33 KV Data Sheet

download 33 KV Data Sheet

of 4

Transcript of 33 KV Data Sheet

  • 7/29/2019 33 KV Data Sheet

    1/4

    LARSEN & TOUBRO

    LTD.

    CAPTIVE POWER PLANT

    PANIPAT NAPHTHA CRACKER PROJECT,

    INDIAN OIL CORPORATION LTD.L&T SARGENT & LUNDY

    LTD.

    TITLE: TECHNICAL SPECIFICATION FOR HT CABLES

    [33kV (E) CABLES]

    Doc. No. :

    6556-EPCC4-52-SP-E-0016

    Rev.: 1

    LOI No.:IOCL/PUR/SU/E19/254

    Dated 23.03.07

    Item

    No. Description Units

    1 C x 240 1 C x 300 1 C x 400

    1 Manufacturer Polycab Wires Pvt. Limited .Daman

    2 Voltage Grade kV 19 / 33 19 / 33 19 / 333 Cable sizes and no. of core 1 C x 240 1 C x 300 1 C x 400

    4 Type designation 2XWaY 2XWaY 2XWaY

    5 Applicable standard I S 7098 ( PART - II ) / 85

    6 Conductor

    a) Nominal area and

    constructionmm2 240 300 400

    b) Shape of conductor Compact Circular

    c) Number and dia of

    strands (Nom.)35 / 3.08 35 / 3.4 57 / 3.06

    d) Material and grade Annealed Bare Copper

    e) Max. D.C. resistance at

    20C (/km)0.0754 0.0601 0.0470

    7

    Normal current rating of

    cable circuit under as

    installed conditions in

    air at ambient

    temperature of 45oC

    A 570 655 750

    8

    Estimated conductor

    temperature under as

    installed condition

    0C 90

    9

    Conductor short circuit

    carrying capacity for one

    (1) sec cable loaded as item

    7 before short circuit :

    a) Short circuit current kA 34.3 42.9 57.1

    b) Conductor temperature 0C 250

    10 Conductor screen:

    Page 1 of 4

  • 7/29/2019 33 KV Data Sheet

    2/4

    LARSEN & TOUBRO

    LTD.

    CAPTIVE POWER PLANT

    PANIPAT NAPHTHA CRACKER PROJECT,

    INDIAN OIL CORPORATION LTD.L&T SARGENT & LUNDY

    LTD.

    TITLE: TECHNICAL SPECIFICATION FOR HT CABLES

    [33kV (E) CABLES]

    Doc. No. :

    6556-EPCC4-52-SP-E-0016

    Rev.: 1

    LOI No.:IOCL/PUR/SU/E19/254

    Dated 23.03.07

    a) Type of material Semi conducting XLPE Compound

    b) Nominal Thickness mm 0.5

    c)Method of application By Extrusion

    11 Insulation

    a) Material XLPE Compound

    b) Nominal thickness mm 8.8

    c) Tolerance on

    insulation thickness

    The Smallest value of insulation thickness shall not fall

    below the Nom. Value by 0.1 + 0.1 ti , where ti is the Nom.

    Values given above.

    d) Type of extrusion and

    curing processTriple Extrusion and Dry Curing.

    e)Estimated cable

    insulation temperature

    under as installed

    condition

    0C The Respective ground or Air temperature at Site

    f) Identification of cores NA NA NAg) Dia under inner sheath

    (approx.) mmmm 43.0 45.0 48.0

    12 Insulation Screen

    a) Material Semi conducting XLPE Compound

    b) Nominal thickness mm 0.5

    c) Method of application By Extrusion

    13 Metallic screen

    a) Screen or metallic

    sheath short circuit carryingcapacity for one (1) sec

    cable loaded as item 7

    before short circuit.

    kA 17.9

    b) Recommended screen or

    sheath temperatureC 80 C

    c) Material and Type Annealed Plain Copper Wires

    14 Inner sheath :

    a) Material & Type PVC Type "ST2" as per IS 5831 / 84

    b) Minimum thickness mm 0.5 0.5 0.5

    c) Tolerance on thicknessNO Tolerance . The above Mentioned Minimum Shall be

    met.

    Page 2 of 4

  • 7/29/2019 33 KV Data Sheet

    3/4

    LARSEN & TOUBRO

    LTD.

    CAPTIVE POWER PLANT

    PANIPAT NAPHTHA CRACKER PROJECT,

    INDIAN OIL CORPORATION LTD.L&T SARGENT & LUNDY

    LTD.

    TITLE: TECHNICAL SPECIFICATION FOR HT CABLES

    [33kV (E) CABLES]

    Doc. No. :

    6556-EPCC4-52-SP-E-0016

    Rev.: 1

    LOI No.:IOCL/PUR/SU/E19/254

    Dated 23.03.07

    d) Wrapped or Extruded Extruded

    e) Colour of sheath Black

    f) Filler material Not Applicable

    g) Dia below Armour (if

    applicable) Approx. mm44.2 46.2 49.2

    15 Armour (if applicable)

    a) Material Hard Aluminium Wires

    b) Round wire / strip Round wires

    c) No. and Dimension of

    round wire / strip(approx.)50 52 55

    d) Dimension ( mm ) 2.5 2.5 2.5

    e) Max.Resistance (DC) at

    20c / km 0.130 0.125 0.118

    f) Diameter. below outersheath ( Approx. ) mm

    49.2 51.2 54.2

    16 Outer Sheath :

    a) Material & Type PVC Type "ST2" ( FRLS ) to IS 5831 / 84

    b) Colour of outer sheath Black

    c) Minimum thickness of

    outer sheathmm 1.88 2.04 2.04

    d) Tolerance on thicknessNO Tolerance . The above Mentioned Minimum Shall be

    met.

    17

    Electrical parameters at

    maximum operating

    temperature :

    ( i ) Resistance / km 0.0975 0.0783 0.0622

    ( ii )Reactance / km 0.1233 0.1216 0.1161

    (iii) Capacitance F/km 0.217 0.234 0.259

    (iv) Impedance / km 0.1572 0.1446 0.1317

    18 Guaranteed value of

    minimum oxygen index of

    outer sheath to ASTMD

    29

    Page 3 of 4

  • 7/29/2019 33 KV Data Sheet

    4/4

    LARSEN & TOUBRO

    LTD.

    CAPTIVE POWER PLANT

    PANIPAT NAPHTHA CRACKER PROJECT,

    INDIAN OIL CORPORATION LTD.L&T SARGENT & LUNDY

    LTD.

    TITLE: TECHNICAL SPECIFICATION FOR HT CABLES

    [33kV (E) CABLES]

    Doc. No. :

    6556-EPCC4-52-SP-E-0016

    Rev.: 1

    LOI No.:IOCL/PUR/SU/E19/254

    Dated 23.03.07

    2863.

    19

    Maximum acid-gas

    generation by weight (%) of

    outer sheath to IEC 754-1.

    20

    20Minimum light transmission

    to ASTMD 2843.40

    21Approx. weight of finished

    cable (kg/km)Kg/km 5350 6175 7270

    22 O .D . ( Approx. ) mm mm 54 56 59

    23Recommended minimum

    bending radiusxD 20 x O D

    24Maximum pulling force for

    each cablekN 12 15 20

    25 Type test reports enclosedYes /

    NoYes

    26 Catalogue attachedYes /

    NoYes

    27Type of Drum (Wooden /

    Steel)Wooden

    28Standard length per drum

    (EIL's.) - Mts.1000 3 % 1000 3 % 1000 3 %

    Page 4 of 4