3.2.4_design Info-water Supply

4
ACE/TECHNICAL/DIWS* Project: Date: Client Type of Building Design Engineer No. Descriptions Design Parameters Remarks A. B. B.1 B.2 C. C.1 C.2 D. D.1 D.2 D.3 E. E.1 E.2 E.3 F. F.1 F.2 F.3 G. G.1 G.2 G.3 G.3.1 G.3.2 Design Guidelines For Water Supply Water Demand Scale of Development Total Water Demand Local Authority Scale of Development Total Water Demand Existing Pipeline Location Type of Pipe Size of Pipe (mm) Pressure Head Test Location Fee (Rm) Pressure Available (meter/bar) Incoming Pipe Location Normal Tapping Pipe Jacking Distribution Pipeline Peak flow (gallon per minute gpm) Fire flow (gallon per minute gpm) Residual Head (meter) Peak Flow Fire Flow 1 litre = 0.264 gallon 1 m 3 = 264 gallon 10m = 1 bar 2.5 x total water demand (gpm) Total water demand (gpm)+ fire risk (gpm) (refer Appendix `C ) - Malaysian Water Association (MWA) - Panduan Teknik Air JKR 92/87 Refer to Appendix `BNo. Descriptions Design Parameters Remarks Rev 05 A4.1 ARSEA CONSULTING ENGINEERS SDN BHD (333114-U) DESIGN INFORMATION WATER SUPPLY

description

water supply

Transcript of 3.2.4_design Info-water Supply

ACE/TECHNICAL/DIWS*

Project:Date:

Client

Type of BuildingDesign Engineer

No.DescriptionsDesign ParametersRemarks

A.

B.

B.1

B.2

C.

C.1

C.2

D.

D.1

D.2

D.3

E.

E.1

E.2

E.3

F.

F.1

F.2

F.3

G.

G.1

G.2G.3

G.3.1

G.3.2

Design Guidelines For Water Supply

Water Demand

Scale of Development

Total Water Demand

Local Authority

Scale of Development

Total Water Demand

Existing PipelineLocation

Type of Pipe

Size of Pipe (mm)

Pressure Head Test

Location

Fee (Rm)

Pressure Available (meter/bar)

Incoming Pipe

Location

Normal Tapping

Pipe Jacking

Distribution Pipeline

Peak flow (gallon per minute gpm)

Fire flow (gallon per minute gpm)

Residual Head (meter)

Peak Flow

Fire Flow

1 litre = 0.264 gallon

1 m3 = 264 gallon

10m = 1 bar

2.5 x total water demand (gpm)

Total water demand (gpm)+ fire risk (gpm) (refer Appendix `C)

- Malaysian Water Association

(MWA)

- Panduan Teknik Air JKR 92/87

Refer to Appendix `B

No.DescriptionsDesign ParametersRemarks

G.4

G.4.1

G.4.2

G.4.3

G.4.4

G.5

G.5.1

G.5.2

G.5.3G.6

H.

H.1

H.2

H.3

H.4

H.5

H.5.1

H.5.2

H.5.3

H.6

H.6.1

H.6.2

H.6.3

H.6.4

I.

I.1

J.

J.1

K.

K.1

L.

Type of pipe

Under Roads & Paved Area

Marrine Area

Incoming

Others

Pipe Coefficient

M.S Pipe

D.I Pipe

HDPE

Minimum Cover

Distribution System

Residual Head (meter)

Pumping System Running Hours (hours)

Suction Tank (capacity from total water demand)

Elevated water tank capacity from total water demand

Suction Tank

Type

Size

Capacity

Elevated Water Tank

Type

Size

Capacity

Height of Elevated Structure

Submission

Submission level

Contribution

Constribution fees (RM)

Approval Validity

Approval Validity (years)

Design Software

M.S Pipe/D.I Pipe

D.I Pipe

M.S/ D.I Pipe

HDPE

Gallons/day

Gallons/day

Highest supply level + minimum residual head + losses

CASIO Software for pipe network (loop) analysis

D.I Pipe

D.I Pipe

D.I Pipe

G.5.1 110

G.5.2 110

G.5.3 - 130

- 1.2m for pipes buried at

the side and under road

- 0.9m for pipes buried in

ground, away from roads

Required Elevated Water Tank

12 hours

Determine by local Authority

2 years

Hardys Cross Method

No.Appendix AAppendix B

Water DemandLocal Authority

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

Low Cost Terrace House /Flat

Single Storey Terrace / Low Medium & Medium Costs Flats

Double Storey Terrace House/High Cost Flats

Semi Detached House

Bungalow / Condominiums

Shophouse (Single Storey)/ Gerai

Shophouse (Double Storey)

Shophouse (Three Storey)

Light Industrial Workshop

Semi Detached / Bungalow Workshops

Heavy Industry

Medium Industry

Light Industry

Office / Complex / Commercial (Domestic Usage)

Hotels (with dining and laundry facility Demestic Usage)

Hotel (3 star)

Hotel (5 star)

Schools /Education

Institutions

-Day School / Institution

- Fully Residential

Hospitals (domestic usage)

Mosque (domestic usage)

Other place of worship

Wet Market

Petrol Kiosk

= 1135 lpd (250 gpd)

= 1360 lpd (300 gpd)

= 1590 lpd (350 gpd)

= 1820 lpd (400 gpd)

= 2270 lpd (500gpd)

= 2270 lpd (500 gpd)

= 2730 lpd (600 gpd)

= 4090 lpd (900 gpd)

= 1590 lpd (350 gpd)

= 2730 lpd (600 gpd)

= 65,000 l/ha/day

(6,000 gal/acre/day)

= 50,000 l/ha/day

(4,500 gal/acre/day)

= 33,000 l/ha/day

(3,000 gal/acre/day)

= 1,200 lpd/100Sq.M (250gpd/1,000 sq.ft.)

1,360 lpd/room (300 gpd /room)

2,000 lpd/room (440

gpd/room)

55 lpd / student (12 gpd / student)

360 lpd / student (80 gpd / student)

1,100 lpd / bed (240 gpd / bed)

135 lpd / person (12 gpd / person)

55 lpd / person ( 12 gpd / person)

820 lpd / store (180 gpd / store)

5000 lpd / service bay (1080gpd / service bay)

Johor

Melaka

Negeri Sembilan

Selangor

Perak

Pulau Pinang

Kedah

Perlis

Pahang

Terengganu

Kelantan

Sabah

Sarawak- Syarikat Air Johor (SAJ) Holdings

Sdn Bhd

- Perbadanan Air Melaka

- Jabatan Bekalan air negeri

sembilan

- Syarikat Bekalan Air Selangor

Sdn Bhd

- Lembaga Air Perak

- Perbadanan Air Pulau Pinang

- Jabatan Bekalan Air Negeri

Kedah

- Jabatan Bekalan Air Negeri

Perlis

- Jabatan Bekalan Air Negeri

Pahang

- Syarikat Air Terengganu

- Syarikat Air Kelantan

- Lembaga Air Sabah

- Lembaga Air Sarawak

No.Appendix AAppendix B

Water DemandLocal Authority

22.

23.Stadium

Golf Course55 lpd / person ( 12 gpd / person )

5500 lpd / hole (1200 gpd / hole )

Note:-

gpd

=Gallon per day

lpd

=Liter per day

l/ha/day=Liter/hectares/day

Appendix C

FIRE RISK

Class A Risk

Large buildings, shopping complexes, high rise buildings, large industrial estate, warehouse and ports.

Class B Risk

Congested areas with buildings up to 5 storeys.

Class C Risk

Shophouse up to 3 storey, light industry

Class D Risk

Residential terrace house, detached, semi detached

Class E Risk

Others

Average Total Flow

( Litres )

( Per Minute )

Spanning

(Meters )Maximum No. Of. Hydrant

Outlets Used

Simultaneously

4100

2700

1370

1140

680

90

90

90

120-terrace

150-detached /

semi detached

180

3@ 1370 1 pm

2 @ 1370 1 pm

1

1

1

ARSEA CONSULTING ENGINEERS SDN BHD (333114-U)

DESIGN INFORMATION WATER SUPPLY

EMBED WPWin6.1

PAGE A4.4Rev 05

_1085559434.unknown