Estimated Loads For New National Cancer Institute (500500)
(kVA) (kw)
1 HOSPITAL (IN &Out Patients) 211,500 170 35955 0.8 28764 23011 5621 129 90 19035
2 Research Center 34,000 160 5440 0.8 4352 3482 3650 13 60 2040
3 Conference Center 13,600 140 1904 0.8 1523 1219 1460 2 50 680
4 International Cooperation Center 28,050 140 3927 0.8 3142 2513 2920 7 35 982
11 Technical Institute 6,800 130 884 0.8 707 566 2190 1 35 238
11 Nursing Institute 5,100 130 663 0.8 530 424 2190 1 35 179
7 Housing 16,200 100 1620 0.8 1296 1037 3650 4 20 324
8 Underground Car Park 252,000 40 10080 0.8 8064 6451 4380 28 20 5040
9 Site Utility 1000 0.8 800 640 4380 3 500
10 Mosque 500 60 30 0.8 24 19 2920 0 20 10
11 Oncology Electrical Equipment 800 0.8 640 512 2190 1 800
CAMPUS TOTAL 567,750 62303 49842 39874 189 29827
≈ 30 MVA
Esti.Load
(VA/m2)with Div.
factor
Demand load
(kVA)
EssentialLoad
NO BUILDING / FUNCTION Aream2
Demand load at Dist. Trans. (kVA)
Rated Working Hrs/Year
Annual Consum.
Rate Million (kWHrs)
Norma Power Load
EstimatedLoad
(VA/m2)
Simult.Factor
Demand load at Distribution