3. PUIL PP BARU 2008

download 3. PUIL PP BARU 2008

of 59

Transcript of 3. PUIL PP BARU 2008

  • 5/20/2018 3. PUIL PP BARU 2008

    1/59

    INSTALASI LISTRIKBERDASARKAN PUIL 2000

    OLEH

    IR. H.M. MASGUNARTO BUDIMAN M.SC.

    DISAMPAIKAN PADA ACARA PEMBEKALAN DALAM RANGKA

    UJI KOMPETENSI TENAGA AHLI KONSTRUKSI INSTALASI KETENAGALISTRIKAN

    DISELENGGARAKAN OLEH

    ASOSIASI PROFESIONALIS ELEKTRIKAL-MEKANIKAL INDONESIA (APEI)

    JAKARTA 18=21 APRIL 2013

  • 5/20/2018 3. PUIL PP BARU 2008

    2/59

    PUIL 2000 - PERSYARATAN UNTUKINSTALASI LISTRIK

    ISI BUKU PUIL (SNI 04-0225-2000):

    BAGIAN 1. PENDAHULUAN

    BAGIAN 2. PERSYARATAN DASAR BAGIAN 3. PROTEKSI UNTUK KESELAMATAN

    BAGIAN 4. PERANCANGAN INSTALASI LISTRIK

    BAGIAN 5. PERLENGKAPAN LISTRIK

    BAGIAN 6. PERLENGKAPAN HUBUNG BAGI DAN

    KENDALI (PHB) SERTA KOMPONENNYA

    BAGIAN 7. PENGHANTAR DAN PEMASANGANNYA

    BAGIAN 8. KETENTUAN UNTUK BERBAGAI RUANG

    DAN INSTALASI KHUSUS

    BAGIAN 9. PENGUSAHAAN INSTALASI LISTRIK

  • 5/20/2018 3. PUIL PP BARU 2008

    3/59

    MAKSUD DAN TUJUAN PUIL

    AGAR TERWUJUD:

    PENGUSAHAAN INSTALASI LISTRIK

    TERSELENGGARA DENGAN BAIK

    KESELAMATAN MANUSIA DARI BAHAYA KEJUT

    LISTRIK

    KEAMANAN INSTALASI LISTRIK BESERTA

    PERLENGKAPANNYA

    KEAMANAN GEDUNG SERTA ISINYA DARI

    KEBAKARAN AKIBAT LISTRIK, DAN

    PERLINDUNGAN LINGKUNGAN.

  • 5/20/2018 3. PUIL PP BARU 2008

    4/59

    RUANG LINGKUP PUIL

    BERLAKU UNTUK SEMUA PENGUSAHAANINSTALASI LISTRIK TEGANGAN RENDAH ARUS

    BOLAK-BALIK SAMPAI DENGAN 1000 V, ARUSSEARAH 1500 V DAN TEGANGAN MENENGAHSAMPAI DENGAN 35 KV DALAM BANGUNAN DANSEKITARNYA

    UNTUK PERANCANGAN, PEMASANGAN,PEMERIKSAAN DAN PENGUJIAN, PELAYANAN,PEMELIHARAAN MAUPUN PENGAWASANNYA

  • 5/20/2018 3. PUIL PP BARU 2008

    5/59

    PUIL TIDAK BERLAKU UNTUK

    BAGIAN INSTALASI LISTRIK DENGAN TEGANGAN RENDAH YANGHANYA DIGUNAKAN UNTUK MENYALURKAN BERITA DAN ISYARAT;

    BAGIAN INSTALASI LISTRIK YANG DIGUNAKAN UNTUKKEPERLUAN TELEKOMUNIKASI DAN PELAYANAN KERETA RELLISTRIK;

    INSTALASI LISTRIK DALAM KAPAL LAUT, KAPAL TERBANG,KERETA REL LISTRIK, DAN KENDARAAN LAIN YANG DIGERAKKANSECARA MEKANIS;

    INSTALASI LISTRIK DI BAWAH TANAH DALAM TAMBANG;

    INSTALASI LISTRIK DENGAN TEGANGAN RENDAH YANG TIDAKMELEBIHI 25 V DAN DAYANYA TIDAK MELEBIHI 100 W.

  • 5/20/2018 3. PUIL PP BARU 2008

    6/59

    ACUAN DAN KETENTUAN TERKAIT

    ACUAN:

    PERATURAN UMUM INSTALASI LISTRIK 1987 DENGAN MEMPERHATIKANSTANDAR IEC, TC 64 ELECTRICAL INSTALLATIONS OF BUILDINGS DAN

    STANDAR INTERNASIONAL LAINNYA YANG BERKAITAN.KETENTUAN YANG TERKAIT YANGHARUS DIPERHATIKAN :

    UNDANG-UNDANG NOMOR 1 TAHUN 1970 TENTANG KESELAMATANKERJA, BESERTA PERATURAN PELAKSANAANNYA;

    UNDANG-UNDANG NOMOR 15 TAHUN 1985 TENTANGKETENAGALISTRIKAN;

    UNDANG-UNDANG NOMOR 23 TAHUN 1997 TENTANG PENGELOLAANLINGKUNGAN HIDUP;

    UNDANG-UNDANG NOMOR 18 TAHUN 1999 TENTANG JASAKONSTRUKSI;

    PP NOMOR 10 TAHUN 1989 TENTANG PENYEDIAAN DAN PEMANFAATANTENAGA LISTRIK;

  • 5/20/2018 3. PUIL PP BARU 2008

    7/59

    KETENTUAN YANG TERKAIT

    (LANJUTAN)

    PP NOMOR 51 TAHUN 1993 TENTANG ANALISA MENGENAI DAMPAKLINGKUNGAN;

    PP NOMOR 25 TAHUN 1995 TENTANG USAHA PENUNJANG TENAGA LISTRIK;

    PERMEN ESDM NOMOR 01.P/40/M.PE/1990 TENTANG INSTALASIKETENAGALISTRIKAN;

    PERMEN ESDM NOMOR 02.P/0322/M.PE/1995 TENTANG STANDARDISASI,SERTIFIKASI DAN AKREDITASI DALAM LINGKUNGAN PERTAMBANGAN DANENERGI;

    PERMEN ESDM NOMOR 103.K/008/M.PE/1994 TENTANG PENGAWASAN ATASPELAKSANAAN RENCANA PENGELOLAAN LINGKUNGAN DAN RENCANAPEMANTAUAN LINGKUNGAN DALAM BIDANG PERTAMBANGAN DAN ENERGI;

    PERMEN ESDM NOMOR 2500.K/40/M.PE/1997 TENTANG USAHA PENUNJANGTENAGA LISTRIK BIDANG KONSULTASI, BIDANG PEMBANGUNAN DANPEMASANGAN DAN BIDANG PEMELIHARAAN PERALATANKETENAGALISTRIKAN;

    PERMEN ESDM NOMOR 198.K/008/M.PE/1998 TENTANG IZIN USAHAKETENAGALISTRIKAN UNTUK KEPENTINGAN SENDIRI;

  • 5/20/2018 3. PUIL PP BARU 2008

    8/59

    PERSYARATAN DASAR

    ISTALASI LISTRIK

    1. PROTEKSI UNTUK KESELAMATAN

    2. PROTEKSI PERLENGKAPAN DAN INSTALASI

    LISTRIK3. PERANCANGAN INSTALASI LISTRIK

    4. PEMILIHAN PERLENGKAPAN LISTRIK

    5. PEMASANGAN DAN VERIFIKASI AWAL

    INSTALASI LISTRIK6. PENGUJIAN INSTALASI LISTRIK

    7. PEMELIHARAAN INSTALASI LISTRIK

  • 5/20/2018 3. PUIL PP BARU 2008

    9/59

    POTENSI BAHAYA LISTRIK

    TEGANGAN SENTUH

    ARUS HUBUNG PENDEK ARUS BEBAN LEBIH

    TEGANGAN TINGGI

    TEGANGAN RENDAH PANAS

  • 5/20/2018 3. PUIL PP BARU 2008

    10/59

    2. Bahaya sentuh tidak langsung(3.5)

    Sentuh pada BKT perlengkapan atau instalasi listrikyang menjadi bertegangan akibat kegagalan isolasi

    Syarat:

    Perlengkapan listrik harus dirancang dan dibuat dengan baik. Bagian aktif harus diisolasi dengan bahan yang tepat

    Instalasi listrik harus dipasang dengan baik.

  • 5/20/2018 3. PUIL PP BARU 2008

    11/59

    PROTEKSI SENTUH TIDAK

    LANGSUNG

    Sentuh tidak langsung(3.5.2.1)

    a. Proteksi dengan pemutus suplai secara otomatisb. Proteksi dengan penggunaan kelas II atau

    dengan isolasi ekivalen

    c. Proteksi dengan lokasi tidak konduktif

    d. Proteksi dengan ikatan penyama potensial lokalbebas bumi

    e. Proteksi dengan separasi listrik

  • 5/20/2018 3. PUIL PP BARU 2008

    12/59

    PROTEKSI UNTUK KESELAMATAN

    PROTEKSI DARI SENTUH LANGSUNG

    MANUSIA DAN TERNAK HARUS DIHINDARKAN/ DISELAMATKAN

    DARI BAHAYA YANG BISA TIMBUL KARENA SENTUHAN DENGANBAGIAN AKTIF INSTALASI (SENTUH LANGSUNG) DENGAN SALAHSATU CARA DI BAWAH INI:

    MENCEGAH MENGALIRNYA ARUS MELALUI BADAN MANUSIAATAU TERNAK;

    MEMBATASI ARUS YANG DAPAT MENGALIR MELALUI BADANSAMPAI SUATU NILAI YANG LEBIH KECIL DARI ARUS KEJUT.

  • 5/20/2018 3. PUIL PP BARU 2008

    13/59

    CARA PROTEKSI

    RUMAH PERALATAN

    IP UNTUK PERALATAN DENGAN PERINTANG

    DI LUAR JANGKAUAN TANGAN

    RUANG KHUSUS DAN PETUGAS KHUSUSUNTUK LLISTRIK

  • 5/20/2018 3. PUIL PP BARU 2008

    14/59

    1. PROTEKSI UNTUK KESELAMATAN

    (LANJUTAN)

    1.3 PROTEKSI DARI EFEK TERMAL DAN DARI ARUS LEBIH

    INSTALASI LISTRIK HARUS DISUSUN SEDEMIKIAN RUPA SEHINGGA TIDAKADA RISIKO TERSULUTNYA BAHAN YANG MUDAH TERBAKAR KARENATINGGINYA SUHU ATAU BUSUR API LISTRIK. DEMIKIAN PULA TIDAK AKAN

    ADA RISIKO LUKA BAKAR PADA MANUSIA MAUPUN TERNAK SELAMAPERLENGKAPAN LISTRIK BEROPERASI SECARA NORMAL.

    MANUSIA ATAU TERNAK HARUS DIHINDARKAN/DISELAMATKAN DARICEDERA, DAN HARTA BENDA DIAMANKAN DARI KERUSAKAN KARENA SUHUYANG BERLEBIHAN ATAU STRES ELEKTROMEKANIS KARENA ARUS LEBIHYANG SANGAT MUNGKIN TIMBUL PADA PENGHANTAR AKTIF.

    PROTEKSI INI DAPAT DICAPAI DENGAN SALAH SATU CARA DI BAWAH INI:A) PEMUTUSAN SECARA OTOMATIS PADA SAAT TERJADI ARUS

    LEBIH

    B) PEMBATASAN ARUS LEBIH MAKSIMUM SEHINGGA NILAI DAN

    LAMANYA YANG AMAN TIDAK TERLAMPAUI.

  • 5/20/2018 3. PUIL PP BARU 2008

    15/59

    1. PROTEKSI UNTUK KESELAMATAN(LANJUTAN)

    1.4 PROTEKSI DARI ARUS GANGGUAN DAN DARITEGANGAN LEBIH

    PENGHANTAR, SELAIN PENGHANTAR AKTIF, DAN BAGIAN LAINYANG DIMAKSUDKAN UNTUK MENYALURKAN ARUS GANGGUANHARUS MAMPU MENYALURKAN ARUS TERSEBUT TANPAMENIMBULKAN SUHU YANG BERLEBIHAN.

    MANUSIA ATAU TERNAK HARUS DICEGAH DARI CEDERA DAN HARTABENDA HARUS DICEGAH DARI SETIAP EFEK YANG BERBAHAYAAKIBAT ADANYA GANGGUAN ANTARA BAGIAN AKTIF SIRKIT YANG

    DISUPLAI DENGAN TEGANGAN YANG BERBEDA.

    MANUSIA DAN TERNAK HARUS DICEGAH DARI CEDERA DAN HARTABENDA HARUS DICEGAH DARI KERUSAKAN AKIBAT ADANYATEGANGAN YANG BERLEBIHAN YANG MUNGKIN TIMBUL AKIBATSEBAB LAIN (MISALNYA, FENOMENA ATMOSFER ATAU TEGANGANLEBIH PENYAKELARAN).

  • 5/20/2018 3. PUIL PP BARU 2008

    16/59

    2. PROTEKSI PERLENGKAPAN DAN

    INSTALASI LISTRIK

    2.1 PERLENGKAPAN LISTRIK PADA SETIAP PERLENGKAPAN LISTRIK HARUS ADA PAPAN

    NAMA YANG TIDAK MUDAH LEPAS DAN PADANYATERCANTUM DENGAN JELAS DAN DAN TIDAK MUDAHTERHAPUS:

    1. NAMA PEMBUAT DAN ATAU MEREK DAGANG;

    2. LOGO ATAU TANDA STANDAR SNI ATAU STANDAR LAIN

    MISALNYA IEC,JIS,BS,VDEUL

    3. DAYA, TEGANGAN, DAN/ATAU ARUS PENGENAL SERTADATA TEKNIS LAIN SEPERTI DISYARATKAN SNI .

    PERLENGKAPAN LISTRIK HANYA BOLEH DIPASANG PADAINSTALASI JIKA MEMENUHI KETENTUAN DALAM PUIL 2000DAN/ATAU STANDAR YANG BERLAKU.

    SETIAP PERLENGKAPAN LISTRIK TIDAK BOLEH DIBEBANI

    MELEBIHI KEMAMPUANNYA.

  • 5/20/2018 3. PUIL PP BARU 2008

    17/59

    2. PROTEKSI PERLENGKAPAN DAN

    INSTALASI LISTRIK (LANJUTAN)

    2.2 INSTALASI LISTRIK

    INSTALASI YANG BARU DIPASANG ATAU MENGALAMI

    PERUBAHAN HARUS DIPERIKSA DAN DIUJI DULU SESUAIDENGAN KETENTUAN MENGENAI :

    1. RESISTANS ISOLASI (3.20);

    2. PENGUJIAN SISTEM PROTEKSI (3.21);

    3. PEMERIKSAAN DAN PENGUJIAN INSTALASI LISTRIK (9.5.6).

    INSTALASI LISTRIK YANG SUDAH MEMENUHI SEMUAKETENTUAN TERSEBUT DAPAT DIOPERASIKAN SETELAHMENDAPAT IZIN ATAU PENGESAHAN DARI INSTANSI YANGBERWENANG (KONSUIL DAN LEMBAGA INSPEKSI) DENGANSYARAT TIDAK BOLEH DIBEBANI MELEBIHI KEMAMPUANNYA.

  • 5/20/2018 3. PUIL PP BARU 2008

    18/59

    1. Sistem TT atau Pembumian Pengaman (PP)

    Tujuan pembumian :

    Bila terjadi arus bocor atau hubung singkat, arusakan tersalur ke bumi yang akan menyebabkan

    meningkatnya arus sehingga pengaman akan

    terputus secara otomatik

    Fasa tunggal 2 kawat AktifNol/Netral

  • 5/20/2018 3. PUIL PP BARU 2008

    19/59

    2. Sistem IT atau Hantaran pengaman (HP)Tujuan pembumian :

    Bila terjadi arus bacor atau hubung singkat, arus

    akan tersalur ke bumi melalui penghantarpengaman sehingga arus meningkat dan

    pengaman akan terputus secara otomatik

    Fasa tunggal 3 kawat Penghantar AktifPenghantar Nol/Netral

    Hantaran pengaman

  • 5/20/2018 3. PUIL PP BARU 2008

    20/59

    3. Sistem TN atau

    Pembumian Netral Pengaman (PNP)

    Nol &Ground

    dihubungkan

    Fasa tunggal 3 kawat

  • 5/20/2018 3. PUIL PP BARU 2008

    21/59

    SISTIM PROTEKSI

    Pembumian

    Ikatan penyama potensial

    Arester

    L1

    L2

    L3

    N

    PEN

    GPAS

    Pengaman lebur

    L1 L2 L3PEN

    Penempatan arester untuk sistem TT

  • 5/20/2018 3. PUIL PP BARU 2008

    22/59

    SISTIM PROTEKSI

    Proteksi dengan separasi listrik

    Adalah suatu tindakan proteksi dengan memisahkan sirkit

    perlengkapan listrik dari jaringan sumber denganmenggunakan transformator pemisah atau motor generator

    (3.11)

    Sistim ini hanya akan efektif selama dalam sirkit sekunder

    tidak terjadi gangguan bumi.

    Sirkit sekunder adalah sirkit sekunder dari transformatorpemisah atau sirkit generator dari motor generator.

    Tegangan jaringan yang diizinkan max. 500 volt.

  • 5/20/2018 3. PUIL PP BARU 2008

    23/59

    Rekom : a. V x l kwt 100.000b. L kwt 500 m

    Transformator pemisah dengan pendek ke bumi pada sirkit

    sekunder dan hubung pendek ke BKT perlengkapan listrik

  • 5/20/2018 3. PUIL PP BARU 2008

    24/59

    PROTEKSI BAHAYA LISTRIK

    1. Bahaya sentuh langsung

    Sentuh langsung pada bagian aktif perlengkapan atauinstalasi listrik(3.4)

    Cara Mengatasia. Proteksi dengan isolasi bagian aktif(3.4.1)

    b. Proteksi dengan penghalang atau selungkup(3.4.2)

    c. Proteksi dengan rintangan(3.4.3)

    d. Proteksi dengan penempatan diluar jangkauan(3.4.4)

    e. Proteksi tambahan dengan gawai pengaman arus sisa(3.4.5)

  • 5/20/2018 3. PUIL PP BARU 2008

    25/59

    3. PERANCANGAN INSTALASI LISTRIK

    HAL-HAL YANG PERLU DIPERHATIKAN:

    FAKTOR YANG HARUS DIPERHATIKAN UNTUK MENJAMINKESELAMATAN MANUSIA DAN KESELAMATAN HARTA BENDA SERTA

    BERFUNGSINYA INSTALASI LISTRIK DENGAN BAIK KARAKTERISTIK SUPLAI

    MACAM KEBUTUHAN AKAN LISTRIK

    SUPLAI DARURAT

    KONDISI LINGKUNGAN

    LUAS PENAMPANG PENGHANTAR

    JENIS PENGAWATAN DAN CARA PEMASANGAN GAWAI PROTEKSI

    KENDALI DARURAT

    GAWAI PEMISAH

    PENCEGAHAN PENGARUH TIMBAL BALIK

    KETERJANGKAUAN PERLENGKAPAN LISTRIK

    RUANG KERJA DI SEKITAR`PERLENGKAPAN LISTRIK

  • 5/20/2018 3. PUIL PP BARU 2008

    26/59

    PENGHANTAR,PEMASANGAN

    DAN PEMBEBANANNYA

    FUNGSI

    JENIS DAN PENGGUNAAN KONSTRUKSI DAN BAHAN

    PERSYARATAN

    KETENTUAN WARNA PENYAMBUNGAN DAN PEMASANGAN

    PEMBEBANAN

  • 5/20/2018 3. PUIL PP BARU 2008

    27/59

    SIRKIT MOTOR

    Sirkit penghantar motor.

    2.1.1. KHA sirkit motor tunggal minimal 125 %

    arus pengenal beban penuh motor.

    KHA = 125 % x In

    2.1.2. Sirkit penghantar motor yang mensuplai 2

    motor atau lebih, minimal jumlah arus beban

    penuh semua motor + 25 % arus beban penuhmotor terbesar ( arus beban tertinggi).

    KHA = I n + 25 % x I n terbesar.

    2.1.3. Untuk motor dengan daur kerja intermitten,

    pembebanan singkat, tidak bekerja bersama-

    sama, KHA penghantar sirkit dapat minimal

  • 5/20/2018 3. PUIL PP BARU 2008

    28/59

    PROTEKSI BEBAN LEBIH

    Proteksi beban lebih sirkit motor.

    2.2.1

    Jika gawai proteksi bukan pengaman lebur

    (misalnya relai, Bimetal) dipasang pada :

    Satu fasa : pada penghantar fasa.

    Tiga fasa : cukup pada penghantar fasa 1

    dan 2, atau 2 dan 3, atau 1 dan 3.

    2.2.5. Proteksi beban lebih harus dilengkapi

    dengan proteksi arus hubung pendek.

  • 5/20/2018 3. PUIL PP BARU 2008

    29/59

    SETELAN GAWAI PENGAMAN MOTOR

    Setelan beberapa motor tidak boleh melebihi nilai terbesar

    berdasarkan tabel 5.5.2 untuk masing- masing motor

    ditambahjum lah arus beban penuh motor lain dalamsirk i t tersebut.

    Setelan gawai = setelan gawai proteksi terbesar + In motor

    lain.

    x

    x

    x

    M1

    M2

    M3

    IN3

    IN2

    IN1

    IG2 = IG3 + IN1 + In2

    IG3

    IG2x

  • 5/20/2018 3. PUIL PP BARU 2008

    30/59

    Arus gawai proteksi hubung singkat sirkitcabang yang mensuplai beberapa motor :

    Arus gawai proteksi menurut tabel 5.5.2 + Jumlah

    arus beban penuh semua motor yang di pasok

    sirkit cabang tersebut.

    x

    Sirkit cabang

    x

    M MM

    BA C

    Gawai proteksi 218 A

    85A + 52,5A +67,5A = 181A

    125% x 54A

    67,5A

    125% x 42A

    52,5A

    125% x 68A

    85A

    Sirkit

    Akhir

    motor

    102A108A

    Motor sinkron

    dengan autotrafoIN : 54A

    Motor cincin

    IN : 68A

    Motort sangkar

    IN : 42A

    KHA Penghantar

    Sirkit A

    125% x 42A = 52,5 A

    Sirkit B

    125% x 54,5A

    Sirkit C125% x 68 = 85A

    Kuat hantar arus sirkit cabang

    125% x Iu motor terbesar + In

    masing-masing motor lain

    = 125 % x 68A+42A+54 = 181A

  • 5/20/2018 3. PUIL PP BARU 2008

    31/59

    x x

    M MM

    Gawai proteksi

    = 108A + 42A + 68A= 218 A

    1,25 x 68

    = 85A

    1,25 x 54

    = 67,5A

    1,25 x 42

    = 52,5A

    2,5 x 54A

    =108A

    Motor sinkron

    dengan autotrafo

    IN : 54A

    Motor cincin

    IN : 68A

    Motort sangkar

    IN : 42A

    KHA

    x 1,5 x 68 =102A Gawa Proteksi2,5 x 42

    =105A

    x

    KHA =

    85A+42+54

    =181A

    x

    M

    Motor cincin

    68A

    KHA =

    1,25 x 68 = 85A

    Sirkit Cabang

    Sirkit Akhir

    Sirkit UtamaxGawai proteksi

    218A+68A=286A

    KHA = 181+68=249A

    1,5 x 68 = 102A

  • 5/20/2018 3. PUIL PP BARU 2008

    32/59

    PERLENGKAPAN HUBUNG BAGI

    FUNGSI

    JENIS SIRKIT MASUK DAN KELUAR

    KOMPONEN

    RUANG PELAYANAN PENANDAAN

  • 5/20/2018 3. PUIL PP BARU 2008

    33/59

    3. PERANCANGAN INSTALASI LISTRIK

    KONDISI LINGKUNGANDALAM MENETAPKAN KONDISI LINGKUNGAN PENGGUNAANPERLENGKAPAN INSTALASI, PERLU DIPERHITUNGKAN BEBERAPA FAKTORDAN PARAMETER LINGKUNGAN TERKAIT, DAN DIPILIH TINGKAT

    KEPARAHAN AKIBAT PARAMETER LINGKUNGAN TERSEBUT. FAKTOR DANPARAMETER LINGKUNGAN TERSEBUT, ANTARA LAIN :

    KONDISI IKLIM: DINGIN/PANAS, KELEMBABAN, TEKANAN, GERAKAN MEDIASEKELILING PENGUAPAN, RADIASI DAN AIR SELAIN DARI HUJAN.

    KONDISI BIOLOGIS: FLORA DAN FAUNA SEPERTI JAMUR DAN RAYAP.

    BAHAN KIMIA AKTIF: GARAM, SULFUR DIOKSIDA, HIDROGEN SULFIT,NITROGEN OKSIDA, OZON, AMONIA, KLOR, HIDROGEN KLORIDA, HIDROGENFLOR DAN HIDROKARBON ORGANIK.

    BAHAN MEKANIS AKTIF: PASIR, DEBU, DEBU MELAYANG, SEDIMEN DEBU,LUMPUR DAN JELAGA.

    CAIRAN PENGOTOR: BERBAGAI MINYAK, CAIRAN PENDINGIN, GEMUK,BAHAN BAKAR DAN AIR BATERAI.

    KONDISI MEKANIS: GETARAN, JATUH BEBAS, BENTURAN, GERAKANBERPUTAR, DEVIASI SUDUT, PERCEPATAN, BEBAN STATIS DAN ROBOH.

    GANGGUAN LISTRIK DAN ELEKTROMAGNET: MEDAN MAGNET, MEDAN

    LISTRIK, HARMONIK, TEGANGAN SINYAL, VARIASI TEGANGAN DANFREKUENSI, DAN TEGANGAN INDUKSI DAN TRANSIEN.

  • 5/20/2018 3. PUIL PP BARU 2008

    34/59

    3. PEMASANGAN INSTALASI LISTRIK

    JENIS PENGAWATAN DAN CARA PEMASANGAN

    PEMILIHAN JENIS PENGAWATAN DAN CARA PEMASANGANBERGANTUNG PADA:

    SIFAT LOKASI; SIFAT DINDING ATAU BAGIAN LAIN DARI BANGUNAN YANG

    MENYANGGA PENGAWATAN;

    DAPAT TERJANGKAUNYA PENGAWATAN OLEH MANUSIA ATAUTERNAK;

    TEGANGAN A.L. MENENYUKAN DIMENSI (CLEARANCE);

    STRES ELEKTROMEKANIS YANG MUNGKIN TERJADI KARENAHUBUNG-PENDEK;

    STRES LAIN YANG MUNGKIN DIALAMI OLEH PENGAWATAN ITUSELAMA PEMASANGAN INSTALASI LISTRIK ATAU WAKTUPENGOPERASIAN.

  • 5/20/2018 3. PUIL PP BARU 2008

    35/59

    3. GAWAI PROTEKSI

    KARAKTERISTIK GAWAI PROTEKSI HARUS

    DITENTUKAN BERDASARKAN FUNGSINYA,YAITU PROTEKSI DARI EFEK:

    ARUS LEBIH (BEBAN LEBIH, HUBUNG PENDEK);

    ARUS GANGGUAN BUMI;

    TEGANGAN LEBIH; TEGANGAN KURANG ATAU TAK BERTEGANGAN

    .

  • 5/20/2018 3. PUIL PP BARU 2008

    36/59

    PERALATAN PENYAMBUNG

    PEMUTUS

    PEMISAH (DS)

    UNTUK MENGAMANKAN MANUSIASAKLAR BEBAN

    UNTUK PENGENDALIAN

    PEMUTUS SIRKIT

    UNTUK MENGAMANKAN

    INSTALASI/PERALATAN

  • 5/20/2018 3. PUIL PP BARU 2008

    37/59

    4. PEMILIHAN

    PERLENGKAPAN LISTRIK

    1. UMUM

    SETIAP BAGIAN PERLENGKAPAN LISTRIK YANG DIGUNAKAN DALAMINSTALASI LISTRIK HARUS MEMENUHI PUIL 2000 DAN/ATAU STANDAR

    YANG BERLAKU.

    - BAIK, TIDAK CACAT DAN BERFUNGSI DENGAN BAIK

    - BAIK, SESUAI DENGAN STANDAR YANG DITETAPKAN (ADA TANDA

    STANDAR)

    - HARUS DIPILIH SESUAI DENGAN PEMBEBANANNYA

    2. KARAKTERISTIK

    SETIAP BAGIAN PERLENGKAPAN LISTRIK YANG DIPILIH HARUS

    MEMPUNYAI KARAKTERISTIK YANG SESUAI DENGAN NILAI DANKONDISI YANG MENDASARI PERANCANGAN INSTALASI LISTRIK DANKHUSUSNYA HARUS MEMENUHI PERSYARATAN DALAM BUTIRBERIKUTNYA.

    - TEGANGAN

    - ARUS

    - FREKUENSI

    - DAYA

  • 5/20/2018 3. PUIL PP BARU 2008

    38/59

    4. PEMILIHAN

    PERLENGKAPAN LISTRIK

    3. KONDISI INSTALASI DAN PENCEGAHAN PENGARUH YANG

    MERUSAK

    DALAM MEMILIH PERLENGKAPAN INSTALASI LISTRIK, TERMASUK JUGAMENENTUKAN JENIS, UKURAN, TEGANGAN DAN KEMAMPUANNYA, HARUSDIPERHATIKAN HAL BERIKUT :

    KESESUAIAN DENGAN MAKSUD PEMASANGAN DAN PENGGUNAANNYA;

    KEKUATAN DAN KEAWETANNYA, TERMASUK BAGIAN YANG DIMAKSUDKANUNTUK MELINDUNGI PERLENGKAPAN LAIN;

    KEADAAN DAN RESISTANS ISOLASINYA;

    PENGARUH SUHU, BAIK PADA KEADAAN NORMAL MAUPUN TIDAK NORMAL;

    PENGARUH API;

    PENGARUH KELEMBABAN

  • 5/20/2018 3. PUIL PP BARU 2008

    39/59

    4. PEMILIHAN

    PERLENGKAPAN LISTRIK

    4. PENCEGAHAN DARI EFEK YANG MERUSAK

    SEMUA PERLENGKAPAN LISTRIK HARUS DIPILIH SEHINGGATIDAK MEMPENGARUHI DAN TIDAK MENYEBABKAN EFEKMERUSAK PADA PERLENGKAPAN LAIN ATAU MENGGANGGUSUPLAI SELAMA PELAYANAN NORMAL, TERMASUK OPERASIPENYAKELARAN.

    DALAM KONTEKS INI, FAKTOR-FAKTOR YANG MUNGKINBERPENGARUH, TERMASUK ANTARA LAIN :

    A) FAKTOR DAYA;B) ARUS KEJUT AWAL (INRUSH CURRENT);

    C) BEBAN TAK SEIMBANG;

    D) HARMONIK.

  • 5/20/2018 3. PUIL PP BARU 2008

    40/59

    4. PEMILIHAN

    PERLENGKAPAN LISTRIK

    5. GAWAI PROTEKSI

    PEMUTUS SIRKIT HARUS MEMPUNYAI

    KAPASITAS PEMUTUS SEKURANG-KURANGNYASAMA DENGAN HASIL PERKALIAN TEGANGANNOMINAL DAN ARUS PUTUS.

    GAWAI PROTEKSI ARUS-LEBIH DANKARAKTERISTIK SIRKIT YANG DIAMANKAN,HARUS DIPILIH DAN DIKOORDINASIKANSEHINGGA KERUSAKAN KOMPONEN LISTRIKSIRKIT DAPAT DICEGAH ATAU DIKURANGI.

  • 5/20/2018 3. PUIL PP BARU 2008

    41/59

    5. PEMASANGAN DAN VERIFIKASI

    AWAL INSTALASI LISTRIK

    1 UMUM

    INSTALASI LISTRIK HARUS DIPASANG SEHINGGA MENGHASILKAN KERJA YANGBAIK, DIKERJAKAN OLEH PERSONEL YANG BERKUALITAS SESUAI DENGAN

    BIDANGNYA, DAN MENGGUNAKAN BAHAN YANG TEPAT. PENGAWATAN HARUS DILAKUKAN SEHINGGA BEBAS DARI HUBUNG PENDEK

    DAN HUBUNG BUMI.

    PERLENGKAPAN LISTRIK YANG DIPASANG HARUS BERMUTU LAIK PASANGDAN/ATAU MEMENUHI PERSYARATAN STANDAR (LIHAT 2.2.1.2).

    KARAKTERISTIK TERTENTU DARI PERLENGKAPAN LISTRIK SEPERTI TERSEBUTDALAM 2.4.2, TIDAK BOLEH MEMBURUK DALAM PROSES PEMASANGANNYA.

    PERLENGKAPAN LISTRIK HARUS DIRAWAT DENGAN BAIK UNTUK MENCEGAHKEMUNGKINAN MENURUNNYA MUTU PERLENGKAPAN LISTRIK AKIBAT PROSESTERTENTU DALAM MASA PENYIMPANAN, PERSIAPAN, PELAKSANAANPEKERJAAN DAN MASA PENGGUNAAN.

  • 5/20/2018 3. PUIL PP BARU 2008

    42/59

    5. PEMASANGAN DAN VERIFIKASI

    AWAL INSTALASI LISTRIK (LANJUTAN)

    2. PENANDAAN DAN POLARITAS

    SETIAP SIRKIT SUPLAI, REL ATAU SIRKIT CABANG PADA TITIKSUMBERNYA HARUS DITANDAI DENGAN JELAS MAKSUDPENGGUNAANNYA DENGAN TANDA YANG CUKUP AWET TERHADAPPENGARUH CUACA SEKITARNYA. PENANDAAN YANG DEMIKIAN ITUDIPERLUKAN PULA BAGI SETIAP SARANA PEMUTUS UNTUK MOTORDAN PERANTI LISTRIK. PENANDAAN TIDAK DIPERLUKAN APABILAMAKSUD PENGGUNAANNYA SUDAH JELAS DARI PENEMPATANNYA.

    PENGHANTAR PROTEKSI DAN PENGHANTAR NETRAL HARUS BISADIIDENTIFIKASI, PALING TIDAK PADA TERMINALNYA, DENGAN WARNAATAU CARA LAIN. PENGHANTAR-PENGHANTAR BERBENTUK KAWATATAU KABEL YANG FLEKSIBEL, HARUS BISA DIIDENTIFIKASI DENGANWARNA ATAU CARA LAIN SEPANJANG PENGHANTARNYA.

  • 5/20/2018 3. PUIL PP BARU 2008

    43/59

    5. PEMASANGAN DAN VERIFIKASI

    AWAL INSTALASI LISTRIK (LANJUTAN)

    SAKELAR HARUS DIPASANG SEHINGGA :

    A) BAGIAN YANG DAPAT BERGERAK, TIDAK BERTEGANGAN PADA WAKTU

    SAKELAR DALAM KEADAAN TERBUKA ATAU TIDAK MENGHUBUNG;

    B) KEDUDUKAN KONTAK SEMUA TUAS SAKELAR DAN TOMBOL SAKELARDALAM SATU INSTALASI HARUS SERAGAM; MISALNYA AKAN

    MENGHUBUNG JIKA TUASNYA DIDORONG KE ATAS ATAU TOMBOLNYA

    DITEKAN.

    FITING LAMPU JENIS EDISON HARUS DIPASANG DENGAN CARAMENGHUBUNGKAN KONTAK DASARNYA PADA PENGHANTAR FASE, DANKONTAK LUARNYA PADA PENGHANTAR NETRAL (LIHAT JUGA BAB 5).

    PENGAMAN LEBUR JENIS D (DIASED) HARUS DIPASANG DENGAN KONTAKLUARNYA MENGHUBUNG PADA PENGHANTAR YANG MENUJU KE BEBAN.

    KOTAK-KONTAK FASE TUNGGAL, BAIK YANG BERKUTUB DUA MAUPUNTIGA HARUS DIPASANG SEHINGGA KUTUB NETRALNYA ADA DI SEBELAHKANAN ATAU DI SEBELAH BAWAH KUTUB TEGANGAN.

  • 5/20/2018 3. PUIL PP BARU 2008

    44/59

    5. PEMASANGAN DAN VERIFIKASI

    AWAL INSTALASI LISTRIK (LANJUTAN)

    3. PEMASANGAN DAN PENEMPATAN PERLENGKAPAN LISTRIK

    JIKA TIDAK ADA KETENTUAN LAIN, PERLENGKAPAN LISTRIKTIDAK BOLEH DITEMPATKAN DI :

    DAERAH LEMBAB ATAU BASAH; RUANG YANG MENGANDUNG GAS, UAP, DEBU, CAIRAN, ATAU

    ZAT LAIN YANG DAPAT MERUSAKKAN PERLENGKAPAN LISTRIK;

    RUANG YANG SUHUNYA MELAMPAUI BATAS NORMAL (LIHATBAB 8).

    SELAMA MASA PEMBANGUNAN, PERLENGKAPAN LISTRIK YANGHANYA BOLEH DIPASANG DI RUANG KERING HARUS

    DILINDUNGI TERHADAP CUACA UNTUK MENCEGAHPERLENGKAPAN TERSEBUT MENGALAMI KERUSAKAN YANGPERMANEN (LIHAT BAB 8).

    PERLENGKAPAN LISTRIK HARUS DIPASANG DENGAN RAPI DANDENGAN CARA YANG BAIK DAN TEPAT.

  • 5/20/2018 3. PUIL PP BARU 2008

    45/59

    5. PEMASANGAN DAN VERIFIKASI

    AWAL INSTALASI LISTRIK (LANJUTAN)

    4. SAMBUNGAN LISTRIK

    SEMUA SAMBUNGAN LISTRIK HARUS BAIK DAN BEBAS DARI GAYATARIK.

    SAMBUNGAN ANTAR PENGHANTAR DAN ANTARA PENGHANTAR DAN

    PERLENGKAPAN LISTRIK YANG LAIN HARUS DIBUAT SEDEMIKIANSEHINGGA TERJAMIN KONTAK YANG AMAN DAN ANDAL.

    GAWAI PENYAMBUNG SEPERTI TERMINAL TEKAN, PENYAMBUNGPUNTIR TEKAN, ATAU PENYAMBUNG DENGAN SOLDER HARUS SESUAIDENGAN BAHAN PENGHANTAR YANG DISAMBUNGNYA DAN HARUSDIPASANG DENGAN BAIK (LIHAT JUGA 2.5.4.4).

    DUA PENGHANTAR LOGAM YANG TIDAK SEJENIS (SEPERTI TEMBAGADAN ALUMINIUM ATAU TEMBAGA BERLAPIS ALUMINIUM) TIDAKBOLEH DISATUKAN DALAM TERMINAL ATAU PENYAMBUNG PUNTIRKECUALI JIKA ALAT PENYAMBUNG ITU COCOK UNTUK MAKSUD DANKEADAAN PENGGUNAANNYA.

  • 5/20/2018 3. PUIL PP BARU 2008

    46/59

    5. PEMASANGAN DAN VERIFIKASI

    AWAL INSTALASI LISTRIK (LANJUTAN)

    Sambungan penghantar pada terminal harus terjaminkebaikannya dan tidak merusakkan penghantar. Menyambungkabel fleksibel harus menggunakan sambung tekan (termasuk

    jenis sekrup), sambung solder atau sambung puntir. Sepatukabel harus disambungkan dengan mur baut secara baik.

    Sambung puntir harus dilaksanakan dengan:

    a) menggunakan penyambung puntir; atau

    b) cara dilas atau disolder. Sebelum dilas atau disolder,sambungan itu harus dipuntir dahulu agar diperoleh

    sambungan yang baik secara mekanis dan listrik. Bahan yang digunakan seperti solder, fluks, dan pasta harus

    terbuat dari jenis yang tidak berakibat buruk terhadap instalasidan perlengkapan listrik.

  • 5/20/2018 3. PUIL PP BARU 2008

    47/59

    5. PEMASANGAN DAN VERIFIKASI

    AWAL INSTALASI LISTRIK (LANJUTAN)

    5. Pemeriksaan dan pengujian (verifikasi)

    Instalasi listrik harus diuji dan diperiksa sebelum dioperasikan dan/atausetelah mengalami perubahan penting untuk membuktikan bahwa

    pekerjaan pemasangan telah dilaksanakan sebagaimana semestinyasesuai dengan PUIL 2000 dan/atau standar lain yang berlaku.

    Instalasi dalam pabrik atau bengkel, instalasi dengan 100 titik beban ataulebih, dan instalasi dengan daya lebih dari 5 kW, sebaiknya keadaanresistans isolasinya diperiksa secara berkala, dan jika resistans isolasinyatidak memenuhi ketentuan atau terlihat adanya gejala penurunan instalasiitu harus diperbaiki.

    Pengukuran resistans isolasi harus dilakukan dengan gawai khusus yangbaik dan telah ditera.

    Resistans isolasi harus diuji dengan cara seperti dijelaskan dalam 3.20.

    Pada sistem IT harus ada sekurang-kurangnya satu gawai yang dipasangpermanen untuk memantau keadaan isolasi instalasi (gawai monitor isolasi,lihat 3.14.2.2).

  • 5/20/2018 3. PUIL PP BARU 2008

    48/59

    5. PEMASANGAN DAN VERIFIKASI

    AWAL INSTALASI LISTRIK (LANJUTAN)

    6 PEMELIHARAAN

    PEMELIHARAAN INSTALASI LISTRIK MELIPUTI PROGRAMPEMERIKSAAN, PERAWATAN, PERBAIKAN, DAN PENGUJIAN

    ULANG BERDASARKAN PETUNJUK PEMELIHARAAN YANGTELAH DITENTUKAN.

    PEMELIHARAAN TERSEBUT DIMAKSUDKAN AGAR INSTALASISELALU BAIK DAN BERSIH SERTA PENGGUNAAN DANPERBAIKANNYA DENGAN MUDAH DAN AMAN SEHINGGA

    INSTALASI BERFUNGSI DENGAN BAIK SESUAI DENGAN YANGDIHARAPKAN.

    KETENTUAN DASAR

    UNTUK MEMELIHARA DAN MEMPEROLEH INSTALASI SEPERTITERSEBUT PADA 2.6.1.2 HARUS DIIKUTI PETUNJUKPEMELIHARAAN SEPERTI TERTUANG DALAM BAB 9, 9.12.

  • 5/20/2018 3. PUIL PP BARU 2008

    49/59

    6. PEMERIKSAAN DAN PENGUJIAN

    (VERIFIKASI)

    Instalasi listrik harus diuji dan diperiksa sebelumdioperasikan dan/atau setelah mengalami perubahanpenting untuk membuktikan bahwa pekerjaan pemasangan

    telah dilaksanakan sebagaimana semestinya sesuaidengan PUIL 2000 dan/atau standar lain yang berlaku.

    Instalasi dalam pabrik atau bengkel, instalasi dengan 100titik beban atau lebih, dan instalasi dengan daya lebih dari5 kW, sebaiknya keadaan resistans isolasinya diperiksasecara berkala, dan jika resistans isolasinya tidakmemenuhi ketentuan atau terlihat adanya gejala penurunaninstalasi itu harus diperbaiki.

    Pengukuran resistans isolasi harus dilakukan dengangawai khusus yang baik dan telah ditera.

    Resistans isolasi harus diuji dengan cara sepertidijelaskan dalam 3.20.

    Pada sistem IT harus ada sekurang-kurangnya satu gawaiyang dipasang permanen untuk memantau keadaan isolasi

  • 5/20/2018 3. PUIL PP BARU 2008

    50/59

    TUJUANMEMASTIKAN INSTALASI YANG TELAH DIPASANG TELAHMEMENUHI KONTRAK DAN PERATURAN PERUNDANGANYANG BERLAKU (PUIL 2000)

    PELAKSANALEMBAGA INSPEKSI KONSUIL DAN LEMBAGA LAIN YANGDITUNJUK OLEH BADAN YANG BERWENANG

    MATA UJI A.L.:

    PERALATAN DAN PENANDAANTANDA DAN POLARITASTAHANAN ISOLASITEGANGANKONTINUITAS SIRKITSISTEM PROTEKSI

  • 5/20/2018 3. PUIL PP BARU 2008

    51/59

    PENGUJIAN INSTALASI LISTRIK

    INSTALASI LISTRIK YANG TELAH SELESAI DIPASANG,ATAU YANG MENGALAMI PERUBAHAN, HARUS

    DIPERIKSA DAN DIUJI DAHULU SEBELUM DIALIRI LISTRIKSESUAI DENGAN KETENTUAN YANG DITETAPKAN DALAM

    PUIL 2000.

    AGAR INSTALASI LISTRIK DAPAT DIGUNAKAN DENGAN

    BAIK, INSTALASI PERLU DIULANG UJISECARA BERKALA

  • 5/20/2018 3. PUIL PP BARU 2008

    52/59

    PENGUJIAN INSTALASI LISTRIK

    PENGGUNA INSTALASI HARUS MEMPUNYAI DOKUMEN

    BERIKUT:

    DIAGRAM UMUM ATAU DIAGRAM LISTRIK SEDERHANA GAMBAR INSTALASI LISTRIK SESUAI KETENTUAN

    PETUNJUK PENGGUNAAN DAN PEMELIHARAAN

    BERITA ACARA PENGUJIAN MENGENAI HASIL HASIL

    SEMUA PENGUJIAA

  • 5/20/2018 3. PUIL PP BARU 2008

    53/59

    PENGUJIAN INSTALASI LISTRIK

    TUJUAN

    MEMASTIKAN INSTALASI YANG TELAH DIPASANG TELAH

    MEMENUHI KONTRAK DAN PERATURAN PERUNDANGANYANG BERLAKU (PUIL 2000)

    PELAKSANA

    LEMBAGA INSPEKSI KONSUIL DAN LEMBAGA LAIN YANG

    DITUNJUK OLEH BADAN YANG BERWENANG

    (DIAKREDITASI)

    .

  • 5/20/2018 3. PUIL PP BARU 2008

    54/59

    PENGUJIAN INSTALASI LISTRIK

    KETENTUAN:

    1. PERSONIL PELAKSANA PENGUJIAN HARUS KOMPETEN

    DALAM BIDANG PENGUJIAN DAN MEMILIKI SERTIFIKATYANG MASIH BERLAKU

    2. METODE PENGUJIAN HARUS SESUAI STANDAR YANG

    TELAH DITETAPKAN(TELAH DIKALIBRASI

    3. ALAT ATAU PERLENGKAPAN UJI HARUS SESUAI

    KETENTUAN

  • 5/20/2018 3. PUIL PP BARU 2008

    55/59

    PENGUJIAN INSTALASI LISTRIK

    PEMERIKSAAN DAN PENGUJIAN SBB.:

    1. BERBAGAI MACAM TANDA PENGENAL DAN PAPAN

    PERINGATAN2. PERLENGKAPAN LISTRIK YANG DIPASANG

    3. CARA MEMASANG PERLENGKAPAN LISTRIK

    4. POLARITAS

    5. PEMBUMIAN

    6. RESISTAN ISOLASI

    7. KESINAMBUNGAN SIRKIT

    8. FUNGSI PROTEKSI SISTEM INSTALASI

  • 5/20/2018 3. PUIL PP BARU 2008

    56/59

    7. PEMELIHARAAN INSTALASI

    Pemeliharaan instalasi listrik meliputi programpemeriksaan, perawatan, perbaikan, dan

    pengujian ulang berdasarkan petunjukpemeliharaan yang telah ditentukan.

    Pemeliharaan tersebut dimaksudkan agarinstalasi selalu baik dan bersih sertapenggunaan dan perbaikannya dengan mudah

    dan aman sehingga instalasi berfungsi denganbaik sesuai dengan yang diharapkan.

    Untuk memelihara dan memperoleh instalasiyang layak operasi harus diikuti petunjukpemeliharaan seperti tertuang dalam BAB 9, 9.12.

  • 5/20/2018 3. PUIL PP BARU 2008

    57/59

    7. PEMELIHARAAN INSTALASI

    PEMELIHARAAN INSTALASI LISTRIK MELIPUTI

    PROGRAM PEMERIKSAAN, PERAWATAN,

    PERBAIKAN DAN UJI ULANG BERDASARKANPETUNJUK PEMELIHARAAN YANG SUDAH

    DITENTUKAN, AGAR KEADAAN INSTALASI

    SELALU BAIK DAN BERSIH, PENGGUNAANNYA

    AMAN DAN GANGGUAN SERTA KERUSAKANMUDAH DIKETAHUI, DICEGAH ATAU

    DIPERKECIL. TUJUANNYA AGAR INSTALASI

    LISTRIK BERFUNGSI DENGAN BAIK..

  • 5/20/2018 3. PUIL PP BARU 2008

    58/59

    PEMELIHARAAN INSTALASI

    KETENTUAN PEMELIHARAAN A.L.:SELURUH INSTALASI LISTRIK TERMASUK PENGAMAN,

    PELINDUNG DAN LENGKAPANNYA SERTA BANGUNANINSTALASINYA HARUS TERPELIHARA DENGAN BAIK

    KARENA INSTALASI MENGALAMI KEAUSAN, PENUAAN DAN

    KERUSAKAN, SECARA BERKALA HARUS DIPRIKSA DAN

    DIPERBAIKI DAN KOMPONEN YANG RUSAK

    MINYAK ISOLASI CB ATAU TRAFO HARUS DIJAGA AGARKEMAMPUAN ISOLASINYA TIDAK KURANG DARI

    PERSYARATAN YANG TELAH DITETAPKAN.

    KONTAK CB, RELE SECARA BERKALA HRUS DIPERIKSA

    SECARA RUTIN

  • 5/20/2018 3. PUIL PP BARU 2008

    59/59

    emoga