    Control System Topics SLIDE NO-introduction to control systems 3

    - feedback in control systems (click on any line to read the contents)19

    Laplace transforms 41-Transfer Functions and its properties 80

    -Mason's Gain Formula 89

    -Time Domain Analysis and steady state errors 113

    - Concept of BIBO and Routh Harwitz criterion for stability 127

    -State variable Analysis 156

    An introduction to controllers 169

    - Root locus technique 193

    -Frequency Domain Analysis(polar and Bode plot) 206

    -Digital Control Systems 238

    Z - Transforms 261

    1

  • 8/6/2019 3-1 Control System Presentation

    2/361

    D.C. MOTOR SPEED CONTROL 272Compensation 327

    Control system in Biotechnology 350

    2

  • 8/6/2019 3-1 Control System Presentation

    3/361

    INTRODUCTIONTO

    CONTROLSYSTEMSBY

    V DINESH BHARGAV ( 07359 )MECHANICAL ENGINEERING

  • 8/6/2019 3-1 Control System Presentation

    4/361

    The following presentation consists of:What is control system?

    History of the control systems,Introductory concepts and terms,Types of control systems,Comparison between open loop and

    closed loop control systems,Transfer function and its properties,Types of signals and

    Examples.

  • 8/6/2019 3-1 Control System Presentation

    5/361

    WHAT IS CONTROL SYSTEM?

    Control system is an amalgamation orcombination of different physical components relatedor connected together in such a manner to regulate,

    direct , control itself to obtain desired output.In the following slides the terms used in

    control system are explained.

  • 8/6/2019 3-1 Control System Presentation

    6/361

    HISTORY OF CONTROL SYSTEMS:-Historically, the wide practical applications of control

    systems first took place in the process areas likepetroleum processing, etc. Most were developed by thesuccessful realization by the intuitive and experimentallyoriented engineering methods.

    The first known control system was the centrifugal

    governor used for speed control of steam engine inventedbyJames Watt.

    Later, people like Minorsky, Hazen and Nyquistcontributed to the development of the control systems.

    In the year 1922, Minorsky invented automatic

    controller for the ships.In the year 1932, Nyquist developed the criterion forstability of the closed loop systems.

  • 8/6/2019 3-1 Control System Presentation

    7/361

    In the year 1934, Hazen developed the theory of servomechanism, which is a comprehensive mathematical theoryaimed at applications where in there is need to control

    mechanical motions viz., displacement, velocity, acceleration.Around the second world war, the technical needs of militarylike automatic airplane pilots , radar antennae etc, led to thescientific approach in this field.

    In the year 1940, Bode developed bode plot which made

    linear closed loop control systems that satisfied performancecriteria possible.

    In the year 1950, Evans developed root locus. Between 1960to 1980, the control of deterministic and stochastic controlsystems were achieved.

    By the year 1980, research was being done modern controlsystems and digital control systems. From the year 2000,developments were made in the field of micro and nanocontrol systems.

  • 8/6/2019 3-1 Control System Presentation

    8/361

    WATTS CENTRIFUGAL GOVERNOR

  • 8/6/2019 3-1 Control System Presentation

    9/361

    INTRODUCTORY CONCEPTSAND TERMS:-System:

    It is an arrangement or combination of different physicalcomponents that are connected or related together toform an entire unit to achieve a certain objective.

    Control:

    It is the process of regulation, direction and tracking.

    Plant:

    It is the portion of the system which needs to becontrolled, also called as controlled system.

    Process:

    It is a natural or artificial, voluntary progressing,continuous operation or development marked by gradualchanges that succeed one another in relatively fixed wayto obtain a desired result.

  • 8/6/2019 3-1 Control System Presentation

    10/361

    Input:

    It is a signal or excitation that is applied to a control system to get aspecified result. It is of two types:

    Manipulated input: Input which is subject to our control. Disturbance input: These are undesirable effects beyond our control

    generated from surrounding environment.

    Output:

    It is the actual response from the control system due to theapplication of specified input .

    Disturbance:

    It is any signal that has an adverse impact on the system.

    Controller:

    It is the element of the system itself or an external agency whichcontrol the plant or process.

    The words controller, regulator, tracking system are used indifferent situations.

  • 8/6/2019 3-1 Control System Presentation

    11/361

    o Controller:

    The primary role of the controller is the clevermanagement of manipulated variables so as to

    counteract the effects of disturbance for the specifiedoutput.

    o Regulator:

    When the desired value of the controlled outputs is

    more or less fixed and the main problem is to rejectdisturbance effects, the control system is called aregulator.

    o Tracking system:

    In the follow up or tracking system , the controlledoutput is required to follow or track a time varyingcommand input.

  • 8/6/2019 3-1 Control System Presentation

    12/361

    Command input

    Controller

    Process

    Manipulated variable

    Controlled output

    Disturbance

    Block diagram representing various parts of control systems

  • 8/6/2019 3-1 Control System Presentation

    13/361

    TYPES OF CONTROL SYSTEMS:-Based on various parameters, control systems areclassified in different ways as follows:

    1.Open loop and closed loop control systems:

    The systems in which output doesnt have any impact onthe system are called open loop control systems.

    The systems which maintains a prescribed relationshipbetween the output and the reference input by comparingand using the difference as a means of control usingfeedback is closed loop control system.

    Feedback:

    The arrangement of a system by which output is compared

    with a input to reduce error to make system more stable iscalled feedback.

  • 8/6/2019 3-1 Control System Presentation

    14/361

    Controlled

    outputCommand

    inputController Process

    Manipulatedvariable

    DisturbanceOpen loop control systems:

    Commandinput

    Controller Process

    Manipulatedvariable

    Controlledoutput

    Disturbance

    MeasurementFeedback signal

    Closed loop control systems:

    2 Stochastic and deterministic control systems:

  • 8/6/2019 3-1 Control System Presentation

    15/361

    2. Stochastic and deterministic control systems:

    If the output is known from input or externaldisturbances it is known as deterministic controlsystems.

    If the output is unpredictable it is known as stochastic

    control system.3. Linear and non linear control system:

    Linear control system is the one which obeys theprinciple of superposition and homogeneity.

    i.e., f( x+y ) = f( x ) + f( y ) ; f( kx ) = k f( x )

    Non linear control system is the one which does notobey the above principle. Linearization over desiredranges of operation is possible.

    4. Time varying and time invariant control systems:

    When the parameters of the model vary with time it is

    called time varying control system. Eg: mass changesshould be considered in guidance of rocket systems.

    If the parameters of the model doesnt vary with time ,they are called time invariant control systems.

  • 8/6/2019 3-1 Control System Presentation

    16/361

    5. Distributed and lumped parameter models:

    In a distributed parameter models, the variables in a systemare distributed in space and vary with both the spatialcoordinates and time. These models consists of partialdifferential equations w.r.t time and space.

    In lumped parameter models, the matter is assumed to belumped at some discrete points of space. These models usedifferential equations w.r.t time.

    6. SISO and MIMO systems:

    If the system has only single input and single output , it iscalled single input single output system.

    If the system has multiple inputs and outputs, it is calledmultiple input and multiple output system.

    7. According to application:

    the control systems may be electrical, mechanical, thermal,pneumatic, business, managerial control systems.

    COMPARISON BETWEEN OPEN

  • 8/6/2019 3-1 Control System Presentation

    17/361

    COMPARISON BETWEEN OPENLOOP AND CLOSED LOOP CONTROLSYSTEM:-

    Depending on the application of control system, one mayeither use open loop control system or closed loop control

    system. The selection of the control system is also based upon

    sensitivity criteria and economic considerations.In the closed loop control systems , the effects offeedback depend upon the kind of feedback used . There aretwo types namely , positive feedback and negative feedback

    The main differences between open loop and closed control

  • 8/6/2019 3-1 Control System Presentation

    18/361

    Open loop controlsystem

    Closed loop controlsystem

    It is sensitive to external disturbances andinternal variations. It is insensitive to external disturbancesand internal variations.

    To get accurate results ,we need to usehighly expensive components.

    To get accurate results ,we can useinexpensive components also.

    It is used when inputs are known andthere are minimal disturbances.

    It is used where high sensitivity is required.

    Calibration is easy . Recalibration isneeded from time to time.

    Calibration is difficult. Generallyrecalibration is not needed.

    Generally very easy to build. Design of the system is much morecomplicated.

    Generally ,the problem of oscillations isnot witnessed.

    To achieve accurate results , it may tend toovercorrect errors leading to oscillations of

    the system.

    High in manufacturing , maintainance costand power consumption.

    Low in manufacturing , maintainance costand power consumption.

    Stability until unless disturbance is given. Wider range of stability.

    The main differences between open loop and closed controlsystems are:-

  • 8/6/2019 3-1 Control System Presentation

    19/361

    FEEDBACK IN CONTROL SYSTEMSBy

    V.V.Kaushik Sridhar,

    3/4 B.Tech, MME,

    Roll no. 7532

  • 8/6/2019 3-1 Control System Presentation

    20/361

    Based on whether feedback is given to a system ornot, control systems can be classified into:

    1. Open control system (in which no feedback is

    given).2. Closed control system (in which feedback is given)

    Both the above mentioned control systems havetheir own advantages and disadvantages.

  • 8/6/2019 3-1 Control System Presentation

    21/361

    WHAT IS FEEDBACK?

    The arrangement of a system by which output iscompared with the input to make the systemmore stable or error-free is known as feedback.

    Feedback can also be defined as an arrangementin which a part of the output is given back or fed-

    back into the input.

  • 8/6/2019 3-1 Control System Presentation

    22/361

    Based on the definition of feedback given inthe previous slide, one can define open loopand closed loop control systems as given

    below:An open loop system may be defined as one

    that is activated by a single signal i.e. theinput and the output has no effect on the

    system.A closed loop system can be defined as onethat is driven by two signals- one the inputsignal and the other, a signal called thefeedback derived from the output of thesystem.

  • 8/6/2019 3-1 Control System Presentation

    23/361

    BLOCK DIAGRAM OF OPEN ANDCLOSED LOOP CONTROL SYSTEMS

    Closed Loop Control System

  • 8/6/2019 3-1 Control System Presentation

    24/361

    TYPES OF FEEDBACK

    There are two types of feedback namely positivefeedback and negative feedback.

    Negative feedback occurs when the output of asystem acts to oppose changes to the input of thesystem; with the result that the changes areattenuated. If the overall feedback of the system isnegative, then the system will tend to be stable.

    Positive feedback, sometimes referred to as"cumulative causation", is a feedback loop system

    in which the system responds to perturbation inthe same direction as the perturbation.

    AND NEGATIVE FEEDBACK

  • 8/6/2019 3-1 Control System Presentation

    25/361

    AND NEGATIVE FEEDBACKSYSTEMS

    Positive feedback1.Very rarely used.

    2.Transfer function is givenby:

    T.F.= G(s)1-G(s)H(s)

    3. In this feedback, errorcannot be reduced but

    overall gain of thesystem increases.

    Negative feedback1.Very widely used.

    2.Transfer function is givenby:

    T.F.= G(s)1+G(s)H(s)

    3. In this feedback, errorcan be reduced but

    overall gain of thesystem decreases.

  • 8/6/2019 3-1 Control System Presentation

    26/361

    EFFECTS OF FEEDBACK

    Gain is reduced in ve feedback and increased in+ve feedback. Parameter variation is reduced. Sensitivity is increased.

    The above effects of feedback help us to listdown the various advantages and disadvantagesof open loop and closed loop control systems.

    ADVANTAGES OF OPEN LOOP AND

  • 8/6/2019 3-1 Control System Presentation

    27/361

    ADVANTAGES OF OPEN LOOP ANDCLOSED LOOP CS

    Open loop CS1. Easy to design.

    2. Cost factor- moreeconomical.

    3. More stable (nooscillations tilldisturbances).

    4. No error signal.

    5. Easy to maintain.

    Closed loop CS1. More accurate.

    2. Can accomodate anydisturbance.

    3. Wider stability.

    DISADVANTAGES OF OPEN LOOP

  • 8/6/2019 3-1 Control System Presentation

    28/361

    DISADVANTAGES OF OPEN LOOPAND CLOSED LOOP CS

    Open loop CS1. Cannot accommodate

    disturbances.

    2. Poor performance

    under disturbances.3. Re- calibration

    needed from time totime.

    Examples: Driving a

    scooter, immersion

    heater

    Closed loop CS1. Complex design.

    2. Cost factor-Costly.

    3. Difficult to calibrate.

    4. Oscillations.

    Examples: Iron box, Airconditioner.

  • 8/6/2019 3-1 Control System Presentation

    29/361

    EXAMPLES AND APPLICATIONS OFFEEDBACK CONTROL SYSTEMS

    Open loop control systems(non-feedback):Most automatic toasters are open loop control

    systems because they are controlled by a timer.This time required to make the toast should beestimated by the user, who is not a part of the

    system. Control over the quality of the toast (theoutput) is removed once the time, which is botthe input and the control action , has been set.

    The time is typically set by calibrated means or aswitch.

    Closed loop control systems:

  • 8/6/2019 3-1 Control System Presentation

    30/361

    Closed loop control systems:

    An autopilot mechanism and the airplane itcontrols is an example of a closed loop controlsystem. Its purpose is to maintain a specified airplaneheading, despite atmospheric changes. It performsthis task by continuously measuring the airplaneheading, and automatically adjusting the airplanecontrol surfaces ( rudder, ailerons) so as to bring the

    actual airplane into correspondence with the specifiedheading. The human pilot or operator who presets theautopilot is not a part of the control system.

  • 8/6/2019 3-1 Control System Presentation

    31/361

    BLOCK

    D

    IAGRAM

    OFA

    N AUTOPILO

    T

    SYSTEM

    TH

    ATUSES

    FEED

    BACK

    CONTR

    OL

  • 8/6/2019 3-1 Control System Presentation

    32/361

    Positive feedback control systems:

    Audio feedback or acoustic feedback is

    a common example of positive feedback. Itis the familiar squeal that results whensound from loudspeakers enters a closely-placed microphone and gets amplified, and

    as a result the sound gets louder and louder.To avoid this condition, the microphone

    must be prevented from "hearing" itsown loudspeaker.

    Example of a biological positive feedback loop is the

  • 8/6/2019 3-1 Control System Presentation

    33/361

    Example of a biological positive feedback loop is theprocess of blood clotting. The loop is initiated wheninjured tissue releases signal chemicals that activateplatelets in the blood. An activated platelet releases

    chemicals to activate more platelets, causing a rapidcascade and the formation of a blood clot.

  • 8/6/2019 3-1 Control System Presentation

    34/361

    Negative feedback control systems: 1. A negative feedback amplifier, or more commonly simply

    a feedback amplifier, is an amplifier which uses negative feedback toimprove performance (gain stability, linearity, frequencyresponse, step response) and reduce sensitivity to parametervariations due to manufacturing or environmental uncertainties.

    2. Its operation is most easily seen in its use by James Watt to controlthe speed of his steam engine. Two heavy balls on an upright framerotate at the same speed as the engine. As their speed increases they

    move outwards due to the centrifugal force. This causes them to lift amechanism which closes the steam inlet valve and the engine slows.When the speed of the engine falls too far, the balls will move in theopposite direction and open the steam valve.

    3 Many biological process (e g in the human

  • 8/6/2019 3-1 Control System Presentation

    35/361

    3. Many biological process (e.g., in the humananatomy) use negative feedback. Examples ofthis are numerous, from the regulating of body

    temperature, to the regulating ofblood glucose levels. The disruption offeedback loops can lead to undesirable results:in the case of blood glucose levels, if negative

    feedback fails, the glucose levels in the bloodmay begin to rise dramatically, thus resultingin diabetes.

  • 8/6/2019 3-1 Control System Presentation

    36/361

    FEEDB

    AC

    KLOOP

    IN

    AB

    IOLOGICAL

    C

    ONTROL

    SYST

    E M

    EXAMPLES:-

  • 8/6/2019 3-1 Control System Presentation

    37/361

    There are many examples for both open loop and closed loop control systems both in natureand which are man made .

    A MAN DRIVING A CAR:-Consider the possibility in which a man drives a car blind folded . Then he is safe as

    long as there is no traffic on the road . But without his eyes while driving a car in traffic , hecant sense the mechanical motions like distance , speed , acceleration of his own vehicle andthat of others also . But when he is able to see , he can sense these motions . This information

    is sent to brain which commands the limbs to act accordingly .In the example discussed above , brain acts like a controller.

    The motions which are sensed are the feedback signals . Therefore the case in which the mandrives with his eyes closed is an example for open loop control system . And the case in which

    the man drives normally is an example for closed loop control system .

  • 8/6/2019 3-1 Control System Presentation

    38/361

    RESIDENTIAL HEATING SYSTEM:-Consider the case of the residential heating system , which can be

    controlled by using both open loop and closed loop control system .

    Consider the heating which makes use of open loop control system, whose basic structure is shown below;

    Temperature

    set point Valve Roomradiator

    Steam

    Outdoortemperature

    Open loop model:

    Controlled ro

    temperature

  • 8/6/2019 3-1 Control System Presentation

    39/361

    In this system , the indoor temperature is variable which is to be controlledand the outdoor temperature is main disturbance input.

    The desired is set on a calibrated dial , which positions the valvethat admits the steam for circulation through the radiator . The valve dialis calibrated at a certain temperature . When the value changes

    significantly the controlled temperature will deviate from the desiredvalue by a large error and hence precise control isnt realized . The openloop model is used for residential areas where control isnt very stringent

  • 8/6/2019 3-1 Control System Presentation

    40/361

    The open loop model can be converted to a closed loop model by adding the function ofmeasurement of the controlled temperature. Comparison of measured and desired values of

    temperature makes the control logic element to make changes in the heating rate so as to obtain

    the desired value .To control the above system , a thermostat with a bimetallic temperature sensor and asnap action switch to control a simple solenoid actuated steam valve is often used .This

    controls the power supply to the solenoid . Generally , two cases arise when the measuredtemperature isnt equal to the desired value .

    If T , represent desired and measured temperatures respectively , thenWhen T i.e., T is negative then switch opens , solenoid de-energized , temperature

    falls down due to heat transfer to surroundings .

  • 8/6/2019 3-1 Control System Presentation

    41/361

    LAPLACE TRANSFORMS

    V.Vasudeven07360Mechanical department

  • 8/6/2019 3-1 Control System Presentation

    42/361

    WHAT ARE LAPLACE TRANSFORMS?

  • 8/6/2019 3-1 Control System Presentation

    43/361

    A Laplace transform is a type ofintegral transform.

    Plug one function in0

    s te dt

    ( ) f t

    Get another function out

    ( )F s=

    The new function is in a different domain.

  • 8/6/2019 3-1 Control System Presentation

    44/361

    ( )F s is the Laplace transform of ( ). f t

    Write

    { }( ) ( ), f t F s=L

    0s te dt

    ( )f t ( )F s=When

    { }

    { }

    ( ) ( ),

    ( ) ( ), etc.

    y t Y s

    x t X s

    =

    =

    L

    L

  • 8/6/2019 3-1 Control System Presentation

    45/361

    A Laplace transform is an example of an improper integral : one ofits limits is infinite.

    0 0

    ( ) lim ( )

    h

    s t s t

    he f t dt e f t dt

    =

    Define

  • 8/6/2019 3-1 Control System Presentation

    46/361

    A CALCULATION

    Let0 if

    ( )1 if

    t cu t c

    t c

  • 8/6/2019 3-1 Control System Presentation

    47/361

    c

    1

    t

    0 if( )

    1 if

    t cu t c

    t c

  • 8/6/2019 3-1 Control System Presentation

    48/361

    { }0

    1 1

    ( ) ( ) lim

    lim lim ( )

    h s t s t

    hc

    h s c s t s h s c

    s sch h

    u t c e u t c dt e dt

    ee e e s

    = = =

    = =

    L

    Calculating the Laplace transform of theHeaviside function is almost trivial.

    Remember that ( )u t c is zero untilthen its one.

    ,t c=

    We can use Laplace transforms to turn ani i i l l bl

  • 8/6/2019 3-1 Control System Presentation

    49/361

    initial value problem

    " 3 ' 4 ( 1)

    (0) 1, '(0) 2

    y y y t u t y y

    + = = =

    into an algebraic problem

    2

    2 1( )*( 3 4) ( 1) ss

    s e

    Y s s s s +

    + + + =

    Solve for y(t)

    Solve for Y(s)

    Laplace transforms are particularly effectiveon differential equations with forcing functions

  • 8/6/2019 3-1 Control System Presentation

    50/361

    1

    1

    Asawtooth function

    t

    that are piecewise, like the Heaviside function,and other functions that turn on and off.

    I V P

  • 8/6/2019 3-1 Control System Presentation

    51/361

    I.V.P.

    Laplace transform

    Algebraic Eqn

  • 8/6/2019 3-1 Control System Presentation

    52/361

    If we solve the algebraic equation

    2

    2 2

    ( 1) ( 1)( )

    ( 3 4)

    s s s s e eY s

    s s s

    + =

    + and find the inverse Laplace transform of the solution, Y(s), we have the

    solution to the I.V.P.

    Algebraic Expression

  • 8/6/2019 3-1 Control System Presentation

    53/361

    Algebraic Expression

    Soln. to IVP

    Inverse

    Laplacetransform

    The inverse Laplace transform of

  • 8/6/2019 3-1 Control System Presentation

    54/361

    is

    4 43 32 15 80 4 16

    4325 5

    ( ) ( 1)( + ( ) )

    ( )( ( ) )

    t tee

    t t

    y t u t e e t

    u t e e

    =

    2

    2 2( 1) ( 1)( )

    ( 3 4)

    s s s s e eY s s s s

    + = +

    Th

  • 8/6/2019 3-1 Control System Presentation

    55/361

    4 43 32 15 80 4 16

    4325 5

    ( ) ( 1)( + ( ) )

    ( )( ( ) )

    t tee

    t t

    y t u t e e t

    u t e e

    =

    is the solution to the I.V.P.

    " 3 ' 4 ( 1)

    (0) 1, '(0) 2

    y y y t u t

    y y

    + =

    = =

    Thus

  • 8/6/2019 3-1 Control System Presentation

    56/361

    HOW DO WE TRANSFORM ANDIFFERENTIAL EQUATION?

    we need several nice properties of Laplace

  • 8/6/2019 3-1 Control System Presentation

    57/361

    we need several nice properties of Laplacetransforms that may not be readily apparent.

    First, Laplace transforms, and inversetransforms, are linear:

    { } { } { }{ } { } { }1 1 -1

    ( ) ( ) ( ) ( ) ,( ) ( ) ( ) ( )

    cf t g t c f t g t cF s G s c F s G s

    ++

    L = L +L

    L = L +L

    for functionsf(t),g(t), constant c, andtransformsF(s), G(s).

    there is a very simple relationshipb h L l f f iSecond,

  • 8/6/2019 3-1 Control System Presentation

    58/361

    between the Laplace transform of a givenfunction and the Laplace transform of that

    functions derivative.

    { } { }

    { } { }2'( ) ( ) (0),

    ''( ) ( ) (0) '(0)

    f t s f t f

    f t s f t s f f

    L = L

    L = L

    and

    These show when we apply differentiationby parts to the integral defining the transform.

    DIFFERENTIAL EQUATIONS

  • 8/6/2019 3-1 Control System Presentation

    59/361

    DIFFERENTIAL EQUATIONS

    10

    )0(')0()('" KyKytrbyayy ===++

    )()]0([)]0(')0([ 2 sRbYysYaysyYs =++

    )()()()]0(')0()[()(

    1)(

    2

    sQsRsQyyassY

    basssQ

    +++=++

    =

    )()( 1 YLty =

    1st step

    2nd step

    3rd

    step

  • 8/6/2019 3-1 Control System Presentation

    60/361

    Now we know there are rules that letus determine the Laplace transform

    of an initial value problem, but...

  • 8/6/2019 3-1 Control System Presentation

    61/361

    HOW DO WE FIND INVERSELAPLACE TRANSFORMS?

    First you must know that Laplace transforms

  • 8/6/2019 3-1 Control System Presentation

    62/361

    First you must know that Laplace transformsare one-to-one on continuous functions.

    In symbols

    { } { }( ) ( ) ( ) ( ) f t g t f t g t =L =L

    whenfandgare continuous.

    That means that Laplace transforms areinvertible.

    INVERSE LAPLACE TRANSFORMS

  • 8/6/2019 3-1 Control System Presentation

    63/361

    INVERSE LAPLACE TRANSFORMS

    If { }( ) ( ), f t F s=L

    { }1 12( ) ( )c i

    s t

    i c i F s e F s ds

    +

    = L

    then { }-1 ( ) ( ), F s f t =L where

    An inverse Laplace transform is an improper

  • 8/6/2019 3-1 Control System Presentation

    64/361

    An inverse Laplace transform is an impropercontour integral, a creature from the world

    of complex variables.

    Thats why you dont see them naked very often. You usually just see what theyyield, the output.

    In practice, Laplace transforms and inverseLaplace transforms are obtained using tables

    and computer algebra systems.

    IMPULSE?

  • 8/6/2019 3-1 Control System Presentation

    65/361

    IMPULSE?

    An impulse is the effect of a force that acts over a very short time interval.

    Engineers and physicists use theDirac delta function to model impulses.

    A lightning strike creates an electricalimpulse.

    The force of a major leaguers batstriking a baseball creates a mechanical

    impulse.

    THE DIRAC DELTA FUNCTION

  • 8/6/2019 3-1 Control System Presentation

    66/361

    THE DIRAC DELTA FUNCTION

    This so-called quasi-function was createdby P.A.M. Dirac, the inventor of quantum

    mechanics.

    0( ) 0 ( ) 1t a t a t a dt = =when and

    People use this thing all the time. Youneed to be familiar with it.

  • 8/6/2019 3-1 Control System Presentation

    67/361

    THE LAPLACE TRANSFORM OF THE

    DIRAC DELTA FUNCTION

    { ( )} 1/ a s L t a e =

    DIRAC DELTA (UNIT IMPULSE) FUNCTION

  • 8/6/2019 3-1 Control System Presentation

    68/361

    DIRAC DELTA (UNIT IMPULSE) FUNCTION

    Impulse of f(t), for

    Generalized function

    Laplace transform

    = =

    =0

    1)(andotherwise0

    if)( at

    atat

    aseatL = )}({

    10 ttt

    t t

  • 8/6/2019 3-1 Control System Presentation

    69/361

    LAPLACE TRANSFORMS

  • 8/6/2019 3-1 Control System Presentation

    70/361

    Def:

    Inverse:

    Linearity:

    Shifting Theorom:

    0),(for)()()(0

    >==

    ttfdttfefLsFst

    )()( 1 FLtf =

    )}({)}({)}()({ tgbLtfaLtbgtafL +=+

    )}({)(

    )()}({

    1asFLtfe

    asFtfeL

    at

    at

    =

    =

    REVIEW: PARTIAL FRACTIONS

    C I t d l f t

  • 8/6/2019 3-1 Control System Presentation

    71/361

    n

    nk

    kk

    n

    k

    m

    m

    m

    ps

    A

    ps

    A

    ps

    A

    ps

    A

    ps

    A

    pspsps

    asas

    +

    +

    +

    +

    =

    ++

    )()()()(

    )()()(

    2

    2

    1

    1

    1

    1

    12

    1

    11

    21

    0

    1

    1

    Case I: unrepeated real factor

    Case II: repeated real factor

    Case III: unrepeated complex factor

    Case IV: repeated complex factor

    n

    nkk

    kk

    nk

    m

    m

    m

    ps

    A

    ps

    A

    cbss

    BsA

    cbss

    BsA

    cbss

    BsA

    pspscbss

    asas

    +

    +

    +++

    +++

    ++

    +++

    =

    ++

    ++

    )()()()(

    )()()(

    2

    2

    2

    11

    12

    1212

    2

    1111

    22

    0

    1

    1

    EXISTENCE FOR LAPLACE TRANSFORM

  • 8/6/2019 3-1 Control System Presentation

    72/361

    EXISTENCE FOR LAPLACE TRANSFORM

    piecewise continuous on every finite inteval in therange of

    satisfy

    for some constant kandM.Conclusion:

    The Laplace transform of exists for alls > k

    0allfor|)(| tMetf kt

    )(tf

    )(tf

    0t

    )(tf

    Condition:

  • 8/6/2019 3-1 Control System Presentation

    73/361

    TRANSFORM OF INTEGRALS

  • 8/6/2019 3-1 Control System Presentation

    74/361

    s

    sF

    s

    fLdfL

    t)()(

    })({0

    ==

    })(

    {)( 1

    0s

    sFLdf

    t

    =

    CONVOLUTIONfi i i

  • 8/6/2019 3-1 Control System Presentation

    75/361

    Definition

    Property

    Application

    ==t

    dtgftgfth0

    )()())(()(

    )}()({))(*( 1 sGsFLtgf=

    )()()(

    1)(

    2

    sQsRsY

    basssQ

    =

    ++=

    =t

    dttqty

    0

    )()()(

    0)0('0)0()('" ===++ yytrbyayy1. Solve

    2. Calculate integral

    List of Laplace Transformsf(t) L(f) f(t) L(f)

  • 8/6/2019 3-1 Control System Presentation

    76/361

    f(t) L(f) f(t) L(f)

    1

    11/s 7

    cos t2 t 1/s2 8 sin t

    3 t2 2!/s3 9 cosh at

    4 tn(n=0, 1,)

    10 sinh at

    5 ta

    (a positive)

    11 eat cos t

    6 eat 12 eat sin t

    1

    !+n

    s

    n

    1

    )1(+

    +a

    s

    a

    as

    1

    22 +s

    s

    22

    +s

    22

    as

    s

    22as

    a

    22

    )( +

    as

    as

    22)(

    +as

    LINEAR SYSTEM APPLICATIONS

  • 8/6/2019 3-1 Control System Presentation

    77/361

    Definition: A linear mapping of a set of input functions

    into a corresponding set of output functions

    Transfer function: ratio of the Laplace transform of theoutput of the system to that of the input of the system

    )}({)( txfty =

    TRANSFER FUNCTION PROPERTIES

  • 8/6/2019 3-1 Control System Presentation

    78/361

    TRANSFER FUNCTION PROPERTIES

    Completely characterizes the systems (initiallyrelaxed)

    Independent of inputs and outputs

    Equals the Laplace transform of the impulseresponse of system

    Can be used to find the response to another systeminput (using convolution or partial fraction)

  • 8/6/2019 3-1 Control System Presentation

    79/361

    THANK YOU

    TRANSFER FUNCTION AND ITSPROPERTIES:-

    Transfer function of a system is a mathematical

  • 8/6/2019 3-1 Control System Presentation

    80/361

    ymodel and an operational method of expressing

    differential equations that relates the output variableto the input variable. It is the property of the systemitself which is independent of the magnitude of theinput or the driving function.

    Transfer function is the ratio of Laplace transform

    of output to the Laplace transform of input with initialconditions set to zero.

    Transfer function= C(s)/R(s), initial conditions zero. Poles and zeros of transfer function:

    C(s)/R(s) = ( bosn + b1sn-1 + _ _ _ + bn ) / ( aosm + a1sm-1 + _ _ _ + am )= N(s) / P(s).

    The poles of the transfer function are the roots ofthe equation P(s)=0. The equation P(s)=0 is calledth h t i ti ti f th t

  • 8/6/2019 3-1 Control System Presentation

    81/361

    the characteristic equation of the system.

    The zeros of the transfer function are the roots ofthe equation N(s)=0.Order and type of the system:

    C(s)/R(s) = ( bosn + b1s

    n-1 + _ _ _ + bn ) / ( aosm +

    a1sm-1

    + _ _ _ + am )*sr

    = N(s) / P(s)

    Order of the system is the degree of the equationP(s)=0.

    Type of the system is the number of poles at theorigin.

    TYPES OF INPUT SIGNALS

  • 8/6/2019 3-1 Control System Presentation

    82/361

    TYPES OF INPUT SIGNALS

    submitted by Tushar Ranjan Moharana

    Date 9th September 2009

    Assignment-I

    BASIC TYPES

  • 8/6/2019 3-1 Control System Presentation

    83/361

    Basically inputs are classified into four groups :-

    1. Step input

    2. Ramp input3. Parabolic input

    4. Impulse input

  • 8/6/2019 3-1 Control System Presentation

    84/361

    STEP INPUTMagnitude of input is constant(let 0) for certain time and suddenly increases tosome other value (let 1) and maintained at that value.

    Use : The functioning of automobiles on smooth road is tested by using

    this input through

    Simulation

    Used to test signal forElectronic equipment.

    By giving step input signal

    We can determine the

    response of system when

    it is switched on or off.

    X axis (time)

    RAMP INPUT

  • 8/6/2019 3-1 Control System Presentation

    85/361

    Impulse varies linearly with time.It is used in the horizontal deflection plates of a cathode rayoscilloscope.

    It moves the electron beam horizontally with a constant speedas the vertical deflection

    plate trace the wave

    form

    X axis (time)

  • 8/6/2019 3-1 Control System Presentation

    86/361

    PARABOLIC

    INPUT

    Magnitude of input signal is proportional to

    square of the timeUsed in accelerating speed of vehicle etc.

    X axis (time)

    INPUT

  • 8/6/2019 3-1 Control System Presentation

    87/361

    Impulse have high magnitude but acts for lesstime X axis (time)

    It is used to test the

    response of equipments tosudden fluctuation in the

    inputBy giving impulse input

    to any system we can

    determine its behavior to anyother signal

    Parabolic signal:

    f(t)=t2/2, when t > 0

    =0, otherwise.

  • 8/6/2019 3-1 Control System Presentation

    88/361

    Ramp signal and parabolic signal are used for the analysis

    of faster signals. Sinusoidal signal:

    f(t)=sin(t)*(t)

    Parabolic SignalRamp Signal

    Step Input Signal

    Impulse Signal Sinusoidal Signal

    MASONS GAINFORMULA

  • 8/6/2019 3-1 Control System Presentation

    89/361

    FORMULA

    NAME-SINGO SABATINIHEMBRAM

    BRANCH-METALLURGICALAND MATERIALSENGINEERING

    ROLL NUMBER- 7528

    MASONS GAINFORMULA

  • 8/6/2019 3-1 Control System Presentation

    90/361

    FORMULATo reduce a block diagram, one may use the Masons gain formula(also called Masons rule).

    Mason first derived the idea using what he called a signal-flowgraph, which is a different

    graphical representation of a block diagram. A signal-flow graph isdrawn with paths (lines) and

    nodes. The transfer functions in a block diagram become the pathsand the variables in between

    the blocks become the nodes. The input and output variables of ablock diagram are designated the

    source and sink nodes

    Signal flow graph is a diagramwhich represents a set of simultaneouslinear algebraic equation When applying

  • 8/6/2019 3-1 Control System Presentation

    91/361

    linear algebraic equation When applyingthe signal flow graph method to controlsystem we must first transform lineardifferential equation into algebraicequation in s.

    Signal flow graph consist of a network, inwhich nodes are connected by directedbranches.

    Each node represents a system variable and

    each branch connected between two nodesacts as a signal multiplier.

    Note that signal flows only in one direction.

    The signal flow graph depicts the flow of signals

    from one point of a system to another and gives the relationshipamong the signals.

    Signal flow graph contains essentially the same information as a

  • 8/6/2019 3-1 Control System Presentation

    92/361

    block diagram. The advantage of using

    signal flow graph is to represent a control system is that a gainformula or Masons gain formula is available

    which gives the relationships among the system variableswithout requiring a reduction of the graph.

  • 8/6/2019 3-1 Control System Presentation

    93/361

    TERMINOLOGY

  • 8/6/2019 3-1 Control System Presentation

    94/361

    The gain of the branch is a transmittance

    Branch :It is a directed line segmentjoining two nodes.

    Transmittance :It is a gain between the two

    nodes.

    Feed back loop: If a loop originates andterminates at the same node ,is known as

    feed back loop.

    Self loop: A loop that consists of only one

    node where it originates and terminates.

    Chain node: In this node no incoming or outgoing .Here x2 and x3are chain nodes.

    Flow of signals: Source to sink.

    Feed back: Sink to sour.

  • 8/6/2019 3-1 Control System Presentation

    95/361

    Dummy nodes: If incoming and outgoing branches exists at the

    first and last nodes representing input and output variables can notbe considered input and output nodes.

    In determining forward and backward paths self loops are notconsidered.

    In such cases separate input and output nodes are created byadjoining branches with unity gain.

    Path : It is a traversal ofconnected branches in thedirection of the branch arrows.

  • 8/6/2019 3-1 Control System Presentation

    96/361

    Path gain: The product of allgains going to the forwardpath.Loop :It is a closed path .Loop gain :It is the product of thebranch transmittance of a loop.Non touching loops : Loopsare non-touching if they do notposses any common nodes.

    Non touching loopx1

    x x3 x4

  • 8/6/2019 3-1 Control System Presentation

    97/361

    Touching loop

    2

    x2x1 x3 x4x5

    Forward path : Af d th i th

  • 8/6/2019 3-1 Control System Presentation

    98/361

    forward path is a pathfrom an input node toan output node which

    does not cross anynodes more then once.Forward path gain : It is the

    product of the branchtransmittances of a forward

  • 8/6/2019 3-1 Control System Presentation

    99/361

    TRANSMISSION RULE: x2 x5=dx1

    a x4=cx1

  • 8/6/2019 3-1 Control System Presentation

    100/361

    x5 d b x2=ax1

    c x3=bx1

    x4

    MULTIPLICATION RULE:

    a b c abc

    x3x1

    x2x1

    x1 x2

    x3 x4

    SFG VS BLOCK DIAGRAMS

  • 8/6/2019 3-1 Control System Presentation

    101/361

    Source orinput node

    Sink or outputnode

    Branch

    Node

    Input signal Output signal

    BlockSignal

    Signal Flow Graph Block Diagram

    PROPERTIES OF SIGNALFLOW GRAPH

  • 8/6/2019 3-1 Control System Presentation

    102/361

    1. A branch indicates the functional dependence of one signal

    upon another. A signal passes through only

    in the direction specified by the arrow of the branch .

    2. A node adds the signals of all incoming branches and

    transmits this sum to all outgoing branches.

    3. A mixed node which has both incoming and outgoing

    branches may be treated as an output node by adding anoutgoing branch of unity transmittance.

    4. For a given system, signal flow graph is not unique. Manydifferent signal flow graphs can be drawn for a given system bywriting the system equations differently.

    Utility of Signal FlowGraphs Alternative to block diagram approach

  • 8/6/2019 3-1 Control System Presentation

    103/361

    Alternative to block diagram approach

    - may be better for complex systems.- good for highly interwoven systems.

    - system variables represented as nodes, branches(lines) betweennodes show relationships between system variables.

    The flow graph gain formula (Mason)allows the system transferfunction to be directly computed without manipulation or reduction

    of the diagram.

    We now need to define somemore terms and show how eachof these quantities can be

  • 8/6/2019 3-1 Control System Presentation

    104/361

    of these quantities can be

    calculated:System determinant:

    = 1 (sum of all individual loop gains)

    + (sum of the products of the gains of all possible two loops thatdo not touch each other)

    (sum of the products of the gains of all possible three loops

    that do not touch each other)

    + and so forth with sums of higher number of non-touching loopgains.

    EXAMPLEG6

  • 8/6/2019 3-1 Control System Presentation

    105/361

    Step 1: forward paths=2

    G1 G

    2

    G4G3 G

    5-H1 -H2

    -

    H3

    G1G2G3G4G

    5

    G6

    1 1

    P1=G1G2G3G4G5

    P2=G6

    Step 2: No. of loops=4

  • 8/6/2019 3-1 Control System Presentation

    106/361

    Sum of product gain of two non touching loops=G4G6H2H3 +G2G6H1H3 + G2G4H1H2

    Step 3: three non touching loops=1

    =L1L2L4= -G2G4G6H1H2H3-H1

    G2L1

    G4

    -H2L2

    G1G2G3G4G5

    L3 -H3

    G6

    L4

    -H4

    PRODUCT GAIN:

    =1 ( - G2H1-G4H2-G1G2G3G4G5H3-G6H3)

  • 8/6/2019 3-1 Control System Presentation

    107/361

    G1G2G3G4G5H3-G6H3)

    +(G2G6H1H3+G4G6H2H3+G2G4H1H2)

    - (-G2G4G6H1H2H3)

    1=Product gain(excluding P1)=12=Product gain(excludinP2)=1-(-G2H1-G4H2)+

    (G2G4G6H1H2H3)=1+G2H1+G4H2+G2G4H1H2

    TRANSFER FUNCTION:The ratio of laplace transform ofoutput to laplace transform of

  • 8/6/2019 3-1 Control System Presentation

    108/361

    output to laplace transform of

    input at zero initials.

    T.F=C(S)/R(S)

    at zero initials

    C(S)/R(S)=((P1*1)+(P2*2))/

    HOW TO DEVLOP SFG FOR THE SYSTEM REPRESENTED BY THESEEQUATIONS .

    5-X1-2X2-3X3=0

    -2X1+X2+1.5X4=0

  • 8/6/2019 3-1 Control System Presentation

    109/361

    -2X2+X3-3X1=0.5X3X4=2X3

    Arrange the above equations :

    X1=5-2X2-3X3

    X2=2X1-1.5X4

    X3=0.5X3+3X1+2X2X4=2X3

    HERE 5 IS INPUT.

    -1.5

  • 8/6/2019 3-1 Control System Presentation

    110/361

    X1 XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX4

    2

    5

    0.5

    -2

    -3

    X2 X3

    2

    3

    DISADVANTAGESMissing a critical loop or

  • 8/6/2019 3-1 Control System Presentation

    111/361

    g p

    probability of missing acritical loop ,reduces the

    accuracy.Does not give a idea ofcause and effect of theoverall system.

    FLOW GRAPH SUMMARY Block diagrams and signal flow graphs allow visualrepresentation of complex dynamic systems.

    Through Masons gain formula, we can compute the input to

  • 8/6/2019 3-1 Control System Presentation

    112/361

    Through Mason s gain formula, we can compute the input to

    output transfer function of the overall system.Note how easily other transfer functions can be obtained e.g.noise response they all share the same .

  • 8/6/2019 3-1 Control System Presentation

    113/361

    TIME DOMAIN ANALYSIS

    The variation of output/response of a system wrttime is called time response. It has two parts-

    Steady state response and transient response.

  • 8/6/2019 3-1 Control System Presentation

    114/361

    STEADY STATE RESPONSE:THERESPONSE WHICH REMAINS EVEN

  • 8/6/2019 3-1 Control System Presentation

    115/361

    RESPONSE WHICH REMAINS EVEN

    AFTER THE TRANSIENTS HAVE DIEDOUT.

    From this response we can observe-

    1.Time taken by the system to reach steady state value.

    2.Whether there error is existing in the output or not

    STEADY STATE ERROR IN TIMEDOMAIN ANALYSIS

  • 8/6/2019 3-1 Control System Presentation

    116/361

    One of the objectives of most control systems is that thesystem output response follows a specific reference signalaccurately in the steady state.

    Steady-state error is the difference between the outputand the reference in the steady state.

    Steady-state errors in control systems are almostunavoidable and generally derive from the imperfections,frictions, and the natural composition of the system.

    In the design problem, one of the objectives is to keep thesteady-state error below a certain tolerable value.

    The error in control system is defined ase(t) = r(t) - b(t)

    or

    E(s) = R(s) - B(s) =R(s) - H(s)C(s)

  • 8/6/2019 3-1 Control System Presentation

    117/361

    The steady-state error is then given by:

    The steady-state error can be evaluated using the final-value theorem as:

  • 8/6/2019 3-1 Control System Presentation

    118/361

    This shows that the steady-state error depends on thereference input R(s) and the loop transfer function

    G(S)H(S)

    The open- loop transfer function, G(S)H(S), may bewritten as

    Steady-state error due to a step inputSteady

    -state error due to a step input

    For R(s)

  • 8/6/2019 3-1 Control System Presentation

    119/361

    G(s)H(s) as the positional error constant, then

    We can summarize the steady-state error due to a step input as follows:

    Type-0 system

    (or higher)Type-1 system

  • 8/6/2019 3-1 Control System Presentation

    120/361

    Steady-state errors: (a) step

    input, (b) ramp input

    Steady-state error due to a ramp inputSteady

    -state error due to a ramp input

    For R(S)= , we have

  • 8/6/2019 3-1 Control System Presentation

    121/361

    =K lim limv

    K ;n=0,1,2,..n-1s 0 s 0 s

    sG(s)H(s)=

    If we defineIf we define = velocity error constant= velocity error constant

    Therefore,

    Hence, we have

    Laplace transform of r(t) is given by:

    The input is described by:

    Steady-state error due to a parabolic inputSteady-

    state error due to a parabolic input

  • 8/6/2019 3-1 Control System Presentation

    122/361

    Hence, the following conclusions can be made:

    The steady-state error could be written as:

    Defining the acceleration error constant as:

    The steady-state error of the system is:

    Steady-state errors for various inputs and systemtypesaretabulated below.

  • 8/6/2019 3-1 Control System Presentation

    123/361

    The error constants for non-unity feedback systems may be obtained byreplacing G(s) by G(s)H(s).

    Systems of type higher than two are not employed for two reasons:

  • 8/6/2019 3-1 Control System Presentation

    124/361

    Systems of type higher than two are not employed for two reasons:1. The system is difficult to stabilize.

    2. The dynamic errors for such systems tend to be larger than thosetypes-0, -1 and -2.

    GENERALISED COEFFICIENT METHODBy using convolution theorem and taylors seriesexpansion we can write steady state error as

  • 8/6/2019 3-1 Control System Presentation

    125/361

    Es=k0R(t)+k1dR(t)/dt+..+kn d^nR(t)/dts

    Where kn= lt s 0 d^n(1/1+G(s)H(s))

    ds^n

    IMPORTANT INFORMATIONABOUT VARIATION OF ERRORWITH TIME.

  • 8/6/2019 3-1 Control System Presentation

    126/361

    Demerits:

    # It gives error of only

    standard signals.# the value of error at zeroor infinity is not given by

    this method.# Applicable only for stables stems.

  • 8/6/2019 3-1 Control System Presentation

    127/361

    CONCEPT OF BIBO

    By : Alok Ranjan

    WHY INVESTIGATE STABILITY?

    The issue of ensuring the stability of a closed-

  • 8/6/2019 3-1 Control System Presentation

    128/361

    loop system is the most important to controlsystem design. An unstable feedback system isof no practical value. A stable system shouldexhibit a bounded output if the correspondinginput is bounded. This is known as BIBO stability.

    CONCEPT OF BIBO

    A system is defined to be BIBO stable if every

  • 8/6/2019 3-1 Control System Presentation

    129/361

    bounded input to the system results in abounded output over the time interval zero toinfinity.

    BIBO stability is based on transfer functionrepresentation.

    For Linear-Time-invariant (LTI) system, if theimpulse response is absolutely integrable,thesystem is BIBO stable.

    Impulse response approach to zero when time

    lead to infinite.

    CRITERION FOR BIBO STABILITY FOR LTICSYSTEMS

  • 8/6/2019 3-1 Control System Presentation

    130/361

    x(t) y(t)

    y(t) = h(t)*x(t)

    = x(t- )d

    = d

    h(t)

    If x(t) is bounded, i.e. < K< ,then

    < K < , and K d

  • 8/6/2019 3-1 Control System Presentation

    131/361

    Hence for BIBO stability.d 0 If this condition is

  • 8/6/2019 3-1 Control System Presentation

    145/361

    characteristic equation be positive if a0 > 0. If this condition is

    not met, the system is unstable and number of sign changes of

    the terms of the first column of the Routh array corresponds to

    the number of roots of the characteristic equation in the right

    half of the s plane.

  • 8/6/2019 3-1 Control System Presentation

    146/361

    Special cases:

    Occasionally, in applying the Routh stability criterion,

    certain difficulties arise causing the breakdown of the Rouths

    test. The difficulties encountered are generally of the following

    types:

    Difficulty 1: When the first term in any row is zero while rest of

  • 8/6/2019 3-1 Control System Presentation

    147/361

    Difficulty 1: When the first term in any row is zero while rest of

    the row has at least one non zero term.

    Because of this zero term, the terms in the next row

    become infinity and Rouths test breaks down. The following

    method is used to overcome this difficulty:

    Substitute a small positive number for the zero and proceed toevaluate the rest of the array. Then examine the signs of the first columnby limiting 0.

    Ex:-3) Consider the following with characteristic equations5 +s4 +2s3 + 2s2 + 3s + 5 = 0

    The Routh array for this system is as below:1s5 : 2 3

  • 8/6/2019 3-1 Control System Presentation

    148/361

    s4

    s3

    s0

    s1

    s2

    2

    -2

    5

    2* +2

    5

    -4-4 -522+2

    -2

    5

    :

    :

    :

    :

    :

    1

    0

    It is seen that since the first element in the third row is zero it isreplaced by and proceeded. There are two sign changes in thefirst column. Therefore the given system is unstable having two

    poles in the right half ofs-plane.

    Difficulty 2 :When all the elements in any row of the Routh array

    are zero.

    This condition indicates that there are symmetrically

    located roots in the s-plane .The polynomial whose coefficients

    are the elements of the row just above the row of zeros in the

  • 8/6/2019 3-1 Control System Presentation

    149/361

    are the elements of the row just above the row of zeros in theRouth array is called an auxiliary polynomial. Because of a zero

    row, the Rouths test breaks down. This situation is overcome by

    replacing the row of zeros in the Routh array by a row of

    coefficients of the polynomial generated by taking the first

    derivative of the auxiliary polynomial.

    Ex:-4) Consider the following with characteristic equations6 +2s5 + 8s4 +12s3 + 20s2 + 16s + 16 = 0

    The Routh array for this system is as below:

    s5

    1

    12 16:

    s6

    2

    : 8 20 16

  • 8/6/2019 3-1 Control System Presentation

    150/361

    s

    s4

    s3

    12

    0

    2

    0

    1216

    ::

    :

    216

    Since the terms in the third row are zero the Rouths test breaks.

    Now the auxiliary polynomial is formed from the coefficients ofthes4-row, which is given by,

    A(s) = 2s4 + 12s2 + 16

    The derivative of the polynomial with respect tos is

    dds

    A(s) = 8s3 + 24s

  • 8/6/2019 3-1 Control System Presentation

    151/361

    APPLICATIONS OF ROUTH-HURWITZ CRITERION TOLINEAR FEED BACK SYSTEMS:

    The Routh stability criterion is frequently used for the

    determination of the condition of stability of linear feedback

  • 8/6/2019 3-1 Control System Presentation

    152/361

    determination of the condition of stability of linear feedbacksystems as shown in the in the following example:

    Ex -5):-

    Consider the closed loop transfer function of the system as

    C(s)/R(s)=K/{s*(s2 + s + 1)*(s + 4)+K}

    Then , the characteristic equation becomes,

    s*(s2 + s + 1)*(s + 4)+K=0

    s4 + 5s3 + 5s2 + 4s + K=0

    s4 1 5

    4

    K:

    Applying Routh-Hurwitz stability criterion for the abovesystem:

  • 8/6/2019 3-1 Control System Presentation

    153/361

    s3

    s0

    s1

    s2

    45

    K

    21/5

    84/5 5K21/5

    :

    :

    :

    :

    K

    Since for a stable system, the signs of elements ofthe first column of the Routh array should be all positive ,the condition of system stability requires that,K > 0 and

    (84/5-5K) > 0

    Therefore for stability , K should lie in the range84/25 > K > 0

  • 8/6/2019 3-1 Control System Presentation

    154/361

    Therefore for stability , K should lie in the range84/25 > K > 0When K=84/25 , there will be a zero at the first entry in

    the fourth row of the Routh array . This corresponds to thepresence of a pair of symmetrical roots . Therefore

    K=84/25, will cause sustained self oscillations in theclosedloop system .

    LIMITATIONS OF ROUTH-HURWITZCRITERION:

    Routh Hurwitz criterion has the following disadvantages :

    It gives only the number of roots in the right half of the s-

    plane . It i i f ti d th l f th t

  • 8/6/2019 3-1 Control System Presentation

    155/361

    p It gives no information as regards the values of the roots

    and does not distinguish between real and complex roots .

    It cant be used for characteristic equations containingexponential , trigonometric coefficients .

    It is very complicated . It is time consuming for higher ordersystems .

    It becomes tough to predict marginal stability for biggersystems .

    STATE VARIABLE METHODS

  • 8/6/2019 3-1 Control System Presentation

    156/361

    PRESENTED BY

    K.RAJASEKHARA REDDY(7837)

    BIOTECHNOLOGY

    DEFINITIONS:

  • 8/6/2019 3-1 Control System Presentation

    157/361

    STATE VARIBLES IN A SYSTEM

    systemm inputs p outputs

  • 8/6/2019 3-1 Control System Presentation

    158/361

    system

    Statevaribles(x1,x2,x3)

    STANDARD STATE FORM EQUATION

  • 8/6/2019 3-1 Control System Presentation

    159/361

    STANDARD STATE FORM EQUATION

  • 8/6/2019 3-1 Control System Presentation

    160/361

  • 8/6/2019 3-1 Control System Presentation

    161/361

    EXAMPLE WITH GENERAL CIRCUIT

    CIRCUIT DIAGRAM

  • 8/6/2019 3-1 Control System Presentation

    162/361

    EQUATIONS:

    i1+i2+i3=0

    i1+i2+c dv/dt =0 L1 di1/dt +i1R1+(e-V)=0

  • 8/6/2019 3-1 Control System Presentation

    163/361

    L1 di1/dt +i1R1+(e V) 0 L2 di2/dt +i2R2-V=0dV/dt=x1=(-1/c)(i1+i2)

    di1/dt=x2=(-1/L1)(i1R1+e-V)di2/dt =x3=(-1/L2)(i2R2-V)

    STATE EQUATION FROM PREVIOUSEQUATIONS

    x1 0 -1/c -1/c x1 o

    x2 = 1/L1 R1/L1 0 x2 + -1/L1 ux3 1/L2 0 R2/L2 x3 0

  • 8/6/2019 3-1 Control System Presentation

    164/361

    x3 1/L2 0 R2/L2 x3 0

    Consider the voltage and current in R2 as outputvariables y1,y2

    y=Cx+Du

    INPUT STATE OUTPUT EQUATION

    y1 0 0 R2 x1

    = x2y2 0 0 1 x3

  • 8/6/2019 3-1 Control System Presentation

    165/361

    y2 0 0 1 x3

    TRANSFER FUNCTION FROM STATEVARIABLE MODELS

    x=Ax+Bu

    y=Cx+DuTaking laplace transform on both sides

  • 8/6/2019 3-1 Control System Presentation

    166/361

    g pS*x(s)-x(0)=A*x(s)+B*u(s) (sI-A)*x(s)=B*u(s)

    x(s)=(1/(sI-A))*B*u(s)y(s)=c/(sI-A)*B*u(s)+D*u(s)Transfer function=y(s)/x(s)=(c/(sI-A))*B+D

    WHY WE GO FOR STATE VARIABLETECHNIQUE

  • 8/6/2019 3-1 Control System Presentation

    167/361

    Due to many demerits of transfer function we gofor state variable method.

    DEMERITS OF TRANSFER FUNCTION

    Applicable only for linear systemsAnalysis of multiple i/p system become tediousApplicable only for time invarient system

  • 8/6/2019 3-1 Control System Presentation

    168/361

    Initial conditions need to be zeroDoes not provide any information about the

    internal structure of the system Issues with stability there are many cases where

    the analysis using transfer function gives overallstable system but the system elements show thetendency to exceed the specified ratings.

    More of hit and trial error method.

  • 8/6/2019 3-1 Control System Presentation

    169/361

    AN INTRODUCTION TO P ANDPI CONTROLLERS.By:-SHASHANK KUMAR

    B.TECH, MECHANICAL ENGINEERING

    ROLL NO. 07352

    WHAT IS A CONTROLLER ?

    A controller compares the actual value of a system with thereference input i.e. the desired value , measures the deviation

    and then produces a control signal in accordance with theerror signal so as to reduce the deviation to zero or a

  • 8/6/2019 3-1 Control System Presentation

    170/361

    error signal so as to reduce the deviation to zero or aminimum value.

    This action is called the control action.

    DIFFERENT TYPES OF CONTROLLER

    The different types of controller used today in industrialapplications can be categorized as follows :-

    1. Two-position or on-off controllers.

  • 8/6/2019 3-1 Control System Presentation

    171/361

    2. Proportional controllers.

    3. Integral controllers.

    4. Proportional-plus-integral controllers.

    5. Proportional-plus-derivative-controllers.

    6. Proportional-plus-integral-plus-derivative controllers.

    PROPORTIONAL CONTROLLER

    A proportional controller is a type of linear feedback control system which followsthe following relation between input and output:-

    U(t)= ;here e(t) is the error signal which is the difference between the reference value and

  • 8/6/2019 3-1 Control System Presentation

    172/361

    the process variable.

    in laplace form, this is

    The proportional mode adjusts the output signal in direct proportion to thecontroller input. The adjustable parameter to be specified is the proportionalcontroller gain kp.

    The proportional controller is basically an amplifier with an adjustable gain. An example is a driver driving a car , if he is over speeding he reduces the

    accelerator, if he is at a lower speed he accelerates the car.,

    A SIMPLE PROPORTIONAL

    CONTROLLER

    e(s)c(s)

  • 8/6/2019 3-1 Control System Presentation

    173/361

    ADVANTAGES OF THE PROPORTIONALCONTROLLER

    1. It does not require a very precise analytical

    modeling of the system being controlled.2. It is very simple to implement

  • 8/6/2019 3-1 Control System Presentation

    174/361

    y p p

    DRAWBACKS OF THE PROPORTIONALCONTROLLER

    1. A proportional controller reduces error but does noteliminate it (unless the process has naturally integrating

    properties).2 It causes non zero steady state error

  • 8/6/2019 3-1 Control System Presentation

    175/361

    2. It causes non-zero steady state error.

    3. It does not provide any protection against oscillations.

    PROPOTIONAL AND INTEGRALCONTROLLER

    CONTROLLER PART

  • 8/6/2019 3-1 Control System Presentation

    176/361

    THE SPECIFICATION OF VARIOUS

    CONSTANTS ARE AS FOLLOWS

  • 8/6/2019 3-1 Control System Presentation

    177/361

    Kp =PROPOTIONAL GAINKi =INTEGRAL GAIN

    E(t) =ERROR FUNCTIONTi= INTEGRAL TIME

    THE EQUATION RELATED WITH IT ARE AS FOLLOWS :

    M(t)=Kp e(t) + Kp/Ti e(t) dt

    0

    t

  • 8/6/2019 3-1 Control System Presentation

    178/361

    TRANSFER FUNCTION

    M(s)/E(s)=Kp(1+1/Ti s)

    WHERE Kp : PROPOTIONAL GAIN OF THE CONTROLLER

    Ti : INTEGRAL TIME

    THE OUTPUT GRAPH OF PICONTROLLER

  • 8/6/2019 3-1 Control System Presentation

    179/361

    ADVANTAGES OF PI CONTROLLER

    The integral term of the PI controller causes the steadystate error to be zero for a step input

    LIMITATION OF PI CONTROLLER

  • 8/6/2019 3-1 Control System Presentation

    180/361

    The problem with using a PI controller isthat it introduces a phase-lag. This means

    that the phase margin (a measure ofstability) decreases. So careful designconsiderations with respect to the gain mustbe considered.

    APPLICATION OF PI CONTROLLERS

    THEY ARE USED IN FINDING AIR FLOWSMOTOR POSITIONING IN ROBOTS ETC

  • 8/6/2019 3-1 Control System Presentation

    181/361

  • 8/6/2019 3-1 Control System Presentation

    182/361

    PROPORTIONAL PLUSDERIVATIVE CONTROLLERBy

    Akhilesh Kumar

    Proportional-Derivative control is useful for fast response controllers that donot need a steady-state error of zero. Proportional controllers are fast.

    Derivative controllers are fast. The two together is very fast.

    INTRODUCTION:

  • 8/6/2019 3-1 Control System Presentation

    183/361

    1. Proportional action

    Provides an instantaneous response to the control error.

    This is useful for improving the response of a stable system but cannotcontrol an unstable system by itself.

    The gain is the same for all frequencies leaving the system with a nonzero

    steady-state error.

    2. Derivative action:

    Derivative action acts on the derivative or rate of change of the control error.

    This provides a fast response, as opposed to the integral action, but cannot

    accommodate constant errors (i.e. the derivative of a constant, nonzero error is 0). Derivatives have a phase of +90 degrees leading to a predictive response.However,

  • 8/6/2019 3-1 Control System Presentation

    184/361

    p g g p pderivative control will produce large control signals in response to high frequency

    control errors.Combination of proportional and derivative:

    Proportional-Derivative or PD control combines proportional control andderivative control in parallel.

    where

    is the proportional control gain andis the derivative gain or derivative time.

    DESIGN:

    KpR(s) C(s)E(s)+ _ + +Wns(s+2*Wn*e)

    The block diagram of PD controller is shown below:

  • 8/6/2019 3-1 Control System Presentation

    185/361

    Kd s

    Output, C(s)= (Kp + sKd)E(s)

    OP-AMP REALIZATION OF PD CONTROLLER:

    R1

    R2

    R

    R

    EE

  • 8/6/2019 3-1 Control System Presentation

    186/361

    Transfer function of the circuit : E/E= R2/R1 + R3*C*s

    R

    R3

    C

    AN PRACTICAL EXAMPLE:Consider the figure shown below:

    controller J

    Ia= constant

    TwTm,Bm

    Rf

    LfV

  • 8/6/2019 3-1 Control System Presentation

    187/361

    B

    Br

    The figure shows an electromechanical servo where

    Tm = Motor TorqueJ = Inertia

    Tw = Torque disturbance

    V = Viscous friction coefficient

  • 8/6/2019 3-1 Control System Presentation

    188/361

    The damper torque on J, due to V, behaves exactly like a derivative control mode in that italways opposes velocity dB/dt with a strength proportional to dB/dt, making motion less

    oscillatory.

    Solving the system and considering second order characteristic equation, we get

    Wn = (K/J) and e = (Td/2) * (K/J)

    If Td > 0, motor torque is felt by the load similar to mechanical viscousdamping torque. The derivative control is hence interpreted as pseudo-friction

    effect.

    The block diagram of the given system is as shown below:

    Tw

  • 8/6/2019 3-1 Control System Presentation

    189/361

    KpKc(1+Td*

    s)

    1/R

    f

    Kt1/Js*

    s

    Kp

    BBr+

    _

    ++

    If we change the system by using a proportional controller in the forward path andadding derivative mode at the controlled variable B.

    And comparing derivative control applied to system error with that to the controlledvariable. We find the similar effect on characteristic equation. However , derivative

    control has more violent response to sudden changes due to derivative term Brspresence.

    If we study the effect of derivative control on steady state errors (say for a unit step

  • 8/6/2019 3-1 Control System Presentation

    190/361

    If we study the effect of derivative control on steady state errors (say for a unit stepdisturbance with Br= zero, we conclude that :

    The performance is unaffected by the derivative mode.

    However, there is an indirect method for gaining improvements in steady state accuracyi.e. by proper choice of derivative mode allows the use of higher values of proportional

    gain, thereby improving the steady state accuracy.

  • 8/6/2019 3-1 Control System Presentation

    191/361

    APPLICATIONS:

    1. Fast steering mirror.

    2. Helicopter Hover.

  • 8/6/2019 3-1 Control System Presentation

    192/361

    3. Inverted pendulum.

    4. Mixing tank.5. Vibration Isolation.

    6. Simple offline least squares system identification.

    ROOT LOCUS(THEORY)

  • 8/6/2019 3-1 Control System Presentation

    193/361

    ROOT LOCUS(THEORY)

    Consider the following standard control system,

    C(s)G(s)

    R(s) error

    1+ KG(s)H(s)

    Where K is varied

  • 8/6/2019 3-1 Control System Presentation

    194/361

    G(s)

    H(s)

    Transience and stability of a system depends upon its CLOSED LOOPPOLES.

    To build a better system, movement of poles can be adjusted by modifyingthe system parameters.

    The ROOT LOCUS method thus is of help.

  • 8/6/2019 3-1 Control System Presentation

    195/361

    What is a ROOT LOCUS?

    Plot of the LOCI of the closed loop poles as a function of the open loopgain (K), where K is varied from infinity to infinity

    When,K is varied from infinity to zero, it is a direct root locus.

    K is varied from zero to infinity, it is a inverse root locus.

    There are 8 steps to constructing a ROOT LOCUS and must be followedin order to reach a conclusion

    RULE 1:

    Root locus is always symmetrical to the x-axis or the real axis.

    CONSTRUCTION OF A ROOT LOCUS

  • 8/6/2019 3-1 Control System Presentation

    196/361

    Roots are either real or complex conjugate pairs or both.

    Hence the roots or poles and zeroes of the equation are found first.Say,

    G(s)=_________(s+1)___(s^2 + 4s +5)(s+3)

    So the poles of the equation ares+3=0, s=-3

    s^2 +4s+5=0 s=-2+I and -2-IAnd the poles are

    RULE 2: Number of LOCI

    If the number of poles be n and the number of zeroes be m.

    If n>m , then

    Total number of loci= n

    Each locus starts from a pole and ends in a zero.

  • 8/6/2019 3-1 Control System Presentation

    197/361

    So, number of loci that start from a pole and end in infinity is n-m.

    E.g. in the previous caseTotal number of loci=3

    And number of loci starting from a pole and end in infinity is 3-2=1

    Rule 3: Real axis loci

  • 8/6/2019 3-1 Control System Presentation

    198/361

    Some of the loci will lie on the real axis.

    A point on the real axis will lie on the root locus if and only if,

    Number of poles and zeroes to the right is odd

    RULE 4: Angle of asymptotes

    Mostly, number of poles > number of zeroes. i.e. n>mHence, n-m branches move to infinity, along the asymptote.

    Asymptote: It is defined as a line on the root locus whichconverges at infinity.

  • 8/6/2019 3-1 Control System Presentation

    199/361

    The angle of asymptote is given by,Theta= (2*q + 1)*180 / n-m for K>0

    Theta= (2*q)*180 / n-m for K

  • 8/6/2019 3-1 Control System Presentation

    200/361

    e.g. In the above exampleG(s)=_________(s+1)___

    (s^2 + 4s +5)(s+3)

    sum(real part of poles) = -2+(-2)+(-3)= -7sum(real parts of zeroes) = -1

    n-m =2Centroid= (-7+1)/2= -3

    RULE 6: break away and break-in point

    Break-in point is defined as the point where the root locus enters real axis.

    Break away point is defined as the point where the root locus comes out of the realaxis.

    Break away & break in points are points on the real axis at which multiple roots ofthe characteristic equation occur.

  • 8/6/2019 3-1 Control System Presentation

    201/361

    Observation: If there are 2 adjacently placed poles on the real axis and the real axisis a part of the root locus, hence minimum 1 break away point exists between the 2

    poles.

    1+ G(s)H(s)=0; we get a relation in terms of K.

    -dk/ds=0, gives the break away point.e.g. G(s)H(s)=K / s^2 + 4s+5

    Hence,s^2+4s+5+K=0, and K=(-s^2+4s+5)

    -dk/ds=0, 2s+4=0

    RULE 7: Intersection of root locus with jw axis.

    To calculate the intersection with jw axis, this is followed

    1.Construct 1+G(s)H(s)=02.Develop the routh array in terms of K

    3.Find K value for which routh array contains a term of zeroes.4.Frame auxiliary equation with the help of coefficients from the row above the row ofzeroes.

    5 Substitute the K value found in step 2 equate the equation to zero find the value of

  • 8/6/2019 3-1 Control System Presentation

    202/361

    5.Substitute the K value found in step 2, equate the equation to zero, find the value ofs.

    The roots of the equation give the intersection points.

    e.g. say G(s)H(s)= K/s*s+1*s+3Characteristic equation will be s^3+ 4s^2 +3s+K=0,

    Routh array s^3: 1 3s : 4 K

    s^0: (12-K)/4..hence K-12=0 K=12Substituting K=12 in the auxiliary equation, 4s^2+K=0,

    hence we get K=(+or-) root(3)i , which are the intersection points.

    RULE 8: Angle of departure and angle of arrival.

    The root locus always leaves a complex pole, at an angle known as the departureangle given by,

    Theta=180+ arg( G(s)H(s) )

    The root locus always arrives at a complex zero, at an angle known as the arrivalangle.Theta=180- arg( G(s)H(s) ),

  • 8/6/2019 3-1 Control System Presentation

    203/361

    Where G(s)H(s) is the angle excluding the zero where the angle has the becalculated

    Steps of a ROOT LOCUS method:

    1.Determine the branch number ending at infinity of the loci using rule 1.

    2.Plot the poles and zeroes.

    3.Find the real axis loci using dark lines.

    4.Find the asymptotes and their angles using rule 3.

  • 8/6/2019 3-1 Control System Presentation

    204/361

    5.Using rule 4 determine the asymptotes centre and draw step 4 and step 5.

    6.Calculate the break in or breakaway points.

    7.Calculate angle of departure and angle of arrival using the rule.

    8.Determine the jw crossover if root locus has complex poles and zeroes.

    ByK S Venkatakrishnan

    7328Mechanical Engineering

  • 8/6/2019 3-1 Control System Presentation

    205/361

  • 8/6/2019 3-1 Control System Presentation

    206/361

    FREQUENCYFREQUENCY

    DOMAIN ANALYSISDOMAIN ANALYSISBY

    T V D .GOWTHAM

    ROLL NO -7356

    B.TECH

    MECHANICAL ENGINEERING

    FREQUENCY RESPONSE

    The term frequency response means the steadystate response of a system to a sinusoidal input

    In frequency response analysis we vary the

  • 8/6/2019 3-1 Control System Presentation

    207/361

    In frequency response analysis,we vary thefrequency of input signal over a certain range

    and study the resulting response

    Frequency response requirements differdepending on the application.

    Frequency response curves are often used toindicate the accuracy of electronic components

  • 8/6/2019 3-1 Control System Presentation

    208/361

    y por systems

    WHY FREQUENCY RESPONSE ANALYSISCOMES INTO PICTURE

    The frequency response of a control systempresents a qualitative picture of the transient

    response the frequency response allows us to understand

    a circuit's response to more complex inputs

  • 8/6/2019 3-1 Control System Presentation

    209/361

    Time domain analysis is limited to only smallersystems,the stability of larger systems is difficultto analyse

    Generation of sinusoidal signals is very easy

    Frequency response measurements can be useddirectly to quantify system performance and

    design control systems.

  • 8/6/2019 3-1 Control System Presentation

    210/361

    FREQUENCY RESPONSE FOR A GIVENSINUSOIDAL INPUT

  • 8/6/2019 3-1 Control System Presentation

    211/361

  • 8/6/2019 3-1 Control System Presentation

    212/361

  • 8/6/2019 3-1 Control System Presentation

    213/361

  • 8/6/2019 3-1 Control System Presentation

    214/361

    The sinusoidal transfer function G(jw) ,the ratio ofY(jw) to X(jw),is a complex quantity and can berepresented by magnitude and phase angle withfrequency as a parameter

    A negative phase angle is called phase lag andpositive phase angle is called phase lead

  • 8/6/2019 3-1 Control System Presentation

    215/361

    p p g pThe sinusoidal transfer function of linear system

    can be obtained by substituting jw in S of atransfer function

    REPRESENTATION OF FREQUENCY RESPONSECHARACTERISTICS IN GRAPHICAL FORMS

    There are three commonly used representations ofsinusoidal transfer functions:-

    Bode plots

  • 8/6/2019 3-1 Control System Presentation

    216/361

    Bode plots Polar plots Nyquist plots

    1. INTRODUCTION2. ILLUSTRATION3. GUIDELINES FOR A POLAR PLOT4 SIMPLE PLOTS

    POLAR PLOT

  • 8/6/2019 3-1 Control System Presentation

    217/361

    4. SIMPLE PLOTS

    5. STABILITY OF POLAR PLOT6. ADVANTAGES OF FREQUENCY

    RESPONSE OVER TIME RESPONSEANALYSIS

    A POLAR PLOT IS DEFINED AS THE LOCUS OF GH(JW) PHASOR

    IN POLAR REPRESENTATION WHEN W CHANGES FROM INFINITYTO ZERO AND THE PLOT IS IN GH(JW) PLANE

    Here the plot is between IG(jw)I & IG(jw) as a function ofw

    This is used in determining the stability of closed loopsystem from its open loop frequency response .For closedloop system stability, open loop transfer function is G(s)H(s) instead of G(s) unless H(s) is 1.Unless stated abovethe open loop tranfer function is G(s)

  • 8/6/2019 3-1 Control System Presentation

    218/361

    the open loop tranfer function is G(s).

    ILLUSTRATION OF POLAR PLOTS

    G(s)H(s) = K (s+a)/s(s+b) (s+c)

    Replacing s by jw ,we haveG(jw)H(jw)= K(a+jw)/jw(b+jw)(c+jw)

    = lGH(jw)l F(w) is called polar representation

    lGH(jw)l is called magnitude and F(w) is called phase angle

    lGH(jw)l = K(a^2+w^2)^.5 /jw(b^2+w^2)^.5 (c^2+w^2)^.5;

  • 8/6/2019 3-1 Control System Presentation

    219/361

    F(w) = arg(a+jw)-arg(b+jw)-arg(c+jw)-90

    Let us suppose GH(s) =K/(s+4)(s+6)(s+9)putting s =jw

    GH(jw) = K/(jw+4)(jw+6)(jw+9)= K/{(16+w^2)^.5 arg(4+jw) (36+w^2)^.5

    arg(6+jw) (81+w^2)^.5 arg(9+jw)}Next step is to variation of w from infinity to 0

    GUDELINES TO DRAW THE POLAR PLOTS1.IDENTIFY G(s)H(s)

    2.APPLY W TENDS TO INFINITY BY CONSIDERINGONLY HIGHER ORDER TERMS

    3.APPLY W TENDS TO ZERO BY CONSIDERING ONLY

    LOWER ORDER TERMS4.CONSIDER W=1 AS A TRAIL POINT AND GIVE THELOCATION OF ITS MAGNITUDE AND PHASE ANGLE

  • 8/6/2019 3-1 Control System Presentation

    220/361

    5.NOW GIVE THE APPROXIMATE SHAPE OF POLAR

    PLOT IN GH(w) PLANE6.APPLY POLAR PLOT ANALYSIS TO IDENTIFY THEOBSERVED STABILITY AND DEGREE OF STABILITY

    OF CONTROL SYSTEM

    FOR G(s) = K/[(s+4)(s+6)(s+9)] POLAR PLOT IS

  • 8/6/2019 3-1 Control System Presentation

    221/361

    Similarly for the following we get the corresponding graphs in polar planeand X-Y PLANE

    . G(s)H(s)= (1+sT)^-1

  • 8/6/2019 3-1 Control System Presentation

    222/361

    SIMPLE PLOTS OF THE FOLLOWING FUNCTIONS

    Polar plot of G(s)=1/(S+2)

    First substitutes =j in G(s)

    2tan)(

    4

    1)(

    1

    2

    =+

    = jGjG

  • 8/6/2019 3-1 Control System Presentation

    223/361

    polar plot for the system with

    )2)(1(

    10)(

    ++

    =

    sss

    sG

    )2)(1(

    10)(

    ++=

    jjjjG

    )2()1(

    10)(

    22++

    =

    jG

    11 tan2

    tan90)( = jG

    The plot is shown in Fig

  • 8/6/2019 3-1 Control System Presentation

    224/361

    STABILITY ANALYSIS OF POLAR PLOTS

    HERE WE ARE CONSIDERING CHARACTERISTIC EQUATION1+GH(jw) = 0 WHERE (-1,J0) IS CONSIDERED AS ORIGIN AND AS

    A CRITICAL POINT W.R.T CLOSED LOOP STABILITYIF POLAR PLOT PASSES THROUGH (-1,J0) POINT SYSTEM IS

    CRITICALLY STABLEIF (-1,JO)IS NOT ENCLOSED BY PLOT SYSTEM IS ABSOLUTELYSTABLE

    IF (-1,J0) IS ENCLOSED BY THE PLOT THEN THE SYSTEMIS

  • 8/6/2019 3-1 Control System Presentation

    225/361

    IF ( 1,J0) IS ENCLOSED BY THE PLOT THEN THE SYSTEMISUNSTABLE

    CONCEPT OF ENCLOSURE : A POINT OR REGION IS SAID TO BEENCLOSED BY POLAR PLOT IF THE POINT OR REGION LIES ON

    THE LHS OF DIRECTION OF JOURNEY OF PLOT STARTING FROMW =INFINITY TO W=0

    FOR FINDING OUT STABILITY

    CONSIDER THE EXPRESSION AND RATIONALISE IT EQUATE THE IMAGINARY VALUE T0 ZERO TO FIND OUT PHASECROSSOVER FRQUENCY FIND OUT GH(jw) AND EQUATE IT TO a+JOSUPPOSING CRITICAL K=SOME VALUE WE CALCULATE a

    IT IS SAIDlal = 1 SYSTEM IS CRITICALLY STABLE

    lal < 1 SYSTEM IS STABLElal >1 SYSTEMIS UNSTABLE

    WHERE a=(CRITICAL K)/(ACTUAL K)GAIN MARGIN ALSO DETERMINES THE STABILITY : GM=-20 loglal

  • 8/6/2019 3-1 Control System Presentation

    226/361

    GM= 6dB IS THE BEST RANGE GM=0 Db CRITICALLY STABLE

    GM= -6dB UNSTABLE

    HENCE POLAR PLOT AND CONCEPT OF ENCIRCLEMENT ARE ABLE TOPREDICT THE STABILITY OF A SYSTEM.

    FURTHER THIS PORTION OF POLAR PLOT IS USED IN NYQUIST CRITERION

    PRESENTATION ON BODE PLOTS

    By

    Jaivee T.Joseph

    O7324

    Mechanical dept

  • 8/6/2019 3-1 Control System Presentation

    227/361

    Mechanical dept.

    B. Tech

    BODE PLOTS

    A Bode plot is a graph of the logarithm of the transferfunction of a linear, time-invariant system versusfrequency, plotted with a log-frequency axis, to show thesystem's frequency response It is usually a combination

  • 8/6/2019 3-1 Control System Presentation

    228/361

    system s frequency response. It is usually a combinationof a Bode magnitude plot (usually expressed as dB of

    gain) and a Bode phase plot (the phase is the imaginarypart of the complex logarithm of the complex transfer

    function).

    EXPRESSING IN DB

    Given the tranfer function:

    )1/)((

    )1/()(

    +

    +=

    pjwjw

    zjwKjwG B

  • 8/6/2019 3-1 Control System Presentation

    229/361

    )1/)(( +pjwjw

    20log|G(jw) = 20logK + 20log|(jw/z+1)| - 20log|jw| -20log|jw/p + 1|

    The gain term, 20logKB, is just so manydB and this is a straight line on Bode paper,independent of omega (radian frequency).

    The term, - 20log|jw| = - 20logw, when plottedon semi-log paper is a straight line sloping at-20dB/decade. It has a magnitude of 0 at w = 1.

    Poles, zeros and bode plots

  • 8/6/2019 3-1 Control System Presentation

    230/361

    0

    20

    -20

    =1

    -20db/dec

    wlg

    The term, - 20log|(jw/p + 1), is drawn with the

    following approximation: If w < p we use theapproximation that 20log|(jw/p + 1 )| = 0 dB,a flat line on the Bode. If w > p we use the

    approximation of 20log(w/p), which slopes at-20dB/dec starting at w = p. Illustrated below.It is easy to show that the plot has an error of

    -3dB at w = p and 1 dB at w = p/2 and w = 2p.One can easily make these corrections if it is

    appropriate.

  • 8/6/2019 3-1 Control System Presentation

    231/361

    0

    20

    -20

    -40

    = p

    -20db/dec

    wlg

    20

    +20db/dec

    When we have a term of 20log|(jw/z + 1)| weapproximate it be a straight line of slop 0 dB/decwhen w < z. We approximate it as 20log(w/z)

    when w > z, which is a straight line on Bode paperwith a slope of + 20dB/dec. Illustrated below.

  • 8/6/2019 3-1 Control System Presentation

    232/361

    0

    -20

    -40

    = z

    +20db/dec

    wlg

    STRAIGHT-LINE AMPLITUDE PLOT

    At every value of s where =xn

    (a zero), increasethe slope of the line by per decade.

    At every value of s where =yn

    (a pole), decrease

    the slope of the line by per decade.The initial value of the graph depends on the

    boundaries. The initial point is found by putting theinitial angular frequency into the function andfinding |H(j)|.

    http://en.wikipedia.org/wiki/Decade_%28log_scale%29http://en.wikipedia.org/wiki/Decade_%28log_scale%29
  • 8/6/2019 3-1 Control System Presentation

    233/361

    finding |H(j)|.The initial slope of the function at the initial value

    depends on the number and order of zeros and polesthat are at values below the initial value, and arefound using the first two rules.

    STRAIGHT-LINE PHASE PLOT To draw the phase plot, for each pole and zero: if A is positive, start line (with zero slope) at 0 degrees if A is negative, start line (with zero slope) at 180 degrees at every =x

    n(for stable zeros Re(z) < 0), increase the slope by

    degrees per decade, beginning one decade before =xn (E.g.: ) at every =y

    n(for stable poles Re(p) < 0), decrease the slope by

    degrees per decade, beginning one decade before =yn

    (E.g.: )

    "unstable" (right half plane) poles and zeros (Re(s) > 0) haveopposite behavior

  • 8/6/2019 3-1 Control System Presentation

    234/361

    flatten the slope again when the phase has changed by degrees(for a zero) or degrees (for a pole),

    After plotting one line for each pole or zero, add the lines together toobtain the final phase plot; that is, the final phase plot is thesuperposition of each earlier phase plot.

    ADVANTAGES

    In the absence of a computer, a bode plotcan be sketched by approximating the

    magnitude and phase with right linesegments.

    Gain crossover, phase crossover, gainmargin and phase margin are more easily

  • 8/6/2019 3-1 Control System Presentation

    235/361

    margin and phase margin are more easily

    determined on the bode plot than the otherplots

    For design purposes, the affect of addingcontrollers and their parameters are more

    easily visualized here.

    DISADVANTAGES

    Absolute and relative stability of only minimumphase systems can be determined from bodeplots

    They are useful only for stability studies ofsystems with minimum phase loop transferfunctions

  • 8/6/2019 3-1 Control System Presentation

    236/361

    ADVANTAGES OF FREQUENCY RESPONSE OVER TIME

    RESPONSE ANALYSIS

    Here a system may be designed so that effects of undesirable noises arenegligible and such analysis and design canbe extended to certainnonlinear systems

    In design problems, there are no unified methods of arriving at adesignated system that meets time-domain performance specifications. Onthe other hand, in frequency domain, a wealth of graphical and othertechniques are available that are useful for system analysis and design,irrespective of the order of the system

  • 8/6/2019 3-1 Control System Presentation

    237/361

    irrespective of the order of the system

    We can use the data obtained from measurements on the physical systemwithout deriving its mathematical model Frequency response tests are simple and canmake use readily available

    sinusoidal signal generators

    DIGITAL CONTROLSYSTEM

  • 8/6/2019 3-1 Control System Presentation

    238/361

    Ashique Poyilil

    7308

    Mechanical engineering

    238

    Digital Control System - (DCS) A digital computer usedfor real-time control of a dynamic system, usually in anindustrial environment, possibly as part of aSupervisory Control and Data Acquisition (SCADA)system.

    A DCS samples feedback from the system undercontrol and modifies the control signals in an attemptto achieve some desired behaviour.

  • 8/6/2019 3-1 Control System Presentation

    239/361

    239

    Analysis of such digital-analogue feedbacksystems can i