant sets have been introduced as a Non-Dominated solution and final redundant set has been selected through max-min approach.

    2

    II. METHOD

    A. Research Methodology

    For evaluating the overall smart grid reliability and the

    positive effect of redundancy expansion on reinforcement of

    the Smart Grid healer, the reliability of protection and

    control subsystems should be modeled. Reliability modeling

    for protection and control systems and different redundant

    schemes are presented, in section 2.3.

    Figure. l shows the flowchart of the overall and load point

    base reliability evaluation. In this flowchart, ARPM and

    ARTM represent Auto-Restoration Probability Matrix and

    Average Restoration Time Matrix, respectively. ARPM is

    calculated by conditional probabilities and depends on the

    allocated automatic and manual switches, protection devices

    and probability of their successful operation [8]. In [3]

    ARPM is calculated by using RadPow software base on

    event tree, while in this article, reliability evaluations are

    simulated in a home developed program. ARTM is

    calculated by conditional probability and depends on

    switching time and the calculated ARPM. Redundancy

    influences the values of protection and control block in the

    flowchart; therefore, redundancy affects the system reliability.

    Feeders' Evaluation

    Figure.I.Flowchart of the reliability evaluation

    B. Problem Formulation

    As mentioned before, the economical and technical

    effects of redundancy expansion on subsystems are

    investigated in this paper by using prepared models and

    evaluation flowchart. For investigating technical impact of

    redundancy expansion some reliability indices are

    examined, for instance, SAIFI, SAIDI, CAIDI, AENS and

    ASAI, which are expressed in [9, lO]. To evaluate the

    economical the impact of the proposed healer reinforcement

    by components redundancy expansion on the system

  • reliability, total cost of energy not supplied (TCENS) during

    the life cycle is examined, which is expressed as:

    ny LP TCENS = L L CENSi x (EF) n (1)

    n=l i

    Where n is the number of years, i is the load point numbers and EF is the economic factor for evaluation of present worth/cost factor which changes the cost of time

    study to current cost. The CENSi and the EF are written as:

    AlC-(U) CENS = ENS x ! ! ! ! Ui

    E F = _1

    _+

    _I

    _n.:....f

    1 + Int

    (2)

    (3)

    (4)

    In equation (2), AICi(Ui) is computed by equation eq.(5), j is the faulted section.

    AICi(Ui) = wfesICRes(Ui) + wfomm I Ccomm (Ui)

    +w{nd ICrnd(Ui) + wfc ICpc(Ui) + wfPC ICcpc(UJ (5)

    The IC represents interruption cost function for each kind of consumers. In (6), the total cost of redundancy approach and upcoming costs is computed. Also by using (7) benefit

    of implementing redundancy in distribution system is

    computed.

    TCR = TCENS + TPI

    RB = TCRnon-redundant - TCRredundant

    C. Reliability Modeling for Redundancy

    (6)

    (7)

    Figure.2 shows smart grid subsystems including control,

    protection and IT infrastructure interacting with legacy

    system [12]. Protection and control systems in contingencies

    conditions are responsible for isolating faulted zone and

    supply restorable zones, for minimizing the duration of

    interruption and to limit the impact of fault [7, 11], thus the

    overall smart grid reliability depends on successful

    operation of protection and control systems. In this section, protection and control subsystems reliability models are

    presented and different redundancy extensions are

    implemented.

    Control and Protection Power Distribution System System (The Legacy System)

    IT Infrastructure of Smart Grid Figure.2. Smart Grid Sub-systems [12]

    J) Protection System Reliability Modeling

    Protection system is the most important factor to the

    secure operation of the electrical power networks, induding

    3

    di stri buti on systems. A rei i ci:lI e prota::ti on system improves the overall network reliability. The probctlility for a prota::tion system to operate responding to a fault depends on the rei i aI:li I i ty of its components One etfa::ti ve approcrll for improving the prota::tion system's relial:lility is

    enhancing its ra::tundancy.

    a. Feeder Protection (Breakers) Reliability Modeling

    For a normally dosa::l breaker the operaing and failure states are [3]:

    1- Passes currents from in its closed state; 2- Opens successfully when requested to do so; 3- Fails to open when requested to do so; 4- Opens inadvertently when not requested. State 1 and 2 are the desirable conditions and 3 and 4 are

    the unwanted ones. 1 and 4 refer to dependability and

    security of the protection system [13]. In [9] these two aspects of reliability in redundant protections system have

    been discussed.

    Figure3 represents the protection system in term of its

    components block diagrams. These blocks related to feeder

    protection in which the digital relay unit (DRU) includes the

    electronic circuits of signal conditioning and the digital

    processing relay system. The auxiliary relay unit (ARU)

    contains trip relay (TR) and the associated power supply

    unit (PSU).

    1

    ................................ : PR :ARt:j ..

    1---F"Ti-.

    Figure.3.Block diagram of the base protection scheme, adapted [3]

    When a permanent fault occurs, all components should

    operate correctly, i.e., failure in each block causes fault in

    protection operation. From the reliability point of view, all

    components are series and the reliability block diagram

    (RBD) of the basic protection scheme is shown in figure.4.

    Figure.4. Reliability block diagram of the basic protection scheme.

    In the basic protection scheme, any failure in each block

    causes malfunction in protection operation. Consequently,

    back up protection operates and both faulted and faultless

    feeders experience outage. The probability of malfunction in

    protection scheme reduces by redundancy enhancing in

    components. In order to see different redundant protection schemes, for preventing from unnecessary repetition,

    figure.5 shows only sample of reliability block diagram

    cases. Cases 2-5 comprise one redundant component in

    sequence for Breaker, DRU, ARU, and CT.

    Case 6 comprises two DRUs and two ARUs which

    prepare two paths; the system is operating if at least one

    path is functioning. Case 7 has two breakers and two CTs and prepares 4 paths; the system is functioning if at least one

    of breakers and one of CTs are functioning. Figure.6 shows

  • the even tree of case 8, it consist of two DRUs and two

    ARUs and prepares 4 paths; the system is functioning if at

    least one of DR Us and one of ARUs are functioning. Case 9

    and case 10 are equal to (n-l) index of reliability, case 10 in

    components layer and case 9 in system layer. Assuming the

    failure events of the components blocks are independent,

    also the probability of each basic component operation is

    equal to tablel and the probability of each redundant

    component operation is 0.95% of the basic component.

    Table2 shows the probabilities of base case and redundant

    protection cases operation.

    Fault

    CT

    Case 6

    Case 8

    Non-redundant Protection system 1

    Non-redundant Protection system 2

    Case 9

    Case 10

    Figure.5. Reliability block diagram of different

    redundancy schemes in protection systems

    B

    o

    i ARUI i ARU2 i 0 i

    Outcome

    i->'---:-----: I: Trips 2: Trips

    3: Fails to Trips

    -"";""----i 4: Trips 5: Trips

    o 6: Fails to Trips

    I-'-F _--+-__ +-_-1 7: Fails to Trips F _-+ __ +-_-+ __ +-_-i 8: Fails to Trips

    L..:...F __ ---'----'---""'"""---'-----' 9: Fails to TrillS

    F

    Figure.6. Event tree of case 8

    b. Fuses Reliability Modeling

    Fuses in automated distribution systems have direct

    impact on systems reliability. Fuse in low voltage branches

    decreases duration and frequency of interruptions. From the

    reliability point view, fuse is independent device and its

    reliability block diagram is one block.

    2. Control System Reliability Modeling

    Distribution automation and control systems consist of

    three functions; line's facilities or secondary substations,

    primary substations, and distribution control centers (DCC)

    4

    [3, 14, 15, 17]. Communication systems are non-negligible

    and

    requisite infrastructures for data exchanges in these three

    layers [16]. In this paper, the reliability of automation

    control systems is investigated into two layers, local control

    system and central control system.

    The central control system performs functions, including

    control and monitoring of all substation equipments,

    accumulate and process local controls data, dispatch control

    commands and receive results. The local control system

    consists of remote terminal units (RTUs), these devices

    exquisite various types of information, execute commands

    from the central center and reporting status after

    implemented commands to the central center.

    A rei i cD! e control systan improves the overall smai gri d rei icDi I ity. The probabi I ity for the control systan to operate responding to a commald depends on the reliability of its

    components. One effective approcdl for improving the

    control systan rei i cDi I i ty is enhalo ng its redundalCY. Figure.7,8 represents control system consists of local and

    central layers in term of component block diagrams. Central

    control includes Power Supply Unit (PSU), Central

    Processing Unit (CPU), Memory Unit (MU), controller and

    Communication Interface (CI). The main components in

    local control system are Switching Device (SD), battery and

    charger or Power Supply Unit (PSU), power actuator (Drive), Current transformer and Voltage Transformer

    (CTIVT), Remote Terminal Unit (RTU) , Fault Passage

    Indicator (FPI) and Communication Interface (CI). The

    RTU includes central processing unit (CPU), Input / Output

    interface (I/O). A typical RTU possess eight digital inputs

    (D!) and eight digital outputs (DO), also may equipped with

    six analog inputs [3, 11, 14, 15].

    Ccntral Computer [ cPu I [ Controller I

    I Power Supply I Urnt I Communication I Interface

    (a)

  • Figure.8.(a). Block diagram of the base central control system

    (b). Block diagram of the base local control system; adapted [3, II, 14, 15]

    In order to achieve a proper operating control system,

    each component in both local and central control layers

    should operates correctly, i.e., any individual event that

    causes failure of each component in local/central control

    layers fails the local/central control system. From the

    reliability point of view, all components are connected in

    series. Assuming failure events are independent, equations

    (8) and (9) represent the probabilities of non-redundant local

    and central control operation.

    P(cent ral cont rol) = P(PSU) P( Cont roller) ' P( CPU) . P(MU) . P( CI)

    P(local cont rol) = P(SD) . P( CT) ' P(PSU) P(FPI)

    (8)

    . P(PA) . P(RTU) . P( CI) (9)

    a. Central Control Reliability Modeling

    In order to see different redundant central control

    schemes, figure.9 shows reliability block diagrams of four

    different redundancy schemes in central control system. For

    preventing from unnecessary repetition, figure4 shows only

    sample of reliability block diagram cases. Cases 2-6 comprise one redundant component in sequence for CI,

    PSU, CPU, MU and controller.

    Case 7

    Case 8

    Central control system 1

    Central control system 2

    Case 9

    Case 10

    Figure.9. Reliability block diagram of different

    redundancy schemes in central control systems

    Case 7 comprises two CPUs, MUs, and controller which

    prepare two paths, and Case 8 is alike case 2, which

    prepares 8 paths; the system is functioning if at least one of

    paths is functioning. Case 9 and case 10 are equal to (n-l)

    5

    index of reliability, case 10 in components layer and case 9

    in system layer. Assuming independent failure events for the

    components, also considering the probability of each

    component operation is equal to table 1 and the probability

    of redundant component operation is 0.95% of the basic

    component. Table 2 shows the probabilities of base case and

    redundant cases operation.

    b. Local Control Reliability Modeling

    In order to see the effect of redundancy expansion in local

    control system, figure. 10 shows reliability block diagrams of

    four different redundancy schemes in local control system.

    Also case 2-6 comprise one redundant component III

    sequence for CI, PSU, RTU, power actuator, and FPI.

    Local control system 1

    Local control system 2

    Case 9

    Case 10

    Figure.lO. Reliability block diagram of different

    redundancy schemes in local control systems

    As discussed in protection and control modeling, table2

    shows the probabilities of base and redundant local control cases operation, assuming independent failure events for the

    components, also considering the probability of each

    component operation is equal to table 1 and the probability

    of redundant component operation is 0.95% of the basic

    component.

    Tablel. Components reliability, adapted [3]

    Control system Protection system

    Central Control Local Control

    Component Reliability Component Reliability Component Reliability

    CT 0.98 5 PSU 0.995 SO 0.990

    DRU 0.990 CPU 0.994 PSU 0.995

    ARU 0.98 8 MU 0.993 PA 0.992

    B 0.993 Controller 0.98 7 CTIVT 0.990

    CI 0.997 FPI 0.990

    RTU 0.993

    CI 0.997

    Table2 antICipates the redundancy improves the

    probability of successful protection and control operation.

    Comparison between case 6 and 8 of protection system (or

    case 7 and 8 in control system) illustrates redundant

    components connection is extremely important, parallel

    connections make more reliable than series. As expected,

    redundancy in components layer is more reliable than the

    redundancy in system layer, case 9 and 10 indicate that.

    Table2. Probabilities of each considered cases operation

  • Protection System Control System

    Case Feeder Fuse

    Central Local Control

    Protection Control

    Base 0.956704 0.90 0.966431 0.943378

    Case 2 0.963066 0.91 0.969185 0.946066

    Case 3 0.965792 0.92 0.971021 0.947859

    Case 4 0.967610 0.93 0.971940 0.949651

    Case 5 0.970337 0.94 0.972858 0.950547

    Case 6 0.975597 0.95 0.978366 0.952340

    Case 7 0.976789 0.96 0.98 7800 0.959456

    Case 8 0.976802 0.97 0.990486 0.961405

    Case 9 0.990442 0.98 0.991534 0.980680

    Case 10 0.997310 0.99 0.998027 0.996561

    III. Case Study

    A. Example Case

    The effect of the proposed healer reinforcement approach

    on the overall Smart Grid reliability is shown on RBTS4.

    The RBTS has 5 buses (Bus2-Bus6), two buses (Bus2, Bus4) are defined as distribution network. Figure. 1 1 shows

    RBTS4 which has three supply points, seven feeders, 38

    load points, 4770 customers, and the peak and average load

    40 MW and 24.58 MW, respectively. Customers data and

    lines length are taken from [18]. Table3 shows components

    and lines failure rates and average repair or replacement

    time per failure. For evaluating the reliability, auto

    switching time and manual switching time are assumed 40 seconds and l.5 hour, respectively. Life cycle of study is

    considered 25 years, also inflation rate and interest rate 6%

    and 7%, respectively. Figure.I2 shows the Ie s of different customer types.

    S3W lIkV I

  • control facilities prices are exist, component's reliability

    cost curve is an upward concavity exponential function [9,

    10], Thus the reliability-cost curve for subsystems

    consequence of components reliability-cost curve and can be

    calculated.

    Figure15 shows total cost of redundant planning in central

    and local control, as shown minimum TCR consequences of

    case 8 for both local and central control, it shows that by

    implementing more redundant for instance cases 9 or 10,

    planning costs increases more than decreased TCENS.

    1.826

    1.824

    1.822

    Vl 1.82 1.818 '" 1.816

    1.814

    1.812

    X 106

    L81-..J.--=-,"-- Case 3 Case I

    Case 1 ease2 ca';"3 3 -:C"C:C

    '4i-

    C:;C

    "'='5

    C:;C

    ""=6S$s;'::::::::'c Case 5 \ CO\\tt"O

    \ , .,:dunda High Redundant LOCal C::, Case 8 Case 9 Case 10 Case 9

    Figurel5. Total cost of redundancy of redundant control cases

    C. Impact of redundancy in protection system

    This section presents impact of redundancy in protection

    system base on explained modeling in part "C" of section II.

    For investigating the positive impact of redundancy in

    protection system on network, the control system is modeled

    as the base case. By comparing 100 possible cases

    determines that the CENS is reduced about 8% also the

    SAID! is reduced about 10%, as shows in figure 16, 17.

    7.9

    7.7

    7.6 8 7.5 U7.4

    7.3 7.2 /- Case I ease 2 Case 3 cas;'gh Case 5 Case 6 Cac 7 Case 8 Case 9 Case 10 0.98 I ' Re