4-Pipe VAV vs. Active Chilled Beams · Active Chilled Beams Steven T. Taylor, PE ... Alameda, CA...
Transcript of 4-Pipe VAV vs. Active Chilled Beams · Active Chilled Beams Steven T. Taylor, PE ... Alameda, CA...
Session C5: Ventilation Choices
4-Pipe VAV vs. Active Chilled Beams
Steven T. Taylor, PEPrincipalTaylor Engineering, Alameda, [email protected]
Learning Objectives
• Explore the pros and cons of using active chilled beams versus 4-pipe VAV systems;
•Become familiar with different lab types as they define which system type is more appropriate;
•Understand the difference between a load-dominated, hood-dominated, and ventilation-dominated lab space; and
•Understand the cost and energy implications of two popular mechanical systems used in laboratories.
Agenda
• System schematics• 4-pipe VAV (4PVAV) • Active Chilled Beams (ACB)
• Important fundamentals: Lab types• Ventilation-dominated• Hood-dominated• Load-dominated
• Case study: Lab in Oakland, CA• Cooling loads• Energy use
• Other factors• Conclusions
4-pipe VAV Schematic
Lab Exhaust fans
VFD
VFD
VFD
Air Handler
FSD
Lab air valves -typ
Cond. drain
Change-over valves
Control valves
Sub
-du
ct
Outdoor Air
Min. Flow Bypass
Dampers
Supply Air Duct
Hot Water Coil
No chilled water coil at air handler in “dry” climates
Chilled water coil with condensate drain at zones
“Dry”: <63F Dewpoint (75F/65%RH) except for a few hundred hours/year
DenverPortland
Includes most of west coast, southwest, mountain states (ASHRAE B and C Climate Zones)
Changeover Piping
Why Changeover instead of two coils?
•Much higher hot water temperature drop ΔT• Improved boiler efficiency with condensing boilers• Smaller piping and HW pumps• Lower HW pump energy
• Less space required• Lower air pressure drop
• Lower fan energy
• Less expensive• Eliminated HW coil• Smaller HW piping
Active Chilled Beam Schematic
Lab Exhaust fans
VFD
VFD
VFD
Air Handler
FSD
Lab air valves
Active Chilled Beam
Sub
-du
ct
Outdoor Air
Supply Air Duct
Hot Water Coil
Chilled water coil required at air handler
Active chilled beams (changeover piping same as 4PVAV)
Lab Types
•Ventilation-dominated• Where the minimum ventilation rate (air changes per hour
ACH) is greater than hood exhaust rates and rates required for cooling
•Hood-dominated• Where the hood exhaust rate exceeds those required for
cooling or minimum ventilation
• Load-dominated• Where the airflow needed for cooling exceeds the hood
exhaust and minimum ventilation rates
Only “load-dominated” labs benefit from ACBs
• ACB induction cooling increases cooling capacity at a lower outdoor air rate• ~2.5 times the sensible load that primary outdoor air can provide alone
• So labs that require 6 ACH to 15 ACH for cooling require only 6 ACH of outdoor air
• Reduces fan energy and energy needed to condition outdoor air
How prevalent are “load dominated” labs?
UC Davis Lab Plug Loads (from Labs21 Minimizing Reheat Energy Use in Laboratories)
•Varies significantly from lab to lab•Occupied lab vent
typically 6 to 10 ACH• Equates to ~5.8 to
9.7 w/ft2 total load
• Some labs may be designed for high w/ft2, but seldom operate there
Equivalence of ACH to plug loads assuming a 9 foot ceiling and 55°F supply air temperature, 75°F space temperature
ACHLoads w/ft2
2 1.94 3.96 5.88 7.7
10 9.712 11.614 13.5
Example Lab
• 55000 ft2 Lab in Oakland, CA
• 6 ACH occupied, 4 ACH unoccupied
• Air-to-water heat pump/chillers• 2-pipe changeover since there is no simultaneous heat/cool
with 4PVAV and not enough hours with ACB system to be cost effective
• Lab mix (which favors ACBs)• 22% ventilation dominated • 78% load dominated labs• 0% hood dominated labs
• EnergyPlus model
ACB supply air temperature control
• Ideally just low enough to prevent condensation on chilled beams
• Ideal: condensation sensor based reset
Equipment Sizing vs. Supply air Temperature
ACB 55°F SAT
ACB 58°F SAT
ACB 60°F SAT
ACB 65°F SAT
4-Pipe VAV
AHU (cfm) 39,402 39,402 39,402 39,402 61,492
HP/chillers (tons) 196 185 178 162 105
4PVAV has larger AHU but smaller chiller plant
4PVAV has only HW coil so SAT does not affect loads or energy
~63F SAT warmest to ensure spaces <65% RH
Site Energy Use Index, Btu/h/ft2
Ideal condensate reset between these two
Energy Cost Index $/ft2
$0.00
$0.10
$0.20
$0.30
$0.40
$0.50
$0.60
$0.70
$0.80
Heating Cooling Fans Pumps Heat Rejection
Co
st
[$/f
t²]
ACB 55°F SAT + Chilled Beam
ACB 58°F SAT + Chilled Beam
ACB 60°F SAT + Chilled Beam
ACB 65°F SAT + Chilled Beam
4-Pipe VAV
$3.24 /ft²$3.01 /ft² $2.90 /ft² $2.82 /ft²
$2.56 /ft²
$0.00
$0.50
$1.00
$1.50
$2.00
$2.50
$3.00
$3.50
Total
Co
st
[$/f
t²]
ACB 55°F SAT + Chilled Beam
ACB 58°F SAT + Chilled Beam
ACB 60°F SAT + Chilled Beam
ACB 65°F SAT + Chilled Beam
4-Pipe VAV
Ideal condensate reset between these two
EnergyPlus Results - Heating
•Heating energy is lower for 4PVAV • Literally no reheat• Higher for labs in load-dominated mode
in cold weather due to greater OA conditioning
• But lower for labs in ventilation-dominated mode since ACB dehumidification increases reheat En
ergy
Co
st $
/ft2
AC
B 5
5F
AC
B 5
8F
AC
B 6
0F
AC
B 6
5F
4P
VA
V
EnergyPlus Results - Cooling
• Cooling energy is lower for 4PVAV • Economizer effect in load-dominated labs
• Many hours/year with Oakland’s mild weather
• ACB could mitigate with waterside economizer but at added cost
• Single temperature chiller plant • No cooling efficiency benefit for lukewarm
CHWST to ACBs
• ACB could mitigate with dual temperature plant or DX for AHU but at added cost/complexity
Ener
gy C
ost
$/f
t2
AC
B 5
5F
AC
B 5
8F
AC
B 6
0F
AC
B 6
5F
4P
VA
V
EnergyPlus Results - Fans
• Fan energy is lower for 4PVAV • Because ACBs provide higher sensible
loads, all labs become ventilation-dominated so the system is ~CAV
• 4PVAV has cube-law performance of fans at part load• Pressure drop through entire duct
system goes down with square of flow
• Exhaust system also VAV due to high exhaust stacks – savings lower if high exhaust velocity must be maintained
Ener
gy C
ost
$/f
t2
AC
B 5
5F
AC
B 5
8F
AC
B 6
0F
AC
B 6
5F
4P
VA
V
Why does 4PVAV have lower fan energy?
Other 4PVAV Advantages:
• Net first costs are usually lower • Very high cost of the ACBs and their installation• Smaller cooling and heating plants• Even smaller piping and pumps due to higher ΔTs• Partially offset by larger AHUs & ductwork, terminal unit condensate drains
• Works for all zones• ACB system only effective in load-dominated labs
• Ventilation-dominated zones are essentially constant volume reheat• ACB cannot be used on some hood-dominated labs due to insufficient
ceiling space to house the ACBs
• More flexible for future remodels• Hoods can be added to load-dominated labs without any modifications • 4PVAV diffusers more readily relocated vs. ACBs
• Lower risk of condensation damage
Other ACB Advantages:
• Smaller supply air system if many load-dominated labs• Less roof space needed for AHUs• Less ceiling space needed for ductwork
• Possible floor/floor height reduction
•No condensate drains at terminal units
Conclusions
• 4PVAV Advantages• Usually more energy efficient
• For sure in mild, dry climates• For sure if most zones hood- or ventilation-dominated
• Usually costs less• Unless most labs are highly load-dominated
• More flexible• Works for all lab types• Less expensive to remodel
• ACB Advantages• Less space required for AHUs, duct mains• No condensate drains at terminal units