420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings...
Transcript of 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings...
![Page 1: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/1.jpg)
EN
OILFLAM 700.1 PR TC 230-400-50OILFLAM 800.1 PR TC 230-400-50 3142127OILFLAM 1000.1 PR TC 230-400-50OILFLAM 1200.1 PR TC 230-400-50
Technical data
Operating instructions
Electric diagrams
Spare parts list
OILFLAM 700.1 PROILFLAM 800.1 PROILFLAM 1000.1 PROILFLAM 1200.1 PR
www.ecoflam-burners.comHEAVY OIL BURNERS
![Page 2: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/2.jpg)
INDEX
420010513700
EN
www.ecoflam-burners.com2
General warnings - Conformity declaration 3Burner designation - Modular delivery system 4Burner description 5
Electrical control panel 5Technical data 6Working fields 7Test boiler - Flame dimension 7Overall dimensions 8Oil operating mode - General safety functions 9
Installation 10Fitting the burner to the boiler 10Heavy oil preparating ring 11Oil connection 12Heavy oil preparating ring scheme 13Feeding line for heavy oil 14Electrical connections 15
Start-up: checking procedure 16Exhaust gas test 17
Start-up 18Fuel selection - Start-up 18Adjusting the max air flow rate 18Firing head setting 18GEFRAN Setting 19Adjusting the max oil flow rate 20Servomotor SQM50 - Air damper motor pre-setting 20Adjusting the pump pressure 20Adjusting the intermediate burner capacity 21Servomotor SQM50 - Final setting 21
Maintenance program 22Troubleshooting instructions 24Operating troubles 25
Appendix 26Control box - Damper actuators 26Fluidics nozzle chart 27Bergonzo nozzle tables 28Pump and pressure regulators 31Electrical diagrams 34Spare parts list 37
OILFLAM 700.1OILFLAM 800.1OILFLAM 1000.1OILFLAM 1200.1
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 14000 kW10000 11000 12000 13000
![Page 3: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/3.jpg)
GENERAL WARNINGS - CONFORMITY DECLARATION
OILFLAM burners are designed forthe combustion of heavy oil. The design and function of the burnersmeet the standard EN267. They aresuitable for use with allheat generators complying with standardwithin their respective performance range.Any other type of application requires theapproval of ECOFLAM.Installation, start-up and maintenancemust only be carried out by authorisedspecialists and all applicable guidelinesand regulations must be complied with.
BURNER DESCRIPTIONOILFLAM burners are progressivemechanical fully automatic monoblockdevices.Emissions values may differ, depending oncombustion chamber dimensions,combustion chamber load and the firingsystem (three-pass boilers, boilers withreverse firing).
PACKAGINGThe burner and all the additionalcomponents are supplied in a modularsystem of packages according to theconfiguration ordered that based on thecountry of installation shall follow theapplicable standards and the local rulesand code of practise. The following standards should beobserved in order to ensure safe,environmentally sound and energy-efficientoperation:
EN 267Automatic forced draught burners for liquidfuels.
EN 60335-1, -2-102Specification for safety of household andsimilar electrical appliances, particularrequirements for gas burning appliances
INSTALLATION LOCATIONThe burner must not be operated in roomscontaining aggressive vapours (e.g. spray,perchloroethylene, hydrocarbontetrachloride, solvent, etc.) or tending toheavy dust formation or high air humidity.Adequate ventilation must be provided atthe place of installation of the furnacesystem to ensure a reliable supply withcombustion air.
!BURNER SELECTION: Type of operation and configuration must be done by professional personnel in order to grant correct working of theburner. Installation, start-up and maintenance must be carried out by authorised specialists and all applicable guidelines and regulations(including local safety regulations and codes of practise) must be observed.
We accept no responsibility for damage arising from:
- inappropriate use;- incorrect installation and/or repair onthe part of the buyer or any third party,including the fitting of non-original parts;- non authorised modifications madeon the burner.
Final delivery and instructions for use
The firing system installer must supplythe operator of the system with operatingand maintenance instructions on or beforefinal delivery. These instructions shouldbe displayed in a prominent location at thepoint of installation of the heat generator,They should include the address andtelephone number of the nearest customerservice centre.
Notes for the operator
The system should be inspected by aspecialist at least once a year.Depending on the type of installation,shorter maintenance intervals may benecessary.It is advisable to take out a maintenancecontract to guarantee regular servicing.
Ecoflam burners have been designed and built in compliance with all current regulationsand directives.All burners comply to the safety and energy saving operation regulations within the standardof their respective performance range. The quality is guaranteed by a quality and managementsystem certified in accordance with ISO 9001:2008.
Declaration of conformityfor dual fuel burners
We,Ecoflam Bruciatori S.p.A.
declare under our sole responsibilitythat the products:OILFLAM 700.1 PROILFLAM 800.1 PROILFLAM 1000.1 PROILFLAM 1200.1 PR
conform to the following standards:EN 267: 2010EN 60335-1: 2008EN 60335-2-30: 2006EN 60335-2-102: 2007EN 55014-1: 2008 + A1: 2009EN 55014-2: 1998 + A1: 2001 + A2: 2008
These products are built in accordancewith the following directives2006/42/EC Machinery directive2004/108/EC EMC directive2006/95/EC Low voltage directive
CE certification, when required, must bedone at installation site by the end user
Resana, 20th December 2010M. PANIZZON
420010513700
EN
www.ecoflam-burners.com 3
![Page 4: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/4.jpg)
BURNER DESIGNATION
MODULAR DELIVERY SYSTEM
OILFLAM 300.1 PR TC 230-400-50
OILFLAM Heavy oil
RANGE NAME BY FUEL TYPE
OILFLAM 300.1 264 kg/h - 3000 kW
MODEL SIZE (Gas: kW; Oil: kg/h)
Standard Class 1 - OIL EN267 (<250 mg/kWh)
EMISSIONS
PR 2 stages progressive mechanicalMD 2 stages modulating mechanical with PIDE 2 stages modulating electronic
OPERATION TYPE
TC Short headTL Long head
HEAD TYPE
Heavy oil
FUEL
420010513700
EN
www.ecoflam-burners.com4
230-400V/50Hz 230-400 Volt, 50 Hz
ELECTRICAL POWER SUPPLY
Heavy oil burners
All heavy oil burners are delivered with electrical pre-heater preassembled into theburner body, including filter and flexible hoses up to 6 MW. Additional accessories and options shall be installed by the installer in accordance to theinstruction and local safety regulations and codes of practise.
KITS - Accessories
Kits and accessories are managed and delivered separately.
Component type
CB Complete burner
KIT Kits
ACS Accessories
![Page 5: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/5.jpg)
BURNER DESCRIPTION
Control panel
420010513700
EN
www.ecoflam-burners.com 5
RWF 40
HLF
HLR
HLBT
SAMA
RA
GEFRAN
SA
S.RSA
SAL
0=STOP1=UP2=LOW3=AUTO
0: OFF 1: ON
Modulating unit RWF 40 (optional)
Main switch I/0
Working lamp
GEFRAN regulator
Selector (0-STOP / 1-Hight Flame /2-Low Flame / 3-Automatic)
Resistor lamp
Lock-out lamp
Reset button
Auxiliaries Resistances switch
LEGENDA1. Housing2. Electrical control panel3. Blower motor4. Pump6. Blast tube8. Burner fixing flange9. Air flap regulation11. Silencer
12. Lifting eyebolts14. Mechanical cam oil15. Servomotor18. Oil pressure regulator
1
6
8
9
11
3
4
18 15
14
12
2
![Page 6: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/6.jpg)
6 www.ecoflam-burners.com
EN
420010513700
TECHNICAL DATA
MODEL OILFLAM 700.1 OILFLAM 800.1 OILFLAM 1000.1 OILFLAM 1200.1
Thermal power max.
kW 7.500 8.500 10.500 12.500
kcal/h 6.465.000 7.328.000 9.052.000 10.776.000
kg/h 660 748 924 1.099
Thermal power min.
kW 2.417 2.750 3.300 4.367
kcal/h 2.096.000 2.385.000 2.862.000 3.788.000
kg/h 214 243 292 386
Operation mode Type Progressive mechanical heavy oil - Modulating with PID
Regulation ratio nominal Type 1÷3 HEAVY OIL
Fuel Type Heavy oil (L.C.V. 9.800 kcal/kg max visc. 50°E at 50°C) - (S) Hu = 10,97 kWh/kg
Emission class std N/A
Control unit Type LAL
Air regulation Type Air flap Air flap Air flap Air flap
Air flap control with servomotor Model SQM50
Air pressure switch mbar 2,5…50 mbar
Flame monitoring Type photoresistor
Ignitier Model BRAHMA / COFI
Motor kW 15 18,5 22 37
Rpm N° 2.800 2.800 2.800 2.800
Voltage V/Hz 230/400 V - 50 Hz
Total power consumption operation W 45.200 49.000 71.000 98.000
Weight body BBCH Kg 683
Electrical panel protection level IP IP55 IP55 IP55 IP54
Sound pressure level without silencer dB(A)
Labtests
95 95,6 96,5 96,5
Sound pressure level with silencer 87,9 88,8 89,1 89,1
Ambient temperature storageMin/Max
-20°…+70° C
Ambient temperature use -10°…+60° C
Oil pump Model TA5 TA5 T5+TV T5+TV
Oil pump motor kW - - 5,5 kW 5,5 kW
Nozzles Type according to the output requested
Fuel thermo regulator Type GEFRAN
Electrical pre-heater kW 30 30 44 30 x2
![Page 7: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/7.jpg)
OILFLAM 700.1
OILFLAM 1200.1
OILFLAM 1000.1
OILFLAM 800.1
7www.ecoflam-burners.com
EN
420010513700
WORKING FIELDS
TEST BOILER - FLAME DIMENSIONS
The burner/boiler matching does not poseany problems if the boiler is CE type-approved.If the burner must be combined with aboiler that has not been CE type-approvedand/or its combustion chamber dimensionsare clearly smaller than those indicated indiagram, consult the manufacturer.The firing rates were set in relation tospecial test boilers, according to EN 267regulations.
The sizes are indicative and dipend onthe configuration, to the combustionchamber pressure and to the draught.The values have been taken out fromtests executed with flame tubes.
The dimensions of the flame are madein test boiler in laboratory withoutresistence therefore exists max andmin lenght that take into account thedifference in lenght that comes from theboiler backpressure.
Example:Burner thermal output = 8000 kW;L flame (m) = 5 m (medium value)D flame (m) = 1 m (medium value)
WARNING: Some flame modificationscan be done in our FLEXSHOP in thefactory in order to shape the flame andadapt it to some special boileror application.
L (m)
2000 3000 4000 5000 6000 7000 8000 9000 10000
4
5
1000
2000 30001000
6
11000
0
2
3
7
8
12000 kW13000
9
10
11
kcal/hx 10004000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000
14000 15000 16000 17000
Ø (m)
2000 3000 4000 5000 6000 7000 8000 9000 10000
0,6
0,8
1000
2000 30001000
1
11000
0
0,2
0,4
1,2
1,4
12000 kW13000
1,6
1,8
2
kcal/hx 10004000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000
14000 15000 16000 17000
FLAME LENGHT HEAVY OIL BURNERS
FLAME DIAMETER HEAVY OIL BURNERS
kg/h100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
kg/h100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
Working fieldsThe working field shows burneroutput as a function ofcombustion chamber pressure. It corresponds to the maximumvalues specified by EN 267measured at the test fire tube.Boiler efficiency should betaken into consideration whenselecting the burner.
Calculation of burner outputQF = Burner output (kW)QN = Rated boiler output(kW)η = Boiler efficiency (%)
QF = QN x 100η
![Page 8: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/8.jpg)
8 www.ecoflam-burners.com
EN
420010513700
OVERALL DIMENSIONS
Packaging (only burner)
X Y Z kgOILFLAM 700.1 1750 2380 1460OILFLAM 800.1 1750 2380 1460 883
OILFLAM 1000.1 1750 2380 1460
OILFLAM 1200.1 1750 2380 1460
X Y
Z
A B C D D1 E F G G1 H1 I L MOILFLAM 700.1 1390 660 730 525 - 1240 385 775 520 1270 460 460 M20OILFLAM 800.1 1480 660 820 535 - 1240 430 775 520 1270 460 460 M20OILFLAM 1000.1 1505 685 820 535 - 1240 460 775 520 1270 460 460 M20OILFLAM 1200.1 1750 800 950 535 - 1410 460 775 900 1270 460 460 M20
R R1 S S1OILFLAM 7-1200.1 360 360 290 400
Dimensions (mm)
D = Short headD1= Long head
Fixing hole dimensions are “I” and “L” as per dimension table.Boiler hole shall be done according to the blast tube dimension “F” plus15-25 mm in order to be able to extract it during maintenance.
Burner-boiler mounting flange
WARNING: Please follow the suggested dimension for the hole onthe boiler flange in order to fit the burner. Make sure that between the boiler andthe blast tube proper insulation is fitted.
640
R R1
SS1
M N °4 fori Ø23
640
R R1
SS1
M N °4 fori Ø23
E D - D1
F
G1
CBA
1023
I
O
H1
G
![Page 9: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/9.jpg)
9www.ecoflam-burners.com
EN
420010513700
OIL OPERATING MODE - GENERAL SAFETY FUNCTIONS
START-UP MODE
As soon as the furnace system is requiredto supply heat the burner control circuit willclose and the program be started. After theprogram has run down the burner will start.The air damper is closed when the burneris out of operation.The automatic furnace controller controlsand monitors the starting function.The electric actuator opens the closed airdamper to its full-load position so that theburner will sweep the furnacecompartment and exhaust ports at therequired air flow rates. Shortly after thepre-ventilation process has been startedthe lack-of-air cut-out must change over tooperating position within a certain time, i.e.the minimum air pressure setting must bereached and maintained until the burner isturned off. At the end of the specified pre-ventilation time the air damper will bemoved into its partial load position. Thisoperation will be followed by the pre-ignition procedure and the oil feed start.The solenoid valves will open and thusallow the pressurized oil to flow to thenozzle and to the return line. The oil will be atomized, mixed with thecombustion air and ignited.A safety period is provided to allow theflame to develop a proper and steady
pattern. On the termination of the safety period, aflame signal must have been received bythe automatic furnace controller via theflame monitor and remain on until theregular shut-off.The startup program of the burner has nowbeen completed.
OIL OPERATING MODE
After the flame has developed the loadregulator will be enabled which brings theburner into its operating position.The load regulator will now control theburner automatically between its partial-load and full-load stages.
Depending on the heat demand, theelectric actuator of the mechanicalcompound control system will be fed withthe OPEN or CLOSE signal via theregulator and thus increase or decreasethe oil and air flow rates.This compound control system will varythe positions of the oil control valve and airdamper and thus regulate the oil flow ratein conjunction with the air flow rate. Theburner can either be controlled in two-stage sliding mode or, if a respective
controller is provided, in stepless controlmode.The stepless control will allow the burnerto be operated at any desired stagebetween its partial-load and full-loadpositions. The burner will be turned offfrom its partial-load position. The airdamper will be closed when the burner isout of operation and will thus prevent coldair flowing through the burner chamber,heat exchanger and chimney.The interior cooling losses will be greatlyminimized.
GENERAL SAFETY FUNCTIONS
In case a flame does not develop whenstarting the burner (fuel release) theburner will shut off at the end of the safetyperiod (safety lock-out). A safety lock-out will also occur in the caseof flame failure during operation, air flowfailure during the pre-ventilation phase andpressure failure during the whole period ofburner operation. Any failure of the flame signal at the end ofthe safety period and a flame signal during
the pre-ventilation phase (external lightcontrol) will result in a safety lock-out withthe control box being locked.
The trouble is indicated by the troublesignal lamp lighting up. The control box can be unlockedimmediately after a safety lock-out bypressing the unlocking key. The programunit will return to its starting position andproceed with the restart of the burner.A voltage failure will result in a regularshut-off of the burner. Upon voltage
recovery there may be an automaticrestart unless another interlock isprovided, e.g. by the safety system. In anycase of trouble the fuel oil supply will beshut off right away. The program unit willstop at the same time causing also thetrouble location indicator to stop.The symbols will indicate the kind oftrouble.
Zündung/VentilePumpe
Teillast
EIN
Betriebsstellung
Leistungsregulierung
Freigabe
Vollast
AUS
Zündung/VentilePumpe
Teillast
EIN
Freigabe
Leistungsregulierung
Betriebsstellung
Vollast
AUS
Oil control:
2-stage sliding Stepless
Full load
Operating position
Load regulator
Release
Partial load
Ignition/valvesPump
Full load
Operating position
Load regulator
Release
Partial load
Ignition/valvesPump
ON OFF ON OFF
![Page 10: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/10.jpg)
5 ÷ 6 mm
3 ÷ 4 mm
10 www.ecoflam-burners.com
EN
420010513700
! WARNING: handling and moving operations must be carried out by specialised personnel.Use the eyebolts to lift the burner in order that it will not overturn and fall down.
INSTALLATION
Fitting the burner to the boiler
To perform the installation of the burnerinto the boiler drill the boiler plateaccording to the dimension given on thismanual and place the burner towards it bylifting and moving the burner by means ofeyebolts.
Place the gasket on the burner flange andinstall the burner into the boiler by fixingnuts into the bolts.The space between the blast tube and theboiler lining must be sealed withappropriate insulating material.
Position of the electrodes - nozzle installation
Ignition Electrode
BURNER LININGCheck before burner installation:
1. Depending on the type of boiler (reverse flame or threepass) check the burner blast tube installation depthaccording to the data specified by the boiler manufacturer orconsult the burner producer.
2. From the factory the nozzle for progressive version mustbe specified from the customer according to boiler output andcombustion chamber geometry, otherwise we will select thenozzle for the 80% capacity of the burner.
3. Check the ignition electrodes and the nozzle on the burnerhead as per factory setting (see figures).The setting of the mixing and ignition unit according to theboiler output will be performed during commissioningprocedure.
4. Check that the head is preset at 50%.
SAL
0 1
MAIN SWITCH
0 - OFF
1 - ON
![Page 11: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/11.jpg)
11www.ecoflam-burners.com
EN
420010513700
! WARNING: make sure that the feeding line is properly dimensioned and is in compliance the local safety rules and code of practise in thecountry of installation.
INSTALLATION
Heavy oil preparation ring, kit and accessories connection
All installations using heavy oil burners haveto be completed with a forced oil preparationring in order to guarantee oil supply to theburner at suitable temperature and pressure(temperature +/- 50° C, pressure 3 bar).For heavy oil with more than 50°E at 50°CEcoflam recommends to lower the maximumoutput of 10-20% and work in excess of air inorder to grant better operation and reducemaintenance.
Installation with heavy oil must provide to the burners:
- CONSTANT PRESSURE- CONSTANT TEMPERATURE
To size correctly the ring for the heavy oil supplyconsider the diagram of the pre-heatingtemperature of the heavy oil according toviscosity and the pump pressure according totemperature.Ecoflam heavy oil and dual fuel heavy oilburners do have in the electrical panel the fueltemperature device GEFRAN that adjusts thetemperature of the heavy oil and grantstemperature stability.
Service tanks + Pumps units.Quotation on request depending on output and configuration.
Ecoflam heavy oil burners are delivered with electrical pre-heater assembled into the burner body or in a separate skid.Additional Forced system “OIL RING” can be design and delivered assembledon skid/frame or offered as singlecomponent.
I. Feeding and filtering system
II. Fuel heating system for reducing oil viscosity plus service tank
III. Forced oil supply system “RING”
STANDARD SYSTEM COMPOSITION FOR LIGHT OILAND HEAVY OIL HEATING AND PUMPING UNIT
ACCESSORIES
OIL PREPARATION UNIT
1
2
3
4
5
0
bar 6
05100105Oil temperature
C°
Pum
p in
let p
ress
ure
RACOMMENDED OIL SUPPLY PRESSURE
Modulation Kit
KITMD-RWF40
Probe-...
KITMD-RWF40 PID regulatorAll progressive burner can be turned modulationgwith the installation of the PID that regulates theoutput combined with a probe.
![Page 12: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/12.jpg)
12 www.ecoflam-burners.com
EN
420010513700
! WARNING: make sure that the feeding line is properly dimensioned and is in compliance with the local safety rules and code of practise in the country of installation
INSTALLATION
Oil connection
HYDRAULIC CIRCUITHEAVY OIL FEEDING
176: oil pump178: solenoid valve180: nozzle rod184: output control valve311: return oil pressure switchCV: check valveRL: return lineVL: suction lineVLO: working oil valve
OIL PRESSURE CONTROL (FEED)The feed pressure is controlled by meansof the pressure regulator installed in thepump and should be set at 25 bar. Thepressure regulator is operated by turningits screw. Make sure to fill the pump withoil prior to taking into operation.
PUMP BLEEDINGOpen the feed and return stop valves andensure the ring line (if any) is in operation.Reduce the oil pressure at the pressureregulating valve. Turn on the pump bypressing the contactor.Check the pump for proper direction ofrotation. Check for proper oil delivery andabsence of leaks in the hydraulic oilsystem. For bleeding the pump open thepressure gauge connection.When taking the burner into operation pro
ceed by gradually increasing the pressureto operating level (25 bar).
CHECKING OIL RING PRESSURE Refer to diagram at page 11 to defineracommended oil pressure.
OIL CONNECTIONHoses are used for connection to the oillines and stop valves. The hoses must beinstalled according to the applicablestandards (relieved of tensile load, free ofdistortion) to avoid kinking and exclude thedanger of breakage. Take care whenmounting the oil lines to bring their ends asclose to the burners as possible and toarrange them in a way that the boiler doorand the burner can be swing out withoutany obstruction.Refer to the technical documentation for
the line dimensions for the feed and returnlines from the stop valves to the tank.
OIL FILTERA filter must be installed upstream of thepump to protect the oil pressure pump andthe hydraulic system.
INSTALLATION OPTIONS• Two-line installation (separate feed andreturn lines without delivery pump).• Ring line system (with delivery pump andgas-air separator).
LEGENDA1. Inlet2. Return3. Bleed and pressure gauge port4. Vacuum gauge port5. Pressure adjustment6. Nozzle outlet7. Heater8. Hose9. Oil filter10. Oil ball valve
! WARNING: Check that the pump rotation is correct and before start up it has been pre-filled
8
8
910
VLO
311
178
180
176
184
VLRL
CV
CV
VLO
176
VL
178
180
RLVL
113
184
CV
CV
![Page 13: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/13.jpg)
13www.ecoflam-burners.com
EN
420010513700
INSTALLATION
Heavy oil preparation ring scheme
Hot water
Hot water
Return
hot water pipe
hot water pipe
oil pipe oil pipe
heating cable insulation
section13
12
LEGENDA1 - Burners2 - Service tank3 - Electric heaters4 - Safety and operation thermostat5 - Level switch (working + safety )6 - Heating coil7 - Self-cleaning oil filter8 - Load pumps9 - Ring pumps10 - Oil ring control pressure device11 - Heating cable12 - Main heavy oil storage tank13 - Heating coil
![Page 14: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/14.jpg)
14 www.ecoflam-burners.com
EN
420010513700
INSTALLATION
Feeding line for heavy oil
The pumps that are used can be installed both into single-pipe anddouble-pipe systems:Single-pipe system: a single pipe drives the oil from the tank to the pump’sinlet that deliver the pressurized oil to the nozzle and part of the oil not usedgoes back to the pump. With this single pipe the by-pass plug must beremoved and the return port must be sealed with steel plug and washer. Double-pipe system: this is the default solution from the factory. The return pipe send the excess oil from the pump to the tank. Dependingon the type of pump used to change from a 1-pipe system to a 2-pipe-system, insert the by-pass plug (as for ccw-rotation referring to the pumpshaft).
Note for commissioning: during commissioning, the filter, pipelines andpumps must be pre-filled with fuel oil and vented. The direction of rotation of the motor should be checked. Whencommissioning it must be ensured that pump never run dry.
SUNTEC TA
NOZZLE SELECTIONPlease refer to diagram to select Ecoflam recommended nozzle for theoutput that is required given the output necessary in the installation. Regular maintenance is highly recommended. Nozzle has to be cleaned in petrol or paraffin and if filter or other parts aredefective or damaged the nozzle must be replaced.
NOZZLE CHART IS AVAILABLE ON APPENDIX PAGE
Oil under suction
Oil under pressure Pressuregauge port
To nozzle
Pressureadjustment
By-passplug
inserted
By-passplug
removed
Return
Intake from Tank
TWO PIPEINSTALLATION
Vacuum orinlet pressure
gauge portBy-passed oilreturned to tank,or to suction
Intake from Tank
ONE PIPEINSTALLATION
Returnplugged
SUNTEC T
Pressuregauge port
Topressure
regulatingvalve
Plug inserted betweenhigh pressure and shaft seal
Intakefrom Tank
Vacuum orinlet pressure
gauge port
Oil under pressure
Oil under suction
Intake from Tank
Topressure
regulating valve
![Page 15: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/15.jpg)
15www.ecoflam-burners.com
EN
420010513700
INSTALLATION
Electrical connections
! WARNING: Electrical wiring must be carried out with electrical supply disconnected and with burner switch in position OFF.Electrical supply must correspond to the one shown on the burner label.
APPLICABLE STANDARDThe electrical connection work comprisingall the installation materials, terminals andearth connections must be carried out inaccordance with the applicableregulations. For the electrical installation ofthe burner care must be taken to observethe circuit diagram made out for thefurnace system.The electrical connection of the burner andinstruments shall be entrusted toauthorized specialists only.
NOTE: For the installation of theconnection cables care must be taken toprovide cable loops of sufficient length toallow for the swing-out of the boiler doorand burner. Make sure after the completion of theelectrical connection work to check thewiring of the electrical system of theburner. This should include a check of thedirection of rotation of the burner motor(fan).
GENERAL WARNINGS:All applicable electrical safety regulationsmust be followed. Failure to correctlydimension the suitable input power andearth the equipment may cause damagesto person and compromise the correctfunction of the burner therefore theelectrical system shall be checked byqualifed personnel. The manufacturer declines allresponsibility for modifcations orconnections different from those shown inthe electrical scheme.Adapters, multiple plugs and extensioncables may not be used for theequipment’s power supply. An multi-pole switch in accordance withcurrent safety regulations is required forthe mains supply connection.
ELECTRICAL CONNECTION1) of the burner- Built-in electrical cabinetUse cable gland in order to secure therequired level of protection. All the links,power and control, are connected to theterminal block of the cabinet. Providecables in sufficient length to secure therotation of the burner body according tothe assembly.Check and adjust the size of thecontactors and thermal relays and thewires section according to the motor andsupply voltage specs.
ATTENTION: Wiring is not supplied.
2) of the fuel oil motor-pump unit- Connect the power circuit of the motor(hanging wires) to the plugs on the fuel oilvalves.- Check proper motor rotation.
The burners are produced withconnections suitable for power supply400 V three-phase.The burners with electric motors of anoutput lower or equal to 7,5 kW can beadapted to 220-230 V (please follow theinstructions on the backside); motors withhigher output can only work 380-400 Vthree-phase.In case of request of burners different fromthe above mentioned standard, it isrecommended to make specific mention inthe order.
Instructions: how to adapt electricmotors of an output lower or equal to7,5 kW to 220-230 V power supplyIt is possible to change the voltage of theburner by operating as follows:1. change the connection inside theelectric box of the motor, from star to delta(see picture 1);
LEGENDAHLB: lock-out lampSTAB: two stages thermostatHLF: burner on flame lampSTC: boiler thermostatSTS: safety thermostatSA: active probeSP: passive probe
T P
STAB50 Hz 400 V
50 Hz 400 V
RP
T P
STSTV
T PSTC
HLB
B
RA RAHLF
Q1
Q2
PE
S
T
R
R
S
T
PE
N
N
13 503 N51 2221N858476 84 5 9 10 11R1TSR N S1 T1 N 1 2 12
PROBES CONNECTION
9 13121110
SA
QBE....
GL M U1
ACTIVE PROBE CONNECTION(FOR MODULATING VERSION)
12 13119 10
SPQAE...
M B
PASSIVE PROBE CONNECTION(FOR MODULATING VERSION)
230V
400Vfig.1
2. change the setting of the thermal relay,referring to the absorption values indicatedin the motor nameplate. If necessary,replace the thermal relay with another oneof suitable scale.This operation is not possible on motorsabove 7.5 kW. For more information, please contact theEcoflam staff.
![Page 16: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/16.jpg)
16 www.ecoflam-burners.com
EN
420010513700
START-UP: CHECKING PROCEDURE
CHECKS BEFORE COMMISSIONING:
• That the burner is assembled inaccordance with the instructions givenhere.• Setting the combustion components.• All electrical connections must be correct.• Check the burner motor for correctdirection of rotation.• The heat generator must be ready foroperation, and the operating regulationsfor the heat generator must be observed.• The heat generator and heating systemmust be filled with water and thecirculating pumps must be in operation.• The temperature regulator, pressureregulator, low water detectors and anyother safety or limiting devices that mightbe fitted must be connected andoperational.• The exhaust gas duct must beunobstructed and the secondary airsystem, if available, must be operational.• An adequate supply of fresh air must beguaranteed.• Check tank, lines and oil pump are filledwith oil and correct oil nozzle is fitted.• With burner in starting position check thatair damper is in “CLOSED” position.• Check that control box is unlocked and inits original position.• A standard-compliant measuring pointmust be available, the exhaust gas duct upto the measuring point must be free ofleaks to prevent anomalies in themeasurement results.
OIL START-UPOpen all shut-off valves of oil supplysystem.• Set fuel selector switch to its “Oil”position.• Fill pump with oil.• Mount pressure gauge in the feed lineand return line.• Mount the pressure gauge for checkingthe pump suction pressure.• Make sure that the nozzle is size andmounted correctly.Bleeding of oil systemShortly start the burner and check forproper direction of rotation. Bleed the oilline and oil pump.
CAUTION: The hydraulic system has beenfilled with oil by the manufacturer.This may cause ignition trouble wheninitially operating the system. When starting the burner take care toincrease the oil pressure slowly to theoperating level.
Prior to the initial fuel feed start makea functional test of the burner programflow:
Oil system:• Open all shut-off valves of the oil supplysystem.• The oil solenoid valve in the feed linedisconnect on the terminal strip (seeCircuit Diagram).• Start burner and check program flow forcorrect start-up sequence:
1. Fan starts.2. Pre-ventilating damper.3. Air pressure check.4. Partial-load air damper.5. Ignition.6. Valves open (disconnected valveremains closed).7. Safety lock-out after expiry of safetyperiod (see control box).
• Reconnect the valve.• Unlock the control box.
![Page 17: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/17.jpg)
17www.ecoflam-burners.com
EN
420010513700
QF = QN = 1000 = 1136 kW
Volumetric gas flow rate at STP:
vBn = QN = 1000 = 125 m3/h
Volumetric gas flow rate in operatingcondition:
vBB = vBnT = pn =
= 125 273+15 1013,25 = 123,9 m3/h
EXHAUST GAS TEST
To ensure an economically efficient andtrouble-free operation of the system it willbe necessary to adjust the burnerspecifically in accordance with the furnacesystem. This is achieved by means of afuel-combustion air compound control unitwhich adjusts the burner to ensure aproper combustion. Exhaust gas tests arerequired for this purpose.The percentage CO2 and O2 and theexhaust gas temperature will have to bemeasured to determine the efficiency andcombustion quality.Prior to any measurement make sure tocheck the boiler and exhaust gas systemfor absence of leaks.
Secondary air will falsify the measuredresultsCheck that the exhaust gases have aresidual oxygen (O2) content as low aspossible and a carbon dioxide (CO2)content as high as possible.The carbon monoxide content of theexhaust gases must be below the currentlyapplicable specifications in all load stages.In the fuel oil combustion mode thepermissible soot number in the exhaustgas is not allowed to be exceeded
DETERMINING THE VOLUMETRIC GASFLOW RATEThe thermal furnace output of a boiler (QF)is the amount of heat supplied with the gasin a unit of time.When taking the burner into operation thevolumetric fuel flow rate should beselected according to the nominal thermalcapacity of the boiler.
Example:
Nom. thermal output QN 1000 kWBoiler efficiency nK 0,88Calorific value of gas Hu 9,1 kWh/m3
Gas pressure pU 100 mbarBarometer reading pamb 980 mbarGas temperaturerelative tgas 15°C
Gas temperatureabsolute T (tgas+273)
Standard atmosfericpressure pn 1013 mbar
0,88nK
Hu*nK 9,1*0,88
273 pamb+ pu
273 980+100
Recommended combustion parameters
Ratio between O2- and CO2- for natural gas H (CO2max = 11,7%)
Ratio between O2- and CO2- for light oil EL (CO2max = 15,40%)
Ratio between O2- and CO2- for heavy oil S (CO2max = 15,60%)
O2 = 21 CO2max - CO2gem = %CO2max
WARNING: if the installation is above sea level the output of the burnervary base on the diagram.The regulation of the burner in this case shall take into account thereduced power of the burner due to the missing air.
Fuel Recommended(%) CO2
Recommended(%) O2
Natural gas 10 ÷ 9 3,1 ÷ 4,8
Light oil 13 ÷ 11,5 3,3 ÷ 5,3
Heavy oil 12,5 ÷ 11 4,2 ÷ 6,2
00
500100015002000250030003500400045005000
5 10 15 20 25 30 35 40 45 50
Mean air pressure vs. altitude above sea-level
Fan capacity reduced by [%]
Altit
ude
of in
stal
latio
n si
te [m
]
CO2 gem = % CO2 measured on dry flue gases
![Page 18: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/18.jpg)
18 www.ecoflam-burners.com
EN
420010513700
START-UP
Select the oil operation in order to proceed with start up on the oil side. On the selector put the operation on minimum capacity.
Adjusting the maximum air flow rate
START UP THE BURNERThe control box starts the pre-purge cycle, the fan motor and the oil motor and opens the air flaps in full open positon.At the end of pre-purging, the control box drives the servomotor into the igniton positon and starts the igniton transformer.After a few seconds the control box opens the oil valve and starts the flame. After the flame stabilisaton the control box drives theservomotor in the low flame.In case of faulty igniton, the control box switches the burner into safety condition, in such a case you must rearm the burner.Gradually go step by step using the selector on positon 0 to stop the flame, from the low flame to the high flame in order to havea stable flame. For each position from 0 to 90° do oil setting adjusting oil return pressure as described in the next pages. When theservomotor arrives at 90° you have completed first tuning of air and oil flow according to the boiler capacity required. Check thecombustion values and adjust the oil pressure.
Firing head setting
In order to adjust the maximum air flow rate see figure withselector in maximum operation. Loosen the nut holding the airdamper transmission rod and correct air flow till you reachthe combustion values suggested by reading the value on thecombustion analyser. If you do not reach acceptable air flowrate you shall adjust the firing head. Move the blast tubebackwards to increase air flow forward to reduce.
++ -
-
The firing head is pre-adjusted at the 50% from the factory. Thesetting fully open enables to reach the full power of the burnerand full close to reach the minimum power of the burner. The optimal position depends on the output that we need toreach but the default setting shall be modified only when you arenot able to reach the suggested combustion value by adjustingthe air flow in the maximum flame.
Fuel selection - Start-up
SAMA
3=AUTO2=LOW1=UP0=STOP0 1
2
3
0 : operating elements locked in an intermediate position.
1 : operation on maximum capacity2 : operation on minimum capacity3 : automatic operation
+ -
MAIN SWITCH
0 - OFF
1 - ON
SAL
0 1
KMV
KMP! KMP - KMV contactor: check the oil pump motor and air fan motorrotation and keep KMP pressed till the oil circuit is loaded.If the rotation if not correct invert the two phases on the power supply.
![Page 19: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/19.jpg)
19www.ecoflam-burners.com
EN
420010513700
START-UP
Gefran setting
The display shows oil temperature.
The 4 leds are related to the following functions:• Out 1: contact driving working heaters• Out 2: contact driving upper heaters KMRL1• Out 3: contact driving upper heaters KMRL2• Out 4: burner start driving contact (as the oil reaches this temp the pump is activated)
The temperatures are already properly factory setted:• Out 1 (113°)• Out 2 (115°)• Out 3 (120°)• Out 4 (105°)
WARNING: Burner will start only when the first three led of the temperature will be off so that heavy oil will be in temperature.
To modify factory temperature setting act as follow:• press key “F”• the led Out 1 starts to ash, if You need to modify minimum oil temperature press increase or decrease button, after confirm the newvalue pressing again “F”• if you need to modify an other temperature press again “F” untill You the relevant led ashes.Please take care: if key “F” is pressed for a too long time, you enter in “configuration level” phase 1, (see “CF1” on the display); these parameters are factory setted and they have not to be modified: if you enter this function – you see CF1 ashing on the display –wait 10 seconds until the regulator automatically goes out from “configuration level”.
Increase key
Decrease key
“Function” key
Display
ADJUSTMENT OF FUEL THERMOSTATS
Inside the electrical panel there is a safety termostat that is set up at 160°C.
Said adjustments can be slightly modified following the type of fuel and particular uses.
![Page 20: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/20.jpg)
20 www.ecoflam-burners.com
EN
420010513700
START-UP
Adjusting the maximum oil flow rate
Put the selector on the maximum operation. Adjust the oil pressure reading the value on the return manometer / pressure gaugeaccording to the nozzle tables provided in the appendix. NOTE: the pump pressure is set from the factory at the pressure required nozzle pressure required as per table of nozzle selection inappendix. If the output required is different from the one set from the factory the pressure can be adjusted according to the instructionbelow.
Adjusting the pump pressure
The pump pressure is set at avalue of 22-25 bar during thetesting of burners. Before starting the burner, bleedthe air in the pump through thegauge port. Fill the piping with heavy oil to facilitate the pump priming. Start the burner and check the pump feeding pressure. In case the pumppriming does not take place during the first pre-purging, with a consequent, subsequent lock-out of the burner, rearm the burner’s lock-out to restart, by pushing the button on the control box. If, after a successful pump priming, the burner locks-out after the prepurging,due to a fuel pressure drop in the pump, rearm the burner’s lock-out to restart the burner. Do never allow the pump working without oilfor more than three minutes.NOTE: before starting the burner, check that the return pipe is open. An eventual obstruction could damage the pump sealing device.
SUNTEC TA.... 1 - INLET2 - RETURN3 - BLEED AND PRESSURE GAUGE PORT.4 - INLET GAUGE PORT 5 - PRESSURE ADJUSTMENT6 - TO NOZZLE
1
2
5
6
34
Servomotor SQM50 - Air damper motor pre-setting
The cams of the servomotor are set from the factory in order to start the burner and reach the maximum output. The following setting are the standard one:I. High flame position 90° (maximum value 70°).II. Air flap position in standby 0° (minimum value 0°).III. Ignition position 15°.IV. Low flame position 40° (can be modified depending on the minimum output of the boiler).V. To VIII not used
Cam VIII is never used
1
4 3 6
TV
2
5
SUNTEC T.... + TV
Adjusting the valve TV
1. Remove the cap A of the pressure regulating valve TV.
2. Loosen the fixing nut B and use an Allen wrench on the screw C toadjust the delivery oil pressure. To increase the pressure turn clockwise, todecrease the pressure turn anticlockwise.
3. Tighten the nut B and pay attention not to turn also the adjusting screw.
4. Screw on the cap A, back to its previous position.
A
B
C
B
A
1 2
3 4
![Page 21: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/21.jpg)
21www.ecoflam-burners.com
EN
420010513700
START-UP
Once the point to point oil cam setting has been completed we need to set the finalminimum output of the burner using the servomotor cam VI (low flame oil). Using the suitable key regulate the grades (“+/-“ switch). The low flame position must be higher than the ignition position cam on the servomotor.Turn the burner off and start it again in order to check if the burner start properlyotherwise adjust the ignition oil cam number IV.
OIL SETTING ENDED: switch the selector to automatic position.
Servomotor SQM50 - Final setting
! WARNING: Do not use the button cam drum release button.
Adjusting the intermediate burner capacity
In order to adjust intermediate capacity of the burner use the selector on position 0 to stop the stroke and regulate the cam onthe different screw position. The adjustment shall be done according to the drawing in orderto have the correct combustion value in each point “+/-“ switch(different screw positions). Using a suitable Allen wrench, change the position of the cam guide blade; if you screw it down, the flow rate is reduced; if you unscrew it, the flow rate increases.
WARNING: the variable profile of the cam shall have a normal proportional curvature in order to have good combustion values and reduce its mechanical stress breakdown.
+--
+ -
Point to point oilcam configuration
! WARNING: Once the setting on the oil has beencompleted make sure that you close the manometer– pressure switch tap.
VLO
311
178
180
176
184
186
VLRL
CV
CVmin
II
185
VLO
311
178
180
176
VLRL
CV
CV
max II
185
184186
VLO
180
176
RLVL
176
CV
CV
131
178
CV
max
CV186
184
185
I
186
VLO
180
176
RLVL
176
CV
CV
131
178
186
184
CV
CVmin 186
185
I
LEGENDA
176: oil pump178: solenoid valve180: nozzle rod184: output control valve185: manometer186: pressure regulator311: return oil pressure switchCV: check valveRL: return lineVL: suction lineVLO: working oil valve
![Page 22: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/22.jpg)
22 www.ecoflam-burners.com
EN
420010513700
MAINTENANCE PROGRAM
!Burner and boiler servicing must only be carried out by authorised qualied personnel at least once a year. Depending on the type of installation, shorter maintenance intervals may be necessary.The system operator is advised to take out a maintenance contract to guarantee regular servicing.WARNING: Use original spare parts.
SAFETY WARNINGS: 1. Turn off the power supply and protect the system from accidental start-up.2. Cut oil supply.3. Make sure there is no residual power in the system and that the actions in points 1
and 2 have been completed.4. Before opening the burner casing, ensure that the fan motor has stopped completely.
Failure to observe any of these instructions will result in the risk of death or injury!
WORKS RECOMMENDED AS PART OF ANNUAL BURNER MAINTENANCE:
• Emergency stop button function check• Check burner start characteristics• Run burner test and input measurement in the boiler room• Clean the combustion components and replace defective parts if necessary• Check the combustion head components and make sure that all components are in good condition otherwise replace them• Replace ignition electrodes and nozzle if necessary and check their correct position after any intervention• Flame monitor and automatic combustion control unit function check• Clean the fan wheel and the housing and grease rotating parts if necessary• Clean the oil filter cartridge with gasoline periodically and check the tightening of the O rings, replace them if necessary • Make visual inspection of the burner’s electrical components and eliminate malfunctions if necessary• Burner safety devices function check (air pressure/gas pressure switches)• Commissioning the burner and correct the adjustment values if necessary
NOTES ON REASSEMBLING: Perform the described step in reverse order and make sure to refit components as they were originally assembled and the system is free from leaks. Use only original spare parts.
DRAW UP A MEASUREMENT REPORT ACCORDING TO THE LOCAL REGULATION AND CODES OF PRACTISE OF THECOUNTRY
EXHAUST GAS LOSSExhaust gas loss by way of free heat willoccur as a result of the temperaturedifference between the fuel-air mixtureentering the furnace chamber and thegases discharged. Any increase in theexcess of air and the resultant higherexhaust gas volume will cause the exhaustgas loss to rise. The exhaust gas loss canbe calculated as follows:
qA = (tA - tL) A1 + BCO2
qA = exhaust gas loss [%]
tA = exhaust gas temperature [°C]
tL = combustion air temperature [°C]
CO2 = volumetric content of carbon dioxide [%]
ExampleData measured in natural gas mode:CO2 content of exhaust gases: 10,8%Exhaust gas temperature: 195°CAir intake temperature: 22°C
The exhaust gas loss can be calculated as follows:
qAf = (195-22)( 0,37 + 0,009) = 7,48%10,8
Data measured in fuel oil mode:CO2 content of exhaust gases: 12,8%Exhaust gas temperature: 195°CAir intake temperature: 22°C
The exhaust gas loss can be calculated as follows:
qAf = (195-22)( 0,49 + 0,007) = 7,83%12,8
Light oilEL
Heavy oilS Natural gas Town gas LPG
A1 0,50 0,490 0,370 0,350 0,420
B 0,007 0,007 0,009 0,011 0,008
SAMA
3=AUTO2=LOW1=UP0=STOP0 1
2
3
![Page 23: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/23.jpg)
23www.ecoflam-burners.com
EN
420010513700
MAINTENANCE PROGRAM
ATTENTION: to remove the nozzle use thesuitable box wrench taking careto not damage the electrodes.Check the position of the electrodes after any interventionas wrong position could cause ignition troubles.
POSITION OF ELECTRODES
OIL FILTER CLEANING
ATTENTION: Periodically clean oil cartridge withgasoline and replace them if it is necessary!
REMOVING THE FIRING HEAD
5 ÷ 6 mm
3 ÷ 4 mm Ignition Electrode
![Page 24: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/24.jpg)
24 www.ecoflam-burners.com
EN
420010513700
TROUBLESHOOTING INSTRUCTIONS
TROUBLESHOOTING TABLEOIL OPERATION
Burn
er d
oesn
't st
art
Fuel
pum
p no
isy
/un
prim
es /
leak
s
Burn
er s
tarts
with
cont
inuo
us p
re-
purg
eBu
rner
sta
rts a
ndth
en g
oes
into
lo
ck-o
utPi
lot I
gniti
on fa
ilure
(1
st s
afet
y tim
e -
LFL
only
)
Mai
n Ig
nitio
n fa
ilure
(2
nd s
afet
y tim
e)
Burn
er lo
ck-o
ut a
fter
flam
e ap
pere
ance
/pu
lsatio
nFl
ame
cont
rol re
peat
sth
e cy
cle a
nd d
oesn
’tgiv
e co
nsen
t
Smok
e in
flam
e -
dark
Bac
hara
ch
Burn
er d
oesn
'tsw
itch
into
Hi f
lam
e
Burn
er lo
ck-o
utdu
ring
oper
atio
n LFL LAL
STAT
US
CAUSES REMEDIES
MUL
TICA
LOR
MU
LTIF
LAM
MAI
OR
OIL
FLAM
HEA
VYO
IL
Preheating period too long Check GEFRAN controller, replace if necessary X X X YES YES
Defective Gefran controller Replace control unit X X X YES YES
PRE-
STAR
T(M
ISSI
NG
SIG
NAL
S)
Defective control box unit Replace control box unit X X X X X X X X YES YESNo electrical power supplyWrong electrical connections
Check switches/contactorsCheck connections X YES YES
Air pressure switch not "closed" Check contacts X YES YES
Boiler thermostats open Check contacts X YES YES
Fan motor overload intervention Replace fuse X YES YES
Auxiliaries fuses interrupted Replace fuse X YES YESServomotor [CLOSE] position switch not reach Check servomotor settings X YES YES
PRE-
STAR
T (O
IL P
UM
P)
High vacuum in oil pipe due todirty filter
Clean filter or replace filtercartridge X X YES YES
Burner is higher than oil tank bymore than 3 m
Reduce Height or prepare a ringline pump X X YES YES
Air in the oil pipeline Re-tighten pipe connections X YES YES
SEQ
UEN
CE
STAR
T Servomotor [OPEN] positionswitch not reach Check servomotor settings X YES YESServomotor [MIN] positionswitch not reach Check servomotor settings X YES YES
Extraneous Light Eliminate light source X YES YESFuel solenoid valve fails to close(Light oil Burner - direct ignition)
Clean valves or replace ifnecessary X YES YES
LAC
KO
F AI
R
Air pressure switch fail to connect to Terminal 14 Check contacts X YES NO
Fan contaminated/dirty Clean fan X X X YES NOFan motor rotation direction notcorrect Check direction and contactor X X X YES NO
IGN
ITIO
N &
FLA
ME
STAB
LISA
TIO
N P
ERIO
D
Flame supervision circuitinternal test failed Replace control unit X YES NOPilot flame failure - Pilot gasvalves not open
Check valves contacts / replace ifnecessary X YES NO
Pilot flame establish - weakflame signal
Check flame sensorReplace if necessary X YES NO
Ignition transformer faulty Replace X X YES YESIgnition cable & electrodesdefective Replace X X YES YES
Electrode bad position Check setting / replace ifnecessary X X YES YES
Fuel oil solenoid valve fails toopen
Check contacts and clean valves.Replace solenoid coil if necessary X YES YES
ON
LYFO
R O
ILBU
RN
ER
Air pressure switch not close,Oil pump contactor open Check air pressure switch contacts X NO YES
No oil supply Check shut-off valvesCheck Pump, replace if necessary X NO YES
Oil pump coupling broken Replace pump unit X NO YES
CO
MBU
STIO
N
Flame sensor signal failure Clean, re-position or replace ifnecessary X X X X X YES YES
Head adjustment not correct Check settings X X X YES YESOil/Air mixture setting notcorrect Check settings X X X YES YES
Dirty combustion head Clean or replace disk if necessary X X X YES YES
Nozzle dirty or damaged Clean or replace nozzle ifnecessary X X YES YES
Fuel pressure inappropriate Adjust pressure or replace pump ifnecessary X X X YES YES
Capacity reduction Check filter, pump pressure andnozzle. Replace item if necessary X YES YES
Load control device does notclose
Check load control, replace ifnecessary X X YES YES
The list of faults/causes/possible solutions for a set of main failures is a guideline for professional personell authorised to carry outservice and maintenance. Irregular burner operation or malfunction: check that every adjustment parameter is correctly set as per instruction on this manual.
![Page 25: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/25.jpg)
25www.ecoflam-burners.com
EN
420010513700
OPERATING TROUBLE
In case of operating trouble it should bechecked whether the system is in properworking order.
Make a check for the following:1. Availability of fuel oil in the tank. Correct position of fuel selector switch.2. Availability of electric power in theburner system.3. Proper functional order and setting of allcontrol and safety instruments such astemperature controller, safety limiter, waterfailure cut-out, electrical limit switches, etc.
If the trouble is not found to be due to anyof the above-mentioned points it will benecessary to test the burner functions verycarefully.
Prevailing conditions:The burner will be found to be out ofoperation and in faulty and interlockedposition.Proceed with searching for the cause ofthe trouble and eliminate it. Unlock thecontrol box by pressing the fault eliminatekey and start the burner.
Do not press the fault eliminate key longerthan 10 seconds.The start-up program will be initiated andshould be carefully monitored. The possible cause of the fault may bequickly found by reference to the faultindicator of the control box and watchingthe start-up and operating program.
Control program in the case of troubleand fault indicator LAL 1... / LAL 2...
LAL 1... / LAL 2...
a-b Starting program
b-b’ In a number of time versions; idle steps of the program unit to self-stop afterburner start-up (b’ = operating position ofprogram unit)
b(b’)-a After-flushing program after regular stop. In the starting position “a” theprogram unit will automatically stop orinitiate an immediate restart of the burner,e.g. after a fault has been eliminated
• Duration of the safety period for single-tube burners
•• Duration of the safety period forburners with ignition gas valve
Basically, any type of trouble will resultin the immediate stop of the fuel supply.At the same time, the program unit andconsequently the fault indicator will stop.The type of trouble can be identified by thesymbol opposite to the reading mark of theindicator:
◄ No start, e.g. because the “CLOSED”signal from the “Air Damper CLOSED” limitswitch is missing or a contact is not closedbetween terminals (12) and (4) or (4) and(5); or the contacts of all control and safetyunits in the controlled system are notclosed (e.g. gas pressure or air pressureswitches, temperature or pressureswitches, temperature or pressureregulators).
▲ Operating stop because the “OPEN”signal from the “Air Damper OPEN” limitswitch is missing. Check and adjust the limit switchconcerned.
P Shut-off on trouble because there isnot air pressure signal at the beginning ofthe air pressure check (apply only to LAL2.25). Any air pressure failure after this timewill also lead to a shut-off on trouble.
■ Shut-off on trouble because of a faultin the flame monitoring circuit.
▼ Operating stop because the positionsignal of the “Partial Load” limit switch (airdamper in “Partial Load” position) is notavailable on terminal (8). Check and adjustthe limit switch concerned.
1 Shut-off on trouble because a flamesignal is not available on the expiry of the(1st) safety time.
Any failure of the flame signal on theexpiry of the safety time will also leadto a shut-off on trouble.
| Shut-off on trouble because the flamesignal failed during burner operation or alack of air has occurred.
◄ Shut-off on trouble during or after thecontrol program flow due to external light(e.g. by flame not extinguished, leakingfuel valves) or a faulty flame signal (e.g.fault in flame monitoring circuit, or similar);see flame monitor.
If the shut-off on trouble occurs at anyother time between start and pre-ignition that is not identified by asymbol as above, this will normally bedue to an early flame signal which isconsidered to be a faulty flame signal.
The automatic furnace controller maybe unlocked immediately after a shut-offon trouble using the unlock button withintegrated fault signal lamp or an externalswitch. After it has been unlocked (andafter a defect with resultant operating stophas been eliminated and after a voltagefailure), the program unit will in any casereturn to its starting position with voltagebeing only supplied to terminals 7, 9, 10and 11 as preset by the control program. Itis only at this stage that the program of theautomatic furnace controller will restart the burner.
![Page 26: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/26.jpg)
26 www.ecoflam-burners.com
EN
420010513700
APPENDIX
Control box - Damper actuators
DAMPER ACTUATORS SQM50...
DescriptionThe SQM actuator is intended for use with two-stage sliding or modulating oil, gas or dual-fuel burners. The reversible actuator is fittedwith a synchronous motor which drives a shaft via a gearbox. The shaft end carries a coupling to drive the fuel and combustion aircontrolling element.The SQM actuator has been designed for dual-wire control by controller or switching units with change-over contacts. Potentiometers can be installed for a range of applications on customer’s request.The limit and auxiliary switches are set by means of manually adjustable latching cam plates. Scales are fitted between the disks tofacilitate the selection of the switching points.The cam plates are provided with a small pointer for indicating the switching point of a scale between the setting ranges.An additional scale fitted to the end of the cam roller serves to indicate the position of the actuator.The drive unit may be disconnected from the controlling element by changing over a rocker arm mounted to the gearbox.This will allow any desired position of the controller plate to be selected by hand. Drive and output will be coupled in the verticalposition of the rocker arm.The fuel-air curve should be set over the full range of the cam plate so that operating safety will be retained also when the limit switchis overrun.
CONTROL BOX LAL...
R LRt5t11 t12
t13FS
min.LK0...
M 100%
RV
A
BV1
M2
Z
~M
P R
M1
T
t4
t3
t7 t1
TSA
B
t6
C D
7153a10/0498
BV: Fuel valveFS: Flame signal amplifierLK: Air damperLR: Load controller
M: Fan or burner motorR: Control thermostat or pressurestatRV: Modulating fuel valveZ: Ignition transformer
A: Starting type intervalA-B: Flame development intervalB: Burner has reached operating positionB-C: Burner operation (heat generation)C-D: Regular shut-offt1: Pre-ventilating timet2: Safety timet3: Pre-ignition timet4: Fuel valve enablet5: Load regulator enablet11: “OPEN” run time of air dampert12: “CLOSE” run time of air damper
![Page 27: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/27.jpg)
27www.ecoflam-burners.com
EN
420010513700
APPENDIX
Fluidics nozzle chart
RETURN NOZZLEThe nozzle type Fluidics W is a by-passnozzle with integrated spring-loaded cut-off needle.The throughput rate is controlled byvarying the return pressure while keeping the supply pressure at a constant level.Prior to burner start, check the nozzle sizeagainst the required output. It might be necessary to replace the nozzle (see nozzle selection diagram).
25 50° 70° 90°
20
15
10
5Bar
Return pressure
20 40 60 80 100 % Output
Spray angle
Supply 25 Bar
≤60 kg/h
> 60 kg/h
![Page 28: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/28.jpg)
28 www.ecoflam-burners.com
EN
420010513700
APPENDIX
Bergonzo nozzle tables
GPH
Bar
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2912
5A
2022
2325
2627
2932
3437
4044
5057
6577
9512
5B
2028
528
027
527
427
227
124
523
522
020
519
017
516
014
513
011
512
5A
2524
2526
2728
2930
3132
3435
3740
4345
5260
6880
9511
512
5B
2533
032
832
532
031
530
730
028
528
027
526
025
023
522
019
018
018
017
016
815
013
512
5A
3025
2626
2728
2829
3031
3233
3537
3842
4346
5054
6065
7280
9010
813
012
5B
3037
036
536
035
535
034
834
534
033
532
832
030
530
029
028
027
026
024
524
022
521
019
018
016
515
013
015
0A
2030
3334
3537
3943
4650
5560
6875
8510
012
015
0B
2032
532
031
530
830
029
028
527
526
025
024
022
019
018
016
014
015
0A
2532
3334
3537
3738
4245
4750
5560
6570
7883
9411
012
015
015
0B
2537
537
036
536
335
835
535
034
533
032
031
030
028
527
526
025
024
022
019
518
015
015
0A
3035
3636
3737
3739
4142
4546
4850
5458
6265
7075
8088
9511
012
014
018
015
0B
3042
042
041
541
040
540
040
039
539
038
037
536
535
034
534
033
032
030
029
028
027
025
024
022
020
018
017
5A
2035
3739
4244
4648
5558
6268
7584
9511
815
517
5B
2035
035
034
934
833
032
531
530
029
028
026
524
822
519
517
515
517
5A
2535
3637
4142
4445
4750
5258
6265
7078
8895
110
120
140
170
175
B25
395
390
385
382
380
378
370
360
350
348
330
325
315
300
280
275
260
240
225
200
170
175
A30
4243
4445
4647
4850
5255
5860
6265
7072
7885
9010
011
011
813
515
819
017
5B
3044
044
043
543
042
542
041
541
040
840
039
038
037
036
035
033
032
030
028
527
526
025
023
522
019
020
0A
2038
4042
4447
5055
6065
7080
9010
012
014
017
020
0B
2040
039
838
838
037
036
035
034
033
032
030
028
027
525
023
021
020
0A
2542
4343
4445
4750
5255
6065
7078
8595
105
115
130
150
170
220
200
B25
450
448
448
445
440
430
425
412
405
400
390
380
375
360
345
325
315
290
280
260
220
200
A30
4849
5051
5253
5556
5860
6264
6870
7580
8592
100
110
120
130
150
175
200
200
B30
500
500
495
490
485
480
475
470
460
450
440
430
420
410
395
385
375
350
340
325
315
300
290
275
260
225
A20
4243
4547
4852
5660
6570
8090
100
115
140
180
225
B20
420
410
405
400
395
380
375
365
350
345
335
320
300
280
265
250
225
A25
4546
4748
5052
5558
6063
6873
8090
9810
812
014
016
018
022
522
5B
2547
546
846
045
545
045
044
543
742
541
040
038
037
536
035
034
031
530
028
026
024
022
5A
3050
5051
5252
5354
5557
6062
6668
7580
8894
100
110
120
130
140
155
175
200
240
225
B30
510
510
505
505
503
500
495
490
480
460
440
430
420
410
400
390
380
370
360
350
340
325
310
300
285
275
250
A20
4244
4647
5055
6065
7080
9010
011
514
016
022
025
0B
2042
541
540
840
340
038
037
536
535
033
832
530
028
026
525
024
025
0A
2546
4749
5052
5558
6063
6672
7885
9210
011
013
014
016
520
025
0B
2548
047
547
547
046
545
044
544
042
541
040
038
037
535
534
033
031
030
028
027
525
0A
3052
5252
5354
5558
6062
6568
7278
8290
9510
510
512
513
515
016
518
022
026
025
0B
3052
051
551
551
051
050
550
050
049
048
047
546
045
044
043
042
040
038
037
036
035
034
032
531
028
027
5A
2052
5355
5860
6368
7580
9010
011
512
515
017
022
527
5B
2054
053
052
051
050
049
047
545
044
042
040
037
535
032
530
027
527
5A
2555
5657
5860
6468
7075
8085
9510
011
512
513
515
017
019
022
526
527
5B
2560
060
059
559
058
057
056
055
054
052
551
050
048
046
044
042
540
037
535
032
530
027
5A
3060
6162
6364
6566
6770
7478
8288
9510
011
011
812
513
515
016
518
020
024
027
527
5B
3068
067
566
866
265
865
064
063
062
061
060
059
058
056
555
554
552
550
048
046
044
042
540
037
535
0
Ret
urn
pres
sure
[bar
]
Supp
ly: 2
5 ba
rO
utpu
t [kg
/h]
A =
nozz
le o
utpu
tB
= pu
mp
outp
ut
![Page 29: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/29.jpg)
29www.ecoflam-burners.com
EN
420010513700
APPENDIX
Bergonzo nozzle tables
Ret
urn
pres
sure
[bar
]
Supp
ly: 2
5 ba
rO
utpu
t [kg
/h]
A =
nozz
le o
utpu
tB
= pu
mp
outp
ut
GPH
Bar
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
0A
2055
5860
6465
7076
8592
105
118
135
145
175
200
270
300
B20
550
535
525
515
500
485
470
450
430
410
380
375
360
330
310
280
300
A25
2425
2627
2829
3031
3234
3537
4043
4552
6068
8095
115
300
B25
330
328
325
320
315
307
300
285
280
275
260
250
235
220
190
180
180
170
168
150
135
300
A30
2526
2627
2828
2930
3132
3335
3738
4243
4650
5460
6572
8090
108
130
300
B30
370
365
360
355
350
348
345
340
335
328
320
305
300
290
280
270
260
245
240
225
210
190
180
165
150
130
325
A20
5862
6568
7278
8895
110
118
135
150
170
200
240
290
325
B20
570
560
550
530
510
500
485
475
450
440
425
400
370
350
330
300
325
A25
6567
6972
7475
8085
9098
105
115
125
140
160
170
190
225
270
320
325
B25
650
643
638
630
628
620
610
600
590
580
565
540
520
500
475
450
425
400
375
350
325
A30
6869
7071
7375
7882
8892
9810
511
012
013
014
015
016
518
020
022
525
028
032
036
032
5B
3072
071
571
070
570
270
070
069
068
067
065
562
061
060
058
057
055
052
050
048
046
044
042
040
038
035
0A
2064
6870
7580
9098
105
118
130
145
160
180
210
250
310
350
B20
620
600
590
580
570
550
530
500
480
460
440
420
400
375
360
340
350
A25
6869
7075
8085
9098
105
112
120
130
145
160
170
190
210
240
270
300
350
350
B25
700
700
690
680
670
660
650
630
610
590
580
550
520
500
480
465
450
430
410
380
360
350
A30
6869
7073
7882
8892
9810
511
012
012
813
814
516
017
019
021
022
525
027
530
035
037
535
0B
3079
078
077
076
075
074
072
071
070
069
068
066
565
062
561
059
057
055
052
050
549
047
544
042
540
037
5A
2072
7682
8894
105
115
125
140
155
170
195
225
250
300
375
B20
630
615
600
590
580
565
550
520
490
475
450
425
400
375
360
375
A25
7880
8590
9510
010
511
012
013
014
015
517
019
020
023
025
028
032
537
537
5B
2570
069
068
067
066
065
064
062
561
560
058
056
555
052
050
048
046
044
042
040
037
5A
3090
9293
9598
100
105
110
115
120
130
140
150
160
170
180
200
220
240
260
280
320
350
400
375
B30
800
790
786
778
770
760
750
730
710
700
690
670
650
630
610
600
590
570
550
530
510
490
470
440
400
A20
8590
9810
511
512
513
515
016
518
521
024
027
032
040
0B
2061
060
559
558
557
556
555
052
050
048
046
044
042
040
040
0A
2585
9098
104
110
118
125
135
145
155
170
190
200
225
250
280
310
360
400
400
B25
710
705
700
695
690
680
670
650
630
610
590
580
560
540
520
500
480
450
425
400
A30
100
102
106
110
114
117
120
130
138
148
158
170
180
195
210
230
250
275
300
340
360
400
440
400
B30
800
790
786
778
770
760
750
730
710
700
690
670
650
630
610
600
590
570
550
530
510
490
470
425
A20
7880
8590
9510
011
012
013
515
017
019
022
025
030
035
042
5B
2070
069
068
067
065
063
061
560
059
057
053
051
049
045
041
038
042
5A
2585
8890
9395
100
105
110
120
130
140
150
165
180
195
225
250
280
325
380
425
B25
750
745
740
730
720
710
700
685
675
665
650
630
610
600
580
560
540
515
490
430
425
A30
9192
9496
9899
100
104
110
118
128
138
145
158
168
180
195
210
235
260
280
320
350
400
450
425
B30
820
816
812
808
804
800
790
780
770
760
750
740
730
720
710
695
680
650
625
600
590
570
540
515
490
450
A20
8690
9498
105
115
125
135
150
170
195
225
250
280
340
380
450
B20
700
685
660
645
635
620
605
585
570
545
530
515
490
470
440
410
450
A25
9295
100
105
110
115
120
130
140
150
165
175
190
210
230
260
280
325
375
425
450
B25
805
800
790
775
760
745
730
715
700
690
670
650
625
605
580
560
540
520
500
480
450
A30
100
102
105
108
111
114
117
120
130
140
150
160
170
180
190
220
240
260
280
310
350
380
425
475
450
B30
860
856
850
842
834
826
818
810
790
760
750
740
730
720
700
680
660
640
620
600
580
540
520
500
![Page 30: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/30.jpg)
30 www.ecoflam-burners.com
EN
420010513700
APPENDIX
Bergonzo nozzle tables
Ret
urn
pres
sure
[bar
]
Supp
ly: 2
5 ba
rO
utpu
t [kg
/h]
A =
nozz
le o
utpu
tB
= pu
mp
outp
ut
GPH
Bar
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2947
5A
2082
8895
100
110
120
130
145
160
170
195
225
260
300
360
475
B20
800
780
760
740
720
700
680
655
625
600
580
560
520
480
440
475
A25
9810
210
811
211
612
013
014
015
016
017
018
019
522
525
027
530
035
040
047
547
5B
2591
090
590
088
086
084
082
080
078
075
073
071
069
067
065
062
059
056
053
050
047
5A
3010
410
711
011
311
712
012
513
514
515
516
317
018
019
020
022
525
027
530
032
536
039
044
048
047
5B
3010
0099
097
596
594
593
091
590
089
088
086
084
082
080
078
076
073
070
068
066
064
062
059
046
050
0A
2094
102
106
113
120
130
150
170
190
210
230
250
280
325
380
500
B20
800
780
760
740
720
710
680
660
640
610
580
560
520
500
475
500
A25
100
104
108
116
120
130
140
150
160
170
190
210
230
250
270
325
350
400
475
500
B25
900
895
880
865
850
845
830
815
800
780
750
720
700
670
650
620
600
580
550
500
A30
110
113
117
120
125
130
135
140
150
160
170
180
190
220
250
280
250
300
325
350
380
425
480
520
500
B30
1000
990
980
970
960
950
940
925
910
900
880
860
840
820
800
775
750
725
700
775
750
725
600
575
575
A20
105
110
115
125
135
150
160
180
200
230
265
300
350
425
500
575
B20
910
900
890
870
830
800
780
750
720
690
670
640
600
580
530
575
A25
110
113
115
125
130
140
150
160
170
190
210
230
260
300
340
375
425
500
550
575
B25
1000
990
975
960
950
930
910
890
870
850
830
800
780
750
720
700
670
630
600
575
A30
120
122
125
127
130
135
140
145
155
165
180
195
210
230
250
280
300
340
375
420
475
530
600
575
B30
1190
1170
1150
1120
1100
1080
1050
1020
1000
990
975
965
950
920
900
880
850
820
800
770
740
700
680
600
A20
115
120
130
140
150
165
180
200
225
250
280
325
375
440
600
B20
920
900
890
850
820
800
780
760
740
710
690
670
650
610
600
A25
120
125
130
140
150
160
170
180
190
220
240
260
280
330
370
410
460
530
600
B25
1050
1030
1010
1000
990
980
960
940
920
900
880
840
810
790
760
730
700
680
600
A30
135
140
145
150
155
160
165
170
185
200
220
240
250
270
290
310
340
370
400
450
500
550
640
600
B30
1120
1115
1110
1105
1100
1095
1090
1085
1075
1050
1020
1000
980
960
940
920
900
880
850
825
800
780
720
650
A20
120
130
140
155
165
180
190
220
240
270
320
370
425
510
650
B20
990
950
920
900
890
870
850
800
780
760
710
680
660
620
650
A25
130
135
140
145
150
165
175
190
200
225
250
270
300
330
370
420
475
580
650
B25
1100
1090
1080
1060
1040
1000
990
970
945
920
900
880
850
820
800
780
750
720
650
A30
145
150
155
160
165
170
175
185
200
210
230
250
270
290
310
340
370
400
450
500
580
650
650
B30
1200
1195
1190
1185
1175
1150
1120
1100
1085
1065
1045
1020
1000
980
960
940
920
900
880
845
815
770
700
A20
130
140
155
170
180
200
230
250
280
325
375
425
500
630
700
B20
1000
980
960
940
920
900
880
850
830
800
780
740
700
680
700
A25
140
145
150
160
170
190
200
225
250
275
300
325
360
400
450
525
600
700
700
B25
1150
1130
1110
1100
1080
1060
1040
1020
1000
980
960
940
920
900
870
840
810
780
700
A30
150
155
160
170
180
190
200
215
230
250
270
290
320
345
370
400
440
480
540
600
680
780
700
B30
1250
1240
1230
1220
1210
1200
1180
1160
1140
1120
1100
1080
1060
1040
1020
1000
970
940
910
890
870
850
750
A25
150
155
160
170
175
185
195
200
225
240
260
280
320
350
375
400
500
600
750
750
B25
1200
1180
1160
1140
1120
1100
1080
1060
1040
1020
1000
980
965
950
930
910
900
880
850
820
800
A25
160
165
170
175
185
190
210
225
250
270
290
325
350
400
480
580
680
800
800
B25
1230
1215
1200
1180
1140
1120
1100
1080
1050
1020
1000
980
960
940
920
900
890
870
900
A25
300
325
350
375
400
430
470
500
550
600
650
700
750
800
850
900
900
B25
1350
1330
1310
1300
1285
1275
1260
1245
1230
1215
1200
1180
1160
1140
100
970
![Page 31: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/31.jpg)
31www.ecoflam-burners.com
EN
420010513700
APPENDIX
Pumps and pressure regulators
PUMP SUNTEC TA TECHNICAL DATANote: All TA models are delivered for two-pipe system (by-pass plug fitted in vacuum gauge port). For one-pipe system, the by-pass plug must be removed and the return port sealed by steel plug and washer.
TA : type
TA 2 A 40 10 5
PUMPIDENTIFICATION
(Not all model combinations are availableConsult your Suntec representative)
Gear set capacity(see pump capacity curves)
Shaft rotation(seen from shaft end)
A : clockwise rotationC : anti clockwise rotation
Pressure range :30 : 7 - 30 bars40 : 7 - 40 bars
Preheater facility
Revision number
Oil under suction
Oil under pressure Pressuregauge port
To nozzle
Pressureadjustment
By-passplug
inserted
By-passplug
removed
Return
Intake from Tank
TWO PIPEINSTALLATION
Vacuum orinlet pressure
gauge portBy-passed oilreturned to tank,or to suction
Intake from Tank
ONE PIPEINSTALLATION
Returnplugged
Inlet end return G 1/2"To nozzle G 1/2"Pressure gauge port G 1/4"Vacuum gauge port G 1/4"
4020 30 3510 15 255
1000
1200
1400
200
400
0
600
800
TA5
TA4
TA3
TA2
0
900
1500
1100
1300
100
300
500
700
General
Mounting Flange mountingConnection threads Cylindrical according to ISO 228/1
Shaft Ø 12 mmBy-pass plug Inserted in vacuum gauge port
for 2 pipe system;to be removed with a 3/16" Allen keyfor 1 pipe system
Weight 5,4 kg (TA2) - 5,7 kg (TA3)6 kg (TA4) - 6,4 kg (TA5)
Hydraulic data
Nozzle pressure ranges 30 : 7 - 30 bars40 : 7 - 40 bars
Delivery pressuresetting 30 barsOperating viscosity 4 - 450 cStOil temperature 0 - 140°C max. in the pumpInlet pressure light oil : 0,45 bars max. vacuum to prevent
air separation from oilheavy oil : 5 bars max.
Return pressure light oil : 5 bars max.heavy oil : 5 bars max.
Rated speed 3600 rpm max.Starting torque 0,3 N.m
Choice of heater
Cartridge Ø 12 mmFitting according to DIN 40430, NFC 68190 (N°9 elec.)Rating 80-100 W
Data shown are for new pumps, with no allowance for wear.
Pump capacityCapacity (L/h)
Viscosity = 200 cSt20 cSt
5 cSt - Rated speed = 2850 rpm
Pressure(bars)
2850 rpm
![Page 32: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/32.jpg)
32 www.ecoflam-burners.com
EN
420010513700
APPENDIX
Pumps and pressure regulators
PUMP SUNTEC T TECHNICAL DATANote: The bypass plug inserted beween high pressure and shaft seal is only intended to change the pump rotation, check the presenceof this plug with a 4 mm Allen key in the pressure outlet of the pump. Caution : changing the direction of pump rotation involves changing of all pump connections.
T : type
T 2 A 10 6
Preheater facility
Revision number
PUMPIDENTIFICATION
(Not all model combinations are availableConsult your Suntec representative)
Gear set capacity(see pump capacity curves)
Shaft rotation(seen from shaft end)
A :clockwise rotationC :anti clockwise rotation
Pressuregauge port
Topressure
regulatingvalve
Plug inserted betweenhigh pressure and shaft seal
Intakefrom Tank
Vacuum orinlet pressure
gauge port
Oil under pressure
Oil under suction
Intake from Tank
Topressure
regulating valve
4020 30 3510 15 255
3000
3400
3800
1400
1800
1000
2200
2600
T5
T4
T3
T2
0
2800
4000
3200
3600
1200
1600
2000
2400
4200
General
Mounting Flange mounting
Shaft Ø 20 mmWeight 7,8 kg (T2) - 8,1 kg (T3)
8,7 kg (T4) - 9,4 kg (T5)
Hydraulic data
Nozzle pressure range 40 bars max. (T2, T3, T4)30 bars max. (T5)
Operating viscosity 4 - 450 cStOil temperature 0 - 150°C max. in the pumpInlet pressure light oil : 0,45 bars max. vacuum to prevent
air separation from oilheavy oil : 5 bars max.
Rated speed 3600 rpm max.Starting torque 0,4 N.m
Choice of heater
Cartridge Ø 12 mmFitting according to DIN 40430, NFC 68190 (N°9 elec.)Rating 80-100 W
Data shown are for new pumps, with no allowance for wear.
Pump capacity
Power consumption
Capacity (L/h)
Viscosity = 200 cSt20 cSt
5 cSt - Rated speed = 2850 rpm
Pressure(bars)
2850 rpmInlet end return G 1/2"To nozzle G 1/2"Pressure gauge port G 1/4"Vacuum gauge port G 1/4"
Connection threads Cylindrical according to ISO 228/1
![Page 33: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/33.jpg)
33www.ecoflam-burners.com
EN
420010513700
APPENDIX
Pumps and pressure regulators
VALVE SUNTEC TV TECHNICAL DATAThe pressure of the nozzle line is adjusted with the adjusting screw of the TV valve. The oil in excess to nozzle requirement is dumpedto the return. Two pipe system : oil in excess is returned to tank. One pipe system : oil in excess is returned to pump suction.
TV : Pressure regulating valve
TV 40 01 1
VALVEIDENTIFICATION
(Not all model combinations are availableConsult your Suntec representative)
Pressure range :10 : 2 - 10 bars40 : 7 - 40 bars
Regulation type :01 : by screw02 : by piston,
for modulating purpose
Revision number
Oil under pressure
By-passed oilIntake Return
To nozzle
Pressureadjustment
Return
To nozzle
To tank
ot nruteRsuction
Oil under pressure
Oil under suction
By-passed oilreturned to tank,or to suction
Intakefrom Tank
TVvalve T pump
General
Weight 3 kg
Hydraulic data
Pressure ranges 10 : 2 - 10 bars(delivery pressure setting : 7 bars)
40 : 7 - 40 bars(delivery pressure setting : 20 bars)
Operating viscosity 4 - 450 cStOil temperature 0 - 150°C max. in the valve.
Inlet G 3/4"To nozzle G 3/4"Return G 3/4"
Connection threads Cylindrical according to ISO 228/1
MOUNTING POSITIONTV valve may be mounted in any position.
PRESSURE ADJUSTMENTRemove cap-nut ➊ and washer ➋, unscrew lock-nut ➍.To increase pressure, turn adjusting screw ➌ clockwise.To decrease the pressure, turn screw anticlockwise.Block lock-nut ➍, refasten washer ➋ and cap-nut ➊.
➊ cap-nut➋ adjusting screw➌ washer➍ lock-nut➎ washer
➊
➎
➋
➍➌
![Page 34: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/34.jpg)
34 www.ecoflam-burners.com
EN
420010513700
APPENDIX
Electrical diagrams
FU
YVgC
-U
TP
STAB
KMRL
I 1R
ST
NOKM
RLI 2
RS
TNO
KMRL
AR
ST
NO
50 H
z 400
V
50 H
z 400
V
RP
TP
STS
TV
TP
STC
HLB
B
FU SAL
LINE
LOAD
Z
HLBT
HLR
TP
STR
RARA
GEFR
AN 60
0
19KA
1
24232221206 1
12111023
945
TP
STm
rHL
FKA
2
HLF
Q1
Q2
PT
SPA
YVGP
YVGP
S
KTav
vKT
avv
KTav
v
SAs.r
56 9
8
4 7
1211
1013
2
98
745
6
21
3
1110
12
+
-
B1
PE S TRR S TPE
FMV
97 98
FMV
95 96
N N
F
1
ED
23
4
CBA
12
34
56
78
FED
56
7
CB
8
A
TOT.
SHEE
T
SHEE
TDE
SIGNE
RDE
SCRIP
TION
DATE
FIST
CREA
TION
CODE
SIGNA
TURE
R&D
DEPA
RTME
NT
CONT
ROLL
EREc
oflam
Bru
ciat
ori
SERV
OMOT
OR
FLAM
E SEN
SOR
S.p.
AEC
N FIR
ST CR
EATIO
N
BY TERM LAWS WE RESERVED THE PROPERTY OF THIS WIRING DIAGRAM WITH PROHIBITION OF USE AND REPRODUCTION
LEAK
AGE C
ONTR
OL
CONT
ROL B
OX
DATE
ECN
MODI
CATIO
NMO
DIFIC
ATIO
N DE
SCRIP
TION
ECN
MODI
FICAT
ION
OILF
LAM
800.1
PR
A.POZ
ZOBO
N
07-09
-2012
2
4201
1009
1800
1 A
.RIGO
NI
LAND
IS SQ
M 50
.481A
2
UV
RBA1
2PC2
88LA
NDIS
LAL 2
.25
SARA
3M
MV
W1
V1U1
KMV2
FMV
KMV1
KMV3
W2
U2V2
KMV3
KMV1
KMV2
KMV1
Mas
chio
13
Fem
mina
Rliv2
Slav
Rlav
Tliv1
Sliv1
Sliv2
Tliv2
Rliv1
Tlav
503
N51
2221
N85
847
68
45
910
11R1
TS
RN
S1T1
N
125
24LA
NDIS
LAL 2
.257
42
36
510
89
1112
1815
1413
1617
2120
1922
23
SAM
A 12
30
3132
LAND
IS SQM
50.48
1A2
131
M
111
N2
1222
214
143
235
1524
1726
616
277
12
12
pos 0
: ARR
ESTO
/ STO
P/ G
ESPE
RRE
pos 2
: BAS
SA FI
AMM
A/LO
W FL
AME/
1e A
LLUR
E/BA
JA LL
AMA/
NIED
RIGE F
LAM
E
pos 1
: ALT
A FIA
MM
A/HI
GH FL
AME/
2e A
LLUR
E/AL
TA LL
AMA/
HOCH
E FLA
MM
E
pos 3
: AUT
OMAT
ICO/
AUTO
MAT
IC/A
UTOM
ATIQ
UE/A
UTOM
ATIC
O
SAM
A
12
30
UMSC
HALT
ER M
ANUE
LL-A
UTOM
ATISC
HCO
NMUT
ADOR
MAN
UAL-A
UTOM
ATIC
O
COM
MUT
ATOR
E MAN
UALE
-AUT
OMAT
ICO
SWITC
H M
ANUA
L-AUT
OMAT
ICIN
TERR
RUPT
EUR M
ANUE
L-AUT
OMAT
IQUE
![Page 35: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/35.jpg)
35www.ecoflam-burners.com
EN
420010513700
APPENDIX
Electrical diagrams
ELEC
TROV
ALVU
LA G
AS PI
LOTO
ELEC
TROV
ANNE
GAZ
PILO
TEPIL
OT FL
AME S
OLEN
OID
GAS V
ALVE
ELET
TROV
ALVO
LA G
AS PI
LOTA
YVGP
INTE
RRUP
TOR R
ESIST
ANCIA
AUXIL
IARIA
INTE
RRUP
TOR D
U RE
SISTA
NCE A
UXLIA
IRESW
ITCH
AUXIL
IARY
RESIS
TOR
INTE
RUTT
ORE R
ESIST
ENZE
AUSIL
IARIE
PRES
OSTA
TO AI
REPR
ESSO
STAT
AIR
AIR P
RESS
URE S
WITC
HPR
ESSO
STAT
O AR
IA
SARA
SPA
CONM
UTAD
OR M
ANUA
L-AUT
OMAT
ICOIN
TERR
UPTE
UR M
ANUE
L-AUT
OMAT
IQUE
SWITC
H (M
ANUA
L-AUT
OMAT
IC))
COMM
UTAT
ORE M
ANUA
LE-A
UTOM
ATICO
SAMA
OUT 2
:KMRL
I 1
OUT 1
:KMRL
A
USCI
TE RE
LE D
EL RE
GOLA
TORE
WOR
KING
RESIS
TOR S
WITC
H
INTE
RRUF
TOR D
E LAS
RESIS
TENC
IAS D
E TRA
BAJIO
CONT
ATTO
RE RE
SISTE
NZE D
I LAV
ORO
INTE
RRUP
TEUR
DES
RESIS
TANC
ES D
E TRA
VAIL
SAFE
TY TH
ERMO
STAT
TERM
OSTA
TO D
I SICU
REZZ
A
REST
OR SA
FETY
TERM
OSTA
T
TERM
OSTA
TO D
E SEG
URID
ADTH
ERMO
STAT
DE S
ECUR
ITE
TERM
OSTA
TO D
E SEG
URID
AD RE
SISTE
NCIA
STE
RMOS
TAT D
E SEC
URITE
RESIS
TANC
ES
TERM
OSTA
TO D
I SICU
REZZ
A RES
ISTEN
ZE
OUT 3
:KMRL
I 2
OUT 4
:TERM
OSTA
TO D
I ACC
ENSIO
NE
OIL S
HUT-O
FF SO
LENO
IDSO
LENO
IDE C
HIUS
URA U
GELL
O
CONT
ATTO
RE RE
SISTE
NZE D
I LIVE
LLAM
ENTO
LEVE
LLIN
G RE
SISTO
R SW
ITCH
INTE
RRUP
TEUR
DES
RESIS
TANC
ES D
E NIVE
LLEM
ENT
INTE
RRUF
TOR D
E LAS
RESIS
NCIA
S DE N
IVELA
CION
LEVE
LLIN
G RE
SISTO
R SW
ITCH
CONT
ATTO
RE RE
SISTE
NZE D
I LIVE
LLAM
ENTO
INTE
RRUF
TOR D
E LAS
RESIS
NCIA
S DE N
IVELA
CION
INTE
RRUP
TEUR
DES
RESIS
TANC
ES D
E NIVE
LLEM
ENT
FILTR
O AN
TIDIST
URBO
FUSIB
LEFU
SIBLE
FUSE
FILTR
E ANT
IPARA
SITES
FUSIB
ILE
ANTJA
MMIN
G FIL
TER
FILTR
O DE
PROT
ECIO
N AN
TIDIST
URBIO
INTE
RRUP
TOR G
ENER
AL CO
N FU
SIBLE
INTE
RRUP
TEUR
GEN
ERAL
AVEC
FUSIB
LEMA
IN SW
ITCH W
ITH FU
SEIN
TERR
UTTO
RE G
ENER
ALE C
ON FU
SIBILE
ZQ1 FU
MOTO
R FAN
MOTO
RE VE
NTILA
TORE
RESIS
TANC
E AUX
ILIAI
RE
RESIS
TENZ
A AUS
ILIAR
IA
RESIS
TENZ
A POM
PA
MOTO
R VEN
TILAD
OR
AUXIL
IARY
RESIS
TOR
MUTE
UR VE
NTILA
TEUR
RESIS
TENC
IA AU
XILIA
RIA
RESIS
TENC
IA BO
MBA
RESIS
TANC
E POM
PEPU
MP RE
SISTO
R
IGNI
TION T
RANS
FORM
ER
TRAN
SFOR
MADO
R
UV CE
LLFO
TOCE
LLUL
A
TRAS
FORM
ATOR
E
TRAN
SFOR
MATE
UR D
'ALLU
MAGE
MV RPRA BTV
FOTO
CELU
LA
ESPIA
DE B
LOQU
EOLA
MPE D
E SEC
URITE
LOCK
-OUT
LAMP
LAMP
ADA D
I BLO
CCO
RELE
' TER
MICO
MOT
OR VE
NTILA
DOR
RELA
IS TH
ERMI
QUE M
OTEU
R VEN
TILAT
EUR
MOTO
R THE
RMAL
RELA
Y (FA
N MO
TOR)
RELE
' TER
MICO
MOT
ORE V
ENTIL
ATOR
E
RELA
Y
TEMO
IN RE
SISTE
NCES
RELE
'
RESIS
TOR L
AMP
LAMP
ADA R
ESIST
ENZE
RELE
'RE
LAIS
RELE
'
RELA
YRE
LE'
RELA
IS
INDI
CADO
R RES
ISTEN
CIAS
KA1
KA2
HLR
HLB
HLF
FMV
CELL
ULE
UV
YVOc
-u
KMRL
I 2
STS
STR
KMRL
A
KMRL
I 1
WOR
KING
SWITC
H
TERM
OSTA
TO CA
LDAI
A
TERM
OSTA
TO CA
LDER
A
BOILE
R THE
RMOS
TAT
INTE
RRUP
TOR D
E LIN
EA
INTE
RRUT
TORE
DI L
INEA
INTE
RRUP
TEUR
DE L
IGNE
TELE
RRUP
TOR M
OTOR
VENT
ILATO
RCO
NTAC
TEUR
MOT
EUR V
ENTIL
ATEU
RRE
MOTE
CONT
ROL S
WITC
H (FA
N MO
TOR)
THER
MOST
AT CH
AUDI
ERE
SAL
STC
CONT
ATTO
RE M
OTOR
E VEN
TILAT
ORE
KMV2
HLBT
LAMP
ADA D
I BLO
CCO
TERM
ICOTH
ERMA
L LOC
K-OU
T LAM
PLA
MPE D
E THE
RMAL
DE S
ECUR
ITEES
PIA D
E BLO
QUEO
RELE
TERM
ICO
LAMP
ADA D
I FUN
ZIONA
MENT
OW
ORKIN
G LA
MPLA
MPE D
E FON
CTIO
NNEM
ENT
ESPIA
DE F
UNCIO
NAMI
ENTO
INTE
RRUT
TORE
GEN
ERAL
E CON
FUSIB
ILEQ2
MAIN
SWITC
H WITH
FUSE
INTE
RRUP
TEUR
GEN
ERAL
AVEC
FUSIB
LEIN
TERR
UPTO
R GEN
ERAL
CON
FUSIB
LE
STmr
SAs.r
PULS
ANTE
DI S
BLOC
CO AP
PARE
CCHI
ATUR
ARE
SET L
OCK O
UT BU
TTON
BOUT
ON D
E DEB
LOCA
GE D
U CO
FFRE
DE S
ECUR
ITERE
ARME
DE L
A CEN
TRAL
ITA
TERM
OSTA
TO D
I RICI
RCOL
ORE
-DIRC
ULAT
ING
PUMP
THER
MOST
ATTH
ERMO
STAT
DE L
A POM
PE D
E REC
IRCUL
ATIO
NTE
RMOS
TATO
DE L
A BOM
BA D
E REC
IRCUL
ACIO
N
KMV1
KMV3
CONT
ATTO
RE D
I TRIA
NGOL
ODE
LTA CO
NTAC
TOR
CONT
ACTE
UR TR
IANG
LECO
NTAT
TORE
DI T
RIANG
OLO
CONT
ATTO
RE D
I STE
LLA
STAR
CONT
ACTO
RCO
NTAC
TEUR
D'ET
OILE
CONT
ATTO
RE D
I STE
LLA
YVGP
SEL
ETTR
OVAL
VOLA
GAS
PILO
TA D
I SICU
REZZ
AEX
TRA S
AFET
Y PILO
T SOL
ENOI
D GA
S VAL
VEEL
ECTR
OVAN
NE G
AZ PI
LOTE
DE S
ICURIT
EEL
ECTR
OVAL
VULA
GAS
PILO
TO D
E SEG
URID
AD
F
1
ED
23
4
CBA
12
34
56
78
FED
56
7
CB
8
A
TOT.
SHEE
T
SHEE
TDE
SIGNE
RDE
SCRIP
TION
DATE
FIST
CREA
TION
CODE
SIGNA
TURE
R&D
DEPA
RTME
NT
CONT
ROLL
EREc
oflam
Bru
ciat
ori
SERV
OMOT
OR
FLAM
E SEN
SOR
S.p.
AEC
N FIR
ST CR
EATIO
N
BY TERM LAWS WE RESERVED THE PROPERTY OF THIS WIRING DIAGRAM WITH PROHIBITION OF USE AND REPRODUCTION
LEAK
AGE C
ONTR
OL
CONT
ROL B
OX
DATE
ECN
MODI
CATIO
NMO
DIFIC
ATIO
N DE
SCRIP
TION
ECN
MODI
FICAT
ION
OILF
LAM
800.1
PR
A.POZ
ZOBO
N
07-09
-2012
2
4201
1009
1800
2 A
.RIGO
NI
LAND
IS SQ
M 50
.481A
2
UV
RBA1
2PC2
88LA
NDIS
LAL 2
.25
0
VI
0
VIIVII
I
0
IIIV
IV
00
III
REGO
LAZIO
NE CA
MME P
ER O
ILFLA
M 80
0.1 PR
CAMM
A NON
UTIL
IZZAT
ACA
MMA N
ON U
TILIZZ
ATA
CAMM
A NON
UTIL
IZZAT
A
(60°)
I:
(0°) V
:(0°
) VI:
(0°) II
:(15
°) III:
(40°)
IV:
CAMM
A NON
UTIL
IZZAT
A(0°
) VIII:
(0°) V
II:
CAMM
A DI R
EGOL
AZIO
NE AR
IA M
ASSIM
A FIA
MMA
CAMM
A DI R
EGOL
AZIO
NE CH
IUSU
RA TO
TALE
CAMM
A DI R
EGOL
AZIO
NE AR
IA AC
CENS
IONE
CAMM
A DI R
EGOL
AZIO
NE AR
IA BA
SSA F
IAMM
A
![Page 36: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/36.jpg)
36 www.ecoflam-burners.com
EN
420010513700
S.p.A.
0001
0203
0405
0607
0809
A
0001
0203
0405
0607
0809
B C D E
A B C D E
COLL
EGAM
ENTO
BAR
ILO
TTO
ECO
FLAM resis
tenz
e
T
S1
RS
T1
S2T2
R1
R2
Part
e su
perio
rere
siste
nze
Colle
gam
ento
ele
ttric
oPo
sizio
nam
ento
IND.
MOD
IFICA
SOST
.DA
SOST
.IL
IND.
MOD
.
PROPRIETA' RISERVATA DELLA DITTA ECOFLAM S.p.A.
DATA
-FIRM
A
DATA
FIRMA
CONT
ROLL
ATO
DESC
RIZIO
NE M
ODIFI
CA
DISE
GNAT
O
DATA
FIRMA
COMUNICARE A TERZI IL CONTENUTO DEL PRESENTE. A TERMINE DI LEGGE E' VIETATO RIPRODURRE O
CONT
ROLL
O DI
TENU
TAAP
PARE
CCHI
ATUR
A
UFF.T
ECNI
CO-SE
TTOR
E ELE
TTRIC
O
DENO
MIN
AZIO
NE
SIST.
RIVEL
AZ.
CODI
CE
MOT
ORID
UTTO
RE
OIL
HEA
THER
ELE
CTR
IC C
ON
NEC
TIO
N
HEA
THER
S C
ON
NEC
TIO
NH
EATH
ERS
POSI
TIO
N
APPENDIX
Electrical diagrams
![Page 37: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/37.jpg)
37www.ecoflam-burners.com
EN
420010513700
APPENDIX
Spare partsOI
LFLA
M 80
0.1 P
R
7
28
910
2627
5455
5651
32
015
30
7590
37
8
45
38
3940
41 4445
4347
46
4849
50
52
5342
70
741211
1314
1617
15
FIND
FINDE
R
10
10
20
1921
2324
2522
18
77
6
29
57
30
015
3045
6075
90
6061
62
31
6465
6359
1
358
2
36
34
35
33
7172
73
30
30
75
75
6667
6869
76
78
79
![Page 38: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/38.jpg)
38 www.ecoflam-burners.com
EN
420010513700
APPENDIX
Spare parts list
TC = SHORT HEAD TL = LONG HEAD
OILFLAM 800.1 PRN° DESCRIPTION code1 PUMP SUNTEC TA5C30106 653229932 HEATING ELEMENT PUMP 50 W 653230723 HOSES 25 x1500 653231814 COIL EL011 653238095 CONETTORE BOBINA EL011 653248096 MANOMETER CEWAL R1/4 D50 653241057 COVER 653240598 GLASS 653204879 PEEP WINDOW FRAME 6532048810 MOTOR 18500 W 6532524811 CONTROL BOX BASE LANDIS LAL2.25 6532009712 CONTROL BOX LANDIS LAL2.25 Tv22" 6532006313 RELAY FINDER 5532 8 6532313914 RELAY BASE FINDER 5532 8 6532314915 REMOTE CONTROL SWITCH AEG LS11K.00(1) 65323135
AEG LS15K.00(2) 6532313616 REMOTE CONTROL SWITCH AEG LS4K.00(2) 65323133
AEG LS7K.10(1) 6532409717 MOTOR THERMAL RELAY AEG B18K-260 21-26A 6532406618 ANTIJAMMING FILTER 6532317019 ADJUSTMENT OF FUEL TEMPERATURE GEFRAN 600 6532204520 MAIN SWITCH cod.40100I1509 6532409821 MANUAL / AUTOMATIC Selector 6532306322 RESET SWITCH 6532410123 FUSE HOLDER 6532427924 LAMP LYVIA 10X28 BA9S 6532410025 AUXILIARY SWITCH HEATER 6532427826 IGNITION TRANSFORMER BRAHMA T8 6532322227 PHOTORESISTOR LANDIS 6532007628 FAN RU-560 M d.42 6532406329 AIR CONVEYOR 6532064830 RING 6532064631 COVER AIR INLET 6532406532 AIR DAMPER MOTOR SQM50.481A2 6532290233 THERMOCOUPLE TC6MD2JBC 6532204634 FILTER U21008/01 6532315835 HEATER 30 kW 6532309136 OIL TANK 6532448137 CABLE 6532094738 RING 6532172139 HOLDER SPRING 6532172040 FIRING HEAD 6532172241 PIPE 6532426742 ROD FIRING HEAD TC 6532457943 ROD NOZZLE HOLDER TC 6532426944 HOLDER WAISTBAND 6532457745 WAISTBAND 6532457846 ELECTRODES 6532500447 SUPPORT NOZZLE HOLDER 6532069748 NOZZLE HOLDER 6532070949 NOZZLE50 DIFFUSER 65320788
![Page 39: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/39.jpg)
39www.ecoflam-burners.com
EN
420010513700
APPENDIX
Spare parts list
TC = SHORT HEAD TL = LONG HEAD
OILFLAM 800.1 PRN° DESCRIPTION code51 BLAST TUBE 6532498152 BLAST TUBE END 6532512953 ASSEMBLY FIRING HEAD TC 6532249954 GASKET 6532113755 GASKET 6532113856 GASKET 6532113957 SILENCER 6532407158 FILTER 70501/03 6532410359 ROD 6532146860 COUPLING (FAN) 6532179261 UNION (FAN) 6532179162 COUPLING 6532179063 COUPLING 6532178264 UNION (PUMP) 6532178665 COUPLING (PUMP) 6532521966 GAS VALVE BRAHMA EG12SRGMO 6532359567 COIL BRAHMA EG12S 6532370968 GAS VALVE BRAHMA EG12SRGMO 6532359569 COIL BRAHMA EG12S 6532370970 AIR PRESSURE SWITCH 6532303371 PREHEATEDʼS AUX. RESISTOR HOLDER 6532171672 FIXING PLATE 6532171773 HEATING ELEMENT 50 W 6532307274 THERMOSTAT IMIT TR2 40/200 6532314775 HEATING ELEMENT 30 W 6532420776 TIMER 6532407377 ADJUSTMENT OIL PRESSURE B-P-PRO-2 a.070H0115 6532316778 OIL CAM GROUP 6532235679 CHECK VALVE ART. FZVR13 1-2 65325173
![Page 40: 420010---- Oilflam7-1200-1PR EN Layout 1 · 2017-02-21 · INDEX 420010513700 EN 2 General warnings - Conformity declaration 3 Burner designation - Modular delivery system 4 Burner](https://reader033.fdocuments.net/reader033/viewer/2022041904/5e6223cbd963017e5e0bd828/html5/thumbnails/40.jpg)
Ecoflam Bruciatori S.p.A.Via Roma, 64 - 31023 Resana (TV) - ItalyTel. +39 0423 719500Fax +39 0423 719580http://www.ecoflam-burners.come-mail: [email protected]à soggetta alla direzione e al coordinamento di Ariston Thermo S.p.A.Via A. Merloni, 45 - 60044 Fabriano (AN) - CF 01026940427
Ecoflam Bruciatori S.p.A. reserves the right to make any adjustments, without prior notice, which is considered necessaryor useful to its products, without affecting their main featuresEcoflam Bruciatori S.p.A. si riserva il diritto di apportare ai prodotti le modifiche che riterrà necessarie o utili, senza pregiudicarne le caratteristiche principali.La maison Ecoflam Bruciatori S.p.A. se réserve le droit d’apporter les modifications qu’elle jugera nécessaires ou utilesà ses produits sans pour autant nuire à leurs caractéristiques principalesEcoflam Bruciatori S.p.A. se reserva el derecho a introducir en sus productos todas las modificaciones que considerenecesarias o utiles, sin prejudicar sus caracteristicas“Ecoflam Bruciatori S.p.A.” оставляет за собой право вносить в конструкцию оборудования любые необходимыеизменения без особого предупреждения