7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles,...

20
SD 24"x12" 24"/12" 12" o GENERAL NOTES: MECHANICAL SYMBOL LEGEND ABBREVIATIONS FIRE DAMPER FLEXIBLE DUCT ACOUSTICAL DUCT LINING FLEXIBLE CONNECTION MANUAL BALANCING DAMPER SMOKE DAMPER MITERED ELBOW (ALL MITERED ELBOWS ARE TO HAVE VANES EXCEPT TRANSFER AIR SOUND ELBOW) EXISTING DUCT TO BE REMOVED CONNECT NEW DUCT TO EXISTING DUCT SUPPLY DUCT, SECTION EXHAUST DUCT, SECTION RETURN DUCT, SECTION DUCT TRANSITION OR REGISTER STANDARD RADIUS ELBOW SHORT RADIUS VANED ELBOW (ALL SHORT RADIUS ELBOWS ARE TO HAVE VANES PER SMACNA) CEILING RETURN AIR REGISTER OR TRANSFER AIR GRILLE INDICATES A RECTANGULAR DUCT SIZE (WIDTH x DEPTH) INDICATES A FLAT OVAL DUCT SIZE (WIDTH x DEPTH) INDICATES A ROUND DUCT SIZE IF THROW IS SOMETHING OTHER THAN 4-WAY) CEILING DIFFUSERS (ARROWS DENOTE THROW PATTERN DUCTED EXHAUST REGISTER SIDEWALL EXHAUST OR RETURN AIR GRILLE SIDEWALL SUPPLY REGISTER T ACCESS DOOR SEE CONTROL DRAWINGS FOR TYPE ROOM THERMOSTAT/TEMP. TRANSMITTER LOCATION ONLY DUCT MOUNTED STATIC PRESSURE PROBE ### XX - ## NUMBERS REFER TO SPECIFIC EQUIPMENT SYMBOL INDICATES NEW EQUIPMENT EQUIPMENT SYMBOLS IDENTIFIED IN EQUIPMENT SCHEDULE CFM SYMBOL INDICATES GRILLE OR DIFFUSER IDENTIFIED IN EQUIPMENT SCHEDULE SIDEWALL GRILLE DIMENSION WHERE SHOWN ON PLANS LETTERS REFER TO THE EQUIPMENT TYPE ACCESS DOOR AIR CONDITIONING UNIT ABOVE FINISHED FLOOR ACOUSTIC LINING ACU AD AFF AL BOP BOD BOTTOM OF PIPE BOTTOM OF DUCT CUBIC FEET PER MINUTE CLEANOUT CFM CO MOTOR CONTROL CENTER MCC NOT APPLICABLE NOT IN CONTRACT NUMBER (QUANTITY) NA NIC NO. OUTSIDE AIR OPPOSED BLADE DAMPER OA OBD PSIG PRV PRESSURE REDUCING VALVE POUNDS PER SQUARE INCH GAGE QUADRANT QUANTITY QTY QUAD RETURN AIR R.A. SMOKE CONTROL DAMPER SCD EXHAUST EXH FLAT TOP FEET PER MINUTE FT FPM DEGREES FAHRENHEIT FAN COIL UNIT FLOOR DRAIN FLEXIBLE FCU FD FLEX °F TOPT TOP OF PIPE TRAPEZE VENT THRU ROOF VTR VEL VAV VARIABLE AIR VOLUME VELOCITY GALLONS PER HOUR GALLONS PER MINUTE GPH GPM HAND DAMPER (VOLUME DAMPER) HIGH EFFICIENCY PARTICULATE AIR (FILTER) HD HEPA INCHES IN MAKE-UP WATER CONDENSATE DRAIN PIPING SYMBOLS PLUG VALVE VALVE SYMBOLS GATE VALVE GLOBE VALVE SAFETY VALVE OR PRESSURE RELIEF MANUAL AIR VENT BALL VALVE VALVE IN RISE WCO WH WALL CLEANOUT WALL HYDRANT V VAC VOLTS VOLTS, ALTERNATING CURRENT TP TOTAL PRESSURE (INCHES OF WATER) SP STATIC PRESSURE (INCHES OF WATER) Rh RPM RELATIVE HUMIDITY REVOLUTIONS PER MINUTE KWH KW KILOWATT KILOWATT HOUR HB HOSE BIBB FS FLOOR SINK FCO FLOOR CLEANOUT ENT ENTERING DX DIRECT EXPANSION BTU BTUH BRITISH THERMAL UNIT BTU PER HOUR BHP BRAKE HORSEPOWER DUCTWORK SYMBOLS SECTION SYMBOLS SDVV SINGLE DUCT VARIABLE VOLUME ST SOUND TRAP TYP. TYPICAL CONT. CONTINUATION D DRAIN EMCS ENERGY MANAGEMENT CONTROL SYSTEM FT. FEET F.G. FILTER GAUGE FB FLAT BOTTOM MA MAIN AIR (CONTROLS) NOTE: NOT ALL ABBREVIATIONS AND SYMBOLS APPLY TO THIS PROJECT. COMBINATION FIRE/SMOKE DAMPER DUCTED RETURN REGISTER DUCT MOUNTED SMOKE DETECTOR 1HR FIRE BARRIER (VERIFY WITH ARCHITECTURAL DRAWINGS) CD ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN FURRED CHASES OR SUSPENDED CEILINGS, UNLESS OTHERWISE NOTED. PROVIDE ACCESS PANELS OR DOORS IN INACCESSIBLE CEILINGS AND/OR CHASES FOR ALL VALVES, TRAPS, DAMPERS, CLEANOUTS, COILS, FANS, CONTROLS, ETC. THEY SHALL BE FURNISHED UNDER DIVISION 23 AND INSTALLED UNDER THE ARCHITECTURAL SPECIFICATION. ACCESS DOOR RATING SHALL MATCH CLASSIFICATION OF WALL AND CEILING FIRE RATING. COORDINATE THE LOCATION OF ALL DIFFUSERS, GRILLES, REGISTERS, ACCESS DOORS, ETC., WITH THE ARCHITECTURAL REFLECTED CEILING PLAN(S). ALL ROUND RUNOUTS AND DROPS TO DIFFUSERS SHALL BE THE SAME NOMINAL SIZE AS THE SCHEDULED DIFFUSER NECK SIZE. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED. ALL DUCT SIZES SHOWN ON DRAWINGS ARE NET INSIDE DIMENSIONS. PROVIDE ONE INCH ACOUSTICAL LINING IN LOW VELOCITY RECTANGULAR DUCTWORK UNLESS NOTED OTHERWISE ON THE DRAWINGS. SEE SPECIFICATIONS. PROVIDE TURNING VANES IN ALL SQUARE ELBOWS, EXCEPT TRANSFER AIR SOUND ELBOWS. THE CFM OF EACH DIFFUSER, REGISTER, ETC., IS INDICATED AS A NUMBER NEXT TO THE SYMBOL DESIGNATION ON THE DRAWINGS. REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF ALL FIRE RATED AND/OR SMOKE RATED WALLS AND ASSEMBLIES. PROVIDE APPROVED FIRE DAMPERS IN ALL REQUIRED PENETRATIONS FOR DUCTWORK, GRILLES, REGISTERS AND DIFFUSERS. ALL PIPE AND DUCTWORK PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF CAULKING MATERIAL. CONTRACTOR SHALL COORDINATE ALL DUCTWORK, PIPING, PLUMBING AND FIRE PROTECTION PIPING WITH STRUCTURAL AND ELECTRICAL SYSTEMS AND SHALL PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY. CONTRACTOR SHALL FURNISH ALL NECESSARY STRUCTURES, INSERTS, SLEEVES, AND HANGING DEVICES FOR INSTALLATION OF MECHANICAL AND PLUMBING EQUIPMENT, DUCTWORK AND PIPING, ETC. CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND ALL BUILDING TRADES TO AVOID CONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY MISCELLANEOUS ANGLES, CHANNELS, UNISTRUT, ETC., AS MAY BE REQUIRED TO ADEQUATELY SUPPORT THE MECHANICAL PIPING, DUCTWORK, AND EQUIPMENT IN A MANNER APPROVED BY THE ARCHITECT, WHICH WILL NOT OVERLOAD THE BUILDING STRUCTURAL SYSTEM. CONTRACTOR SHALL PROVIDE RETURN AIR OR TRANSFER AIR OPENINGS IN FULL HEIGHT WALLS SIZED AT 350 FPM (UNLESS OTHERWISE SPECIFICALLY SHOWN ON THE DRAWINGS) TO CREATE AND/OR MAINTAIN A RETURN AIR PATH AS REQUIRED. FIRE DAMPERS AND/OR SMOKE DAMPERS SHALL BE PROVIDED IN SUCH OPENINGS WHERE REQUIRED BY NOTE #10. SEAL ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS, DUCT WALL PENETRATIONS AND FITTING CONNECTIONS ON ALL DUCT SYSTEMS. MECHANICAL ITEMS SUCH AS ROOF DRAINS, FLOOR DRAINS, PLUMBING FIXTURES, ETC. SHOWN ON THE ARCHITECTURAL DRAWINGS BUT NOT SHOWN ON THE MECHANICAL DRAWINGS SHALL BE INCLUDED IN THE PROJECT. THESE ITEMS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR INCLUSION IN ADDENDUM. 1. 2. 3. 4 5 6. 7. 8. 9. 10. 11. 12. 13. 14. F.DPR S.DPR F/S DPR XX - # ##x# SINGLE LINE PIPE SYMBOLS ELBOW - DOWN ELBOW - UP PIPE RISE - DROP ELBOW - DOWN TO TEE TEE - DOWN TEE - UP ELBOW - UP TO TEE END CAP FLEX CONNECTION PIPE REDUCER - CONCENTRIC PIPE REDUCER - ECCENTRIC PIPE STRAINER UNION - SCREWED AIR VENT - AUTOMATIC AIR VENT - MANUAL GAUGE - DIFFERENTIAL GAUGE - PRESSURE GAUGE - PRESSURE GAUGE - PRESSURE WITH COCK GAUGE - TEMPERATURE PIPE - CAPPED WITH SHUT-OFF VALVE PIPE ANCHOR PIPE EXPANSION JOINT P PS A F PS TS PIPE GUIDE SENSOR - FLOW SWITCH - FLOW SWITCH - PRESSURE SWITCH - TEMPERATURE TEMPERATURE - PRESSURE TEST FITTING THERMOMETER THERMOMETER WELL SECTION NUMBER DRAWING NUMBER WHERE DETAILED DETAIL LOCATION DRAWING NUMBER WHERE DETAILED X# X### X#/X### DETAIL LOCATION X# SECTION LOCATION X# SECTION DETAIL SCALE SCALE FITTING SYMBOLS RS REFRIGERATION SUCTION RL REFRIGERATION LIQUID VALVE - BALL LEVER VALVE - GATE MANUAL VALVE - GLOBE MANUAL VALVE - GLOBE LEVER VALVE - PLUG LEVER VALVE - PLUG MANUAL VALVE - PRESSURE RELIEF R REFRIGERATION MU DRAIN D SINGLE LINE PIPE SYMBOLS THE DEMOLITION DRAWINGS REFLECT INFORMATION ON EXISTING BUILDING SERVICES GATHERED BY SITE INSPECTION, DISCUSSIONS WITH MAINTENANCE PERSONNEL AND PREVIOUS CONSTRUCTION DRAWINGS. THE EXACT LOCATION, ARRANGEMENT, AND SIZES OF PIPE LINES AND DUCTWORK IN THE EXISTING BUILDING MAY BE DIFFERENT FROM THAT SHOWN ON THESE DRAWINGS. THE CONTRACTOR SHALL COORDINATE THE SHUTDOWN OF EXISTING BUILDING SERVICES FOR REMOVALS WITH OWNER AUTHORIZED REPRESENTATIVE AND SHALL CONFORM TO THEIR REQUIREMENTS. DISRUPTION OF NORMAL SCHOOL ACTIVITIES ARE TO BE KEPT TO AN ABSOLUTE MINIMUM. DUST, DEBRIS, AND FUMES SHALL BE CONTROLLED SO AS NOT TO AFFECT THE HEALTH AND SAFETY OF OCCUPIED AREAS WITHIN THE SCHOOL CENTER WHICH ARE OUTSIDE THE AREA OF WORK. COORDINATE WITH THE ARCHITECT AND THE OWNER'S REPRESENTATIVE WITH REGARD TO ALL ACTIVITIES TO BE CONDUCTED OUTSIDE OF THE REMODEL AREA WHICH MAY AFFECT THE OPERATION OF THE SCHOOL. THE CONTRACTOR SHALL PRESENT AN AREA BY AREA WORK PLAN WELL IN ADVANCE TO THE ARCHITECT AND THE OWNER'S AUTHORIZED REPRESENTATIVE FOR APPROVAL PRIOR TO BEGINNING WORK. THE WORK PLAN SHALL INCLUDE AN OUTLINE OF ALL ACTIVITIES OF ALL SUBCONTRACTORS. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER'S AUTHORIZED REPRESENTATIVE TO ESTABLISH ACCEPTABLE ROUTING AND ACCESS WITHIN THE SCHOOL FOR MATERIALS REQUIRED FOR THE NEW INSTALLATION. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL TRADES INCLUDING MECHANICAL, PLUMBING, ELECTRICAL, FURNITURE, AND ARCHITECTURAL. ANY DISCREPANCIES SHALL BE REPORTED IMMEDIATELY TO THE ARCHITECT PRIOR TO START OF WORK. ALL NEW TO EXISTING DUCT CONNECTIONS SHALL BE FIELD VERIFIED PRIOR TO ORDERING AND FABRICATING NEW DUCTWORK OR DAMPERS A B C D E F GENERAL DEMO NOTES: ACCESS DOOR AD AIR HANDLING UNIT AHU COMPRESSED AIR CONDENSATE DRAIN CA CD DETAIL REFERENCE SECTION AND DETAIL TITLES 2HR FIRE BARRIER (VERIFY WITH ARCHITECTURAL DRAWINGS) 2HR SMOKE BARRIER (VERIFY WITH ARCHITECTURAL DRAWINGS) RISE IN DUCT T F O E C I N E I L D E S N S A X A T S E R E E N I G N L A O S S E F O R P E T ABBAS SHIRIAN 102840 PROJECT 1 A 2 3 4 5 B C D 1 2 3 4 5 SEAL REVISIONS SHEET NO DRAWING NAME PROJECT NO: REVIEWED BY DATE V E G A I S D C A R E E R T E C H N O L O G Y B U I L D I N G 2 0 0 L O N G H O R N S T . V E G A , T X 7 9 0 9 2 14-0424.002 01.29.2016 Addendum 01 DATE 1 / 2 9 / 2 0 1 6 1 1 : 2 4 : 0 8 A M M001a MECHANICAL LEGEND RLM Digitally signed by Abbas Shirian Date: 2016.01.29 11:29:11-07'00'

Transcript of 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles,...

Page 1: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

SD

24"x12"

24"/12"

12" o

GENERAL NOTES:MECHANICAL SYMBOL LEGENDABBREVIATIONS

FIRE DAMPER

FLEXIBLE DUCT

ACOUSTICAL DUCT LINING

FLEXIBLE CONNECTION

MANUAL BALANCING DAMPER

SMOKE DAMPER

MITERED ELBOW (ALL MITERED ELBOWS ARE TO HAVEVANES EXCEPT TRANSFER AIR SOUND ELBOW)

EXISTING DUCT TO BE REMOVED

CONNECT NEW DUCT TO EXISTING DUCT

SUPPLY DUCT, SECTION

EXHAUST DUCT, SECTION

RETURN DUCT, SECTION

DUCT TRANSITION

OR REGISTER

STANDARD RADIUS ELBOW

SHORT RADIUS VANED ELBOW (ALL SHORT RADIUS ELBOWS ARE

TO HAVE VANES PER SMACNA)

CEILING RETURN AIR REGISTER OR TRANSFER AIR GRILLE

INDICATES A RECTANGULAR DUCT SIZE (WIDTH x DEPTH)

INDICATES A FLAT OVAL DUCT SIZE (WIDTH x DEPTH)

INDICATES A ROUND DUCT SIZE

IF THROW IS SOMETHING OTHER THAN 4-WAY)CEILING DIFFUSERS (ARROWS DENOTE THROW PATTERN

DUCTED EXHAUST REGISTER

SIDEWALL EXHAUST OR RETURN AIR GRILLE

SIDEWALL SUPPLY REGISTER

T

ACCESS DOOR

SEE CONTROL DRAWINGS FOR TYPEROOM THERMOSTAT/TEMP. TRANSMITTER LOCATION ONLY

DUCT MOUNTED STATIC PRESSURE PROBE

###

XX - ## NUMBERS REFER TO SPECIFIC EQUIPMENT

SYMBOL INDICATES NEW EQUIPMENT

EQUIPMENT SYMBOLS

IDENTIFIED IN EQUIPMENT SCHEDULE

CFM

SYMBOL INDICATES GRILLE OR

DIFFUSER IDENTIFIED IN EQUIPMENT

SCHEDULE

SIDEWALL GRILLE DIMENSION WHERE SHOWN ON

PLANS

LETTERS REFER TO THE EQUIPMENT TYPE

ACCESS DOOR

AIR CONDITIONING UNIT

ABOVE FINISHED FLOOR

ACOUSTIC LINING

ACU

AD

AFF

AL

BOP

BOD

BOTTOM OF PIPE

BOTTOM OF DUCT

CUBIC FEET PER MINUTE CLEANOUT

CFM CO

MOTOR CONTROL CENTERMCC

NOT APPLICABLE

NOT IN CONTRACT

NUMBER (QUANTITY)

NA

NIC

NO.

OUTSIDE AIR

OPPOSED BLADE DAMPER

OA

OBD

PSIG

PRV PRESSURE REDUCING VALVE

POUNDS PER SQUARE INCH GAGE

QUADRANT

QUANTITYQTY

QUAD

RETURN AIRR.A.

SMOKE CONTROL DAMPER SCD

EXHAUST EXH

FLAT TOP

FEET PER MINUTE

FT

FPM

DEGREES FAHRENHEIT

FAN COIL UNIT

FLOOR DRAIN

FLEXIBLE

FCU FD

FLEX

°F

TOPT TOP OF PIPE TRAPEZE

VENT THRU ROOFVTR

VEL

VAV VARIABLE AIR VOLUME

VELOCITY

GALLONS PER HOUR GALLONS PER MINUTE

GPH GPM

HAND DAMPER (VOLUME DAMPER)

HIGH EFFICIENCY PARTICULATE AIR (FILTER)

HD

HEPA

INCHESIN

MAKE-UP WATER

CONDENSATE DRAIN

PIPING SYMBOLS

PLUG VALVE

VALVE SYMBOLS

GATE VALVE

GLOBE VALVE

SAFETY VALVE OR PRESSURE RELIEF

MANUAL AIR VENT

BALL VALVE

VALVE IN RISE

WCO

WH

WALL CLEANOUT

WALL HYDRANT

V

VAC

VOLTS

VOLTS, ALTERNATING CURRENT

TP TOTAL PRESSURE (INCHES OF WATER)

SP STATIC PRESSURE (INCHES OF WATER)

Rh

RPM

RELATIVE HUMIDITY

REVOLUTIONS PER MINUTE

KWH

KW KILOWATT

KILOWATT HOUR

HB HOSE BIBB

FS FLOOR SINK

FCO FLOOR CLEANOUT

ENT ENTERING

DX DIRECT EXPANSION

BTU

BTUH

BRITISH THERMAL UNIT

BTU PER HOUR

BHP BRAKE HORSEPOWER

DUCTWORK SYMBOLS

SECTION SYMBOLS

SDVV SINGLE DUCT VARIABLE VOLUME

ST SOUND TRAP

TYP. TYPICAL

CONT. CONTINUATION

D DRAIN

EMCS ENERGY MANAGEMENT CONTROL SYSTEM

FT. FEET

F.G. FILTER GAUGE

FB FLAT BOTTOM

MA MAIN AIR (CONTROLS)

NOTE: NOT ALL ABBREVIATIONS AND SYMBOLS

APPLY TO THIS PROJECT.

COMBINATION FIRE/SMOKE DAMPER

DUCTED RETURN REGISTER

DUCT MOUNTED SMOKE DETECTOR

1HR FIRE BARRIER (VERIFY WITH ARCHITECTURAL

DRAWINGS)

CD

ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN FURRED CHASES OR

SUSPENDED CEILINGS, UNLESS OTHERWISE NOTED.

PROVIDE ACCESS PANELS OR DOORS IN INACCESSIBLE CEILINGS AND/OR CHASES FOR ALL VALVES,

TRAPS, DAMPERS, CLEANOUTS, COILS, FANS, CONTROLS, ETC. THEY SHALL BE FURNISHED UNDER

DIVISION 23 AND INSTALLED UNDER THE ARCHITECTURAL SPECIFICATION. ACCESS DOOR RATING SHALL

MATCH CLASSIFICATION OF WALL AND CEILING FIRE RATING.

COORDINATE THE LOCATION OF ALL DIFFUSERS, GRILLES, REGISTERS, ACCESS DOORS, ETC., WITH THE

ARCHITECTURAL REFLECTED CEILING PLAN(S).

ALL ROUND RUNOUTS AND DROPS TO DIFFUSERS SHALL BE THE SAME NOMINAL SIZE AS THE SCHEDULED

DIFFUSER NECK SIZE.

THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED. ALL DUCT SIZES

SHOWN ON DRAWINGS ARE NET INSIDE DIMENSIONS. PROVIDE ONE INCH ACOUSTICAL LINING IN LOW

VELOCITY RECTANGULAR DUCTWORK UNLESS NOTED OTHERWISE ON THE DRAWINGS. SEE

SPECIFICATIONS.

PROVIDE TURNING VANES IN ALL SQUARE ELBOWS, EXCEPT TRANSFER AIR SOUND ELBOWS.

THE CFM OF EACH DIFFUSER, REGISTER, ETC., IS INDICATED AS A NUMBER NEXT TO THE SYMBOL

DESIGNATION ON THE DRAWINGS.

REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF ALL FIRE RATED AND/OR SMOKE

RATED WALLS AND ASSEMBLIES. PROVIDE APPROVED FIRE DAMPERS IN ALL REQUIRED PENETRATIONS

FOR DUCTWORK, GRILLES, REGISTERS AND DIFFUSERS. ALL PIPE AND DUCTWORK PENETRATIONS OF

FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY

MEANS OF U.L. APPROVED FIRE PROOF CAULKING MATERIAL.

CONTRACTOR SHALL COORDINATE ALL DUCTWORK, PIPING, PLUMBING AND FIRE PROTECTION PIPING

WITH STRUCTURAL AND ELECTRICAL SYSTEMS AND SHALL PROVIDE NECESSARY OFFSETS TO AVOID

CONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY.

CONTRACTOR SHALL FURNISH ALL NECESSARY STRUCTURES, INSERTS, SLEEVES, AND HANGING DEVICES

FOR INSTALLATION OF MECHANICAL AND PLUMBING EQUIPMENT, DUCTWORK AND PIPING, ETC.

CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND ALL BUILDING TRADES TO AVOID

CONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY.

CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY MISCELLANEOUS ANGLES,

CHANNELS, UNISTRUT, ETC., AS MAY BE REQUIRED TO ADEQUATELY SUPPORT THE MECHANICAL PIPING,

DUCTWORK, AND EQUIPMENT IN A MANNER APPROVED BY THE ARCHITECT, WHICH WILL NOT OVERLOAD

THE BUILDING STRUCTURAL SYSTEM.

CONTRACTOR SHALL PROVIDE RETURN AIR OR TRANSFER AIR OPENINGS IN FULL HEIGHT WALLS SIZED AT

350 FPM (UNLESS OTHERWISE SPECIFICALLY SHOWN ON THE DRAWINGS) TO CREATE AND/OR MAINTAIN A

RETURN AIR PATH AS REQUIRED. FIRE DAMPERS AND/OR SMOKE DAMPERS SHALL BE PROVIDED IN SUCH

OPENINGS WHERE REQUIRED BY NOTE #10.

SEAL ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS, DUCT WALL PENETRATIONS AND FITTING

CONNECTIONS ON ALL DUCT SYSTEMS.

MECHANICAL ITEMS SUCH AS ROOF DRAINS, FLOOR DRAINS, PLUMBING FIXTURES, ETC. SHOWN ON THE

ARCHITECTURAL DRAWINGS BUT NOT SHOWN ON THE MECHANICAL DRAWINGS SHALL BE INCLUDED IN

THE PROJECT. THESE ITEMS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR INCLUSION

IN ADDENDUM.

1.

2.

3.

4

5

6.

7.

8.

9.

10.

11.

12.

13.

14.

F.DPR

S.DPR

F/S DPR

XX - ###x#

SINGLE LINE PIPE SYMBOLS

ELBOW - DOWN

ELBOW - UP

PIPE RISE - DROP

ELBOW - DOWN TO TEE

TEE - DOWN

TEE - UP

ELBOW - UP TO TEE

END CAP

FLEX CONNECTION

PIPE REDUCER - CONCENTRIC

PIPE REDUCER - ECCENTRIC

PIPE STRAINERUNION - SCREWED

AIR VENT - AUTOMATIC

AIR VENT - MANUAL

GAUGE - DIFFERENTIALGAUGE - PRESSURE

GAUGE - PRESSURE

GAUGE - PRESSURE WITH COCK

GAUGE - TEMPERATURE

PIPE - CAPPED WITH SHUT-OFF VALVE

PIPE ANCHOR

PIPE EXPANSION JOINT

P

PS

A

F

PS

TS

PIPE GUIDE

SENSOR - FLOW

SWITCH - FLOW

SWITCH - PRESSURE

SWITCH - TEMPERATURE

TEMPERATURE - PRESSURE TEST FITTING

THERMOMETER

THERMOMETER WELL

SECTION NUMBER

DRAWING NUMBER WHERE DETAILED

DETAIL LOCATION

DRAWING NUMBER WHERE DETAILED

X#X###

X#/X### DETAIL LOCATION X#

SECTION LOCATION X#SECTION

DETAIL

SCALE

SCALE

FITTING SYMBOLS

RS REFRIGERATION SUCTION

RL REFRIGERATION LIQUID

VALVE - BALL LEVER

VALVE - GATE MANUAL

VALVE - GLOBE MANUAL

VALVE - GLOBE LEVER

VALVE - PLUG LEVER

VALVE - PLUG MANUAL

VALVE - PRESSURE RELIEF

R REFRIGERATION

MU

DRAIND

SINGLE LINE PIPE SYMBOLS

THE DEMOLITION DRAWINGS REFLECT INFORMATION ON EXISTING BUILDING SERVICES GATHERED BY SITE

INSPECTION, DISCUSSIONS WITH MAINTENANCE PERSONNEL AND PREVIOUS CONSTRUCTION DRAWINGS. THE

EXACT LOCATION, ARRANGEMENT, AND SIZES OF PIPE LINES AND DUCTWORK IN THE EXISTING BUILDING MAY BE

DIFFERENT FROM THAT SHOWN ON THESE DRAWINGS.

THE CONTRACTOR SHALL COORDINATE THE SHUTDOWN OF EXISTING BUILDING SERVICES FOR REMOVALS

WITH OWNER AUTHORIZED REPRESENTATIVE AND SHALL CONFORM TO THEIR REQUIREMENTS.

DISRUPTION OF NORMAL SCHOOL ACTIVITIES ARE TO BE KEPT TO AN ABSOLUTE MINIMUM. DUST, DEBRIS, AND

FUMES SHALL BE CONTROLLED SO AS NOT TO AFFECT THE HEALTH AND SAFETY OF OCCUPIED AREAS WITHIN

THE SCHOOL CENTER WHICH ARE OUTSIDE THE AREA OF WORK. COORDINATE WITH THE ARCHITECT AND THE

OWNER'S REPRESENTATIVE WITH REGARD TO ALL ACTIVITIES TO BE CONDUCTED OUTSIDE OF THE REMODEL

AREA WHICH MAY AFFECT THE OPERATION OF THE SCHOOL.

THE CONTRACTOR SHALL PRESENT AN AREA BY AREA WORK PLAN WELL IN ADVANCE TO THE ARCHITECT AND

THE OWNER'S AUTHORIZED REPRESENTATIVE FOR APPROVAL PRIOR TO BEGINNING WORK. THE WORK PLAN

SHALL INCLUDE AN OUTLINE OF ALL ACTIVITIES OF ALL SUBCONTRACTORS. THE CONTRACTOR SHALL

COORDINATE WITH THE OWNER'S AUTHORIZED REPRESENTATIVE TO ESTABLISH ACCEPTABLE ROUTING AND

ACCESS WITHIN THE SCHOOL FOR MATERIALS REQUIRED FOR THE NEW INSTALLATION.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL TRADES INCLUDING MECHANICAL,

PLUMBING, ELECTRICAL, FURNITURE, AND ARCHITECTURAL. ANY DISCREPANCIES SHALL BE REPORTED

IMMEDIATELY TO THE ARCHITECT PRIOR TO START OF WORK.

ALL NEW TO EXISTING DUCT CONNECTIONS SHALL BE FIELD VERIFIED PRIOR TO ORDERING AND FABRICATING

NEW DUCTWORK OR DAMPERS

A

B

C

D

E

F

GENERAL DEMO NOTES:

ACCESS DOORAD

AIR HANDLING UNIT AHU

COMPRESSED AIR CONDENSATE DRAIN

CA CD

DETAIL REFERENCE

SECTION AND DETAIL TITLES

2HR FIRE BARRIER (VERIFY WITH ARCHITECTURAL

DRAWINGS)2HR SMOKE BARRIER (VERIFY WITH ARCHITECTURAL

DRAWINGS)

RISE IN DUCT

TFOE

C

I N

EI

L D

ESN

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

ABBAS SHIRIAN

102840

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 11

:24:

08 A

M

M001a

MECHANICALLEGEND

RLM

Digitally signed by Abbas ShirianDate: 2016.01.29 11:29:11-07'00'

Page 2: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

AG-RTU-01

20"x

20"

32"x18"

RTU ON16" CURB

20"X20" TO AG BLDG

1" ACOUSTICAL LINING

2" RIGID POLYSTYRENEINSULATION

4" THICK CONCRETEHOUSEKEEPING PAD

RTU ON16" CURB

AG-RTU-0132"x18"

18"x

18"

2" RIGID POLYSTYRENEINSULATION

18"X18" TO AG BLDG

SMOKE DETECTOR ANDSAMPLING TUBES

4" THICK CONCRETEHOUSEKEEPING PAD

TFOE

C

I N

EI

L D

ESN

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

ABBAS SHIRIAN

102840

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 11

:24:

10 A

M

M301a

MECHANICALSECTIONS

RLB

SCALE: 3/8" = 1'-0"1 AG SHOP - RTU DUCTWORK - 01SCALE: 3/8" = 1'-0"2 AG SHOP - RTU DUCTWORK - 02

Page 3: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

SECTION A

SECTION B

W X L

ROUND

DUCT

DIAMETER

MAJOR AXIS

WHEN MOUNTED

ON MAJOR AXIS

MINOR AXIS

WHEN MOUNTED

ON MAJOR AXIS

W

L

D 3/4D

FLAT OVAL DUCT

ROUND OR FLAT OVAL DUCT, 8" +

8" X 12"

12" X 12"

14" X 20"

8" - 12"

13" X 18"

19" +

8" - 16"

17" - 24"

25" +

8" - 11"

12" - 13"

14" +

W

SECTION C

RECTANGULAR DUCTS

NOTE:

DUCT ACCESS DOORS SHALL

BE PROVIDED AT EACH

FIRE DAMPER, SMOKE DAMPER,

DUCT MOUNTED EQUIPMENT,

AND AS REQUIRED FOR DUCT

CLEANING AND INSPECTION

DUCT DIMENSION ON WHICH

ACCESS DOOR IS PLACED

OUTSIDE FRAME

W X L

6" - 8"

9" - 12"

13" - 15"

16" - 33"

34" - 66"

67" +

5" X 12"

8" X 8"

12" X 12"

14" X 14"

(2) 14" X 14"

(3) 14" X 14"

SCALE = NONE

DUCT ACCESS DOOR DETAIL

BOLT AND WING NUT AT MAX.

3" O.C.

TACK WELD BOLT TO DUCT

PROVIDE GASKET BETWEEN

DUCT AND ACCESS DOOR

HANDLE

INSULATE COVER AS REQUIRED

BY DUCT INSULATION SPEC.

MIN. 20 GA FRAME WELDED TO

DUCT

PRESSURE SENSITIVE LATCH

FOR VACUUM RELEASE

RETAINER CHAIN

MIN. 22 GA GALV. STEEL

FRAME

FRAME SECURED TO DUCT

WITH 5/8" NOTCHED

KNOCK-OVER EDGES ON ALL

SIDES

CONTINUOUS HINGE

CAM LATCH

MIN. 22 GA DOOR

C5

C

B

B

3

1

4

5

2

9 7

6

7

4

12

9

10

13

11

10

3

9L

1

2

3

4

5

6

7

8

9

10

11

12

13

A5SCALE = NONE

20 30

30

RISE

PLAN

NOTES

1. ANGLE A=30 MAXIMUM WHEN AIR FLOWS IN

DIRECTION OF ARROS. (SUPPLY AIR)

2. ANGLE A=15 WHEN AIR FLOWS IN OPPOSITE

DIRECTION OF ARROS (R.A. OR EXHAUST)

20°

3.73xH

FBFT

FT FB

A°A°

PLAN VIEW PLAN VIEW PLAN VIEW

TRANSITION

w/ EQUIPMENT

ELEVATION

PLAN

DUCT OFFSET

FT FB

FBFT

A° A°

ELEVATION ELEVATION ELEVATION BRANCH DUCT

PLAN

45°

LOW PRESSURE DUCT FITTING DETAIL

W

1/2 W

(4"MIN.)

PLAN A

A

B

C

(1) NECK DIA. MIN.

PROVIDE HAND DAMPER

WITH ACCESS DOOR

WHERE SHOWN ON PLANS

BRANCH

DUCT

BRANCH

MAIN

FIXED CEILINGS

SECTION A

FLEX DUCT. DIAMETER EQUAL

TO DIFFUSER NECK SIZE (MAX.

LENGTH 4'-0")

SPIN IN FITTING

W/HAND DAMPER

SECTION B

LAY-IN CEILINGS

PLAN B

RIGID DUCT WHERE

RUN-OUT EXCEEDS

4'-0"

PROVIDE HAND DAMPER

WITH ACCESS DOOR

WHERE SHOWN ON

PLANS

SHEET METAL

PLENUM

RIGID DUCT WHERE

RUN-OUT EXCEEDS

4'-0"FLEX. DUCT FOR

LAY-IN CEILING

APPLICATION

EXHAUST/DUCTED RETURN

GRILLE. SEE FLOOR PLAN

FOR SIZE, TYPE, AND

LOCATION

SCALE = NONEC3

DIFFUSER AND REGISTER CONNECTION DETAIL

SECTION C

RETURN/EXHAUST REGISTER

FOR LAY-IN AND FIXED CEILINGS

PLAN C

SCALE = NONEB3GROUND MOUNTED DUCT SUPPORT DETAIL

P-1000

UNISTRUT

3"X3"X1/16"

STEEL PLATE TYP.

MIN. 6" GREATER THAN

DUCT DIMENSION AS

SHOWN ON PLANS

6"x6"x1/4" PLATE

4'-0" O.C.

12'-0" O.C.

SCALE = NONEC1FLUE THRU ROOF DETAIL

1

1

FLUE HEIGHT SHALL BE NO LESS THAN 3'-0" ABOVE THE HORIZONTAL ROOF

PLANE. SHOULD ANY OBSTRUCTION WITHIN A 10 FOOT RADIUS OF THE FLUE

PROJECT ABOVE THE HORIZONTAL ROOF PLANE, THE FLUE SHALL EXTEND TO 3'-0"

ABOVE THE OBSTRUCTION. OBSTRUCTIONS INCLUDE BUT ARE NOT LIMITED TO

ITEMS SUCH AS PARAPETS, WALLS, AIR INTAKES, AND ROOF SLOPES.

OPEN BELOW

RAIN CAP

FLASH AND

COUNTERFLASH

METAL ROOF

JACK

TYPE L FLUE CAP

TYPE B VENT

SOLDER

METAL RAIN CAP

1" MIN. CLEARANCE

CEILING

9"

SCALE = NONE

IN-LINE FAN DETAILA1

PLAN

ELEVATION

1

4 3

27

6

12

5

43

8

7

IN-LINE FAN

SIDE MOUNTED MOTOR WHERE CEILING SPACE IS LIMITED

ACOUSTICALLY LINED DUCT UNLESS NOTED OTHERWISE ON PLAN

FLEXIBLE DUCT CONNECTION (TYPICAL)

TYPICAL VIBRATION ISOLATOR

1/2" STEEL ALL-THREAD SUPPORT RODS SECURELY ANCHORED

TO STRUCTURE ABOVE IN A MANNER APPROVED BY THE

STRUCTURAL ENGINEER

BELT GUARD ON BELT-DRIVE FANS (TYPICAL)

ACCESS DOOR IN HOUSING TO FAN

1

2

3

4

5

6

7

8 CLEAR FROM ALL PIPING

CONTAINING WATER

6'-0" OR TO

SURFACE CLEAR FOR

CONDUIT

RECESSED OF SURFACE

MOUNTED ELECTRICAL

PANEL

6'-0" OR TO

SURFACE CLEAR FOR

CONDUIT

STRUCTURE

CEILING WALL

42" MINIMUM IN

COMPLIANCE WITH

ARTICLE 110 IN THE NEC

3'-6"x6'-6"

HIGH

MINIMUM

FLOOR

EXCLUSIVELY DEDICATED

ELECTRICAL SPACE. NO PIPING OR

DUCT SHALL BE ALLOWED WITHIN

THESE AREAS

ELECTRICAL SPACE. NO WATER PIPING

SHALL BE ALLOWED WITHIN THESE

AREAS

CLEARANCE REQUIREMENTS AT ELECTRICAL PANELSA3 SCALE = NONE

TFOE

C

I N

EI

L D

ESN

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

ABBAS SHIRIAN

102840

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 11

:24:

13 A

M

M501a

MECHANICALDETAILS

RLM

Page 4: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

LA LEVEL ALARM

AT ANALYTICAL TRANSMITTER

AY ANALYTICAL SIGNAL CONVERTER

ACV ANALYTICAL CONTROL VALVE

AIT ANALYTICAL INDICATING CONTROLLER

EY VOLTAGE SIGNAL CONVERTER

IY CURRENT SIGNAL CONVERTER

HS HAND SWITCH

FIT FLOW INDICATING TRANSMITTER

FET FLOW ELEMENT\TRANSMITTER

ESL VOLTAGE SWITCH LOW (24 VAC OR LESS)

II CURRENT INDICATOR

IT CURRENT TRANSMITTER

IS CURRENT SWITCH

IA CURRENT ALARM

FA FLOW ALARM

HSI HAND SWITCH INDICATOR

HK MANUAL VARIABLE CONTROL

FY FLOW SIGNAL CONVERTER

FT FLOW TRANSMITTER

FS FLOW SWITCH

FI FLOW INDICATOR

FE FLOW ELEMENT

FCV FLOW CONTROL VALVE

ET VOLTAGE TRANSMITTER

ES VOLTAGE SWITCH (CONTROL RELAY)

EA VOLTAGE ALARM

EI VOLTAGE INDICATOR

PY PRESSURE SIGNAL CONVERTER

PDT PRESSURE DIFFERENTIAL TRANSMITTER

PS PRESSURE SWITCH

PA PRESSURE ALARM

PT PRESSURE TRANSMITTER

PIT PRESSURE INDICATING TRANSMITTER

PIS PRESSURE INDICATING SWITCH

PI PRESSURE INDICATOR

PDS PRESSURE DIFFERENTIAL SWITCH

PDI PRESSURE DIFFERENTIAL INDICATOR

PCV PRESSURE CONTROL VALVE

MV MANUAL HAND VALVE

LT LEVEL TRANSMITTER

LS LEVEL SWITCH

LE LEVEL ELEMENT

LY LEVEL SIGNAL CONVERTER

LIT LEVEL INDICATING TRANSMITTER

LIC LEVEL INDICATING CONTROLLER

LCV LEVEL CONTROL VALVE

LC LEVEL CONTROLLER (STAND ALONE)

VA VIBRATION ALARM

VS VIBRATION SWITCH

XV SOLENOID VALVE

YS SMOKE DETECTOR

VA VIBRATION ALARM

VS VIBRATION SWITCH

YCD SMOKE DAMPER

TT TEMPERATURE TRANSMITTER

TS TEMPERATURE SWITCH

TIC TEMPERATURE INDICATING CONTROLLER

TIT TEMPERATURE INDICATING TRANSMITTER

TI TEMPERATURE INDICATOR

TET TEMPERATURE ELEMENT TRANSMITTER

TE TEMPERATURE ELEMENT

TCV TEMPERATURE CONTROL VALVE

TC TEMPERATURE CONTROLLER

TA TEMPERATURE ALARM

SCM SPEED CONTROL MANUAL

TSL FREEZE STAT

SC SPEED CONTROL

INSTRUMENTATION SOCIETY OF AMERICA TABLE

INSTRUMENTATION TYPE ABBREVIATION LIST

AIC ANALYTICAL INDICATING CONTROLLER

AET ANALYTICAL ELEMENT TRANSMITTER

A

AC ANALYTICAL CONTROLLER

AI ANALYTICAL INDICATOR

AE ANALYTICAL ELEMENT

AA ANALYTICAL ALARM

CODE DESCRIPTION

VARIABLE

FINAL CONTROL ELEMENT

CODE DESCRIPTION

KC TIME CLOCK

JY POWER SIGNAL CONVERTER

JIT POWER INDICATING TRANSMITTER

TOTALIZE

CHANGE

CONNECTION

CODE DESCRIPTION

VIEWING DEVICE

PRIMARY ELEMENT

NORMALLY CLOSED OVERLOAD CONTACTS

ABBREVIATIONS

IA INSTRUMENTATION AIRDDC DIRECT DIGITAL CONTROLC COMMON VALVE PORTF.O FAIL OPENF.C FAIL CLOSEDSR SPRING RANGETR THROTTLING RANGEPH PREHEATHR HEAT RECOVERYCPA CONTROL POINT ADJUSTMENTSPDT SINGLE POLE DOUBLE THROWDPDT DOUBLE THROW DOUBLE POLEDA DIRECT ACTINGRA REVERSE ACTING

EP COIL IN MOTOR STARTER

TRANSFORMER

R

C

OL

HOA

CONTACT NORMALLY OPEN

PILOT LIGHT (COLOR INDICATION)

COIL IN MOTOR STARTER

CONTACT NORMALLY CLOSED

SWITCH

FUSE

HAND-OFF-AUTO SWITCH

I UNDEFINED INTERLOCK LOGIC

GENERAL INSTRUMENT OR FUNCTION SYMBOLS

FIELD

MOUNTED MOUNTED

PANEL AUXILIARY

LOCATION

ACCESSIBLE INACCESSIBLE

LOCATION

AUXILIARY

DISCRETE INSTRUMENTS

SHARED DISPLAY, SHARED CONTROL

PROGRAMMABLE LOGIC CONTROL

OR DIRECT DIGITAL CONTROL

COMPUTER FUNCTION

DUAL (MULTI)

FUNCTION INSTRUMENT

INDICATING LIGHTS, ALARMS OR HORNS

CONTROL VALVE BODY/ DAMPER SYMBOLS

GENERAL SYMBOL

ANGLE

BUTTERFLY

ROTARY VALVE

THREE - WAY

FOUR - WAY

GLOBE

PARALLEL BLADE

OPPOSED BLADE

TEMPERATURE

DUCT MOUNTED AVERAGING

WELL MOUNTED

ELEMENT/SENSOR ELEMENT/SENSOR

ELEMENT/SENSOR ELEMENT/SENSOR

SURFACE MOUNTED

PRESSURE

DIRECT MOUNTED

ELEMENT/SENSOR

DIFFERENTIAL PRESSURE

ELEMENT/SENSOR

LEVEL

FLOAT TYPE PADDLE TYPE

LEVEL TRANSMITTER

TANK MOUNTED

SONIC OR

RADIOACTIVE

FLOW

ORIFICE PLATETURBINE OR

PROPELLER

TYPE

SENSOR

VORTEX

TYPE

TARGET

SENSOR TRANSMITTER

MAGNETIC

TYPE

M

TRANSIT TIME

SONIC FLOWMETER

"DOPPLER" OR

~

FLOW ARROW

XXX INDICATES

AIR TYPE

INSTRUMENT NAMING CONVENTION

XXX - FUNCTION ID

NNN - DEVICE NUMBER

ZZZ - USER CHOICE

CURRENT

CURRENT SENSOR/TRANSMITTER

LINE LEGEND

INTERNAL SYSTEM LINK

ELECTRICAL SIGNAL

PNEUMATIC SIGNAL

YI EQUIPMENT STATUS

YA EQUIPMENT ALARM

ZI POSITION INDICATOR

ZS POSITION SWITCH

ZC POSITION CONTROL

AAA - UNIT ASSOCIATION OR

PROCESS CODE

PROCESS CODES

TW COOLING TOWER OR CONDENSER WATERCHW CHILLED WATERSCHW SECONDARY CHILLED WATERHW HOT WATERSHW SECONDARY HOT WATERSTM STEAM

AAA-NNN

XXX

ZZZ

NT HUMIDITY TRANSMITTER

FMS SYSTEM OPERATING CONSTRAINTS

THE FMS CONTROL SYSTEM SHALL OPERATE WITHIN THE FOLLOWING SYSTEM CONSTRAINTS FOR CONTROL:

SUPPLY AIR DRYBULB TEMPERATURE

MIXED AIR DRYBULB TEMPERATURE

WATER TEMPERATURE

DUCT STATIC PRESSURE

SUPPLY/ RETURN AIR VOLUME

OUTSIDE AIR/ RELIEF AIR VOLUME

BUILDING PRESSURE

ROOM TEMPERATURE

ROOM AIR VOLUME

HUMIDITY LEVEL

WATER TEMPERATURE

WATER DIFFERENTIAL PRESSURE

+/- 0.5°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

~

~

~

FT

~

~

FT

~

~

FE

~

~

FE

~

~

FEFE

~

~

~

~

~

L

L

L

TE

L

~

~

~

~

PD

TETE

TE

~

~~

~

~

~

~

~

~

~

~~

~

~

~

+/- 0.5°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 1.0 PSI OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 0.5°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 0.1" W.C. OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 2.5% OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 2.5% OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 0.01" W.C. OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 1.0°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 2.5% OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 2.5% R.H. OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 1.0°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

FIRST LETTER SUCCEEDING LETTERS (3)

MEASURING OR MODIFIER READOUT OR OUTPUT MODIFIER

INITIATING PASSIVE FUNCTION FUNCTION

ANALYSIS ALARM

B BURNER FLAME USER CHOICE USER CHOICE USER CHOICE

C CONDUCTIVITY CONTROL (13)

D DENSITY DIFFERENTIAL

E VOLTAGE SENSOR

F FLOW RATE RATIO FRACTION

G GAUGE GLASS,

H HAND HIGH

I CURRENT INDICATE

J POWER SCAN

K TIME TIME RATE OF CONTROL STATION

L LEVEL LIGHT LOW

M MOTION MOMENTARY MIDDLE

INTERMEDIATE

N HUMIDITY USER DEFINED USER DEFINED USER DEFINED

O USER CHOICE ORIFICE RESTRICTION

P PRESSURE, VACUUM POINT (TEST)

Q QUANTITY INTEGRATE,

R RADIATION RECORD

S SPEED, FREQUENCY SAFETY SWITCH

T TEMPERATURE TRANSMIT

U MULTI-VARIABLE MULTI-FUNCTION MULTI-FUNCTION MULTI-FUNCTION

V VIBRATION, MECHANICAL VALVE, DAMPER

ANALYSIS LOUVER

W WEIGHT, FORCE WELL

X UNCLASSIFIED X-AXIS UNCLASSIFIED UNCLASSIFIED UNCLASSIFIED

Y EVENT, STATE OR Y-AXIS RELAY, COMPUTE

PRESENCE CONVERT

Z POSITION Z-AXIS DRIVER, ACTUATOR

DIMENSION UNCLASSIFIED

TFOE

C

I N

EI

L D

ESN

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

ABBAS SHIRIAN

102840

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 11

:24:

27 A

M

MI001a

MECHANICALINSTRUMENTATIONLEGEND

RLM

Page 5: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

~

~

ESEF-01

ISEF-01

EF-01

HS

EF-01

II

TITFCU-01

TTFCU-01

FCU-01

TI

FCVRTU-02

YSRTU-01

TTRTU-01

PDIRTU-01

FCVRTU-01

TTRTU-03

TTRTU-04I

FU

RN

AC

E

X

D

EACH AIR HANDLING UNIT SHALL BE FURNISHED WITH FACTORY DDC CONTROLS FOR THE AIR HANDLING UNIT. THE AIR HANDLING UNIT SHALLBE CONNECTED TO THE FMS THROUGH A FMS COMMUNICATIONS TRUNK USING A BACNET COMMUNICATIONS CONNECTION. THE FMSCONTRACTOR SHALL COORDINATE COMMUNICATIONS REQUIREMENTS WITH THE AIR HANDLING UNIT MANUFACTURER. THE CONTRACTORSHALL PROVIDE INSTALLATION FOR ALL FIELD INSTALLED DEVICES FURNISHED WITH THE MECHANICAL EQUIPMENT. REFER TOSPECIFICATIONS FOR MORE INFORMATION. REFER TO SEQUENCE OF OPERATIONS FOR CONTROL FUNCTIONALITY.

R.A

S.A

FACTORY DDCCONTROL PANEL

E.A

O.A

LOCATE SENSORWHERE SHOWNON THE PLANS

1

LINE

E.A

ST

AR

T/S

TO

P

(DO) ST

AT

US

(DI)

BACKDRAFT

RETURN

CONTROLLER

C

R

AIR

FACTORY

RO

OM

TE

MP

.

(AI)

BARROMETRIC

MS

NC

FMS NETWORK

GENERAL

SYSTEM STATUS DISPLAYTHE FMS SHALL PROVIDE OPERATING STATUS FOR ALL SYSTEMS CONTROLLED BY THE FMS. THE DISPLAYS SHALL INCLUDE ALL POINTS INDICATED ON THE DRAWINGS AND ANY OTHERSREQUIRED TO ACHIEVE THE SEQUENCE OF OPERATIONS. THE FMS SHALL BE ABLE TO INTEGRATE SYSTEM DIAGNOSTICS INTO CONTROL ACTION DECISIONS. THIS SHALL ALSO INCLUDETHE ABILITY TO DESIGNATE INDIVIDUAL UNITS AS BEING IN MAINTENANCE MODE TO AVOID GENERATING ALARMS. ALL SYSTEM CONTROL AND STATUS EVENTS SHALL BE RECORDED, ATTHE OPERATOR'S SELECTION, IN THE FMS EVENT LOG TO FACILITATE TROUBLESHOOTING. ALL DETECTED ALARMS OR FAILURES SHALL INITIATE AN ALARM WITHIN THE FMS.

POWER FAILURE RECOVERYTHE FMS SHALL CONTAIN A POWER FAILURE RECOVERY MODE (OPERATOR ADJUSTABLE). THE POWER FAILURE RECOVERY CAPABILITY SHALL RETURN THE SYSTEM TO ITS LAST STATE(BEFORE THE BUILDING LOST POWER).

OCCUPANCY CONTROLTHE FMS SHALL BE SETUP WITH AN OCCUPANCY SCHEDULE FOR DIFFERENT AREAS OF THE BUILDING. THE OWNER SHALL BE INTERVIEWED BY THE CONTRACTOR AT START-UP TOESTABLISH THESE SCHEDULES. SOME AREAS OF THE BUILDING SHALL BE SETUP TO BE CONTINUOUSLY OCCUPIED.

EMERGENCY OUTDOOR AIR OVERRIDETHE FMS SHALL HAVE AN EMERGENCY OUTDOOR AIR OVERRIDE SWITCH ON THE MAIN GRAPHIC AT THE OPERATOR WORKSTATION WHICH WILL ALLOW THE OPERATOR TO SHUTDOWNTHE OUTSIDE AIR INTAKE DAMPERS AND RELIEF DAMPERS FOR ALL AIR HANDLING UNITS IN THE EVENT THAT TOXIC ODORS ARE DETECTED OUTSIDE. WHEN THE OUTSIDE AIR ANDRELIEF DAMPERS FULLY CLOSE, THE RETURN AIR DAMPER SHALL FULLY OPEN. THE OUTSIDE AIR INTAKE DAMPERS FOR ALL UNITS SHALL REMAIN CLOSED UNTIL THE OPERATORRESETS THE OVERRIDE

PACKAGED ROOFTOP AIR HANDLING UNIT

GENERALTHE AIR HANDLING UNIT SHALL BE FURNISHED WITH A COMPLETE FACTORY PACKAGED DDC CONTROL SYSTEM. THE FMS SHALL INTEGRATE THE AIR HANDLING UNIT CONTROLS INTOTHE FMS USING AN OPEN PROTOCOL COMMUNICATION NETWORK CONNECTION BETWEEN THE TWO SYSTEMS. THE FOLLOWING SEQUENCE OF OPERATIONS SHALL BE USED AS ADESIGN BASIS GUIDELINE FOR CONTROL OF THE UNIT HOWEVER THE EXACT SEQUENCE OF OPERATIONS SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S STANDARD FACTORYSEQUENCE OF CONTROL FOR THE SPECIFIED UNIT. REFER TO THE AIR HANDLING UNIT MANUFACTURER'S SUBMITTAL AND O&M MANUAL FOR EXACT SEQUENCE DETAILS.

MIXED AIR DAMPER CONTROLTHE AIR HANDLING UNIT CONTROL SYSTEM SHALL MODULATE THE MIXED AIR DAMPERS TO MAINTAIN THE SUPPLY AIR TEMPERATURE AT SET POINT. WHENEVER THE OUTSIDE AIRTEMPERATURE IS GREATER THAN THE RETURN AIR TEMPERATURE AND MECHANICAL COOLING IS REQUIRED, THE MIXED AIR DAMPERS SHALL BE IN THEIR NORMAL POSITION (FULLRETURN AIR WITH MINIMUM OUTSIDE AIR). WHEN THE AIR HANDLING UNIT IS STOPPED, THE CONTROL SYSTEM SHALL CLOSE ALL OUTSIDE AIR DAMPERS AND THE RELIEF DAMPER ANDOPEN THE RETURN AIR DAMPER.

MINIMUM OUTSIDE AIR CONTROLTHE MINIMUM OUTSIDE AIR VOLUME SHALL BE CONTROLLED BY THE AIR HANDLING UNIT CONTROL SYSTEM THROUGH THE MINIMUM OUTSIDE AIR DAMPER POSITION SETPOINT. THECONTROL SYSTEM SHALL NOT MODULATE THE OUTSIDE AIR DAMPER BELOW MINIMUM OUTSIDE AIR DAMPER POSITION SETPOINT. IF THE AIR HANDLING UNIT IS STOPPED, THECONTROL SYSTEM SHALL CLOSE THE DAMPER.

TEMPERATURE CONTROLTHE AIR HANDLING UNIT CONTROL SYSTEM SHALL MODULATE THE GAS FIRED FURNACE AND STAGE THE CONDENSING UNIT TO MAINTAIN THE SPACE TEMPERATURE SETPOINT. THEFMS SHALL PREVENT SIMULTANEOUS HEATING AND COOLING. THE COOLING SETPOINTS SHALL BE 76 °F (ADJUSTABLE) FOR OCCUPIED PERIODS AND 85°F (ADJUSTABLE) DURINGUNOCCUPIED PERIODS. THE HEATING SETPOINTS SHALL BE 72°F (ADJUSTABLE) FOR OCCUPIED PERIODS AND 55°F (A DJUSTABLE) FOR UNOCCUPIED PERIODS.

SUPPLY FAN CONTROLTHE SUPPLY FAN SHALL BE STARTED AND STOPPED BY THE FMS SYSTEM BASED ON AN OCCUPANCY SCHEDULE FOR THE SPACE PROGRAMMED INTO THE FMS. THE FAN SHALLOPERATE CONTINUOUSLY DURING OCCUPIED PERIODS. IF DURING UNOCCUPIED PERIODS, THE SPACE TEMPERATURE RISES ABOVE THE UNOCCUPIED COOLING SETPOINT OR FALLSBELOW THE UNOCCUPIED HEATING SETPOINT, THE AIR HANDLING UNIT SHALL START AND OPERATE TO CHANGE THE SPACE TEMPERATURE 2°F (ADJUSTABLE) BEFORE STOPPING. I FDURING UNOCCUPIED PERIODS, THE SPACE OCCUPANCY SWITCH IS ACTIVATED, THE AIR HANDLING UNIT SHALL START AND OPERATE FOR A PERIOD OF TWO HOURS BEFORE STOPPING.

SUPPLY FAN MONITORINGTHE FAN OPERATION SHALL BE INDICATED TO THE AIR HANDLING UNIT CONTROL SYSTEM THROUGH A CURRENT SWITCH OR OTHER FLOW INDICATOR. IF AN ALARM CONDITION ISDETECTED, THE FMS SHALL INITIATE AN ALARM.

SMOKE DETECTORSA SMOKE DETECTOR LOCATED IN THE SUPPLY AIR STREAM, SHALL STOP THE FAN THROUGH THE FIRE ALARM SYSTEM IF AN ALARM CONDITION IS DETECTED. WHEN THE FAN ISSTOPPED, THE AIR HANDLING UNIT CONTROL SYSTEM SHALL POSITION THE DAMPERS TO THEIR NORMAL STATE.

START/STOP OPTIMIZATION AND MORNING WARM-UPTHE FMS SHALL BE PROGRAMMED WITH A SELF-ADJUSTING START/STOP OPTIMIZATION SEQUENCE WHICH SHALL PROVIDE THE OPTIMUM START TIME FOR THE UNIT IN ORDER TO HAVETHE SPACE TEMPERATURE AT THE OCCUPIED SETPOINT WHEN SCHEDULED OCCUPANCY IS TO OCCUR EACH DAY. IF THE SPACE REQUIRES HEATING TO REACH THE OCCUPIED SPACETEMPERATURE SETPOINT, THE FMS SHALL OPERATE THE UNIT USING A MORNING WARM-UP CYCLE. DURING THE MORNING WARM-UP CYCLE, THE UNIT SHALL OPERATE WITH THEOUTSIDE AIR AND RELIEF AIR DAMPER CLOSED WITH THE RETURN AIR DAMPER FULLY OPEN. THE UNIT SHALL OPERATE THE FURNACE TO MAINTAIN THE SPACE TEMPERATURE ATSETPOINT. ONCE THE SPACE TEMPERATURE OCCUPIED SETPOINT IS REACHED, THE UNIT SHALL RETURN TO NORMAL OCCUPIED CONTROL.

GENERAL EXHAUST FANS

EACH FAN SHALL OPERATE BASED ON THE OCCUPANCY SCHEDULE IN THE FMS. THE FAN SHALL OPERATE CONTINUOUSLY DURING OCCUPIED PERIODS. THE FAN OPERATION SHALL BEINDICATED TO THE FMS THROUGH A CURRENT SWITCH INSTALLED IN THE MOTOR STARTER. IF A FAN FAILURE IS DETECTED, THE FMS SHALL STOP THE FAN AND INITIATE AN ALARM.

TYPICAL SPLIT SYSTEM

EACH UNIT SHALL BE PROVIDED WITH A FACTORY PACKAGED CONTROL SYSTEM WHICH SHALL CONTROL THE UNIT TO MAINTAIN THE SPACE TEMPERATURE AT SETPOINT. THE FMSSHALL MONITOR THE SPACE TEMPERATURE THROUGH A SEPARATE SPACE TEMPERATURE SENSOR AND SHALL INITIATE AN ALARM IF THE SPACE TEMPERATURE RISES ABOVE THESPACE HIGH TEMPERATURE ALARM SETPOINT.

KITCHEN MAKE-UP AIR SYSTEM

MAKE-UP AIR UNIT CONTROLTHE MAKE-UP AIR SYSTEM SHALL BE CONTROLLED THROUGH THE FACTORY PACKAGED CONTROL SYSTEM TO MAINTAIN THE SUPPLY AIR TEMPERATURE AT SETPOINT ANYTIME THEUNIT IS OPERATING. THE FMS SHALL MONITOR THE SUPPLY AIR TEMPERATURE IN THE UNIT AND SHALL INITIATE AN ALARM IF THE SUPPLY AIR TEMPERATURE FALLS BELOW 40°F(ADJUSTABLE). THE OPERATION OF THE KITCHEN HOOD MAKE-UP AIR UNIT WILL BE INTERLOCKED WITH THE OPERATION OF THE KITCHEN HOOD EXHAUST FAN(S) AND FIRESUPPRESSION SYSTEM. UNDER NORMAL OPERATING CONDITIONS- THE MAKEUP AIR UNIT SHALL BE STARTED WITH A SINGLE FAN ON/OFF SWITCH. THE MAKEUP AIR UNIT ANDASSOCIATED KITCHEN HOOD EXHAUST FAN WILL OPERATE TOGETHER.

FIRE SUPPRESSION SYSTEMIF THE HOOD FIRE SUPPRESSION SYSTEM ENTERS A FIRE CONDITION, THE MAKE UP AIR UNIT FAN SHALL BE DE-ENERGIZED. THE HOOD EXHAUST FAN SHALL CONTINUE TO OPERATE (ORSTART OPERATION) UNDER THIS CONDITION. ADDITIONALLY, AN ELECTRICAL SHUNT TRIP CIRCUIT BREAKER AND GAS SOLENOID VALVE SERVING ALL APPLIANCES BELOW THE HOODSHALL DE-ENERGIZED REMOVING POWER AND GAS SERVICE TO THE APPLIANCES.

TYPICAL EXHAUST FAN CONTROL DIAGRAM

TYPICAL SPLIT SYSTEM CONTROL DIAGRAM

SHEET KEYED NOTES1. THE PACKAGED ROOFTOP UNITS SHALL BE CONNECTED TO

THE FMS NETWORK THROUGH A BACNET NETWORKCONNECTION AS INDICATED. THE CONTRACTOR SHALLCOORDINATE WITH THE UNIT MANUFACTURER AND SUBMIT APROPOSED LIST OF POINTS FOR REVIEW AND APPROVAL PRIORTO INSTALLATION. THE FOLLOWING POINTS SHALL BEINTEGRATED INTO AND MONITORED BY THE FMS IF AVAILABLEIN THE UNIT CONTROLLER.

A. SYSTEM SETPOINTSB. SYSTEM DIAGNOSTICSC. SYSTEM SENSOR INPUTSD. SUPPLY FAN MODE STATUSE. SUPPLY FAN STATUSF. UNIT HEAT/COOL MODEG. ZONE TEMPERATUREH. ECONOMIZER POSITIONI. MINIMUM OUTSIDE AIR DAMPER POSITIONJ. ECONOMIZER SETPOINTK. ON/OFF STATUS OF COMPRESSORSL. HEATING OUTPUTM. REFRIGERANT EVAPORATOR TEMPERATUREN. SATURATED CONDENSER TEMPERATUREO. OUTSIDE AIR TEMPERATUREP. RETURN AIR TEMPERATUREQ. SUPPLY AIR TEMPERATURE

THE FOLLOWING POINTS SHALL BE INTEGRATED INTO ANDCONTROLLED BY THE FMS:

A. COOLING SETPOINTB. HEATING SETPOINTC. ZONE TEMPERATURE SETPOINTD. ZONE VALUESE. ECONOMIZER ENABLE/DISABLEF. ECONOMIZER SETPOINTG. ECONOMIZER MINIMUM POSITIONH. DIAGNOSTICS RESETI. UNIT PRIORITY SHUTDOWNJ. SUPPLY FAN MODEK. OCCUPANCY

TYPICAL PACKAGED ROOFTOP CAV AIR HANDLING UNIT CONTROL DIAGRAM

SEQUENCE OF OPERATIONS TFOE

C

I N

EI

L D

ESN

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

ABBAS SHIRIAN

102840

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 11

:24:

29 A

M

MI601a

MECHANICALDIAGRAMS(CONTROLS)

RLM

Page 6: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

TFOE

C

I N

EI

L D

ESN

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

ABBAS SHIRIAN

102840

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 11

:24:

24 A

M

M701a

MECHANICALSCHEDULES

RLM

AG BLDG - PACKAGED ROOFTOP UNIT (DX/GAS)

SYMBOL MANUFACTURER MODEL NO. GROSSTONS OA CFM TYPE

SUPPLY FAN DX COOLING HEATING DATA (GAS HEAT)APPROXIMATE

OPERATINGWEIGHT (LBS.)

ELECTRICAL

NOTESSA CFM BHP HP ESP

(WG)AIR

FLOWOD

AMB.

ENT. AIR LVG. AIR TOTAL

CAP. (MBH)SEN CAP.

(MBH) SEERAIR DATA GAS CAPACITY

V PH HZ MCA MOCPDB WB DB WB AIR

FLOWEAT(F)

LAT(F)

HEATING S/LINPUT (MBH)

HEATING SITEOUTPUT (MBH)

AG-RTU-01 TRANE YHC067 5.0 785 FC 2,000 0.58 1.0 0.5 2,000 100 84 63 61 54 56.0 47.0 17.2 2,000 48.0 78.0 80 55 1150 460 3 60 15.2 20.0

FURNISH W/ 16" TALL ROOF CURB, HAIL GUARDS,ECONOMIZER, BAORMETRIC RELIEF, FACTORY MOUNTEDFUSED DISCONNECT, NON-POWERED CONVIENCEOUTLET

AG BLDG - EXHAUST FANS

SYMBOL MANUFACTURER & MODEL NO. AREA SERVED TYPE CFM S.P.(IN. WC)

FANRPM BHP

MOTOR DATA OPERATINGWEIGHT (LBS.) DAMPER NOTES

HP VOLT PHASE HZ FLAAG-EF-01 GREENHECK - SQ-99-VG BOYS109-GIRLS110 DIRECT DRIVE INLINE FAN 720 0.5 1,656 0.21 1/4 115 1 60 3.7 50 BACKDRAFT ELEC DISCONNECT

AG-EF-02 GREENHECK - SBE-3H30-3 SHOP 105 SIDE WALL BELT DRIVE FAN 4,300 0.2 628 0.29 1/3 115 1 60 7.2 90 NONEGALVANIZED STEEL DRIVE FRAME ASSEMBLY,STATIC RESISTANT BELTS - CORROSION RESISTANT FASTENERS,ELEC DISCONNECT, NEMA 1, TOGGLE SWITCH

AG-EF-03 GREENHECK - SBE-3H30-3 SHOP 105 SIDE WALL BELT DRIVE FAN 4,300 0.2 628 0.29 1/3 115 1 60 7.2 90 NONEGALVANIZED STEEL DRIVE FRAME ASSEMBLY,STATIC RESISTANT BELTS - CORROSION RESISTANT FASTENERS,ELEC DISCONNECT, NEMA 1, TOGGLE SWITCH

AG-EF-04 GREENHECK - SBE-3H30-3 SHOP 105 SIDE WALL BELT DRIVE FAN 4,300 0.2 628 0.29 1/3 115 1 60 7.2 90 NONEGALVANIZED STEEL DRIVE FRAME ASSEMBLY,STATIC RESISTANT BELTS - CORROSION RESISTANT FASTENERS,ELEC DISCONNECT, NEMA 1, TOGGLE SWITCH

AG-EF-05 GREENHECK - SBE-3H30-3 SHOP 105 SIDE WALL BELT DRIVE FAN 4,300 0.2 628 0.29 1/3 115 1 60 7.2 90 NONE GALVANIZED STEEL DRIVE FRAME ASSEMBLY,STATIC RESISTANT BELTS - CORROSION RESISTANT FASTENERS,ELEC DISCONNECT, NEMA 1, TOGGLE SWITCH

AG BLDG - GAS FIRED UNIT HEATER

SYMBOLMANUFACTURER

& MODEL NO. LOCATION

SEELLEVEL MIN

INPUT(MBH)

SEEL LEVEL MINOUTPUT(MBH)

AIR FLOWCFM

ELECTRICAL DATA

WEIGHT(LBS.) NOTESVOLT PHASE HZ MOTOR HP MOTOR RPM

AG-UH-01 TRANE GTND003 TOOL RM-106 30 21 370 115 1 60 1/20 1,650 70 UNIT MOUNTED 24 VOLT THERMOSTAT, ELEC. INTERMITTENT,SPARK IGNITION, ALUMINUM HT EXHCHANGER, 4" DIA. TYPE B VENT, 1/2" GAS CONN.

AG BLDG - RADAINT TUBE HEATER

SYMBOL MANUFACTURER &MODEL NO.

AREASERVED

SEE LEVEL MININPUT (MBH)

SEE LEVEL MINOUTPUT (MBH)

ELEC TUBEDIAMETER

(in)

TOTAL TUBELENGTH (FT)

MOUNTINGHEIGHT (FT) NOTE

VOLT PH HZ FLAAMPS

AG-RH-01 SPACE RAY - LTU125 SHOP -105 125 105 115 1 60 2.6 4 30 14 THERMOSTAT, ELEC. DIRECT SPARK IGNITION, TWO STAGE GAS VALVE, 4" DIA. TYPE B VENT WITH BRIEDERT TYPE L CAP, HORIZONTAL DUCTED COMBUSTION AIR WITH LESLIE VERSACAP,1/2" GAS CONN., 3 FT STAINLESS STEEL FLEXIBLE GAS LINE

AG-RH-02 SPACE RAY - LTU125 SHOP -105 125 105 115 1 60 2.6 4 30 14 THERMOSTAT, ELEC. DIRECT SPARK IGNITION, TWO STAGE GAS VALVE, 4" DIA. TYPE B VENT WITH BRIEDERT TYPE L CAP, HORIZONTAL DUCTED COMBUSTION AIR WITH LESLIE VERSACAP,1/2" GAS CONN., 3 FT STAINLESS STEEL FLEXIBLE GAS LINE

AG-RH-02 SPACE RAY - LTU125 SHOP -105 125 105 115 1 60 2.6 4 30 14 THERMOSTAT, ELEC. DIRECT SPARK IGNITION, TWO STAGE GAS VALVE, 4" DIA. TYPE B VENT WITH BRIEDERT TYPE L CAP, HORIZONTAL DUCTED COMBUSTION AIR WITH LESLIE VERSACAP,1/2" GAS CONN., 3 FT STAINLESS STEEL FLEXIBLE GAS LINE

AG-RH-04 SPACE RAY - LTU125 SHOP -105 125 105 115 1 60 2.6 4 30 14 THERMOSTAT, ELEC. DIRECT SPARK IGNITION, TWO STAGE GAS VALVE, 4" DIA. TYPE B VENT WITH BRIEDERT TYPE L CAP, HORIZONTAL DUCTED COMBUSTION AIR WITH LESLIE VERSACAP,1/2" GAS CONN., 3 FT STAINLESS STEEL FLEXIBLE GAS LINE

AG-RH-05 SPACE RAY - LTU125 SHOP -105 125 105 115 1 60 2.6 4 30 14 THERMOSTAT, ELEC. DIRECT SPARK IGNITION, TWO STAGE GAS VALVE, 4" DIA. TYPE B VENT WITH BRIEDERT TYPE L CAP, HORIZONTAL DUCTED COMBUSTION AIR WITH LESLIE VERSACAP,1/2" GAS CONN., 3 FT STAINLESS STEEL FLEXIBLE GAS LINE

AG-RH-06 SPACE RAY - LTU125 SHOP -105 125 105 115 1 60 2.6 4 30 14 THERMOSTAT, ELEC. DIRECT SPARK IGNITION, TWO STAGE GAS VALVE, 4" DIA. TYPE B VENT WITH BRIEDERT TYPE L CAP, HORIZONTAL DUCTED COMBUSTION AIR WITH LESLIE VERSACAP,1/2" GAS CONN., 3 FT STAINLESS STEEL FLEXIBLE GAS LINE

AG-RH-07 SPACE RAY - LTU125 SHOP -105 125 105 115 1 60 2.6 4 30 14 THERMOSTAT, ELEC. DIRECT SPARK IGNITION, TWO STAGE GAS VALVE, 4" DIA. TYPE B VENT WITH BRIEDERT TYPE L CAP, HORIZONTAL DUCTED COMBUSTION AIR WITH LESLIE VERSACAP,1/2" GAS CONN., 3 FT STAINLESS STEEL FLEXIBLE GAS LINE

AG-RH-08 SPACE RAY - LTU125 SHOP -105 125 105 115 1 60 2.6 4 30 14 THERMOSTAT, ELEC. DIRECT SPARK IGNITION, TWO STAGE GAS VALVE, 4" DIA. TYPE B VENT WITH BRIEDERT TYPE L CAP, HORIZONTAL DUCTED COMBUSTION AIR WITH LESLIE VERSACAP,1/2" GAS CONN., 3 FT STAINLESS STEEL FLEXIBLE GAS LINE

AG BLDG - MOTORIZED DAMPER

SYMBOLMANUFACTURER &

MODEL NO. LOCATION W (IN) IN (IN)PRESSURE

DROP (IN.WG) DRIVE ARP. ACTUATOR ACT QTY. ACT TYPEAG-MD-01 GREENHECK VCD-23 SHOP 105 192 24 0.004 DRIVE-CC-41-2FIL-2 MS4120F1006 2 120VAC - SPRING RETURN

AG BLDG - SPLIT SYSTEM INDOOR UNITS

SYMBOL MANUFACTURER MODEL NO. NOMINALTON

AREASERVED

AIR FLOWCFM

COOLING HEATING PIPING SIZE ELEC PHSYSICAL DIMENSIONSNOTESOUTSIDE

TEMPINDOOR DB

TEMPINDOOR WB

TEMPTOTALBTUH

SENSIBLEBTUH

OUTSIDETEMP

INDOORDB TEMP

TOTALBTUH

RSDIA

RLDIA

DRAINDIA V/PH/HZ PWOER

CONSUMPTIONWEIGHT

(LB)WIDTH

(IN)LENGTH

(IN)HEIGHT

(IN)

AG-FC-01 MITSUBISHI PKA-A18HA4 1.5 ELEC-107 425 104 F 80 F 67 F 18,000 12,200 17 F 59 F 19,000 1/2" 1/4" 5/8" 115/1/60 FROM AG-CU-01 29 36 10 12FURNISH W/ WIRED 7-DAY PROG T'STAT,CONDENSATE PUMP - SAUERMANNMODEL SI3100, CONNECT TO AG-CU-01, R-410A REFRIGERANT, ELECDISCONNECT BY DIV 26

AG BLDG - SPLIT SYSTEM OUTDOOR UNITS

SYMBOL MANUFACTURER MODEL NO. NOMINALTON

COOLING HEATING ELEC PHYSICAL DIMENSION PIPE SIZESNOTESOUTDOOR

TEMPTOTALBTUH

OUTDOORTEMP

TOTALBTUH V/PH/HZ MCA MOP WEIGHT

(LB)WIDTH

(IN)LENGTH

(IN)HIGHT(I

N)RSDIA

RLDIA

AG-CU-01 MITSUBISHI PUZ-A18NHA4 1.5 104 F 18,000 17 F 19,000 115/1/60 13 15 90 32 12 24 1/2" 1/4" FURNISH W/ LO AMBIENT KIT (HEATING TO 5°F AMBIENT) AND WIND BAFFLE BAFFL E, INTERLOCK W/ AG-FC-01

ALL SELECTIONS BASEDON 3,600 FT ELEVATION.

Page 7: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

R

EX

A

X

3

a

WALL

CEILING

WALL

CEILING

OS

OS

208Y/120VT1A

75kVA

K-4

E4E3

A

DRAWING NUMBER WHERE TAKEN

DRAWING NUMBER WHERE DETAILED

SECTION/ELEVATION LETTER OR DETAIL NUMBER

A

E4

6

E4

+44"

DRAWING NUMBER WHERE DETAILED

SECTION/ELEVATION LETTER OR DETAIL NUMBER

VAV-9

(NOT ALL SYMBOLS APPLY TO THIS PROJECT)

NORTH ARROW OR MATCH ARCHITECT'S

SCALE BAR OR MATCH ARCHITECT'S

SURFACE

WALL

CEILING

+44"

UON

ONE-LINE DIAGRAM

SPD

3000/5

CIRCUIT BREAKER; TRIP SETTING/FRAME SIZE OR NO. OF

POLES. SETTINGS AND PROTECTION AS NOTED ON PLANS

DRAWOUT CIRCUIT BREAKER

MEDIUM VOLTAGE DRAWOUT CIRCUIT

BREAKER

POTENTIAL TRANSFORMER.

DISCONNECT SWITCH. "300A"

DENOTES AMPERAGE RATING

FUSE. "300A" DENOTES AMPERAGE

RATING

GROUND CONNECTION

TRANSFER SWITCH. SEE PLANS

FOR TYPE OF SWITCH

SURGE ARRESTOR

SURGE PROTECTIVE DEVICE

KILOWATT METER

ELECTRONIC METER

KIRK KEY INTERLOCK No.1

RELAY No.1

AMMETER SWITCH

AMMETER

VOLTMETER SWITCH

VOLTMETER

DELTA CONNECTED

WYE CONNECTED

LIGHTING

RECESSED MOUNTED LUMINAIRE. SMALL CASE "a"

DENOTES SWITCHING, NUMBER "3" DENOTES BRANCH

CIRCUITING. SYMBOL "A" DENOTES LUMINAIRE TYPE

WALL MOUNTED LUMINAIRES

STRIP LUMINAIRE

LINEAR DIRECT/INDIRECT LUMINAIRE. CABLE

OR STEM MOUNTED

DOWN LIGHT LUMINAIRE; CEILING MOUNTED

EXIT LUMINAIRE. SHADED SIDE INDICATES

FACE SIDE. PROVIDE DIRECTIONAL ARROW(S)

AS INDICATED ON PLANS

EMERGENCY BATTERY PACK LUMINAIRE

(BUG-EYE/FROG-EYE)

DOUBLE HEAD, POLE MOUNTED LUMINAIRE

TRACK MOUNTED LUMINAIRES

SURFACE

AS

DETAILED

CEILING

EXTERIOR

WALL

DEMOLITION

DASHED SYMBOL INDICATES EXISTING DEVICE OR

EQUIPMENT TO BE REMOVED

SOLID SYMBOL, LIGHTER IN COLOR INDICATES EXISTING

DEVICE OR EQUIPMENT TO REMAIN

EXISTING CONDUIT TO BE REUSED

REMOVE EXISTING RACEWAY IN ALL ACCESSIBLE AREAS.

CAPPED AND ABANDONED IF IN UNACCESSIBLE AREA

SYMBOL DEFINITION

REFERENCE TAGS

KEYED NOTE REFERENCE

MECHANICAL EQUIPMENT REFERENCE

DENOTES MOUNTING HEIGHT AFF

KITCHEN EQUIPMENT REFERENCE

MEDICAL EQUIPMENT REFERENCE

GENERAL DRAWING SYMBOLS

TRIP SETTING

FRAME SIZE

300

400

VARIES

RE

FE

R T

O L

IGH

TIN

G S

CH

ED

ULE

EMERGENCY, CRITICALEC

EMERGENCY, LIFE SAFETYEL

EMERGENCY, EQUIPMENTEQ

TELEVISIONTV

EXISTINGEX

GROUND FAULT PROTECTIONGFP

SWITCHSW

FEEDERFDR

UNDERGROUND ELECTRICUGE

MANHOLEMH

MIXED MEDIAMM

UNDERGROUNDU/G

POWER MONITORING AND CONTROL SYSTEMPMCS

AUTOMATIC TRANSFER SWITCH CONTROLATSC

TEMPORARYTEMP

SECURITYSEC

DEFINITIONABBREV.

ABBREVIATIONS

A

ADA

AFF

AFG

AWG

ANSI

AIC

C

CCTV

CLF

CO

GFI

GND

HOA

G OR GFCI

FACP

AMPS, AMPERE, AMPERAGE

ABOVE FINISHED GRADE

ABOVE FINISHED FLOOR

AMERICANS WITH DISABILITIES ACT

AVAILABLE INTERRUPTING CURRENT

AMERICAN NATIONAL STANDARDS INSTITUTE

GROUND FAULT CIRCUIT INTERRUPTER

HAND-OFF-AUTOMATIC.

GROUND.

GROUND FAULT INTERRUPTER

CURRENT LIMITING FUSE

AMERICAN WIRE GAUGE

CLOSED CIRCUIT TELEVISION

FIRE ALARM CONTROL PANEL

CONDUIT ONLY

CONDUIT

HP

IEEE

KV

KVA

KW

KWH

MVA

MCC

NEC

NEMA

NIC

NFPA

NM

P

PA

PC

NC

POLE

KILOVOLT AMPS

NATIONAL FIRE PROTECTION ASSOCIATION

PHOTOCELL

PUBLIC ADDRESS

NEW MEXICO

NOT IN CONTRACT

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURERS

MOTOR CONTROL CENTER

MEGAVOLT AMPS

NORMALLY CLOSED

KILOWATT HOUR.

KILOWATT

HORSEPOWER

KILOVOLT

TVSS

UPS

UON

V

VFD

XFER

XFMR (TRANSF)

VARIABLE FREQUENCY DRIVE

UNINTERRUPTABLE POWER SUPPLY

TRANSIENT VOLTAGE SURGE SUPPRESSER

TRANSFORMER

TRANSFER

UNLESS OTHERWISE NOTED

VOLTS, VOLTAGE

TTB TELEPHONE TERMINAL BOARD

INSTITUTE OF ELECTRICAL AND ELECTRONICS

CEILING MOUNTED OCCUPANCY SENSOR; TYPE AS

INDICATED ON PLANS

GENERATOR

a =

2 =

3 =

4 =

P =

M =

K =

WP =

T =

D =

AC ABOVE COUNTER

AL ALUMINUM

ATS AUTOMATIC TRANSFER SWITCH

CKT CIRCUIT

CU COPPER

DL DAY-LIGHTING

DIA DIAMETER

FA FIRE ALARM

KCMIL THOUSAND CIRCULAR MILS

MAX MAXIMUM

MIN MINIMUM

NEUT NEUTRAL

PH PHASE

RSC RIGID STEEL CONDUIT

UC UNDER COUNTER

WP WEATHERPROOF

WALL MOUNTED OCCUPANCY SENSOR; TYPE

AS INDICATED ON PLANS

HATCHING INDICATES EMERGENCY LIGHTING.

HATCH WILL BE MODIFIED FOR EACH

LUMINAIRE TYPE. EMERGENCY LUMINAIRE

DESIGNATED WITH "E" IN TYPE DESIGNATION.

VARIES

SURFACE MOUNTED LUMINAIRE.

LUMINAIRE TYPE AS INDICATED ON PLANS

FIRE ALARM

REFER TO

DEMOLITION PLANS

FOR ADDITIONAL

INFORMATION

FUT FUTURE

LSIG LONG TIME, SHORT TIME, INSTANTANEOUS,

N NEW

W WALL MOUNTED

NL NORMAL

MTS MANUAL TRANSFER SWITCH

UL UNDERWRITERS' LABORATORIES

EMERGENCYE

IG ISOLATED GROUND

KVAR KILOVOLT AMPS REACTIVE

NO NORMALLY OPEN

SURGE PROTECTIVE DEVICESPD

REFER TO LUMINAIRE SCHEDULE FOR ALL LUMINAIRE TYPES WHETHER WALL MOUNTED OR CEILING

MOUNTED.

GROUND FAULT PROTECTION

SHUNT TRIP OPERATORTYP. TYPICAL

300

400

TRIP SETTING

FRAME SIZE

300A

300A

N/A NOT APPLICABLE

O/H OVERHEAD

GEN GENERATOR

ENGINE GENERATOREG

SYMBOL DESCRIPTIONMOUNTING

HT.LOC.

SINGLE HEAD, POLE MOUNTED LUMINAIRE

MOUNTINGHT.LOC.

DOUBLE FACE EXIT LUMINAIRE. SHADED SIDE

INDICATES FACE SIDE. PROVIDE DIRECTIONAL

ARROW(S) AS INDICATED ON PLANS

SYMBOL DESCRIPTION

SYMBOL DESCRIPTION NOTES

ASSOCIATION

AND GROUND FAULT PROTECTION

ENGINEERS

300

400

NORTH

ELECTRICAL SYMBOL LEGEND

E3 E4

6

TRANSFORMER. TRANSFORMER NAME, TRANSFORMER kVA

RATING, PRIMARY VOLTAGE AND WIRING CONFIGURATION,

SECONDARY VOLTAGE, K RATING (IF APPLICABLE)

G

ST

0 10' 20' 40' 80'

1" = 40'-0"

DEVICE INDICATOR LETTER. "X" EQUALS DESIGNATION

BELOW

(TYPICAL FOR MOST SWITCH TYPES):

SMALL CASE LETTER DENOTES SWITCHING

CONTROL

DOUBLE POLE TOGGLE SWITCH

THREE-WAY TOGGLE SWITCH

FOUR-WAY TOGGLE SWITCH

PILOT LIGHT TOGGLE SWITCH

MOMENTARY CONTACT SWITCH

KEY OPERATED SWITCH

WEATHERPROOF TOGGLE SWITCH

MANUAL MOTOR STARTER SWITCH WITH THERMAL

OVERLOAD PROTECTION

DIMMER SWITCH

FACP

FAA

F

F

S

C

B

P

I

R/F

F

R

U

PS

TS

FS

PIV

M

R

MM

R

FIRE ALARM CONTROL PANEL

-WALL

+44"WALL

+80"

UONWALL

CEILING

UNDER

FLOOR

SEE

PLANS

AT DUCT

VARIESPIPE

SEE

PLANSVARIES

SEE

PLANS

FIRE ALARM ANNUNCIATOR PANEL

PULL STATION

FIREMAN'S TELEPHONE OUTLET

HORN NOTIFICATION

SPEAKER NOTIFICATION

CHIME NOTIFICATION

COMBINATION SPEAKER AND CHIME NOTIFICATION

SPEAKER/HORN WITH STROBE LIGHT

STROBE LIGHT ONLY

BELL (GONG)

PHOTOELECTRIC SMOKE DETECTOR

IONIZATION SMOKE DETECTOR

COMBINATION RATE OF RISE / FIXED TEMPERATURE

FIXED TEMERATURE; TEMPERATURE AS NOTED

ON PLANS OR SPECIFICATIONS

RATE OF RISE ONLY

UNDER FLOOR SMOKE DETECTOR

DUCT DETECTOR

FIRE/SMOKE DAMPER

PRESSURE SWITCH

TAMPER SWITCH

FLOW SWITCH

POST INDICATOR VALVE

MAGNETIC DOOR HOLDER

CONTROL RELAY

MONITOR MODULE

REMOTE ALARM INDICATING LIGHT

ADDRESSABLE/SUPERVISED RELAY

KW

M

K1

R1

AS

A

VS

V

VFD CONNECTION

MOTOR CONNECTION

UPS

5

VFD

J

T

5

30/3R

0/1

1/30/3R

F

30/1

30/3R

DEVICES

CODE SIZE JUNCTION BOX

WALL MOUNTED CODE SIZE J-BOX

CODE SIZE PULLBOX (OR AS SIZED ON PLAN)

ENCLOSED CIRCUIT BREAKER.

AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE

UON

NON-FUSED DISCONNECT SWITCH.

AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE

UON

FUSED DISCONNECT SWITCH.

AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE

UON

MOTOR STARTER. STARTER SIZE INDICATED

BY NUMBER/NEMA ENCLOSURE RATING,

SINGLE SPEED UON

COMBINATION FUSIBLE DISCONNECT SWITCH

AND MOTOR STARTER. NEMA STARTER

SIZE/AMPERAGE/NEMA ENCLOSURE RATING, 3

POLE UON

MOTOR. NUMBER INDICATES HORSEPOWER

RATING FOR 1HP AND LARGER

THERMOSTAT

PHOTOCELL

LIGHTNING PROTECTION AIR TERMINAL

PUSHBUTTON (EMERGENCY POWER OFF - EPO)

SYMBOL DESCRIPTIONMOUNTING

+44"

UON

N/A

VARIES

HT.LOC.

WALL

ROOF

VARIES

N/A

VARIES

MULTI-OULET ASSEMBLY (SURFACE MOUNTED

RACEWAY) VARIES

SEE

PLANS

VARIES

SEE

PLANS

MOTOR. "F" INDICATES FRACTIONAL

HORSEPOWER

VARIES

SEE

PLANS

VARIES

SEE

PLANS

VARIES

DEVICE INDICATOR LETTER. "X" EQUALS DESIGNATION BELOW

(TYPICAL FOR MOST RECEPTACLE TYPES):

BLANK FOR NORMAL POWERG = GFCI RATED

IG = ISOLATED GROUND

T = TAMPERPROOF

WG = WEATHERPROOF AND GFCI

WP = WEATHERPROOF (IN-USE COVER)

CL = CLOCK

TV = TELEVISION

+18",

UON

FLUSH

IN FLOOR DUPLEX RECEPTACLE.

CONFIGURATION AS INDICATED ON PLANS

IN FLOOR DOUBLE DUPLEX (QUADPLEX) RECEPTACLE.

CONFIGURATION AS INDICATED ON PLANS

CEILING MOUNTED DUPLEX RECEPTACLE

CEILING MOUNTED DOUBLE DUPLEX

(QUADPLEX) RECEPTACLE

SIMPLEX RECEPTACLE

DUPLEX RECEPTACLE

DOUBLE DUPLEX (QUADPLEX) RECEPTACLE

EMERGENCY DOUBLE DUPLEX (QUADPLEX)

RECEPTACLE

SPECIAL PURPOSE RECEPTACLE. NEMA

CONFIGURATION AND AMPERAGE AS NOTED ON

PLANS

COMBINATION POWER/COMMUNICATION POLE.

CONFIGURATION AS NOTED ON PLANS

FLOOR

CEILING

WALL,

UON

IN FLOOR EMERGENCY DUPLEX RECEPTACLE.

CONFIGURATION AS INDICATED ON PLANS

CEILING MOUNTED EMERGENCY DUPLEX RECEPTACLE

EMERGENCY DUPLEX RECEPTACLE

COMBINATION POWER/COMMUNICATION IN

CEILING OUTLET. CONFIGURATION AS

INDICATED ON PLANS

COMBINATION DUPLEX RECEPTACLE AND

COMMUNICATIONS FLOORBOX. DEVICE

CONFIGURATION AS INDICATED ON PLANS.

X

X

X

X

X

X

X

X

X

X

X

X

X

X

J

P

IN FLOOR EMERGENCY DOUBLE DUPLEX

(QUADPLEX) RECEPTACLE. CONFIGURATION AS INDICATED ON

PLANS

X

A, B, C, = SEQUENCE OF PANELS OF THIS TYPE

1, 2, 3, . . = SUBFED PANEL

1, 2, 3, . . = FLOOR LEVEL

HL

T

BLANK FOR NORMAL POWER

ELECEQ

= EMERGENCY-LIFE SAFETY-BRANCH= EMERGENCY-CRITICAL-BRANCH= EMERGENCY-EQUIPMENT-BRANCH

GROUND BAR

MAIN SWITCHBOARD. DASHED LINES INDICATE CLEARANCES.

VARIABLE FREQUENCY DRIVE

SYMBOL

EQUIPMENTDESCRIPTION

EQUIPMENT NAMING CONVENTION

= HIGH VOLTAGE PANELBOARD (480Y/277V)= LOW VOLTAGE PANELBOARD (208Y/120V)

= TRANSFORMER= DISTRIBUTION BOARDDB= MAIN SWITCH BOARDMSB

MCC = MOTOR CONTROL CENTER

= UNINTERRUPTABLE POWER SUPPLYUPS= POWER DISTRIBUTION UNIT

ATS = AUTOMATIC TRANSFER SWITCHPDU

= ISOLATED PANELBOARDI

B = BUSWAY

MSB

FLUSH MOUNTED PANELBOARD. DASHED LINES INDICATE CLEARANCES.

SURFACE MOUNTED PANELBOARD. DASHED LINES INDICATE CLEARANCES.

H1A

L1A

MCCMOTOR CONTROL CENTER. DASHED LINES INDICATE CLEARANCES.

T1A

UNINTERRUPTABLE POWER SUPPLY. DASHED LINES INDICATE

CLEARANCES.

AUTOMATIC TRANSFER SWITCH. DASHED LINES INDICATE CLEARANCES.

DRY TYPE TRANSFORMER (15kVA OR ABOVE), WITH EQUIPMENT TAG

(TAG INSIDE OR OUTSIDE, DEPENDING ON SIZE). IN MOST CASES,

ACTUAL SIZE SHOWN ON PLANS (ELECTRICAL ROOMS).

E = EMERGENCY

DISTRIBUTION BOARD. DASHED LINES INDICATE CLEARANCES.DB

UPS-A

ATS-1

EXAMPLES:

A. SES1 (SERVICE ENTRANCE SECTION #1)

B. 1H1A (SERVED FROM SES#1, 480/277 NORMAL, LEVEL 1, FIRST BOARD)

C. 1EQH1A (SERVED FROM MAIN EMER SWBD #1, 480/277 EQUIP POWER, LEVEL 1, FIRST

BOARD)

SES

G

= GROUND

= HOT/PHASE

= NEUTRAL

= SWITCH LEG

CONDUCTOR IDENTIFICATION SYMBOLS. REFER TO PLANS FOR

COMBINATION USE. CONDUCTOR IDENTIFICATION MOSTLY USED IN

HOMERUN LOCATION, BUT CAN ALSO BE USED IN BRANCH

CIRCUITING WHERE APPLIED. GROUND CONDUCTORS WILL BE

INSTALLED IN ALL RACEWAYS WHETHER SHOWN OR NOT.

LA-1

HOMERUN FROM EQUIPMENT LOCATION. THE CIRCUIT NUMBER

ADJACENT TO HOMERUN INDICATES PANEL SOURCE AND

INDIVIDUAL SINGLE POLE CIRCUIT BREAKER(S). CONDUCTOR

IDENTIFICATION SYMBOL INDICATES NUMBER OF CONDUCTORS IN

HOMERUN. MINIMUM #12 CONDUCTORS AND 3/4" RACEWAY PATH

WILL BE PROVIDED IN HOMERUN UON. ALL HOMERUNS WILL

INCLUDE GROUND CONDUCTOR.

LA-1,3

HOMERUN FROM EQUIPMENT LOCATION. THE CIRCUIT NUMBER

ADJACENT TO HOMERUN INDICATES PANEL SOURCE AND INDIVIDUAL

TWO OR THREE POLE CIRCUIT BREAKERS. CONDUCTOR

IDENTIFICATION SYMBOL INDICATES NUMBER OF CONDUCTORS IN

HOMERUN. MINIMUM #12 CONDUCTORS AND 3/4" RACEWAY PATH

WILL BE PROVIDED IN HOMERUN UON. NEUTRAL MAY BE USED

WHERE INDICATED ON PLAN. ALL HOMERUNS WILL INCLUDE

GROUND CONDUCTOR.

LA-5,7,9

CONCEALED RACEWAY BETWEEN DEVICES AND OR EQUIPMENT

IN WALLS OR IN CEILING SPACE

UNDERGROUND RACEWAY BETWEEN DEVICES AND OR

EQUIPMENT

EXPOSED RACEWAY BETWEEN DEVICES AND OR EQUIPMENT

ON WALLS OR CEILINGS

CONDUIT TURNSDOWN UP

B BUSWAY

GROUNDING CONDUCTORG

CABLE TRAY - POWER AND TELECOMMUNICATIONS

T TELECOMMUNICATIONS RACEWAY

D DATA RACEWAY

FA FIRE ALARM RACEWAY

CONDUIT STUBBED AND CAPPED

VOICE/DATA COMBINATION RACEWAYV/D

BRANCH CIRCUIT GENERAL INFORMATION:BRANCH CIRCUITS FROM OVERCURRENT PROTECTION (20A) TO FURTHEST DEVICESHALL NOT EXCEED 75 FEET FOR #12AWG COPPER AND 150 FEET FOR #10AWG

COPPER; MEASURED ALONG CONDUCTORS ROUTING PATH. BRANCH CIRCUITS

EXCEEDING 150 FEET WILL BE SIZED SO THAT VOLTAGE DROP DOES NOT EXCEED 5%.

LA-1,3

LA-5,7,9

HOMERUN FROM EQUIPMENT LOCATION. THE CIRCUIT NUMBER

ADJACENT TO HOMERUN INDICATES PANEL SOURCE AND INDIVIDUAL

SINGLE POLE CIRCUIT BREAKER(S). SYMBOL REPRESENTS A MULTI-

BRANCH CIRCUIT. NUMBER OF CONDUCTORS IN HOMERUN WILL

INCLUDE A SEPERATE NEUTRAL FOR EACH CIRCUIT PHASE

CONDUCTOR. MINIMUM #12 CONDUCTORS AND 3/4" RACEWAY PATH

WILL BE PROVIDED IN HOMERUN UON. ALL HOMERUNS WILL

INCLUDE GROUND CONDUCTOR.

RACEWAY & CONDUCTORS

CURRENT TRANFORMER, NUMBER

"3000/5" DENOTES RATIO.

WG WEATHERPROOF AND GFCI

R REMOVED/REMOVAL

RC ROOM CONTROLLER

FAA FIRE ALARM ANNUNCIATOR

FMS FACILITY MANAGEMENT SYSTEM

GROUND FAULT EQUIPMENT PROTECTIONGFEP

CB CIRCUIT BREAKER

D DIMMING

DC DIRECT CURRENT

UPS

NUMBER OR MAIN EMERG SWBD NUMBER= SERVICE ENTRANCE SECTION

(SB=SUB-BASEMENT, B=BASEMENT, M=MEZZANINE,

P=PENTHOUSE)

CEILING MOUNTED EMERGENCY DOUBLE

DUPLEX (QUADPLEX) RECEPTACLEX

PC

DL DAY-LIGHTING SENSOR; TYPE AS INDICATED

ON PLANS

PP POWER PACK; TYPE AS INDICATED

ON PLANS

SURFACE

BT

BR

BEAM TRANSMITTER

BEAM RECEIVERVARIES

CEILING OR

WALL

FATCFIRE ALARM TERMINAL CABINET (EQUIP. NAMING

CONVENTION PER PLANS)

480V

CL CLOCK

CB

FATC FIRE ALARM TERMINAL CABINET

UPDATED: 06/08/2015

A/V AUDIO/VISUAL

DRY TYPE TRANSFORMER (LESS THAN 15kVA), WITH NO EQUIPMENT TAG. SIZE,

TYPE AND LOCATION NOTED ON PLANS.

A/C ALTERNATING CURRENT

SYMBOL DESCRIPTION

DESCRIPTIONSYMBOL

T

VFD

TFOE

I N

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

JOHN F. HECK IV

82984

I SG

ER D

E

RET

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 12

:41:

23 P

M

E002a

ELECTRICALLEGEND

Approver

John Heck2016.01.29 13:47:22-07'00'

Page 8: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

A B C D E F G

1

2

3

4

5

K-3544HIGHLINE

C_TOILETS

VITREOUS CHINA

K-3544HIGHLINE

C_TOILETS

VITREOUS CHINA

K-3544HIGHLINE

C_TOILETS

VITREOUS CHINA

OS

OS

OS

OSOS

OS

OS

RC

RC

ARb ARb ARb

ARb

ARb

BL

A1Fb A1Fb

A1Fb A1Fb

EGEG

EGEG

EGE

AL02

AL03

AL02

AL02

AL03

EL02

AL02

AL02 AL02

BVL BVL

BVL BVL

BVL BVL

BVL BVL

BVL BVL

BVL BVL

aa

b b

b b

b b

b b

a a

3,aEM EM EM

BVL

c

BVL

c

BVL

d

BVL

d

BVL

e

BVL

e

BVL

c

BVL

c

BVL

d

BVL

d

BVL

e

BVL

e

BVL

e

BVL

e

BVL

a

BVLBVL

a

BVL

a

BVL

d

BVL

d

BVL

c

BVL

c

BVL

a

BVL

a

BVL

e

BVL

e

BVL

a

BVL

a

BVL

d

BVL

d

BVL

a

BVL

a

BVL

c

BVL

c

BVL

a

AL02

EM 3,a

BVL

aEM

AL02EM

a

EM

EM EM

EM

EM

EM

3,abcd

e

AL02

3,a

3,a

DPHAG - 1FLE

AL08AL08

DPHAG - 3

DPHAG - 3.

.

DPHAG - 5 DPHAG - 7 DPHAG - 9 DPHAG - 11

DPHAG - 1FLE

BL BL

EM

DPHAG

BL AL07

AL04

BL EM

A1Fb A1Fb

AL04AL04

AL02AL02

K K

EMEM

EM EM

AL03

ARaD ARaD ARaD

ARaD ARaD ARaD

ARaD ARaD ARaD

AL02

AL02

AL06AL05AL05

EEM

DPHAG - 1FLE

DPHAG - 1FLE

AL08

AL08

DPHAG - 13

FLEDPHAG - 1

AL08

FLEDPHAG - 1

AL08

105

SHOP

101

HALLWAY

102

CLASSROOM

103

STORAGE

104

OFFICE

110

GIRLS109

BOYS

108

JANITOR

106

TOOLSTORAGE

107

ELEC./COMP.

A2

E500a

BL

TFOE

I N

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

JOHN F. HECK IV

82984

I SG

ER D

E

RET

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 12

:41:

28 P

M

EL101

AG SHOPLIGHTING PLAN

Approver

GENERAL SHEET NOTES

SHEET KEYNOTES

SCALE: 1/8" = 1'-0"B1 AG SHOP LIGHTING PLAN0' 4' 8' 16'

NORTH

AL02 ONE SWITCH; SWITCH TYPE AS INDICATED. WILL CONTROL THE LUMINAIRES INROOM.

AL03 WALL-MOUNTED OCCUPANCY SENSOR, WATT STOPPER PW-100 OR APPROVEDEQUAL. LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FORBID PURPOSES.

AL04 CEILING-MOUNTED SENSOR, WATT STOPPER DT-355 OR APPROVED EQUAL.LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR BIDPURPOSES.

AL05 LIGHTING ROOM CONTROLLERS FOR LIGHTING CONTROL SYSTEM IN THIS ROOM.REFER TO SHEET E500a FOR WIRING DIAGRAM AND ADDITIONAL INFORMATIONON ROOM CONTROLLER TYPE.

AL06 CEILING-MOUNTED OCCUPANCY SENSOR, LOCATE PER MANUFACTURER'SRECOMMENDATIONS. SHOWN HERE FOR BID PURPOSES. REFER TO SHEETE500a FOR WIRING DIAGRAM AND ADDITIONAL INFORMATION ON SENSOR TYPE.

AL07 ONE PROGRAMMABLE TIME CLOCK WITH ROOF MOUNTED PHOTO CELL AND 4POLE CONTACTOR FOR EXTERIOR BUILDING LIGHTINGTO BE CONTROLLEDSEPARATELY. REFER TO DETAIL D2 ON SHEET E500a FOR ADDITIONALINFORMATION.

AL08 LUMINAIRE WILL BE CONNECTED TO LIGHTING BATTERY INVERTER "BAG1"LOCATED IN ELECTRICAL ROOM 107. REFER TO DETAIL B2 ON SHEET E500a FORTYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM.

EL02 ONE SWITCH; SWITCH TYPE AS INDICATED. WILL CONTROL THE LUMINAIRES INROOM.

A. ALL EXIT SIGNS, TYPES "E" OR "EG", WILL BE CONNECTED TO CIRCUIT SERVING THEROOM THEY ARE LOCATED IN AND FROM NO OTHER CIRCUIT.

B. REFER TO SHEET E701a FOR ELECTRICAL LUMINAIRE SCHEDULE.C. REFER TO SHEET EP103 FOR ELECTRICAL ROOMS AND ELECTRICAL EQUIPMENT

LAYOUT.D. REFER TO SHEET E500a FOR LIGHTING DIAGRAMS AND SEQUENCE OF OPERATION.E. REFER TO DETAIL C4 ON SHEET E500a FOR LUMINAIRE MOUNTING.F. REFER TO ARCHITECTURAL SHEET AE501 FOR ADDITIONAL CEILING GRID MOUNTING

SUPPORT INFORMATION. ALL LUMINAIRES WILL BE SECURELY SUPPORTEDSEPARATELY FROM CEILING GRIDS TO CEILING STRUCTURE.

G. REFER TO ARCHITECTURAL SHEETS FOR EXTERIOR LIGHTING ELEVATIONS.H. ALL EXTERIOR BUILDING LUMINAIRES WILL BE ROUTED THROUGH A TIME CLOCK AND

CONTACTOR LOCATED IN THE ELECTRICAL ROOM WHERE THE PANEL FEEDINGTHOSE LUMINAIRES IS LOCATED. REFER TO DIAGRAM D2 ON SHEET E500a FORADDITIONAL INFORMATION.

I. ALL LUMINAIRES IN DASHED AREA WILL BE CONNECTED TO CIRCUIT INDICATED UNLESSOTHERWISE NOTED.

John Heck2016.01.29 13:47:15-07'00'

Page 9: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

A B C D E F G

1

2

3

4

5

K-3544HIGHLINE

C_TOILETS

VITREOUS CHINA

K-3544HIGHLINE

C_TOILETS

VITREOUS CHINA

K-3544HIGHLINE

C_TOILETS

VITREOUS CHINA F

F

J

F F

F F

J

F

P

P P

R/F

R/FP

F

F

FF

FF

TS

FS

J

G G

WG

WG

WG

T

T

T T T T

T T T T

T T

T T

T

AG-CU-01 AP01

DPHAG - 2,4,6

AG-RTU-01 AP01

EP21AP02AP03

AG-FC-01

AP01

LAG1 - 37

AP04

LAG1 - 34

LAG1 - 35

LAG1 - 39

LAG1 - 41

LAG1 - 36

LAG1 - 38

LAG2 - 74LAG2 - 76

LAG2 - 78

LAG2 - 80 LAG2 - 82 LAG2 - 84

LAG2 - 79

LAG2 - 81

11

11

1

2

2

2

2 2LAG1 - 1

LAG1 - 2

3 3

3

LAG1 - 3

LAG1 - 40,42

WG

3

3

4

LAG2 - 40

AP05

AF03

T

G

FACP

DWH-1

AP09

G GG

G G

G

G

G

G

G GGG G

G

AF02AF02

AP09

AP06

AP09

AP09

AP08

AP09

AP09

AP09AP08 AP09

AP07

AP09

AP08

AP06

AP09

AP09

AP08

AP09

AP07

AP09

AP08

AP08

AP09

AP09

AP08AP09

AP08AP09

AP08

AP09

AP09

AF01

AG-AC-1AD-1

AP10AP01

ILP-1

WG

G

AP09

AP08

G

AP09

LAG2

HOT BOX PIV

FA

FA

LAG1 - 6,8

AP14AP13AP13

14

LAG1 - 14

14

LAG1 - 12

LAG1 - 10

LAG1 - 4

G

LAG2 - 42

LAG1 - 55,57

LAG2 - 30 LAG1 - 11 LAG2 - 28 LAG1 - 51,53

LAG2 - 26

LAG1 - 43,45

LAG1 - 13LAG1 - 47,49

LAG2 - 24

LAG2 - 22

LAG2 - 37,39

105

SHOP

101

HALLWAY

102

CLASSROOM

103

STORAGE

104

OFFICE

110

GIRLS109

BOYS

108

JANITOR

106

TOOLSTORAGE

107

ELEC./COMP.

LAG1 - 15

LAG2 - 33,35LAG2 - 20

WG

LAG1 - 1818

LAG2 - 18

LAG2 - 29,31

LAG1 - 17

LAG2 - 16

LAG2 - 14

LAG2 - 21,23

LAG1 - 19

LAG2 - 12

LAG1 - 21

LAG2 - 17,19

LAG2 - 10

LAG2 - 13,15

LAG2 - 8

LAG2 - 6

LAG2 - 9,11

LAG1 - 23

LAG2 - 4

LAG2 - 5,7

LAG2 - 2

LAG2 - 1,3LAG2 - 32LAG2 - 34

LAG1 - 25

LAG1 - 59,61

LAG2 - 36

LAG1 - 27

LAG1 - 9

LAG2 - 38

LAG1 - 16

WG16

LAG1 - 68,70,72

LAG1 - 66

LAG1 - 74,76,78

LAG1 - 79,81,83

LAG1 - 80,82,84

LAG1 - 73,75,77

LAG1 - 62

LAG1 - 64

LAG1 - 63,65

LAG2 - 25,27

AP12

AP11

AP12

AP11

AP08

LAG1 - 7

EP101A3

LAG1 - 5

TAG2

TAG1

LAG1

107

ELEC./COMP.

DPHAG

AP16AP15

AP17

TFOE

I N

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

JOHN F. HECK IV

82984

I SG

ER D

E

RET

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 12

:41:

33 P

M

EP101

AG SHOP POWERPLAN

Approver

0' 4' 8' 16'

NORTH

SCALE: 1/8" = 1'-0"B1 AG SHOP POWER PLAN

GENERAL SHEET NOTES

A. GFCI RECEPTACLES WILL BE INSTALLED AT ALL LOCATIONS AS REQUIRED BY THE LATEST VERSION OF NEC, STATE AND LOCAL CODES WHETHER INDICATED ON PLANS OR NOT. SOME LOCATIONS WILL BE WITHIN 6'-0" OF SINKS, EXTERIOR DOORS AND WET

LOCATIONS. ALL EXTERIOR RECEPTACLE LOCATIONS WILL BE GFCI RATED AND WEATHERPROOF.

SHEET KEYNOTES

AF01 FIRE ALARM CONTROL PANEL (FACP). REFER TO FIRE ALARM RISER DIAGRAMON SHEET E603A FOR ADDTIONAL INFORMATION.

AF02 COORDINATE FLOW AND TAMPER SWITCH LOCATION WITH PLUMBINGDRAWINGS. PROVIDE INDICATOR LIGHT TO INDICATE LOCATION OF FLOW ANDTAMPER SWITCHES THAT ARE ABOVE THE CEILING.

AF03 REFER TO SHEET SERIES "MH" FOR LOCATION OF FIRE SMOKE DAMPERS OFDUCT DETECTOR LOCATIONS. PROVIDE INDICATED LIGHT AT CEILING LEVEL TOIDENTIFY LOCATION OF DEVICE.

AP01 REFER TO SHEET E701A FOR ADDITIONAL ELECTRICAL CONNECTIONREQUIREMENTS. REFER TO "M700" SHEET SERIES FOR MECHANICAL /ELECTRICAL INFORMATION.

AP02 EXTEND POWER CIRCUIT TO CONDENSING UNIT ON GROUND.AP03 CONDENSATE LIFT PUMP.AP04 RECEPTACLE IS GFCI AND WEATHER PROOF AND WILL BE PART OF UNIT.

CONTRACTOR WILL PROVIDE CIRCUIT INDICATED.AP05 EXTEND POWER CIRCUIT TO FAN COIL UNIT INSIDE OF BUILDING. REFER TO

SHEET E701A FOR ADDITIONAL ELECTRICAL CONNECTION REQUIREMENTS.AP06 DEVICE WILL BE RATED FOR 208-240V, 3PH & 50A. (4) #8 & (1) #10 GND IN 1 1/2"

CONDUIT. MOUNT AT 42" A.F.F.AP07 DEVICE WILL BE RATED FOR 208-240V, 3PH, & 30A. (4) #8 & (1) #10 GND IN 1 1/2"

CONDUIT. MOUNT AT 42" A.F.F.AP08 DEVICE WILL BE RATED FOR 208-240V, 1PH & 50A. (3) #8 & (1) #10 GND IN 1 1/4"

CONDUIT. MOUNT AT 42" A.F.F.AP09 DEVICE WILL BE RATED FOR 120V, 1PH & 30A. (2) #10 & (1) #10 GND IN 1"

CONDUIT. MOUNT AT 42" A.F.F.AP10 JUNCTION BOX WILL SERVE AD-1 AND ALSO HEAT TAPE ASSOCIATED WITH AC-1.AP11 PROVIDE A DROP CORD REEL RATED FOR 208V, 1PH & 50A. SECURLEY MOUNT

TO CEILING STRUCTURE. DROP CORD WILL REACH 42" A.F.F. FROM FLOOR.AP12 PROVIDE A DROP CORD REEL RATED FOR 120V, 1PH & 30A. SECURLEY MOUNT

TO CEILING STRUCTURE. DROP CORD WILL REACH 42" A.F.F. FROM FLOOR.AP13 PROVIDE A 1" CONDUIT TO FACP FOR FIRE ALARM CONNECTION TO SITE

EQUIPMENT. REFER TO SHEET E60X FOR ADDITIONAL INFORMATION. (NOTE FORBEL - FIRE ALARM DIAGRAM SHEET)

AP14 PROVIDE A 1" CONDUIT WITH (2) #10 & (1) #10 GND FOR EACH CIRCUITINDICATED.

AP15 TIME CLOCK, PROVIDE A 277V CIRCUIT. REFER TO SHEET EL103 AND DIAGRAMD2 ON SHEET E500a FOR ADDITIONAL INFORMATION.

AP16 BATTERY INVERTER, PROVIDE 277V CIRCUIT. REFER TO SHEET EL103 ANDDIAGRAM B2 ON SHEET E500a FOR ADDITIONAL INFORMATION.

AP17 MAIN GROUNDING ELECTRODE GROUND BAR. REFER TO DETAIL A4 ON SHEETE500a AND ELECTRICAL GROUNDING DIAGRAM ON SHEET E602 FOR ADDITIONALINFORMATION.

EP21 EXTEND POWER CIRCUIT TO CONDENSING UNIT ON ROOF. REFER TO EP-141CFOR ADDITIONAL INFORMATION.

SCALE: 1/4" = 1'-0"A3 ENLARGED ELEC./COMP 107

John Heck2016.01.29 13:47:08-07'00'

Page 10: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

(TYP.)HANGER WIRES

CORNERS OF FIXTURE.

NO. 12 GAUGE WIRE HANGER TOBUILDING FRAMING OR STRUCTURALMEMBERS). SUSPEND FROM ALL FOUR

CEILING SYSTEM

LAY-IN LUMINAIRE

SEISMIC FIXTURE CLAMPS:REQUIRED AT ALL (4) LUMINAIRECORNERS WITH (2) #10 SELF-TAPPINGSCREWS. AGI SEISMIC PRODUCTSOR EQUAL. AC 184 COMPLIANT.

(TYP.)HANGER WIRESCEILING SYSTEM

BOLT CONNECTION WITH

COMPRESSION SPADE LUG

FITTING (TYPICAL)

TO SERVICE ENTRANCE GROUND

2700V INSULATORS

STAND-OFFS

COPPER BUS BAR

(REFER TO DIAGRAM AND

KEYED NOTE ON SHEET E-602.)

DEVICE AND OUTLET BOX TYPES

PER PLANS

CORD INSULATION

AND CONDUCTORS

PER PLANS

CORD REEL

BALL STOP

CHANNEL

THREADED ROD OR

APPROVED EQUIVALENT

CORD GRIP

7'-0" AFF

(MIN)

SUSPENDED

CEILING

CORD & PLUG

NEMA 5-20R

CEILING OUTLET

ASSEMBLY TO CONSIST OF THE FOLLOWING COMPONENTS

(BASIS OF DESIGN):

- HUBBELL #HBLC40123--REEL W/MOUNTING BASE

AND 12/3 WIRE LEADS

- HUBBELL #3059H--PORTABLE OUTLET BOX

- HUBBELL #3061H--LIFTING COVER WITH GFCI DEVICE PLATE

- HUBBELL #074011335--STAINLESS STEEL CORD GRIP

Hot

120/277

CAT5eLMRJ-Watt Stopper Cable

REFER TO SHEET SERIES "EL" FOR QUANTITIES AND ADDITIONAL INFORMATION

ROOM CONTROLLERLMRC-212

LMDC-100

SEE INSTALLATION INSTRUCTIONSFOR TERMINATION TYPE.

LIGHTING CONTROL DESCRIPTIONLoad (a) ALL Inboard Lamps = Manual-ON/Auto-OFFLoad (b) ALL Outboard Lamps = Manual-ON/Auto-OFF

LightingLoad(a)

Neutral

LightingLoad(b)

Two Button SwitchLMSW-102

LightingLoads(a), (b)

Watt Stopper

b

a = INNER LAMPS

b = OUTER LAMPS

LIGHTING CONTROLDESCRIPTION PLACARD MOUNT ADJACENT TO SWITCHES

a

Two Button SwitchLMSW-102

Watt Stopper

RJ45(TYPICAL)

LightingLoads(a), (b) b

a

Two Button SwitchLMSW-102

Watt Stopper

LightingLoads(a), (b) b

a

LIGHTING BATTERYINVERTER

LIGHTING BATTERY INVERTER WILL BE RATED FOR500VA OR AS INDICATED ON PLAN. INVERTER WILLOPERATE IN THE EVENT OF AN EMERGENCY.INVERTER LOCATED IN THE ELECTRICAL ROOM.

YELLOW

EMERGENCYLOAD

120V

277V

RED

INVERTERHOT

INVERTERNEUTRAL

TO PANEL FOR CONSTANT POWERREFER TO PLANS FOR CIRCUIT ANDOTHER INFORMATION

CIRCUIT (HOT/NEUTRAL)FROM LIGHTING PANEL FOR

MULTIPLE ROOMS ANDCONTROL IN EACH ROOM

WHITE

BLUE

INDIVIDUAL ROOM

SINGLE ROOM AND CONTROL ON ONE LIGHTING CIRCUIT AND ONE INVERTER

2 AMP / OR 4 WIRECONTROL DIAGRAM

ABOVE FOR THISUNIT

4 POLE

CONTACTOR

LIGHTING CONTACTOR - ELECTRICAL ROOM 107

CONTROL SEQUENCE:

(a) ON AUTOMATICALLY SELECTED ASTRONOMIC SETTING.

(b) OFF AT PRESET TIME; COORDINATE WITH OWNER'S REPRESENTATIVE.

SPARE

SPARE

DPHAG-1

SPARE

C

2.0A FUSE

PC

(18"x18"x6" HINGED COVERED PULLBOX)

NEMA TYPE1 ENCLOSURE 277V

TIMECLOCK

TERMINALBLOCK

TIMECLOCK WILL INCORPORATE

AN H-O-A SWITCH FOR MANUAL AND

AUTOMATIC CONTROL

DPHAG-8

PHOTOCELL ON

ROOF

TFOE

I N

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

JOHN F. HECK IV

82984

I SG

ER D

E

RET

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 12

:43:

53 P

M

E500a

ELECTRICALDETAILS ANDDIAGRAMS

Approver

SCALE: NO SCALEC4 LUMINAIRE SUPPORT DETAIL

SCALE: NO SCALEA4 MAIN GROUNDING ELECTRODE BUS BAR DETAIL

SCALE: NO SCALEB4 DROP CORD REEL DETAIL

SCALE: NO SCALEA2 WATT STOPPER "DLM" WIRING DIAGRAM

SCALE: NO SCALEB2 EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM

SCALE: NO SCALED2 EXTERIOR LIGHTING TIME CLOCK DIAGRAM

LIGHTING SEQUENCE OF OPERATION

A. CLASSROOM

1. UNOCCUPIED MODE:

WHEN ROOM IS UNOCCUPIED, ALL LIGHTING SHALL BE DISABLED AND DE-ENERGIZED BY

OCCUPANCY SENSOR IN ROOM.

2. OCCUPIED MODE:

a. LIGHTING CONTROL IN ROOM WILL BE ENABLED BY SWITCHES IN ROOM. NO LUMINAIRES WILL

AUTOMATICALLY ENERGIZE.

b. DURING OCCUPANCY AT THREE BUTTON SWITCH:

- TOP BUTTON (a) WILL CONTROL INBOARD LAMP(S) OF LUMINAIRES IN ENTRIE OF

CLASSROOM.

- BOTTOM BUTTON (b) WILL CONTROL OUTBOARD LAMPS OF LUMINAIRES IN ENTIRE

CLASSROOM.

c. WHEN PERSONNEL LEAVE THE ROOM AND OCCUPANCY SENSOR TIMES OUT, THE SYSTEM

SHALL RESET TO THE UNOCCUPIED MODE.

B. RESTROOMS, SMALL AND LARGE:

DUAL TECHNOLOGY (ULTRASONIC/INFRARED) CEILING MOUNTED SENSOR WILL CONTROL LUMINAIRES

ON AND OFF AUTOMATICALLY. KEYED SWITCH WILL BE SECONDARY MEANS OF CONTROL.

C. STORAGE & JANITOR ROOMS:

WALL MOUNTED OCCUPANCY SENSOR WILL CONTROL THE LUMINAIRE(S) IN THE ROOM.

D. OFFICES:

1. UNOCCUPIED MODE:

WHEN ROOM IS UNOCCUPIED, ALL LIGHTING SHALL BE DISABLED AND DE-ENERGIZED BY

OCCUPANCY SENSOR IN ROOM.

2. OCCUPIED MODE:

a. LIGHTING CONTROL IN ROOM WILL BE ENABLED BY SWITCHES IN ROOM. NO LUMINAIRES WILL

AUTOMATICALLY ENERGIZE.

b. WHEN PERSONNEL LEAVE THE ROOM AND OCCUPANCY SENSOR TIMES OUT, THE SYSTEM

SHALL RESET TO THE UNOCCUPIED MODE.

E. CORRIDOR:

1. LOCAL CONTROL OF LUMINAIRES WILL BE VIA TOGGLE SWITCH.

F. EXTERIOR BUILDING LIGHTING:

1. ALL EXTERIOR BUILDING LIGHTING WILL BE PROGRAMMED TO COME ON A 1/2 HOUR BEFORE

DUSK AND OFF A 1/2 HOUR AFTER DAWN.

John Heck2016.01.29 13:46:40-07'00'

Page 11: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

"MSB2"

1

"DPHAG"

480Y/277V, 3PH, 4W, 400A MAIN BUS

DEVICESMINIMUM

BUS BRACINGMINIMUM

35KAIC

35KA

26

60A3P

SPD

5

225A3P

225A3P

GROUND BUS3

60Y

480V

208Y/120V

3

"TAG1"150kVAK-4 RATED

225

11

225A3P

4

225A3P

2

400Y

400A3P

400A3P

2

M

8

7

400Y

6

225A3P

400A

PANEL"LAG1"

(2 SECT)

480V

208Y/120V

3

"TAG2"150kVAK-4 RATED

225

400Y

400A

PANEL"LAG2"

(2 SECT)

25

40

35

30

45

50

60

70

90

80

125

100

200

175

225

250

150

300

350

450

400

700

600

800

1000

500

1200

1600

2500

2000

3000

NOTE:

NOTESDESIGNATION

35Y

40Y

30Y

45Y

50Y

60Y

70Y

80Y

90Y

125Y

100Y

175Y

200Y

225Y

250Y

150Y

300Y

350Y

450Y

400Y

600Y

700Y

800Y

1000Y

500Y

1200Y

1600Y

2000Y

2500Y

3000Y

THREE PHASE THREE WIRE & GROUND FEEDER

FEEDER SCHEDULE

25Y

20Y

EQUIPMENT BONDING JUMPER FOR SEPARATELY DERIVED SYSTEMS PER

NEC 250.66 (PROVIDE CONDUCTOR GROUND BELOW INSTEAD OF FEEDER GROUND FOR THREE PHASE,

4-WIRE SYSTEMS INDICATED ABOVE)

20

4000

4000Y

5000Y

CONDUCTORS

4#6

(3) 4-600 KCMIL

(4) 4-600 KCMIL

(5) 4-600 KCMIL

(8) 4-500 KCMIL

(6) 4-600 KCMIL

(10) 4-600 KCMIL

(12) 4-600 KCMIL

(2) 4-250 KCMIL

(2) 4-350 KCMIL

(2) 4-500 KCMIL

(2) 4-600 KCMIL

(3) 4-400 KCMIL

4-250 KCMIL

(2) 4#4/0

4-350 KCMIL

4-500 KCMIL

4-600 KCMIL

4#4

4#4

4#2

4#2

4#1/0

4#2/0

4#3/0

4#4/0

4#1

4#10

4#10

4#12

4#8

4#8

4#8

4#8

GROUND

(3) 3/0

(4) 4/0

(5) 250 KCMIL

(6) 350 KCMIL

(8) 400 KCMIL

(10) 500 KCMIL

(12) 700 KCMIL

4

(2) 2

(2) 1

(2) 1

(2) 2

(2) 1/0

(3) 2/0

2

4

2

6

6

4

6

6

8

8

8

8

10

10

12

10

10

10

10

10

CONDUIT

(3) 4"

(4) 4"

(5) 4"

(6) 4"

(8) 4"

(10) 4"

(12) 4"

3"

(2) 3"

(2) 4"

(2) 4"

(3) 3"

(2) 3"

(2) 2 1/2"

4"

3"

4"

1 1/4"

1 1/4"

1 1/4"

1 1/4"

2 1/2"

1 1/2"

2"

2"

2"

3/4"

3/4"

1"

3/4"

3/4"

3/4"

3/4"

3/4"

(6) 3-600 KCMIL

(8) 3-500 KCMIL

(10) 3-600 KCMIL

(5) 3-600 KCMIL

(2) 3-600 KCMIL

(4) 3-600 KCMIL

(3) 3-600 KCMIL

(3) 3-400 KCMIL

(2) 3-250 KCMIL

(2) 3-500 KCMIL

(2) 3-350 KCMIL

3-600 KCMIL

(2) 3#4/0

3#1

3#2

3#2/0

3#1/0

3#4/0

3#3/0

3-250 KCMIL

3-500 KCMIL

3-350 KCMIL

3#10

3#8

3#10

3#8

3#8

3#6

3#4

3#8

3#2

3#4

3#12

(8)400 KCMIL

(6)350 KCMIL

(10)500 KCMIL

2

(2) 2

(2) 1

(2) 1

(2) 2

(5)250 KCMIL

(4) 4/0

(3) 3/0

(3) 2/0

(2) 1/0

4

2

4

4

6

6

6

6

8

10

10

10

10

10

10

10

8

8

8

12

(6) 4"

(8) 4"

(10) 4"

4"

(2) 4"

(2) 3"

(2) 3"

(3) 3"

(5) 4"

(4) 4"

(3) 4"

(2) 4"

(2) 2 1/2"

1 1/2"

1 1/4"

1 1/2"

2 1/2"

2"

3"

4"

3"

2"

3/4"

1 1/4"

1 1/4"

1 1/4"

1"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

8

6

THREE PHASE FOUR WIRE & GROUND FEEDER

ALL CONDUCTORS ARE COPPER, TYPE THWN/THHN UNLESS OTHERWISE NOTED.

100Y-E

THREE PHASE FOUR WIRE 200% NEUTRAL & GROUND FEEDER

150Y-E

225Y-E

350Y-E

500Y-E

400Y-E

3-250 KCMIL,

2-250 KCMIL NEUT.

(2) 3#3/0,

(2) 2#3/0 NEUT.

(2) 3#4/0,

(2) 2#4/0 NEUT.

(2) 3-350 KCMIL,

(2) 2-350KCMIL NEUT.

3#2, 1#4/0 NEUTRAL

3#2/0, 2#2/0 NEUT.

(2) 2

(2) 2

8

(2) 2

4

6 2"

2 1/2"

2"

(2) 3"

(2) 2 1/2"

(2) 2 1/2"

20YS THRU 100YS

125YS THRU 150YS

4175YS THRU 200YS

2225YS THRU 300YS

1/0350YS THRU 500YS

2/0600YS THRU 700YS

GROUNDDESIGNATION

800YS THRU 5000YS 3/0

TFOE

I N

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

JOHN F. HECK IV

82984

I SG

ER D

E

RET

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 12

:43:

53 P

M

E600a

ELECTRICALONE-LINEDIAGRAM

Approver

SCALE: NO SCALEC2 ELECTRICAL ONE-LINE DIAGRAM

SCALE: NO SCALEA1 COPPER FEEDER SCHEDULE

GENERAL SHEET NOTES

SHEET KEYNOTES

1. ALL IN SQUARE DASHED AREA ARE A PART OF EARLY WORK PACKAGE PHASE OF THIS PROJECT.

2. MOLDED CASE, THERMAL-MAGNETIC CIRCUIT BREAKERS, 100% RATED AND LOCKABLE.

3. REFER TO SHEET E-602 FOR GROUNDING INFORMATION FOR THIS EQUIPMENT.

4. PROVIDE SPACE FOR ADDITIONAL CIRCUIT BREAKERS. SIZE AS INDICATED.

5. SPD MOUNTED EXTERNALLY TO SWITCHBOARD / PANELBOARD. REFERENCE SECTION 264313 FOR

ADDITIONAL INFORMATION.

6. PROVIDE SPARE CIRCUIT BREAKER(S). SIZE AS INDICATED.

7. POWER MONITOR MOUNTED EXTERNAL TO SWITCHBOARD. REFER TO SPECIFICATON SECTION 262413

FOR ADDTIONAL INFORMATION.

8. PROVIDE DATA OUTLET FOR USE UTILITY METER AND FUTURE REMOTE MONTIORING.

A. PANELBOARD AIC RATINGS ARE INDICATED ON THE PANEL SCHEDULES.

B. INFORMATION SHOWN IS DIAGRAMMATIC AND IS NOT INTENDED TO REPRESENT PHYSICAL

ARRANGEMENTS, LOCATIONS, ROUTING OR CONNECTIONS. PHYSICAL LAYOUTS ARE TO BE PER FIELD

CONDITIONS AND AS INDICATED ELSEWHERE IN THE ELECTRICAL PLANS.

C. REFERENCE THE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS REGARDING EQUIPMENT AND

INSTALLATION. NOT ALL INFORMATION SHOWN ON THIS DIAGRAM.

D. ALL PANELS WILL HAVE DOOR-IN-DOOR ACCESSIBILITY FOR EACH PANEL.

E. CONTRACTOR WILL MEASURE AND TORQUE ALL PANEL FEEDERS, MEASURE RESISTANCE TO GROUND AT

SERVICE GROUND AND PROVIDE WRITTEN DOCUMENTATION OF TEST RESULTS. CONTRACTOR WILL

COORDINATE TIME SO THAT APSD REPRESENTATIVE IS PRESENT DURING TEST.

F. CONTRACTOR WILL LABEL ALL DISTRIBUTION EQUIPMENT PRIOR TO FINAL OBSERVATION WALK THROUGH.

G. WHEN ALL EQUIPMENT IS INSTALLED REQUIRING PROGRAMMING AND TRAINING HAS BEEN COMPLETED,

THE SCHOOL'S IP ADDRESS WILL NEED TO BE GIVEN TO OWNER'S REPRESENTATIVE FOR ELECTRICAL M&O

USE.

H. REFER TO GROUNDING DIAGRAM ON SHEET E602.

B4SCALE: NO SCALE

B1 VOLTAGE DROP CALCULATIONSCALE: NO SCALE

A2 FAULT CURRENT CALCULATIONSCALE: NO SCALE

ELECTRICAL SERVICE CALCULATION

John Heck2016.01.29 13:46:23-07'00'

Page 12: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

~ ~

<5'-0"

2'-4" MINIMUM

BUILDING STRUCTURAL STEEL

NEUTRALGROUND

PANELBOARD WITHFIRST OVERCURRENTDEVICE FOR SEPARATELYDERIVED SYSTEM (SIMILARFOR ALL SUCH PANELBOARDS)

COLD WATERPIPE

GROUND NEUTRAL

DPH2AGEQUIPMENT

TRANSFORMER FORSEPARATELY DERIVEDSYSTEM (SIMILAR FORALL SEPARATELYDERIVED DRY-TYPETRANSFORMERS)

GROUND NEUTRAL

GROUND NEUTRALMAIN GROUNDINGELECTRODEGROUND BAR

TELECOMM ROOM

#4/0

#4/0

#4/0

CW HW

WATERHEATER(TYPICAL)

NEUTRALGROUND

GROUND NEUTRAL

#4/0

COLD WATER PIPE

METER &BACKFLOWPREVENTER(S)

SWITCHBOARD,DISTRIBUTION BOARDOR PANELBOARD

GROUND

#4/0

#4/0

PANELBOARD

#4/0WITH 600VINSULATION

GRADE

GROUNDING ELECTRODECONDUCTOR SCHEDULE

NOTE: ALL CONDUCTORS ARE COPPER.

SERVICECONDUCTOR

SIZE(AWG OR kCMIL)

GROUNDING ELECTRODECONDUCTOR (AWG)

NON K-RATEDTRANSFORMER

<= #2

1/0 OR 1/0

2/0 OR 3/0

OVER 3/0THROUGH 350

OVER 350THROUGH 600

OVER 600THROUGH 1100

OVER 1100

8

6

4

2

1/0

2/0

3/0

21

23

16 14

23

1416

23

23

22

20

18

19

11

23

16

21

17

23

TO MSB2

PF

R

FAA

FSTS

TTB

FACP

SHOP106

120VAC

120VAC

DC

SUP.RET.

CEILING SPACE

5

2

7

TYP.

6

TYP.

1

9

13

11

34

10

8

PIV12

TFOE

I N

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

JOHN F. HECK IV

82984

I SG

ER D

E

RET

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 12

:43:

53 P

M

E601a

ELECTRICALDIAGRAMS

Approver

IT IS THE INTENT OF THESE DOCUMENTS TO SHOW A BASIC REPRESENTATION OF THE FIRE

ALARM SYSTEM. DEVICES INDICATED ON THESE DOCUMENTS ARE IN NO WAY IMPLIED TO BE

COMPREHENSIVE OF THE FINAL DESIGN. IT IS THE RESPONSIBILITY OF THE FIRE ALARM

CONTRACTOR TO PROVIDE A DESIGN/BUILD FIRE ALARM SYSTEM BASED UPON A THOROUGH

REVIEW OF ALL CONTRACT DOCUMENTS. IT IS THE RESPONSIBILITY OF THE FIRE ALARM

CONTRACTOR TO ENSURE THAT THE FIRE ALARM SYSTEM IS CODE COMPLIANT, MEETS THE

REQUIREMENTS OF THE AHJ AND COMPREHENSIVELY COVERS AND INCLUDES ALL NECESSARY

PARTS AND LABOR ASSOCIATED WITH OTHER TRADES AND SYSTEMS IMPACTING THE FIRE ALARM

SYSTEM. NO CHANGE ORDERS SHALL BE APPROVED FOR THE BASE SCOPE OF WORK.

GENERAL SHEET NOTES

SHEET KEYNOTES

1. MINIMUM 3/4" CONDUIT WILL BE USED FOR THIS SYSTEM FIRE ALARM CABLING AS REQUIRED BY THE

FIRE ALARM MANUFACTURER.

2. INDEPENDENTLY SUPERVISE EACH FLOW AND TAMPER SWITCH WITH AN ADDRESSABLE MODULE.

REFER TO FIRE PROTECTION / PLUMBING PLANS FOR EACH LOCATION.

3. DIGITAL COMMUNICATOR FOR CENTRAL STATION MONITORING.

4. CONDUIT AND COMMUNICATIONS CABLING FOR CENTRAL STATION REPORTING.

5. FIRE ALARM SYSTEM F.A.C.P.

6. DUCT SMOKE DETECTOR, FURNISHED BY DIVISION 28, INSTALLED IN DUCT BY DIVISION 23,

CONNECTED, WIRED AND TESTED BY DIVISION 28. REFERENCE MECHANICAL CONTROL DIAGRAMS FOR

MECHANICAL INTERCONNECTIONS. PROVIDE DUCT DETECTORS IN NEW AND EXISTING UNITS WHERE

2000CFM AND ABOVE EXIST. INSTALL PER CODE.

7. FIRE SMOKE DAMPER, ROUTE 120VAC VIA FIRE ALARM ADDRESSABLE RELAY.

8. TELEPHONE TERMINAL BOARD.

9. PROVIDE NEW ANNUNCIATOR PANEL AT ENTRY. FIELD COORDINATE EXACT LOCATION.

10. PROVIDE SURGE PROTECTION FOR CIRCUIT TO FIRE ALARM PANEL.

11. REFER TO SHEET SERIES "EP" FOR CIRCUITS SERVING THIS SYSTEM.

12. PROVIDE CONNECTION TO PIV LOCATED ON SITE. PROVIDE 1" CONDUIT AND CABLING AS DICTATED BY

MANUFACTURER.

13. PROVIDE CONNECTION TO BACK FLOW PREVENTION. PROVIDE 1" CONDUIT AND CABLING AS DICTATED

BY MANUFACTURER.

14. REFER TO ONE-LINE DIAGRAM AND FEEDER SCHEDULE FOR GROUNDED CONDUCTOR SIZE.

15. CONNECT GROUNDING ELECTRODE CONDUCTOR TO GROUND ROD.

16. FOR EQUIPMENT GROUNDING CONDUCTOR SIZE REFER TO ONE-LINE DIAGRAM AND FEEDER

SCHEDULE.

17. PROVIDE GROUNDING ELECTRODE CONDUCTOR SIZE BASED ON THE CONDUCTOR SIZE OF THE

SECONDARY OF THE TRANSFORMER. SIZE PER NEC 250.66 AND PER SCHEDULE ON THIS SHEET.

18. PROVIDE A CONCRETE-ENCASED MAIN GROUNDING ELECTRODE IN THE BUILDING FOUNDATION

AROUND THE ENTIRE PERIMETER OF THE BUILDING. LOCATE ELECTRODE IN THE BOTTOM ONE-THIRD

OF THE FOUNDATION WITH AT LEAST 3 INCHES OF CONCRETE COVER. USE EITHER #4/0 BARE COPPER

CABLE OR #6 OR LARGER STEEL REINFORCING BARS MADE ELECTRICALLY CONTINUOUS USING

EXOTHERMICALLY WELDED #4/0 JUMPERS.

19. BOND EACH PERIMETER STRUCTURAL STEEL COLUMN TO THE CONCRETE-ENCASED MAIN GROUNDING

ELECTRODE. USE EXOTHERMIC WELDS.

20. PROVIDE A 1/4" X 4" X 12" "MAIN GROUNDING ELECTRODE GROUND BAR" FOR SINGLE POINT

GROUNDING. LOCATE AT AN ACCESSIBLE POINT NEAR THE SERVICE ENTRANCE EQUIPMENT. MAKE

OTHER CONNECTIONS TO THE GROUND BAR USING TWO-HOLE COMPRESSION SPADE LUGS THAT

MEET IEEE 837 REQUIREMENTS. LABEL EACH CONNECTION.

21. USE THE "MAIN GROUNDING ELECTRODE GROUND BAR" INSTEAD OF BUILDING STRUCTURAL STEEL IF

THE FIRST OVER CURRENT DEVICE FOR THE SEPARATELY DERIVED SYSTEM IS WITHIN SAME ROOM OF

THE "MAIN GROUNDING ELECTRODE GROUND BAR".

22. INSTALL A 1/4" X 4" COPPER "TELECOMMUNICATIONS GROUNDING BUSBAR" IN EACH

TELECOMMUNICATIONS ROOM. CONNECT CABLES TO THE "TELECOMMUNICATIONS GROUNDING

BUSBAR" USING COMPRESSION SPADE LUGS. LABEL CONDUCTORS PER ANSI-J-STD-607-A. LABEL

EACH CONNECTION. SEE PLAN FOR BAR LENGTH AND LOCATIONS.

23. BONDING JUMPER SIZED PER GROUNDING ELECTRODE CONDUCTOR SCHEDULE THIS SHEET.

24. BOND HOT WATER PIPE TO COLD WATER PIPE AT EACH WATER HEATER WITH A #8 BARE COPPER

CONDUCTOR.

A. FIRE ALARM DIAGRAM INDICATES GENERAL DIAGRAMMATIC CONNECTIONS ONLY. ALL CONNECTIONS

AND INSTALLATION WILL BE PER FIRE ALARM SYSTEM MANUFACTURER'S SHOP DRAWINGS.

B. DEVICE QUANTITIES ARE NOT INDICATED ON THIS DRAWING. REFER TO FLOOR PLANS FOR QUANTITIES

AND LOCATIONS.

C. REFER TO SPECIFICATION SECTION 283111 FOR FIRE ALARM SYSTEM REQUIREMENTS.

D. FIRE ALARM WIRING AND CABLING SHALL BE IN CONFORMANCE WITH NEC AND TYPE SHALL BE AS

RECOMMENDED BY FIRE ALARM SYSTEM MANUFACTURER.

E. SEAL ALL PENETRATIONS THROUGH WALLS, FLOOR, CEILINGS AND ROOF PER ARCHITECTURAL

SPECIFIED REQUIREMENTS. SEAL WILL MATCH THE FIRE RATING OF EACH PENETRATION LOCATION.

F. INSTALL GROUNDING CONNECTIONS TO BUILDING STRUCTURE AND WATER PIPES AT LOCATIONS THAT

ARE VISIBLE AND ACCESSIBLE FOR INSPECTION, MAINTENANCE, AND TESTING.

G. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH METALLIC SERVICE ENTRANCE

CONDUIT. BOND TO SERVICE ENTRANCE EQUIPMENT GROUND BUS USING GROUNDING ELECTRODE

CONDUCTOR.

H. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH METALLIC FEEDER CONDUIT. BOND TO

GROUND BUS USING CONDUCTOR THAT IS SIZED EQUAL TO EQUIPMENT GROUNDING CONDUCTOR.

I. BOND ELECTRICAL EQUIPMENT ENCLOSURES TO GROUND BAR USING SAME SIZE CONDUCTOR AS

FEEDER EQUIPMENT GROUND CONDUCTOR OR FACTORY PROVIDED GREEN SCREW.

J. CLEAN COATED RE-BAR PRIOR TO PERFORMING ELECTRICAL CONNECTION.

SCALE: NO SCALEC2 FIRE ALARM RISER DIAGRAM

A1SCALE: NO SCALE

GROUNDING DIAGRAM

John Heck2016.01.29 13:46:10-07'00'

Page 13: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

TFOE

I N

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

JOHN F. HECK IV

82984

I SG

ER D

E

RET

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 12

:43:

58 P

M

E700a

ELECTRICALSCHEDULES

Approver

Notes:

Total Est. Demand Current: 171 ATotal Conn. Current: 294 A

REC 98404 VA 55.08% 54202 VA Total Est. Demand: 61562 VA

MTR 3660 VA 100.00% 3660 VA Total Conn. Load: 105764 VA

NC 3700 VA 100.00% 3700 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 312 A 297 A 278 ATotal Load: 37124 VA 35324 VA 33316 VA

83 2880 VA 4200 VA 8481 2880 VA 4200 VA 8279

REC SHOP 106 30 A 32880 VA 4200 VA

3 50 A REC SHOP 10680

77 2880 VA 4200 VA 7875 2880 VA 4200 VA 7673

REC SHOP 106 30 A 32880 VA 4200 VA

3 50 A REC SHOP 10674

71 SPARE 30 A 1 0 VA 0 VA 7269 0 VA 0 VA 7067

SPARE 50 A 20 VA 0 VA

3 50 A MTR AC-1, EXTERIOR68

65 3640 VA 0 VA 1 20 A MTR AD-1, EXTERIOR 6663

REC DROP CARD, SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 64

61 3640 VA 2400 VA 1 30 A REC SHOP 106 6259

REC SHOP 106 50 A 23640 VA 0 VA 1 30 A SPARE 60

57 3640 VA 0 VA 1 30 A SPARE 5855

REC SHOP 106 50 A 23640 VA 0 VA 1 20 A SPARE 56

53 3640 VA 0 VA 1 20 A SPARE 5451

REC SHOP 106 50 A 23640 VA 0 VA 1 20 A SPARE 52

49 3640 VA 0 VA 1 20 A SPARE 5047

REC SHOP 106 50 A 23640 VA 0 VA 1 20 A SPARE 48

45 3640 VA 0 VA 1 20 A SPARE 4643

REC SHOP 106 50 A 23640 VA 0 VA 1 20 A SPARE 44

41 MTR RH-AH-01, SHOP 105 20 A 1 312 VA 0 VA 4239 MTR RH-AG-05, SHOP 105 20 A 1 312 VA 0 VA

2 20 A MTR CU-AG-01/FC-AG-0140

37 REC RTU-AG-01 20 A 1 312 VA 696 VA 1 20 A MTR EF-AG-04, SHOP 105 3835 MTR UH-AG-01, TOOL STORAGE 106 20 A 1 300 VA 696 VA 1 20 A MTR EF-AG-02, SHOP 105 3633 SPARE 2 A 1 0 VA 444 VA 1 20 A MTR EF-AG-01, BOYS ROOM 109 3431 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 3229 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 3027 REC SHOP 106 20 A 1 180 VA 0 VA 1 20 A SPARE 2825 REC SHOP 106 20 A 1 180 VA 0 VA 1 20 A SPARE 2623 REC SHOP 106 20 A 1 208 VA 0 VA 1 20 A SPARE 2421 REC SHOP 106 20 A 1 208 VA 0 VA 1 20 A SPARE 2219 REC SHOP 106 20 A 1 180 VA 0 VA 1 20 A SPARE 2017 REC SHOP 106 20 A 1 180 VA 360 VA 1 20 A REC EXTERIOR 1815 REC SHOP 106 20 A 1 180 VA 360 VA 1 20 A REC EXTERIOR 1613 REC SHOP 106 20 A 1 208 VA 568 VA 1 20 A REC EXTERIOR 1411 REC SHOP 106 20 A 1 180 VA 500 VA 1 20 A NC WATER FOUNTAIN, HALLWAY 101 129 REC SHOP 106 20 A 1 180 VA 900 VA 1 20 A MTR DWH-1 / ILP-1, JANITOR 108 107 NC FACP, SHOP 106 20 A 1 200 VA 1500 VA 85 REC TELECOMMUNICATIONS CABINET, STORAGE 103 20 A 1 360 VA 1500 VA

2 20 A NC HOT BOX6

3 REC ROOM 101, 106, 108, 109, 110 20 A 1 1080 VA 360 VA 1 20 A REC ROOM 104, 105, 106 41 REC ROOM 102,103,104 20 A 1 1080 VA 1080 VA 1 20 A REC ROOM 102, 104 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 84Mounting: Surface Wires: 4 Mains Rating: 400 A

Supply From: Phases: 3 Mains Type: MCBLocation: Volts: 120/208 Wye A.I.C. Rating: 10.000

Branch Panel: LAG1

LUMINAIRE SCHEDULE NOTES:

1. MANUFACTURER'S CATALOG NUMBERS REPRESENT MANUFACTURER SERIES. SHOP DRAWING SUBMITTALS WILL INCLUDE ALL PART NUMBERS REPRESENTING ALL ITEMS OF THIS LUMINAIRE SCHEDULE. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO ORDER LUMINAIRES TO INCLUDE ALL PARTS INDICATED ON SCHEDULE FOR EACH

LUMINAIRE. SUBMITTAL WILL CALL OUT EACH PART CLEARLY.

2. LUMINAIRE REQUIRES MOUNTING COORDINATION WITH ARCHITECT PRIOR TO COMMENCEMENT OF ANY WORK. THIS LUMINAIRE MAY REQUIRE A HIGHER OR LOWER MOUNTING FROM THAT PROVIDED ON THIS SCHEDULE OR NOTES ON PLAN DUE TO ARCHITECTURAL REQUIREMENTS OR CONSTRUCTION CONDITIONS.

3. ALL LUMINAIRES ON THIS LUMINAIRE SCHEDULE ARE APPROVED FOR BID ON THIS PROJECT. IF A LUMINAIRE IS SUBMITTED THAT IS NOT ON THIS SCHEDULE, IT WILL BE REJECTED.

4. SHOULD ANY LUMINAIRE BE NOT AVAILABLE AT TIME OF SUBMITTAL, CONTRACTOR WILL USE ONE OF THE OTHER LUMINAIRES INDICATED IN EACH TYPE FOR REPLACEMENT. NO OTHERS WILL BE ACCEPTED.

LUMINAIRE SCHEDULE - AG BLDGTYPE DESCRIPTION VOLTS MOUNTING LAMPS

BALLASTTYPE

EM. BAT.PK. LENS MANUFACTURER/MODEL NOTES

A1Fb 1' x 4' FLUORESCENT HIGH PERFORMANCE LUMINAIRE. LOW PROFILE SPECIFICATION

GRADE TROFFER, COLD ROLLED STEEL HOUSING WITH BAKED MATTE WHITE ENAMEL

FINISH. FLAT STEEL DOOR FRAME.

277 OR 120

MULTI-TAP

(UNV.)

CEILING RECESSED

(GYPSUM BOARD)

(2) 32W F32T8

EXTRA LONG LIFE,

3500° K,

80 CRI MIN.

ELECTRONIC

PROGRAMMED

RAPID START;

≤10% THD,

NORMAL BALLAST

FACTOR

NONE ACRYLIC PRISMATIC

A12.125

LITHONIA # SP8-F-2-32-A12125 1,3,4

ARaD 2' x 4' ARCHITECTURAL/DECORATIVE FLUORESCENT LUMINAIRE. "HIGH EFFICIENCY",

LOW PROFILE, COLD ROLLED STEEL HOUSING, BAKED MATTE WHITE ENAMEL FINISH.

277 OR 120

MULTI-TAP

(UNV.)

CEILING RECESSED

(LAY-IN GRID)

(3) 32W F32T8

EXTRA LONG LIFE,

3500° K,

80 CRI MIN.

ELECTRONIC

PROGRAMMED

RAPID START;

≤10% THD,

NORMAL BALLAST

FACTOR

NONE ACRYLIC FROSTED

CENTER BASKET

LITHONIA # 2VT8-3-32-ADP-MVOLT-GEB10PS-LP835 1,3,4

ARb 2' x 4' ARCHITECTURAL/DECORATIVE FLUORESCENT LUMINAIRE. "HIGH EFFICIENCY",

LOW PROFILE, COLD ROLLED STEEL HOUSING, BAKED MATTE WHITE ENAMEL FINISH.

277 OR 120

MULTI-TAP

(UNV.)

CEILING RECESSED

(LAY-IN GRID)

(2) 32W F32T8

EXTRA LONG LIFE,

3500° K,

80 CRI MIN.

ELECTRONIC

PROGRAMMED

RAPID START;

≤10% THD,

NORMAL BALLAST

FACTOR

NONE ACRYLIC FROSTED

CENTER BASKET

LITHONIA # 2VT8-2-32-ADP-MVOLT-GEB10PS-LP835 1,3,4

BL 4' LONG LIFE LED, HIGH ENERGY EFFICIENT LINEAR STRIP LUMINAIRE. BAKED MATTE

WHITE ENAMEL FINISH.

277 OR 120

MULTI-TAP

(UNV.)

CEILING SURFACE OR SUSPENDED

FROM JOIST OR STRUCTURE

AT 10'-0" A.F.F.

3000 LUMEN

LED, LP835,

3500° K,

80 CRI MIN.

LED DRIVER NONE WHITE ACRYLIC LITHONIA # ZL1N-L48-3000LM-FST-MVOLT-35K-80CRI-WH

METALUX # SNLED-LD1-30-UNV-LW-L835-CD-1-U

COLUMBIA # LCL4-35ML-EU

PHILIPS # LF-4-EZ-38-35-U-LAG

1,2,3,4

BVL 4' EXTREME ENVIROMENT LED, HIGH ENERGY EFFICIENT, ENCLOSED LINEAR STRIP

LUMINAIRE. INDOOR/OUTDOOR VANDAL RESISTANT WITH WIDE DISTRIBUTION.

277 OR 120

MULTI-TAP

(UNV.)

CEILING SURFACE OR SUSPENDED

FROM JOIST OR STRUCTURE

AT 10'-0" A.F.F.

4000 LUMEN LED,

LP835, 3500° K,

80 CRI MIN.

LED DRIVER NONE ACRYLIC FROSTED LITHONIA # FEM4LED-4L/35-IMAFL-SD 1,2,3,4

E LED SINGLE FACED EXIT SIGN, EMERGENCY, DIE CAST ALUMINUM HOUSING WITH

GREEN CHARACTERS, BLACK HOUSING AND BRUSHED ALUMINUM FACE

(DIRECTIONAL ARROWS AS INDICATED ON LIGHTING PLANS). MEETS UL LISTINGS

FOR THIS TYPE OF LUMINAIRE. WITH SELF-CONTAINED, SELF DIAGNOSING,

EMERGENCY BATTERY PACK.

277 OR 120

MULTI-TAP

(UNV.)

CEILING OR WALL SURFACE

8'-6" A.F.F. OR AS DIRECTED

BY ARCHITECT

LED LAMPS NONE NICKEL

CADIMUM

PER MFG.

BRUSHED ALUMINUM

FACE

LITHONIA # LE-S-1-G-ELN-SD

SURE-LITES # CX71SD

DUAL-LITE # SE-S-G-BN-E-I

EVENLITE # CCDS-EM-G-1-AB

1,2,3,4

EG LED SINGLE FACED EXIT SIGN, EMERGENCY, DIE CAST ALUMINUM HOUSING WITH

GREEN CHARACTERS, BLACK HOUSING AND BRUSHED ALUMINUM FACE

(DIRECTIONAL ARROWS AS INDICATED ON LIGHTING PLANS). MEETS UL LISTINGS

FOR THIS TYPE OF LUMINAIRE. WITH SELF-CONTAINED, SELF DIAGNOSING,

EMERGENCY BATTERY PACK. 9-GUAGE STEEL ROD WIRE GUARD PROTECTION.

277 OR 120

MULTI-TAP

(UNV.)

CEILING OR WALL SURFACE

8'-6" A.F.F. OR AS DIRECTED

BY ARCHITECT

LED LAMPS NONE NICKEL

CADMIUM PER

MFG.

BRUSHED ALUMINUM

FACE

LITHONIA # LE-S-1-G-ELN-SD-ELAWG1

SURE-LITES # CX71SD-WG10

DUAL-LITE # SE-S-G-BN-E-I-WGLX

EVENLITE # CCDS-EM-G-1-AB-M990010

1,2,3,4

EM CONTEMPORARY, LOW PROFILE EMERGENCY BATTERY PACK FIXTURE WITH AN

INJECTED MOLDED, HIGH IMPACT, UV STABILIZED THERMOPLASTIC HOUSING, ADA

COMPLIANT, ADJUSTABLE LAMP SOCKETS, SHORT CIRCUIT AND BROWNOUT

PROTECTION, SELF DIAGNOSING SYSTEM.

277 OR 120

MULTI-TAP

(UNV.)

WALL SURFACE 7'-6" A.F.F.

OR AS DIRECTED

BY ARCHITECT

(2) TWO 1.5W LED

LAMPS

LED DRIVER NICKEL

CADMIUM PER

MFG.

ACRYLIC FRESNAL LITHONIA # ELM2-LED-SD

SURE-LITES # LEM2-SD

DUAL-LITE # EV2I

EVENLITE # TCL-2-W-SD

1,2,3,4

FLE ENERGY EFFICIENT, LOW MAINTENCE, LOW PROFILE WALL MOUNTED EXTERIOR

LUMINAIRE. HIGH PERFORMANCE LED WITH SILOCONE SEALED OPTICAL CHAMBER

AND TEMPERED GLASS LENS. THROUGH LIGHTING INVERTER.

277 OR 120

MULTI-TAP

(UNV)

EXTERIOR WALL SURFACE

10'-0" A.F.F. OR AS

DIRECTED BY ARCHITECT

1800 LUMEN

LED, 4000° K,

80 CRI MIN.

LED DRIVER via INVERTER TEMPERED GLASS LITHONIA # OLWX1-LED-20W-40K

LUMARK # XTOR3A-N

ENVOY # DLC-LWP22-3500K

DECO # VINCI-LED-20-40-UNV-BZ

1,2,3,4

John Heck2016.01.29 13:46:02-07'00'

Page 14: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

TFOE

I N

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

JOHN F. HECK IV

82984

I SG

ER D

E

RET

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 12

:44:

02 P

M

E701a

ELECTRICALSCHEDULES

Approver

Notes:

Total Est. Demand Current: 194 ATotal Conn. Current: 351 A

Total Est. Demand: 69864 VA

REC 123200 VA 54.06% 66600 VA Total Conn. Load: 126464 VA

MTR 3264 VA 100.00% 3264 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 369 A 369 A 327 ATotal Load: 43600 VA 43600 VA 39264 VA

83 SPARE 20 A 1 0 VA 312 VA 1 20 A MTR RH-AG-08, SHOP 105 8481 MTR EF-AG-05, SHOP 105 20 A 1 696 VA 312 VA 1 20 A MTR RH-AG-07, SHOP 105 8279 MTR EF-AG-03, SHOP 105 20 A 1 696 VA 312 VA 1 20 A MTR RH-AG-06, SHOP 105 8077 SPARE 20 A 1 0 VA 312 VA 1 20 A MTR RH-AG-04, SHOP 105 7875 SPARE 20 A 1 0 VA 312 VA 1 20 A MTR RH-AG-03, SHOP 105 7673 SPARE 20 A 1 0 VA 312 VA 1 20 A MTR RH-AG-02, SHOP 105 7471 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 7269 0 VA 0 VA 1 20 A SPARE 7067

SPARE 50 A 20 VA 0 VA 1 20 A SPARE 68

65 0 VA 0 VA 1 20 A SPARE 6663

SPARE 50 A 20 VA 0 VA 1 20 A SPARE 64

61 0 VA 0 VA 1 20 A SPARE 6259

SPARE 50 A 20 VA 0 VA 1 20 A SPARE 60

57 0 VA 0 VA 1 20 A SPARE 5855

SPARE 50 A 20 VA 0 VA 1 20 A SPARE 56

53 0 VA 0 VA 1 20 A SPARE 5451

SPARE 50 A 20 VA 0 VA 1 20 A SPARE 52

49 0 VA 0 VA 1 20 A SPARE 5047

SPARE 50 A 20 VA 0 VA 1 30 A SPARE 48

45 0 VA 0 VA 1 30 A SPARE 4643

SPARE 50 A 20 VA 0 VA 1 30 A SPARE 44

41 SPARE 20 A 1 0 VA 2400 VA 1 30 A REC SHOP 106 4239 3640 VA 2400 VA 1 30 A REC SHOP 106 4037

REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 38

35 3640 VA 2400 VA 1 30 A REC SHOP 106 3633

REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 34

31 3640 VA 2400 VA 1 30 A REC SHOP 106 3229

REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 30

27 3640 VA 2400 VA 1 30 A REC SHOP 106 2825

REC DROP CARD, SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 26

23 3640 VA 2400 VA 1 30 A REC SHOP 106 2421

REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 22

19 3640 VA 2400 VA 1 30 A REC SHOP 106 2017

REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 18

15 3640 VA 2400 VA 1 30 A REC SHOP 106 1613

REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 14

11 3640 VA 2400 VA 1 30 A REC SHOP 106 129

REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 10

7 3640 VA 2400 VA 1 30 A REC SHOP 106 85

REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 6

3 3640 VA 2400 VA 1 30 A REC SHOP 106 41

REC SHOP 106 50 A 23640 VA 2400 VA 1 30 A REC SHOP 106 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 84Mounting: Surface Wires: 4 Mains Rating: 400 A

Supply From: Phases: 3 Mains Type: MCBLocation: Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: LAG2

ELECTRICAL CONNECTIONS FOR MECHANICAL EQUIPMENT SCHEDULE- AG BLDG

EQUIPMENTNUMBER EQUIPMENT DESCRIPTION VOLTAGE PHASE

BRANCH CIRCUITCONDUCTORDESCRIPTION C

ON

DU

IT S

IZE

MOTOR STARTERCHRACTERISTICS

DISCONNECT SWITCHCHARACTERISTICS

KEY NOTEST

AR

TE

R T

YP

E

ST

AR

TE

R S

IZE

OF

F/A

UT

O O

R H

OA

PILOTLIGHT

EXTRACONTACT

S

VO

LTS

FR

AM

E A

MP

S

FU

SE

SIZ

E

SOLIDNEUT. /

GND LUG NE

MA

RA

TIN

G

RE

D

GR

EE

N

NO NCAG-AC-1 AIR COMPRESOR 208 V 3 (4) #8 & (1) #10 GND 1 1/2" - - - - - - - 250 60 C YES 3R B,D

AG-CU-01 SPLIT SYSTEM 115 V 1 (3) #10 & (1) #10 GND 3/4" - - - - - - - 250 30 C YES 3R B,D

AG-FC-01 SPLIT SYSTEM 115 V 1 (3) #10 & (1) #10 GND 3/4" - - - - - - - 250 30 C YES 1 B,D

AG-RTU-01 ROOF TOP UNIT 480 V 3 (4) #10 & (1) #10 GND 3/4" - - - - - - - - - - - - A,B

ELECTRICAL CONNECTIONS FOR MECHANICAL EQUIPMENT SCHEDULE NOTES:

A. STARTER, CONTROL SYSTEM AND DISCONNECTING MEANS FOR UNIT WILL BE FACTORY PROVIDED. CONTRACTOR WILL HAVE ONE POINT OF ELECTRICAL CONNECTION. FOR VFD OR CONTROL EQUIPMENT INFORMATION, REFER TO SHEET SERIES M700.

B. RACEWAY SYSTEM AND CONDUCTORS FOR CONTROLS WILL BE PROVIDED BY DIVISION 26 UNLESS SPECIFICALLY CALLED OUT TO BE PROVIDED BY OTHER SECTIONS OF THESE DOCUMENTS. REFER TO SHEET SERIES "M" FOR CONTROL DIAGRAMS AND ALSO REFER TO

SPECIFICATION SECTION 230549.

C. STARTER, CONTROL SYSTEM FOR UNIT WILL BE FACTORY PROVIDED. CONTRACTOR WILL PROVIDE DISCONNECTING MEANS AND HAVE ONE POINT OF ELECTRICAL CONNECTION. FOR CONTROL EQUIPMENT INFORMATION, REFER TO SHEET SERIES M700

John Heck2016.01.29 13:45:49-07'00'

Page 15: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

TFOE

I N

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

JOHN F. HECK IV

82984

I SG

ER D

E

RET

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 12

:44:

04 P

M

E702a

ELECTRICALSCHEDULES

Approver

Notes:

Total Est. Demand Current: 12 A

LTG-EXT 180 VA 125.00% 225 VA Total Conn. Current: 11 A

LTG 4358 VA 125.00% 5448 VA Total Est. Demand: 10083 VA

MTR 4210 VA 100.00% 4210 VA Total Conn. Load: 8948 VA

NC 200 VA 100.00% 200 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 14 A 13 A 9 ATotal Load: 3651 VA 3394 VA 2390 VA

41 SPACE ONLY -- -- 0 VA 0 VA 42

39 SPACE ONLY -- -- 0 VA 0 VA 40

37 SPACE ONLY -- -- 0 VA 0 VA

3 225 A PANEL LAG1 VIA TAG2

38

35 SPACE ONLY -- -- 0 VA 0 VA 36

33 SPACE ONLY -- -- 0 VA 0 VA 34

31 SPACE ONLY -- -- 0 VA 0 VA

3 225 A PANEL LAG1 VIA TAG1

32

29 SPACE ONLY -- -- 0 VA 0 VA -- -- SPACE ONLY 30

27 SPACE ONLY -- -- 0 VA 0 VA -- -- SPACE ONLY 28

25 SPACE ONLY -- -- 0 VA 0 VA -- -- SPACE ONLY 26

23 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 24

21 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 22

19 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 LTG ROOMS 20 A 1 1380 VA 0 VA 1 20 A SPARE 14

11 LTG SHOP 105 20 A 1 490 VA 0 VA 1 20 A SPARE 12

9 LTG SHOP 105 20 A 1 488 VA 500 VA 1 20 A BATTERY INVERTER, ELEC 107 10

7 LTG SHOP 105 20 A 1 488 VA 200 VA 1 20 A NC TIME CLOCK, ELEC 107 8

5 LTG SHOP 105 20 A 1 497 VA 1403 VA 6

3 LTG SHOP 105 20 A 1 1003 VA 1403 VA 4

1 LTG-EXT EXTERIOR BUILDING LIGHTING 20 A 1 180 VA 1403 VA

3 20 A MTR RTU-AG-01, EXTERIOR

2CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 Spaces: 84Mounting: Surface Wires: 4 Mains Rating: 400 A

Supply From: Phases: 3 Mains Type: 400A MCBLocation: Volts: 480/277 Wye A.I.C. Rating: 22,000

Branch Panel: DPHAGROOM 107

"MSB2"

John Heck2016.01.29 13:45:40-07'00'

Page 16: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

A B C D E F G

1

2

3

4

5

K-3544HIGHLINE

C_TOILETS

VITREOUS CHINA

K-3544HIGHLINE

C_TOILETS

VITREOUS CHINA

K-3544HIGHLINE

C_TOILETS

VITREOUS CHINA

P1a P1a

P2P1

P5

P4

P3

P3P3

P3FD1

FD1

~

SA

N

SAN

4" SAN

2" SAN

4" SAN

4" SAN

4" VTR

V

V

2" V

2" V

DCOTG

AG-RTU-01

AG-CU-01

CD

3/4" CD

AG-FC-01

AG-RH-05 AG-RH-06 AG-RH-07 AG-RH-08

AG-EF-05AG-EF-04

AG-RH-01AG-RH-02

AG-RH-02

AG-RH-04

AG-EF-03AG-EF-02

105

SHOP

101

HALLWAY

102

CLASSROOM

103

STORAGE

104

OFFICE

110

GIRLS109

BOYS

108

JANITOR

106

TOOLSTORAGE

107

ELEC./COMP.

P7

SAN

4" SAN

2" SAN

1 1/2" VV

TFOE

C

I N

EI

L D

ESN

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

ABBAS SHIRIAN

102840

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 11

:44:

05 A

M

PL101

AG SHOP WASTE& VENT PLAN

AS

GENERAL SHEET NOTES

SHEET KEYNOTES

1. ROUTE PIPING BELOW FLOOR.

2. ROUTE PIPING ABOVE CEILING.

3. ROUTE PIPING BELOW GRADE.

4. SEE CIVIL DRAWINGS FOR CONTINUATION.

5. CONDENSATE DRAIN FROM ROOF TOP UNITS (RTU) SHALL DRAIN TO GRADE IN CODE COMPLIANT

MANNER.

6. CONDENSATE DRAIN FROM AC UNIT SHALL DRAIN TO SERVICE IN CODE COMPLIANT MANNER.

A. SEE SHEET P702 FOR PLUMBING FIXTURE ROUGH-IN SCHEDULE.

B. ALL VERTICAL SANITARY PIPING ABOVE FINISHED FLOOR SHALL HAVE WALL CLEANOUT INSTALLED.

SCALE: 1/8" = 1'-0"A1 AG SHOP WASTE & VENT PLAN

1

12

2

2

3

4

5

6

0' 4' 8' 16'

NORTH

Abbas2016.01.29 11:57:13-07'00'

Page 17: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

A B C D E F G

1

2

3

4

5

K-3544HIGHLINE

C_TOILETS

VITREOUS CHINA

K-3544HIGHLINE

C_TOILETS

VITREOUS CHINA

K-3544HIGHLINE

C_TOILETS

VITREOUS CHINA

AG-RTU-01

AG-EF-02 AG-EF-03

AG-RH-01

AG-RH-02 AG-RH-02

AG-RH-04

AG-RH-05 AG-RH-06 AG-RH-07AG-RH-08

AG-EF-05AG-EF-04

AG-CU-01

AG-FC-01

AG-UH-01

AG-EF-01

P1a P1a

P2P1

P10

P9

P3

P3P3

P3

DWH-1

P14

DCWDHW

DC

W

DH

WR

DH

W

~

2" DCW

2" DCW

2" DCW2" DCW1" DHW 3/4" DHWR

~

G G

G

G G G

2 1/2" G

1/2" G

2" G

G

2" G 1 1/2" G 1 1/2" G

2" G

1 1/2" G

1 1/2" G

G

1 1/4" G

P16

3/4" DCW

P16

3/4" DCW

3/4" A

3/4" A

2" A

105

SHOP

101

HALLWAY

102

CLASSROOM

103

STORAGE

104

OFFICE

110

GIRLS109

BOYS

108

JANITOR

106

TOOLSTORAGE

107

ELEC./COMP.

TFOE

C

I N

EI

L D

ESN

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

ABBAS SHIRIAN

102840

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 11

:39:

15 A

M

PP101

AG SHOPPRESSUREPIPING PLAN

AS

GENERAL SHEET NOTES

SHEET KEYNOTES

1. ROUTE PIPING ABOVE CEILING.

2. ROUTE PIPING HIGH IN CEILING SPACE.

3. ROUTE PIPING BELOW GRADE.

4. SEE CIVIL DRAWINGS FOR CONTINUATION.

5. GAS METER/REGULATOR SIZED FOR ____CFH WITH AN ENTERING HIGH PRESSURE AND LEAVING

PRESSURE OF 14" WC. INSTALL PETES PLUGS ON BOTH SIDES OF REGULATOR. REGULATOR SHALL BE

VENT LIMITING TYPE.

6. SEE DETAIL ____ FOR AIR COMPRESSOR DETAIL.

7. VERIFY EXACT LOCATION OF EXISTING GAS LINE.

8. CONDENSATE DRAIN FROM AIR COMPRESSOR SHALL DRAIN TO GRADE IN CODE COMPLIANT MANNER.

9. PROVIDE 18" X 18" ACCESS DOOR.

10. ROUTE FULL SIZE T&P DRAIN RELIEF VALVE TO MOP SINK.

11. FIRE SPRINKLER ALARM VALVE.

A. SEE SHEET P702 FOR PLUMBING FIXTURE ROUGH-IN SCHEDULE.

B. PROVIDE GAS SHUT-OFF VALVE DIRTLEG AND UNION AT GAS FIRED EQUIPMENT.

SCALE: 1/8" = 1'-0"A1 AG SHOP PRESSURE PIPING PLAN

4

7

2

2

22

1

1

1

2

33

3 5

4

9

10

11

8

6

2

0' 4' 8' 16'

NORTH

Abbas2016.01.29 11:57:44-07'00'

Page 18: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

4

5

1

5 5

2

3

6

1

2

3

4

5

6

AMES IN-BUILDING RISER. STAINLESS

STEEL TYPE 304. SEE PLANS FOR SIZE AND

SERVICE

DUCTILE, CAST-IRON, OR PVC WATER

SERVICE.

MECHANICAL JOINT FROM SUPPLY PIPE TO

STAINLESS STEEL, CONTINUE INTO

BUILDING WITH STAINLESS STEEL.

CONCRETE THRUST BLOCK SIZED IN

ACCORDANCE WITH UBC IF REQUIRED BY

AHJ

PIPE SLEEVE, SEE SPECIFICATIONS

MEGALUG PIPE RESTRAINT HARNESS

FLOW

4

1

2

3

4

5

6

1

5 5

2

3

6

AMES IN-BUILDING RISER. STAINLESS

STEEL TYPE 304. SEE PLANS FOR SIZE AND

DUCTILE, CAST-IRON, OR PVC WATER

MECHANICAL JOINT FROM SUPPLY PIPE TO

STAINLESS STEEL, CONTINUE INTO

BUILDING WITH STAINLESS STEEL

CONCRETE THRUST BLOCK SIZED IN

ACCORDANCE WITH UBC IF REQUIRED BY

PIPE SLEEVE, SEE SPECIFICATIONS

MEGALUG PIPE RESTRAINT HARNESS

FLOW

1

2

3

4

5

6

7

8

9

10

11

12

13

14

16

4

13

2

12

7

3

2

9

10

5

911

7

8

#

#

#

#

#

#

#

#

#

#

14

FINISH FLOOR

DCW

DHW

DCW

DHW

SAN

NOTE: INSTALL THERMOSTATIC MIXING VALVE ASSEMBLY

IN ACCORDANCE WITH MANUFACTURERS

RECOMMENDATION. PROVIDE PIPING SCHEMATIC WITH

SUBMITTALS

DHC

DHC

G

G

D

EXPANSION TANK P#

FULL SIZED T&P RELIEF VALVE

INDIRECTLY DISCHARGED TO FLOOR SINK,

2X PIPE DIA.

PLUG VALVE W/DIRT LEG

THERMOMETER (TYPICAL)

THERMOSTATIC MIXING VALVE P#

IN-LINE PUMP ILP-#

SEISMIC STRAPPING PER UPC 508.2

(IF REQUIRED)

4" MIN. HOUSEKEEPING PAD

CIRCUIT SETTER/BALANCING VALVE

PETE'S PLUGS (TYPICAL)

HEAT TRAP PER MFG. SPEC'S

UNION (TYPICAL)

COMBUSTION AIR INTAKE AND FLUE BY

MECHANICAL

DOMESTIC WATER HEATER, SEE SPEC'S

6" MIN.## GPM

## GPM

#

#

#

#

#

#

#

#

#

#

1

2

3

4

5

6

7

8

9

10

19

2

8

3

44

106 7 5

SERVICE LINE, SEE SPECIFICATIONS FOR PIPE

MATERIALS.

SAME SIZE AS SERVICE LINE,

THRU 4" PIPE, MAXIMUM 4"

SIZE REQUIRED.

CAST IRON SOIL PIPE RISER

AND FITTINGS.

COMPACTED EARTH, SEE

SPECIFICATIONS.

CLEANOUT WITH HEAVY DUTY SCORIATED

SECURED TOP .

FINISH HARDSCAPE. SEE SITE PLAN

DRAWINGS FOR ELEVATION.

18"X18"X4" THICK CONCRETE COLLAR.

1/8TH BEND.

WYE FITTING.

2" CHAMFER ON ALL COLLARS IN EARTH.

FLOW

7 5

1

2

3

4

5

6

7

8

9

10

8 5 6

44 2

3

9

101

9

10

SERVICE LINE, SEE SPECIFICATIONS FOR

PIPE MATERIALS.

SAME SIZE AS SERVICE LINE,

THRU 4" PIPE, MAXIMUM 4"

SIZE REQUIRED.

CAST IRON SOIL PIPE RISER

AND FITTINGS.

COMPACTED EARTH, SEE

SPECIFICATIONS.

12"-18"

CLEANOUT WITH HEAVY DUTY SCORIATED SECURED TOP .

2" CHAMFER ON ALL COLLARS IN EARTH.

FINISH HARDSCAPE. SEE SITE PLAN DRAWINGS

FOR ELEVATION.

4" THICK CONCRETE PAD.

1/8TH BEND.

WYE FITTING.

FLOW

CLEANOUT PLUG

W/LEAD SEAL

STAINLESS STEEL

ACCESS COVER W/

COUNTERSUNK SCREW

FINISHED WALL

CLEANOUT TEE1

2

3

4

5

6

7

8

2 6

1

3 5

7

4

8

TRAP GUARD WATER SAVING DEVICE

SIZED PER DRAIN (IF SPECIFIED)

FINISHED FLOOR SLOPED IN

ACCORDANCE WITH ARCH.

DRAWINGS. COORDINATE WITH

STRUCTURAL

SEE PLUMBING FLOOR PLANS FOR

SIZING AND P-TRAP REQUIREMENTS

FOUR BAND HEAVY DUTY CLAMP, SEE

SPECIFICATIONS

FLOOR DRAIN WITH ADJUSTABLE

STRAINER, DOUBLE DRAINAGE

FLANGE AND WEEP HOLES. SEE

FLOOR DRAIN SPECIFICATIONS

CLAMP TO 24"x24" 4# LEAD SHEET AND

WATERPROOFING MEMBRANE (NOT

REQUIRED FOR SINGLE POUR

CONSTRUCTION)

CONCRETE FLOOR OF TWO POUR

CAULK AS REQUIRED ON

INSTALLATION ABOVE GRADE

TFOE

C

I N

EI

L D

ESN

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

ABBAS SHIRIAN

102840

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 11

:44:

56 A

M

P500a

PLUMBINGDETAILS

AS

SCALE: 1/4" = 1'-0"1 WATER ENTRY THRU FOOTINGSCALE: 1/4" = 1'-0"2 WATER ENTRY BELOW FOOTING

SCALE: 1/4" = 1'-0"3 $P-06-23 DOMESTIC WATER HEATER Copy 1

SCALE: 1/4" = 1'-0"4 CLEANOUT TO GRADESCALE: 1/4" = 1'-0"5 DOUBLE CLEANOUT TO GRADE

SCALE: 1/4" = 1'-0"6 WALL CLEANOUTSCALE: 1/4" = 1'-0"7 FLOOR DRAIN

Abbas2016.01.29 11:57:27-07'00'

Page 19: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

P1 WATER CLOSET:

TYPE: FLOOR MOUNT, SIPHON JET, 1-1/2" TOP-SPUD, 1.28 GALLON PER FLUSH, ELONGATED,

VITREOUS CHINA,

MFG: KOHLER NO. K-4405 "HIGHLINE".

SEAT: SOLID PLASTIC, OPEN FRONT, FIRE RETARDANT, ELONGATED, WITHOUT COVER,

STAINLESS STEEL CHECK HINGE.

MFG: OLSONITE NO. 95.

FLUSH VALVE: EXPOSED, MANUAL, CHROME PLATED, DIAPHRAGM TYPE, FLUSHOMETER, 1.28 GALLON

PER FLUSH.

MFG: SLOAN NO. 111-1.28 "ROYAL"

CARRIER: ZURN, WADE JOSAM OR SMITH (1,000 LBS. CAPACITY)

MTD. HEIGHT: SEE ARCHITECTURAL DRAWINGS.

PLUMBING FIXTURE SPECIFICATIONS

SYMBOL DESCRIPTION

P2 URINAL:

TYPE: WALL MOUNTED, SIPHON JET FLUSHING, VITREOUS CHINA, 3/4" TOP SPUD, LOW

CONSUMPTION, 0.125 GALLON PER FLUSH.

MFG: KOHLER K-4904-ET "BARDON"

CARRIER: FLOOR SUPPORTED, CONCEALED IN WALL.

MFG: ZURN, WADE, JOSAM OR SMITH.

FLUSH VALVE:EXPOSED, MANUAL, CHROME PLATED FLUSHOMETER.

0.125 GALLON PER FLUSH.

MTD HEIGHT: SEE ARCHITECTURAL DRAWINGS.

P2a URINAL (HANDICAP):

TYPE: SAME AS P2 EXCEPT MOUNTING HEIGHT. SEE ARCH. PLANS.

P5 DRINKING FOUNTAIN (HANDICAP):

TYPE: WALL HUNG, ADA COMPLIANT, BI-LEVEL, FRONT PUSH BUTTON, 18 GA. STAINLESS

STEEL, VANDAL RESISTANT CHROME PLATED BUBBLER, VANDAL RESISTANT

BOTTOM PLATES, INLINE STRAINER, WITH BOTTLE FILLING STATION.

MFG: ELKAY EZH20 VRCGRNTL8WSK

ACCESSORY: APRON LKAPREZL

SUPPLIES: 1/2" X 3/8" WHEEL ANGLE STOPS WITH 3/8" O.D. FLEX RISERS.

TRAP: 1-1/4" 17 GA. POLISHED CHROME TUBULAR P-TRAP.

CARRIER:CONCEALED BY ZURN, WADE, JOSAM, OR SMITH.

MTD HEIGHT: SEE ARCHITECTURAL DRAWINGS.

P4 SERVICE SINK:

TYPE: FLOOR MOUNTED, 24" X 24" X 10" DEEP, MOLDED STONE, 3" DRAIN OPENING.

MFG: FIAT NO. MSB-2424.

FAUCET: POLISHED CHROME, WALL MOUNTED 42" ABOVE FLOOR, WALL BRACE, VACUUM

BREAKER, INTEGRAL CHECK STOPS.

MFG: CHICAGO NO. 897-CP-C.

DRAIN: INTEGRAL WITH STAINLESS STEEL STRAINER.

TRAP: 3" CAST IRON "P" TRAP.

ACCESSORIES: HOSE AND HOSE BRACKET NO. 832AA, STAINLESS STEEL, 24" X 3" MOP HANGER NO.

889-CC, VINYL BUMPER GUARD NO. E-77-AA.

P7 WATER HAMMER ARRESTOR:

TYPE: STAINLESS STEEL CONSTRUCTION, PRE-CHARGED, PERMANENTLY SEALED.

SEE SHOCK ABSORBER SCHEDULE FOR UNIT SIZE

MFG: JAY R. SMITH 5000 SERIES.

NOTE: PROVIDE AND INSTALL BEHIND LOCKING 14"X14" ACCESS PANEL.

P8 EXPANSION TANK:

TYPE: PRE-PRESSURED TANK WITH SEALED-IN AIR CHARGE OF 55 PSI.

SIZE: 53 GAL, TOTAL VOLUME, 0.65 MAX. ACCEPTANCE.

MFG: AMTROL NO. ST-80V-C.

P9 WALL HYDRANT:

TYPE: BRONZE HYDRANT, FREEZE-PROOF, INTEGRAL VACUUM BREAKER, WITH LOOSE-KEY,

3/4" INLET AND 3/4" GARDEN HOSE OUTLET, LOOSE KEY HANDLE, VERIFY WALL

THICKNESS BEFORE ORDERING.

MFG: ZURN NO. Z-1310.

TMV THERMOSTATIC MIXING ASSEMBLY (DOMESTIC HOT WATER):

TYPE: HIGH LOW DUAL STAGE THERMOSTATIC WATER MIXING SYSTEM SET FOR 120F.

LARGE AND SMALL TYPE THERMOSTATIC WATER MIXING VALVES, ADJUSTABLE

HIGH TEMPERATURE LIMIT STOP, INLET CHECKSTOPS, WALL SUPPORT, OUTLET

BALL VALVE, 1 GPM MINIMUM FLOW CAPACITY, INLET MANIFOLD PIPING, OUTLET

PRESSURE REGULATING VALVE AND PRESSURE GAUGES, COLOR-COATED

DIAL THERMOMETER (0 TO 140F), FACTORY ASSEMBLED AND TESTED, ROUGH

FINISH.

INLET: 3".

OUTLET: 3".

MFG: LEONARD NO. TM-186-20015020-PRV-RF.

FD1 FLOOR DRAIN:

TYPE: 7" DIAMETER, ROUND TYPE "B" STRAINER. POLISHED BRONZE, CAST IRON BODY WITH

BOTTOM OUTLET, COMBINATION INVERTABLE MEMBRANE CLAMP, DEEP SEAL P-TRAP,

VANDAL-PROOF SECURED TOP, DIAMETER OF OUTLET AS SHOWN ON DRAWINGS.

MFG: ZURN NO. Z-415-B-VP-Z1000.

NOTE: PROVIDE WITH PROSET TRAP GUARD WATER SAVING DEVICE. SIZE AS INDICATED BY

DRAIN.

FS1 FLOOR SINK:

TYPE: CAST IRON BODY WITH WHITE ACID RESISTING ENAMEL BODY INTERIOR, SLOTTED 3/4

LOOSE SET GRATE ALUMINUM ANTI-SPASH DOME STRAINER, DEEP SEAL P-TRAP,

DIAMETER OF OUTLET AS SHOWN ON DRAWINGS.

MFG: ZURN NO. Z-1901-Z1000.

NOTE: PROVIDE WITH PROSET TRAP GUARD WATER SAVING DEVICE. SIZE AS INDICATED BY

DRAIN.

RPZ REDUCED PRESSURE BACKFLOW PREVENTER:

TYPE: 2-1/2" SIZE WITH THREADED CONNECTION, COMPLETE WITH 2 SPRING LOADED CHECK

VALVES, BALL VALVES, TEST COCKS. 12 PSI LOSS AT 80 GPM.

SERVICE:MECH. COOLING TOWER MAKE-UP.

MFG: FEBCO NO. 860Y-AGD.

NOTE: AIR GAP DRAIN SHALL BE PIPED TO NEAREST FLOOR DRAIN, FLOOR SINK, OR AS

INDICATED ON DRAWINGS.

P1a WATER CLOSET (PUBLIC RESTROOMS-HANDICAP):

TYPE: SAME AS Pb EXCEPT MOUNTING HEIGHT. SEE ARCH. PLANS.

P3 LAVATORY (HANDICAP):

TYPE: WALL HUNG, VITREOUS CHINA, 21" X 18" OVERALL DIMENSIONS, 3-HOLE, 4"CENTERS.

MFG: KOHLER NO. K-2005 "KINGSTON".

FAUCET: 4" CENTERS, METAL WRISTBLADE HANDLES, CHROME PLATED, 0.5 GPM LAMINAR FLOW

AERATOR

MFG: CHICAGO No. 802-317CP

SUPPLIES: 1/2" SWEAT WHEEL HANDLE ANGLE STOPS WITH 3/8" O.D. FLEXIBLE RISERS, CHROME

PLATED FINISH.

TRAP: 1-1/4" IN X 1-1/2" OUT, 17 GA, CHROME PLATED, ADJUSTABLE, CLEANOUT PLUG, SEMI-CAST P-TRAP.

MFG: MCGUIRE NO. 8902.

MTD HEIGHT: SEE ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHT.

NOTE: INSULATE SUPPLY AND WASTE PIPING PER SPECIFICATIONS.

P6 MULTI-STATION HAND SINK:

TYPE: WALL HUNG, 5-STATION, 140 GA. 304 STAINLESS STEEL, ADJUSTABLE LEGS. MOUNTING BRACKET, 102"L X 18"W, 4" CENTER.

MFG: BRADLEY NO. S96-051 (6951A-5)

SERVICE RQRS:SUPPLY AND WASTE, 1-1/4" IPS. SUPPLY VALVE HANDLES REMOVED OR LOCKED OPEN.

FAUCET: 4" CENTER, 4" UNTEGRAL SPOUT, CHROME PLATED, METAL WRISTBLADE HANDLES, 0.5 GPM VANDAL-PROOF AERATOR.

MFG: CHICAGO NO. 802-VE2805-317ABCP

SYMBOLSYMBOL

FLOOR DRAIN/SINK SPECIFICATIONS

SYMBOL DESCRIPTION

PLUMBING FIXTURE SPECIFICATIONSPLUMBING FIXTURE SPECIFICATIONS

PLUMBING ROUGH-IN SCHEDULE

LAVATORY - HANDICAP

SERVICE SINKP4

P3

URINAL

SYMBOL

P2

P1

DESCRIPTION TRAP

WASTE

FLOOR MOUNTED, CORNER TYPE, INTEGRAL CHECK STOPS

1-1/2"

REMARKS

WALL MOUNT, ELECTRONIC FLUSH VALVE, 0.125 GPF

HWCW

VENT

3/4" WALL MOUNT, ELECTRONIC FLUSH VALVE, 0.125 GPFP2a URINAL - HANDICAP

NON-FREEZEP9 WALL HYDRANT

WATER CLOSET - HANDICAP FLOOR MOUNT, CONCEALED MANUAL FLUSH, 1.6 GPF

COUNTERTOP, MANUAL FAUCET, 0.5 GPM LAMINAR AERATOR

PDIP7 WATER HAMMER ARRESTOR INSTALL IN 14"X14" ACCESS PANEL

P1a WATER CLOSET - HANDICAP FLOOR MOUNT, CONCEALED MANUAL FLUSH, 1.6 GPF1"

DRINKING FOUNTAINP5 BI-LEVEL HANDICAPPED ACCESSIBLE

MULTI-STATION HAND SINKP6 WALL HUNG, STAINLESS STEEL

P8 EXPANSION TANK CENTRAL STERILE IHW SYSTEM

-

-

-

-

1/2"

-

1/2"

-

-

-

1/2"1/2"

3/4"

3/4"

3/4"

1/2"

1/2"

3/4"

1" 4"

4"

2"

2"

2"

2"

2"

-

-

-

2"

ROUGH-IN SIZE

2"

2"

2"

2"

1-1/2"

2"

-

-

-

2"

INTEGRAL

INTEGRAL

INTEGRAL

INTEGRAL

1-1/4" X 1-1/2"

1-1/4"

3"

-

-

-

1-1/2" X 1-1/2"

DOMESTIC WATER HEATER SCHEDULE

SYMBOL LOCATION MANUFACTURER/MODEL No.SERVICE SET

POINTTYPE STORAGE

ELECTRICAL DATAOPERATING

WEIGHT POWER

HW RECOVERY

GPH RATE TEMP.RATE

REMARKS

ALL SELECTIONS BASED ON5300 FT. ELEVATION

DWH-1 MECHANICAL RM 140° NATURAL GAS BOCK MODELNo: OT200N-A

100 GAL 253 90°1353 LBS INSTALL ON 4" HOUSE KEEPING PAD, ROUTE T&PRELIEF VALVE TO NEAREST FLOOR SINK,PROVIDE CONDENSATE NEUTRALIZATION KIT

120

PHHz

160

PUMP SCHEDULE

SYMBOL DESCRIPTION MANUFACTURER/MODEL No.

LOCATIONELECTRICAL DATA

TOTAL HEAD(FT) RPM MOTOR HP VOLT

REMARKS

ALL SELECTIONS BASED ON5300 FT. ELEVATION

TYPE FLOWPHASE AMPS

BASIN SIZE

N/AILP-1 INLINE PUMP SIMPLEX 4.5 GPM 35 TACO: 0013-BF33250 1151/6 1 2.0 120° DOMESTIC HOT WATER RETURN, BRONZE FLANGED, 3/4"CONNECTION SIZE. COORDINATE CONNECTION OF BMS WITH

ELECTRICAL

Kw

-120°

BTUH

199,000

MECHANICAL RM

TFOE

C

I N

EI

L D

ESN

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

ABBAS SHIRIAN

102840

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DATE

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

01.29.2016

Addendum 01

DATE

1/29

/201

6 11

:45:

32 A

M

P700a

PLUMBINGSCHEDULES

AS

Abbas2016.01.29 11:57:02-07'00'

Page 20: 7390 MEP - VISD VEGA HS NZhiani - Sheet - M001a - … · 2016. 2. 2. · for ductwork, grilles, registers and diffusers. all pipe and ductwork penetrations of fire, smoke and full

A B C D E F G

1

2

3

4

5

K-3544HIGHLINE

C_TOILETS

VITREOUS CHINA

K-3544HIGHLINE

C_TOILETS

VITREOUS CHINA

K-3544HIGHLINE

C_TOILETS

VITREOUS CHINA

2

2

2

2

IC

S

IC

S

IC

S

IC

S

IC

S

C

S

IC

105

SHOP

101

HALLWAY

102

CLASSROOM

103

STORAGE

104

OFFICE

110

GIRLS109

BOYS

108

JANITOR

106

TOOLSTORAGE

107

ELEC./COMP.

T02

T01

T29

T06

T30TO IDF141

T31

TFOE

I N

SAXATS

E

RE

ENIGN

LAOSSEFO

RP

ET

JOHN F. HECK IV

82984

I SG

ER D

E

RET

PROJECT

1

A

2 3 4 5

B

C

D

1 2 3 4 5

SEAL

REVISIONS

SHEET NO

DRAWING NAME

PROJECT NO:

REVIEWED BY

DRAWN BY

VE

GA

ISD

CA

RE

ER

TE

CH

NO

LOG

Y B

UIL

DIN

G20

0 LO

NG

HO

RN

ST

.V

EG

A, T

X 7

9 092

14-0424.002

TBD

1/29

/201

6 10

:25:

32 A

M

T101

AG SHOPTECHNOLOGYSYSTEMS PLAN

Approver

Author

GENERAL SHEET NOTES

SHEET KEYNOTES

SCALE: 1/8" = 1'-0"A1 AG SHOP TECHNOLOGY SYSTEMS PLAN0' 4' 8' 16'

NORTH

1 01/29/16 ADDENDUM#01

T01 INTERCOM CALL SWITCH. REFER TO SPECIFICATIONS SECTION 27 5123.50 FORADDITIONAL REQUIREMENTS.

T02 WALL MOUNTED CLOCK/SPEAKER COMBO. REFER TO SPECIFICATIONS SECTION27 5313 FOR ADDITIONAL REQUIREMENTS.

T06 PAGING LOUDSPEAKER FOR DISTRIBUTED INTERCOM/PAGING SYSTEM.COORDINATE SIGNAL PULL BOX TYPE AND ROUGH-IN LOCATION WITHEQUIPMENT INSTALLER PRIOR TO COMMENCING ANY WORK. REFER TOSPECIFICATIONS SECTION 27 5123 AND DETAILS ON SHEET T504 FORADDITIONAL REQUIREMENTS.

T29 4-11/16" X 2-5/8" SQ TELECOMMUNICATIONS OUTLET BOX WITH 1" EMT STUB UPTO NEAREST ACCESSIBLE CEILING SPACE. REFER TO GENERAL NOTES FORADDITION REQUIREMENTS.

T30 PROVIDE 36" X 24" X 30" WALL MOUNTED ENCLOSURE. CUBE-IT CPI # 12419-236.MOUNT 32" AFF BOTTOM OF CABINET. PROVIDE FAN KIT CPI # 12804-701.PROVIDE PATCH PANELS AND HORIZONTAL WIRE MANAGEMENT AS NEEDED.

T31 REFERENCE CONDUIT PATHWAY CONTINUATION ON SHEET ES101.

A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS

PER OWNER, CODE, AND AHJ.

B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES.

C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR

PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING.

D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.

E. ALL COMMUNICATIONS CABLING TO MEET OR EXCEED CAT6 STANDARDS.

F. TELECOMMUNICATIONS OUTLETS TO BE MOUNTED AT +18" A.F.F. (BOTTOM OF BOX) UNLESS OTHERWISE

NOTED. FOR EXAMPLE, DEVICES SPECIFIED AT +18" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT

FOR POWER RECEPTACLES AND TELECOMMUNICATIONS OUTLETS. DEVICES SPECIFIED AT + 48" A.F.F.

SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR LIGHT SWITCHES ETC.

G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL, THINWALL ELECTRICAL METALLIC

TUBING (TYPE EMT) UNLESS OTHERWISE NOTED. UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE

USED FOR PATHWAYS INDICATED ON THIS SHEET. ALL CONDUITS ARE TO BE, AT A MINIMUM, 1” TRADE SIZE,

UNLESS OTHERWISE NOTED. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO

NEAREST CABLE TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL.

H. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL

OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE

SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED.

LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER

SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE

SYSTEMS.

I. NUMBER ADJACENT TO TELECOMMUNICAITONS OUTLET SYMBOL REPRESENTS NUMBER OF CAT 6 CABLES

TO BE INSTALLED AND TERMINATED AT THAT LOCATION. A "B" ADJACENT TO AN OUTLET LOCATION

REPRESENTS A ROUGH-IN ONLY LOCATION, PROVIDE BOX, CONDUIT, AND BLANK FACEPLATE.

J. FOR ALL EXTERIOR WALL-MOUNTED DEVICES, PROVIDE BACKBOX AND EXTENSION RING, TOTAL DEPTH AS

REQUIRED TO MATCH THICKNESS OF COMPLETE WALL & INSULATION ASSEMBLY.

K. WIRELESS ACCESS POINTS IN GYMNASIUM WILL HAVE WIRE GUARDS.

L. ALL CONDUIT TURNS FOR A/V AND IT CONDUITS SHALL BE "SWEEP" TYPE, NO BEND FITTINGS ARE

PERMITTED.

M. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS

OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX.

N. CONTRACTOR TO VERIFY ALL CABLE COUNTS AND NUMBER OF PATCH PANELS REQUIRED.

O. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES

SHEETS FOR POWER OUTLET LOCATIONS.

P. FOR ALL OUTLETS INSTALLED IN ARTS/MUSIC/DRAMA AREAS, CLASSROOMS, LABS, MISC. LEARNING AREAS,

OFFICES AND OTHER ACOUSTICALLY-RATED PARTITIONS (AS INDICATED ON ARCHITECTURAL DRAWINGS):

MAINTAIN A MINIMUM OF 12 INCHES SEPARATION BETWEEN OUTLETS ON OPPOSITE SIDES OF PARTITION.

PROVIDE ACOUSTICAL OUTLET BACKER PUTTY (AS MANUFACTURED BY KINETICS NOISE CONTROL, OR

EQUAL). PUTTY PADS SHALL MAINTAIN ACOUSTICAL RATINGS PER ASTM C 919 AND ASTM E 497, AND BE

TESTED TO UL 263 (ASTM E119) AND UL 1479 (ASTM E814) STANDARDS.