Fronius prints on elemental chlorine free paper (ECF) sourced from certified sustainable forests (FSC). / Perfect Charging / Perfect Welding / Solar Energy 8 kW 220 V Selectiva 4120 / 4140 / 4160 8 kW 400 V Selectiva 2100 / 2120 / 2140 2160 / 2180 / 2200 4060 / 4075 / 4090 4120 / 4140 / 4160 8040 / 8060 / 8075 8090 16 kW 400 V Selectiva 8120 / 8140 / 8160 8180 / 8210 EN Operating instructions Battery charging system 42,0426,0151,EN 032-03022021

Embed Size (px)

Transcript of 8180 / 8210 - Fronius

Fronius prints on elemental chlorine free paper (ECF) sourced from certified sustainable forests (FSC).
/ Perfect Charging / Perfect Welding / Solar Energy
8 kW 220 V Selectiva 4120 / 4140 / 4160 8 kW 400 V Selectiva 2100 / 2120 / 2140 2160 / 2180 / 2200 4060 / 4075 / 4090 4120 / 4140 / 4160 8040 / 8060 / 8075 8090 16 kW 400 V Selectiva 8120 / 8140 / 8160 8180 / 8210
EN Operating instructions
Battery charging system
Contents Safety rules 5
General 5 Intended use 5 Environmental conditions 5 Mains connection 5 Dangers from mains current and charging current 6 Danger due to acid, gases and vapours 6 General information regarding the handling of batteries 7 Protecting yourself and others 7 Safety measures in normal operation 7 EMC Device Classifications 7 EMC measures 8 Data protection 8 Maintenance 8 Maintenance and repair 8 Obligations of the operator 8 Safety inspection 8 Markings on the device 9 Disposal 9 Copyright 9
General information 10 Explanation of safety notices 10 Device concept 10 Battery configuration 10 Mains connection 11 Charging lead 11 Warning notices on the device 11 Warning notices inside the device 13 Setup regulations 13 Wall bracket 15 Correct routing of the mains/charging cables 19
Control elements and connections 20 Controls and connections 20 Control panel 21
Charging the battery 23 Charging 23 Interrupting charging 24 Stopping charging 25
Display 27 Overview of display modes 27 Standard mode 27 Menu selection 28 Statistics mode 28 History mode 28 Configuration mode 30 Settings 33 Electrolyte circulation 34 Temperature-controlled charging 34 Equalising charge 35 Delay 36 Calendar 37 Special charges 38 “Opportunity Charge” special function 39 Additional functions 40 General settings 43 Reset settings 45 USB mode 45 Status codes 47
Options 51 Safety 51
3
EN
Electrolyte circulation (not available on the Selectiva 3x220 16 kW variants) 51 External start/stop 53 Charging lights 53 Temperature-controlled charging 53 CAN card 54 Relay board 55 Aquamatic control 56 Charging 56 Charge 50% 56 Charge 80% 56 Charging not complete 56 Charge finish 56 Main charge finished 56 Common error message 56 Common error + warning 56 Signal lamp 56 Immobiliser device 57 Battery cooled down 57 External air pump - electrolyte circulation 57 Wall bracket 57 Floor bracket 57 LED strip 57 IP 23 57 Air filter 57 "Mobile" kit 57 Remote control system 58
Technical data 59 Selectiva 16 kW 220 V 59 Selectiva 8 kW 400 V 61 Selectiva 16 kW 400 V 63
4
Safety rules
General The device has been manufactured in line with the state of the art and according to recognized safety standards. If used incorrectly or misused, however, it can cause: - Serious or fatal injury to the operator or third parties - Damage to the device and other material assets belonging to the operating company - Inefficient operation of the device
All persons involved in commissioning, operating, maintaining and servicing the device must: - Be suitably qualified - Read and follow these Operating Instructions carefully
The Operating Instructions must always be at hand wherever the device is being used. In addition to the Operating Instructions, attention must also be paid to any generally applicable and local regulations regarding accident prevention and environmental protec- tion.
All safety and danger notices on the device: - Must be kept in a legible state - Must not be damaged/marked - Must not be removed - Must not be covered, pasted, or painted over
For the location of the safety and danger notices on the device, refer to the section headed "General information" in the Operating Instructions for your device. Before switching on the device, rectify any faults that could compromise safety.
This is for your personal safety!
Intended use The device is to be used exclusively for its intended purpose. Any use above and beyond this purpose is deemed improper. The manufacturer is not liable for any damage, or unexpected or incorrect results arising out of such misuse.
Proper use also includes: - Carefully reading and following all Operating Instructions, safety and danger notices - Performing all stipulated inspection and servicing work - Following all instructions from the battery and vehicle manufacturers
Proper handling of the device is essential for it to function correctly. Never pull on the cable when handling the device.
Environmental conditions
Operation or storage of the device outside the stipulated area will be deemed as not in accordance with the intended purpose. The manufacturer shall not be held liable for any damage arising from such usage.
For exact information on permitted environmental conditions, please refer to the "Tech- nical data" section.
Mains connection Devices with a higher rating may affect the energy quality of the mains due to their cur- rent consumption.
5
EN
This may affect a number device types in terms of: - Connection restrictions - Criteria with regard to the maximum permissible mains impedance *) - Criteria with regard to the minimum short-circuit power requirement *)
*) at the interface with the public grid see "Technical data"
In this case, the plant operator or the person using the device should check whether the device may be connected, where appropriate by discussing the matter with the power supply company.
IMPORTANT! Ensure that the mains connection is earthed properly
The mains voltage tolerances of the devices may deviate from those specified in the technical data depending on the mains connection.
Dangers from mains current and charging cur- rent
Anyone working with battery chargers exposes themselves to numerous dangers, e.g.: - Risk of electrocution from mains current and charging current. - Hazardous electromagnetic fields, which can risk the lives of those using cardiac
pacemakers.
An electric shock can be fatal. Every electric shock is potentially life threatening. To avoid electric shocks while using the charger: - Do not touch any live parts inside or on the outside of the charger. - Under no circumstances touch the battery poles. - Do not short-circuit the charging cable or charging terminals.
All cables and leads must be secured, undamaged, insulated and adequately dimen- sioned. Loose connections, scorched, damaged or inadequately dimensioned cables and leads must be immediately repaired by authorised personnel.
Danger due to acid, gases and vapours
Batteries contain acid which is harmful to the eyes and skin. During charging, gases and vapours are released that may be harmful to health and are highly explosive in certain circumstances.
Only use the charger in well-ventilated areas to prevent the accumulation of explosive gases. Battery rooms are not deemed to be hazardous areas provided that a concentra- tion of hydrogen of less than 4% can be guaranteed by the use of natural or forced vent- ilation.
Maintain a distance of at least 0.5 m (19.69 in.) between the battery and charger during the charging procedure. Possible sources of ignition such as fire and naked flames must be kept away from the battery.
The battery connection (e.g. charging terminals) must not be disconnected for any reason during charging.
Do not inhale any of the gases and vapours released under any circumstances - Make sure the area is well ventilated.
To prevent short circuits, do not place any tools or conductive metals on the battery.
6
Battery acid must not get into the eyes or onto the skin or clothes. Wear protective goggles and suitable protective clothing. Rinse any acid splashes thoroughly with clean water and seek medical advice if necessary.
General informa- tion regarding the handling of bat- teries
- Protect batteries from dirt and mechanical damage. - Store charged batteries in a cool place. Self discharge is kept to a minimum at
approx. +2 °C (35.6 °F). - Carry out a visual inspection at least once a week or as often as specified by the
battery manufacturer to ensure that the acid (electrolyte) level in the battery is at the max. mark.
- If any of the following occur, do not start the device (or stop immediately if already in use) and have the battery checked by an authorised workshop: - uneven acid levels and/or high water consumption in individual cells caused by
a possible fault. - overheating of the battery above 55 °C (131 °F).
Protecting your- self and others
While the charger is in operation, keep all persons, especially children, out of the working area. If, however, there are people in the vicinity, - warn them about all the dangers (hazardous acids and gases, danger from mains
and charging current, etc.), - provide suitable protective equipment.
Before leaving the work area, ensure that people or property cannot come to any harm in your absence.
Safety measures in normal opera- tion
Chargers with a ground conductor must only be operated on a mains supply with a ground conductor and a socket with a ground conductor contact. If the charger is oper- ated on a mains supply without a ground conductor or in a socket without a ground con- ductor contact, this will be deemed gross negligence. The manufacturer shall not be held liable for any damage arising from such usage.
Only operate the charger in accordance with the degree of protection shown on the rat- ing plate.
Under no circumstances operate the charger if there is any evidence of damage.
Arrange for the mains cable to be checked regularly by a qualified electrician to ensure the ground conductor is functioning properly.
Any safety devices and parts that are not functioning properly or are in imperfect condi- tion must be repaired by a qualified technician before switching on the charger.
Never bypass or disable protection devices.
After installation, an accessible mains plug is required.
EMC Device Clas- sifications
Devices in emission class A: - Are only designed for use in industrial settings - Can cause line-bound and radiated interference in other areas
Devices in emission class B: - Satisfy the emissions criteria for residential and industrial areas. This is also true for
residential areas in which the energy is supplied from the public low-voltage mains.
7
EN
EMC device classification as per the rating plate or technical data.
EMC measures In certain cases, even though a device complies with the standard limit values for emis- sions, it may affect the application area for which it was designed (e.g. when there is sensitive equipment at the same location, or if the site where the device is installed is close to either radio or television receivers). If this is the case, then the operating company is obliged to take appropriate action to rectify the situation.
Data protection The user is responsible for the safekeeping of any changes made to the factory settings. The manufacturer accepts no liability for any deleted personal settings.
Maintenance Before switching on, always check the mains plug and cable as well as charger leads and charging terminals for any signs of damage. If the surface of the device housing is dirty, clean with a soft cloth and solvent-free clean- ing agent only.
Maintenance and repair
Maintenance and repair work must only be carried out by authorised personnel. Use only original spare and wearing parts (also applies to standard parts). It is impossible to guar- antee that bought-in parts are designed and manufactured to meet the demands made on them, or that they satisfy safety requirements.
Modifications, installations or conversions are only permitted with the approval of the manufacturer.
Obligations of the operator
The operator must only allow persons to work with the device who: - are familiar with the fundamental instructions regarding safety at work and accident
prevention and have been instructed in how to use the device - have read and understood these operating instructions, especially the section
"safety rules", and have confirmed as much with their signatures - are trained to produce the required results.
Checks must be carried out at regular intervals to ensure that operators are working in a safety-conscious manner.
Safety inspection The manufacturer recommends that a safety inspection of the device is performed at least once every 12 months.
The safety inspection may only be performed by an appropriately qualified electrician - After any changes have been made - After any additional parts are installed, or after any conversions - After repair, care and maintenance are carried out - At least every twelve months
For safety inspections, follow the appropriate national and international standards and directives.
Further details on safety inspections can be obtained from your service centre. They will provide you on request with any documents you may require.
8
Markings on the device
Devices with the CE marking satisfy the essential requirements of the applicable guidelines.
Devices displaying the EAC mark of conformity satisfy the requirements of the relevant standards in Russia, Belarus, Kazakhstan, Armenia and Kyrgyzstan.
Disposal Do not dispose of this device with normal domestic waste! To comply with the European Directive on Waste Electrical and Electronic Equipment and its implementation as national law, electrical equipment that has reached the end of its life must be collected separately and returned to an approved recycling facility. Any device that you no longer require must either be returned to your dealer or given to one of the approved collection and recycling facilities in your area. Ignoring this European Directive may have poten- tially adverse affects on the environment and your health!
Copyright Copyright of these operating instructions remains with the manufacturer.
The text and illustrations are all technically correct at the time of printing. We reserve the right to make changes. The contents of the operating instructions shall not provide the basis for any claims whatsoever on the part of the purchaser. If you have any sugges- tions for improvement, or can point out any mistakes that you have found in the instruc- tions, we will be most grateful for your comments.
9
EN
Explanation of safety notices DANGER!
Indicates immediate danger. If not avoided, death or serious injury will result.
WARNING!
Indicates a potentially hazardous situation. If not avoided, death or serious injury may result.
CAUTION!
Indicates a situation where damage or injury could occur. If not avoided, minor injury and/or damage to property may result.
NOTE!
Indicates a risk of flawed results and possible damage to the equipment.
Device concept The three-phase battery charging systems are fitted with intelligent charging technology. The successful Active Inverter Technology with the revolutionary Ri charging process adapts itself to the requirements of the battery and only charges the battery with the cur- rent that it actually needs.
The technology is embedded in a robust industry-standard housing. The exceptionally compact design complies with all safety standards, requires less installation space and protects the components to ensure a long service life.
Fitted with a graphical display, an integrated datalogger, new interfaces and additional options, the device is perfectly equipped for the future.
Battery configur- ation WARNING!
Danger due to unsuitable batteries being connected to the charger. Escaping gas, fire or explosion may result in serious injury and damage to property. Never connect a battery to the charger unless it is compatible in terms of its type,
voltage and capacity and corresponds to the charger settings.
10
Mains connection WARNING!
Danger from electrical current. This may result in serious injuries or death. Before starting work, switch off all the devices and components involved and discon-
nect them from the grid. Secure all the devices and components involved to prevent unintentional restarting.
If required, nothing other than a type B residual current circuit breaker should ever be used for connecting the device to the mains.
WARNING!
Danger due to incorrect operation and incorrectly performed work. This may result in serious injury and damage to property. All the work and functions described in this document must only be carried out by
trained and qualified personnel. Read and understand this document.
Read and understand all the Operating Instructions for the system components, especially the safety rules.
WARNING!
Danger due to faulty or insufficient power supply. This may result in serious injury and damage to property. The power supply requirements detailed in "Technical data" must be met.
Charging lead WARNING!
Danger due to trailing charging leads. This may result in serious injury and damage to property. People may become entangled in or trip over loose, unwound cables Lay the charging leads so that no one can trip over or become entangled in them.
WARNING!
Danger due to the charging plug being pulled out during the charging process. This may result in serious injury and damage to property. The sparks caused by this can ignite the charging gases that build up during the charging process, causing a fire or an explosion. Once the charging process is complete, wind up the charging leads, or if available,
place them on the cable holder.
Warning notices on the device
A number of safety symbols can be seen on the charger's rating plate. The safety sym- bols must not be removed or painted over.
11
EN
WARNING Explosive gases. Prevent flames and sparks. Provide adequate ventilation during charge! Always stop charging before you disconnect the charging cable!
IAC max.
UAC nom.
PAC max.
www.fronius.com xxxxxxxx
Selectiva xxxx
Ladevorgang immer stoppen bevor das Ladekabel abgezogen wird! Explosive Gase. Flammen und Funken vermeiden. Während des Ladens für ausreichend Frischluft-Zufuhr sorgen! Always stop charging before you disconnect the charging cable! Explosive gases. Prevent flames and sparks. Provide adequate ventilation during charge! Toujours arrêter la charge avant de déconnecter le câble de charge! Gaz explosifs. Éviter les flammes et les étincelles. Prévoir une ventilation adaptée pendant la charge! ¡Detener siempre la carga antes de desconectar el cable de carga! Gases explosivos. Evitar llamas y chipas. ¡Mantener una ventilación adecuada durante la carga! Interrompere sempre la carica prima di scollegare il cavo di carica! Gas esplosivi. Evitare fiamme libere e scintille. Predisporre una ventilazione adeguata durante la carica!
WARNUNG - WARNING - ATTENTION ADVERTENCIA - AVVISO
42,0409,0419
An electric shock can be fatal. The housing must never be opened by anyone other than a service technician trained by the manufacturer. The device must be disconnected from the mains before starting any work with the housing open. A suitable measuring instrument must be used to ensure that electric- ally charged components (e.g. capacitors) are fully discharged. Ensure that the device remains disconnected from the mains until all work has been com- pleted.
Do not use the functions until you have fully read the Operating Instructions.
Possible sources of ignition, such as fire, sparks and naked flames, must be kept away from the battery.
Risk of explosion! Oxyhydrogen is generated in the battery during charging.
Battery acid is corrosive and must be kept away from eyes, skin and clothes.
Ensure an adequate supply of fresh air during charging.
The charger can cause DC fault currents in the ground conductor. If a fault current protection device (RCD) is used on the mains side to protect against electric shock, it must conform to type B.
Do not dispose of the product in domestic waste. Dispose of it according to the disposal requirements for waste electrical and electronic equipment valid at the installation site.
12
Warning notices inside the device WARNING!
Danger from electrical current. This may result in serious injuries or death. The housing must never be opened by anyone other than a service technician
trained by the manufacturer. Before starting work, switch off all the devices and components involved and discon-
nect them from the grid. Secure all the devices and components involved to prevent unintentional restarting.
After opening the device, use a suitable measuring instrument to check that electric- ally charged components (such as capacitors) have been discharged.
Use an easily legible and understandable warning sign to ensure that the device is not reconnected to the mains supply before all the work has been completed.
(4) (5)
Temp. Sensor Ext. Start/Stop
WARNING Hazardous Voltage Kondensator Entladezeit < 3 min. Capacitor discharge time < 3 min. Décharge de condensateur < 3 min. Condensador tiempo de descarga < 3 min. Condensatore tempo di scaricamento < 3 min.
Risk of Electric Shock! Do not operate at circuits more than 250 V to ground! 0... 30V DC/4A 0... 250V AC/4A Use Copper Conductors Only!
C Common NC Normally Closed NO Normally Opened L Line N Neutral Wire
max. 1A AC Output!
42 ,0
40 9,
00 08
C NC NO C NC NO C NC NO L/C NC NO N
WARNING!
Setup regulations WARNING!
Danger from devices falling or toppling over. May result in serious injuries or death. Set up all system components in a stable position. When using a floor bracket or
wall bracket, always ensure that all fastening elements are firmly seated. Devices weighing more than 25 kg (55.12 lb.) must be carried by at least 2 persons.
When mounted on a shelf, the load capacity of the shelf must at least correspond to the weight of the device.
13
EN
The device has been tested according to degree of protection IP20. This means: - Protection against the penetration of solid foreign bodies with a diameter of more
than 12.5 mm (0.49 in.) - No protection against water.
The device can be set up and operated in dry, closed rooms in accordance with degree of protection IP20. Avoid exposure to moisture.
The permissible operating position of the device is horizontal.
The ambient air surrounding the device must be kept free from battery acid vapors. Mounting the device directly above the battery to be charged should therefore be avoided.
Cooling air The device must be set up so that cooling air can flow through the housing openings provided unhindered. There must always be a minimum distance of 0.2 m (7.874 in.) from the air inlet and outlet openings. The ambient air must be free from - excessive dust exposure, - electrically conductive particles (carbon black or metal chips), - heat sources.
The cooling air flows in and out as indicated by the arrows in the following illustrations.
NOTE!
Air inlet and outlet openings must not be blocked or even partially covered.
16 kW: 60 cm (1 ft. 11.62 in.)
8 kW: 30 cm (11.81 in.)
The setup of several devices one behind the other should be staggered.
The setup of several devices one behind the other should be staggered, otherwise a minimum distance of:
14
- 8 kW: Minimum distance 30 cm (11.81 in.) - 16 kW: Minimum distance 60 cm (1 ft. 23.62 in.)
must be observed.
Wall bracket WARNING!
Danger due to incorrect operation and incorrectly performed work. This may result in serious injury and damage to property. All the work and functions described in this document must only be carried out by
trained and qualified personnel. Read and understand this document.
Read and understand all the Operating Instructions for the system components, especially the safety rules.
Different wall plugs and screws are required depending on the supporting surface. Wall plugs and screws are therefore not included in the scope of supply. The installer is responsible for selecting the correct wall plugs and screws.
WARNING!
Danger from machines falling or toppling over. This may result in serious injury and damage to property. Ensure that all screw connections are secure.
Only use with a Fronius Selectiva 8/16 kW charger.
Ensure the device is level when mounting.
1
15
EN
3
1
2
32
3 (1
7. 83
mm (in.)
Drilling template
Weight of wall bracket: - 8 kW 400 V: 1.8 kg (3.97 lb.) - 8 kW 220 V: 3.15 kg (6.49 lb.) - 16 kW 400 V: 3.15 kg (6.49 lb.)
18
CAUTION!
Danger due to overheating as a result of incorrectly laid mains/charging cables. Risk of damage to the components. Lay the mains/charging cable without a loop.
Do not cover the mains/charging cable.
Charging cables longer than 5 m (16 ft. 4.85 in.) must be laid individually (no bund- ling).
For charging cables longer than 5 m (16 ft. 4.85 in.), a maximum ambient temperat- ure of 30 °C (86 °F) must not be exceeded.
The mains/charging cable may only be replaced by a qualified electrician.
Charging cables longer than 5 m (16 ft. 4.85 in.) can have an increased surface tem- perature (be aware of hot surfaces).
19
EN
No. Function
(1) USB port The USB port allows a USB flash drive to be used to update the device and also to log the charging parameters while charging is in progress. The maximum supply current is 0.5 A.
(2) Position for the remote control system or charging lights options.
(3) Position for the external start/ stop option or temperature-con- trolled charging option.
No. Function
(6) Positions for the relay-related options. (e.g. Aquamatic control) More information can be found in the "Options" chapter.
(7) Position for the internal electrolyte circulation option. Compressed air outlet
(8) Position for the internal electrolyte circulation option. Air intake with air filter
20
(9) Mains cable
(10) Optional LED strip. Lights up in different colours depending on the state of charge, as explained in the "Control panel" section.
(11) Control panel
(12) CAN connection area The connection area can only be accessed by removing the connection plate on the front of the device. The warning notices in the "Safety" section of the "Options" chapter must be obeyed.
Control panel
(1) (8)
(1) Display Displays the current charging parameters Displays settings
(2) "Menu" key Selects the desired menu Selects the appropriate symbol to return to the previous display
(3) "Up/Down" keys Selects the desired menu item Sets the desired value
(4) "Stop/Start" key For interrupting and resuming the charging process Confirms a menu item or setting
21
EN
(5) "Battery cooled down" indicator (blue) Indicates that a battery has cooled down and is ready for use On steady: After charging has finished, the set cooling time or optionally the bat- tery temperature has been reached. Flashes every second: The water refill indicator has also tripped. More information can be found under "Additional functions" in the "Display" sec- tion.
(6) "Fault" indicator (red) On steady: The charger outputs an error. The current conditions do not allow proper charge. While the red indicator is on, charging cannot take place (char- ging interrupted). The relevant status code appears in the display. Flashes briefly every 3 seconds: The charger outputs a warning. Charging is continued despite the adverse charging parameters. The relevant status code and the state of charge appear alternately on the display.
(7) "Charge" indicator (orange) Lit: during charging Flashes: If charging has been interrupted
(8) "Battery charged" indicator (green) On steady: Charging ended Flashes every second: Charging ended. The water refill indicator has also tripped.
22
Charging WARNING!
Danger due to escaping battery acid or explosion if faulty batteries are charged. This may result in serious injury and damage to property. Before charging, ensure that the battery to be charged is fully functional.
WARNING!
Danger due to faulty charging settings or a defective battery. This may result in serious injury and damage to property. Before charging, ensure that the battery to be charged is fully functional.
NOTE!
Risk of property damage if the charging plug contacts are very dirty. The resulting increase in contact resistance can lead to overheating and subsequent destruction of the charging plug. Keep the charging plug contacts free from impurities and clean them if necessary
1 Connect the charger mains plug to the electrical mains supply
The display appears in standard mode. The display shows the charger paramet- ers: - Type of battery (e.g. wet) - Charging characteristic (e.g. IUI) - Nominal voltage (e.g. 48 V) - Capacity (e.g. 300 Ah) - Day of the week, date and time
The charger parameters can be set individually. More information on the charger para- meters can be found under "Configuration mode" in the "Display functions" chapter. Ensure that the battery to be charged matches the configuration of the battery charging system.
2 Connect the charging plug or connect the (+) charging lead to the positive pole of the battery and the (-) charging lead to the negative pole of the battery
The charger detects that the battery is connected and starts charging. If start-up delay is activated, then charging will start at the end of the set delay time. For more information, see "Configuration mode" in the "Display" section.
During the charging process the display shows the following values: - Current charging current (A) - Current charging voltage (V) - The charge already input (Ah) - Battery temperature with the "temperature-controlled charging" option - The time (hh:mm) since charging started
23
EN
The battery symbol indicates the current state of charge. The greater the number of bars that are displayed, the further advanced the charging process is. As soon as the battery is fully charged, a minute counter will appear (see figure on right). This counts the minutes since the end of charging; when a number of chargers are being used, this makes it easier to decide which battery will have already cooled down most.
If, however, the standard display is still to be shown rather than the minute counter:
1 Use the "Up/Down" keys to toggle between the minute counter and standard display
When the battery is fully charged all 4 bars of the battery symbol appear black. As soon as the battery is fully charged, the charger begins conservation charging.
- All bars are displayed - The green "Battery charged" indic-
ator is on - The battery is always ready to use - The battery can remain connected
to the charger for as long as required
- Conservation charging counteracts battery self discharge
Interrupting char- ging
While the charging progress is interrupted:
24
2 Press the "Stop/Start" key again
As long as a battery is connected to the charger, only the charging process can be inter- rupted and resumed using the "Stop/Start" key. Display modes can be changed using the "Menu" key as described in the "Display" section, but this is only possible when there is no battery connected to the charger.
Stopping char- ging WARNING!
Danger due to ignition of oxyhydrogen caused by sparks generated when the charging leads are disconnected. This may result in serious injury and damage to property. Before disconnecting or unplugging the charging plug, first stop the charging pro-
cess by pressing the "Stop/Start" key
NOTE!
Risk of damage to the battery if it is disconnected from the charger before the charging process is complete. This may result in damage to the battery. Only disconnect the battery from the charger when it is fully charged (green "Battery
charged" indicator lights up)
As soon as the battery is fully charged and has cooled down, the following indicators light up:
- "Battery charged" indicator (green) - "Battery cooled down" indicator (blue)
25
EN
For an optimal battery life, only discon- nect the battery from the battery char- ging system when the blue "Battery cooled" indicator is showing in addition to the green indicator, in accordance with the explanation below. If several battery charging systems are in use, first disconnect the battery which has been fully charged for the longest (the coolest).
To stop the charging process:
1 Press the "Stop/Start" key
2 Unplug the charging plug or disconnect the (-) charging lead from the negative pole of the battery and the (+) charging lead from the positive pole of the battery
26
Display
The device has the following display modes:
No. Function
Standard mode In standard mode the display shows the charging parameters.
Statistics mode Visualises the frequency of the device operating modes and shows the total number of charging actions. Also shows an overview of the total and average Ah produced and energy consumed per charge.
History mode Provides information about the parameters for all the stored charging pro- cesses.
Configuration mode Configuration mode enables all the settings for the device and the charging process to be adjusted.
USB mode USB mode enables a device to be updated, device configurations to be saved and loaded, and the charging parameters to be recorded during the charging process - all using a USB flash drive.
As long as a battery is connected to the charger, the charging process can only be inter- rupted and resumed using the "Pause/Start" key. Display modes can be changed using the "Menu" key as described in the following sections that explain the individual modes, but this is only possible when there is no battery connected to the charger.
During a pause in the charging process the menu selection is available, however only in a limited form. In this case the display modes described below are available as follows:
Statistics mode and history mode remain unrestricted.
In configuration mode the following data is available: - Date and time - Device serial number - Hardware version and serial number - Software: main software, secondary software, primary software and characteristic
block version
In USB mode all options except for "Update" and "Load configuration" are available.
Standard mode Once the mains plug has been connected to the electrical mains supply, the display will automatically operate in standard mode.
In standard mode, the display shows the following charger parameters: - Type of battery (e.g. Pb-WET) - Charging characteristic (e.g. IUI) - Nominal voltage (e.g. 48 V) - Capacity (e.g. 300 Ah) - Day of the week, date and time
27
EN
The charger parameters can be set individually. More information can be found in the "Configuration mode" section.
Menu selection
Change from standard mode to the menu selection as follows: 1 Press and hold the "Menu" key for approx. 5 seconds.
Change from all other modes to the menu selection as follows: 1 Briefly press the "Menu" key.
To select the desired mode: 2 Use the "Up/Down" keys to select the symbol for the desired mode.
- e.g. the battery symbol for standard mode 3 Use the "Pause/Start" key to confirm the "Tick" symbol.
Statistics mode In statistics mode, horizontal bars display the frequency of the following device oper- ating statuses: - Idle - Charging - Floatingcharge - Cooldown - Error
1 Use the "Up/Down" keys to toggle between page 1/2 and page 2/2.
Page 2/2 shows the following values: - Total number of charges. - Total Ah output. - Average Ah output per charge. - Total energy consumed (kWh). - Average energy consumed (kWh) per
charge.
The consumed energy display is a standard value and can deviate from the actual amount of energy by up to 5% at nominal output. At lower power levels the deviation may be higher.
History mode History mode provides information about the parameters for all the stored charging pro- cesses. In order to show changing or different displays, two versions of the display win- dow are shown below:
28
1 Use the "Up/Down" keys to switch between the pages for each stored charging pro- cess.
Contents of the display window - Charge start date, e.g.: Thursday, 19/06/14. - Charge start time, e.g.: 19:29 or charging time, e.g.: 8 h 28 min. - Voltage at charge start, e.g.: 45.9 V. - Voltage after 5 minutes, e.g.: 47.9 V. - Voltage at charge end, e.g.: 48.0 V. - Ah consumed, e.g.: 397 Ah. - kWh consumed, e.g.: 19 kWh. - Charging characteristic, e.g.: 6 RI. - Set charging time, e.g.: 8 - 9 h or set Ah, e.g.: 400 Ah or set charge end time (not
shown).
(2) Empty battery Charging has not been completed.
(3) Exclamation mark with number Warning has been issued with the corresponding status code. More information can be found in the "Status codes" section.
(4) Symbol with number Error has been issued with the corresponding status code. More information can be found in the "Status codes" section.
(5) Key symbol with a tick Charging was stopped properly using the "Pause/Start" key.
(6) Key symbol with a cross Charging was stopped without using the "Pause/Start" key.
(7) Charging details Displays certain battery data at the beginning and end of the charging process:
29
EN
Configuration mode
Configuration mode provides the following setting options:
"Charging settings": settings for the battery - Type of battery, e.g. "Wet". - Charging characteristic, e.g. "IU". - Capacity (Ah) or charging time (h) depending on the charging characteristic. - Cells: voltage (V) and number of battery cells or automatic setting of the number of
cells.
CAUTION!
Danger of damage to the battery. This may result in damage to the battery. The number of cells should only be set automatically for batteries with the fol-
lowing nominal voltages: 12 V and 24 V for 24 V devices, 24 V and 48 V for 48 V devices.
Do not set the number of cells automatically for deep discharged batteries.
- Additional settings: for individual adaptation options for the charging characteristic.
"Additional functions": Additional functions - Blue LED - External start/stop - Refill indicator - Options area - Start charging again after a grid failure
"General options": General settings - Language - Contrast - Time (hh:mm:ss)
Time zone Daylight saving time/normal time
- Date (dd:mm:yy) - Length of charging cable (m) - Charging cable cross section (mm2) - AC current limitation - Unit for temperature values - Code for accessing the configuration menu activated/deactivated. - Time interval for the parameters recorded on the USB flash drive (s). - Reset statistics - Reset history
“Reset Settings” - Includes a double-check prompt ("OK?") that requires the operator to reconfirm that
this step is intended.
30
First the screen will appear in its initial format, showing the date, time and soft- ware version.
1 The "Up/Down" keys can be used to retrieve the following information: - Serial number of the charger plus serial number and version of the configuration
memory. - PC board for controller/power electronics: hardware version and serial number. - Software: main software, secondary software, primary software and character-
istic block version.
The procedure for opening the configuration menu is as follows: 1 Press the "Pause/Start" key.
You will be prompted to enter a code.
The code required is "1511" and is entered as follows:
1 Using the "Up/Down" keys, enter the first digit of the code. 2 Press the "Menu" key to move to the next digit of the code. 3 Continue following the procedure described above until the complete code has been
entered. 4 Use the "Pause/Start" key to confirm the code entered.
You will now be prompted to select one of the main menu items for the configuration mode.
31
EN
When you select a menu item you may be presented with a prompt to read the Oper- ating Instructions. Confirm this prompt by pressing the "Pause/Start" key again.
The procedure for navigating the configuration menu and its submenus is as follows: 1 Use the "Up/Down" keys to select the desired menu item. 2 Use the "Pause/Start" key to confirm the menu item, and reconfirm any double-
check prompt (e.g. "OK?"). 3 Use the "Up/Down" keys as necessary to choose an item, e.g. "Off/On" or enter a
value. 4 Use the "Pause/Start" key to confirm what you have entered. 5 If the cursor moves to another setting or position after confirmation of the previous
setting, repeat the procedure described in points (3) and (4).
To exit the current menu: 6 Press the "Menu" key to return to the higher-level menu.
See the following explanation of how to set the charging settings by way of example:
1 Use the "Up/Down" keys to select the "Charging settings" menu item. 2 Use the "Pause/Start" key to confirm this menu item.
The choice of settings for the "Charging settings" menu item will now be displayed:
the display may vary depending on the selection made. If the "Pb-WET" type of battery has been selected in combination with the "RI" characteristic ("Curve") as in the example here, the "Ah" heading is replaced by the "Charging time" setting option.
Both the start and end time can be set for this charging time period. The starting time can be deselected as required; the charging time then bases itself exclusively on the specified charge end time following a manual charge start.
When applying the settings, the user will be guided through the menu in much the same way as a wizard function.
3 Use the "Up/Down" keys to select the desired parameter (e.g. "Cells"). 4 Use the "Pause/Start" key to confirm the parameter.
32
5 Use the "Up/Down" keys to set the desired value (e.g. "24" for the number of battery cells).
6 Use the "Pause/Start" key to confirm what you have entered.
If one or more relevant settings are changed for the charging process in configuration mode, you will once again be prompted to confirm acceptance of the changed settings when exiting configuration mode.
The following settings need to be confirmed when exiting configuration mode: - Characteristic - Battery capacity in Ah (excluding the RI characteristic) - Number of cells - Equalising charge ON/OFF - CAN protocol
Example: Changing the characteristic from 3 - UI (Pb-WET) to 6 - RI (Pb-WET).
If the setting is not confirmed, the charger returns to configuration mode and the set- ting can be changed to the desired value.
Settings Below is a detailed description of the "Settings" menu item for the "Charging settings" menu item discussed above. Navigation is performed as described in the "Configuration mode" section.
A list appears with the following selection options:
The individual selection options are explained in greater detail below.
33
EN
Electrolyte circu- lation
"Air Pump" electrolyte circulation (not available on the Selectiva 220 V variant):
The electrolyte circulation cycle is con- trolled by the charger's control system. A number of selection options are available for this purpose.
The following settings are available for electrolyte circulation:
Off - Electrolyte circulation switched off.
Continuous operation (“continuous”) - Electrolyte circulation permanently on.
Program 1 to 5 - Default electrolyte circulation programs and their relevant parameters can be found
in the table under "Settings" in the "Display" chapter.
Automatic - Automatic adjustment of the electrolyte circulation flow rate based on the set battery
parameters.
User - “On”/”Off” - Individual setting of the electrolyte circulation. - The settings for "On" and "Off" determine the pulse/pause ratio of the air flow inter-
vals.
Default electrolyte circulation programs and their relevant parameters can be found in the table below:
Program ON 1 OFF 1 Repeat ON 2 OFF 2
1 30 min 25 min 1 x 5 min 25 min
2 3 min 10 min 4 x 3 min 20 min
3 3 min 12 min 1 x 3 min 12 min
4 5 min 10 min 3 x 5 min 20 min
5 2,5 min 7,5 min 1 x 2,5 min 7,5 min
In each of these programs, the solenoid valve opens for a time "ON 1" and closes for a time "OFF 1". This process is repeated for the number of times specified under "Repeat". After this number of repetitions has been completed, the process continues with the "ON 2" and "OFF 2" times until charging is completed.
Temperature-con- trolled charging
automatic/OFF/required - automatic ... Temperature-dependent adjustment of the charging characteristic. - OFF ... The measured battery temperature is not taken into account. - required ...
Charging only starts if the temperature sensor is connected.
Error overtemperature ON/OFF - ON ... Error message in the event of battery overtemperature.
Charging process stops and can only be continued once the battery has cooled down and been reconnected.
- OFF ... No error message in the event of battery overtemperature.
Warning overtemperature ON/OFF - ON ... Warning in the event of battery overtemperature. - OFF ... No warning in the event of battery overtemperature.
An external temperature sensor is required for certain characteristics. If this type of char- acteristic is selected in configuration mode, a note is shown indicating that an external temperature sensor is required.
The following characteristics require an external temperature sensor: - 28 - FCC IUI - CSM WET - 30 - FCC IUI - WET
A note is displayed if a characteristic that requires an external temperature sensor is selected.
1 Use the "Pause/Start" key to confirm the note.
Equalising charge
Equalising charge
35
EN
Delay - If the battery remains connected to the charger for the duration of the equalising
charge delay ("equalize charge delay"), a special type of charging takes place. This prevents acid stratification.
- The parameters for the current (ampere/100 ampere hours), voltage (volt/cell) and duration of the equalising charge may all be changed.
Weekday - Specify the weekday on which the equalising charge is to take place. - The parameters for the current (ampere/100 ampere hours), voltage (volt/cell) and
duration of the equalising charge may all be changed.
Manual equalising charge (“Manual”) - An equalising charge can be started manually by pressing the relevant key on the
display. - The equalising charge starts after a set delay time has been observed. The charge
parameters that have been set are followed. - The parameters for the current (ampere/100 ampere hours), voltage (volt/cell) and
duration of the equalising charge may all be changed. - This function is only available for Pb-Wet characteristics.
If a setting for the equalising charge is enabled, a symbol on the home screen next to the set ampere hours or charging time shows whether an equalising charge is being carried out or can be started.
Delay "Delay"
"Charge start delay" - Delay time (minutes) between the activation time of the charge start and the actual
charge start.
“Charge end delay” - Delay time (minutes) between the signaled end of charge (e.g. green indicator) and
the actual end of charge.
"At mains failure restart charging" - If this option is activated, the charging process is automatically restarted after a fault
in the electrical network as soon as the electrical network is available again.
"At mains failure" - Restart charging - Automatic/continue charging
If the "Restart charging" option is activated, the charging process is automatically restar- ted after a fault in the electrical network as soon as the electrical network is available again.
If the "Automatic/continue charging" option is activated, the charging process is automat- ically continued after a fault in the electrical network as soon as the electrical network is available again.
36
Calendar Calendar
The calendar function allows charging to be started automatically according to the follow- ing criteria: - Time window in which charging may not be started if a battery is connected. - Time window in which charging is to be started using a defined characteristic 1 if a
battery is connected. - Time window in which charging is to be started using a defined characteristic 2 if a
battery is connected.
1 To activate the calendar function, select the "ON" setting and confirm.
"Charging settings" menu item: - Type of battery for every character-
istic: e.g. Pb-WET.
Additional settings can be found under the "Calendar" function:
Day Setting 1-5:
The day settings allow up to five different charging start time profiles to be defined with the following settings:
- Symbol for characteristic 1: Time window in which charging is to be started using characteristic 1 (e.g.: 00:00-06:00)
- Stop: Time window in which charging must not take place (e.g.: 06:00-20:00)
- Symbol for characteristic 1: Time window in which charging is to be started using characteristic 1 (e.g.: 20:00-24:00)
37
EN
NOTE!
Ongoing charging operations are unaffected by the set time windows. If, in the example above, a battery is connected at 05:45, the charge end time is
governed according to need and is not interrupted by the end time specified for the set time window (06:00 in the example).
If the battery is connected during the "stop" time window, charging is started auto- matically during the next time window. If charging is started manually during the "stop" time window, charging will always take place using characteristic 1.
Additional settings: - Change the allocated characteristic:
characteristics symbol. - Remove the selected characteristic:
"remove".
defined.
A previously created day setting can be assigned to any day of the week.
Year Setting: - Multiple periods throughout the year
may be defined, each containing a single week setting (e.g. 1/1 - 7/1).
When the calendar function is active, a calendar symbol (shown here with the number "4" as the current date) appears on the display.
Special charges Special Charges
38
Selecting "Special Charges" allows one or more of the alternative charging types to be performed temporarily.
The "repeat" setting defines how often the alternative charging mode should be per- formed until the device reverts to the original charging parameters again:
Setting range - 1 to 99 repetitions
Disable Start Button
ON - The charging process cannot be started using the "Pause/Start" key, e.g. to prevent
unauthorised intervention.
OFF - The charging process can be started using the "Pause/Start" key.
The following settings are also possible: - Characteristic:
e.g. "Deep discharge 10" - Number of battery cells:
"Cells" - e.g. 12x - Battery capacity in Ah:
e.g. 375 Ah
“Opportunity Charge” special function
"Opportunity Charge” special function:
To extend the usage interval of a battery, it is possible to recharge it at a time when it will not be needed, e.g. during scheduled plant shutdowns.
The following curve settings are available: -
Curve - e.g. RI - Pb-WET -
Charging time - e.g. 5 - 6 h
When opportunity charging is "ON" and a battery is connected, the following appears:
39
EN
Display when RI characteristic is selected Display for other characteristics (e.g. IUI)
To start opportunity charging: - Use the "Up" key to select the runner symbol (1).
(1)
Additional func- tions
Detailed explanation of the "Additional functions" menu item in configuration mode. Nav- igation is carried out as described in the "Configuration mode" section.
1 Select the "Additional functions" menu item.
A list appears with the following selection options:
The individual selection options are explained in detail below:
“Blue LED" Setting for the time (minutes) after which the blue "Battery cold" indicator should light up to indicate that the battery is sufficiently cooled down. The set value is the time from the end of charging.
In conjunction with the "Temperature-controlled charging" option, it is possible to set a temperature value from which the blue "Battery cold" indicator should light up to indicate that the battery is sufficiently cooled down.
40
The following settings are available for external start/stop:
"Button" - The function of the "Pause/Start" button can be simulated by means of an external
button.
Normal - Start ON:
Charging starts when an external switch is closed and a battery is detected or when the charging plug is connected by closing the auxiliary contacts and a bat- tery is detected.
- Start OFF: Charging starts when a battery is connected.
- Stop ON: Charging is interrupted when an external switch is opened or when the charging plug is disconnected by opening the auxiliary contacts.
- Stop OFF: The opening of an external switch or the auxiliary contacts is ignored.
“Contact detection” - ON:
If a battery is connected when "Start ON" is set and the external start/stop contact is not closed, the status message (16) "External start/stop is not closed" appears. If charging has been started when "Stop ON" is set, the external start/stop contact is opened and the battery is not fully charged, and the status message (16) "External start/stop is not closed" appears.
- OFF: Contact detection is not executed.
“Refill indicator” The refill indicator is activated as soon as it is necessary to add distilled water to the bat- tery. The time of the refill request can be defined as follows:
Every x-th week and weekday - e.g. refill water every 2nd week on Friday
When "OFF" of set, the refill request does not have to be confirmed.
41
EN
"Relays"
Under Relays, one of the following functionalities can be set for each of the 4 terminals, viewed from left to right:
Aquamatic - Signal, e.g. for actuating a solenoid valve - "Standard" program with settings pre-configured at the factory - "User" program with user-defined setting options - For more information on Aquamatic, see the "Aquamatic" section of the "Options"
chapter.
"Charging"
"Main Charge Finished" - Signal when main charging phase is finished
“Charge not complete” - Signal if the battery is prematurely disconnected from the charger - Can be set from 1 to 10 s
"Charge OK" - Battery is being charged or is already fully charged
“Cumulative Error” - Signal in the event of an error - A power failure can be displayed as an error ("ON" setting). - If the device is in an error state, a freely defined text can be displayed, which can
contain the contact details of the dealer, for example. Detailed information can be found in the "USB mode" section.
Cumulative error + warning - In the same way as the "Cumulative error" function, the corresponding relay picks up
as soon as an error or warning is present.
"Signal Lamp" - It is possible to connect one or more suitable lamps to the relay board to indicate the
state of charge or the operating status of the battery charger. - Detailed information can be found in the "Signal lamp" section of the "Options"
chapter.
“Immobiliser”
ON - The relay picks up continuously as soon as the battery charger is connected to the
mains.
42
"Refill Indicator" - Indicates that it is necessary to refill the battery with distilled water. - Detailed information can be found in the "Additional functions" section of the "Dis-
play" chapter.
"Battery Cold"
"External Air Pump" - The settings are made as explained in section "-> Settings" for electrolyte circulation
("Air Pump").
Detailed information on the relay board can be found in the "Options" chapter.
Setting for "External lamp” According to the "Charging lights" section of the "Options" chapter, suitable external indicators can be connected in order to visualize the state of charge or the operating status of the battery charger. The following settings are available: - Normal (conventional external indicators) - RGB (LED strips)
"Remote control system"
The contrast for the remote control system can be adjusted.
"At mains failure restart charging" If this option is activated, the charging process is automatically restarted after a fault in the electrical network as soon as the electrical network is available again.
General settings Detailed explanation of the "general options" menu item in configuration mode.
1 Select the "general options" menu item.
43
EN
- Language - Display settings
• Contrast • LED brightness • Show Ah at charge end ON/OFF
- Time and Date • daylight saving time / normal time • Predefined time zones • User-defined time zones
Charging cable:
Cable cross section: - Cross-section of the charging cable (mm²)
AC current consumption:
- Adapt the maximum consumed device current to the on-site electrical install- ation or the device connector fitted on the device.
- The minimum and maximum values differ depending on the different device classes. The minimum value is approx. 25% of the maximum nominal current of the charger.
Temperature:
44
Code: - Code entry required / not required to access configuration mode ("Code ON / OFF")
USB Logging Time:
- Time interval (s) for recording char- ging parameters on the USB flash drive (USB Logging Time)
Reset statistics
Reset history
For more detailed information on the statistics and history, please refer to the "Statistics mode" and "History mode" sections.
Reset settings The menu item below "General options" offers two alternative ways of resetting all the settings:
Reset Factory Settings: - Resets to factory settings.
Reset Default Settings: - Resets settings to the manufacturer's
defaults.
USB mode In USB mode, the display shows whether or not a USB flash drive is connected.
The USB flash drive must conform to the following specifications: - Formatting: FAT32 - 32 Gigabyte maximum - No multiple partitioning
The I-SPoT VIEWER software supports the visualisation and evaluation of data on the USB flash drive. The I-SPoT VIEWER software can be found online at the following address: http://www.fronius.com/i-spot.
Only insert the USB flash drive when charging is not in progress or if the charging pro- cess has been interrupted.
If the charging process is only interrupted, not completed, it is only possible to read out data. A new update or configuration cannot be loaded.
45
EN
1 Use the "Stop/Start" key to access the following settings
2 Use the "Up/Down" keys to scroll between the settings
3 Use the "Stop/Start" key to confirm the desired setting
A USB flash drive may be connected while charging is in progress, after the "Stop/Start" key has been pressed. However, this can only be to read out data. An update or new configuration cannot be loaded.
- Safely remove Safely remove the USB flash drive as soon as the desired action has been com- pleted.
- Update A list of the suitable update files stored on the USB flash drive opens. Select and confirm the desired file in the same way as scrolling through the settings. Do not change the automatically assigned file names of the update file!
- Download The data relating to the logged charging parameters stored in the device's datalog- ger is saved to the USB flash drive for the I-SPoT VIEWER. Additionally, events - such as the device settings and user curves (configuration) - are saved. The following time ranges can be selected for the datalogger: • 1 month • 3 months • All • Since the last save
- Download optional The following options are available: • I-SPoT VIEWER
The logged data is saved in the same way as for the "Download" function, but saving only the I-SPoT VIEWER data.
• Save datalogger The logged data is saved in the same way as for the "Download" function, but is saved not in the I-SPoT VIEWER format, but as ".csv" files (Automatic folder structure for the ".csv" files: * Fronius\<device serial number>\Charges\<yyyymmdd>\<hhmmss.csv>
• Save events Events are saved to the USB flash drive.
• Save configuration The device settings are saved to the USB flash drive.
46
- Load configuration Loads onto the device one of the suitable device configurations stored on the USB flash drive
- Load dealer text A text file can be loaded from the USB flash drive that is displayed as soon as the device enters an error state. The text file can, for example, contain the contact details of the dealer. The file must be saved on the USB flash drive as a ".txt" file in "unicode" format. The file name must be "dealer.txt". The number of characters is restricted to 99.
* If a USB flash drive is connected while charging is in progress, the .csv files are saved directly to the USB flash drive. The folder structure here is also created automatically and differs due to the presence of the "Datalog" folder instead of the "Charges" folder.
Status codes
If a fault occurs during operation, specific status codes may be displayed. Faults can res- ult from the following: - Battery fault - The voltage of the connected battery is unsuitable. - The device has overheated. - There is a software or hardware fault.
Battery fault: If the battery signals a fault, the charger displays this fault as a battery fault including the corresponding fault number for the battery. The respective fault is explained in the bat- tery's Operating Instructions.
If an error message appears on the display and if you cannot resolve the error yourself: 1 Note the displayed status code: e.g. "Statecode (31)". 2 Note the configuration of the device. 3 Contact your authorised service centre
Freely-defined text, which could for example include the contact details of the distrib- utor, can be displayed if the device is in an error state.
47
EN
No. Cause / Remedy
(14) Electrolyte circulation faulty (pressure switch not switching)
(15) Control voltage not detected
(16) External start/stop is not closed.
(17) Open circuit voltage detection triggered more than once during charging (e.g. worn charging contacts)
Status codes in the event of a battery fault
No. Cause / Remedy
(22) Battery undervoltage
(23) Battery overvoltage
(26) Cell fault detected
(27) Battery not supported
(28) Battery heavily discharged - safety charging is being carried out
(29) Battery is connected with reverse polarity
(30) Thermal runaway
No. Cause / Remedy
(53) Battery voltage not supported
(54) Communication fault
(55) Battery fault
(57) Message time limit exceeded
(58) Registration failed
No. Cause / Remedy
(33) Battery overvoltage in the I2 phase
(34) Ah limit exceed
(35) Timeout in I2 phase
(36) Target voltage in I2 phase not reached (with format characteristic only)
(37) Problem with RI charge
(38) Set charging time cannot be reached
(39) Timeout in RI charge
Status codes in the event of a fault in the primary circuit
No. Cause / Remedy
(502) PCB temperature sensor faulty
(503) Primary overtemperature
(504) Fan blocked/faulty
(508) Grid failure
(530) Communication error
(533) Reference voltage outside the tolerance
(534) Start-up error
(535) PFC overcurrent
49
EN
Status codes in the event of a fault in the secondary circuit
No. Cause / Remedy
(521) Secondary overtemperature
(525) Current offset
(527) Power module overcurrent (primary)
(529) No secondary communication
(530) No primary communication
(531) Secondary EEPROM faulty
(571) ADC/SPI error
Status codes in the event of a fault in the controller
No. Cause / Remedy
(541) No secondary communication
(542) Secondary initialisation failed
(545) Primary initialisation failed
(549) Charging could not be resumed after a power failure
(550) Time not set
(551) Hardware change detected
(553) Primary update failed
(555) Incorrect device software
50
Options
Safety In order to connect optional components, it may be necessary to open the housing. The following warning notices must be obeyed:
WARNING!
Danger due to work that has been carried out improperly. This can result in serious injury and damage to property. All work involved with connecting optional components must only be carried out by
qualified specialist technicians. If Installation Instructions or User Information is available for the optional component
concerned, all warning notices and instructions therein must be obeyed. In the case of all optional components with electrical connections, once the connec-
tion work is complete, a safety inspection must be carried out in accordance with rel- evant national and international standards and directives.
Further details on safety inspections can be obtained from your authorised service centre.
They will provide you with any documents you may require on request.
WARNING!
Danger from machines falling or toppling over. This can result in serious injury and damage to property. Due to its weight, the device must be secured using suitable fittings to prevent it
from toppling or falling over. The wall and floor brackets provided by the manufacturer must be used.
Electrolyte circu- lation (not avail- able on the Selectiva 3x220 16 kW variants)
NOTE!
Danger due to the ingress of electrolyte from the battery or due to operation without any back pressure. This may result in damage to the air pump. Always set up the charger at least 0.5 m (1 ft. 7.69 in.) above the battery to be
charged. Always use an undamaged connecting hose provided specifically for this purpose to
connect the charger's compressed air outlet to the battery.
NOTE!
Danger due to non-observance of the permissible mains voltage tolerance. This can cause malfunctions and damage. For the electrolyte circulation option, a restricted mains voltage tolerance of 207 V to
250 V, phase-phase: 360 V to 433 V, applies for the charger.
The electrolyte circulation option features an air pump integrated in the charger. This introduces air into the battery through capillary tubes that are provided specifically for this purpose. This allows intensive mixing of the electrolyte to take place. The benefit is the reduced heating of the battery, and consequently longer battery-life, plus reduced water loss during charging.
51
EN
If a pump fault or leaks in the connection with the battery result in a fault being detected, then the status code "Statecode 14" will appear on the display. One way in which this fault can be indicated is by using an external indicator lamp to show a common error.
The electrolyte circulation cycle is controlled by the charger's control system. A number of selection options are available in the configuration menu for this purpose. More information can be found under "Additional functions" in the "Display" section.
The default preconfigured programs 1 to 5 are among these selection options. The relev- ant parameters for these programs are listed in the table below together with a sub- sequent explanation.
Program ON 1 OFF 1 Repeat ON 2 OFF 2
1 30 min 25 min 1 x 5 min 25 min
2 3 min 10 min 4 x 3 min 20 min
3 3 min 12 min 1 x 3 min 12 min
4 5 min 10 min 3 x 5 min 20 min
5 2.5 min 7.5 min 1 x 2.5 min 7.5 min
In each of these programs, the solenoid valve opens for a time "ON 1" and closes for a time "OFF 1". This process is repeated for the number of times specified under "Repeat". After this number of repetitions has been completed, the process continues with the "ON 2" and "OFF 2" times until charging is completed.
Cleaning the air filter insert
The air filter insert for the integrated air pump should be cleaned once a year. In dusty environments, the cleaning interval should be shortened accordingly. The air filter insert (2) must be removed for cleaning. Remove the air filter (1) by pulling it out and then refit it as follows:
(1)
External start/ stop
The external start/stop option prevents sparking if the charging plug is disconnected dur- ing charging. Special contacts inside the charging plug register a separation from the charging socket. These are leading contacts in relation to the main contacts. This trig- gers an immediate stop to charging. As a result there is no wear to the main contacts, and this arrangement safeguards more effectively against an oxyhydrogen explosion.
Charging lights
(4) (5)
Temp. Sensor Ext. Start/Stop
WARNING Hazardous Voltage Kondensator Entladezeit < 2 min. Capacitor discharge time < 2 min. Décharge de condensateur < 2 min. Condensador tiempo de descarga < 2 min. Condensatore tempo di scaricamento < 2 min.
Suitable signal lamps can be connected to the connections inside the device as illus- trated in order to indicate the state of charge or operating status of the charger. Each sig- nal lamp must have a working voltage of 12 V, and the total current drawn by all the lamps must not exceed 0.5 A. Connections (1) to (5) in the Figure are assigned as shown below. It is advisable to use the lamp colours shown below:
Connection Function Colour
(2) Battery is fully charged Green
(3) On: battery is being charged Flashing: charging has been interrupted
Yellow
(4) An error has occurred (common error) Red
(5) The battery has already cooled down and is ready for use Blue
If the RGB setting (LED strip) is set in the menu, then connection 3 (YELLOW) is not supported. The normal setting (conventional signal lamp) or RGB (LED strip) for the "External Lamp" function is explained under "Additional functions" in the "Display" sec- tion.
Temperature-con- trolled charging
The temperature-controlled charging option always adjusts the charging voltage accord- ing to the current temperature of the battery. This results in considerably longer battery- life, especially where batteries are used in cold stores.
53
EN
CAN card WARNING!
Danger from using the CAN card for safety-critical functions. This may result in serious injury and damage to property. Do not use the CAN card for safety-critical functions.
The optional CAN card enables the charger's operating statuses and the connected bat- tery's state of charge to be evaluated externally.
More information on the CAN card can be found in the instructions supplied with the CAN card option.
WARNING!
An electric shock can be fatal. Only trained service technicians may open the housing. This includes removing the con- nection plate. The device must be disconnected from the mains before starting any work with the housing open. A suitable measuring instrument must be used to ensure that electrically charged components (e.g. capacitors) are fully discharged. Use an easily legible and understandable warning sign to ensure that the charger is not reconnected to the mains supply before all the work has been completed.
WARNING!
Work that is carried out improperly can cause serious injury or damage. Connection work on the device must only be carried out by qualified specialist techni- cians. If there are Installation Instructions or User Information for the optional component concerned, then all warning notices and instructions therein must be obeyed. Once the connection work is complete, a safety inspection must be carried out in accord- ance with relevant national and international standards and directives. Further details on safety inspections can be obtained from your authorised service centre. They will provide you with any documents you may require on request.
The figure shows the connections in the CAN connection area. The CAN connection area is located behind the connection plate on the front of the device.
(2) black
CAN GND brown
Ext. Start/Stop (+)
Relay board WARNING!
Danger from using the relay board for safety-critical functions. This can result in serious injury and damage to property. Do not use the relay board for safety-critical functions.
NOTE!
Danger due to non-observance of the permissible mains voltage tolerance. This can cause malfunctions and damage. For the relay board option, a restricted L-N input voltage of a maximum of 250 V
applies in relation to the charger.
Risk of Electric Shock! Do not operate at circuits more than 250 V to ground! 0... 30V DC/4A 0... 250V AC/4A Use Copper Conductors Only!
C Common NC Normally Closed NO Normally Opened L Line N Neutral Wire
max. 1A AC Output!
42 ,0
40 9,
00 08
C NC NO C NC NO C NC NO L/C NC NO N
WARNING!

The optional relay board enables the charger's operating statuses and the connected battery's state of charge to be evaluated externally. One or more external consumers can also be supplied with L-N input voltage. A neutral conductor in the electrical mains sup- ply is a prerequisite for this. The configuration of the relay board outputs is explained in the Operating Instructions for the charger: "Additional functions" in the "Display" section.
More information on the relay board can be found in the instructions supplied with the relay board option.
There follows an overview of the options that are directly connected with the relay board. These relay-connected options are activated through the relay board outputs: - Aquamatic control - Charging - Charge 50% - Charge 80% - Charge end - Main charge finished - Charge OK - Charging not finished
Signal if the battery is prematurely disconnected from the charger - Common error - Common error + warning - Signal lamp - Immobiliser device - ON - Refill indicator - Battery cooled - External air pump (electrolyte circulation)
55
EN
Aquamatic con- trol
The Aquamatic control contains the controller for a solenoid valve that automatically tops up the water in the battery to be charged.
Standard setting - At the start of the recharging phase, the solenoid valve opens for 12 seconds and
then closes for 4 seconds. - This cycle is repeated 26 times.
USER setting - Configurable "ON" time (solenoid valve opens) after the end of the main charge
phase.
Charging The "Charging" option is suitable for actuating a signal lamp for instance. While charging is in progress, the corresponding relay picks up automatically.
Charge 50% Like the "Main charge finished" function, the relevant relay switches as soon as the bat- tery is 50% charged.
Charge 80% Like the "Main charge finished" function, the relevant relay switches as soon as the bat- tery is 80% charged.
Charging not complete
The "Charging not complete" option lends itself to the actuation of an audible alarm device, for example. If the battery is disconnected from the charger before the charging process is complete, the relay switches for an adjustable time of 1 to 10 seconds.
Charge finish The "Charge finish" option is suitable for actuating a signal lamp for instance. Once the configured charging characteristic is fully completed, the corresponding relay picks up automatically.
Main charge fin- ished
The "Main charge finished" option is suitable for actuating a signal lamp for instance. When the main charge phase finishes, the corresponding relay picks up automatically.
Common error message
The "Common error message" option is suitable for actuating a signal lamp for instance. Each time an error is detected, the relevant relay picks up automatically.
Common error + warning
In the same way as for the "Common error" function, the corresponding relay trips as soon as an error or warning is detected.
Signal lamp As an alternative to the charging lights, one or more suitable lamps can be connected to the relay board to indicate the state of charge or operating status of the charger. These
56
lamps can be designed for a voltage of up to 30 V DC or up to 250 V AC on a starpoint- earthed network.
If the lamp circuit is potential-free, then the switching current must not exceed 4 A. A lamp that is actuated by the 230 V supply relay must be operated with an output current of max. 1 A.
Immobiliser device
If the charger is built into a vehicle as an on-board device, the optional immobiliser device will prevent the vehicle from being started unintentionally whilst charging is taking place. This protects the vehicle, the battery and the charger leads from damage.
As soon as the vehicle is connected to the mains supply, the corresponding relay picks up and blocks the ignition signal for instance. Another example is the actuation of a suit- able signal lamp to convey the message visually that charging is currently in progress.
Battery cooled down
The corresponding relay switches automatically once the time set in the menu has passed.
External air pump - electrolyte cir- culation
This option enables an external air pump to be activated by a relay contact in the sense of the "electrolyte circulation" option.
Wall bracket The robust wall bracket ensures safe fitting on site. More information can be found in the corresponding Installation Instructions.
Floor bracket The robust floor bracket ensures safe fitting on site. More information can be found in the corresponding Installation Instructions.
LED strip The LED strip acts as a status indicator and lights up in the same colours as the display elements on the control panel. An LED strip including a diffuser is installed in the gap between the front wall and upper part of the housing.
IP 23 The IP 23 option increases the IP protection rating of the device from IP 20 to IP 23. More detailed information can be found in the corresponding User Information.
Air filter In dusty environments, the air filter prevents the inside of the device from becoming dirty. This avoids a possible reduction in power and other problems. Detailed information can be found in the corresponding User Information. Cleaning interval as required (manufacturer's recommendation: monthly)
"Mobile" kit A carrying strap and handle improve the mobility of the device.
57
EN
Remote control system
The remote control system allows the device to be fully controlled from a distance of up to 30 m (98 ft., 5.1 in.). This option includes a full control panel in an aluminium housing that provides IP42 protection.
58
Selectiva 16 kW 220 V
Mains voltage (-10%/+30%) 1)
Optional: 3~ NPE 220 V/50/60 Hz 3~ PE 220 V/50/60 Hz
Mains fuse protection 2) 32 A
Minimum mains lead cross section Selectiva 4120 Selectiva 4140/4160
4 mm² (0.0062 in.²) 6 mm² (0.0093 in.²)
Duty cycle 100%
According to the "Device-specific data" table below
Degree of protection 4) IP 20
Overvoltage category III
Operating temperature 5) -20°C to +40°C (-4°F to 104°F)
Storage temperature -25°C to +80°C (-13°F to 176°F)
Relative humidity max. 85%
Mark of conformity according to rating plate
Product standard EN 62477-1
Dimensions L x W x H 647 x 247 x 392 mm (25.47 x 9.72 x 15.43 in.)
Weight (with standard mains and charging leads) 34.84 kg (76.81 lb)
Degree of contamination 3
1) The device is approved for operation on neutral-earthed mains networks with a maximum outer conductor nominal voltage of 220 V.
2) Nothing other than a type B residual current circuit breaker should ever be used for connecting the device to the mains. The earth leakage current is less than 3.5 mA.
3) Interface to a 127/220 V and 50 Hz public grid.
4) For indoor use only, do not expose to rain or snow.
5) A high ambient temperature may result in power degradation (derating).
59
EN
Zmax
28.5 A 9070 W 48 V 120 A 203 mOhm
4140 3x220 16 kW
29.6 A 9390 W 48 V 140 A 183 mOhm
4160 3x220 16 kW
29.9 A 9490 W 48 V 160 A 156 mOhm
60
Selectiva 8 kW 400 V
Mains voltage (-10%/+30%) 1)
Optional: 3~ NPE 400 V / 50/60 Hz 3~ PE 400 V/50/60 Hz
Mains fuse protection 2) 16 A
Minimum mains lead cross section 2.5 mm² (0.003875 in.²)
Duty cycle 100%
EMC device class B
Standby consumption 24 V devices 48 V devices 80 V devices
10 W 10.1 W 10.3 W
Protection class I
None
Overvoltage category III
Operating temperature 5) -20°C to +40°C (-4°F to 104°F)
Storage temperature -25°C to +80°C (-13°F to 176°F)
Relative humidity max. 85%
Mark of conformity according to rating plate
Product standard EN 62477-1
Dimensions L x W x H 633 x 180 x 344 mm (24.92 x 7.09 x 13.54 in.)
Weight (with standard mains and charging leads) 23 kg (50.71 lb)
Degree of contamination 3
1) The device is approved for operation on neutral-earthed mains networks with a maximum outer conductor nominal voltage of 400 V. An L-N mains voltage toler- ance of 207 V to 250 V applies for the electrolyte circulation and relay board options.
2) Nothing other than a type B residual current circuit breaker should ever be used for connecting the device to the mains. If the charger is protected by a 32 A fuse, the thermal stress of the automatic cir- cuit breaker must not exceed 82000 A²s. The earth leakage current is less than 3.5 mA.
3) Interface to a 230/400 V and 50 Hz public grid.
4) For indoor use only, do not expose to rain or snow.
5) A high ambient temperature may result in power degradation (derating).
Device-specific data
Max. AC power
Max. charging current
2100 8 kW 6.7 A 3860 W 24 V 100 A
61
EN
Max. AC power
Max. charging current
2120 8 kW 7.8 A 4590 W 24 V 120 A
2140 8 kW 9.0 A 5350 W 24 V 140 A
2160 8 kW 10.1 A 6090 W 24 V 160 A
2180 8 kW 11.2 A 6860 W 24 V 180 A
2200 8 kW 12.3 A 7610 W 24 V 200 A
2225 8 kW 13.7 A 8560 W 24 V 225 A
4060 8 kW 7.3 A 4610 W 48 V 60 A
4075 8 kW 9.0 A 5710 W 48 V 75 A
4090 8 kW 10.6 A 6820 W 48 V 90 A
4090A 8 kW 10.4 A 6810 W 48 V 90 A
4120 8 kW 13.8 A 9050 W 48 V 120 A
4120A 8 kW 13.7 A 9040 W 48 V 120 A
4140 8 kW 14.4 A 9340 W 48 V 140 A
4140A 8 kW 14.3 A 9280 W 48 V 140 A
4160 8 kW 14.5 A 9390 W 48 V 160 A
4160A 8 kW 14.4 A 9370 W 48 V 160 A
4185 8 kW 15.3 A 9950 W 48 V 185 A
8040 8 kW 8.2 A 5000 W 80 V 40 A
8060 8 kW 12.0 A 7440 W 80 V 60 A
8060A 8 kW 11.8 A 7440 W 80 V 60 A
8075 8 kW 14.1 A 9110 W 80 V 75 A
8075A 8 kW 14.0 A 9110 W 80 V 75 A
8090 8 kW 14.2 A 9210 W 80 V 90 A
8090A 8 kW 14.1 A 9190 W 80 V 90 A
8110 8 kW 15.1 A 9740 W 80 V 110 A
62
Selectiva 16 kW 400 V
Mains voltage (-10%/+30%) 1)
Optional: 3~ NPE 400 V/50/60 Hz 3~ PE 400 V/50/60 Hz
Mains fuse protection 2) 32 A
Minimum mains lead cross-section Selectiva 4210/8120/8140 Selectiva 8160/8180/8210
4 mm² (0.0062 in.²) 6 mm² (0.0093 in.²)
Duty cycle 100%
According to the "Device-specific data" table below
Degree of protection 4) IP 20
Overvoltage category III
Operating temperature 5) -20°C to +40°C (-4°F to 104°F)
Storage temperature -25°C to +80°C (-13°F to 176°F)
Relative humidity max. 85%
Mark of conformity according to rating plate
Product standard EN 62477-1
Dimensions L x W x H 647 x 247 x 392 mm (25.47 x 9.72 x 15.43 in.)
Weight (with standard mains and charging leads) 36.8 kg (81.13 lb)
Degree of contamination 3
1) The device is approved for operation on neutral-earthed mains networks with a maximum outer conductor nominal voltage of 400 V. An L-N mains voltage toler- ance of 207 V to 250 V applies for the electrolyte circulation and relay board options.
2) Nothing other than a type B residual current circuit breaker should ever be used for connecting the device to the mains. The earth leakage current is less than 3.5 mA.
3) Interface to a 230/400 V and 50 Hz public grid.
4) For indoor use only, do not expose to rain or snow.
5) A high ambient temperature may result in power degradation (derating).
Device-specific data
Zmax
4210 16 kW 27.6 A 15860 W 48 V 210 A
8120 16 kW 23.8 A 14830 W 80 V 120 A 96 mOhm
63
EN
Zmax
8140 16 kW 27.5 A 17270 W 80 V 140 A 82 mOhm
8160 16 kW 30.3 A 18150 W 80 V 160 A 74 mOhm
8180 16 kW 30.6 A 18260 W 80 V 180 A 67 mOhm
8210 16 kW 30.9 A 18430 W 80 V 210 A 67 mOhm
64
65
EN
66
67
EN