25471 Energy Conversion 5

download 25471 Energy Conversion 5

of 27

Transcript of 25471 Energy Conversion 5

  • 8/6/2019 25471 Energy Conversion 5

    1/27

    ENERGY CONVERSION ONE

    (Course 25741)

    Chapter Two

    TRANSFORMERScontinued

  • 8/6/2019 25471 Energy Conversion 5

    2/27

    Equivalent Circuit of Transformer

    Major Items to be considered in Construction of

    Transformer Model:

    Copper losses (in primary & Secondarywinding) ~ I

    Eddy current losses (in core) ~ V

    Hysteresis losses (in core) a complex nonlinearfunction of applied V

    Leakage flux : LP & LS, these fluxes produce

    self-inductance in primary & secondary coils

  • 8/6/2019 25471 Energy Conversion 5

    3/27

    Equivalent Circuit of Transformer

    Exact Eq. cct. Model for Real Transformer

    Copper losses modeled by resistances Rp & Rs

    As discussed before:

    p=m+Lp p; total av. Primary flux

    S=m+LS S; total av. Secondary flux

    where m; flux linking both P & S

    Lp; primary leakage fluxLS; secondary leakage flux

    The average primary (& Secondary) flux, each, isdivided into two components as:

    mutual flux & leakage flux

  • 8/6/2019 25471 Energy Conversion 5

    4/27

    Equivalent Circuit of Transformer

    Based on application of these components,Faradays law for primary circuit can beexpressed as:

    Vp(t)=Np dp/dt = Np dM/dt + Np dLp/dt or:

    Vp(t)=ep(t) + eLp(t) similarly for secondary:

    Vs(t)=Ns ds/dt = Ns dM/dt + Ns dLs/dt or:

    Vs(t)=es(t) + eLs(t)

    primary & secondary voltages due to mutualflux :

    ep(t) = Np dM/dt es(t)= Ns dM/dt

  • 8/6/2019 25471 Energy Conversion 5

    5/27

    Equivalent Circuit of Transformer

    Note : ep(t)/Np = dM/dt =es(t)/Ns

    ep(t)/es(t) = Np / Ns =a

    while eLp(t) = Np dLp/dt & eLs(t)= Ns dLs/dtif = permeance of leakage flux path

    Lp=(p Np) ip & Ls=(p Ns) is

    eLp(t) = Np d/dt (p Np) ip = Npp dip/dt

    eLs(t) = Ns d/dt (p Ns) is = Nsp dis/dt

    Defining:Lp = Npp primary leakage inductanc

    Ls = Nsp secondary leakage inductance

  • 8/6/2019 25471 Energy Conversion 5

    6/27

    Equivalent Circuit of Transformer

    eLp(t)=Lp dip/dt

    eLs(t)=Ls dis/dt

    Therefore leakage flux can be modeled by primary & secondary

    leakage inductances in equivalent electric circuit Core Excitation that is related to the flux linking both windings(m; flux linking both P & S) should also be realized in modeling

    im (in unsaturated region) ~ e (voltage applied to core)

    and lag applied voltage by 90 modeled by an inductance Lm

    (reactance Xm) Core-loss current ie+h is ~ voltage applied & It can be modeled

    by a resistance Rc across primary voltage source

    Note: these currents nonlinear therefore: Xm & Rc are bestapproximation of real excitation

  • 8/6/2019 25471 Energy Conversion 5

    7/27

    Equivalent Circuit of Transformer

    The resulted equivalent circuit is shown:

    Voltage applied to core = input voltage-internal

    voltage drops of winding

  • 8/6/2019 25471 Energy Conversion 5

    8/27

    Equivalent Circuit of Transformer to analyze practical circuits including Transformers, it

    is required to have equivalent cct. at a single voltage

    Therefore circuit can be referred either to its primary

    side or secondary side as shown:

  • 8/6/2019 25471 Energy Conversion 5

    9/27

    Equivalent Circuit of Transformer

    Approximate Equivalent Circuits of a Transformer

    in practice in some studies these models are more

    complex than necessary

    i.e. the excitation branch add another node to

    circuit, while in steady state study, current of this

    branch is negligible

    And cause negligible voltage drop in Rp & Xp Therefore approximate eq. model offered as:

  • 8/6/2019 25471 Energy Conversion 5

    10/27

    Equivalent Circuit of Transformer

    Approximate transformer models a- referred to primary b- referred to secondary

    c- with no excitation branch referred to p

    d- with no excitation branch referred to s

  • 8/6/2019 25471 Energy Conversion 5

    11/27

    Determination of Transformer Eq. cct.

    parameters Approximation of inductances & resistances obtained

    by two tests:

    open circuit test & short circuit test

    1- open circuit test : transformers secondary windingis open circuited, & primary connected to a full-rated

    line voltage, Open-circuit test connections as below:

  • 8/6/2019 25471 Energy Conversion 5

    12/27

    Determination of Transformer Eq. cct.

    parameters Input current, input voltage & input power measured From these can determine p.f., input current, and

    consequently both magnitude & angle of excitationimpedance (RC, and XM)

    First determining related admittance andSusceptance:

    GC=1/RC & BM=1/XM YE=GC-jBM=1/RC -1/XM

    Magnitude of excitation admittance referred to primarycircuit : |YE |=IOC/VOC

    P.f. used to determine angle,

    PF=cos=POC/[VOC . IOC]

    =cos1 {POC/[VOC . IOC]}

  • 8/6/2019 25471 Energy Conversion 5

    13/27

    Determination of Transformer Eq.

    cct. parameters Thus: YE = IOC/VOC = IOC / VOC

    Using these equations RC & XM can be

    determined from O.C. measurement

    PF1cosU

  • 8/6/2019 25471 Energy Conversion 5

    14/27

    Determination of Transformer Eq. cct.

    parameters Short-Circuit test : the secondary terminals of

    transformer are short circuited, and primary

    terminals connected to a low voltage source:

    Input voltage adjusteduntilcurrent in s.c.

    windings equal to its rated value

  • 8/6/2019 25471 Energy Conversion 5

    15/27

    Determination of Transformer Eq.

    cct. parameters The input voltage, current and power are again measured Since input voltage is so low during short-circuited test, negligible current

    flows through excitation branch

    Therefore, voltage drop in transformer attributed to series elements

    Magnitude of series impedances referred to primary side of transformer is:|ZSE| = VSC/ ISC , PF=cos=PSC/[VSC ISC]

    =cos1 {PSC/[VSC ISC]}

    ZSE= VSC / ISC = VSC/ ISC

    series impedance ZSE is equal to:

    ZSE=Req+jXeq = (RP+ aRS) + j(XP+aXS)

    It is possible to determine the total series impedance referred to primary side

    , however difficult to split series impedance into primary & secondary

    components although it is not necessary to solve problem

    These same tests may also be performed on secondary side of transformer

    U0 U

  • 8/6/2019 25471 Energy Conversion 5

    16/27

    Determination of Transformer Eq.

    cct. parameters Determine Equivalent cct.Impedances of a 20 kVA,8000/240 V, 60 Hz

    transformer O.C. & S.C. measurements

    shown

    P.F. in O.C. is:

    PF=cos=POC/[VOCIOC]=400 W/ [8000V x 0.214A]

    =0.234 lagging

    O.C. test(on primary)

    S.C. test(on primary)

    VOC=8000V VSC=489V

    IOC=0.214A ISC=2.5 A

    POC=400W PSC=240W

  • 8/6/2019 25471 Energy Conversion 5

    17/27

    Determination of Transformer Eq.

    cct. parameters excitation impedance:

    YE=IOC/VOC

    = 0.214 A / 8000 V= 0.0000268

    = 0.0000063 j 0.0000261 = 1/RC- j 1/XM

    Therefore: RC=1/ 0.0000063 = 159 k

    XM= 1/0.0000261=38.4 k

    PF1cos

    234.0cos 1

    ; Q5.76

  • 8/6/2019 25471 Energy Conversion 5

    18/27

    Determination of Transformer Eq.

    cct. parameters PF in sc test:

    PF=cos = PSC/[VSCISC]=240W/ [489x2.5]=0.196 lagging

    Series impedance:

    ZSE=VSC/ISC

    = 489 V/ 2.5 A =195.6

    =38.4 +j 192

    The Eq. resistance & reactance are :

    Req=38.4 , Xeq=192

    PF1cos

    Q7.78 Q7.78

  • 8/6/2019 25471 Energy Conversion 5

    19/27

    Determination of Transformer Eq. cct.

    parameters The resulting Eq. circuit is shown below:

  • 8/6/2019 25471 Energy Conversion 5

    20/27

    The Per Unit System For Modeling

    As seen in last Example, solving cct. containing

    transformers requires tedious operation to refer all

    voltages to a common level

    In another approach, the need mentioned above iseliminated& impedance transformation is avoided

    That method is known asper-unit system of measurement

    there is also another advantage, in application ofper-unit: as size of machinery & Transformer varies its

    internal impedances vary widely, thus a 0.1 cct.

    Impedance may not be adequate & depends on

    devices voltage and power ratings

  • 8/6/2019 25471 Energy Conversion 5

    21/27

    The Per Unit System For Modeling

    In per unit system the voltages, currents,

    powers, impedance and other electrical

    quantities not measured in SIunits system

    However it is measured and define as a

    decimal fraction of some base level

    Any quantity can be expressed onpu basis

    Quantity in p.u. =

    Actual Value / base value of quantity

  • 8/6/2019 25471 Energy Conversion 5

    22/27

    The Per Unit System For Modeling

    Two base quantities selected & other base quantitiescan be determined from them

    Usually; voltage, & power

    Pbase,Qbase, or Sbase = Vbase Ibase

    Zbase= Vbase/Ibase

    Ybase=Ibase/Vbase

    Zbase=(Vbase) / Sbase

    In a power system, bases for power & voltageselected at a specific point, power base remainconstant, while voltage base changes at everytransformer

  • 8/6/2019 25471 Energy Conversion 5

    23/27

    The Per Unit System For Modeling

    Example: A simple power system shown inFigure below:

    Contains a 480 V generator connected to anideal 1:10 step up transformer, a transmissionline, an ideal 20:1 step-down transformer, and a

    load

  • 8/6/2019 25471 Energy Conversion 5

    24/27

    The Per Unit System For Modeling

    Example

    Impedance of line 20+j60,impedance of load

    Base values chosen as 480 V and 10 kVA at genertor

    (a) Find bas voltage, current, impedance, and power

    at every point in power system

    (b) convert this system to its p.u. equivalent cct.

    (c) Find power supplied to load in this system

    (d) Find power lost in transmission line(a) At generator: Ibase=Sbase/Vbase 1=10000/480=20.83 A

    Zbase1=Vbase1/Ibase1=480/20.83=23.04

    Turn ratio of transformer T1 , a=1/10 =0.1 so base

    voltage at line Vbase2=Vbase1/a=480/0.1=4800 V

    ; Q3010

  • 8/6/2019 25471 Energy Conversion 5

    25/27

    The Per Unit System For Modeling

    Example

    Sbase2=10 kVA

    Ibase2=10000/4800=2.083 A

    Zbase2

    =4800 V/ 2.083 A = 2304 Turn ratio of transformer T2 is a=20/1=20, sovoltage base at load is:

    Vbase3=Vbase2/a =4800/20= 240 V

    Other base quantities are:

    Sbase3=10 kVA

    Ibase3=10000/240=41.67 A

    Zbase3=240/41.67 = 5.76

  • 8/6/2019 25471 Energy Conversion 5

    26/27

    The Per Unit System For Modeling

    Example

    (b) to build the pu equivalent cct. Of power system, each

    cct parameter divided by its base value

    VG,pu=

    Zline,pu=(20+j60)/2304=0.0087+j0.0260 pu

    Zload,pu=

    Per unit equivalent cct of PWR. SYS. Shown below:

    puQQ

    00.1480/0480 !

    puQQ

    0736.176.5/3010 !

  • 8/6/2019 25471 Energy Conversion 5

    27/27

    The Per Unit System For Modeling

    Example (c) current flowing in:

    Ipu=Vpu/Ztot,pu=

    pu Per unit power of load :

    Pload,pu =IpuRpu=(0.569)(1.503)=0.487

    actual power supplied to load:

    Pload=Pload,puSbase=0.487 x 10000=4870 W(d) power loss in line:

    Pline loss,pu =IpuRline,pu=(0.569)(0.0087)=0.00282

    Pline= Pline loss,pu Sbase= (0.00282)(10000)=28.2 W

    Q

    Q

    Q

    Q

    6.30569.0894.0512.1

    01

    )30736.1()026.00087.0(

    01

    !

    !

    j

    j