30.09.2013 1
Energy and heat-aware metrics for data centers
Jaume Salom, Laura SisóIREC - Catalonia Institute for Energy Research
Ariel Oleksiak, Mateusz JarusPSNC – Poznan Supercomputing and Networking Center
Thomas ZilioIRIT – Institut de Recherche en Informatique de Toulouse
30 September 2013
30.09.2013 2
Introduction
• CoolEmAll will provide tools for planners and operators of DC to carry out flexible and fast simulations to improve energy efficiency and to reduce the carbon footprint associated
• Metrics suitable to quantify CoolEmAll improvement in energy efficiency
EuroEcoDC Workshop - Karlsruhe
30.09.2013 3EuroEcoDC Workshop - Karlsruhe
Contents
1. Present status of DC metrics2. Properties of CoolEmAll metrics3. New metrics proposed4. Description of experiment5. Check Imbalance of Temperature6. Further steps: other metrics to test7. Conclusions
30.09.2013 4EuroEcoDC Workshop - Karlsruhe
Present status of DC metrics• Metrics related to power for complete DC– PUE– Global KPI
• Metrics that consider energy reuse, carbon emissions or water use:– ERE,CUE,WUE
• Metrics to consider the power required in idle conditions– FVER
• Metrics for IT Components: – Power Usage, resource/Watt
30.09.2013 5EuroEcoDC Workshop - Karlsruhe
Properties of CoolEmAll metrics• Focus on Energy not only on peak-power• Focus on Temperature not only on
Power• Heat-aware metrics• Focus on Useful Work on Applications
not only on IT Consumption• Selection of useful and consistent
metrics to assess different granularity levels of a DC (CPU, rack, room)
• Holistic approach
30.09.2013 6EuroEcoDC Workshop - Karlsruhe
Properties of CoolEmAll metrics
• Granularity:– Node unit– Node group– Rack level– Room of a DC
• Focus on:– Resource usage– Energy– Heat-aware
30.09.2013 7EuroEcoDC Workshop - Karlsruhe
Metrics at node-group level
• Node-group cooling index
Referred to the air inlet temperatures
Recommended and allowed values by ASHRAE
New metrics proposed
𝐶𝐼𝑁𝐺 ,𝐻𝐼=[1−∑ (𝑇 𝑁𝐺 ,𝑥−𝑇𝑚𝑎𝑥−𝑟𝑒𝑐 )𝑇 𝑁𝐺 , 𝑥>𝑇𝑚𝑎𝑥−𝑟𝑒𝑐
(𝑇𝑚𝑎𝑥−𝑎𝑙𝑙−𝑇𝑚𝑎𝑥−𝑟𝑒𝑐 )∗𝑛 ]∗100
𝐶𝐼𝑁𝐺 ,𝐿𝑂=[1−∑ (𝑇𝑚𝑖𝑛−𝑟𝑒𝑐−𝑇𝑁𝐺 , 𝑥 )𝑇 𝑁𝐺 ,𝑥<𝑇𝑚𝑖𝑛− 𝑟𝑒𝑐
(𝑇𝑚𝑖𝑛−𝑟𝑒𝑐−𝑇𝑚𝑖𝑛−𝑎𝑙𝑙 )∗𝑛 ]∗100
30.09.2013 8EuroEcoDC Workshop - Karlsruhe
Metrics at node-group level
• Node-group cooling index - meaning
– CING,HI = 100% All intake temperatures ≤ max. recommended temperature.
– CING,HI < 100% At least one intake temperatures > max. recommended temperature.
– CING,LO = 100% All intake temperatures ≥ min. recommended temperature.
– CING,LO < 100% At least one intake temperatures < min. recommended temperature.
New metrics proposed
𝐶𝐼𝑁𝐺 ,𝐻𝐼=[1−∑ (𝑇 𝑁𝐺 ,𝑥−𝑇𝑚𝑎𝑥−𝑟𝑒𝑐 )𝑇 𝑁𝐺 , 𝑥>𝑇𝑚𝑎𝑥−𝑟𝑒𝑐
(𝑇𝑚𝑎𝑥−𝑎𝑙𝑙−𝑇𝑚𝑎𝑥−𝑟𝑒𝑐 )∗𝑛 ]∗100𝐶𝐼𝑁𝐺 ,𝐿𝑂=[1−∑ (𝑇𝑚𝑖𝑛−𝑟𝑒𝑐−𝑇𝑁𝐺 , 𝑥 )𝑇 𝑁𝐺 ,𝑥<𝑇𝑚𝑖𝑛− 𝑟𝑒𝑐
(𝑇𝑚𝑖𝑛−𝑟𝑒𝑐−𝑇𝑚𝑖𝑛−𝑎𝑙𝑙 )∗𝑛 ]∗100
30.09.2013 9EuroEcoDC Workshop - Karlsruhe
Metrics at node-group, rack and DC level
• Imbalance of temperature of CPU
– ImNG,temp =0 means all of nodes works at the same temperature
New metrics proposed
30.09.2013 10EuroEcoDC Workshop - Karlsruhe
Description of experiment
• Prototype server RECS from Christmann Company
• RECS: high density multinode computer of 18 single server nodes withing one Rack Unit
• CPU: Intel Core i7-3615QE CPU @ 2.30GHz, CPU Cache: 6144 KB, RAM: 16 GB
• Load OpenSSL Benchmark
30.09.2013 11EuroEcoDC Workshop - Karlsruhe
Description of experiment
• 6 configuration1. Idle 2. Full3. Left 4. Right
5. Inlet 6. Outlet
30.09.2013 12EuroEcoDC Workshop - Karlsruhe
Check Imbalance of Temperature
Unexpected imbalance !
30.09.2013 13EuroEcoDC Workshop - Karlsruhe
Check Imbalance of Temperature
• Analysis: – Failure of one fan at right side ! – Imbalance was higher when load was
placed on right side instead of left side
• Metric recalculated assuming CPU temperature of the node with failed fan as average of other nodes with similar load
30.09.2013 14EuroEcoDC Workshop - Karlsruhe
Check Imbalance of Temperature
Balanced!
“Inlet” configuration: temperature of loaded nodes affects temperature of
idle nodes
30.09.2013 15EuroEcoDC Workshop - Karlsruhe
Further steps: other metrics to test
• Idea:heat-aware + useful work + energy
• Other metrics that will be deeply analysed:1. Relation Imbalance of temperature vs
Temperature or Heat-Dissipated2. Productivity (Useful work / Energy)3. PUE Scalability4. FVER
30.09.2013 16EuroEcoDC Workshop - Karlsruhe
Further steps: other metrics to test
• PUE Scalability
Pow
er T
otal
Power IT
mPUE=3.0
mPUE=2.0
mPUE=1.5
mPUE=1.0
Source: The Green Grid. WP#49
30.09.2013 17EuroEcoDC Workshop - Karlsruhe
Further steps: other metrics to test
• PUE Scalability
0
500
1000
1500
2000
2500
3000
3500
4000
4500
0 200 400 600 800 1000 1200 1400 1600
Power_total(i) (kW)
Ideal ScalabilityPUE=1.0
Goal ScalabilityPUE=1.67
ProportionalScalabilitymeanPUE=2.5
Actual Scalability
Source: The Green Grid. WP#49
30.09.2013 18
Further steps: other metrics to test• FVER – Fixed to variable energy ratio• Source: BSC• How much energy produces useful work
and how much could be removed• E_fixed energy when useful work = 0• During flat operation DC can consume up to
80 % of peak power!
1st Review, 30.10.2012, Brussels
𝐹𝑉𝐸𝑅𝐷𝐶=1+𝐸𝐷𝐶 , 𝑓𝑖𝑥𝑒𝑑 [ h𝑊 ]𝐸𝐷𝐶 ,𝑣𝑎𝑟𝑖𝑎𝑏𝑙𝑒 [ h𝑊 ]
=[∅ ]𝐹𝑉𝐸𝑅𝐼𝑇=1+𝐸 𝐼𝑇 , 𝑓𝑖𝑥𝑒𝑑[ h𝑊 ]𝐸 𝐼𝑇 ,𝑣𝑎𝑟𝑖𝑎𝑏𝑙𝑒 [ h𝑊 ]
=[∅ ]
30.09.2013 19EuroEcoDC Workshop - Karlsruhe
Conclusions • Imbalance of temperature permits to detect
failure of IT equipment.• Complementarity between Imbalance of
temperatures and Node-Group-Cooling-Index• Analysis of several metrics together:
– Imbalance of Temperature– Power Usage (Power/Max Power rated)– Productivity (Useful work/Energy)– FVER– PUE Scalability
will allow improve aware about cooling requirements and the possibility of reducing it.
30.09.2013 20
Conclusions• Relation between – power, – cooling requirements, – resource-usage, and – workload management
will be identified to disclose the appropriate strategies to improve the energy efficiency
• First results on tests of the first prototype have been collected. More experiments will be carried out to validate the proposed metrics
EuroEcoDC Workshop - Karlsruhe
30.09.2013
Questions?Comments?
EuroEcoDC Workshop - Karlsruhe 21