8000 Db 0710

download 8000 Db 0710

of 32

Transcript of 8000 Db 0710

  • 8/9/2019 8000 Db 0710

    1/32

    Instruction Bulletin

    8000DB0710

    04/2010

    Raleigh, NC, USA

    Mimicking a PanelMateIndicator Template in Vijeo Designer

    Retain for future use.

    2010 Schneider Electric All Rights Reserved

    Overview This instruction bulletin provides step-by-step instructions on programmingobjects within Vijeo Designer software to mimic the visual and functionaloperation of PanelMateindicator templates when PanelMate is not available.

    Presumptions This bulletin is written for individuals familiar with VijeoDesigner software.If you are not familiar with this software, please consult your system

    administrator before attempting to program objects.

    Requirements The following software is required:

    Software

    PanelMate ePro PS

    Vijeo Designer V4.5.1 or higher

    SnagItor equivalent screen capture tool

  • 8/9/2019 8000 Db 0710

    2/32

    Mimicking a PanelMateIndicator Template in VijeoTM Designer 8000DB0710

    Table of Contents 04/2010

    2010 Schneider Electric All Rights Reserved2

    Table of Contents Overview ..................................................................................................... 1

    Presumptions .............................................................................................. 1

    Requirements .............................................................................................. 1

    Table of Contents ........................................................................................2

    Safety Information ......................................................................................3

    Notice .......................................................................................................... 3Qualified Personnel .....................................................................................4

    Before You Begin ....................................................................................... 4

    Start Up and Test ........................................................................................5

    Operation and Adjustments ......................................................................... 6

    Product Related Information ....................................................................... 6

    User Comments ..........................................................................................6

    PanelMate Indicator Template .................................................................. 7

    Indicator Attributes Tab ...............................................................................7

    Indicator States Tab .................................................................................... 8

    Control Definitions Tab ................................................................................9

    PanelMate Indicator Template Conversion Examples ....................... 10

    Creating Indicator Attributes ...................................................................... 10

    Creating Indicator States ...........................................................................13

    Creating Control Definitions ...................................................................... 21

    Testing the Indicator Template ................................................................. 31

  • 8/9/2019 8000 Db 0710

    3/32

    8000DB0710 Mimicking a PanelMateIndicator Template in VijeoTM Designer

    04/2010 Safety Information

    2010 Schneider Electric All Rights Reserved 3

    Safety Information

    Notice Read these instructions carefully, and look at the equipment to becomefamiliar with the device before trying to install, operate, or maintain it. The

    following special messages may appear throughout this documentation or

    on the equipment to warn of potential hazards, or to call attention toinformation that clarifies or simplifies a procedure.

    A lightning bolt or ANSI man symbol in a Danger or Warning safety label

    on the equipment indicates an electrical hazard which, as indicated below,

    can or will result in personal injury if the instructions are not followed.

    The exclamation point symbol in a safety message in a bulletin indicates

    potential personal injury hazards. Obey all safety messages introduced by

    this symbol to avoid possible injury or death.

    Symbol Name

    Lightning Bolt

    ANSI Man

    Exclamation Point

    DANGERDANGERindicates an imminently hazardous situation which, if not

    avoided, will result indeath or serious injury.

    WARNINGWARNINGindicates a potentially hazardous situation which, if not

    avoided, can result indeath or serious injury.

    CAUTION

    CAUTION indicates a potentially hazardous situation which, if not

    avoided, can result inminor or moderate injury.

    CAUTIONCAUTION, used without the safety alert symbol, indicates a potentially

    hazardous situation which, if not avoided, can result inproperty damage.

  • 8/9/2019 8000 Db 0710

    4/32

    Mimicking a PanelMateIndicator Template in VijeoTM Designer 8000DB0710

    Before You Begin 04/2010

    2010 Schneider Electric All Rights Reserved4

    Qualified Personnel For the protection of personnel and equipment, a qualified person mustperform the procedures detailed in this bulletin.

    A qualified person is one who has skills and knowledge related to the

    construction and operation of this electrical equipment and the installation,

    and has received safety training to recognize and avoid the hazards

    involved. Refer to the most current release of NFPA 70E, Standard for

    Electrical Safety in the Workplace, for safety training requirements.

    In addition, the person must be:

    Able to read, interpret, and follow the instructions and precautions in this

    data bulletin and the other documentation referenced.

    Able to use the required tools listed in this data bulletin in a safe and

    correct manner.

    Before You Begin Do not use this product on machinery lacking effective point-of-operationguarding. Lack of effective point-of-operation guarding can result in serious

    injury to the operator.

    .

    This automation equipment and related software is used to control a variety of

    industrial processes. The type or model of automation equipment suitable for

    each application will vary depending on factors such as the control function

    required, degree of protection required, production methods, unusualconditions, and government regulations. In some applications, more than one

    processor may be required, as when backup redundancy is needed.

    Only the user can be aware of all the conditions and factors present during

    setup, operation, and maintenance of the machine; therefore, only the user can

    determine the correct automation equipment and the related safeties and

    interlocks to be used. When selecting automation and control equipment and

    related software for a particular application, refer to the applicable local and

    national standards and regulations. The National Safety Councils Accident

    Prevention Manual (nationally recognized in the United States of America) also

    provides much useful information.

    In some applications, such as packaging machinery, additional operator

    protection such as point-of-operation guarding must be provided. This is

    necessary if the operators hands and other parts of the body are free to enterthe pinch points or other hazardous areas and serious injury can occur.

    Software products by themselves cannot protect an operator from injury. For

    this reason, the software cannot be substituted for, or take the place of,

    point-of-operation protection.

    WARNINGUNGUARDED MACHINERY CAN CAUSE SERIOUS INJURY

    Do not use this software and related automation equipment on

    equipment which does not have point-of-operation protection.

    Do not reach into machinery during operation.

    Failure to foll ow these instructions can result in death, serious

    injury, or equipment damage.

  • 8/9/2019 8000 Db 0710

    5/32

    8000DB0710 Mimicking a PanelMateIndicator Template in VijeoTM Designer

    04/2010 Before You Begin

    2010 Schneider Electric All Rights Reserved 5

    Ensure that the appropriate safeties and mechanical/electrical interlocks

    related to point-of-operation protection have been installed and are

    operational before placing the equipment into service. All interlocks and

    safeties related to point-of-operation protection must be coordinated with

    the related automation equipment and software programming.

    NOTE: Coordination of safeties and mechanical/electrical interlocks for

    point-of-operation protection is outside the scope of the Function BlockLibrary, System User Guide, or other implementation referenced in this

    documentation.

    Start Up and Test Before using electrical control and automation equipment for regularoperation after installation, test the system to ensure the equipment is

    operating correctly. Allow enough time for a complete test.

    Perform all start up tests recommended in the equipment documentation.

    Store all equipment documentation for future references.

    Software testing must be performed in both simulated and real

    environments.

    Verify that the completed system is free from all short circuits and grounds,

    except those grounds installed according to local regulations (according tothe National Electrical Codein the U.S.A., for instance). If high-potential

    voltage testing is necessary, follow recommendations in the equipment

    documentation to prevent accidental equipment damage.

    Before energizing equipment:

    Remove tools, meters, and debris from equipment.

    Close the equipment enclosure door.

    Remove ground from incoming power lines.

    Perform all start up tests recommended by the manufacturer.

    CAUTION

    EQUIPMENT OPERATION HAZARD

    Verify that all installation and set up procedures have been completed.

    Before operational tests are performed, remove all blocks or othertemporary holding means used for shipment from all component

    devices.

    Remove tools, meters, and debris from equipment.

    Failure to follow these instructions can result in injury or equipment

    damage.

  • 8/9/2019 8000 Db 0710

    6/32

    Mimicking a PanelMateIndicator Template in VijeoTM Designer 8000DB0710

    Before You Begin 04/2010

    2010 Schneider Electric All Rights Reserved6

    Operation and Adjustments The following precautions are from the NEMA Standards PublicationICS 7.1-1995 (English version prevails):

    Regardless of the care exercised in the design and manufacture of

    equipment or in the selection and rating of components, there are

    hazards that can be encountered if such equipment is improperly

    operated.

    It is sometimes possible to misadjust the equipment and thus produce

    unsatisfactory or unsafe operation. Always use the manufacturers

    instructions as a guide for functional adjustments. Personnel who have

    access to these adjustments should be familiar with the equipment

    manufacturers instructions and the machinery used with the electrical

    equipment.

    Only those operational adjustments actually required by the operator

    should be accessible to the operator. Access to other controls should be

    restricted to prevent unauthorized changes in operating characteristics.

    Product Related Information

    User Comments We welcome your comments about this bulletin. You can reach us by e-mailat [email protected].

    DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

    Apply appropriate personal protective equipment (PPE) and follow safe

    electrical work practices. See NFPA 70E.

    This equipment must be installed and serviced only by qualified

    electrical personnel.

    Turn off all power supplying this equipment before working on or inside

    equipment. Disconnect the power at the processor and at the power

    source.

    Always use a properly rated voltage sensing device to confirm power is off.

    Replace all devices, doors, and covers before turning on power to this

    equipment.

    Confirm that a proper ground connection exists before applying power

    to the unit. Use only the specified voltage when operating this equipment and any

    associated products.

    Failure to follow these instructions will result in death or serious injury.

  • 8/9/2019 8000 Db 0710

    7/32

    8000DB0710 Mimicking a PanelMateIndicator Template in VijeoTM Designer

    04/2010 PanelMate Indicator Template

    2010 Schneider Electric All Rights Reserved 7

    PanelMateIndicator

    Template

    The indicator templates are used as the lights and buttons of a control panel

    that indicate the status of devices and control the devices (for example, by

    turning them on or off). See Figure 1.

    When you design or double-click on a new indicator template, a dialog boxappears with three tabs:

    Indicator Attributes

    Indicator States

    Control Definitions

    Indicator Attr ibutes Tab In the Indicator Attributes tab, you can define the indicator label, templatesize, label font, and visibility options. See Figure 2below and Figure 3on

    page 8.

    Figure 1: Indicator Template

    Figure 2: Indicator At tr ibutes Tab

    A. Indicator label

    B. Visibility options

    C. Template size

    D. Label fontA

    B

    C

    D

  • 8/9/2019 8000 Db 0710

    8/32

    Mimicking a PanelMateIndicator Template in VijeoTM Designer 8000DB0710

    PanelMate Indicator Template 04/2010

    2010 Schneider Electric All Rights Reserved8

    Indicator States Tab In the Indicator States tab, you can define the indicator text message, whichis the condition that drives the message, label color, and alarm options. See

    Figures 4and 5.

    Figure 3: Set ting A tt ribu tes

    NOTE: Width=2, double-wide block

    Figure 4: Indicator States Tab

    A. Indicator text message

    B. Label color

    C. Condition that drives message

    D. Alarm options

    Figure 5: Set ting Indicator States

    A. Indicator States summary

    B. As you enter data into these fields, the

    Indicator States summary (A) is automatically

    updated.

    C. This option sets the color for the indicatorwhen the state is true.

    AD

    C

    B

    B

    A

    C

  • 8/9/2019 8000 Db 0710

    9/32

    8000DB0710 Mimicking a PanelMateIndicator Template in VijeoTM Designer

    04/2010 PanelMate Indicator Template

    2010 Schneider Electric All Rights Reserved 9

    Control Definitions Tab In the Control Definitionstab (optional), you can define control for theindicator template.

    If defined, the indicator will display an arrow in the bottom left-hand corner.

    See Figures 6and 7.

    When no control definitions are defined and the indicator is touched, nothing

    happens on the screen. It only functions as a display. When the indicator is

    touched, the control options appear on the screen. See Figure 7.

    Figure 6: Control Def in it ions Tab

    A. Control Definitions summary

    B. As you enter data into these fields, the

    Control Definitions summary (A) is

    automatically updated.

    C. Label color

    D. This option sets the color for the indicator

    when the state is true.

    DC

    B

    A

    B

    Figure 7: Control DefinitionsUndefined and Defined

    Undefined Defined

    NOTE:Arrow appears when definition is defined.

  • 8/9/2019 8000 Db 0710

    10/32

    Mimicking a PanelMateIndicator Template in VijeoTM Designer 8000DB0710

    PanelMate Indicator Template Conversion Examples 04/2010

    2010 Schneider Electric All Rights Reserved10

    PanelMateIndicator Template Conversion Examples

    Creating Indicator Attr ibutes To create indicator attributes that mimic the PanelMate template (seeFigure 8), follow the steps below using Vijeo Designer.

    1. Create a square that is 5 units by 5 units, which is close to the size of a

    1 inch wide template used in the PanelMate software. See Figure 9.

    Figure 8: PanelMate TemplateIndicator Attributes

    Figure 9: Creat ing a Square

    5 units5units

  • 8/9/2019 8000 Db 0710

    11/32

    8000DB0710 Mimicking a PanelMateIndicator Template in VijeoTM Designer

    04/2010 PanelMate Indicator Template Conversion Examples

    2010 Schneider Electric All Rights Reserved 11

    2. Modify the rectangle properties (fore color and shape) to get the visual

    effects shown in Figure 10.

    3. Repeat the procedure with another rectangle the size of 5 units by 2 units

    and modify the shape properties. See Figure 11.

    4. Create a text boxwith the size of 5 units by 2 units.

    Figure 10: Modifying Rectangle Properties

    5 units 2units

    Figure 11: Creat ing a Rectangle

    5 units 2units

  • 8/9/2019 8000 Db 0710

    12/32

    Mimicking a PanelMateIndicator Template in VijeoTM Designer 8000DB0710

    PanelMate Indicator Template Conversion Examples 04/2010

    2010 Schneider Electric All Rights Reserved12

    5. After placing the text box, the Text Editor dialog box appears. Type

    Indicator Label, then click on OK. See Figure 12.

    6. Move thetext box and place it over the smaller rectangle.

    7. To group both objects together, use the pointer to select both objects,

    then right-click. A pop-up window appears. Select Group. See Figure 13.

    8. Move this group over the first square object and group again, if desired.

    Figure 12: Placing Text Box

    Figure 13: Grouping Objects Together

  • 8/9/2019 8000 Db 0710

    13/32

    8000DB0710 Mimicking a PanelMateIndicator Template in VijeoTM Designer

    04/2010 PanelMate Indicator Template Conversion Examples

    2010 Schneider Electric All Rights Reserved 13

    Creating Indicator States To create indicator states that mimic the PanelMatetemplate, follow thesteps below using Vijeo Designer.

    1. In the PanelMate Configuration Editor, examine the Indicator States tab.

    See Figure 14.

    If the PLC reference 0001 istrue, the first state (1:) will display the text

    ON. The color scheme is black text on a green background (no alarm isdeclared).

    Figure 14: Indicator State 1

  • 8/9/2019 8000 Db 0710

    14/32

    Mimicking a PanelMateIndicator Template in VijeoTM Designer 8000DB0710

    PanelMate Indicator Template Conversion Examples 04/2010

    2010 Schneider Electric All Rights Reserved14

    2. In the PanelMateConfiguration Editor, examine the next state within

    the Indicator States tab. See Figure 15.

    If the PLC reference 0001 is false, the second state (2:) will display the

    text OFF. The color scheme is white text on a red background (no alarm

    is declared).

    3. In Vijeo Designer, select the Text Message icon and create a box that is

    5 units by 2 units. After placing the message box on the screen, a

    Message Display Settings dialog box appears. See Figure 16.

    Figure 15: Indicator State 2

    Figure 16: Message Display Settings

  • 8/9/2019 8000 Db 0710

    15/32

    8000DB0710 Mimicking a PanelMateIndicator Template in VijeoTM Designer

    04/2010 PanelMate Indicator Template Conversion Examples

    2010 Schneider Electric All Rights Reserved 15

    4. In the Message Display Settings dialog box, General tab, change the

    States field to 2.

    5. Select the variable by clicking on the light bulb icon. In the Expression

    Editor Pad dialog box, select the variable Discrete01 and click OK. See

    Figure 17..

    Now, assign a Color Resource to match the indicator template.

    1. Click on the New Resource icon. In the New Resources dialog box, click

    OK. In the next pop-up window, click Yes. See Figure 18.

    Figure 17: Selecting Variable

    NOTE: In this example, there are only two

    states: ON and OFF.

    NOTE: In this example, the variable represents the PLC

    reference 00001.

    Figure 18: New Resources

  • 8/9/2019 8000 Db 0710

    16/32

    Mimicking a PanelMateIndicator Template in VijeoTM Designer 8000DB0710

    PanelMate Indicator Template Conversion Examples 04/2010

    2010 Schneider Electric All Rights Reserved16

    2. In the Target1 edit resource dialog box (see Figure 19), under the Label

    column, enter the text OFFand ON. In the Text column, change the text

    color in the bottom row to black. In the Frame and Plate columns,

    change the color to red for state 0 and to green for state 1.

    3. In the Navigator pane (see Figure 20), expand theResource Libraryindex, then click on Color. You should be able to see the color resource.

    Figure 19: Target 1 Edit Resource

    Figure 20: Resource Library IndexColor

  • 8/9/2019 8000 Db 0710

    17/32

    8000DB0710 Mimicking a PanelMateIndicator Template in VijeoTM Designer

    04/2010 PanelMate Indicator Template Conversion Examples

    2010 Schneider Electric All Rights Reserved 17

    4. In the Navigator pane (see Figure 21), under the Resource Library

    index, click on Text. A Target1Text Resources dialog box will appear.

    Click on the pull-down listbox under the Font Name column and select

    New Resource.

    5. In the New Resource dialog box (see Figure 22), select Vijeo Modern

    13x23 font and click OK.

    6. To avoid repeating above steps 4 and 5, in the updated Text Resources

    dialog box (see Figure 22), select the Font Name for state 1 and choose

    Font Resource001.

    Figure 21: Resource Library IndexText

    Figure 22: New ResourceFont

  • 8/9/2019 8000 Db 0710

    18/32

    Mimicking a PanelMateIndicator Template in VijeoTM Designer 8000DB0710

    PanelMate Indicator Template Conversion Examples 04/2010

    2010 Schneider Electric All Rights Reserved18

    7. You have inserted a larger font to accommodate the Quad size selected

    in the Attributes tab. See Figure 23.

    8. In the Message Display settings, select Plate Style, then choose 00027.

    See Figure 24. Your screen should resemble the indicator label in the

    right-hand screen of Figure 24.

    Figure 23: Font for Quad Size

    Figure 24: Message Display Settings

  • 8/9/2019 8000 Db 0710

    19/32

    8000DB0710 Mimicking a PanelMateIndicator Template in VijeoTM Designer

    04/2010 PanelMate Indicator Template Conversion Examples

    2010 Schneider Electric All Rights Reserved 19

    9. Double-click the square object to open the Animation Properties dialog

    box. See Figure 25.

    10. Check the Enable Color Animation box, and then click on the light bulb

    icon. Select the variable Discrete01. Then, for color resource, click on

    the New Resource icon. See Figure 25.

    11. Change the No. of States to 2 and click OK. When the pop-up window

    appears, click Yes. See Figure 26.

    Figure 25: Animation Propert ies

    Figure 26: New ResourceNo. of States

  • 8/9/2019 8000 Db 0710

    20/32

    Mimicking a PanelMateIndicator Template in VijeoTM Designer 8000DB0710

    PanelMate Indicator Template Conversion Examples 04/2010

    2010 Schneider Electric All Rights Reserved20

    12. You should see the ColorResource002 table. See Figure 27.

    Change the Off state color from green to red and the On state color from

    red to green. Then, delete the states 0 and 1. The final version should

    resemble the right-side screen in Figure 27.

    13. Move the message box and place it on the square (as shown in

    Figure 28).

    Figure 27: Color Resource Table

    Figure 28: Placing Message Box

  • 8/9/2019 8000 Db 0710

    21/32

    8000DB0710 Mimicking a PanelMateIndicator Template in VijeoTM Designer

    04/2010 PanelMate Indicator Template Conversion Examples

    2010 Schneider Electric All Rights Reserved 21

    Creating Control Definitions NOTE: In this example, there are two control definitions:

    Turn ON: black text on green background, controls PLC reference

    00100. See Figure 29.

    Turn OFF: white text on red background, controls PLC reference

    00101. See Figure 29.

    When the user touches the screen, these control definitions automatically

    appear on the right-hand side of the screen. When the associated button ispressed, the PanelMatesoftware sends a command that turns these

    references ON, so they act as momentary contacts.

    Figure 29: Control Def ini tions

  • 8/9/2019 8000 Db 0710

    22/32

    Mimicking a PanelMateIndicator Template in VijeoTM Designer 8000DB0710

    PanelMate Indicator Template Conversion Examples 04/2010

    2010 Schneider Electric All Rights Reserved22

    To mimic the behavior of PanelMatesoftware within Vijeo Designer, the

    control definition functionality requires some additional software

    development. It is recommended you use a screen capture tool similar to

    Snagitto capture control definition images within the PanelMate software

    screen. See Figure 30.

    1. To mimic the behavior of the control definitions, use Vijeo Designers

    Popup Windows.

    From the Navigator pane, select Popup Windows, then right-click. In the

    pop-up window that appears, select and click New Popup Window. See

    Figure 31.

    2. Click on the new window. Your screen should resemble the right-hand

    screen in Figure 31.

    Figure 30: Capturing Control Definition Images within PanelMate Software

    Figure 31: Navigator PanePopup Windows

  • 8/9/2019 8000 Db 0710

    23/32

    8000DB0710 Mimicking a PanelMateIndicator Template in VijeoTM Designer

    04/2010 PanelMate Indicator Template Conversion Examples

    2010 Schneider Electric All Rights Reserved 23

    3. To match the background color of the images captured from the

    PanelMatesoftware, select Back Color in the Property Inspector dialog

    box. Select the dark grey icon or tweak the color bar to match the color.

    Click OK. See Figure 32.

    4. For ease of use, change the name of the pop-up window to

    IndicatorPopUp . See Figure 32.

    5. Copy and paste the images of the control definition to the Popup

    Windows screen. See Figure 33.

    6. Click on the Switch icon and create a switch approximately the same

    size as your image. See Figure 33.

    Figure 32: Property Inspector

    Figure 33: Control Definit ion Images

  • 8/9/2019 8000 Db 0710

    24/32

  • 8/9/2019 8000 Db 0710

    25/32

    8000DB0710 Mimicking a PanelMateIndicator Template in VijeoTM Designer

    04/2010 PanelMate Indicator Template Conversion Examples

    2010 Schneider Electric All Rights Reserved 25

    11. To place and size the button, right-click in an unused area of the

    IndicatorPopUp window. In the pop-up window, deselect Snap to Matrix.

    See Figure 36.

    12. Size and place the button over the Turn ON image. Then copy

    (control +C) and paste (control + V) the pushbutton. Move the second

    pushbutton over the Turn OFF image. See Figure 37.

    Figure 36: Deselect Snap to Matrix

    Figure 37: Copying and Pasting Pushbutton

  • 8/9/2019 8000 Db 0710

    26/32

    Mimicking a PanelMateIndicator Template in VijeoTM Designer 8000DB0710

    PanelMate Indicator Template Conversion Examples 04/2010

    2010 Schneider Electric All Rights Reserved26

    13. Double-click the second pushbutton. In the Switch Settings dialog box,

    change the Destination by clicking on the light bulb icon. See Figure 38.

    14. Select the PLC referenced variable that corresponds to 00101. Then,

    click Add >. Select and highlight the previous action for the first

    pushbutton and delete it. Click on OK. See Figure 38.

    15. Add another switch that is programmed to close the pop-up window.

    Click the Switch icon and place it on the screen. See Figure 39.

    Figure 38: Changing the Destination

    Figure 39: Adding Switch

  • 8/9/2019 8000 Db 0710

    27/32

    8000DB0710 Mimicking a PanelMateIndicator Template in VijeoTM Designer

    04/2010 PanelMate Indicator Template Conversion Examples

    2010 Schneider Electric All Rights Reserved 27

    16. In the Switch Settings dialog box, for Category, select Bitmap. For the

    Style, select 12204. In the Operation section, click on the

    pull-down bar and select Script. Click on Edit Script. See Figure 40.

    17. In the script window, type IndicatorPop.close();. See Figure 41. If the

    window name is correct, it will be displayed in a different color.

    18. Click on Validate. If you make a typo, you will see an error message. If

    you have no scripting errors, click on Add >. See Figure 41.

    Figure 40: Modifying Switch Settings

    NOTE: The pop-up window has been renamed

    to IndicatorPop.

    Figure 41: Script Window

  • 8/9/2019 8000 Db 0710

    28/32

    Mimicking a PanelMateIndicator Template in VijeoTM Designer 8000DB0710

    PanelMate Indicator Template Conversion Examples 04/2010

    2010 Schneider Electric All Rights Reserved28

    19. Click on the tab Label. In the Label Type section, click on the pull-down

    and select Static. Type Close. Click on OK. See Figure 42.

    20. The final screen should resemble the right-hand screen in Figure 42.

    21. Return to the pane in Vijeo Designer. Select the Switch icon and place

    a switch over the indicator object. See Figure 43.

    22. In the Switch Settings dialog box, for the Style field, select 00000. This

    will make the switch invisible, but still functional. See Figure 43.

    Figure 42: Switch SettingsLabel

    Figure 43: Placing Switch over Indicator Object

  • 8/9/2019 8000 Db 0710

    29/32

    8000DB0710 Mimicking a PanelMateIndicator Template in VijeoTM Designer

    04/2010 PanelMate Indicator Template Conversion Examples

    2010 Schneider Electric All Rights Reserved 29

    23. In the When Touch tab, for the Operation option, click on the

    pull-down and select Popup. See Figure 44.

    24. In the When Touch tab, under the Panel Name, select IndicatorPopUp

    or whatever you named your pop-up window. For the location option,

    weve selected Centered for this example. Click Add > and the action will

    be updated in the field to the right. Click OK. See Figure 45.

    Figure 44: When Touch Tab

    Figure 45: When Touch TabPanel Name

  • 8/9/2019 8000 Db 0710

    30/32

    Mimicking a PanelMateIndicator Template in VijeoTM Designer 8000DB0710

    PanelMate Indicator Template Conversion Examples 04/2010

    2010 Schneider Electric All Rights Reserved30

    25. Your indicator object should resemble the left-hand window in Figure 46.

    26. To make this indicator look exactly like the PanelMatetemplate, add an

    arrow. Copy the image from the PanelMate screen and paste it into the

    Vijeo Designer pane. After pasting and positioning the arrow, group all

    the objects. See Figure 46.

    Figure 46: Indicator Template

  • 8/9/2019 8000 Db 0710

    31/32

    8000DB0710 Mimicking a PanelMateIndicator Template in VijeoTM Designer

    04/2010 Testing the Indicator Template

    2010 Schneider Electric All Rights Reserved 31

    Testing the Indicator Template Using the device simulator and simulation utilities within Vijeo Designer,test the indicator template you created.

    Figure 47shows what the object looks like when the PLC reference 0001 is

    false. If you toggle the state of reference 0001 to true, it changes the

    indicator to ON. See Figure 47.

    Figure 47: PLC Reference 0001

  • 8/9/2019 8000 Db 0710

    32/32

    Testing the Indicator Template 8000DB0710

    Instruction Bulletin 04/2010

    Electrical equipment should be installed, operated, serviced, and maintained only by

    qualified personnel. No responsibility is assumed by Schneider Electric for any

    consequences arising out of the use of this material

    Schneider Electric USA, Inc.

    8001 Knightdale Blvd

    Knightdale, NC 27545 USA

    ([email protected])

    schneider electric s

    Vijeois a registered trademark of Schneider Electric. Other trademarks used herein

    are the property of their respective owners.

    1. To test, click on the indicator object to open the Device Simulation Tool

    dialog box.

    2. Click (and hold down) the control definition Turn ON (see Figure 48).

    The PLC reference 00100 is True.

    3. Click (and hold down) on the control definition Turn OFF (seeFigure 48). The PLC reference 00101 is now True.

    4. Click Close. See Figure 49.

    5. This concludes the indicator object test and validates a successful

    conversion.

    Figure 48: Control Definit ions Turn ON and Turn OFF

    Figure 49: Close Indicator Template