8. Static Excitation System -Stage-2

download 8. Static Excitation System -Stage-2

of 15

Transcript of 8. Static Excitation System -Stage-2

  • 8/19/2019 8. Static Excitation System -Stage-2

    1/38

    STATIC EXCITATION SYSTEM

    EXCITATION SYSTEMINTRODUCTION:

    All synchronous machines excepting certain machines like permanentmagnet generators require a DC supply to excite their feld winding. As

    synchronous machine is a constant speedy machine or a constant requency

    supply, the output voltage o the machine depends on the excitation current.

     The control o excitation current or maintaining constant voltage at

    generator output terminals started with control through a feld rheostat, the

    supply eing otained rom DC !xciter. The modern trend in interconnected

    operation o power system or the purpose o reliaility and in increasing unitsi"e o generator or the purpose o economy has een mainly responsile

    or the evolution o new excitation schemes.

    #ormer practice, to have an excitation us ed y a numer o exciters

    operating in parallel and supplying power to the felds o all the alternators in

    the station, is now osolete. The present practice is unit exciter scheme, i.e.

    each alternator to have its own exciter. $owever in some plants reserve us

    exciter%standy exciter also provided in case o ailure o unit exciter ig.'(.

    !xciter should e capale o supplying necessary excitation or

    alternator in a reasonale period during normal and anormal conditions, so

    that alternator will e in synchronism with the grid.

    THE RATING OF THE EXCITER

    )nder normal conditions, exciter rating will e in the order o *.+ to

    *.- o generator rating &approx(. t/s rating also expressed in '*to '0 amps.

    &approx.( per 12 at normal load. )nder feld orcing conditions exciter rating

    will e ' to '.0-&approx( o the generator rating. Typical exciter rating or

    various capacity o generators are as given elow3

    EXCITER RATING DIFFERENT CAPACITYS OF GENERATORSINSTALLED IN INDIA (UPTO 210 MW)

     T)456 7!8!4AT64

    '1ax. Continuousrating &12(

    9'* ''* '** * 0*

    9 4ated :ower #actor *.;0 *.; *.;0 *.;=( '0.

  • 8/19/2019 8. Static Excitation System -Stage-2

    2/38

    ? 4ated Current &Amps( @*0*

  • 8/19/2019 8. Static Excitation System -Stage-2

    3/38

     T4A#6

    ?G!87T$ 6#1AC$8!

    B$64T 1!D)1 1!D)1 G687!4

    0C68T46G4!B:68B!

    =!4F #ABT BG62!4 BG62!4 BG62!4

    :46T!CT68B!G!CT=TF 766D 766D 766D 766D

    <4!B:68B!4AT6B!G!CT68

    #G!5G! G1T!D G1T!D G1T!D

    ;C61:68!8T4!I)4871A8T!8A8C!

    BG:487BG:487 E

    C611)TAT64BG: 487 868!

    @#ABT D!H!CTAT68

     F!B F!B F!B 86

    INTRODUCTION TO STATIC EXCITATION EQUIPMENT, ITSSALIENT FEATURES AND COMPARISON WITH OTHERSYSTEMS:

    At present various types o excitation systems, such as, conventional

    DC, $igh requency AC, Btatic E 5rushless are eing adopted in ndia and

    aroad.

     The conventional DC !xciter was the unHchallenged source o 7enerator

    !xcitation or nearly fty years till the rating o turoHgenerator reached

    around '**12.n the last three to our decades, alternative arrangements

    have een widely adopted ecause o limitations o the DC exciters. 2ith

    increase in generator ratings, it is no longer enough to consider the exciter

    used as earlier. nstead, the perormance o the whole excitation system

    including the automatic voltage regulator and the response o the main

    generator have to e considered. Techno economic considerations, grid

    requirements, reliaility and mainte?nance have ecome prime

    consideration.TYPES OF EXCITATION SYSTEMS (TYPICAL)1CONVENTIONAL DC EXCITER:

     The earliest AC turine generators otain their excitation rom the

    power station direct current distriution system. !ach machine had a

    rheostat in series with its feld winding to adJustment o the terminal voltage

    and reactive load. This method was suitale or machines, which needed

    small feld power and low internal reactance. As generator si"es increased

    excitation power requirements also increased and it ecame increasingly

    96

  • 8/19/2019 8. Static Excitation System -Stage-2

    4/38

    desirale or each unit to e sel suKcient or excitation and thus the shat

    driven DC exciter was introduced.

    2 AC (HIGH FREQUENCY) EXCITATION SYSTEM:

     This system was developed to avoid Commutator and 5rush 7ear

    assemly. n this system, a shat driven AC pilot exciter, which has a rotating

    permanent magnetic feld and a stationary armature, eeds the DC feld

    current o the main high requency AC exciter through controlled rectifers.

     The high requency output o the stationary armature is rectifed y

    stationary diodes and ed via slip rings to the feld o the main TuroH

    7enerator. A response ratio o aout two can e achieved.

    ! BRUSHLESS SYSTEM:

    Bupply o high current y means o slip rings involves considerale

    operational prolem and requires suitale design o slip rings and rush gear.

    n rushless excitation system diode rectifers are mounted on

    generator shat and their output is directly connected to the feld o the

    alternator, thus eliminating rushes and slip rings. This arrangement

    necessitates the use o a rotating armature and stationary feld systems or

    the main AC exciter. The voltage regulator fnal stage takes the orm o a

     Thyristor ridge controlling the feld o main AC exciter, which is ed rom

    :17 on the same shat. The response ratio o rushless excitation system is

    normally aout two.

    " STATIC EXCITATION SYSTEM:

    n order to maintain system staility in interconnected system network

    it is necessary to have ast acting excitation system or large synchronous

    machines, which means the feld current must e adJusted extremely ast to

    the changing operational conditions. 5esides maintaining the feld current

    and steady state staility the excitation system is required to extend the

    staility limits. t is ecause o these reasons the static excitation system is

    preerred to conventional excitation system.

    n this system, the AC power is trapped o rom the generator terminal

    stepped down and rectifed y ully controlled Thyristor 5ridges and then ed

    to the generator feld therey controlling the generator voltage output. A

    high control speed is achieved y using an internal ree control and powerelectronic system. Any deviation in the generator terminal voltage is sensed

    97

  • 8/19/2019 8. Static Excitation System -Stage-2

    5/38

    y an error detector and causes the voltage regulator to advance or retard

    the fring angle o the thyristors therey controlling the feld excitation o the

    generator.

    n #ig.9 B.86.&?( shows a lock diagram or a static excitation system.

    Btatic !xcitation Bystem can e designed without any diKculty to achieve

    high response ratio, which is required y this system.

     This equipment controls the generator terminal voltage, and hence the

    reactive load Low y adJusting the excitation current. The rotating exciter is

    dispensed with and

     Transormer E Bilicon controlled rectifers &BC4s( are used which directly eed

    the feld o the Alternator.

    DESCRIPTION OF STATIC EXCITATION SYSTEM#

    Btatic !xcitation !quipment Consist o 

    '. 4ectifer Transormer.

    9. BC4 output stage.

    +. !xcitation start up E feld discharge equipment.

    ?. 4egulator and operational control circuits.

      n the aove ',9,+ are power circuits o Btatic !xcitation Bystem E ? is

    control circuit o Btatic !xcitation Bystem.

    RECTIFIER TRANSFORMER:

     The excitation power is taken rom generator output and ed through

    the excitation &rectifer( transormer, which steps down to the required

    voltage, or the BC4 5ridge and then ed through the feld reaker to the

    generator feld. The rectifer transormer used in the B!! should have high

    reliaility, as ailure o this will cause shutdown o unit%power station.

    Dry type cast coil transormer is suitale or Btatic !xcitationapplications. The transormer is selected such that it supplies rated

    excitation current at rated voltage continuously and is capale o supplying

    ceiling current at the ceiling excitation or a short period o ten seconds.

    SCR OUTPUT STAGE:

     The BC4 output stage consists o a suitale numer o ridges

    connected parallel. !ach Thyristor 5ridge comprises o six Thyristors,

    working as a six pulses controlled ridge. Current carrying capacity o eachridge depends on the rating o individual Thyristor. Thyristors are designed

    98

  • 8/19/2019 8. Static Excitation System -Stage-2

    6/38

    such that their Junction temperature raise is well within its specifed rating.

    5y changing the fring angle o the thyristor variale output is otained. !ach

    ridge is controlled y one fnal pulse stage and controlled y a an.

     These ridges are equipped with protection device and ailure o one

    ridge causes alarm. there is a ailure o our Thyristor ridges &totally (

    then the current will e limited to a predetermined value lesser than the

    normal current. $owever, ailure o the fth ridge results in tripping and

    rapid deHexcitation o the generator. The aove is applicale or ridges

    thyristor with &nH'( principal operation.

     Total numer o ridges M

    &nH?( i.e., ? ridges ailN it will e reduced to predetermined value.

    &nH0( i.e., 0 ridges ailN it will trip the system.

    EXCITATION START UP AND FIELD DISCHARGE EQUIPMENT:

    #or the initial uildHup o the generator voltage, feldHLashing

    equipment is required. The rating o this equipment depends on the noHload

    excitation requirement and feld time constant o the generator. #rom the

    reliaility point o view, provisions or oth the AC feld Lashing are provided.

     The feld reaker is selected such that it carries the ull load excitation

    current continuously and also it reaks the max. #ield current when the three

    phases short circuit occurs at the generator terminals.

     The feld discharge resistor is normally o nonHlinear type or medium

    and large capacity machines i.e. voltage dependent resistor.

     To protect the feld winding o the generator against over voltage, an

    over voltage protection along with a current limiting resistor is used to limit

    the over voltage across the feld winding. The 6=: operates on the insulation

    reak over principle. The voltage level at which 6=: should operate isselected ased on insulation level o feld winding o the generator.

    REGULATOR $ OPERATIONAL CONTROL CIRCUITS (CONTROL

    ELECTRONICS):

    4egulator is the heart o the system. This regulates the generator

    voltage y controlling the fring pulses to the Thyristor.

    A)ERROR DETECTION $ AMPLIFIER

     The generator terminal voltage is stepped down y a three phase :Tand ed to the A=4. The AC input is thus otained is rectifed, fltered and

    99

  • 8/19/2019 8. Static Excitation System -Stage-2

    7/38

    compared against a high staili"ed reerence value and the dierence is

    amplifed d in dierent stage o amplifcation. The A=4 is designed with high

    stale elements so that the variation in the amient temperature does not

    cause any drit or change in the output level. Three CTs sensing the output

    current o the generator eed proportional current across variale resistor in

    the A=4. The voltage thus otained across the resistors, can e added

    tectonically either or compensation can e adJusted as the resistors are o 

    variale type.

    B)GRID % CONTROL UNIT

     The output o the A=4 is ed to a grid control unit, it gets its

    synchronous A.C. reerence through a flter circuit and generates six doule

    pulses spaced *O electrical apart whose position depends on the output o 

    the A=4, i.e. the pulse position varies continuously as a unction o the

    control voltage. Two relays are provided, y energi"ing, which, the pulses can

    e either locked completely or shited to inverter mode o operation.

    C)PULSE&AMPLIFIER

     The pulse output o the P7rid Control )nitQ is amplifed urther at

    intermediate stage amplifcation. This is also known as pulse intermediate

    stage. The unit has a D.C. power supply, and a coarse staili"ed voltage =G.

    A uilt in relay is provided which can e used or locking the six pulse

    channels. n a two channel system &like Auto and 1anual(, the changeover is

    aected y energi"ing%deHenergi"ing the relay.

    D) PULSE FINAL STAGE

     This unit receives input pulses rom the pulse amplifer and transmits

    them through the pulse transormers to the gates o the thyristors. A uilt in

    power supply provides the required D.C. supply to the fnal pulse and

    amplifer. !ach thyristor ridge has its own fnal pulse stage. Thereore, even

    i a thyristor ridge ails with its fnal pulse stage, the remaining thyristors

    ridges can continue to cater to ull load requirement o the machine and

    therey ensure &nH'( operation.

    E)MANUAL CONTROL CHANNEL

    A separate manual control channel is provided where the controlling

    the D.C. signal is taken rom a staili"ed D.C. voltage through a manual

    100

  • 8/19/2019 8. Static Excitation System -Stage-2

    8/38

    reerence card. The D.C. signal is ed to a separate grid control unit whose

    output pulses ater eing amplifed at an intermediate stage can e ed to

    the fnal pulse stage. 2hen one channel is working, generating the required

    pulses, the other remains locked. Thereore locking or releasing the pulses

    o the corresponding intermediate stage aects a changeover rom PAutoQ to

    P1anualQ control or vice versa. PA pulse supervision unit detects spurious

    pulses or loss o pulses at the pulse us ar and transers control rom

    Automatic Channel to manual channelQ.

    F)FOLLOW & UP UNIT

     To ensure a smooth changeover rom PAutoQ to P1anualQ control, it is

    necessary that the position o the pulses on oth channels should e

    identical. A pulse comparison unit detects any dierences in the position o 

    the pulses and with the help o a ollowHup unit actuates the motor operated

    potentiometer on the P1anualQ Channel to turn in a direction so as to

    eliminate the dierence.

    $owever, while transerring control rom P1anualQ to PAutoQ mode any

    dierence in the two control levels can e visually checked on a alance

    meter and adJusted to otain null eore change over.

    G)LIMIT CONTROLLERS

    2hen a generator is running in parallel with the power network, it is

    essential to maintain it in synchronism without exceeding the rating o the

    machine and also without the protection system tripping. 6nly automatic

    regulator cannot ensure this. t is necessary to inLuence the voltage

    regulator y suitale means to limit the over excitation and under excitation.

     This not only improves the security o the parallel operation ut also makes

    operation o the system easier. $owever limiters do not replace theprotection system ut only prevent the protection system rom tripping and

    unnecessarily under extreme transient conditions.

     The A=4 also has a uiltHin requency dependent circuit so that when

    the machine is running elow the rated requency rom the regulated voltage

    should e proportional to requency. 2ith the help o a potentiometer

    provided in the A=4, the circuit can e made to respond proportionally to

    voltage aove a certain requency and proportional to a voltage elow the

    101

  • 8/19/2019 8. Static Excitation System -Stage-2

    9/38

    requency. The range o adJustment o this cut o requency lies etween ?*

    and * $".

     The static excitation system is equipped with three limiters, which act

    in conJunction with the A=4. These limiters are as under3

    • 4otor Current Gimiter

    • 4otor Angle Gimiter

    • Btator Current Gimiter

    1 ROTOR CURRENT LIMITER

     The unit asically comprises an actual value converter a limiter with

    adJustale :D characteristics a reerence valueN dv%dt sensor and a

    signali"ation unit. The feld current is measured on the A.C. input sign o the thyristor

    converter and is converted into proportional D.C. voltages. The signal is

    compared with an adJustale reerence value, amplifed, and with necessary

    time lapse ed to the voltage regulator input.

    4otor current limiter avoids thermal overloading o the rotor winding

    and is provided to protect the generator rotor against excessively long

    duration over loads. Thus ceiling excitation is limited to a predetermined limit

    and is allowed to Low or a time, which is dependent upon the rate o raise o 

    feld o current o eore eing limited to the thermal limit value.

    2 ROTOR ANGLE LIMITER

     This unit is limits the angle etween the voltage o the network center

    and the rotor voltage or it limits the angle etween the generator voltage

    and the rotor voltage. t comprises an actual value converter, a limiting

    amplifer which adJustale :D characteristic and a reerence value unit. The

    limiting regulator operates as soon as the D.C. value exceeds the reerence

    value. #or its operation the unit is given separate power supply rom a D.C.

    power pack.

    t generates a D.C. signal proportional to the load or rotor angle rom

    the stator current and voltage y means o a simple analog circuit. The

    device takes over as soon as the set limit angle is exceeded. ncreasing the

    excitation and ignoring opposite control signals prevent the unit rom ailing

    out o step.

    102

  • 8/19/2019 8. Static Excitation System -Stage-2

    10/38

    ! STATOR CURRENT LIMITER

     This unit unctions in conJunction with an integrator unit, which

    provides the necessary dead time and the gradient that can e adJusted y

    potentiometers. The regulator consists essentially o a measuring converter,

    two comparators, two :D regulators and a D.C. power pack. A discriminator

    in the circuit dierentiates etween inductive and capacitive current. The

    positive and negative signals processed y two separate amplifers are

    rought to the output stage and only that output which has to take care o 

    the limitations is made eective.

    Btator current limiter avoids thermal overloading o the stator

    windings. Btator current limiter is provided to protect the generator against

    long duration o large stator currents. #or excessive inductive current it acts

    over the A=4 ater a certain time lag and decreases the excitation current to

    limit the inductive current to the limit value. 5ut or excessive capacitive

    current it acts on the A=4 without time delay to increase the excitation and

    there y reduce the capacitive loading. This is necessary as there is a risk or

    the machine alling out o step during under excited mode o operation.

    H) SLIP STABILI'ING UNIT

     The slipHstaili"ing unit is used or the suppression o rotor oscillations

    o the alternator to the additional inLuence o excitation. The slip as well as

    acceleration signals needed or staili"ation are derived rom active power

    delivered y the alternator. 5oth the signals, which are correspondingly

    amplifed and summed up, inLuence the excitation o the synchronous

    machine through A=4 in a manner as to suppress the rotor oscillations.

    POWER SUPPLY 

     The voltage regulating equipments needs an A.C. supply +;*=, + :hase

    power supply or its units that is delivered rom the secondary side o the

    rectifer transormer through an auxiliary transormer. This voltage is reduced

    to dierent levels required or the power packs y means o multi winding

    transormers.

    A separate transormer supplies the synchronous voltage + R +;* = or

    the flter circuit o each channel and the voltage relay. During testing and

    precommissioning activities when generator voltage is not availale, thestation auxiliary supply + phase, ?'0= can e temporarily connected through

    103

  • 8/19/2019 8. Static Excitation System -Stage-2

    11/38

    an auxiliary step down transormer or testing purpose with the help o a

    regulator test%service switch.

     The supply or the thyristor 5ridge an is taken rom an independent

    transormer, which gets it, input supply rom the secondary o the excitation

    transormer.

     The control E protection relays need ?;= E 9?= DC which are delivered

    rom the station attery y means o the Dc%Dc converters, which are

    internally protected against overload.

    PROTECTIONS

     The ollowing protections are provided in the Btatic !xcitation

    !quipment.

    '. 4ectifer transormer over current instantaneous and delayed.

    9. 4ectifer transormer over Temperature.

    +. 4otor 6verHvoltage.

    ?. 4otor earth ault &in 74:(.

    0. #use ailureHmonitoring circuit or thyristors.

    . Goss o control voltage &?;= E 9?=(.

  • 8/19/2019 8. Static Excitation System -Stage-2

    12/38

     There inormation particularly or limiting "ones o operations are

    useul in setting the various limiters o Automatic =oltage 4egulator. 6ne

    typical procedure or the construction o capaility diagram is given in

    susequent paras%page. 6perational requirements o excitation system

    essentially call or a ast response particularly $igh nitial 4esponse

    !xcitation Bystem, $igh degree o 4eliaility and also suitale arrangement

    or feld discharge.

    RESPONSE

     The astness o action o an !xcitation system is measured%expressed

    y the term P4esponse 4atio o the !xcitation systemQ. The original defnition

    o this y measuring the rise o exciter volts in frst *.0 second is well known

    i.e. rate o rise o voltage%Bec. Btatic !xciter has very P$igh nitial 4esponseQ

    as given in !!! BTDBH?9' and attains @0- o the ceiling voltage level within

    *.' second or less. Thus it greatly helps or power system staility

    consideration. Typical 4esponse time or static excitation !quipment is

     Twenty 1illiHBeconds i.e., *.9 sec.

    RELIABILITY 

    #or :ower Bystem application, 4eliaility is a very important criteria. To

    ensure this, components are careully selected, lieral ratings wherever

    required are used and redundancies uilt in. n Btatic !xcitation equipment

    PnQ 8o. o Thyristor ridges are used, with &nH'( principle o operation i.e.

    even with three o ridges out o operation, ull load requirement can met y

    alance ridges in parallel. 2herever specifed%required y customers, 9R

    '**- ridges are also given.

    FIELD DISCHARGE

    During load condition whenever the #ield reaker opens suddenly there

    will e a surge voltage in the rotor, which will damage the rotor winding

    insulation. To avoid this rotor winding is connected to the earth through feld

    discharge 4esistor therey y passing the surge voltage to earth and limiting

    the current to earth. #ield discharge greatly helps to limit the damages. 8onH

    linear feld discharge resistance is used which helps in aster feld

    suppression%discharge.

    CAPABILITY DIAGRAM CONSTRUCTION

    105

  • 8/19/2019 8. Static Excitation System -Stage-2

    13/38

    Get us take an example o a '** 1w TuroH7enerator o *.;*p..

    &8ominal( rating and having a BC4 o *.* Choosing suitale scales, 12

    values are marked on FHaxis and 1=A4 values on Haxis. 4eer to #ig.? which

    ahs een drawn on per unit asis and hence ases must e defned or

    interpreting actual values. t is usual to defne the rated 1=A o the machine

    as 5ase 1=A &i.e. 1=A( in which case rated 12 is *.; 1=A. n this case 1=A

    M '90 and rated 12 M &*.; R '90( M '** 12. The other ase unit to defne

    is the per unit excitation and this is usually taken as rotor A1:B to give rated

    terminal voltage on openHcircuit on AirH7ap Gine. To otain actual values, the

    p.u. #igures rom the capaility diagram must e multiplied y the ased

    values Just given.

     The various 12%1=A4 values and the excitation current &4otor Amps(

    can e also e marked directly or the use o operators.

    t should e noted that the diagram scaling is only correct or rated

    machine terminal voltage and that all values must e appropriately adJusted

    or dierent values o terminal voltage i.e., they must e multiplied y =9, so

    that i the terminal voltage is say @*- o normal, then all scaling would have

    to e multiplied y &*.@(9 M *.;', although excitation scaling would remain

    the same.t is oviously undesirale to operate the machine up to theoretical

    staility limits. 6perators have to e inormed through this diagram sae

    limits or operation to allow or various unpredictale change such as sudden

    power increase, a drit in 5usH5ar voltage due to lines or plant tripping etc. t

    is usual to relate this saety actor to an increase in power demand with no

    corresponding increase in excitation. The percentage o the power increase

    used in this way defnes the shape and position o the P:ractical Btaility

    Gimit GineQ.

    4eerring ack to the example stated aove, let us assume that it is required

    to have a '9.0 percent &or '.'90 p.u( power margin. This depends on the si"e

    o the unit and operating practices. 6n Haxis mark point A such that 6A M

    &1=A R BC4( i.e. in this case.

      M &'90 R *.( M

  • 8/19/2019 8. Static Excitation System -Stage-2

    14/38

    :ower intervals : equals to the required saety margin, in this case *.'90 p.u.

    o rated power i.e., &*.; R *.'90( M *.'* p.u. o 1=A are marked on the

    theoretical staility line SAB/ or the loads o *, *.9*, *.?*, *.* and *.;* p.u.

    1=A i.e., at points e,d,c, and a. 2ith radii Aa, A. Ac, Ad and Ae arcs o 

    circles are drawn with A as centre to cut the *.;, *., *.?, *.9 and "ero power

    lines. These intercepts are then Joined y a continuous curve # 5 7. This will

    then e the P:ractical Btaility GineQ or a '9.0 - power margin.

     The reasoning ehind this construction can e understood y taking

    the case o SAa/ arc. This point ' &or 5( would e working point o the

    machine at *.; p.u. 1=A power with an excitation o SAa/ Amps. Bince the

    asis o the saety margin is that there should e provision or increase in

    power without any cha ge in excitation, the working point ' would move

    along arc o radius &fxed excitation( towards theoretical pullHout line, so that

    it is Just suKcient to support *.@ 1=A i.e., '.'90 p.u. :ower &presuming

    turine has the capaility( at a rotor angle o @*O. The same reasoning o 

    course applies to all other points such as 9,+,?,and 0 in the diagram.

    8ext, with P6Q as centre draw a line 6! at an angle o Cos H' *.;* &+O(

    &rated p.. angle( to the FHaxis to cut the rated 1w line &Turine limit line( at

    !. 4ated 1=A is denoted y radius 6!. The line SA!/ represents the C14 excitation required. 2ith A as centre

    and A! as radius, draw an arc o a circle !D representing excitation &or 4otor

    heating( limit.

     The diagram #5!D is the C*+-./ D3 o the machine.

    USEFULNESS OF CAPABILITY DIAGRAM FOR EXCITATIONCONTROL SYSTEM:

    As already mentioned, the inormation given y the capaility diagramregarding ull load rotor current &excitation( maximum rotor angle during

    steady state leading p.. one operation etc., are essential or proper setting

    o the various limiters in the excitation control system. n power system

    operation, the importance and necessity o ast acting and reliale excitation

    control system is well known. Capaility diagram gives the asic inormation

    regarding the limiting ones o operation so that limiters can e

    set%commissioned suitaly or sae operation o the units.

    107

  • 8/19/2019 8. Static Excitation System -Stage-2

    15/38

    PERFORMANCE AND CHARACTERISTICS OF STATICEXCITATION EQUIPMENT

     The steady state and transient ehaviours o a synchronous machine

    coupled to an infnite system must e matched to the desired operatingconditions y suitale selection o control unctions in the entire excitation

    system.

     The asic requirement o a closed loop excitation control system is to

    hold the terminal voltage o a generator at a predetermined value

    independent o the change has to contriute the ollowing unctions also.

    a( 1aintenance o stale operation o a machine under steady state,

    transient and dynamic conditions.

    ( Batisactory operation with other machines connected in parallel.

    c( !ective utili"ation o machine capailities without exceeding machine

    operating limits.

    n order to understand the perormance o excitation system and to

    achieve aoveHmentioned unctions, the ollowing parameters are necessary

    to e studied.

    CEILING VOLTAGE

    t is the maximum voltage that can e impressed on the feld under

    specifed conditions. Ceiling voltage ultimately determines how ast the feld

    current can e changed. #or normal disturances, ceiling condition prevails

    or a ew cycles &Ten seconds maximum( to either increase or decrease the

    excitation until the system returns to steady operating state. #or Btatic

    !xcitation, the ceiling voltage ranges rom '. to 9.* times the rated one,

    which is considered to e adequate or a ast system response.

    RESPONSE

    4esponse is defned as the rate o increase &or decrease( o the

    excitation system output voltage, which can e seen rom the excitation

    voltage time response curve. The starting point or evaluating the rate o 

    change shall e the initial rated value. This is a rough measure o how ast

    the exciter output circuit voltage will rise within a specifed time, when the

    excitation control is adJusted in the maximum increasing direction. 4esponse

    ratio is the numerical value, which is otained when the excitation system

    108

  • 8/19/2019 8. Static Excitation System -Stage-2

    16/38

    response in volts per sec. 1easured over frst *.0 sec. This applies only or

    the increasing !xcitation. As the response is non linear the response ratio is

    determined in terms o equivalent voltage time area or *.0 seconds as

    shown in #ig.0. Area ad M Area acd, y approximation.

    STEADY STATE ACCURACY 

    t is the degree o correspondence etween the controlled variale and

    the ideal value under specifed steady state conditions. The accuracy o the

    excitations system or changing the feld parameters to keep the generator

    terminal voltage at a fxed level depends on its static gain and time

    constants. 5y choosing a higher static gain or the system, the steady state

    error can e minimi"ed apprecialy and therey improving the steady state

    accuracy within U*.0*-. This can e reduced urther with proper integral

    control.

    OTHER SPECIFICATIONS

    !xcitation system perormance could e Judged y the exciter voltage

    =s time characteristic in response to a step change in the generated voltage

    &Bee #ig.(.

     The actors to e studied or optimum perormance are3

    a. 6vershoot

    . 4ise time

    c. Bettling time

    d. Damping ratio

    #or ideal perormance, it should have one overshoot and one

    undershoot with a quicker rise time to have a smaller steady state error.

    Details o each o the parameters are not discussed here since the

    requirement varies rom case to case.T RANSIENT AND DYNAMIC STABILITY LIMIT

     The success o excitation control lies upon the extend o meeting the

    requirement o capaility o the machine and there y giving the dynamic

    perormance o the system. #ast excitation helps during disturances and

    contriutes to the system staility y allowing the required transer o power

    even during the disturances. Due to smaller time

    constants in the excitation control loop, it is assumed that quick controleorts could e achieved through this.

    109

  • 8/19/2019 8. Static Excitation System -Stage-2

    17/38

    n transient staility the machine is suJected to a sever disturance

    &during ault etc.( or a short time. This results in dip in the machine terminal

    voltage and power transer. Taking one machine connected to infnite us,

    the equation or power transer can e written as

    : M =t R = Bin d

      HHHHHHHHH

      x

    where =t M 1achine Terminal =oltage

     = M nfnite 5us =oltage

      x M nterconnected 4eactance

      d M Goad Angle

    #rom the aove equation i S=t/ is reduced S:/ is reduced y

    corresponding amount. #or maintaining the power transer S:/ the excitation

    should e ast acting enough to oost up the feld to ceiling and therey

    holding the terminal voltage S =t/ at the desired value. Thus it is

    advantageous to have higher speed and ceiling values in excitation control

    circuitry. Bimilarly ater the ault is removed, the reactance Sx/ suddenly

    changes therey causing unalanced condition due to power swings, which

    in turn needs ast corrective action through excitation system to ring themachine to normal operating conditions.

    1odern ast and high response excitation system helps in two ways y

    reducing the severity o the machines frst swing during transient

    disturances and also ensuring that the susequent swings are smaller than

    the frst one. Thus it helps in increasing the transient staility limit. 2ith a

    typical static excitation system, ceiling level can e achieved within 9*

    milliseconds due to which it oers an improved transient staility limits.

    #ollowing disturances, the group o machines operating in the same

    control group experience smaller oscillations. 1oreover the oscillating control

    group o machines reacts with each other reinorcing these oscillations. $ere

    the change in excitation may not result in a stale operation &or slow acting

    exciters( ecause y the time corrective action eing taken y the excitation

    system &due to the inherent system delay( the oscillating system changes

    causing separate excitation requirement to e met. Though aster excitation

    system avoids this prolem to certain extent power system staili"ers as

    110

  • 8/19/2019 8. Static Excitation System -Stage-2

    18/38

    mentioned earlier are employed along with the automatic voltage regulators

    to damp out the susequent smaller swings in the system. The staili"er gain

    is adJusted to a value depending o the negative damping o the system and

    other network parameters. :ower system damp out the susequent smaller

    swings in the system. :ower Bystem staili"er helps to damp out inter area

    oscillations explained aove and also machine system oscillations.

    n addition to the aove, limiters are generally uilt into the excitation

    system or large generators connected to the grid. This helps to extract

    maximum operation output i.e., optimal utili"ation o the machine/s

    capaility without Jeopardi"ing its staility. These limit controller act on oth

    the lagging and leading side o the capaility diagram and set elow the

    operating points o the protection relays. Thus they prevent unnecessary

    tripling y keeping the system parameters well within the sae limits. The

    limit controllers do not replace the unction o the protective relays. These

    limiters enhance the staility o the machine, therey increasing its

    availaility to the network. These cannot dispense with protection relays. The

    staili"er gain is adJusted to a value depending on the negative.

    EFFECT OF EXCITATION SYSTEM ON TRANSIENT STABILITY 

    Bince the transient staility prolems deal with the perormance o 

    power system when suJected to sudden disturances, sometimes leading to

    loss o synchronism, it is worthwhile to study the ehavior during the frst

    owing as the period is o very short duration. The maJor actors inLuencing

    the outcome are the machine ehaviour and the power network dynamic

    relations. #or this it is assumed that the mechanical power supplied y the

    prime mover remains constant during the disturances. Thereore the eect

    o the excitation control on this type o transient depends on its aility tohelp generator to maintain its output power in the aove period.

     The main actors that aect the perormance during severe transients

    are3

    '( The disturance inLuence o impactN this includes the type o 

    disturances, its location and duration.

    9( The aility o the transmission system to maintain synchroni"ing orce

    during the transients.

    +( Turine and generator parameters.

    111

  • 8/19/2019 8. Static Excitation System -Stage-2

    19/38

     These actors mainly aect the frst swing transient. The system

    parameters inLuencing these actors are3

    i( The synchronous machine parameters. 6 these, the most

    important are3

    a( The nertia constant

    ( The direct axis transient reactance

    c( The direct axis open circuit time constant

    d( The aility o the excitation system to hold the Lux level

    o the synchronous machine and increase the output

    during transients.

    ii( The transmission system impedances under normal, aulted

    and postHaulted conditions. $ere the Lexiility o the

    switching aulted section is important such that the large

    transer admittances etween synchronous machines are

    maintained when ault is cleared.

    iii( The protecting relaying scheme and equipment. The oJective

    is to detect the ault and isolate the aulty section quickly with

    minimum disruption.

    During transients initiated y a ault, the armature reactionhas the tendency to reduce the Lux linkage. $ence the type o 

    excitation must e chosen as to have a ast speed o response

    and high ceiling voltage &can e reerred to the static type( as

    an aid to the transient staility. 2ith the help o aster ooster

    up o the excitation, the internal Lux can e osetted and

    consequently machine output power may e increased during

    the frst swing. This results in reduction o accelerating power

    and therey eects improvements o transient perormance o 

    the system.

    THYRISTOR CHARACTERISTICS $ ITS APPLICATION INSTATIC EXCITATION SYSTEMINTRODUCTION

     n the latest trend o excitation system neither the rheostatic mode o 

    the excitation control nor the magnetic amplifer type o control system is

    112

  • 8/19/2019 8. Static Excitation System -Stage-2

    20/38

    used as these are slugging in action and have an inherent dead and o the

    operation ecause o their loe loop gains.

     The use o BC4s at the power stage or the excitation system with

    voltage regulator control the response o the system is much aster then the

    conventional ones. The modern excitation system incorporating BC4s at their

    power stages have a very low dead and.

    SYSTEM DESCRIPTION

     The excitation power eing ed rom the generator terminals or

    auxiliary supplies through normally a stepdown transormer and then to the

    input i the BC4s ridge. The voltage regulator having closed loop control

    compares the actual terminal voltage o machine with that o the set

    reerence value and orms an error signal, which controls the fring angle o 

    the Thyristor 5ridge. Busequently, the variale controlled DC voltage is

    applied to the feld o the generator through a feld reaker. The BC4s 5ridge

    orms an important integral part o the excitation system y providing an

    accurate and ast feld DC voltage control.

    THEORY OF DEVICE

     The BC4 consists o our layers o : and 8 material and three Junctions

    etween layers. This has got two locking states. 2hen the anode terminal is

    iased positively with respect to the cathode, the Junctions V '  and V+  are

    orward iased whereas V9 would e reverse iased. Bo that current Low is

    locked and the BC4 is said to e in the orward locking state. Bimilarly,

    with a negative voltage applied to the anode with respect to cathode,

     Junction V' and V+ are reversed iased and Junction V9 is orward iased and the

    device will not switch on. This state o the BC4 is called as reverse locking

    state or high impedance state. The BC4 can e driven into conduction statewhen locking characteristic is erased and the BC4 continues to conduct

    until the current level alls elow the certain lower value termed as holding

    current o the BC4.

     The BC4 e turned on y increasing the anode voltage suKciently to

    exceed the reak over voltage, so that the reverse iased Vunction V9 reaks

    down ecause o large voltage gradient across the depletion layers and the

    orward current increases. 6nly the external resistance o the circuit limits it. The most convenient method o switching the BC4 is y applying a positive

    113

  • 8/19/2019 8. Static Excitation System -Stage-2

    21/38

    trigger pulse to the gate o the BC4 with lower positive anode voltage than

    the reak down voltage. This is known as the gate control.

    6nce the BC4 is 68, the orward current is to e maintained aove a

    certain value known as latching current, so as to enale the BC4 to hold at

    the conducting stage.

    #or turning o a BC4, it is essential that the orward current though it

    should e rought down elow the holding current value y reversing the

    anode potential. #or using gate control methods to turn on the BC4 ollowing

    conditions are to e ulflled or saer operation.

    i( Appropriate anode to cathode voltage must e applied to ring the

    device to the orward locking state.

    ii( The gate signal must e removed once the device is turned 68. The

    gate pulse duration is to e maintained in such a way that the gate

    loss is less than that specifed or the device.

    iii( 8o gate signal should e applied when the device is in the reverse

    locking state.

    iv( 2hen the device is in the o state, a negative voltage applied to the

    gateHcathode Vunction will improve the reverse locking

    characteristic o the device. Turn 68 time is dependent upon theload current and the rate i rise o gate pulse. Turn o time depends

    on the recomination o charges near Junction V9. Bome typical

    values o turn 68 and 6## times are ' to ? micro secs and '* to 90*

    micro secs

    v( 4espectively. #or power requency applications these turn 68 and

    6## times does not pose any prolems.

    SELECTION PROCEDURE OF SCR BRIDGES FOR STATICEXCITATION SYSTEM

     The ollowing actors are taken into account,

    '. :eak inverse voltage.

    9. Vunction temperature.

    +. dv%dt 4ating.

    ?. di%dt 4ating.

    0. 7ate fring requirement.. Current rating.

    114

  • 8/19/2019 8. Static Excitation System -Stage-2

    22/38

    PARALLEL OPERATION

    #or certain high current applications or or redundancy or the power

    stage paralleling o the devices are required. #or such cases, ollowing points

    must e careully oserved while designing the entire system.

    '. #or paralleling, the connections, which are done y us ars and

    cales etc., are to e kept symmetrical as ar as practicale.

    9. Cooling or the devices are to e kept almost similar &i.e.( the

    positions and type o mounting o the ridges and the cooling ans

    are to e maintained identical.

    +. 4C circuit should e so designed to keep the 4C discharge current

    through the device within the specifed limit under all

    circumstances. n addition to the aove, precautions are to e taken

    to limit the rate o rise o 4C discharge current y providing

    decoupling reactors in series with the device.

    ?. The aove series decoupling reactors with proper tolerances also

    serve the purpose o reducing the miss haring actor or the parallelH

    connected device. 2hile designing this, miss haring actor is to e

    taken into account or the Junction temperature calculation.

    SNUBBER CIRCUIT

     The 4C 8etwork across the thyristor is known as snuer circuit. The

    unction o snuer circuit is to limit the dv%dt with in maximum allowale

    rating. The snuer could e polari"ed or unpolari"ed.

    () P4-567

    A orwardHpolari"ed snuer is suitale when a thyristor &or( transistor is

    connected with an anti parallel diode. The resistor, 4 limits the orward dv%dt,

    and 4' limits the discharge current o the capacitor when the device is turned

    68.

    () R68696&P4-567

    A reverse polari"ed snuer, which limits the reverse dv%dt. 2here 4'

    limits the discharge current o the capacitor. The capacitor does not

    discharge through the device, resulting in reduced losses in the device.

    () U*4-567

    115

  • 8/19/2019 8. Static Excitation System -Stage-2

    23/38

    2hen a pair o thyristors is connected in inverse parallel, the snuer

    must e eective in either direction.

    AVR % UN 2010

     The Automatic voltage regulator type )8 9*'* is an electronic control

    module specially designed or the voltage regulation o synchronous

    machines. t primarily consists o an actual value converter, a control

    amplifer with :D characteristics that compares the actual value with the set

    reerence value and orms an output proportional to the dierence. The

    output o this module controls the gate control circuit )8 '**'. The module

    does not have an 85)GT power supply and devices its power rom )8 9**?,

    the pulse intermediate stage and power supply unit. The A=4 works on W

    '0= DC supply.

     The main eatures o this module are listed elow3

    a. The A=4 comprises o an input circuit which accepts + phases voltage

    signals o ''*= AC and + phase current signals o 0A or 'A A.C. t is

    thus necessary to use intermediate :T/s and CT/s to transorm the

    generator voltage and current to the aove mentioned values. The

    module itsel contains :T/s and CT/s with urther step down the signals

    to make them compatile with electronic circuit. A C4C)T4F is

    availale in the module or adding the current signals =!CT64AGF to

    the voltage signals or providing compensation as a unction o active

    or reactive power Lowing in the generator terminals.

    . An actual value converting circuit or converting the AC input signal to

    DC signal with minimum ripple with the aid o flter network.

    c. A reerence value circuit using temperature compensated "ener

    diodes. The output o which is taken to an external potentiometer thatprovide @*H''*- range o operation o the generator voltage.

    d. A control amplifer, which comprises the reerence and actual value

    and provides an output proportional to the deviation. Apart rom this, it

    has the acility to accept other inputs or operation in conJunction with

    various limiters and power system staili"er.

    e. A voltage proportional to requency network, which reduces the

    excitation current when requency alls elow the set level, thus

    116

  • 8/19/2019 8. Static Excitation System -Stage-2

    24/38

    keeping the air gap Lux constant. This prevents saturation o 

    connected transormers and possile over voltage.

    LIMITERS IN STATIC EXCITATION SYSTEMLIMIT CONTROLLERS

    2ith ever increasing si"e o generating units today, more stringent

    requirements have to e met y excitation systems. Today, it is proven

    eyond dout, that static excitation assures, stale operation under dynamic

    and transient conditions, 7enerator running in parallel with the power

    network even under extreme conditions must e remain in synchronism

    without the maximum load limit on it eing exceeded and without the

    protective relays operating. An automatic voltage regulator A=4 alone cannot

    ensure this. 6ptimum utili"ation o the generator can e ensure only i the

    asic A=4 is inLuenced y additional signals to limit the under excitation and

    over excitation o the machine. Thus, limit controllers working in conJunction

    with the A=4 ensure3

    a( 6ptimum utili"ation o the machine.

    ( Becurity o parallel operation.

    Gimit controllers simpliy the Jo o the operating sta and enales

    stale operation close to the limiting values. 2ith limit controllers in service,operational errors and aults in the regulator lead only to the limit value

    control and not to disconnection.

    t has to e understood that limit controllers however are not mean to

    replace the protection system ut they are only intended to prevent the

    protection system rom operating under extreme transient conditions.

    PARAMETERS FOR LIMITATIONS

    Gimiters, whenever they intervene, inLuence the voltage regulatorsuitale or ring aout a corresponding change in the excitation. The

    ollowing are the parameters which are to e limited3

    '( Btator current under condition o over excitation and under excitation.

    9( 4otor current.

    +( 4otor angle or the Goad angle.

    MECHANISM OF LIMITER INTERVENTION:

    During overHexcitation, the rotor current and the stator current limiters

    intervene to ring aout a reduction in excitation. 6n the other hand during

    117

  • 8/19/2019 8. Static Excitation System -Stage-2

    25/38

    under excitation the limitation o the rotor angle and stator current inLuence

    to increase the excitation. 4otor and Btator current limiters must e designed

    to intervene ater a certain deal so as to permit temporary over%ceiling

    excitation, limiters do not impair the construction ehavior o the A=4 as

    overHexcited condition can exist in the event o load surge or ecause o 

    short lived aults in the power supply network. The A=4 reacts to distance

    ault &say + phase short circuit( and commands ceiling excitation to e

    applied, therey increasing the synchroni"ing torque o the machine and

    prevent rom the loss o synchronism. $owever, i the short circuit persists

    and has not e cleared y system protection ater a set time, delayed rotor

    current limiters comes into operation preventing the generator and the

    excitation equipment rom eing suJected to thermal over load. An identical

    situation prevails during such conditions o the system. The A=4 enale short

    time ceiling excitation prevails so as to otain lower settling time.

     The under excited mode, the rotor angle limiter and stator current

    limiter must intervene instantaneously to increase the excitation to prevent

    rom increment in the rotor angle.

    n the under excited mode, stator current limiter is essentially used

    multipleHpole synchronous condensers which run at suitale level o excitation increase the capacitive asorption capaility o the machine.

    POWER DIAGRAM OF THE GENERATOR AND RANGE OFINFLUENCE OF LIMIT CONTROLLERS

     The operational limits o the synchronous machine are shown in the

    circle diagram. The application and range o inLuence o the limiters depends

    on the conditions in the installation and the generator data. The possile

    "one o intervention o the limiters is marked in the power chart%power circlediagram. #ig.<

    ROTOR ANGLE LIMITER

    Gine A5 represents the range o inLuence o the 4otor Angle, limiter the

    maximum angle o which has een taken as ;0O. Although stale operation

    can e ensured even eyond ;0O with the ast acting load angle limiter in

    action and achieve greater possile reactive power asorption capaility, the

    load angle is limited or practical purposes to ;0O ecause o the ollowingconsiderations3

    118

  • 8/19/2019 8. Static Excitation System -Stage-2

    26/38

    '. n the event o a short circuit in the systems, the generators may

    accelerate owing to the arupt partial removal o the electrical load

    and as the turine governor cannot act ast, the rotor angle increases

    and the angle can ecome so large relative to the system vector that

    the machine may all out o step.

    9. The excitation system &A=4( switches over to manual mode in the

    event o internal aults in the autoHmode. Changeover to manualHmode

    signifes constant excitation and hence a stale operation up to a

    maximum angle o @*O electrical only is possile.

     The rotor angle limiter limits the load angle o the machine to an

    acceptale present value. The load angle is the electrical angle etween the

    voltage vector o the system and the vector o the machine voltage Se/ fg.;.

     The system vector is derived rom the voltage vector o the generator )= y

    adding to it the voltage drop in reactance external to the machine. This takes

    into account the transormers and transmission lines etween the generator

    and the system load centre. The rotor voltage is simulated adding the

    inductive voltage drop in the machine xq. The system voltage at the load

    centre is otained y sutracting e  drop &4eactance drop in the

    transmission line, transormers etc.( rom the generator terminal voltage. The phase angle etween Se/ and )8 is converted into a proportional

    dc voltage. The actual value is compared with an adJustale reerence and

    ed to the input o an operational amplifer. n case the angle exceeds the set

    value the output signal immediately takes over the control o thyristor

    network to uild up the generator airHgap Lux ast enough to avoid slipping.

    t stands to reason that the output o the limiter acts directly over A=4 output

    to avoid any loss o time due to flter time constants in the A=4. #ig.@

    explains the operation o Automatic =oltage regulator in conJunction with

    rotor angle limiter.

    ROTOR CURRENT LIMITER

     The A=4 drive the feld or the thyristor network into overload or one or

    more o the ollowing reasons3

    a. #aulty handling.

    . Bystem voltage reduction.

    c. Goss o sensing voltage to A=4 and

    119

  • 8/19/2019 8. Static Excitation System -Stage-2

    27/38

    d. #ailure within the controller.

     The excitation limiter must prevent this overload rom persisting. 6n

    the other hand, during dynamic disturances in the system the excitation

    should not e reduced at once, ut ceiling excitation should e possile or

    a limited time.

     The limiter can e operated in three dierent modes as explained

    elow to cater the aove requirements.

    ) S*-6 476

    n this mode the excitation current is limited to a preset maximum value.

     The limiter intervences with a time delay which is proportional to the

    magnitude o the over load. 2hich the limiter in operation, the current is

    limited steadily to the rated value.

    ) M;67 M476

    during the aove period o limitation, the generator voltage dips

    steeply or any reasons, the ceiling excitation limit is validated again. The

    ceiling excitation current helps in increasing the short circuit current in the

    ault "ones and hence aids selective tripping o the aulted section.

    ) S 476

    n the switching mode the excitation is limited to the thermal or rated

    current value. 6nly in case o sharp dip in the machine voltage, the ceiling

    limit was unale momentarily. The limit switches ack to the rated value

    ater the set time.

    #igureH'* gives the lock diagram o a rotor current limiter acting in

    conJunction with A=4 to limit the over excitation in the desired ashion.

    STATOR CURRENT LIMITER

     The stator current limiter has to inLuence the A=4 dierently

    depending on whether the machine is overHexcited or underHexcited. The

    excitation current is to e suitaly reduced to limit the inductive stator

    current and is increased to limit the capacitive current. The rotor angle

    limiter provides a more defnite protection in preventing the machine rom

    alling out o step. Capacitive stator current limitation comes into play only

    120

  • 8/19/2019 8. Static Excitation System -Stage-2

    28/38

    with synchronous condensers which are to some extent negatively excited

    with generators it prevents excessive leading 1=A4 loading corresponding to

    any given 12 load.

     The generator stator current is converted into polari"ed dc signal Wve

    or Xve, depending upon whether the machine is overHexcited or underH

    excited. This voltage orms the actual value or the controllers which process

    each o the ipolar signal independently. 6ne o these controllers compares

    the capacitive stator current against its reerence and acts directly on the

    regulator via a deHcoupling diode to increase the excitation. The action o 

    second controller, which limits the inductive stator current, is delayed y

    means o an integrator eore it inLuences the control nput o the A=4 so as

    to reduce the excitation. The time lag oered is perectly acceptale as ar

    as stator overheating is concerned ecause o the integrator time constant is

    set one order less than the stator thermal time constant. #ig.'' shows an

    A=4 operating in conJunction with a stator current limiter.

    EXCITATION TRANSFORMERINTRODUCTION

    4ectifer transormers directly connected to the generator terminals

    and eeding power to the feld o the machine via thyristor converters, playsan important role in an excitation system and in turn power generation

    4eliaility o this transormer has to e ensured in all respects.

    mportance o rectifer transormer has een reali"ed ever since the

    mercury arc converters came into existence or important applications like

    large power drives and excitation systems. A gradual development has taken

    place rom oil flled transormers to &resin( cast coil type transormers &dry

    type( or !xcitation transormer.

    6il and clophen%Bovtol flled transormers are still adopted or large

    rating. $owever, in uran areas and thickly populated cities where pollution

    control is also to e thought oN certain countries like 2est 7ermany have

    rought oput regulation that oil immersed transormers can e used only

    under special circumstances. #urther, use o clophen%Bovtol flled

    transormers has already een anned almost in all advanced countries

    ecause o poisonous gases emanating in case o damages. 1oreover, there

    has een constant rise in price o oil in the international market, resulting in

    121

  • 8/19/2019 8. Static Excitation System -Stage-2

    29/38

    sustantial increase in the total price o transormer and its maintenance.

    8ot only the aove reasons ut other ha"ards have led the scientists to think

    o an alternate design which could gradually replace the oil and

    clophen%Bovtol flled transormers. Accordingly vacuum impregnated dry type

    transormers were taken up or large power and high voltage rating. The

    results were however not satisactory ecause o many limitations like eect

    o atmosphere, over voltages and the need or proper alternative and cast

    resin moulding technique came into existence. The development o case

    resin transormers has led to the production o dry insulated type

    transormers up to + >=. These transormers have not only een ound

    comparale to oil flled transormers ut also proved their superiority in all

    respects. These transormers are o class S#/ insulation and indoor type.

    VOLTAGE AND POWER RATING

     The selection o the secondary voltage o excitation transormer

    depends upon the flled orcing voltage. The primary voltage is the same as

    that o generator terminal voltage. Current rating is dependent on the

    maximum continuous current in the feld winding. 7enerally the power rating

    o the !xcitation transormer used in Btatic !xcitation Bystem is around '-

    o the rating o generator in 1=A.

    ENCLOSURE AND COOLING

     The enclosures are normally designed to ensure natural air

    cooling%#orced airHcooling to the transormers. These enclosures are made to

    :9*, :9+ depending upon the requirement. #orced cooling arrangement

    provides increase in rating y ?*- than that with natural airHcooled

    transormer. 8ormally this arrangement is switched on during peak load

    period or in summer to deliver more current rom the same transormer. Thedescription that ollows compares resin cast coil, dry type transormers with

    other transormers or various characteristics.

    SALIENT FEATURESI SHORT CIRCUIT PROOF

     The dynamic short circuit strength exceeds y ar that o oil immersed

    transormers as well as that o conventional dry type transormers. n the

    event o a short circuit the cast resin transormer is not endangered

    mechanically, and only thermal damage can take place. The high mechanical

    122

  • 8/19/2019 8. Static Excitation System -Stage-2

    30/38

    strength is achieved y casting the coils in epoxy resin with a ferglass fller

    to orm a compact tuular spool. An insulation thickness o 'H9 mm is quite

    adequate to withstand the orce that occurs during operation.

    II HIGH OVER LOAD CAPACITY 

    n certain applications where rectifer transormer is suJected to

    intermittent loads like rolling mill, urnace, and traction and also in excitation

    duly high current increase is ollowed y low current demand. t results in the

    windings to e mechanically stressed to a greater extent.

    n cast resin transormers all the windings are cast and thereore no

    diKculties concerning mechanical strength due to repeated overloads.

    8ormally $.=. E G.=. coils are cast separately, all the orces appearing on one

    winding can e suitale asored y it. The resultant orces etween primary

    and secondary windings can e made to asor y putting suitale support

    locks etween the coils and rame. :osition o the support locks can e

    conveniently designed to reduce the orces to a lower value in contrast to

    conventional type transormer.

    Conventional type, wound coil transormers consume a considerale

    amount o insulation material like paper, which asors the expansion o 

    conductor and coils have to e recompressed ater certain periods. The cast

    coils eing homogeneous, the coil structure expands and contracts as a

    whole and the movement are taken care o y means o an elastic support.

    4ecompression o the coils is thereore not required.

    n synthetic liquid cooled transormer there is a rated temperature

     Jump etween winding and cooling liquid o the order o 9* to 90OC with

    current density + to ? A%Bq.mm. n contrast, in these transormers with class

    # insulation the allowale temperature rise etween coil and air is o theorder o '**OC with the same current density. This clearly indicates the

    heating time constant o cast resin, normally H'* times, higher than that o 

    oil flled transormers.

    III RESISTANT AGAINST TEMPERATURE FLUCTUATION

     The selected insulation material is ferglass reinorced epoxy resin,

    which has got high tensile and ending strength. Thereore the transormer

    can withstand the wide range o temperature Luctuations.IV MOISTURE PROOF

    123

  • 8/19/2019 8. Static Excitation System -Stage-2

    31/38

     The cast resin coils are impregnated and cast under vacuum which

    ensures the void ness emedding o all windings into a system o uniorm

    glass ferHepoxy laminate. This process helps the coil to oer an increased

    protection against moisture.

    Conventional dry type transormers are not moisture proo. The

    winding do asor humidity and there is danger o Lashover once they are

    put in service ater a long period.

    V IMMEDIATE SWITCH ON

    5ecause o the cast resin coil, the coils are homogeneously uilt in allrespects. There is no possiility o eect o moisture and amient

    temperature Luctuations over coils. )nder such case the transormer can e

    directly switched on without predrying the same ater long interruption rom

    service.

    VI IMPULSE STRENGTH

    mpulse strength o these transormers is higher than that o 

    conventional dry type transormers and is comparale to that o oil cooled

    transormers according to any international standard.

    VII NON&INFLAMMABLE

    Due to high quality o nonHhydroscopic material, it has een proved

    that neither with welding cutting torches nor with welding electric arc the

    cast coil resin could e induced to urn and as such is almost nonH

    inLammale.

    VIII PARTIAL DISCHARGE

    During operation, there is no partial discharges inside the winding,

    exceeding narrow and '* :.C. i.e. transormers are designed or long lie.

    IX COMPACT INSTALLATION

    Compared to oil and clophen%Bovtol flled transormers, the use o this

    type transormer required less space, less weight and aove all, the cost or

    the necessary erection o catchHpits no longer exist. 5ecause the cast resin

    oils are nonHinLammale in nature a suHstation consisting o a numer o 

    such transormers can e installed in the same uilding near to the

    124

  • 8/19/2019 8. Static Excitation System -Stage-2

    32/38

    consumer end there y the power losses due to long distriution lines are

    also avoided.

    X NO LEA?ING

    8othing can leak out rom these transormers in contrast top

    clophen%sovtol and oil flled transormers where there is a possiility o the

    liquid leaking. Thereore there is no need to make catchHpits at sites to avoid

    contamination to the ground water.

    XI MAINTENANCE FREE

    Considering all aoveHmentioned eatures it can e concluded that

    these transormers are virtually ree rom maintenance.

    8o reHadJustment o the winding and no reHtensioning o the individual

    coils are required to maintain the short circuit strength.

    8o control o oil is required.

    8o checking o electrical quality o used oil.

    8o dry out is necessary even ater long interruption rom use.

    XII OVER CURRENT PROTECTION

    t is normally achieved with the help o current transormers mounted

    on each phase on $.T. Bide o excitation transormer. #rom current

    transormers current signals are given to two over current relays, one is

    meant or instantaneous over current protectionN another is set or delayed

    over current protection. The latter is set to suit the feld orcing

    requirements.

    XIII OVER TEMPERATURE PROTECTION

    t is achieved with the help o temperature sensors kept near the hot

    spot "one o the G.=. coils. The sensors have nonHlinear characteristic.

     The resistance o the sensor is increased consideraly ater a certain

    temperature limit. 8ormally two limits o over temperature are kept

    depending on the class o insulating material used, one is the warning limit

    and another one or tripping o the equipment. 5oth these limits are otained

    y independent temperature sensor. The output o the sensors is rought to

    the temperature monitoring equipment, which signali"es or calls or tripping.

    XIV CONNECTION ARRANGEMENT

    125

  • 8/19/2019 8. Static Excitation System -Stage-2

    33/38

    8ormally the excitation transormer will have Dy0 vector group

    connection to suppress harmonics. The angular displacement etween $T

    and GT winding is '0*O !lectrical degrees.

    XV OPERATING CONDITION

    n spite o all advantages o the cast coil resin transormer mentioned

    aove, it is recommended that this transormer should e mounted in an

    enclosure installed away rom water, oil leaking sources, away rom sum rays

    and heat dissipating equipments. Care has to e taken that suKcient ree

    space all around is availale to maintain the amient temperature and

    ventilation. The installation o the transormer has to e thought o in the

    eginning itsel to avoid dust. $owever, dust%caron particles must e

    removed during periodical shutdowns. 8ormally this transormer is located

     Just elow the generator at exciter at S6/ meter level are at ?.0m level.

    CONCLUSION

    n excitation systems, practically cast resin dry type transormers are

    used and there is no necessity presently o using o oil cooled transormers

    with its inherent disadvantages o fre risk etc., as already mentioned.

    #urther or indoor application it is preerale to use only dry type

    transormers.

    OPERATION OF STATIC EXCITATION EQUIPMENT

    nitially the main Circuit 5reaker as well as #ield Circuit 5reaker is in

    open condition. The signal lamp P!xcitation oQ shows that the machine is

    not excited.

    n order to start up the machine, machine should e frst rought to

    nominal speed i.e. +*** 4:1. :reHselection to e done or selecting the

    manual or auto control. The signal lamps on the control unit indicate whether

    auto or manual control has een preHselected.

    As soon as the nominal speed is reached, the ##5 ield #lashing

    5reaker( E #5 ield 5reaker( to e closed. This is achieved through pressing

    the luminous utton in the cuicle or y a parallel connected push utton

    &remote(. Bince the remanance voltage o the machine is not suKcient to

    operate the regulator, initially suitale station A.C. voltage via ull wave

    ridge rectifer or suitale DC voltage rom station atteries to e suppliedthrough #ield #lashing 5reaker. The machine voltage rises to +*-, then the

    126

  • 8/19/2019 8. Static Excitation System -Stage-2

    34/38

    electronic regulation start unctioning y getting the released pulses, which

    were locked till then. The locking o pulses is cancelled through voltage

    relay and regulator takes over the unction o regulating the machine

    voltage.

    At

  • 8/19/2019 8. Static Excitation System -Stage-2

    35/38

    )8

  • 8/19/2019 8. Static Excitation System -Stage-2

    36/38

    ?( 7uard the machine against inadvertent tripping during

    transients

    0( mprove dynamic and transient staility therey increasing

    plant%machine availaility

    ( 4egulate 1=A4 loading within limits

  • 8/19/2019 8. Static Excitation System -Stage-2

    37/38

    0. During normal operation it is possile to work on any

    thyristor%#use etc. y isolating it on A.C. E D.C. sides.

    . #or initial !xcitation feldHLashing circuit is provided. A.C. supply

    can e used. Circuit cuts o automatically when

  • 8/19/2019 8. Static Excitation System -Stage-2

    38/38

    '0. Blip staili"er unit helps to staili"e the power swings and thus

    prevents the generator rom tripping.

    '. 6ver current relays and temperature supervision protects the

    rectifer transormer.

    BIBILIOGRAPHY 

    '. G!CT)4! 86T!B 68 BTATC !CTAT68 BFBT!1 =6G. E H BHEL BANGALORE

    9. 8BT4)CT68B #64 6:!4AT68 6# BTATC !CTAT68 BFBT!1H BHEL MANUAL

    +. 8:T C6)4B! 1AT!4AG 68 T$!41AG :62!4 :GA8T #A1GA4BAT68

    HVOLUME IV

    131