7SA511 Line2 Setting
42
Substation Name 220KV SS Location MSETCL Relay Serial Number 0 CT Secondary Current 1 Line Length of Protected Zone 100 Line Impedance of Protected Zone 10 CT Primary Current 1000 PT Primary Voltage 400000 PT Secondary Voltage 110 Line Impedance of Protected Zone 2.75 Enable Zone1 YES Zone1 FW X1 2.5 R1ph 1.25 R1E 2.5 t1 for Zone1 0.04 Enable Zone1X YES Zone1X FW X1A 2.5 R1Aph 1.25 R1AE 2.5 t1 for Zone1X 0.04 Enable Zone2 YES Zone2 FW X2 5 R2ph 2.5 R2E 5 t2 for Zone2 0.342 Enable Zone3 YES Zone3 RW X3 10 R3ph 5 R3E 10 t3 for Zone3 0.645 RE/RL 1 XE/XL 1 X+A 20 X-A 20 RA1 5 RA2 10 Angle-A 30 RA1E 15 RA2E 20 Angle-AE 30 Dir Line Ang (Ph-Ph) -45 Dir Line Ang (Ph-E) -45 Line Angle 75
-