(27) Size of Transformer's Circuit Braker & Fuse (10.6.13)

19
Enter Data in White Background Cells Calculate Size of Transformer / Fuse / Circuit Calculation Size of Circuit Breaker & Fuse are as per NEC 450.3 CONNECTED EQUIPMENT TO TRANSFORMER Sr.No Equipment Kw P.F Qty Equipment D.F 3 1 1 100% Total Load (Kva Total Load D.F Total D.F (Kva)

description

trefch

Transcript of (27) Size of Transformer's Circuit Braker & Fuse (10.6.13)

Page 1: (27) Size of Transformer's Circuit Braker & Fuse (10.6.13)

Enter Data in White Background Cells

Calculate Size of Transformer / Fuse / Circuit BreakerCalculation Size of Circuit Breaker & Fuse are as per NEC 450.3

CONNECTED EQUIPMENT TO TRANSFORMER

Sr.No Equipment Kw P.F Qty Equipment D.F Total Kva D.F (Kva)

3 1 1 100% 3 3

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

Total Load (Kva) 3

Total Load D.F 100%

Total D.F (Kva) 3

Page 2: (27) Size of Transformer's Circuit Braker & Fuse (10.6.13)

Transformer Details

Total D.F Load 3 Kva

Primary Side Voltage (L-L): 415 Volt

Secondary Side Voltage (L-L): 230 Volt

Transformer Impedance: 5%

Transformer Connection Y-Y

Size of Transformer: 3 Kva OR Kva 3Efficency of Transformer at Full Load 98.40% 0.984

Efficency of Transformer at 1/4 Load 97.50% 0.975

Location of Transformer

Provide Protection on Transformer: Pri.Side & Sec.Side

Type Protection on Primary & Secondary Side:

:Results:

Transformer Voltage / CurrentPrimary Line Voltage (L-L) 415 Volt

Primary Phase Voltage (L-P) 240 Volt

Primary Line Current(L-L): 4 Amp

Primary Phase Current(L-P): 4 Amp

Secondary Line Voltage (L-L) 230 Volt

Secondary Phase Voltage (L-P) 133 Volt

Secondary Phase Current(L-P): 7.5 Amp

Secondary Line Current(L-L): 7.5 Amp

Size of Circuit Breaker / Fuse (As per NEC 450.3)Size of Circuit Breaker on Primary Side: 10 Amp

Size of Fuse on Primary Side: 10 Amp

Size of Circuit Breaker on Secondary Side: 10 Amp

Size of Fuse on Secondary Side: 10 Amp

Transformer LossesTotal Losses@ Full Load 49 Watt

Total Losses@ 1/4 Load 19 Watt

Full Load Copper Loss 32 Watt

Core Loss 17 Watt

Jignesh.Parmar www.electricalnotes.wordpress.com, [email protected] Detail of TC/CB/Fuse

Supervised Not Supervised

Circuit Breaker Fuse

Page 3: (27) Size of Transformer's Circuit Braker & Fuse (10.6.13)

Size of Transformer / Fuse / Circuit Breaker

1 13 36 69 10

15 1525 2030 25

37.5 3045 3550 40

75 45112.5 50150 60225 70300 80500 90750 100

1000 1101500 1252000 1502500 1603750 1755000 2007500 225

10000 25012000 30015000 35020000 40025000 45030000 50037500 60050000 70060000 80075000 1000

100000 12001600200025003000400050006000

Standard Size of 3 Phase Transformer (KVA)

Standard Size of Fuse / C.B (Amp)

Page 4: (27) Size of Transformer's Circuit Braker & Fuse (10.6.13)
Page 5: (27) Size of Transformer's Circuit Braker & Fuse (10.6.13)

HOME

Page 6: (27) Size of Transformer's Circuit Braker & Fuse (10.6.13)

UnSupervised

Fuse / Inverse Time C.B as per NEC (Amp)

136

10152025303540

455060708090

100110125150160175200225250300350400450500600700800

100012001600200025003000400050006000

Page 7: (27) Size of Transformer's Circuit Braker & Fuse (10.6.13)
Page 8: (27) Size of Transformer's Circuit Braker & Fuse (10.6.13)

3UnSupervised Supervised 2

Fuse / Inverse Time C.B as per NEC (Amp) Fuse / Inverse Time C.B as per NEC (Amp) 3 Phase T.C (KVA)

1 1 1 16 3 3 3

10 6 6 615 10 10 920 15 15 1525 20 20 2530 25 25 3035 30 30 37.540 35 35 4545 40 40 50

50 45 45 7560 50 50 112.570 60 60 15080 70 70 22590 80 80 300

100 90 90 500110 100 100 750125 110 110 1000150 125 125 1500160 150 150 2000175 160 160 2500200 175 175 3750225 200 200 5000250 225 225 7500300 250 250 10000350 300 300 12000400 350 350 15000450 400 400 20000500 450 450 25000600 500 500 30000700 600 600 37500800 700 700 50000

1000 800 800 600001200 1000 1000 750001600 1200 1200 1000002000 1600 16002500 2000 20003000 2500 25004000 3000 30005000 4000 40006000 5000 50006000 6000 6000

Page 9: (27) Size of Transformer's Circuit Braker & Fuse (10.6.13)
Page 10: (27) Size of Transformer's Circuit Braker & Fuse (10.6.13)

233 6

3 Phase T.C (KVA) 1 Primary Secondary

1 3 C.B Fuse C.B 3 6 1 600% 300% 250%6 9 2 600% 300% 125%9 15 600% 300% 250%

15 25 25 13 1925 30 25 10 1530 37.5

37.5 4545 5050 75 More Than 600V

75 112.5

%Imp

Primary112.5 150 >600150 225 C.B Fuse225 300300 500 1% 600% 300%500 750 2% 600% 300%750 1000 3% 600% 300%

1000 1500 4% 600% 300%1500 2000 5% 600% 300%2000 2500 6% 600% 300%2500 3750 7% 400% 300%3750 5000 8% 400% 300%5000 7500 9% 400% 300%7500 10000 10% 400% 300%

10000 1200012000 1500015000 2000020000 25000 Prim. 5% 0 C.B25000 30000 Sec. 0 C.B30000 3750037500 5000050000 6000060000 7500075000 100000 Prim. 5% 0 C.B

100000 100000 Sec. 0 C.B

Page 11: (27) Size of Transformer's Circuit Braker & Fuse (10.6.13)

More Than 600V

%Imp

Primary>600

C.B Fuse

1% 600% 300%2% 600% 300%3% 600% 300%4% 600% 300%5% 600% 300%6% 600% 300%7% 400% 300%8% 400% 300%9% 400% 300%

10% 400% 300%

Maximum Rating of Over current Protection for Transformers Less than 600 Volts

Protection Primary Protection

Method 2A to 9A

125%(NH) 167%

250% 250%

Primary Only Primary only protectionAmp Pri Sec

1 300% 0%2 167% 0%3 167% 0%4 167% 0%5 167% 0%6 167% 0%7 167% 0%8 167% 0%9 167% 0%

10 125% 0%

4.17 167% 0%

More than 9A

Primary only protection

Primary and secondary protection

Page 12: (27) Size of Transformer's Circuit Braker & Fuse (10.6.13)

7.53 6.97 N/A6 N/A

Primary & Secondary protectionAmp Pri Sec

1 250% 167%2 250% 167%3 250% 167%4 250% 167%5 250% 167%6 250% 167%7 250% 167%8 250% 167%9 250% 125%

10 250% 125%

4.17 250% 167%7.53 10.43 12.58

10 10

10 10

Page 13: (27) Size of Transformer's Circuit Braker & Fuse (10.6.13)

Secondary 0

Fuse250%125%250% Primary Secondary

19 C.B Fuse C.B Fuse15 10 10 10 10

More Than 600V Supervised

secondary>600 <600

C.B Fuse C.B/Fuse

300% 250% 250%300% 250% 250%300% 250% 250%300% 250% 250%300% 250% 250%300% 250% 250%250% 225% 250%250% 225% 250%250% 225% 250%250% 225% 250%

600% Fuse 300%250% Fuse 250%

600% Fuse 300%125% Fuse 125%

Page 14: (27) Size of Transformer's Circuit Braker & Fuse (10.6.13)

More Than 600V Not Supervisedsecondary

>600 <600C.B Fuse C.B/Fuse

300% 250% 125%300% 250% 125%300% 250% 125%300% 250% 125%300% 250% 125%300% 250% 125%250% 225% 125%250% 225% 125%250% 225% 125%250% 225% 125%

Maximum Rating of Over current Protection for Transformers Less than 600 Volts

Primary Protection Secondary Protection

300% Not required Not required

250% 125%(NH) 167%

0

Less than 2A

More than 9A

Less than 9A