50ejq Ewq Us

download 50ejq Ewq Us

of 32

Transcript of 50ejq Ewq Us

  • 8/3/2019 50ejq Ewq Us

    1/32

    Single-Package Rooftop Units with:

    dedicated vertical and horizon-tal discharge configurations

    constant volume controls efficiencies from 9.2 to 9.8 meets ASHRAE (American

    Society of Heating, Refrigeration,and Air Conditioning Engineers)Standard 62

    standard cooling operation at out-door ambient temperatures as lowas 35 F at full load

    aluminized steel, sloped conden-sate pan

    all internal surfaces are sheetmetal lined or anti-microbialinsulation

    two-inch return air filters single power entry to unit commercial duty, totally enclosed,

    3-phase outdoor motors with per-manently lubricated bearings

    pre-painted, galvanized steelcabinet

    commercial strength base rails (fuperimeter, 14 gage)

    communicating DDC (Direct DigitaControls) unit controllers includingintelligent defrost

    semi-hermetic compressors withservice valves as standard

    dual independent refrigerantcircuits with face-split indoorcoils

    hinged access panels short cycle protection service diagnostics integrated economizer utilizing

    direct-drive actuators and opposedblade dampers

    IAQ (indoor air quality) options

    ProductData

    50EJQ,EWQSingle-Package Rooftop

    Heat Pump UnitsWith Optional Electric Heat

    20 and 25 Nominal Tons

    Copyright 1997 Carrier Corporation Form 50EJQ,EWQ-2P

  • 8/3/2019 50ejq Ewq Us

    2/32

    Features/Benefits

    De sign fle xibility

    Dedicated vertical supp ly/ return units(50 EJQ) are ideal for new construc-tion or retrofit to existing installations.The low unit profile is maintainedwhen the unit is installed on the acces-sory roof curb, which is approved by

    the National Roofing ContractorsAssociation (NRCA). The roof curb ismade watertight by the roofer.

    The ducts are attached directly tothe roof curb to allow all ductworkto be completed before the unit ispositioned.

    Dedicated horizontal units (50EWQ)are ideal for replacement or applica-tions such as through-the-wall jobsor jobs where sound must be attenu-ated before the duct penetrates theroof. Ducts connect directly to the

    unit. Horizontal units may be curb orslab mounted.

    Direct Digital Controls (DDC) s tandard

    Unit features

    heating/ cooling via thermostat hea ting/ cooling during unoccupied

    periods using accessory remotesensor

    fan cycling hea d pressure control integrated economizer remote start/ stop for non-thermostat

    applications

    provide a power exhaust output control of two stages of powerexhaust

    control of modulating p ower ex-haust with field installed accessory

    two-steps of capacity control LED (light-emitting diode) diagn ostic

    capability field test checkout timed o verride from accessory re-

    mote sensor space temperature averaging from

    using accessory remo te sensor unoccupied heating o r cooling from

    using accessory remo te sensor support supply air reset using acces-sory remote sensor

    Additional features are avail-able with access ory expansionboard

    indoor air quality control inputs for fan status, filter status and

    field applied status demand limit input and function externa l alarm light function smoke control modes control of power exhaust under fire

    outputs

    The Direct Digital Controls alsohave pre-loaded software that is avail-able through the use of a computerand the associated software. The com-puter used to access the DDC maybe permanent or used only duringset-up and commissioning of the

    unit.Unit features with computeraccess

    CCN (Carrier Co mfort Network)protocol

    comp atible with Building Sup er-visor, Service Tool, andComfortWorkssoftware, andLID-2B accessory

    perform demand limit functions alarm monitoring timeclock with ba ck-up daylight savings time function

    occupancy control holiday table temperature compe nsated start Configuration, Maintenance, Serv-

    ice and Set Point data tabledisplay

    Quality and reliability

    Dual serviceable, semi-hermetic com-pressors on independent refrigera-tion circuits provide standby capacityshould one circuit require service.These compressors are proven, reli-able performers.

    Solid core dessicant filter driers aresized at 30 cubic in. to assure longercompressor life. Solid core filters pre-vent erosion and dispersion ofdessicant.

    Totally enclosed outdoor-fan motorsensure many years of trouble-freeoperation.

    Positive-locking bearings for theindoor fan ensure vibration-free opera-tion of the supply fan assembly andremain locked during the life of thebearing.

    Factory-installed economizer(standard)

    All units come equipped with an inte-grated economizer which permitscooling utilizing an outdoor air sensor.The direct gear driven, low leakageblades eliminate conventional inter-blade linkages and the associatedadjustments.

    The economizer operates in con-junction with mecha nical coolingwhen required and is factory-installed

    for either vertical or horizontal opera-tion. The factory-supplied and field-installed rain hood/ filter assemblyprevents moisture or objects fromentering the unit.

    Factory-installed exhaust air relief isavailable for all 50EJQ units as

    barometric relief or power exhaust.Field-installed accessory barometricrelief or power exhaust are availablefor 50EWQ units.

    Field-adjustable set points on acces-sory modulating power exhaust pre-vent space pressurization problems.Factory-installed relief op tions are unitmounted on downflow units. Acces-sories must be duct mounted for hori-zontal app lications.

    Installatio n/ se rviceability

    Dedicated design (vertical or horizon-tal) requires no alteration time toconvert in the field. Single point elec-trical connections are standard onall units. Electrical service access canbe made through roof curb or sideof unit.

    High static capability of standardunits minimize the need to convert tohigher static, oversized motors. Theunit is less sensitive to distributionductwork design.

    The standard microprocessor con-trols replace the need for field in-

    stalled anti-short cycle timers. Thecontrols are compatible with either aroom sensor or conventional ther-mostat with no need to install anaccessory interface. In addition, nospecial tools are required to run theunit through its operational steps. Itsas simple as throwing a DIP (dualin-line package) switch to activate theautomatic test mode. After the testcycle, the unit automatically returns tonormal operation.

    Hinged access panels are locatedfor easy access to standard serviceablecomponents for maintenance. Nofasteners need to be removed, whichreduces servicing time and preventsroof leaks caused by discarded screws.

    Color coded wiring permits easytracing and diagnostics.

    The thermal insulation contains anEPA (Environmental Protection Agency)registered immobilized antimicrobialagent to inhibit the growth of bacteriaand fungi.

    2

  • 8/3/2019 50ejq Ewq Us

    3/32

    Model number nomenclature

    Table of contentsPage

    Features/ Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    ARI Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Op tions and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6,7Base Un it Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8,9Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 0,1 1Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3-17Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 8,1 9Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 -23Typical Wiring Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 5,2 6Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 -31

    LEGEND

    Al AluminumCu Copper

    ISO

    9001:2000 #A22

    60

    Quality Assurance

    Approvals:

    ISO 9001EN 9000:2000

  • 8/3/2019 50ejq Ewq Us

    4/32

    Physical data

    UNIT 50EJQ,EWQ 024 028

    NOMINAL CAPACITY (tons) 20 25

    OPERATING WEIGHT (lb)*Unit

    Al/Al 4168 4168Al/Cu 4388 4388

    Roof Curb (14-in. curb) 365 365

    COMPRESSOR

    Type Ckt 1 06D824 06D328Ckt 2 06D824 06D328Number of Refrigerant Circuits 2 2Oil (oz) (Ckt 1, Ckt 2) 115 ea. 115 ea.

    REFRIGERANT TYPE R-22Expansion Device Acutrol Refrigerant Metering DeviceOperating Charge (lb-oz)

    Circuit 1** 32-2 33-3Circuit 2 34-6 35-11

    OUTDOOR COIL Cross-Hatched 38 Copper Tubes, Aluminum Lanced, Aluminum Precoated or Copper FinsQuantity 1 1Rows...Fins/in. 4...15 4...15Total Face Area (sq ft) 33.3 33.3

    OUTDOOR FAN Propeller TypeNominal Cfm 13,420 13,420Quantity...Diameter (in.) 2...30 2...30Motor Hp (1075 Rpm) 1 1

    INDOOR COIL Cross-Hatched 38 Copper Tubes, Aluminum Plate Fins, Face Split

    Rows...Fins/in. 4...15 4...15Total Face Area (sq ft) 31.7 31.7

    INDOOR FAN Centrifugal TypeQuantity...Size (in.) 2...20x15 2...20x15Type Drive Belt BeltNominal Cfm 8,000 10,000Motor Hp 5 10 15 7.5 10 15

    Motor Frame Size S184T S215TD254T (std)S254T (hi)

    S213T S215TD254T (std)S254T (hi)

    Motor Bearing Type Ball BallMaximum Allowable Rpm 1200 1200Motor Pulley Pitch Diameter 4.8 4.4 5.7 5.4 6.1 5.5Nominal Motor Shaft Diameter (in.) 118 138 158 138 138 158Fan Pully Pitch Diameter (in.) 12.4 8.6 9.1 12.4 11.1 8.7Nominal Fan Shaft Diameter (in.) 11516 11516Belt, Quantity...TypeBelt, Length (in.)

    1...BX5962

    2...BX5154

    2...5VX53053

    1...BX5962

    1...5VX59059

    2...5VX53053

    Pulley Center Line Distance (in.) 16.0-18.7 15.6-18.4 15.0-17.9 15.6-18.4 15.6-18.4 15.0-17.9Factory Speed Setting (rpm) 717 924 1096 773 962 1106

    HIGH-PRESSURE SWITCH (psig)Cutout 426 426Reset (Auto.) 320 320

    LOW-PRESSURE SWITCH (psig)Cutout 7 7Reset (Auto.) 22 22

    RETURN-AIR FILTERSQuantity...Size (in.) 10...20x24x2 10...20x24x2

    OUTDOOR-AIR FILTERS 8...16 x 25Quantity...Size (in.) 4...20 x 25

    POWER EXHAUST Direct Drive, 3-Speed, Single-Phase Motor (Factory-Wired for High Speed) and Forward-Curved FanMotor, Quantity...Hp 4...1 4...1Fan, Diameter...Width (in.) 11...10 11...10

    LEGEND

    Al AluminumCu Copper

    *Weight of unit does not include barometric relief or power exhaust.Indoor coil fin material/outdoor coil fin material.**Circuit 1 uses the upper portion of the outdoor coil, circuit 2 uses the lower por-

    tion. Circuit 1 uses the lower portion of the indoor coil, circuit 2 uses the upperportion.

    Motor and drive shown will deliver approximately 2.5 in. wg net external static.

    4

  • 8/3/2019 50ejq Ewq Us

    5/32

    ARI* capacities

    UNIT50EJQ,EWQ

    COOLING HEATING-HIGH TEMP HEATING-LOW TEMP

    TotalkW

    NetCapacity

    (Btuh)Cfm EER

    TotalCapacity

    (Btuh)

    TotalkW

    COPTotal

    Capacity(Btuh)

    TotalkW

    COP

    024 23.4 230,000 6800 9.8 228,000 20.0 3.3 116,000 16.7 2.0

    028 28.6 262,000 7500 9.2 266,000 23.7 3.3 140,000 19.5 2.1

    LEGEND

    COP Coefficient of Performancedb Dry BulbEER Energy Efficiency RatioESP External Static Pressurewb Wet Bulb

    *Air Conditioning and Refrigeration Institute.

    Cooling ratings are net values, reflecting the effects of circulating fanheat. Ratings are based on:ESP: 0.40 in. wg

    Cooling Standard: 80 F db, 67 F wb indoor coil entering-air tempera-ture and 95 F outdoor coil entering-air temperature.

    High-Temp Heating Standard: 70 F db indoor coil entering-air tem-perature and 47 F db, 43 F wb outdoor coil entering-air temperature.

    Low-Temp Heating Standard: 70 F db indoor coil entering-air tempera-ture and 17 F db, 15 F wb outdoor coil entering-air temperature.

    COOLING S TAGING S EQUENCE 5 0 EJQ,EWQ

    STAGES 0 1 2

    COMP NO. 1 OFF ON ON

    COMP NO. 2 OFF OFF ONUNITSIZE

    UNIT CAPACITY

    024 0% 50% 100%

    028 0% 50% 100%

    NOTE: Field-installed accessory unloaders are not approved for theseunits due to low-load performance with fixed-orifice metering devices.

    ELECTRIC RESISTANCE HEATER DATA

    UNIT

    HEATER kWHEATERSTAGES

    % HEATPER

    STAGE

    MINIMUMCFM

    Unit Voltages

    208 230 460

    50EJQ024

    27 36 36 1 100

    6,00054 72 72 1 100

    50EJQ02827 36 36 1 100

    7,50054 72 72 1 100

    50EWQ02427 36 36 1 100

    6,000 72 1 100

    50EWQ02827 36 36 1 100

    7,500 72 1 100

    NOTES:1. Due to the open design of the electric heaters, the airside pressure

    drop is negligible.2. Heaters are rated at 208, 240 and 480 v. Refer to multiplication fac-

    tors table to rate heaters at other voltages.

    5 0 EJQ,EWQ NO MINAL CFM RANGE(Electric Heat Units)

    UNIT SIZEDESIGN RANGE

    (Cfm)

    024 6,000 TO 10,000

    028 7,500 TO 12,500

    MULTIPLICATION FACTORS

    HEATERkW

    RATING

    VOLTAGEDISTRIBUTION

    V-3-60

    MULTIPLICATIONFACTOR

    240

    200208230240

    0.6940.7510.9181.000

    480440460480

    0.8400.9181.000

    EXAMPLE: 32.0 kW (at 240 v) heater on 208 v= 32.0 (.75 mult factor)= 24.0 kW capacity at 208 v

  • 8/3/2019 50ejq Ewq Us

    6/32

    Options and accessories

    ITEM OPTION* ACCESSORY

    Barometric Relief** X X

    Copper/Copper Condenser Coil X

    Pre-Coated Aluminum Fin Condenser Coil X

    Non-Modulating Power Exhaust** X X

    Power Exhaust Conversion, Non-Modulating to Modulating** X

    Electric Heat X X

    Roof Curb XMotormaster III Head Pressure Control X

    Outdoor Coil Hail Guard Assembly X

    Electronic Programmable Thermostat X

    Thermostat and Subbase X

    Space Temperature Sensor X

    Space Temperature Sensor with Offset (T-56) X

    IAQ (CO2) Sensor X

    Enthalpy Control for Integrated Economizer X

    Expansion Electronic Board X

    Roof Curb Retrofit Kit X

    LID-2B Interface Device X

    LEGEND

    IAQ Indoor Air Quality*Factory installed.Field installed.

    **Not available as a factory-installed option on 50EWQ units. Accessory must befield-installed in the ductwork on 50EWQ units.

    POWER EXHAUST FANS

    When combined with theeconomizer, the power exhaust canbe used

    to exhaust the return air and eliminateover-pressurization of the build-ing. The power exhaust utilizes multiple forward-curved fans, eachdriven by its own motor.

    The constant volume power exhaust stages the motors accordingto economizer position to control the building pressure.

    The modulating power exhaust stages the motors according to in-terior space pressure (field-installed accessory only).

    HEAD PRESSURE CONTROL

    The standard units are designed to operate in cooling at outdoortemperatures down to 35 F. With accessory Motormaster III con-trol (condenser fan speed modulation) units can operate at out-door temperatures down to 20 F. The head pressure controls,which mount in the condenser section, control the condenser-fanmotor to maintain correct condensing temperature. Refer to pricepages or contact your local Carrier representative for appropriateaccessory combinations for desired outdoor ambient temperatureoperation.

    6

  • 8/3/2019 50ejq Ewq Us

    7/32

    ELECTRIC HEATER

    Electric heaters are available in a wide range of capacities for factoryor field installation.

    ENTHALPY CONTROL FORINTEGRATED ECONO MIZER

    +

    C7400A1004

    Enthalpy economizer controls help provide efficient, economical econo-mizer operation. Solid-state enthalpy control includes the logic andone sensor to calculate both dry and wet bulb of the outdoor air toprovide an accurate enthalpy reading. It then decides when to ener-gize the economizer based on this reading. A second sensor providesinformation for comparison of outdoor temperature and humidity toreturn-air temperature and humidity and determines the most eco-nomical mixture of air (purchased in addition to first solid-state en-thalpy sensor for differential enthalpy sensing).

    CO2

    SENSOR

    This sensor monitors building interior or return air carbon dioxide lev-els and automatically activates the outdoor fan and opens the econo-

    mizer for rapid dilution of CO2 levels above an adjustable set point.

    LID-2 B FIELD -INSTALLED INTERFACE D EVICE

    The LID-2B (30HX900007) enhanced display provides access to theunit software for specific application time schedules and control con-figurations. The LID-2B has a separate dedicated 24-v power source.

    ELECTRONIC PROGRAMMABLE THERMOSTAT

    Carriers electronic programmable thermostat provides efficient tem-perature control by allowing you to program heating and cooling set-backs and set ups with provisions for weekends and holidays.

  • 8/3/2019 50ejq Ewq Us

    8/32

    Base unit dimensions, 50EJQ024,028

    UNIT SIZE50EJQ

    OPERATINGWEIGHT

    A BCORNER WEIGHT

    (lb)

    lb ft-in. ft-in. 1 2 3 4

    024 4168 5-738 3-758 843 859 1245 1222

    028 4168 5-738 3-758 843 859 1245 1222

    NOTES:1. Weights include economizer (Std)

    2. Center of gravity.

    3. Do not locate adjacent units withdischargefacing economizer inlet. Minimum clear-ances to be:

    Adjacent Units: 15-0Top of Units: No overhangOutdoor Coil: 4-0Economizer Side: 6-0Filter Access Side: 10-0 (for removalof indoor coil)

    4. For smaller service and operational clear-ances, contact Carrier Application Engi-neering department.

    5. Bottom ducts designed to be attached toaccessory roof curb. If unit is mounted ondunnage, it is recommended the ducts besupported by cross braces as done onaccessory roof curb.

    6. Dimensions are in inches.7. For units with electric heat, a field-supplied

    90elbow must be installed in the supplyductwork below the unit discharge.

    8

  • 8/3/2019 50ejq Ewq Us

    9/32

    Base unit dimensions, 50EWQ024,028

    NOTES:1. Weights include economizer (Std)

    2. Center of gravity.

    3. Do not locate adjacent units with discharge facing economizer inlet. Minimum clearances to be:Adjacent Units: 15-0Top of Units: No overhangCondenser Coil: 4-0Economizer Side: 6-0Filter Access Side: 10-0 (for removal of evaporator coil)

    4. For smaller service and operational clearances, contact Carrier Application Engineering department.5. Dimensions are in inches.6. For units equipped with electric heat, a field-supplied 90 elbow must be installed in the supply

    ductwork below the unit discharge.7. For side-supply/return applications, a single return and supply ductwork connection is recom-

    mended for covering both return and both supply openings.

    UNIT SIZE50EWQ

    OPERATINGWEIGHT

    A BCORNER WEIGHT

    (lb)

    lb ft-in. ft-in. 1 2 3 4

    024 4168 5-738 3-758 843 859 1245 1222

    028 4168 5-738 3-758 843 859 1245 1222

  • 8/3/2019 50ejq Ewq Us

    10/32

    Accessory dimensions

    NOTES:1. Unless otherwise specified, all dimensions

    are to outside of part.2. Roof curb accessory CRRFCURB005A00

    is shipped disassembled.3. All roof curb parts are to be 14 gage gal-

    vanized steel.

    DIMENSIONS*(degrees and inches)

    A B

    Deg. in. Deg. in.

    1.0 2.9 .50 .75

    UNIT LEVELING TOLERANCES

    *From edge of unit to horizontal.

    NOTE: To prevent standing water in the drain pan of the indoor sectionand the heat exchangers, UNIT CAN ONLY BE PITCHED AS SHOWN.

    ROOF CURB

    1 0

  • 8/3/2019 50ejq Ewq Us

    11/32

    LEGEND

    Diameter

    NOTES:1. Unless otherwise specified, all dimensions are to outside of part.2. Dimensions are in inches.3. There are 2 assemblies per unit.

    POWER EXHAUST AND BAROMETRIC RELIEF

    1

  • 8/3/2019 50ejq Ewq Us

    12/32

    Selection procedure (with example)

    I Determine heating and coo ling requirements atdesign conditions.

    Given:

    Required Co oling Capa city (TC) . . . . . 25 0,0 00 BtuhSensible Heat Capacity (SHC) . . . . . . 18 0,0 00 BtuhRequired Heating Capacity . . . . . . . . . 218,000 BtuhOutdoor-Air Temperature (Cooling) . . . . . . . . . . 9 5 F

    Indoo r Entering-Air Temp erature(Cooling) . . . . . . . . . . . . . . . . . 8 0 F Edb/ 67 F Ewb

    Outdoor Coil Entering-Air Temperature(Heating) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 F

    Indoor Winter Design Temperature . . . . . . . . . . 70 FIndoor-Air Quantity . . . . . . . . . . . . . . . . . 1 0, 00 0 CfmExternal Static Pressure (ESP) . . . . . . . . . 1. 40 in. wgElectrical Ch aracteristics (V-Ph-Hz) . . . . . . . 23 0-3-60Vertical unit is specified.Economizer is spe cified.Edb Entering dry bulbEwb Entering wet bulb

    II Se lect unit based on required co oling capacity.

    Enter Cooling Capacity table at outdoor-air enter-ing temperature of 95 F, indoor air entering at10,000 cfm and 67 F ewb. The 50EJQ028 will pro-vide a total capacity (TC) of 276,000 Btuh, a sensibleheat capacity (SHC) of 208 ,40 0 Btuh and a compres-sor kW of 24.90 .

    For indoor-air temperature other than 80 F edb, cal-culate sensible heat capacity correction, as required,using the formula found in Note 3 following the Cool-ing Capacities tables on page 14.

    NOTE: Unit ratings are gross capacities and do notinclude the effect of indoor-fan motor heat. To calcu-late net capacities, see Step V.

    III Se lect electric he at.Enter the Integrated Heating Capacities table onpage 15 at 10 ,00 0 cfm. At 70 F return indoor air and0 F air entering the outdoor coil, the integrated heat-ing capacity is 105,600 Btuh with a unit input kW of17.69.

    The required heating capacity is 21 8,0 00 Btuh; there-fore, 112,400 Btuh (218,000 105,600) additionalelectric heat is necessary.

    Determine the additional electric heat capacity in kW.

    112,400 Btuh= 3 2 .9 k W

    3,4 12 Btuh/ kW

    Enter the Electric Resistance Heater Data table at240-3-60. Heater is rated at 240 v. Multiply 36 kWheater times 0.918 from the Multiplication Factors tableto get 33.05 kW rating at 230 v. The 36-kW heatersatisfies the electric heater requirement.

    IV Dete rmine fan spe ed and motor horsepo wer re-quirements at design conditions.

    Tabulated fan performance includes 2-in. throwawayfilters, wet evaporator coil, economizer, cabinet loss,and roof curb. Find fan rpm and bhp at 1.4 in. wgand 10,000 cfm on 50EJQ028 Fan Performance tablefor vertical app lications. Find that the fan speed is832 rpm and the power required is 7 .95 bhp. See

    Motor Limitations table on page 17. The 7.5 hp mo-tor is required.

    V Determine net co oling capacities.

    Cooling capacities are gross and do not include the ef-fect of indoor-fan motor (IFM) heat.

    Determine net cooling capacity as follows:

    Net capacity = Gross capacity IFM heat

    Btuh2 5 4 5

    hp= 2 7 6 ,0 0 0 7 .9 5 b hp x

    .8 1= 2 7 6 ,0 0 0 2 4 ,9 7 9= 251,021 Btuh

    Net sensible capacity = 20 8,4 00 24 ,97 9= 183,421 Btuh

    NOTE: Heating capacity is net capacity.

    1 2

  • 8/3/2019 50ejq Ewq Us

    13/32

    Performance data

    COO LING CAPACITIES

    50EJQ,EWQ024 (20 TONS)

    Temp (F)Air EnteringOutdoor Coil

    (Edb)

    Indoor Entering Air Cfm/BF

    6000 / 0.05 7000 / 0.06 8000 / 0.07 9000 / 0.08

    Indoor Entering Air Ewb (F)

    62 67 72 62 67 72 62 67 72 62 67 72

    TC 227.0 251.0 273.0 232.0 260.0 277.0 237.0 259.0 282.0 240.0 264.0 283.075 SHC 189.2 158.3 125.9 203.9 171.8 140.1 218.0 180.6 141.7 229.0 190.2 149.8

    kW 15.42 15.90 16.31 15.60 16.13 16.43 15.74 16.13 16.53 15.83 16.31 16.59

    TC 216.0 242.0 268.0 223.0 248.0 273.0 228.0 252.0 275.0 232.0 257.0 279.085 SHC 185.2 156.2 125.5 200.2 167.7 131.6 215.0 177.7 141.1 225.0 188.3 145.3

    kW 16.89 17.49 18.07 17.09 17.72 18.24 17.31 17.83 18.34 17.46 17.99 18.46

    TC 205.0 230.0 257.0 211.0 237.0 261.0 217.0 241.0 265.0 223.0 245.0 268.095 SHC 180.3 152.4 122.5 195.8 163.8 127.0 208.7 174.3 133.8 219.0 185.5 139.3

    kW 18.32 19.03 19.73 18.58 19.28 19.89 18.82 19.42 19.99 19.05 19.59 20.17

    TC 192.7 218.0 244.0 199.0 223.0 250.0 205.0 228.0 255.0 211.0 230.0 256.0105 SHC 174.7 147.3 118.1 189.1 159.2 124.9 201.0 170.0 131.8 209.0 181.0 136.5

    kW 19.73 20.55 21.30 20.08 20.80 21.60 20.31 21.00 21.80 20.62 21.20 21.90

    TC 180.4 205.0 231.0 187.3 210.0 236.0 193.6 213.0 238.0 200.0 216.0 242.0115 SHC 169.2 142.8 114.1 181.9 154.4 120.4 192.0 165.5 127.4 200.0 175.9 133.5

    kW 21.10 22.00 23.00 21.50 22.30 23.30 21.80 22.50 23.30 22.20 22.70 23.50

    LEGEND

    BF Bypass FactorEdb Entering Dry BulbEwb Entering Wet BulbkW Compressor Motor Power InputSHC Sensible Heat Capacity (1000 Btuh)TC Total Capacity (1000 Btuh) Gross

    NOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following formulas may be used:

    sensible capacity (Btuh)t ldb = t edb

    1.10 x cfm

    Wet-bulb temperature corresponding to enthalpy of air leav-t lwb = ing indoor coil (h lwb).

    total capacity (Btuh)h lwb = h ewb

    4.5 x cfm

    Where: h ewb = Enthalpy of air entering indoor coil

    3. SHC is based on 80 F edb temperature of air entering indoor coil

    Below 80 F edb, subtract (corr factor x cfm) from SHC.Above 80 F edb, add (corr factor x cfm) to SHC.

    BF

    ENTERING AIR DRY-BULB TEMP (F)

    79 78 77 76 75 under 75

    81 82 83 84 85 over 85

    Correction Factor

    .05 1.04 2.07 3.11 4.14 4.18Use formula

    shown below..10 .98 1.96 2.94 3.92 4.91

    .20 .87 1.74 2.62 3.49 4.36

    Interpolation is permissible.Correction factor = 1.10 x (1 BF) x (edb 80)

    4. Cooling capacities are gross and do not include deduction for in-door fan motor heat.

    1

  • 8/3/2019 50ejq Ewq Us

    14/32

    Performance data (cont)

    COOLING CAPACITIES (cont)

    50EJQ,EWQ028 (25 TONS)

    Temp (F)Air EnteringOutdoor Coil

    (Edb)

    Indoor Entering Air Cfm/BF

    7500 / 0.06 8750 / 0.07 10,000 / 0.08 11,250 / 0.09

    Indoor Entering Air Ewb (F)

    62 67 72 62 67 72 62 67 72 62 67 72

    TC 263.0 292.0 320.0 268.0 295.0 316.0 271.0 297.0 319.0 275.0 297.0 320.075 SHC 228.0 189.7 150.7 243.0 200.3 164.3 259.0 216.0 175.9 271.0 222.0 173.5

    kW 19.67 20.39 21.00 19.99 20.56 21.00 20.25 20.80 21.40 20.60 21.00 21.60

    TC 252.0 282.0 310.0 257.0 287.0 314.0 262.0 289.0 314.0 265.0 291.0 312.085 SHC 223.0 187.0 146.6 240.0 199.1 153.8 254.0 212.0 165.5 263.0 223.0 171.6

    kW 21.40 22.20 23.00 21.80 22.60 23.30 22.20 23.00 23.50 22.50 23.20 23.70

    TC 239.0 269.0 298.0 244.0 273.0 302.0 250.0 276.0 305.0 255.0 277.0 307.095 SHC 217.0 183.3 144.5 234.0 195.3 151.2 246.0 208.4 158.3 255.0 219.0 165.3

    kW 23.10 24.20 25.00 23.60 24.50 25.40 24.10 24.90 25.70 24.50 25.20 26.00

    TC 225.0 255.0 285.0 231.0 259.0 290.0 238.0 261.0 293.0 244.0 263.0 293.0105 SHC 210.0 177.8 140.7 226.0 190.9 148.6 237.0 205.1 155.2 244.0 215.0 161.8

    kW 24.90 26.00 27.00 25.40 26.40 27.50 26.00 26.80 27.80 26.50 27.20 28.10

    TC 213.0 240.0 270.0 220.0 243.0 274.0 226.0 246.0 277.0 232.0 247.0 278.0115 SHC 204.6 172.1 136.4 217.0 185.5 144.2 226.0 199.0 152.2 232.0 209.5 158.9

    kW 26.60 27.80 28.90 27.20 28.30 29.40 27.90 28.70 29.80 28.40 29.00 30.20

    LEGEND

    BF Bypass FactorEdb Entering Dry BulbEwb Entering Wet BulbkW Compressor Motor Power InputSHC Sensible Heat Capacity (1000 Btuh)TC Total Capacity (1000 Btuh) Gross

    NOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following formulas may be used:

    sensible capacity (Btuh)t ldb = t edb

    1.10 x cfm

    Wet-bulb temperature corresponding to enthalpy of air leav-t lwb = ing indoor coil (h lwb).

    total capacity (Btuh)h lwb = h ewb

    4.5 x cfm

    Where: h ewb = Enthalpy of air entering indoor coil

    3. SHC is based on 80 F edb temperature of air entering indoor coil.

    Below 80 F edb, subtract (corr factor x cfm) from SHC.Above 80 F edb, add (corr factor x cfm) to SHC.

    BF

    ENTERING AIR DRY-BULB TEMP (F)

    79 78 77 76 75 under 75

    81 82 83 84 85 over 85

    Correction Factor

    .05 1.04 2.07 3.11 4.14 4.18Use formula

    shown below..10 .98 1.96 2.94 3.92 4.91

    .20 .87 1.74 2.62 3.49 4.36

    Interpolation is permissible.Correction factor = 1.10 x (1 BF) x (edb 80)

    4. Cooling capacities are gross and do not include deduction for in-door fan motor heat.

    1 4

  • 8/3/2019 50ejq Ewq Us

    15/32

    INTEGRATED H EATING CAPACITIES

    50EJQ,EWQ024 (20 TONS)

    CFMReturn

    Air TempF (db)

    Temp Air Entering Outdoor Coil (F db at 75% RH)

    10 0 10 17 20 30 40 47 50 60

    Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW

    600055 67.2 12.45 90.3 13.44 111.0 14.37 123.8 15.05 130.5 15.39 152.7 16.49 208.0 17.67 238.0 18.69 250.0 19.14 294.0 20.7070 54.7 12.84 79.8 14.02 101.4 15.14 115.6 16.00 121.8 16.39 142.4 17.70 193.2 19.09 222.0 20.20 234.0 20.80 277.0 22.6080 50.0 12.95 74.8 14.25 96.3 15.52 109.9 16.53 115.8 16.97 135.6 18.42 184.0 19.94 212.0 21.20 224.0 21.80 265.0 23.70

    700055 67.0 12.67 92.4 13.60 112.1 14.48 126.5 15.10 133.5 15.40 156.7 16.40 212.0 17.46 244.0 18.31 255.0 18.65 295.0 19.8170 54.3 13.11 79.3 14.21 103.8 15.28 118.1 16.07 124.5 16.44 145.8 17.65 198.4 18.91 228.0 20.00 240.0 20.40 281.0 21.9080 48.0 13.27 73.3 14.52 97.0 15.71 112.2 16.62 118.4 17.04 138.9 18.40 189.2 19.82 218.0 21.00 230.0 21.60 271.0 23.20

    800055 68.7 12.90 94.4 13.79 114.2 14.62 128.9 15.20 135.9 15.47 159.6 16.39 217.0 17.31 245.0 18.01 255.0 18.28 289.0 19.1870 55.0 13.35 82.3 14.42 105.6 15.44 120.3 16.19 126.9 16.53 148.9 17.67 202.0 18.83 232.0 19.77 244.0 20.20 284.0 21.4080 46.2 13.56 72.7 14.77 99.2 15.88 114.4 16.76 102.8 17.14 141.7 18.44 193.2 19.76 222.0 20.80 235.0 21.40 276.0 22.80

    900055 71.4 13.12 95.9 13.99 116.1 14.78 131.0 15.32 138.3 15.58 162.6 16.44 220.0 17.25 242.0 17.76 251.0 17.99 281.0 18.7570 56.4 13.59 85.0 14.62 107.6 15.61 122.2 16.33 128.9 16.65 151.4 17.73 206.0 18.82 234.0 19.57 245.0 19.90 281.0 21.0080 45.9 13.83 73.7 15.00 101.2 16.07 116.5 16.92 122.9 17.28 144.3 18.52 196.7 19.76 227.0 20.80 239.0 21.20 278.0 22.40

    50EJQ,EWQ028 (25 TONS)

    CFMReturn

    Air TempF (db)

    Temp Air Entering Outdoor Coil (F db at 75% RH)

    10 0 10 17 20 30 40 47 50 60

    Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW Cap. kW

    7,50055 85.8 15.31 108.8 16.35 131.2 17.32 147.9 17.99 156.1 18.33 181.9 19.47 247.0 20.70 280.0 21.60 292.0 21.90 322.0 22.7070 72.6 16.04 100.0 17.23 124.3 18.36 139.5 19.20 147.2 19.62 171.5 21.00 233.0 22.40 266.0 23.60 280.0 24.10 327.0 25.8080 69.5 16.36 94.3 17.75 118.4 19.02 134.1 19.91 141.6 20.40 165.0 21.90 223.0 23.50 256.0 24.80 271.0 25.40 317.0 27.40

    8,750 55 88.3 15.56 110.9 16.57 133.9 17.47 150.7 18.09 159.2 18.40 185.6 19.42 253.0 20.50 281.0 21.10 293.0 21.50 332.0 22.5070 71.4 16.37 102.3 17.46 126.2 18.53 142.1 19.31 150.2 19.70 175.2 20.90 238.0 22.30 270.0 23.20 285.0 23.70 325.0 25.0080 68.7 16.71 92.8 18.02 120.8 19.20 136.6 20.09 144.4 20.50 168.4 21.90 228.0 23.30 262.0 24.60 275.0 25.10 320.0 26.70

    10,00055 88.8 15.88 112.9 16.82 136.2 17.67 153.3 18.23 161.7 18.53 188.7 19.47 254.0 20.30 276.0 20.80 283.0 21.00 304.0 21.3070 72.3 16.67 105.6 17.69 128.1 18.74 144.5 19.47 152.7 19.80 178.1 21.00 242.0 22.20 273.0 23.00 288.0 23.50 327.0 24.7080 67.5 17.05 94.5 18.30 123.0 19.41 138.9 20.19 146.8 20.60 171.2 22.00 232.0 23.30 266.0 24.40 279.0 24.80 319.0 26.10

    11,25055 90.8 16.18 114.6 17.09 138.1 17.90 155.2 18.42 163.8 18.70 191.0 19.54 248.0 20.20 275.0 20.80 283.0 21.10 306.0 21.4070 74.0 16.97 107.4 17.96 130.0 18.98 146.6 19.67 154.9 20.01 180.6 21.20 245.0 22.20 261.0 22.50 283.0 23.10 314.0 24.0080 67.7 17.38 98.9 18.53 124.6 19.64 140.8 20.40 148.8 20.80 173.8 22.10 236.0 23.40 267.0 24.30 279.0 24.70 315.0 25.80

    LEGEND

    ARI Air Conditioning and Refrigeration InstituteCap. Integrated Heating Capacity 1000 Btuh (includes effect of defrost

    and indoor-fan motor heat) at ARI conditions.kW Total Unit Power Input Includes compressors, outdoor-fan motors,

    and indoor-fan motors. Indoor-fan motor heat based on unit operatingat cfm shown and external static pressures (ESP) of 0.35.

    RH Relative Humidity

    Conversion formula: Btuh = kW x 3412

    FAN PERFORMANCE POWER EXHAUST

    50EJQ,EWQ024 AND 028 (20 AND 25 TONS)

    Airflow(Cfm)

    Low Speed Medium Speed High Speed

    208 v 230,460 v 208 v 230,460 v 208 v 230,460 v

    ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts

    6,500 0.32 2.82 3160 0.70 2.98 3340 6,700 0.23 2.87 3220 0.63 3.03 3400 0.60 3.01 3380 0.82 3.23 3620 6,900 0.17 2.92 3270 0.59 3.09 3460 0.55 3.07 3440 0.78 3.28 3680 7,100 0.13 2.93 3290 0.56 3.11 3490 0.49 3.12 3500 0.73 3.34 3740 7,300 0.09 2.97 3330 0.53 3.15 3530 0.43 3.18 3560 0.68 3.39 3800 7,500 0.51 3.19 3580 0.39 3.24 3630 0.64 3.44 3860 7,700 0.48 3.23 3620 0.33 3.27 3670 0.59 3.48 3900 0.60 3.69 4140 0.73 3.98 44607,900 0.45 3.27 3670 0.27 3.32 3720 0.54 3.52 3950 0.56 3.74 4190 0.69 4.02 45108,100 0.40 3.33 3730 0.22 3.36 3770 0.49 3.57 4000 0.51 3.78 4240 0.65 4.07 45608,500 0.17 3.47 3890 0.40 3.67 4120 0.41 3.83 4290 0.56 4.12 46208,900 0.00 3.58 4010 0.30 3.77 4230 0.31 3.93 4410 0.47 4.23 47409,300 0.22 3.87 4340 0.20 4.07 4560 0.37 4.37 49009,700 0.16 3.95 4430 0.11 4.17 4670 0.30 4.47 5010

    10,100 0.12 4.03 4520 0.04 4.25 4770 0.23 4.56 511010,500 0.17 4.66 522010,900 0.12 4.75 533010,500 0.17 4.66 522010,900 0.12 4.75 533011,300 0.07 4.80 538011,700 0.04 4.83 5420

    LEGEND

    Bhp Brake HorsepowerESP External Static Pressure (in. wg)Watts Input Watts to Motor

    1

  • 8/3/2019 50ejq Ewq Us

    16/32

    Performance data (cont)

    FAN PERFORMANCE VERTICAL D IS CHARGE UNITS

    For 50 EWQ u n it s, red u ce n et available ext ern al st at ic p ressu re b y 0 . 3 in . wg.

    50EJQ,EWQ024 AND 028 (20 AND 25 TONS)

    Airflow(Cfm)

    Available External Static Pressure (in. wg)

    0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6

    Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp

    6,000 403 1.62 468 2.01 526 2.41 577 2.81 624 3.21 668 3.62 709 4.04 748 4.467,000 448 2.22 508 2.65 561 3.08 609 3.50 654 3.93 696 4.37 736 4.81 773 5.258,000 495 2.97 549 3.42 599 3.88 645 4.33 687 4.79 727 5.25 765 5.71 801 6.188,250 507 3.18 560 3.64 609 4.10 654 4.56 696 5.02 735 5.49 773 5.96 809 6.439,000 543 3.85 593 4.34 639 4.82 682 5.30 723 5.78 761 6.27 797 6.76 832 7.24

    10,000 592 4.90 638 5.41 682 5.91 722 6.42 760 6.93 797 7.44 832 7.95 865 8.4611,000 642 6.10 685 6.64 725 7.17 764 7.70 800 8.24 835 8.77 868 9.30 900 9.8412,000 693 7.48 733 8.04 771 8.60 807 9.15 841 9.71 874 10.26 906 10.82 937 11.3812,500 718 8.23 757 8.80 794 9.37 829 9.94 862 10.51 895 11.08 926 11.64 956 12.21

    50EJQ,EWQ024 AND 028 (20 AND 25 TONS)

    Airflow(Cfm)

    Available External Static Pressure (in. wg)

    1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2

    Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp

    6,000 785 4.89 820 5.32 854 5.76 886 6.21 918 6.65 948 7.11 977 7.56 1006 8.027,000 809 5.70 843 6.16 876 6.61 908 7.08 939 7.54 968 8.01 997 8.49 1025 8.968,000 836 6.65 869 7.12 901 7.60 932 8.08 962 8.57 991 9.05 1019 9.55 1046 10.04

    8,250 843 6.91 876 7.39 908 7.87 938 8.36 968 8.84 997 9.34 1025 9.83 1052 10.339,000 865 7.74 898 8.23 929 8.73 959 9.23 988 9.74 1016 10.24 1043 10.75 1070 11.27

    10,000 897 8.98 928 9.49 958 10.01 987 10.53 1016 11.06 1043 11.58 1070 12.11 1096 12.6411,000 931 10.37 961 10.91 990 11.45 1018 11.99 1046 12.54 1073 13.08 1099 13.63 1124 14.1812,000 967 11.94 996 12.49 1024 13.06 1051 13.62 1078 14.18 1104 14.75 1129 15.31 1154 15.8812,500 985 12.78 1014 13.35 1041 13.92 1068 14.49 1094 15.07 1120 15.64 1145 16.22 1169 16.80

    50EJQ,EWQ024 AND 028 (20 AND 25 TONS)

    Airflow(Cfm)

    Available External Static Pressure (in. wg)

    3.4 3.6 3.8

    Rpm Bhp Rpm Bhp Rpm Bhp

    6,000 1034 8.49 1061 8.96 1087 9.437,000 1052 9.44 1079 9.93 1105 10.428,000 1073 10.54 1099 11.04 1125 11.558,250 1079 10.84 1105 11.34 1130 11.859,000 1096 11.78 1122 12.30 1147 12.82

    10,000 1122 13.18 1147 13.71 1171 14.2511,000 1149 14.73 1173 15.29 1197 15.8412,000 1178 16.45 1202 17.03 12,500 1193 17.38

    LEGEND

    Bhp Brake Horsepower

    NOTES:1. Fan performance is based on wet coils, economizer, roof curb,

    cabinet losses, and clean 2-in. filters.2. Conversion Bhp to watts:

    Bhp x 746Watts =

    Motor efficiency

    1 6

  • 8/3/2019 50ejq Ewq Us

    17/32

    MOTOR LIMITATIONS

    STANDARD EFFICIENCY MOTORS

    NominalHp

    MaximumBhp

    Maximum Amps MaximumWatts

    MotorEfficiency230 460

    55.9 14.6 5,030 87.5

    5.9 7.9 5,030 87.5

    7.5

    8.7 22.0 7,334 88.5

    9.5 12.0 8,008 88.5

    1010.2 28.0 8,502 89.5

    11.8 14.6 9,836 89.5

    1515.3 43.8 12,543 91.0

    18.0 21.9 14,756 91.0

    HIGH EFFICIENCY MOTORS

    NominalHp

    MaximumBhp

    Maximum Amps MaximumWatts

    MotorEfficiency230 460

    55.9 15.8 4,918 89.5

    5.9 7.9 4,918 89.5

    7.58.7 22.0 7,078 91.7

    9.5 12.0 7,728 91.7

    10 10.2 28.0 8,298 91.711.8 15.0 9,600 91.7

    1515.3 43.8 12,273 93.0

    18.0 21.9 14,439 93.0

    LEGEND

    BHP Brake Horsepower

    NOTE: Extensive motor and electrical testing on the Carrier units has ensured that the full horsepowerrange of the motor can be utilized with confidence. Using your fan motors up to the horsepower ratingsshown on the Motor Limitations table will not result in nuisance tripping or premature motor failure. Unitwarranty will not be affected.

    1

  • 8/3/2019 50ejq Ewq Us

    18/32

    Electrical data

    UNIT SIZE50EJQ,EWQ

    NOMINALVOLTAGE

    (3 Ph 60 Hz)

    VOLTAGERANGE

    COMPRESSORS OFM IFMPOWER

    EXHAUSTELECTRIC

    HEAT*POWER SUPPLY

    MIN MAX RLA LRA Qty HpFLA(ea)

    Hp FLA FLA LRA kW FLA MCA MOCP

    024

    208/230 187 254 35.6 198 2 1 5.3

    5 16.7/15.2

    23.6

    4.16

    //

    //

    107.4/105.9131.0/129.5

    125/125150/150

    23.6

    4.16

    27/3627/36

    75.1/86.675.1/86.6

    201.2/214.2224.8/237.8

    225/225225/250

    23.6 4.16 54/7254/72 150.1/173.2150.1/173.2 257.5/279.1281.1/302.7 275/300300/350

    10 30.8/28

    23.6

    4.16

    //

    //

    121.5/118.7145.1/142.3

    150/150175/175

    23.6

    4.16

    27/3627/36

    75.1/86.675.1/86.6

    215.3/227.0230.7/250.6

    225/250250/275

    23.6

    4.16

    54/7254/72

    150.1/173.2150.1/173.2

    271.6/291.9295.2/315.5

    300/300300/350

    15 46.2/42

    23.6

    4.16

    //

    //

    136.9/132.7160.5/156.3

    150/150175/175

    23.6

    4.16

    27/3627/36

    75.1/86.675.1/86.6

    230.7/241.0254.3/264.6

    250/250275/275

    23.6

    4.16

    54/7254/72

    150.1/173.2150.1/173.2

    287.0/305.9310.6/329.5

    300/350350/350

    460 414 508 17.8 99 2 1 2.7

    5 7.6

    23.6

    41.6

    53.165.7

    7080

    23.6

    41.6

    36

    36

    43.3

    43.3

    107.2

    119.8

    110

    125

    23.6

    41.67272

    86.686.6

    139.7152.3

    150175

    10 14

    23.6

    41.6

    59.572.1

    7080

    23.6

    41.6

    3636

    43.343.3

    113.6126.2

    125150

    23.6

    41.6

    7272

    86.686.6

    146.1158.7

    150175

    15 21

    23.6

    41.6

    66.579.1

    8090

    23.6

    41.6

    3636

    43.343.3

    120.6133.2

    125150

    23.6

    41.6

    7272

    86.686.6

    153.1165.7

    175175

    028 208/230 187 254 39.7 228 2 1 5.3

    7.5 24.2/22

    23.6

    4.16

    //

    //

    124.1/121.9147.7/145.5

    150/150175/175

    23.6

    4.16

    27/3627/36

    75.1/86.675.1/86.6

    217.9/230.2241.5/253.8

    225/250250/275

    23.6

    4.16

    54/7254/72

    150.1/173.2150.1/173.2

    274.2/295.1297.8/318.7

    300/300300/350

    10 30.8/28

    23.6

    4.16

    //

    //

    130.7/127.9154.3/151.5

    150/150175/175

    23.6

    4.16

    27/3627/36

    75.1/86.675.1/86.6

    224.5/236.2239.9/259.8

    225/250250/275

    23.6

    4.16

    54/7254/72

    150.1/173.2150.1/173.2

    280.8/301.1304.4/324.7

    300/350350/350

    15 46.2/42

    23.6

    4.16

    //

    //

    146.1/141.9169.7/165.5

    175/175200/200

    23.6

    4.16

    27/3627/36

    75.1/86.675.1/86.6

    239.9/250.2263.5/273.8

    250/275275/275

    23.6

    4.16

    54/7254/72

    150.1/173.2150.1/173.2

    296.2/315.1319.8/338.7

    300/350350/350

    See Legend on next page.

    1 8

  • 8/3/2019 50ejq Ewq Us

    19/32

    UNIT SIZE50EJQ,EWQ

    NOMINALVOLTAGE

    (3 Ph 60 Hz)

    VOLTAGERANGE

    COMPRESSORS OFM IFMPOWER

    EXHAUSTELECTRIC

    HEAT*POWER SUPPLY

    MIN MAX RLA LRA Qty HpFLA(ea)

    Hp FLA FLA LRA kW FLA MCA MOCP

    028(cont)

    460 414 508 19.9 114 2 1 2.7

    7.5 11

    23.6

    41.6

    61.273.8

    8090

    23.6

    41.6

    3636

    43.343.3

    115.3127.9

    125150

    23.6 41.6 7272 86.686.6 147.8160.4 150175

    10 14

    23.6

    41.6

    64.276.8

    8090

    23.6

    41.6

    3636

    43.343.3

    118.3130.9

    125150

    23.6

    41.6

    7272

    86.686.6

    150.8163.4

    175175

    15 21

    23.6

    41.6

    71.283.8

    90100

    23.6

    41.6

    3636

    43.343.3

    125.3137.9

    150150

    23.6

    41.6

    7272

    86.686.6

    157.8170.4

    175175

    LEGEND

    FLA Full Load AmpsHACR Heating, Air Conditioning and

    RefrigerationIFM Indoor Fan MotorLRA Locked Rotor AmpsMCA Minimum Circuit AmpsMOCP Maximum Overcurrent ProtectionNEC National Electrical CodeOFM Outdoor Fan MotorRLA Rated Load Amps

    Boldface indicates electric heaters at speci-fied kW rating are not available on 50EWQunits.

    *Heater capacity (kW) is based on heater voltage of 208 v, 240 v, and480 v. If power distribution voltage to unit varies from rated heater volt-age, heater kW will vary accordingly.

    Fuse or HACR circuit breaker.

    NOTES:

    1. In compliance with NEC requirements for multimotor and combina-tion load equipment (refer to NEC Articles 430 and 440), the over-current protective device for the unit shall be fuse or HACR breaker.The Canadian units may be fuse or circuit breaker.

    2. Unbalanced 3-Phase Supply VoltageNever operate a motor where a phase imbalance in supply voltage isgreater than 2%. Use the following formula to determine the percentof voltage imbalance.

    % Voltage Imbalance

    max voltage deviation from average voltage= 100 x

    average voltage

    EXAMPLE: Supply voltage is 460-3-60.AB = 452 v

    BC = 464 vAC = 455 v452 + 464 + 455

    Average Voltage =3

    1371=

    3

    = 457

    Determine maximum deviation from average voltage.

    (AB) 457 452 = 5 v(BC) 464 457 = 7 v(AC) 457 455 = 2 v

    Maximum deviation is 7 v.

    Determine percent of voltage imbalance.

    % Voltage Imbalance

    7= 100 x

    457= 1.53%

    This amount of phase imbalanceis satisfactory as it is below the maximum allowable 2%.

    IMPORTANT: If the supply voltage phase imbalance is more than2%, contact your local electric utility company immediately.

    3. MCA calculation for units with electric heaters over 50 kW = (1.25 xIFM amps) + (1.00 x heater FLA).

    1

  • 8/3/2019 50ejq Ewq Us

    20/32

    Controls

    Operating sequence

    Cooling, units with wall thermostat When the roomthermostat calls for cooling, the outdoor-air temp erature(OAT) is above 65 F, and the SAT (supply-air temperature)and the OAT are not in alarm, compressor contactor no. 1is energized. Then compressor no. 1 and outdoor-fan mo-tor (OFM) no. 1 and 2 are started. The indoor-fan motor

    (IFM) is then ener gized, and the econo mizer damp er mo vesto the minimum position. The OFM2 cycles on outdoor-airtemperature. The fan motor is energized at 65 F and de-energized at 55 F.

    Upon a further call for cooling, compressor contactorno. 2 will be energized, starting compressor no. 2.

    After the thermostat is satisfied, the compressors andOFMs are turned off, and the damper moves to the fullyclosed position when using an auto. fan. If using continu-ous fan the damper will stay at the minimum position.

    When the outdoor-air temperature is below 65 F, and theroom thermostat calls for cooling, the economizer damp-ers move to the minimum position. If the supply-air tem-

    perature is above 55 F, the damper continues to open untilit reache s the fully op en p osition, or until the supp ly-air tem-perature drops below 55 F.

    When the supply-air temperature is 55 F, the damper willremain at an intermediate open position. If the supply-airtemp erature falls below 5 5 F, the damp er will modulate closeduntil it rea ches th e minimum po sition or until the supply-airtemperature is above 55 F. When the room thermostat issatisfied, the damper will move to the fully closed positionwhen using an auto. fan or to the minimum position whenusing a continuous fan.

    If the o utdoor a ir alone canno t satisfy the cooling re quire-ments of the conditioned space, economizer cooling is in-tegrated with mechanical cooling, providing second-stagecooling. When the thermostat calls for second-stage cool-ing, compressor no . 1 and condenser fan(s) will be e ner-gized and the position of the economizer damper will bedetermined by the supply-air temperature. If the supply-airtemperature is above 55 F for more than 15 minutes, com-pressor no. 2 is energized.

    When the second stage of cooling is satisfied, the lastcompressor energized and OFM(s), if appropriate, will bedeenergized. The damper position will be determined bythe supply-air temperature. When the first stage of coolingis satisfied, the remaining compressor (if any) and the IFMshuts off. If the thermostat fan selector switch is in the ONpo sition, the IFM will run co ntinuously and the damp ers will

    remain in the minimum position.Cooling, units with space sensor and CCN (CarrierComfort Network) When the indoor-fan motor (IFM)is energized and the outside-air temperature sensor is notin alarm, the software controls space temperature by main-taining the supply-air temperature at the value specified bythe supply-air temperature set point through cycling the com-pressors. Both the supply-air temperature and set point tem-perature are used to adjust the cycling deadband to matchthe a ctual load. The control system provides cooling cap ac-ity control of up to 2 stages of cooling to maintain occu-pied space temperature to the occupied or unoccupied setpoint.

    If nighttime free cooling is enabled via CCN, the indoorfan will be energized and dampers opened to pre-cool thespace prior to the system entering the Occupied mode inthe morning.

    Heating The control module is powered by 24 vac. Ifthe unit is controlled with a room sensor, the fan will runcontinuously in the Occupied mode, with the outside-air

    damper in the minimum position. If the unit is controlledthrough a room thermostat (with FAN set to AUTO), upona call for heat the first stage heat is energized, energizingreversing valve solenoids (RVS1 and 2) a nd compressorno. 1 and 2 , indoor and outdoor fan motors start. Upon acall for additional hea t the second stage of hea t is energized.When the call for heat, is satisfied, the compressors, fanmotors, and heaters will be deenergized and the outdoor-air damper will move to the closed position.

    If the unit is controlled with a room sensor the fan willnot run in the Unoccupied mode unless space temperatureis below the unoccup ied hea t set point. Upo n a callfor hea t,the first stage of he at is en ergized, en ergizing reversing valvesolenoids (RVS1 and 2) and starting comp ressor n o. 1 and2. The indoor and outdoor fan motors start, and the out-door air damper will move to the Unoccupied IAQ position(generally set to zero in the Unoccupied mode). The IAQfeature is enabled through system software. Upon a call foradditional heat, the second stage of heat is energized. Whenthe call for heat is satisfied, the compressors, fan motors,and hea ters will be deene rgized and the o utdoor-air dampe rwill move to the closed position.

    Defrost cycle When the temperature of the outdoorcoil drops below 28 F as sensed by the defrost thermostat(DFT1 or 2) and the defrost timer is at the end of a timedperiod (adjustable a t 3 0 to 9 0 minutes) the de frost cycle willbegin. The co ntrol board will deene rgize the reversing valve

    solenoids (RVS1 and 2), and energize the electric heat. Also,the outdoor-fan motor will stop.

    The unit will continue to defrost until the coil tempe r-ature as measured by DFT1 and 2 reaches 65 F, or the de-frost cycle completes its 10-minute cycle.

    During the defrost mo de, if a circuit defrosts first, the RVSwill o scillate between heating and cooling modes untildefrost mode is complete. This will keep the head pressureon that circuit from getting to high.

    At the end of the defrost cycle, the electric heaters willbe deenergized, the reversing valve solenoids will be ener-gized, and the outdoor fan will start.

    Po w e r e x h a u s t o p e ra t io n The optional power ex-

    haust pa ckages a re factory- or field-installed with verticalunits and optionally installed in the return air ductwork forhorizontal app lications. Th e standard an d modulating p owerexhaust (offered on units with non-modulating to modula-ting a ccessory conversion kit) are th e 2 packages a vailable.The modulating power exhaust package is equipped with afield-adjustable static pressure controller which will controlup to 4 power exhaust stages to maintain a building staticpressure. The blue sequencer located in the control boxbelow the control board can be adjusted by removing thecovers and adjusting the set point dial to the desired build-ing pressure. The standard power exhaust package controls

    2 0

  • 8/3/2019 50ejq Ewq Us

    21/32

    up to 2 stages of p ower exhaust to maintain building p res-sure. These power exhaust stages are staged according to apercentage of the econo mizer damper p osition. The defaultvalues are 25% for Stage 1 and 75% for Stage 2. This pack-age h as set p oints that are adjustable thro ugh software (suchas Service Tool, Building Supervisor, or Com fortWorkssoftware).

    Smoke detector A smoke detector can be used to ini-tiate fire shutdown. This can be accomplished by a set ofnor mally closed p ilot relay contacts which will interrupt po werfrom the 24 -v transformer secondary B terminal to thecontrol circuit breaker (CB4). The wire that connects thesetwo points is white and labeled. W78.

    The smoke detector may be mounted in the return airduct or the supply duct. Ca rrier does not m ake recommen-dations as to specific smoke detector location due to liabil-ity considerations.

    S m o k e c o n t r o l m o d e s The 50EJQ,EWQ units withan optional expansion board and power exhaust performfire and smoke control modes. The expansion board pro-

    vides 4 modes which can be used to control smoke withinthe conditioned a rea. The modes of ope ration are fire shut-down, pressurization, evacuation, and smoke purge.

    Control o ptions

    The control options that the units can p rovide are based onthe following parameters: stand-alone unit with field-suppliedsensors installed; as a system via the Carrier Comfort Sys-tem (TEMP); op tiona l electronic expan sion board installed;linked to the Carrier C omfort Network; an d a vailability of acomp uter and software (Com fort Works, Building Supe r-visor, and Service Tool) or accessory LID-2B device toaccess the base control board.

    NOTE: Access to the base control board allows unit occu-

    pancy schedules, unit timeclock, and various set points tobe changed from their factory-defined default settings.

    The units, as shipp ed, a re o perable as stand-alone units,using either a standard (mechanical or electronic) 2-stageheat, 2-stage cool thermostat, or with an electronic roomsensor and a timeclock to establish un it start an d stop times.

    With a standard thermostat (programmable is optional),heating and cooling operation is set by space temperature.

    With a space sensor and timeclock, the machine willoperate at default values unless they are changed usingappropriate input devices. The space sensor senses spacetemperature and may be equipped with a timed overridefeature, which allows unit operation during unoccupiedperiods.

    The space sensors may be used in multiples to achieve

    space temperature averaging. The use of a space sensoralso allows the unit to be turned on and off from a remotesignal.

    Features with thermostat control of unit

    two-stage hea ting (if installed) two-stage cooling control of unit using Y1, Y2, W1, W2, and G ther mostat

    inputs control of the indoor fan outdoor-air temp erature/ supply-air tempe rature monitoring control of an outdoor-air fan based on outdoor-air

    temperature control of modulating economizer damper to provide free

    cooling when outdoor conditions are suitable, usingsupply-air temperature as a control point control of the economizer damper and indoor fan to

    obtain unoccupied free cooling provide power exhaust output to an external power

    exhaust controller support a field test for field checkout control of 2 stages of non-modulated po wer exhaust compressor Time Guard override (power up and mini-

    mum off and on times) compressor lockout during low supply air temp erature

    Additional features are provided by accessing the stand-ard unit control board via software with a computer. Thesefeatures are:

    electronic exp ansion board features (if installed) control board diagnostics ability to change supply air set po int (econo mizer con trol) ability to chan ge high outdoor air temp erature lockout set

    point (economizer control) ability to change power exhaust set po ints

    NOTE: A unit without a thermostat requires a field-suppliedsensor for operation.

    SMOKE CO NTROL MOD ES

    DEVICE PRESSURIZATION SMOKE PURGE EVACUATION FIRE SHUTDOWN

    Economizer 100% 100% 100% 0%

    Indoor Fan ON ON OFF OFF

    Power Exhaust(all outputs)

    OFF ON ON OFF

    Heat Stages OFF OFF OFF OFF

    2

  • 8/3/2019 50ejq Ewq Us

    22/32

    Controls (cont)

    Features with senso r co ntrol of unit (stand-aloneapplications) Unit control is limited to unoccupieddefault set points, 90 F for cooling, 55 F for heating. Thereare 2 sensor options available:

    T-55 sensor will monitor room temperature and p rovideunoccupied override capability (1 hour)

    T-56 sensor will monitor room temperature, provide un-

    occupied override capability (1 hour), and provide a tem-perature offset of 5 F)

    Standard features are:

    support of remote occupied/ unoccupied input to start andstop the unit

    cooling capacity control of 3 stages using economizerand 2 compressors to maintain space temperature to anoccupied or unoccupied set point

    ena ble hea ting (if installed) or coo ling during unoccupiedperiods as required to maintain space temperature withinthe unoccupied set points

    adjustment of space temperature set points of 5 Fwhen using a T-56 sensor

    Features with sensor control of unit are:

    36 5-day timeclock with backup (supports minute, h our,day of week, date, month, and year)

    daylight savings time function occupancy control with 8 periods for unit op eration holiday table containing up to 18 holiday schedules ability to initiate timed override from T-55 or T-56

    sensors ability to use multiple space temperature sensors to

    average the space temperature supply-air temperature reset for the supply-air temper-

    ature set point temp erature compe nsated start to calculate early start times

    before occupancy access to the Display, Maintenan ce, Con figuration, Serv-

    ice, and Set Point data table through network software

    When the unit is equipped with a field-supplied space tem-perature sensor and a remote contact closure (remote start/stop) on the base control board, the occupied default setpo ints will mon itor unit ope ration. The occupied default setpoints are 78 F cooling and 68 F heating.

    NOTE: For units (with a field-supplied space temperaturesensor) which have not had the base unit control boardaccessed via software to set an occupancy schedule, theremote start/ stop closure will allow the unit to operate inthe pre-configured occupied default set points (based o n

    space temperature) of 78 F cooling and 6 8 F heating. With-out this feature, the unit will control to the unoccupieddefault set points of 90 F cooling and 55 F heating.

    An electronic expansion board may be field-installed toprovide the following features:

    control of modulating economizer damper to maintainindoor air quality (IAQ) when outdoor conditions are

    suitable pro vide discrete inputs for fan status, filter status, field-

    applied status, and demand limit provide an output for the external alarm light indicator

    When the unit is connected to the CCN, the followingexpansion board features can be utilized:

    perform Demand Limit functions based on CCN load-shed commands or the state of the discrete input

    alarm monitoring of all key parameters CCN protocol provides po wer exhaust fire outputs for direct control of

    modulated power exhaust stages during fire or smokemodes

    smoke control modes including evacuation, smoke purge,pressurization, and fire shutdown (modulating powerexhaust required)

    pro vides CCN IAQ p articipation

    See Carrier TEMP literature for complete TEMP (singlezone) application information.

    Features with s ens or co ntrol o f unit (network appli-cations) The base control board p rovides, as standard,a connection for use with a Carrier TEMP system and canalso be integrated into a Carrier Comfort Network.

    When the unit is accessed via a PC equipped withCo mfortWorks, Building Sup ervisor, o r S ervice Tool soft-ware, the following features can be accessed:

    on-board timeclock can be programmed

    occupancy schedules can be programmed

    unit set points can be changed

    alarms can be monitored

    This access is available on the base control board via aRJ-11 phone jack or a 3-wire connection to the commu-nication bus. The timeclock has a 10-hour minimum back-up time to provide for unit power off for servicing unit orduring une xpected power outages. For comp lete CarrierComfort System (CCS) and Carrier Comfort Network(CCN) features and benefits, refer to the CCN productliterature.

    2 2

  • 8/3/2019 50ejq Ewq Us

    23/32

    I/O CHANNEL DES IGNATIONS BAS E MOD ULE

    TERMINAL NO. ASSIGNMENT TERMINAL NO. ASSIGNMENT

    T1-2 SPT (CCN) 10K Thermistor T23-25 Compressor 2 Safety DI (24 vac)

    T3-4 STO (CCN) 10K Thermistor T24-25 Outside Air Enthalpy DI (24 vac)

    T5-6 OAT 5K Thermistor T26-27 Economizer Pos. AO (4-20 mA)

    T7-8 SAT 5K Thermistor T28-29 Heat 1 Relay DO (24 vac)

    T9-10 T30-29 Heat 2 Relay DO (24 vac)

    T11-12 SAT Reset AI (4 to 20 mA) T31-32 CV Power Exhaust 1/Modulating Power Exhaust DO (115 vac)

    T13-14 T33-32 CV Power Exhaust 2 DO (115 vac)

    T15-16 T34-35 Condenser Fan DO (115 vac)

    T17-25 Y1 or Remote Start/Stop DI (24 vac) T36-35 OFC2 DO (115 vac)

    T18-25 Y2 DI (24 vac) T37-38

    T19-25 W1 DI (24 vac) T39-38

    T20-25 W2 DI (24 vac) K1 Indoor Fan Relay DO (LV)

    T21-25 G DI (24 vac) K2 Compr. 1 DO (HV)

    T22-25 Compressor 1 Safety DI (24 vac) K3 Compr. 2 DO (HV)

    I/O CHANNEL DES IGNATIONS EXPANS ION MOD ULE (Field -Ins talle d)

    TERMINAL NO. ASSIGNMENT TERMINAL NO. ASSIGNMENT

    T1-2 T23-25 Fire Evacuation DI (24 vac)T3-4 T24-25 Fire Smoke Purge DI (24 vac)

    T5-6 T26-27

    T7-8 T28-29

    T9-10 T30-29 Alarm Light Indicator DO (24 vac)

    T11-12 IAQ Indoor AI (4 to 20 mA) T31-32 Power Exhaust Fire No. 1 DO (115 vac)

    T13-14 IAQ Outdoor AI (4 to 20 mA) T33-32 Power Exhaust Fire No. 2 DO (115 vac)

    T15-16 T34-35 Power Exhaust Fire No. 3 DO (115 vac)

    T17-25 Fan Status DI (24 vac) T36-35 Power Exhaust Fire No. 4 DO (115 vac)

    T18-25 Filter Status DI (24 vac) T37-38

    T19-25 Field Applied Status DI (24 vac) T39-38

    T20-25 Demand Limit DI (24 vac) K1

    T21-25 Fire Unit Shutdown DI (24 vac) K2

    T22-25 Fire Pressurization DI (24 vac) K3

    LEGEND

    AI Analog InputAO Analog OutputCCN Carrier Comfort NetworkCV Constant VolumeDI Direct InputDO Direct OutputHV High VoltageIAQ Indoor Air Quality

    K Kilo-OhmsLV Low VoltageOAT Outdoor-Air TemperatureOFC Outdoor Fan ContactorSAT Supply-Air TemperatureSPT Space TemperatureSTO Space Temperature OffsetT Terminal

    NOTE: All even numbered terminals are negative () polarity and all odd numbered terminals are positive (+) polarity.

    2

  • 8/3/2019 50ejq Ewq Us

    24/32

    Typical wiring schematic

    LEGEND

    AHA

    AdjustableHeatAnticipator

    BP

    BuildingPressure

    CB

    CircuitBreaker

    CC

    CoolingCompensator

    COM

    Communication

    COMP

    Compressor

    CR

    ControlRelay

    DFT

    DefrostThermostat

    DM

    DamperMotor

    EC

    EnthalpyControl

    FU

    Fuse

    HC

    HeaterContactor

    HR

    HeaterRelay

    IFR

    Indoor-FanRelay

    LS

    LimitSwitch

    NC

    NormallyClosed

    NO

    NormallyOpen

    OAT

    Outdoor-AirThermistor

    OD

    Outdoor

    PESC

    PowerExhaustSequencerC

    ontroller

    PL

    PlugAssembly

    RVS

    ReversingValveSolenoid

    SAT

    Supply-AirThermistor

    TB

    TerminalBlock

    TC

    ThermostatCooling

    TH

    ThermostatHeating

    TRAN

    Transformer

    Terminal(Marked)

    Terminal(Unmarked)

    TerminalBlock

    Splice

    FactoryWiring

    FieldWiring

    ToIndicateCommonPo

    tentialOnly.

    NottoRepresentWiring

    NOTE:Redwireandvio

    letwirearespliced

    togetheratthefactory.T

    hebrownwirehas

    awirenutaddedatthe

    factory.

    2 4

  • 8/3/2019 50ejq Ewq Us

    25/32

    Control wiring

    S PACE TEMPERATURE AVERAGING WIRING

    SPACE TEMPERATURE AVERAGING 4 SENS OR APPLICATION

    SPACE TEMPERATURE AVERAGING 9 SENS OR APPLICATION

    2

  • 8/3/2019 50ejq Ewq Us

    26/32

    Control wiring (cont)

    FIELD CONTROL REMOTE S TART/ S TOP WIRING

    R

    Y1

    Y2

    W1

    W2

    G

    C

    X

    CONTROLBOX

    REMOTESTART/STOPSWITCH

    (FIELD-SUPPLIED)

    SMOKE DETECTOR WIRING

    LEGEND

    Field-Supplied Wiring

    2 6

  • 8/3/2019 50ejq Ewq Us

    27/32

    Application data

    Ductwork Secure vertical discharge ductwork to roofcurb. Interior installation may proceed before unit is set inplace on roof. For horizontal discharge applications, attachductwork to unit, or field-supplied flanges can be attachedto horizontal discharge openings and all ductwork attachedto flanges.

    Thru-the-curb service connections Roof curb con-

    nections allow field power wires and control wires to enterthrough the roof curb opening.

    Thermostat Use of a thermistor type room sensor isrecommended on all CCN installations. A thermistor typeroom sensor or a 2-stage heating/ cooling thermostat maybe used for all other units.

    Heating-to-cooling changeover All units are auto-matic changeover from heating to cooling when automaticchangeover thermostat and subbase or a thermistor typeroom sensor are used.

    Airflow Units are draw-thru on cooling and mechanicalheating and blow-thru on electric heating.

    Maximum airflow To minimize the possibility of con-

    densate blow-off from evaporator, airflow through unitsshould not exceed 500 cfm/ ton.

    Minimum airflow The minimum airflow for coolingis 30 0 cfm/ ton. Refer to 5 0EJQ, EWQ Nominal CFM Rangetable on page 5 for minimum airflow cfm for heating.

    Existing roof curbs (48 / 5 0 DD,DF,DL0 2 4 -0 5 4 units) The 50EJQ,EWQ units will install on existing48 / 50 DD,DF,DL vertical supply and return roof curbapplications. This minimizes installation expenses due to theuse of the existing curb. No additional roof penetrations ortransition curbs are required.

    The existing building ductwork on 48 / 50 DD,DF,DLunits is connected to the unit (not the roof curb). The

    ductwork must be disconnected from the existing unit priorto its removal. The ductwork must then be cut back belowthe roof curb to allow for installation of field-supplied

    ductwork. The field-supplied ductwork will transition fromthe existing building ductwork to the newly installed acces-sory roof curb adapter package. The accessory roof curbadapter package provides sheet metal duct connections tobe installed in the existing roof curb. No connections existin the original roof curb since the ductwork is connected tothe unit, not the curb.

    NOTE: Each installation should be evaluated to determineif the a pp lication will accommo date the accessory roof curbadapter package. Call Carrier Application Engineering formore information concerning individual applications.

    Minimum ambient cooling operation temperature All units equipped with factory economizers to allow freecooling at any outdoor ambient. If mechanical cooling isrequired, the units are designed to operate at outdoor tem-peratures down to 35 F at full load conditions. With acces-sory Motormaster III control units can operate at outdoortemperatures down to 20 F. Outdoor-fan motor no. 1changeout is required for Motormaster III applications.

    Maximum operating outdoor-air temperature The

    maximum operating outdoor-air temperature is 1 15 F.Minimum heating operation outdoor-air temper-ature The minimum heating operation outdoor-air tem-perature is 20 F.

    Internal unit design Due to Carriers internal unitdesign (draw-thru over the motor), air path, and speciallydesigned motors, the full horsepower listed in the PhysicalData table and motor limitations table can be utilized withextreme confidence.

    Using Carrier motors with the values listed in the Physi-cal Data and Motor Limitations tables will not result innuisance tripping or premature motor failure. The unit war-ranty will not be affected.

    Electric heat A field-supplied 90 elbow must beinstalled in the supply ductwork below the unit dischargeconnection.

    2

  • 8/3/2019 50ejq Ewq Us

    28/32

    Guide specifications

    Packaged Rooftop Heat Pump ConstantVolume Application

    HVAC Guide Specifications Section 50EJQ,EWQ

    Size Range: 2 0 a n d 2 5 To n s , N o m in a lCarrier Model Number: 5 0 EJ Q , 5 0 EWQ

    Part 1 General1.0 1 SYSTEM DESCRIPTION

    Outdoor roo f curb or slab moun ted, electronically con-trolled hea ting an d co oling unit utilizing sem i-her meticreciprocating type compressors for cooling and heat-ing duty and optional electric heat for second stagehea ting duty. Units shall discharge supply air verti-cally or horizontally as shown on contract drawings.

    1.0 2 QUALITY ASSURANCE

    A. Unit shall be rated in accordance with ARI Stand-ard 340 and designed in accordance with UL Stand-ard 1995 .

    B. Unit shall be designed to conform to ANSI/ ASHRAE 15 and 62 (latest edition) and NEC.

    C. Unit shall be tested a nd certified by ETL in accord-a nce with ANS I Z2 1 .4 7 S ta nda rd s a s a to ta lpackage.

    D. Roof curb shall be NRCA approved.

    E. Insulation and adhe sive shallm eet NFPA 90 A require-ments for flame spread and smoke generation. Insu-lation shall contain an EPA-registered immobilizedantimicrobial agent to effectively resist the growth ofbacteria and fungi as proven by tests in accordancewith ASTM Standards G21 and 22.

    F. Unit shall be m anufactured in a facility registered tothe ISO 9001:2000 man ufacturing quality standard.

    1. 0 3 DELIVERY, STORAGE AND HANDLING

    Unit shall be stored and handled per manufacturersrecommendations.

    Part 2 Products

    2.0 1 EQUIPMENT

    A. Factory-assembled, single-piece hea ting and coolingunit. Contained within the unit enclosure shall be allfactory wiring, piping, refrigerant charge (R-22), op-erating o il charge, dual refrigerant circuits, micro-processor based control system an d associated h ard-ware, and all special features required prior to fieldstart-up.

    B. Unit Cabinet:

    1. Constructed of galvanized steel, bonderized andprecoated with a baked enamel finish.

    a. Top cover shall be 1 8-gage sheet metal,0.7 5-in. thick.

    b. Access panels and doors shall be 20 -gagesheet metal, 0.5-in. thick.

    c. Corner and center posts shall be 16 -gage gal-vanized steel.

    d. Basepans in the heating and return air sec-tions shall be 16-gage galvanized steel.

    e. Basepans in the outdoor section shall be12-gage galvanized steel.

    f. Compressor rail shall be 12-gage galvanizedsteel.

    g. Condensate pan shall be 16 -gage aluminizedsteel.

    h. Air baffles shall be 18 -gage galvanized steel,0.5-in. thick.

    i. Base rail shall be 14 -gage galvanized steel.

    j. Fan deck (indoor and outdoor section) shallbe 16-gage galvanized steel.

    2. Unit casing sha ll be cap able of withstanding Fed-eral test method Standard No. 14 1 (Method 60 61 )500-hour salt spray test.

    3. Sides shall have person-sized insulated hingedaccess doors for easy access to the control boxand other areas requiring servicing. Each door shallseal against a rubber gasket to prevent air andwater leakage and be equipped to permit ease and

    safety during servicing.4. Interior cabinet surfaces shall be shee t metal lined

    or insulated with minimum 12-in. thick flexiblefire-retardant material, coated on the air side andcontaining an EPA-registered immo bilized anti-microbial agent to effectively resist the growth ofbacteria and fungi as proven by tests in accord-ance with ASTM standards G21 and 22.

    5. Unit shall have a factory-installed conden sate drainconnection and an aluminized steel, sloped con-densate drain pan to p revent standing water fromaccumulating.

    6. Equippe d with lifting lugs to facilitate overhead

    rigging.7. Filters shall be accessible thro ugh a hinged access

    panel without requiring any special tools.

    C. Fans:

    1. Indoor Fans:

    a. Double-width/ double-inlet, ce ntrifugal, beltdriven, forward-curved type with single out-let discharge.

    b. Fan shaft bearings shallbe of the pillow-blocktype with positive locking collar and lubrica-tion provisions.

    c. Statically and dynam ically balanced.

    d. Indoor fan shaft bearings shall have a life of20 0,0 00 hours at design op erating condi-tions in accordance with ANSI B3.15.

    e. Solid fan shaft construction.

    2. Outdoor Fans:

    a. Direct-driven propeller type only, withcorrosion-resistant blades riveted to corrosion-resistant steel supports.

    b. Discharge air vertically upward and protectedby PVC coated steel wire safety guards.

    c. Statically and dynam ically balanced.

    2 8

  • 8/3/2019 50ejq Ewq Us

    29/32

    D. Co mpressors:

    1. Reciprocating, semi-hermetic type only andlocated for easy servicing.

    2. Mounted on spring vibration isolators with an iso-lation efficiency of no less than 95%.

    3. Each equipped with an automa tically reversible o ilpump, operating oil charge, insert-type crankcaseheater to prevent refrigerant migration to the com-pressor, and suction and discharge service valves.

    4. Maximum operating speed of 18 00 rpm (30 rps).

    5. Each on independent refrigerant and electricalcircuits.

    E. Coils:

    1. Indoor Coil:

    a. Face-split circuited, constructed of aluminumfins mechanically bonded to seamless inter-nally grooved copper tubes.

    b. Coils shall be leak tested at 150 psig and pres-sure tested at 450 psig.

    2. Outdoor Coil:

    a. Constructed of aluminum fins mechanicallybonded to seamless internally grooved cop-per tubes.

    b. Air-cooled outdoor coils shall be leak testedat 150 psig and pressure tested at 450 psig.

    3. All coils shall be sam e m anufacturer as un it.

    F. Heating Section:

    Optional Electric Heat:

    Electric resistance hea ters shall be factory-installed,open wire, nichrome element type, insulated withceramic bushings, and include operating and safety

    controls.G. Refrigerant Componen ts:

    Unit shall be equipped with dual refrigerant circuitseach containing:

    1. Solid core filter drier.

    2. Fusible p lug.

    3. Fixed expa nsion device for indoor/ outdoor coils.

    4. Accumulator.

    5. Reversing valve.

    H. Filter Section:

    Filter section shall consist of 2-in. thick, disposable

    fiberglass filters or commercially available sizes.I. Con trols and Safeties:

    1. Controls:

    a. Unit shall be comp lete with self-contained,deman d-oriented microprocessor base d, solid-state control system.

    b. Unit shall be compatible with either a roomsensor or room thermostat with no acces-sory interface required.

    c. Unit staging shall be minimum 2-cool, 2-heat.

    d. Unit shall perform in response to a variablespace temperature signal. Controlsystem shalldetermine control sequences through moni-toring the following operational variables:1) Indoor coil leaving-air temperature.2) Economizer position.3) Minimum economizer set point.

    4) Outdoor-air temperature.e. In the event of a power failure, unit control

    system shall sequence the unit to re-startbeginning with the first stage of cooling orheating.

    f. Thermostats shall be of the dualset point typefor heating and cooling.

    g. Set points must have adjustable deadbandbetween heat and cool.

    h. Unit shall be capable of performing night-time free cooling (software access required).

    i. Control boards shall be equipp ed with flash-ing LED(s) for diagnostics.

    j. Minimum heat on-time of 1 minute.

    k. Unit shall incorporate an outdoor coil defrostsystem to prevent excessive frost accumu-lation during heating duty, and shall be con-trolled as follows:1) Defrost shall be initiated on the basis of

    time and coil temperature.2) A field-settable (30, 50, or 90-minute)

    timer shalla ctivate defrost cycle only if coitemperature is low enough to indicate aheavy frost condition.

    3) Defrost cycle shall terminate whendefrost thermostat is satisfied and shall

    have a positive termination time of10 minutes.

    2. Safeties:

    Unit components shall be equipped with the fol-lowing prote ctions:

    a. Compressors:1) Overtemperature (shuts down individua

    compressor).2) Overcurrent (shuts down individua

    compressor).3) Crankcase heaters.4) High-pressure switch (shuts do wn indi-

    vidual compressor, automatic reset type).

    5) Loss-of-charge switch (shuts do wn indi-vidual compressor, automatic reset type).6) Compressor shall be prevented from

    restarting for a minimum of 5 minutesafter shutdown. Compressor shall run aminimum of 1 0 seconds after starting.

    b. Electric Heat:1) Automatic reset high-temperature limit

    switches.2) Heat limiters (fusible links).3) Overcurrent p rotection short-circuit fuses.4) Branch circuit protection.

    2

  • 8/3/2019 50ejq Ewq Us

    30/32

    Guide specifications (cont)

    J. Op erating Ch aracteristics:

    1. Unit shall be capable of starting and running at115 F ambient outdoor temperature per maxi-mum load criteria of ARI Standard 340.

    2. Unit shall be capable of mechanical cooling opera-tion down to 35 F ambient outdoor temperature.

    3 . Pro vides multi-stage mecha nical cooling capability.

    4 . Unit provided with fan time delay to prevent coldstarts.

    5. Comp ressor shall be capable of operation in heat-ing duty down to 20 F ambient outdoor-airtemperature.

    6 . Unit shall be capable of simultaneo us heating dutyand defrost cycle operation when using electricheaters indicated in Section O, Special Features.

    K. Motors:

    1. Comp ressor motors shall be cooled by suction gaspassing over motor windings and shall have linebreak thermal and current overload protection.

    2. Outdoor-fan motors shall be totally enclosed, 3-phasetype with perma nently lubricated ball bearingsand internal, automatic-reset thermal overloadprotection.

    3 . Outdoo r-fan motor no . 2 controlled to cycle off at55 F and on at 65 F.

    4. Indoor blower mo tor shall be o f the 3 -phase ballbearing type.

    L. Electrical Requiremen ts:

    All unit power wiring shall ente r unit cabinet a t a singlelocation.

    M. Integrated Econo mizer:

    Consists of gear driven dampers, direct-drive motorin conjunction with microprocessor co ntrol system toprovide primary cooling using outdoor air, tempera-ture permitting, supplemented with mechanical cool-ing when necessary.

    1. Dampers shall be low leakage type, not to exceed20 cfm per sq ft leakage at 1 in. wg pressure dif-ferential when fully closed.

    2 . Motor shall have a spring return feature which shutsdampers upon a power interruption or unit shut-down.

    3. Equipp ed with solid-state control that sets the econo-mizer cut-in point at an economical level.

    4. Capable of introducing up to 10 0% outdoor air.

    N. Space Temperature Control:

    1. Two-Stage Therm ostat with Integral Sensor:

    a. Thermostat shall be capable of automaticheating and cooling changeover without sys-tem switches.

    b. Each thermostat or transmitter shall providethe following features:1) Separate locking heating and cooling set

    po int adjustments concea led unde r a lock-ing cover.

    2) An adjustable (3 to 30 F) deadband be-tween heating and cooling set points.

    3) Two LEDs concealed under locking coverto provide remote checkout of controlsystem.

    4) Load reactive time delays to ensure stablesystem p erformance.

    2. Thermistor Type Room Sensor

    a. Sensor shall be capable of setback override.

    b. Set point adjustment may be made at sensor.

    c. Allows access to CCN.

    O. Special Features:

    Certain standard features are not applicable when thefeatures designated * are specified. For assistance inamending the specifications, your local Carrier SalesOffice should be contacted.

    * 1. Optional Outdoor Coil Materials:

    a. Unit shall be factory equippe d with an out-door coil made from copper tubes and cop-per fins.

    b. Unit shall be factory equippe d with an out-door coil made from corrosion resistant pre-coated aluminum fins.

    * 2 . Ro of C urb:

    Forme d 14 -gage galvanized steel with wood nailerstrip. Supports full perimeter of unit.

    * 3. Constant Volume Power Exhaust:

    Package shall include 4 double-width, doubleinlet direct drives, forward-curved power exhaustfans with non-modulating dampers at thedischarge.

    a. Fans shall be statically and dynamicallybalanced.

    b. Exhaust ho od and eliminators shall preventobjects from entering unit through the reliefdampers.

    * 4. Non-Modulating to Modulating Power ExhaustConversion Package:

    Package shall include mo dulating devices to m ain-

    tain a field adjustable interior space pressure setpoint.

    3 0

  • 8/3/2019 50ejq Ewq Us

    31/32

    5. Barometric Relief Damper P ackage:

    a. Package shall relieve excess internal pres-sure and consist of damper assembly, hoods,damper screen, seal strip, and requiredhardware.

    b. Damper assembly shall close due to gravityupon unit shutoff.

    c. Unit moun ted on vertical supply/ return unitsonly; can be duct mounted on horizontalapplications.

    6. Modulating H ead P ressure Control:

    Package shall consist of an accessory outdoor-air package and a solid-state control withoutdoor coil temperature sensor capable ofmodulating outdoor-fan motor n o. 1 speed tomaintain condensing temp erature between 90 Fand 1 00 F at outdoor ambient temperature downto 20 F.

    7. Outdoor Coil Hail Guard:

    Hood with welded wire grille complete with sup-po rt retainers and fastene rs shall be pro vided forprotection of outdoor coil.

    8. Electric Heat Package:

    Shall be fully-assembled for installation. The208 / 230 -v and 460 -v units are designed inaccordance with UL standards and all units fea-ture a single point connection.

    * 9. Space Temperature Sensor:

    This space temperature sensor shall determinethe actual temperature in the conditioned space.

    * 10 . Space Temperature Sensor with Offset (T-56 ):

    This space temperature sensor shall determinethe actual temperature in the conditioned space.In addition, this accessory de vice shall provide aspace temperature offset 5 F.

    * 11. Enthalpy Control:

    a. For use with econo mizer only.

    b. Capable of measuring temperature of out-door air and controlling economizer cut-inpoint at a more economical level.

    12 . Enthalpy Sensor:

    For use with enthalpy control to provide differ-ential enthalpy unit control.

    * 13 . Thermostat and Subbase Assembly:

    To provide staged heating and cooling in addi-tion to autom atic (or ma nual)chan geover and fancontrol.

    14 . Indoor Air Quality (CO2

    ) Sensor (ElectronicExpansion Board Required):

    a. Shall have the ability to provide deman d ven-tilation IAQ control though the economizerwith an indoor air quality sensor.

    b. The IAQ sensor shall be a vailable in ductmount, wall mount, a nd wall mount with LED

    display of CO2 in parts per million. The setpoint shall have adjustment capability.

    c. Sensor shall be adjustable between voltage(0 to 1 0 vdc) and amperage (4 to 2 0 mA)output.

    NOTE: A 4 to 20 mA output is required for50EJQ,EWQ units.

    15 . Electronic Expansion Board:

    Shall provide the following:

    a. Control of modulating e conomizer damp erto maintain indoor air quality when outdoorconditions are suitable.

    b. Discrete inputs for fan status, filter status, field-applied status, and demand limit.

    c. Shall perform demand limit functions basedon the state of the discrete input.

    d. An output for the external alarm lightindicator.

    e. Smoke control modes including evacuation,smoke purge, pressurization, and shutdown(po wer exhaust required).

    f. Pre-occupancy purge shall be available.

    16 . Roof Curb Retrofit Kit:

    Shallp rovide sheet me tal hardware to retrofit unit

    to an existing 48/ 50DD/ DF/ DL roof curb.NOTE: Duct transition to new unit duct config-uration from existing ductwork design will berequired below the existing roof curb.

    17 . LID-2B Interface Device:

    Shall provide access to unit software withenhanced display for access to application timeschedules and control configurations. Shall havea dedicated 24-v power source.

    * 18 . Electronic Programmable Thermostat:

    Cap able of using deluxe full-featured electronictherm ostat. Shall use built-in comp ressor cycledelay control for both heating and cooling duty.

    Capable of working with Carrier direct digitacontrols.

    3

  • 8/3/2019 50ejq Ewq Us

    32/32