© ABB GroupMay 13, 2010 | Slide 1 | 1MRS756700 B
Relion® 615 series Ver 2.0General Presentation
ABB Oy Distribution Automation
© ABB Group May 13, 2010 | Slide 2
Relion® 615 series Contents
The 615 series of IEDs
Common features of the 615 series
Feeder Protection and Control REF615
Line Differential Protection and Control RED615
Transformer Protection and Control RET615
Motor Protection and Control REM615
Conclusions
© ABB Group May 13, 2010 | Slide 4
Relion® 615 seriesProducts
The 615 series IEDs (intelligent electronic devices) members of ABB’s Relion® product family
The 615 series IEDs are characterized by their compactness and withdrawable design
615 series products:
Feeder Protection and Control REF615
Line Differential Protection and Control RED615
Transformer Protection and Control RET615
Motor Protection and Control REM615
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 6
Relion® 615 series IEC 61850 based connectivity and interoperability
Native support for IEC 61850 communication between devices in substations (including GOOSE messaging)
Meets the GOOSE requirements for tripping applications in distribution substations as defined by the IEC 61850 standard
The 615 series also supports:
Modbus TCP/IP and RTU / ASCII
DNP3 TCP/IP and serial
IEC 60870-5-103
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 7
Relion® 615 seriesPatented plug-in design
Speeds up installation, maintenance and testing of the protection
Contributes to a shortened MTTR (mean time to recover)
Allows the cases to be installed and wired before the plug-in units are delivered
Mechanical coding system for preventing insertion of a wrong plug-in unit in a case
Sealable pull-out handle to prevent accidental (or unauthorized) withdrawal of the plug-in unit
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 8
Relion® 615 seriesPre-configured functions
Ready-made adaptations (standard configurations)
The IEDs can be rapidly set up and commissioned once they have been given the application-specific settings
The standard signal configuration setting can be adjusted using the PCM600 setting and configuration tool
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 9
Relion® 615 seriesControl functions
Control of one circuit-breaker via the IED’s HMI or a remote control system
Dedicated push-buttons for opening and closing of the CB
Interlocking schemes
Optional multi-shot auto-reclosing of one CB (REF615 and RED615)
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 10
Relion® 615 series Enhanced disturbance recorder functionality
Records up to 12 analog channels and 64 binary channels
Flexible triggering
Selectable sampling rate offers increased flexibility
The disturbance records can be uploaded to PCM600 for in-depth disturbance and fault analysis
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 11
Relion® 615 seriesOperation traceability
For pre and post fault analysis
Data is stored in non-volatile memory Event log Recorded data Settings and configuration,
trip lock-out, disturbance recorder data
Thermal loading Number of auto-reclosing
shots and starts/trips of the protection stages
CB conditioning monitoring values
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 12
Relion® 615 seriesSelf-supervision functionality
Provides information about the operational availability of the protection
Used for continuous monitoring of the IED itself
Monitors both the state of the hardware and the operation of the software
External trip-circuit supervision (TCS)
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 13
Relion® 615 seriesCircuit-breaker condition monitoring
Provides information for scheduling CB maintenance
Monitors the wear and tear of the circuit-breaker
Circuit-breaker gas pressure
Circuit-breaker spring charging
Circuit-breaker travel time
Circuit-breaker operation counter
Scheduled maintenance
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 14
Relion® 615 seriesRole-based access control
Individual user accounts with role-based access control protects the IED from unauthorized access
Four access levels: viewer, operator, engineer and administrator
Applies to: Front-panel user interface Web browser based user
interface PCM600
Passwords programmable by the administrator
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 15
Relion® 615 series Tools and substation automation products
PCM600 One single tool for managing settings,
signal configuration and disturbance handling
Web browser based user interface Local or remote IED access using an IE
7.0 (or later) web browser
IED specific connectivity packages For automatic configuration via
MicroSCADA Pro, Station Automation Series COM600 or PCM600
Station Automation COM600 ver 3.3
MicroSCADA Pro
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 17
REF615 Description
REF615 is a dedicated feeder protection IED designed for the protection, measurement and supervision of utility substations and industrial power systems
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 18
REF615Area of application
Designed for general applications requiring over-current and earth-fault protection
Main application area: cable or overhead line feeders in solidly earthed, resistance earthed, isolated neutral or compensated networks
Optional three-channel arcprotection system
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 19
REF615 Six standard configurations
Std configuration ANon-directional overcurrent and directional E/F protection without CB condition monitoring
Standard configuration BNon-directional overcurrent and directional E/F protection with CB condition monitoring and interlocking schemes
Standard configuration CNon-directional overcurrent and non-directional E/F protection without CB condition monitoring
Standard configuration DNon-directional overcurrent and non-directional E/F protection with CB condition monitoring and interlocking schemes
Standard configuration ENon-directional overcurrent and directional E/F protection with phase-voltage based measurements
Standard configuration FDirectional overcurrent and directional earth-fault protection with phase-voltage based measurements, under- / overvoltage and residual overvoltage protection
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 20
REF615Optional arc protection
Increases safety during maintenance work
Reduces material damage
Minimizes system downtime
Continuously supervises the CB, cable and busbarcompartment of metal-enclosed switchgear
Same lens and optic fibre as for REA 107
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 22
RED615Description
RED615 is a phase-segregated two-end line differential protection and control IED designed for utility and industrial power systems, including looped and meshed distribution networks with or without decentralized power generation
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 23
RED615Grounds for using line differential protection
RED615Difficult to separate fault conditions from normal load conditions
Load current magnitudes close to fault current levels
RED615Difficult to find protection settings that would suit all cases
Varying fault current levels
RED615Protection co-ordination based on definite or inverse time delay might result in too long accumulated time delays within the chain of protection devices
Protection co-ordination
RED615Selective protection scheme still required
Fault current contribution from more than one direction
SolutionOvercurrent protection challengesCaseIntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 24
RED615Selective protection for a defined zone
Unit protection for applications requiring absolutely selective protection for a defined zone
Main application area: two-terminal protection for cable or overhead line feeders
Phase-segregated protection algorithm
Protection communication over a fibre-optic link
GOOSE messaging in combination with binary signal transfer enable smart protection schemes for dynamic power systems
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 25
RED615 Three standard configurations
Standard configuration ALine differential protection
Standard configuration BLine differential protection with directional earth-fault protection
Standard configuration CLine differential protection with non-directional earth-fault protection
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 26
RED615Line differential protection application examples
Parallel feeders
Looped feeder configuration Doubled feeders
Two interconnected feeders Reserve connections or meshed type
of network Distributed generation
Power generation at the remote end of the feeder
Weak grid supplying relatively long distribution lines
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 27
RED615Supervised protection communication
Fibre optic communicationlink
IED 2
IED 1
A pair of optical single mode or multimode fibres form the protection communication link
Distance recommendations < 2 km (multi mode) 2-20 km (single mode)
Continuous supervision of sending and receiving of messages ensures reliable protection communication
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 28
RED615Binary signal transfer
Binary signal transfer (BST) between the two line ends using the protection communication link
Typically used for interlocking and inter-tripping schemes
Eight signals for user definable purposes
Fast communication between two RED615s (<5 ms)
Fully user configurable using the signal matrix tool in PCM600
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 30
RET615Description
RET615 is a dedicated transformer protection and control IED for power transformers, unit and step-up transformers including power generator-transformer blocks in utility and industry power distribution systems
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 31
RET615Area of application
Designed for unit protection applications calling for stabilized differential protection
Main application area: two winding transformers in power distribution networks
Optional three-channel arc protection system
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 32
RET615 Four standard configurations
Standard configuration AThree-phase transformer differential protection for two-winding transformers, with numerical restricted earth-fault protection for the high-voltage (HV) side
Standard configuration BThree-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the low-voltage (LV) side
Standard configuration CThree-phase transformer differential protection for two-winding transformers, high-impedance based restricted earth-fault protection for the high-voltage (HV) side
Standard configuration DThree-phase transformer differential protection for two-winding transformers, high-impedance based restricted earth-fault protection for the low-voltage (LV) side
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 34
REM615Description
REM615 is a dedicated motor protection and control IED designed for the protection, control, measurement and supervision of asynchronous motors in manufacturing and process industry
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 35
REM615Area of application
Circuit-breaker or contactor controlled high-voltage (HV) motors
Contactor controlled medium sized and large low-voltage (LV) motors
Protection for a variety of drives such as:
Pumps and conveyors
Crushers and choppers
Mixers and agitators
Fans and aerators
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 36
REM615 One standard configuration
Standard configuration CMotor protection with current and voltage based protection and measurements functions
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 37
REM615Motor protection functionality
REM615 includes the needed functionality to manage motor starts, normal drive operations and fault clearance Thermal overload protection
Startup supervision
Emergency start
Runtime jam protection
Negative sequence overcurrent protection
Loss-of-load supervision
Phase reversal protection
Optional arc protection with three sensors
Motor start and stop buttons on the local HMI
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 39
Relion® 615 series Supported ABB solutions, page 1(2)
The 615 series IEDs together with COM600 constitute a genuine IEC 61850 solution for reliable power distribution in utility and industrial power systems
The native IEC 61850 support offer: Fast software based communication
Continuous supervision of the integrity of the protection and communication system
Inherent flexibility for reconfiguration and upgrades
ABB’s Connectivity Package concept enables:
Streamlining of the system engineering and IED configuration
Easy integration with COM600 and MicroSCADA Pro
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 40
Relion® 615 series Supported ABB solutions, page 2(2)
The 615 series IEDs complemented with COM600 offer several benefits:
Enhanced substation level functionality using the data content of the bay level IEDs
A web HMI providing single-line mimic diagrams for switchgear bay solutions
COM600 can be used as a local data warehouse for technical documentation and for network data
Extensive reporting and analyzing of network fault situations
Seamless connectivity to MicroSCADAPro and System 800xA
Industrial example
Utility example
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 42
Relion® 615 seriesConclusions
Native support for IEC 61850 and GOOSE messaging
Patented plug-in design for flexible mounting, fast installation and commissioning
Pre-configured IEDs
The 615 series IEDs include a comprehensive range of monitoring and watchdog functions
Versatile tools including IED specific connectivity packages
IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions
© ABB Group May 13, 2010 | Slide 43
Relion® 615 serieswww.abb.com/substationautomation