Page 1: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect

4.1.2.4 Environmental andExisting BuildingAssessments

Page 2: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect

Final Design Program Nauset Regional High SchoolChanges in Site Development Require-

30

Peebles 3-5 Elementary SchoolNauset Regional High SchoolEnvironmental and Existing Building Assessments

Environmental and Existing Building Assessments

A Hazardous Building Materials Inspection Report performed by Fuss & O’Neill has been attached here.

Page 3: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect

108 Myrtle StreetSuite 502

Quincy, MA02171

t 617.282.4675800.286.2469

f 617.481.5885

www.fando.com

California

Connecticut

Maine

Massachusetts

New Hampshire

Rhode Island

Vermont

August 12, 2019

Mr. Kent Kovacs, AIA, LEED APVice PresidentFlansburgh Architects77 North Washington StreetBoston, MA 02114

RE: Supplemental Hazardous Building Materials Consulting ServicesNauset Regional High School100 Cable Road, Eastham, MA 02651Fuss & O’Neill Reference No. 20180940.A10

Dear Mr. Kovacs:

On July 31, 2019 and August 1, 2019, Fuss & O’Neill, Inc. (Fuss & O’Neill) representatives, Mr. Robert Mallett and Ms. Heidi Keller, performed supplemental sampling for suspect Asbestos-Containing Materials (ACM) at select locations within Buildings E, F, and the Boiler Room of Building D of the Nauset Regional High School located at 100 Cable Road in Eastham, Massachusetts (the “Site”).

On July 31, 2019, Mr. Mallett and Ms. Keller conducted slab coring at the Women’s Faculty Restroom located in Building E and the Boiler Room located in Building D. No suspect sub-slab dampproofing was observed during this inspection. Ceramic floor tile components were observed in the Women’s Faculty restroom and samples were collected for analysis. In addition to the slab coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect materials were observed, samples were collected for analysis.

On August, 1, 2019, a series of roof cuts were performed and subsequently patched by a professional roofing subcontractor. These roof cuts were observed by Fuss & O’Neill and if suspect materials were observed, samples were collected for analysis.

All asbestos samples were collected by a Fuss & O’Neill Commonwealth of Massachusetts-certified and United States Environmental Protection Agency (EPA)-accredited Asbestos Inspector. Refer to the report attachments for a copy of the Asbestos Inspector state certifications and accreditations.

Samples were analyzed at EMSL Analytical, Inc. (EMSL), a Commonwealth of Massachusetts-certified and American Industrial Hygiene Association-accredited asbestos laboratory. Asbestos sample analysis was conducted using the EPA Interim Method for the Determination of Asbestos

ProjectData\P2018\0940\A10\Deliverables\Report\Supplemental Sampling\RCM_hjk_NausetHS_AsbSupSampleLtr_20190812.docx

Page 4: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect

Flansburgh ArchitectsAugust 12, 2109Page 2

ProjectData\P2018\0940\A10\Deliverables\Report\Supplemental Sampling\RCM_hjk_Nauset HS_AsbSupSampleLtr_20190812.docx

in Bulk Building Materials (EPA/600/R-93/116) via Polarized Light Microscopy with DispersionStaining (PLM/DS).

The suspect ACM sample locations, material type, sample identification, and asbestos content areidentified by bulk sample analysis in Table 1, attached. The asbestos laboratory analytical reportsand chain-of-custody forms are also included as an attachment.

The samples collected of suspect ACM were reported by EMSL to be “None Detected” (i.e., non-ACM). Any materials not identified during the original or supplemental material survey should bepresumed as ACM until sample collection and analysis determines to be non-ACM.

The EPA, Occupational Safety and Health Administration (OSHA), and the Commonwealth ofMassachusetts Department of Labor Standards (MADLS) defines any material that contains greaterthan one percent (>1%) asbestos, utilizing PLM, as being an ACM. The Commonwealth ofMassachusetts Department of Environmental Protection (MassDEP) defines any material thatcontain equal to or greater than one percent (≥1%) asbestos as being an ACM. MassDEP definesan asbestos-contaminated material as a material containing greater than zero percent (>0%) andless than one percent (<1%) asbestos. Materials that are identified as "none detected" are specifiedas not containing asbestos.

If you should have any questions regarding the contents of this letter, please do not hesitate tocontact me at (617) 282-4675, extension 4706. Thank you for this opportunity to have served yourenvironmental needs.

This report was prepared by Environmental Analyst, Heidi Keller.

Sincerely,

Robert C. MallettEnvironmental Analyst

AttachmentsAsbestos Inspector Certifications & AccreditationsTable 1: Suspect Asbestos-Containing Materials Laboratory Analytical Data SummaryAsbestos Laboratory Report & Chain-of-Custody Forms

Page 5: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect
Page 6: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect
Page 7: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect
Page 8: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect
Page 9: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect

Table 1Suspect Asbestos-Containing Materials Laboratory Analytical Data Summary

Sample Number Material Type NESHAPCategory

Sample Location Result Comments

01A-HK-190731 Black Dampproofing Non-ACM Building E Bathroom ND

01B-HK-190731 Black Dampproofing Non-ACM Building E Bathroom ND

02A-HK-190731 White Grout Non-ACM Building E Bathroom ND

02B-HK-190731 White Grout Non-ACM Building E Bathroom ND

03A-HK-190731 Gray Ceramic Tile Thin-Set Mortar Non-ACM Building E Bathroom ND

03B-HK-190731 Gray Ceramic Tile Thin-Set Mortar Non-ACM Building E Bathroom ND

04A-HK-190731 Black Vapor Barrier Non-ACM Gym Floor (on concrete) ND

04B-HK-190731 Black Vapor Barrier Non-ACM Gym Floor (on concrete) ND

05A-HK-190731 Black Mastic Non-ACM Gym Floor- on Cellulose Material(beneath hardwood)

ND

05B-HK-190731 Black Mastic Non-ACM Gym Floor- on Cellulose Material(beneath hardwood)

ND

06A-HK-190731 Black Felt Paper Non-ACM Stage ND

06B-HK-190731 Black Felt Paper Non-ACM Stage ND

07A-HK-190802 Black Asphaltic Mop Non-ACM Building E Roof System ND

07B-HK-190802 Black Asphaltic Mop Non-ACM Building E Roof System ND

08A-HK-190802 Gray Iso Paper Non-ACM Building E Roof System ND

08B-HK-190802 Gray Iso Paper Non-ACM Building E Roof System ND

09A-HK-190802 Black Asphaltic Mop Non-ACM Building F Roof System ND

09B-HK-190802 Black Asphaltic Mop Non-ACM Building F Roof System ND

10A-HK-190802 Gray Iso Paper Non-ACM Building F Roof System ND

10B-HK-190802 Gray Iso Paper Non-ACM Building F Roof System ND

11A-HK-190802 Blue Flooring (Poured Resilient Floor) Non-ACM Gym Floor (Poured Resilient Floor) ND

11B-HK-190802 Blue Flooring (Poured Resilient Floor) Non-ACM Gym Floor (Poured Resilient Floor) ND

12A-HK-190802 Gray Adhesive (Poured Resilient Floor) Non-ACM Gym Floor (Poured Resilient Floor) ND

12B-HK-190802 Gray Adhesive (Poured Resilient Floor) Non-ACM Gym Floor (Poured Resilient Floor) ND

ND = None Detected

ACM = Asbestos-Containing Material

Nauset Regional High SchoolEastham, Massachusetts

Flansburgh ArchitectsAugust 2019

Fuss & O’Neill Reference No. 20180940.A10

\\private\dfs\ProjectData\P2018\0940\A10\Deliverables\Report\Supplemental Sampling\Table 1 - Attachment 2.xlsx 1 of 1

Page 10: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect

EMSL Analytical, Inc.5 Constitution Way, Unit A Woburn, MA 01801

Tel/Fax: (781) 933-8411 / (781) 933-8412

http://www.EMSL.com / [email protected]

131905914EMSL Order:

Customer ID: ENVI54

Customer PO: 20180940.A10

Project ID:

Attention: Phone:H Keller (860) 646-2469

Fax:Fuss & O’Neill, Inc.

Received Date:146 Hartford Road 08/07/2019 8:30 AM

Analysis Date:Manchester, CT 06040 08/10/2019

Collected Date: 08/07/2019

Project: Nauset Regional High School./ 100 Cable Road., Eastham, MA./ 20180940.A10

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized

Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

01A-HK-190731

131905914-0001

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

BUILDING E

BATHROOM -

BLACK

DAMPPROOFING

01B-HK-190731

131905914-0002

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

BUILDING E

BATHROOM -

BLACK

DAMPPROOFING

02A-HK-190731

131905914-0003

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

BUILDING E

BATHROOM -

WHITE GROUT

02B-HK-190731

131905914-0004

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

BUILDING E

BATHROOM -

WHITE GROUT

03A-HK-190731

131905914-0005

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

BUILDING E

BATHROOM - GRAY

CERAMIC TILE THIN

SET

03B-HK-190731

131905914-0006

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

BUILDING E

BATHROOM - GRAY

CERAMIC TILE THIN

SET

04A-HK-190731

131905914-0007

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

GYM FLOOR -

BLACK VAPOR

BARRIER

04B-HK-190731

131905914-0008

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

GYM FLOOR -

BLACK VAPOR

BARRIER

05A-HK-190731

131905914-0009

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

GYM FLOOR- ON

CELLULOSE

MATERIAL - BLACK

MASTIC

05B-HK-190731

131905914-0010

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

GYM FLOOR- ON

CELLULOSE

MATERIAL - BLACK

MASTIC

06A-HK-190731

131905914-0011

None DetectedNon-fibrous (Other)20%Cellulose80%Black

Fibrous

Homogeneous

STAGE - BLACK

FELT PAPER

06B-HK-190731

131905914-0012

None DetectedNon-fibrous (Other)20%Cellulose80%Black

Fibrous

Homogeneous

STAGE - BLACK

FELT PAPER

07A-HK-190802

131905914-0013

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

BUILDING E ROOF

SYSTEM - BLACK

ASPHALTIC MOP

07B-HK-190802

131905914-0014

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

BUILDING E ROOF

SYSTEM - BLACK

ASPHALTIC MOP

Initial report from: 08/10/2019 12:22:55

Page 1 of 2ASB_PLM_0008_0001 - 1.78 Printed: 8/10/2019 12:22 PM

Page 11: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect

EMSL Analytical, Inc.5 Constitution Way, Unit A Woburn, MA 01801

Tel/Fax: (781) 933-8411 / (781) 933-8412

http://www.EMSL.com / [email protected]

131905914EMSL Order:

Customer ID: ENVI54

Customer PO: 20180940.A10

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized

Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

08A-HK-190802

131905914-0015

None DetectedNon-fibrous (Other)70%Glass30%Gray

Fibrous

Homogeneous

BUILDING E ROOF

SYSTEM - GRAY ISO

PAPER

08B-HK-190802

131905914-0016

None DetectedNon-fibrous (Other)70%Glass30%Gray

Fibrous

Homogeneous

BUILDING E ROOF

SYSTEM - GRAY ISO

PAPER

09A-HK-190802

131905914-0017

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

BUILDING F ROOF

SYSTEM - BLACK

ASPHALTIC MOP

09B-HK-190802

131905914-0018

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

BUILDING F ROOF

SYSTEM - BLACK

ASPHALTIC MOP

10A-HK-190802

131905914-0019

None DetectedNon-fibrous (Other)70%Glass30%Gray

Fibrous

Homogeneous

BUILDING F ROOF

SYSTEM - GRAY ISO

PAPER

10B-HK-190802

131905914-0020

None DetectedNon-fibrous (Other)70%Glass30%Gray

Fibrous

Homogeneous

BUILDING F ROOF

SYSTEM - GRAY ISO

PAPER

11A-HK-190802

131905914-0021

None DetectedNon-fibrous (Other)100%Blue

Non-Fibrous

Homogeneous

GYM FLOOR - BLUE

FLOORING

11B-HK-190802

131905914-0022

None DetectedNon-fibrous (Other)100%Blue

Non-Fibrous

Homogeneous

GYM FLOOR - BLUE

FLOORING

12A-HK-190802

131905914-0023

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

GYM FLOOR - GRAY

FLOORING

12B-HK-190802

131905914-0024

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

GYM FLOOR - GRAY

FLOORING

Analyst(s)

Kevin Pine (24) Steve Grise, Laboratory Manager

or Other Approved Signatory

EMSL maintains liability limited to cost of analysis . The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 "Interim

Method"), but augmented with procedures outlined in the 1993 ("final") version of the method. This report relates only to the samples reported above, and may not be reproduced, except in full, without

written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the responsibility of the client. All

samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of

the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available on request.

Samples analyzed by EMSL Analytical, Inc. Woburn, MA NVLAP Lab Code 101147-0, CT PH-0315, MA AA000188, RI AAL-139, VT AL998919, Maine Bulk Asbestos LB-0039

Initial report from: 08/10/2019 12:22:55

Page 2 of 2ASB_PLM_0008_0001 - 1.78 Printed: 8/10/2019 12:22 PM

Page 12: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect

OrderID: 131905914

Page 1 Of 1

Page 13: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect

Revised

Mr. Kent Kovacs, AIA, LEED APVice PresidentFlansburgh Architects77 North Washington StreetBoston, MA 02114

RE: Hazardous Building Materials Opinion of Abatement CostsNauset Regional High SchoolEastham, MAFuss & O’Neill Reference No. 20180940.A10

EstimatedQuantity

Estimated UnitCost

TotalEstimated Cost

40 EA $250/EA $10,000.00

32 EA $250/EA $8,000.00

1,500 LF $12/LF $18,000.00

2,250 SF $10/SF $22,500.00

300 LF $25/LF $7,500.00

3 EA $200/EA $600.00

46 EA $250/EA $11,500.00

1,330 LF $12/LF $15,960.00

18,000 SF $5.5/SF $99,000.00

Building A

Black Mastic with 12" x 12" Floor Tile (ACM)

August 12, 2019

Dear Mr. Kovacs:

Fuss & O’Neill, Inc. has prepared the hazardous building materials opinion of abatement cost provided below (for theabovementioned site). These cost opinions are based on our Limited Hazardous Building Materials Inspection reportand Supplemental Inspection Report prepared for the Site, dated February 2019 and August 2019, respectively. Unitcosts are based on current industry rates and are inclusive of typical contractor costs for a normal work schedule (1shift/day), Monday to Friday. They do not include costs for an expedited work schedule (double shifts/ weekends/holidays), project design, construction monitoring, air sampling, and other consultant-based fees. Estimated unit costsare based on assumption that listed materials will be removed, disposed, and transported by the abatement contractorduring one phase.

Material Type

12" x 12" Floor Tile (ACM)

Interior Door Caulking (ACM & PCB)

Pipe & Fitting Insulation (ACM)

Side Lite Glazing Compound (ACM & PCB)

Interior Door Caulking (ACM & PCB)

Top-of-Wall Caulking (ACM & PCB)

Building B

Door Lite Glazing Compound (ACM & PCB)

Top-of-Wall Joint Caulking (ACM & PCB)

Blackboard Material (ACM)

1 of 5F:\P2018\0940\A10\Deliverables\Report\Supplemental Sampling\RCM_NRHS_revised2_OOC_20190812.xlsx

Page 14: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect

EstimatedQuantity

Estimated UnitCost

TotalEstimated CostMaterial Type

30 SF $5/SF $150.00

30 SF $5/SF $150.00

2 EA $125/EA $250.00

300 LF $25/LF $7,500.00

4,600 SF $4.75/SF $21,850.00

25 EA $250/EA $6,250.00

25 EA $250/EA $6,250.00

1,420 LF $12/LF $17,040.00

75 EA $25/EA $1,875.00

31 EA $250/EA $7,750.00

31 EA $250/EA $7,750.00

3,750 SF $4.75/SF $17,812.50

4 EA $200/EA $800.00

1,170 LF $12/LF $14,040.00

1,800 LF $12/LF $21,600.00

2 EA $10,000/EA $20,000.00

15 EA $75/EA $1,125.00

175 LF $10/LF $1,750.00

8 EA $125/EA $1,000.00

30 EA $20/EA $600.00

300 LF $25/LF $7,500.00

500 SF $10/SF $5,000.00

Pipe & Fitting Insulation (ACM)

Door Lite Glazing Compound (ACM & PCB)

Stage Lighting Wire Insulation (ACM)

Head Joint Caulking (ACM & PCB)

Building C

Building D

Unknown Size Floor Tile (ACM)

Pipe & Fitting Insulation (ACM)

12" x 12" Mottled Floor Tile (ACM)

Composite Countertop (ACM)

Countertop Adhesive (ACM)

Stick Pin Mastic (ACM)

Top-of-Wall Caulking (ACM & PCB)

Mudded Pipe- Fitting Insulation (ACM)

Interior Door Caulking (ACM & PCB)

12'' x 12'' Floor Tile (ACM)

Window Side Lite Glazing Compound (ACM & PCB)

White Door Lite Glazing Compound (ACM & PCB)

Top-of-Wall Caulking (ACM & PCB)

Boiler Components (Assumed ACM)

Vibration Isolator (ACM)

Sink Undercoating (ACM)

Interior Door Caulking (ACM & PCB)

12" x 12" Mottled Floor Tile (ACM)

Sink Undercoating (ACM)

F:\P2018\0940\A10\Deliverables\Report\Supplemental Sampling\RCM_NRHS_revised2_OOC_20190812.xlsx 2 of 5

Page 15: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect

EstimatedQuantity

Estimated UnitCost

TotalEstimated CostMaterial Type

2,750 LF $12/LF $33,000.00

11,000 SF $4.75/SF $52,250.00

33 EA $12/EA $396.00

25 EA $250/EA $6,250.00

1,500 SF $10/SF $15,000.00

1,500 SF $5/SF $7,500.00

20 EA $250/EA $5,000.00

300 LF $25/LF $7,500.00

4,850 SF $8/SF $38,800.00

500 EA $7/EA $3,500.00

3 EA $200/EA $600.00

15 EA $250/EA $3,750.00

15 EA $250/EA $3,750.00

5,100 SF $4.75/SF $24,225.00

100 SF $10/SF $1,000.00

1275 LF $12/LF $15,300.00

5 EA $75/EA $375.00

200 SF $10/SF $2,000.00

300 LF $25/LF $7,500.00

1,500 SF $10/SF $15,000.00

Decorative Ceiling Plaster (ACM)

Concrete Wall Foundation Plug Caulking (ACM)

Side Lite Window Glazing Compound (ACM & PCB)

Interior Door Caulking (ACM & PCB)

12'' x 12'' Floor Tile (ACM)

Stick Pin Adhesive (ACM)

Top-of-Wall Caulking (ACM & PCB)

Gasket between Duct Flanges (ACM)

Stick Pin Adhesive (ACM)

White Door Lite Glazing Compound (ACM & PCB)

Pipe & Fitting Insulation (ACM)

Quarry Tile Dampproofing (Assumed ACM)

Pipe & Fitting Insulation (ACM)

2,500 SF

Lab Countertop (ACM)

Countertop Adhesive (ACM)

Top-of-Wall Joint Caulking (ACM & PCB)

12" x 12" Mottled Floor Tile (ACM)

Interior Door Caulking (Classroom Doors) (ACM & PCB)

Door Lite Glazing Compound (ACM & PCB)

Countertop Joint Caulking (ACM)

Chalkboard Material (ACM)

Brown Mastic Associated with 12" x 12" "Newer" Tan Mottled Floor Tile(ACM)

$10/SF $25,000.00

Building E

Building F

Sink Undercoating (ACM)

F:\P2018\0940\A10\Deliverables\Report\Supplemental Sampling\RCM_NRHS_revised2_OOC_20190812.xlsx 3 of 5

Page 16: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect

EstimatedQuantity

Estimated UnitCost

TotalEstimated CostMaterial Type

19 EA $275/EA $5,225.00

19 EA $250/EA $4,750.00

920 LF $12/LF $11,040.00

7,920 SF Lump Sum $15,000.00

5 EA $200/EA $1,000.00

30 LF $12/LF $360.00

460 SF $15/SF $6,900.00

2,500 SF $250/SF $625,000.00

1,500 LF $10/LF $15,000.00

3,500 LF $10/LF $35,000.00

1,500 LF $10/LF $15,000.00

1,500 LF $10/LF $15,000.00

3,500 LF $10/LF $35,000.00

1,500 LF $10/LF $15,000.00

Lump Sum $7,500.00

Lump Sum $5,000.00

$1,440,573.50

$86,426.50

$1,527,000.00

Exterior

Side Lite Window Glazing Compound (ACM & PCB)

Door Frame Caulking (ACM & PCB)

Top-of-Wall Caulking (ACM & PCB)

Building G

Poured Resilient Flooring (Hazardous Waste - Mercury)

Door Lite Glazing Compound (ACM & PCB)

Total*

Vent Louver Caulking (ACM & PCB)

Foundation Sill Flashing Mastic (ACM)

Foundation Dampproofing (ACM)(Impacted by Site demolition, only)

Lighting Ballast, Fluorescent Lamp, and Mercury-Containing Equipment Disposal

Lead-Based Paint Work Practices & Limited Disposal

Subtotal

(~6%) Contingency

Presumed PCB-Containing Materials, Only

Floor Control Joint Caulking (PCB)

Wood Panel Flashing-to-Concrete Caulking (PCB)

Expansion Joint Caulking (PCB)

Control Joint Caulking (PCB)

Wood Wall Panel Caulking (PCB)

Sidewalk Expansion Joint Caulking (PCB)

EA = Each, LF = Linear Feet, SF = Square Feet

ACM = Asbestos-Containing Material

PCB = Presumed Polychlorinated Biphenyl (PCB)-Containing Source Building Material

*Does not include consultant fees

F:\P2018\0940\A10\Deliverables\Report\Supplemental Sampling\RCM_NRHS_revised2_OOC_20190812.xlsx 4 of 5

Page 17: 4.1.2.4 Environmental and Existing Building Assessments · 2020. 1. 2. · coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect

EstimatedQuantity

Estimated UnitCost

TotalEstimated CostMaterial Type

DD/rs

Sincerely,

Dustin A. DiedricksenAssociate/Environmental Department Manager

F:\P2018\0940\A10\Deliverables\Report\Supplemental Sampling\RCM_NRHS_revised2_OOC_20190812.xlsx 5 of 5