4.1.2.4 Environmental andExisting BuildingAssessments
Final Design Program Nauset Regional High SchoolChanges in Site Development Require-
30
Peebles 3-5 Elementary SchoolNauset Regional High SchoolEnvironmental and Existing Building Assessments
Environmental and Existing Building Assessments
A Hazardous Building Materials Inspection Report performed by Fuss & O’Neill has been attached here.
108 Myrtle StreetSuite 502
Quincy, MA02171
t 617.282.4675800.286.2469
f 617.481.5885
www.fando.com
California
Connecticut
Maine
Massachusetts
New Hampshire
Rhode Island
Vermont
August 12, 2019
Mr. Kent Kovacs, AIA, LEED APVice PresidentFlansburgh Architects77 North Washington StreetBoston, MA 02114
RE: Supplemental Hazardous Building Materials Consulting ServicesNauset Regional High School100 Cable Road, Eastham, MA 02651Fuss & O’Neill Reference No. 20180940.A10
Dear Mr. Kovacs:
On July 31, 2019 and August 1, 2019, Fuss & O’Neill, Inc. (Fuss & O’Neill) representatives, Mr. Robert Mallett and Ms. Heidi Keller, performed supplemental sampling for suspect Asbestos-Containing Materials (ACM) at select locations within Buildings E, F, and the Boiler Room of Building D of the Nauset Regional High School located at 100 Cable Road in Eastham, Massachusetts (the “Site”).
On July 31, 2019, Mr. Mallett and Ms. Keller conducted slab coring at the Women’s Faculty Restroom located in Building E and the Boiler Room located in Building D. No suspect sub-slab dampproofing was observed during this inspection. Ceramic floor tile components were observed in the Women’s Faculty restroom and samples were collected for analysis. In addition to the slab coring, investigatory cuts were made at the Auditorium Stage as well as the Gymnasium floors. If suspect materials were observed, samples were collected for analysis.
On August, 1, 2019, a series of roof cuts were performed and subsequently patched by a professional roofing subcontractor. These roof cuts were observed by Fuss & O’Neill and if suspect materials were observed, samples were collected for analysis.
All asbestos samples were collected by a Fuss & O’Neill Commonwealth of Massachusetts-certified and United States Environmental Protection Agency (EPA)-accredited Asbestos Inspector. Refer to the report attachments for a copy of the Asbestos Inspector state certifications and accreditations.
Samples were analyzed at EMSL Analytical, Inc. (EMSL), a Commonwealth of Massachusetts-certified and American Industrial Hygiene Association-accredited asbestos laboratory. Asbestos sample analysis was conducted using the EPA Interim Method for the Determination of Asbestos
ProjectData\P2018\0940\A10\Deliverables\Report\Supplemental Sampling\RCM_hjk_NausetHS_AsbSupSampleLtr_20190812.docx
Flansburgh ArchitectsAugust 12, 2109Page 2
ProjectData\P2018\0940\A10\Deliverables\Report\Supplemental Sampling\RCM_hjk_Nauset HS_AsbSupSampleLtr_20190812.docx
in Bulk Building Materials (EPA/600/R-93/116) via Polarized Light Microscopy with DispersionStaining (PLM/DS).
The suspect ACM sample locations, material type, sample identification, and asbestos content areidentified by bulk sample analysis in Table 1, attached. The asbestos laboratory analytical reportsand chain-of-custody forms are also included as an attachment.
The samples collected of suspect ACM were reported by EMSL to be “None Detected” (i.e., non-ACM). Any materials not identified during the original or supplemental material survey should bepresumed as ACM until sample collection and analysis determines to be non-ACM.
The EPA, Occupational Safety and Health Administration (OSHA), and the Commonwealth ofMassachusetts Department of Labor Standards (MADLS) defines any material that contains greaterthan one percent (>1%) asbestos, utilizing PLM, as being an ACM. The Commonwealth ofMassachusetts Department of Environmental Protection (MassDEP) defines any material thatcontain equal to or greater than one percent (≥1%) asbestos as being an ACM. MassDEP definesan asbestos-contaminated material as a material containing greater than zero percent (>0%) andless than one percent (<1%) asbestos. Materials that are identified as "none detected" are specifiedas not containing asbestos.
If you should have any questions regarding the contents of this letter, please do not hesitate tocontact me at (617) 282-4675, extension 4706. Thank you for this opportunity to have served yourenvironmental needs.
This report was prepared by Environmental Analyst, Heidi Keller.
Sincerely,
Robert C. MallettEnvironmental Analyst
AttachmentsAsbestos Inspector Certifications & AccreditationsTable 1: Suspect Asbestos-Containing Materials Laboratory Analytical Data SummaryAsbestos Laboratory Report & Chain-of-Custody Forms
Table 1Suspect Asbestos-Containing Materials Laboratory Analytical Data Summary
Sample Number Material Type NESHAPCategory
Sample Location Result Comments
01A-HK-190731 Black Dampproofing Non-ACM Building E Bathroom ND
01B-HK-190731 Black Dampproofing Non-ACM Building E Bathroom ND
02A-HK-190731 White Grout Non-ACM Building E Bathroom ND
02B-HK-190731 White Grout Non-ACM Building E Bathroom ND
03A-HK-190731 Gray Ceramic Tile Thin-Set Mortar Non-ACM Building E Bathroom ND
03B-HK-190731 Gray Ceramic Tile Thin-Set Mortar Non-ACM Building E Bathroom ND
04A-HK-190731 Black Vapor Barrier Non-ACM Gym Floor (on concrete) ND
04B-HK-190731 Black Vapor Barrier Non-ACM Gym Floor (on concrete) ND
05A-HK-190731 Black Mastic Non-ACM Gym Floor- on Cellulose Material(beneath hardwood)
ND
05B-HK-190731 Black Mastic Non-ACM Gym Floor- on Cellulose Material(beneath hardwood)
ND
06A-HK-190731 Black Felt Paper Non-ACM Stage ND
06B-HK-190731 Black Felt Paper Non-ACM Stage ND
07A-HK-190802 Black Asphaltic Mop Non-ACM Building E Roof System ND
07B-HK-190802 Black Asphaltic Mop Non-ACM Building E Roof System ND
08A-HK-190802 Gray Iso Paper Non-ACM Building E Roof System ND
08B-HK-190802 Gray Iso Paper Non-ACM Building E Roof System ND
09A-HK-190802 Black Asphaltic Mop Non-ACM Building F Roof System ND
09B-HK-190802 Black Asphaltic Mop Non-ACM Building F Roof System ND
10A-HK-190802 Gray Iso Paper Non-ACM Building F Roof System ND
10B-HK-190802 Gray Iso Paper Non-ACM Building F Roof System ND
11A-HK-190802 Blue Flooring (Poured Resilient Floor) Non-ACM Gym Floor (Poured Resilient Floor) ND
11B-HK-190802 Blue Flooring (Poured Resilient Floor) Non-ACM Gym Floor (Poured Resilient Floor) ND
12A-HK-190802 Gray Adhesive (Poured Resilient Floor) Non-ACM Gym Floor (Poured Resilient Floor) ND
12B-HK-190802 Gray Adhesive (Poured Resilient Floor) Non-ACM Gym Floor (Poured Resilient Floor) ND
ND = None Detected
ACM = Asbestos-Containing Material
Nauset Regional High SchoolEastham, Massachusetts
Flansburgh ArchitectsAugust 2019
Fuss & O’Neill Reference No. 20180940.A10
\\private\dfs\ProjectData\P2018\0940\A10\Deliverables\Report\Supplemental Sampling\Table 1 - Attachment 2.xlsx 1 of 1
EMSL Analytical, Inc.5 Constitution Way, Unit A Woburn, MA 01801
Tel/Fax: (781) 933-8411 / (781) 933-8412
http://www.EMSL.com / [email protected]
131905914EMSL Order:
Customer ID: ENVI54
Customer PO: 20180940.A10
Project ID:
Attention: Phone:H Keller (860) 646-2469
Fax:Fuss & O’Neill, Inc.
Received Date:146 Hartford Road 08/07/2019 8:30 AM
Analysis Date:Manchester, CT 06040 08/10/2019
Collected Date: 08/07/2019
Project: Nauset Regional High School./ 100 Cable Road., Eastham, MA./ 20180940.A10
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
01A-HK-190731
131905914-0001
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
BUILDING E
BATHROOM -
BLACK
DAMPPROOFING
01B-HK-190731
131905914-0002
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
BUILDING E
BATHROOM -
BLACK
DAMPPROOFING
02A-HK-190731
131905914-0003
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
BUILDING E
BATHROOM -
WHITE GROUT
02B-HK-190731
131905914-0004
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
BUILDING E
BATHROOM -
WHITE GROUT
03A-HK-190731
131905914-0005
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
BUILDING E
BATHROOM - GRAY
CERAMIC TILE THIN
SET
03B-HK-190731
131905914-0006
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
BUILDING E
BATHROOM - GRAY
CERAMIC TILE THIN
SET
04A-HK-190731
131905914-0007
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
GYM FLOOR -
BLACK VAPOR
BARRIER
04B-HK-190731
131905914-0008
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
GYM FLOOR -
BLACK VAPOR
BARRIER
05A-HK-190731
131905914-0009
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
GYM FLOOR- ON
CELLULOSE
MATERIAL - BLACK
MASTIC
05B-HK-190731
131905914-0010
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
GYM FLOOR- ON
CELLULOSE
MATERIAL - BLACK
MASTIC
06A-HK-190731
131905914-0011
None DetectedNon-fibrous (Other)20%Cellulose80%Black
Fibrous
Homogeneous
STAGE - BLACK
FELT PAPER
06B-HK-190731
131905914-0012
None DetectedNon-fibrous (Other)20%Cellulose80%Black
Fibrous
Homogeneous
STAGE - BLACK
FELT PAPER
07A-HK-190802
131905914-0013
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
BUILDING E ROOF
SYSTEM - BLACK
ASPHALTIC MOP
07B-HK-190802
131905914-0014
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
BUILDING E ROOF
SYSTEM - BLACK
ASPHALTIC MOP
Initial report from: 08/10/2019 12:22:55
Page 1 of 2ASB_PLM_0008_0001 - 1.78 Printed: 8/10/2019 12:22 PM
EMSL Analytical, Inc.5 Constitution Way, Unit A Woburn, MA 01801
Tel/Fax: (781) 933-8411 / (781) 933-8412
http://www.EMSL.com / [email protected]
131905914EMSL Order:
Customer ID: ENVI54
Customer PO: 20180940.A10
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
08A-HK-190802
131905914-0015
None DetectedNon-fibrous (Other)70%Glass30%Gray
Fibrous
Homogeneous
BUILDING E ROOF
SYSTEM - GRAY ISO
PAPER
08B-HK-190802
131905914-0016
None DetectedNon-fibrous (Other)70%Glass30%Gray
Fibrous
Homogeneous
BUILDING E ROOF
SYSTEM - GRAY ISO
PAPER
09A-HK-190802
131905914-0017
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
BUILDING F ROOF
SYSTEM - BLACK
ASPHALTIC MOP
09B-HK-190802
131905914-0018
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
BUILDING F ROOF
SYSTEM - BLACK
ASPHALTIC MOP
10A-HK-190802
131905914-0019
None DetectedNon-fibrous (Other)70%Glass30%Gray
Fibrous
Homogeneous
BUILDING F ROOF
SYSTEM - GRAY ISO
PAPER
10B-HK-190802
131905914-0020
None DetectedNon-fibrous (Other)70%Glass30%Gray
Fibrous
Homogeneous
BUILDING F ROOF
SYSTEM - GRAY ISO
PAPER
11A-HK-190802
131905914-0021
None DetectedNon-fibrous (Other)100%Blue
Non-Fibrous
Homogeneous
GYM FLOOR - BLUE
FLOORING
11B-HK-190802
131905914-0022
None DetectedNon-fibrous (Other)100%Blue
Non-Fibrous
Homogeneous
GYM FLOOR - BLUE
FLOORING
12A-HK-190802
131905914-0023
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
GYM FLOOR - GRAY
FLOORING
12B-HK-190802
131905914-0024
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
GYM FLOOR - GRAY
FLOORING
Analyst(s)
Kevin Pine (24) Steve Grise, Laboratory Manager
or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 "Interim
Method"), but augmented with procedures outlined in the 1993 ("final") version of the method. This report relates only to the samples reported above, and may not be reproduced, except in full, without
written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the responsibility of the client. All
samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of
the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Woburn, MA NVLAP Lab Code 101147-0, CT PH-0315, MA AA000188, RI AAL-139, VT AL998919, Maine Bulk Asbestos LB-0039
Initial report from: 08/10/2019 12:22:55
Page 2 of 2ASB_PLM_0008_0001 - 1.78 Printed: 8/10/2019 12:22 PM
OrderID: 131905914
Page 1 Of 1
Revised
Mr. Kent Kovacs, AIA, LEED APVice PresidentFlansburgh Architects77 North Washington StreetBoston, MA 02114
RE: Hazardous Building Materials Opinion of Abatement CostsNauset Regional High SchoolEastham, MAFuss & O’Neill Reference No. 20180940.A10
EstimatedQuantity
Estimated UnitCost
TotalEstimated Cost
40 EA $250/EA $10,000.00
32 EA $250/EA $8,000.00
1,500 LF $12/LF $18,000.00
2,250 SF $10/SF $22,500.00
300 LF $25/LF $7,500.00
3 EA $200/EA $600.00
46 EA $250/EA $11,500.00
1,330 LF $12/LF $15,960.00
18,000 SF $5.5/SF $99,000.00
Building A
Black Mastic with 12" x 12" Floor Tile (ACM)
August 12, 2019
Dear Mr. Kovacs:
Fuss & O’Neill, Inc. has prepared the hazardous building materials opinion of abatement cost provided below (for theabovementioned site). These cost opinions are based on our Limited Hazardous Building Materials Inspection reportand Supplemental Inspection Report prepared for the Site, dated February 2019 and August 2019, respectively. Unitcosts are based on current industry rates and are inclusive of typical contractor costs for a normal work schedule (1shift/day), Monday to Friday. They do not include costs for an expedited work schedule (double shifts/ weekends/holidays), project design, construction monitoring, air sampling, and other consultant-based fees. Estimated unit costsare based on assumption that listed materials will be removed, disposed, and transported by the abatement contractorduring one phase.
Material Type
12" x 12" Floor Tile (ACM)
Interior Door Caulking (ACM & PCB)
Pipe & Fitting Insulation (ACM)
Side Lite Glazing Compound (ACM & PCB)
Interior Door Caulking (ACM & PCB)
Top-of-Wall Caulking (ACM & PCB)
Building B
Door Lite Glazing Compound (ACM & PCB)
Top-of-Wall Joint Caulking (ACM & PCB)
Blackboard Material (ACM)
1 of 5F:\P2018\0940\A10\Deliverables\Report\Supplemental Sampling\RCM_NRHS_revised2_OOC_20190812.xlsx
EstimatedQuantity
Estimated UnitCost
TotalEstimated CostMaterial Type
30 SF $5/SF $150.00
30 SF $5/SF $150.00
2 EA $125/EA $250.00
300 LF $25/LF $7,500.00
4,600 SF $4.75/SF $21,850.00
25 EA $250/EA $6,250.00
25 EA $250/EA $6,250.00
1,420 LF $12/LF $17,040.00
75 EA $25/EA $1,875.00
31 EA $250/EA $7,750.00
31 EA $250/EA $7,750.00
3,750 SF $4.75/SF $17,812.50
4 EA $200/EA $800.00
1,170 LF $12/LF $14,040.00
1,800 LF $12/LF $21,600.00
2 EA $10,000/EA $20,000.00
15 EA $75/EA $1,125.00
175 LF $10/LF $1,750.00
8 EA $125/EA $1,000.00
30 EA $20/EA $600.00
300 LF $25/LF $7,500.00
500 SF $10/SF $5,000.00
Pipe & Fitting Insulation (ACM)
Door Lite Glazing Compound (ACM & PCB)
Stage Lighting Wire Insulation (ACM)
Head Joint Caulking (ACM & PCB)
Building C
Building D
Unknown Size Floor Tile (ACM)
Pipe & Fitting Insulation (ACM)
12" x 12" Mottled Floor Tile (ACM)
Composite Countertop (ACM)
Countertop Adhesive (ACM)
Stick Pin Mastic (ACM)
Top-of-Wall Caulking (ACM & PCB)
Mudded Pipe- Fitting Insulation (ACM)
Interior Door Caulking (ACM & PCB)
12'' x 12'' Floor Tile (ACM)
Window Side Lite Glazing Compound (ACM & PCB)
White Door Lite Glazing Compound (ACM & PCB)
Top-of-Wall Caulking (ACM & PCB)
Boiler Components (Assumed ACM)
Vibration Isolator (ACM)
Sink Undercoating (ACM)
Interior Door Caulking (ACM & PCB)
12" x 12" Mottled Floor Tile (ACM)
Sink Undercoating (ACM)
F:\P2018\0940\A10\Deliverables\Report\Supplemental Sampling\RCM_NRHS_revised2_OOC_20190812.xlsx 2 of 5
EstimatedQuantity
Estimated UnitCost
TotalEstimated CostMaterial Type
2,750 LF $12/LF $33,000.00
11,000 SF $4.75/SF $52,250.00
33 EA $12/EA $396.00
25 EA $250/EA $6,250.00
1,500 SF $10/SF $15,000.00
1,500 SF $5/SF $7,500.00
20 EA $250/EA $5,000.00
300 LF $25/LF $7,500.00
4,850 SF $8/SF $38,800.00
500 EA $7/EA $3,500.00
3 EA $200/EA $600.00
15 EA $250/EA $3,750.00
15 EA $250/EA $3,750.00
5,100 SF $4.75/SF $24,225.00
100 SF $10/SF $1,000.00
1275 LF $12/LF $15,300.00
5 EA $75/EA $375.00
200 SF $10/SF $2,000.00
300 LF $25/LF $7,500.00
1,500 SF $10/SF $15,000.00
Decorative Ceiling Plaster (ACM)
Concrete Wall Foundation Plug Caulking (ACM)
Side Lite Window Glazing Compound (ACM & PCB)
Interior Door Caulking (ACM & PCB)
12'' x 12'' Floor Tile (ACM)
Stick Pin Adhesive (ACM)
Top-of-Wall Caulking (ACM & PCB)
Gasket between Duct Flanges (ACM)
Stick Pin Adhesive (ACM)
White Door Lite Glazing Compound (ACM & PCB)
Pipe & Fitting Insulation (ACM)
Quarry Tile Dampproofing (Assumed ACM)
Pipe & Fitting Insulation (ACM)
2,500 SF
Lab Countertop (ACM)
Countertop Adhesive (ACM)
Top-of-Wall Joint Caulking (ACM & PCB)
12" x 12" Mottled Floor Tile (ACM)
Interior Door Caulking (Classroom Doors) (ACM & PCB)
Door Lite Glazing Compound (ACM & PCB)
Countertop Joint Caulking (ACM)
Chalkboard Material (ACM)
Brown Mastic Associated with 12" x 12" "Newer" Tan Mottled Floor Tile(ACM)
$10/SF $25,000.00
Building E
Building F
Sink Undercoating (ACM)
F:\P2018\0940\A10\Deliverables\Report\Supplemental Sampling\RCM_NRHS_revised2_OOC_20190812.xlsx 3 of 5
EstimatedQuantity
Estimated UnitCost
TotalEstimated CostMaterial Type
19 EA $275/EA $5,225.00
19 EA $250/EA $4,750.00
920 LF $12/LF $11,040.00
7,920 SF Lump Sum $15,000.00
5 EA $200/EA $1,000.00
30 LF $12/LF $360.00
460 SF $15/SF $6,900.00
2,500 SF $250/SF $625,000.00
1,500 LF $10/LF $15,000.00
3,500 LF $10/LF $35,000.00
1,500 LF $10/LF $15,000.00
1,500 LF $10/LF $15,000.00
3,500 LF $10/LF $35,000.00
1,500 LF $10/LF $15,000.00
Lump Sum $7,500.00
Lump Sum $5,000.00
$1,440,573.50
$86,426.50
$1,527,000.00
Exterior
Side Lite Window Glazing Compound (ACM & PCB)
Door Frame Caulking (ACM & PCB)
Top-of-Wall Caulking (ACM & PCB)
Building G
Poured Resilient Flooring (Hazardous Waste - Mercury)
Door Lite Glazing Compound (ACM & PCB)
Total*
Vent Louver Caulking (ACM & PCB)
Foundation Sill Flashing Mastic (ACM)
Foundation Dampproofing (ACM)(Impacted by Site demolition, only)
Lighting Ballast, Fluorescent Lamp, and Mercury-Containing Equipment Disposal
Lead-Based Paint Work Practices & Limited Disposal
Subtotal
(~6%) Contingency
Presumed PCB-Containing Materials, Only
Floor Control Joint Caulking (PCB)
Wood Panel Flashing-to-Concrete Caulking (PCB)
Expansion Joint Caulking (PCB)
Control Joint Caulking (PCB)
Wood Wall Panel Caulking (PCB)
Sidewalk Expansion Joint Caulking (PCB)
EA = Each, LF = Linear Feet, SF = Square Feet
ACM = Asbestos-Containing Material
PCB = Presumed Polychlorinated Biphenyl (PCB)-Containing Source Building Material
*Does not include consultant fees
F:\P2018\0940\A10\Deliverables\Report\Supplemental Sampling\RCM_NRHS_revised2_OOC_20190812.xlsx 4 of 5
EstimatedQuantity
Estimated UnitCost
TotalEstimated CostMaterial Type
DD/rs
Sincerely,
Dustin A. DiedricksenAssociate/Environmental Department Manager
F:\P2018\0940\A10\Deliverables\Report\Supplemental Sampling\RCM_NRHS_revised2_OOC_20190812.xlsx 5 of 5