33 KV Data Sheet
-
Upload
cherif-yahyaoui -
Category
Documents
-
view
214 -
download
0
Transcript of 33 KV Data Sheet
-
7/29/2019 33 KV Data Sheet
1/4
LARSEN & TOUBRO
LTD.
CAPTIVE POWER PLANT
PANIPAT NAPHTHA CRACKER PROJECT,
INDIAN OIL CORPORATION LTD.L&T SARGENT & LUNDY
LTD.
TITLE: TECHNICAL SPECIFICATION FOR HT CABLES
[33kV (E) CABLES]
Doc. No. :
6556-EPCC4-52-SP-E-0016
Rev.: 1
LOI No.:IOCL/PUR/SU/E19/254
Dated 23.03.07
Item
No. Description Units
1 C x 240 1 C x 300 1 C x 400
1 Manufacturer Polycab Wires Pvt. Limited .Daman
2 Voltage Grade kV 19 / 33 19 / 33 19 / 333 Cable sizes and no. of core 1 C x 240 1 C x 300 1 C x 400
4 Type designation 2XWaY 2XWaY 2XWaY
5 Applicable standard I S 7098 ( PART - II ) / 85
6 Conductor
a) Nominal area and
constructionmm2 240 300 400
b) Shape of conductor Compact Circular
c) Number and dia of
strands (Nom.)35 / 3.08 35 / 3.4 57 / 3.06
d) Material and grade Annealed Bare Copper
e) Max. D.C. resistance at
20C (/km)0.0754 0.0601 0.0470
7
Normal current rating of
cable circuit under as
installed conditions in
air at ambient
temperature of 45oC
A 570 655 750
8
Estimated conductor
temperature under as
installed condition
0C 90
9
Conductor short circuit
carrying capacity for one
(1) sec cable loaded as item
7 before short circuit :
a) Short circuit current kA 34.3 42.9 57.1
b) Conductor temperature 0C 250
10 Conductor screen:
Page 1 of 4
-
7/29/2019 33 KV Data Sheet
2/4
LARSEN & TOUBRO
LTD.
CAPTIVE POWER PLANT
PANIPAT NAPHTHA CRACKER PROJECT,
INDIAN OIL CORPORATION LTD.L&T SARGENT & LUNDY
LTD.
TITLE: TECHNICAL SPECIFICATION FOR HT CABLES
[33kV (E) CABLES]
Doc. No. :
6556-EPCC4-52-SP-E-0016
Rev.: 1
LOI No.:IOCL/PUR/SU/E19/254
Dated 23.03.07
a) Type of material Semi conducting XLPE Compound
b) Nominal Thickness mm 0.5
c)Method of application By Extrusion
11 Insulation
a) Material XLPE Compound
b) Nominal thickness mm 8.8
c) Tolerance on
insulation thickness
The Smallest value of insulation thickness shall not fall
below the Nom. Value by 0.1 + 0.1 ti , where ti is the Nom.
Values given above.
d) Type of extrusion and
curing processTriple Extrusion and Dry Curing.
e)Estimated cable
insulation temperature
under as installed
condition
0C The Respective ground or Air temperature at Site
f) Identification of cores NA NA NAg) Dia under inner sheath
(approx.) mmmm 43.0 45.0 48.0
12 Insulation Screen
a) Material Semi conducting XLPE Compound
b) Nominal thickness mm 0.5
c) Method of application By Extrusion
13 Metallic screen
a) Screen or metallic
sheath short circuit carryingcapacity for one (1) sec
cable loaded as item 7
before short circuit.
kA 17.9
b) Recommended screen or
sheath temperatureC 80 C
c) Material and Type Annealed Plain Copper Wires
14 Inner sheath :
a) Material & Type PVC Type "ST2" as per IS 5831 / 84
b) Minimum thickness mm 0.5 0.5 0.5
c) Tolerance on thicknessNO Tolerance . The above Mentioned Minimum Shall be
met.
Page 2 of 4
-
7/29/2019 33 KV Data Sheet
3/4
LARSEN & TOUBRO
LTD.
CAPTIVE POWER PLANT
PANIPAT NAPHTHA CRACKER PROJECT,
INDIAN OIL CORPORATION LTD.L&T SARGENT & LUNDY
LTD.
TITLE: TECHNICAL SPECIFICATION FOR HT CABLES
[33kV (E) CABLES]
Doc. No. :
6556-EPCC4-52-SP-E-0016
Rev.: 1
LOI No.:IOCL/PUR/SU/E19/254
Dated 23.03.07
d) Wrapped or Extruded Extruded
e) Colour of sheath Black
f) Filler material Not Applicable
g) Dia below Armour (if
applicable) Approx. mm44.2 46.2 49.2
15 Armour (if applicable)
a) Material Hard Aluminium Wires
b) Round wire / strip Round wires
c) No. and Dimension of
round wire / strip(approx.)50 52 55
d) Dimension ( mm ) 2.5 2.5 2.5
e) Max.Resistance (DC) at
20c / km 0.130 0.125 0.118
f) Diameter. below outersheath ( Approx. ) mm
49.2 51.2 54.2
16 Outer Sheath :
a) Material & Type PVC Type "ST2" ( FRLS ) to IS 5831 / 84
b) Colour of outer sheath Black
c) Minimum thickness of
outer sheathmm 1.88 2.04 2.04
d) Tolerance on thicknessNO Tolerance . The above Mentioned Minimum Shall be
met.
17
Electrical parameters at
maximum operating
temperature :
( i ) Resistance / km 0.0975 0.0783 0.0622
( ii )Reactance / km 0.1233 0.1216 0.1161
(iii) Capacitance F/km 0.217 0.234 0.259
(iv) Impedance / km 0.1572 0.1446 0.1317
18 Guaranteed value of
minimum oxygen index of
outer sheath to ASTMD
29
Page 3 of 4
-
7/29/2019 33 KV Data Sheet
4/4
LARSEN & TOUBRO
LTD.
CAPTIVE POWER PLANT
PANIPAT NAPHTHA CRACKER PROJECT,
INDIAN OIL CORPORATION LTD.L&T SARGENT & LUNDY
LTD.
TITLE: TECHNICAL SPECIFICATION FOR HT CABLES
[33kV (E) CABLES]
Doc. No. :
6556-EPCC4-52-SP-E-0016
Rev.: 1
LOI No.:IOCL/PUR/SU/E19/254
Dated 23.03.07
2863.
19
Maximum acid-gas
generation by weight (%) of
outer sheath to IEC 754-1.
20
20Minimum light transmission
to ASTMD 2843.40
21Approx. weight of finished
cable (kg/km)Kg/km 5350 6175 7270
22 O .D . ( Approx. ) mm mm 54 56 59
23Recommended minimum
bending radiusxD 20 x O D
24Maximum pulling force for
each cablekN 12 15 20
25 Type test reports enclosedYes /
NoYes
26 Catalogue attachedYes /
NoYes
27Type of Drum (Wooden /
Steel)Wooden
28Standard length per drum
(EIL's.) - Mts.1000 3 % 1000 3 % 1000 3 %