2.3 Control valve schedule
-
Upload
api-19500842 -
Category
Documents
-
view
332 -
download
2
Transcript of 2.3 Control valve schedule
LEGENDNOTE 1 VALVE PORT NOTE 2 MATERIAL NOTE 3 ACTIONE : EQUAL PECENTAGE 1 : SUS304 C : CLOSE ON AIR FAILUREL : LINEAR 2 : SUS316 O : OPEN ON AIR FAILUREO : ON-OFF 3 : MONEL F : FREE ON AIR FAILURES : GLOBE TYPE 4 : NICKEL RO : OPEN WHEN SOLENOID
(SINGLE SEATED) 5 : STELLITED VALVE IS ENERGIZINGD : GLOBE TYPE 6 : CARBON STEEL RC : CLOSE WHEN SOLENOID
(DOUBLE OR CAGE) 7 : CAST IRON VALVE IS ENERGIZINGA : ANGLE TYPE 8 : HASTELLOYT : SAUNDERS TYPE 9 : GLASSX : BUTTERFLY TYPE 10 : TEFLONB : BALL TYPE 11 : BRONZEG : GATE TYPE 12 : SCS13EC : ECCENTRIC TYPE 13 : SCS316L NOTE 4 ACCESSORIESY : Y SHAPE TYPE 14 : SPECIAL REINFORCED TEFLON SEAT A : PNEUMATIC VALVE POSITIONERV : V BALL TYPE 15 : RUBBER B : ELECTRONIC VALVE POSITIONER(EX. PROOF TYPE)
16 : NEOPRENE F : AIR COOLING FINK : EXTENSION(FOR LOW TEMP.)H : WITH HAND WHEELT : BELLOWS SEALW(O) : LIMIT SWITCH FOR OPEN(EX. PROOF TYPE) W(C) : LIMIT SWITCH FOR CLOSE(EX. PROOF TYPE)R : SOLENOID VALVE(4 WAY OR 3 WAY EXPLOSION PROOF)
90,000 MTPY PVC PLANT IN VIETNAMTPC VINA PLASTIC & CHEMICAL CORP., LTD.
THAIPLASTIC AND CHEMICAL PUBLIC CO RAYONG FACTORYPROJECT TPC VINA LINE-2 PROJECT NAME CONTROL VALVE SCHEDULESCALE JOB NO.
B ### ISSUE FOR REVIEW Akachai K.Akachai K.Paisarn S. NONE EN07001A 7/8/2007 B.E.P ISSUE Akachai K.Akachai K.Paisarn S.DWG NO. SPX-30-A004REV. DATE DESCRIPTION DWG CHK. APP.
LEGEND
90,000 MTPY PVC PLANT IN VIETNAMTPC VINA PLASTIC & CHEMICAL CORP., LTD.
THAIPLASTIC AND CHEMICAL PUBLIC CO RAYONG FACTORY
TPC VINA LINE-2 PROJECT
CONTROL VALVE SCHEDULE
EN07001
SPX-30-A004 REV.B
Page 3 of 26
TPC VINA PLASTIC AND CHEMICAL CORP.,LTDCONTROL VALVE SCHEDULE
PVC LINE 2 PROJECT
TAG NO.
Data from file : PV4 Instrument R29 Operating Condition SpecificationPVC-4 LIQ Press. Nor.Rate Max.Rate Vapor Input Cv Size
Rating
Port Mat'l Action Acces- LineTag no. Service No. Fluid STM Up P Temp. L:kg/h L:kg/h Density M.W. Signal Cal. (inch) Type (Note 2) sories Size M'F'R
Or Stream S:kg/h S:kg/h (kg/m3) Visc. Select Body (Note 1) Body (Note 3) (Note 4) Spec.
GAS G:Nm3/h G:Nm3/h (C.P.) Port TrimFCV-316A/B-1 EA-301A/B 2 CW L 4 0.5 30 629000 700000 1000 1.0 I/P 1161 10 JIS X SCPH2 O B.H 10
INLET 3443 10 WAFER E 1 A1S
FCV-404 FCV-403 DA-401A/B/C 1 RVCM L 5.5 0.3 40 1712.49 1969 872 0.18 I/P 1 1/2 JIS E SCPH2 C B 2 M.SFEED 24 1 1/2 20K RF 2 B2J
FCV-501 DA-501 1 PS SLURRY 6.5 0.2 60 35,747 41,109 1100 1.95 I/P 102.3 3 ANSI EC A351CF8 C B 3 Y.KPS FEED 150 3 150 RF E SCS14 A3J
FCV-503 DA-501 1 LS S 7 1 164 1977 2,965 3.67 0.014 I/P 44.51 3 JIS S SCS13A C B 4 Y.Krecheck sizing INLET 115 3 10K RF E SUS316L A3K-H
FCV-511 FF-501 1 HW L 3.5 0.5 95 150000 264000 1000 I/P 486.9 8 JIS S A216WCB C B 8 M.SINLET 700 8 10K RF E SUS316 A1S-H
FCV-506A/B GF-501A/B 2 PS SLURRY 3 0.5 75 39674 45,626 1100 1.95 I/P 71.82 3 JIS EC SCS13A C B 3INLET 150 3 10K RF E SCS14 A1K-P
FCV-907 GA-9320A/B/C/D/E 1 CW L 4 0.5 30 400,000 400,000 1000 1.0 I/P 704.7 8 JIS 10K EC A216WCB C B.H 10 Y.KBY PASS 1000 8 WAFER E SCS14 A1S
LCV-201 LCV-201 FA-201 1 PW L 3 0.5 AMB 11,057 12,716 1000 1.0 I/P 2 1/2 JIS E 12 C B 4 M.SLNLET 81 2 1/2 10K RF 2 A20P
LCV-302 LCV-302 FA-303 TO 1 WW L 3.5 0.5 40 280 322 1000 1.0 I/P 1 JIS E SCPH2 C B.R 1 M.SFA-804 3 3/8 10K RF 2 A5S
LCV-303 FA-305 1 WW L 5 0.5 AMB 1,024 1,178 1000 1.0 I/P 1.95 1 ANSI S A216WCB C B 1 1/26.3 150 RF E SUS316L A5S
LCV-306 LCV-303 FA-308 1 IW L 6 0.5 AMB 12000 1000 1.0 I/P 2 JIS E 12 C A 2 M.S30 1 1/2 10K RF 2 A1S
LCV-305 FA-306 1 DPW L 4 0.5 70 26,720 30,728 977 0.66 I/P 51.32 4 ANSI S A216WCB C 499 3 150 RF E SUS316L A2P
LCV-307 GA-317 1 WW L 4 0.5 40 3,300 4,950 978 1 I/P 8.4 1 1/2 ANSI S A216WCB O B 3DELIVERY 30 1 1/2 150 RF E SUS316L A2P
LCV-401 LCV-401 GA-401 1 WW L 1.8 0.2 40 1,203 1,384 1000 1.0 I/P 1 JIS E 6 C B.R 1 M.STO FA-803 5.2 1/2 10K RF 2 A2S
LCV-402 LCV-402 GA-402 1 WW L 1.8 0.2 40 962 1,107 990 0.66 I/P 1 JIS E 6 C B 1 M.STO FA-803 5.2 1/2 10K RF 2 A2S
LCV-502 DA-501 1 PS L 6 0.5 101 38,824 44,647 1100 I/P 3 V C 3OUTLET E A1K-P
LCV-701 FA-703 1 HW L 4 0.5 90 5,273 6,064 980 I/P 10.37 1 1/2 ANSI S SCS13A C B 3OUTLET 30 1 1/2 150 RF E SUS316L A5S
LCV-801 LCV-802 GA-801 1 WW L 1.8 0.2 AMB 301.34 347 861.4 1.0 I/P 1 JIS E 6 C B 1 M.SOUTLET 1.5 1/4 10K RF 2 A2S
LCV-802 GA-802 1 WW L 5 0.4 40 502.9 578 1000 1 I/P 1.067 1 JIS S A216WCB C B 1 OUTLET 4 10K RF E SUS316L A1S
LCV-803 GA-803 1 WW L 5 0.4 40 503 578 1000 1 I/P 0.955 1 ANSI S A216WCB C B 1 1/2OUTLET 2.5 150 RF E SUS316L A5S
LCV-901 FB-901 1 IW L 6 0.5 32 20,000 30,000 1000 1 50.75 3 ANSI S A216WCB C B 4MAKE UP IW 99 3 150 RF E SUS316L A1S
PCV-101 GA-100A 1 PA G 7 AMB 1/4 ANSI C 1 AIR SUPPLY 1/4 150 RF A5X
PCV-102 GA-100C 1 PA G 7 AMB 1/4 ANSI C 1
(kg/cm2G) (OC)
(kg/cm2G)
Page 4 of 26
TPC VINA PLASTIC AND CHEMICAL CORP.,LTDCONTROL VALVE SCHEDULE
PVC LINE 2 PROJECT
TAG NO.
Data from file : PV4 Instrument R29 Operating Condition SpecificationPVC-4 LIQ Press. Nor.Rate Max.Rate Vapor Input Cv Size
Rating
Port Mat'l Action Acces- LineTag no. Service No. Fluid STM Up P Temp. L:kg/h L:kg/h Density M.W. Signal Cal. (inch) Type (Note 2) sories Size M'F'R
Or Stream S:kg/h S:kg/h (kg/m3) Visc. Select Body (Note 1) Body (Note 3) (Note 4) Spec.
GAS G:Nm3/h G:Nm3/h (C.P.) Port Trim
(kg/cm2G) (OC)
(kg/cm2G)AIR SUPPLY 1/4 150 RF A5X
PCV-103 GA-100B 1 PA G 7 AMB 1/4 ANSI C 1/2AIR SUPPLY 1/4 150 RF A1X
PCV-211 PCV-211 GA-201 1 PW L 6 1 AMB 3,745 4,306 1000 1.0 I/P 4 JIS E 12 C A 3 M.SBY-PASS 192 4 10K RF 2 A1K
PCV-213 PCV-213 GA-204A/B 1 DW L 18 16 AMB 4,768 5,483 1000 1.0 I/P 1 JIS E 12 C B 1 M.SBY-PASS 3 3/8 20K RF 2,5 B1K
PCV-302 GA-301 1 PS L 3 0.5 58 39,360 45,264 1100 I/P 72.62 4 ANSI EC SCS13A C B 6OUTLET 100 150 RF E SCS14 A1K
PCV-305 OUTLET 1 RVCM GAS 3 0.2 75 24,104 27,719 9.2 0.012 I/P 441.9 8 ANSI 150 EC A216WCB C B 8FA-304 kg/hr kg/hr 510 WAFER E SCS14 A9K
PCV-311 FA-311 1 IA G 7 AMB 1/2 ANSI C 1/21/2 150 RF A5X
PCV-315 FA-324 1 LN G 7 AMB 1/2 ANSI C 1 N2 SEAL 1/2 150 RF A5X
PCV-401 PCV-401 GB-401 1 RVCM G 290 mmHg 0.1 40 1,748 2,010 0.87 I/P 2 JIS E 6 C B 2 M.SBY-PASS 2 10K RF 2 A2S
PCV-402 PCV-402 GB-402 1 RVCM G 6.5 4.5 40 3,805 7,293 2.28 I/P 2 JIS E 6 C B 2 M.SBY-PASS 2 10K RF 2 A2S
PCV-403-1 PCV-403-1 EA-404 1 RW L 3.2 0.2 5 4,348 5,218 1025 1.0 I/P 1 1/2 JIS E 6 C B 1 1/2 M.SINLET 30 1 1/2 10K RF 2 A5S-C
PCV-403-2 PCV-403-2 EA-404 1 WG G 5.5 0.2 25 21 34 12.23 0.014 I/P 1 JIS E 6 C B 1 M.SOUTLET 0.4 1/8 10K RF 2 A2S
PCV-404 EA-403 1 CW L 4 0.5 30 212,000 227,000 1000 1.0 I/P 374.8 8 JIS S A216WCB C B 8INLET 700 8 10K RF E SUS316L A1S
PCV-502 PCV-506 EA-502 1 PS SLURRY 3 0.1 75 39,506 45,432 1100 1.95 I/P 2 1/2 JIS V-BALL 12 C V-BALL 2 1/2 K.MOUT LET 2 1/2 10K RF 12 A1K-P
PCV-801 PCV-802 GB-801 1 RVCM G -130 0.15 40 38.4 44 2.94 I/P 1 JIS E 6 C B 3 M.SBY-PASS mmHg 0.8 3/16 10K RF 2 A2S
PCV-802 FA-803 1 RVCM G 5.5 0.5 60 44.17 51 2.94 I/P 2.08 1 ANSI S A216WCB C B 2INLET 6.3 150 RF E SUS316L A9A
PCV-804-1 GB-801 1 RVCM GAS 0 0.1 35 37 60 1.16 I/P 8.51 1 1/2 JIS S A216WCB C B 3INLET 30 1 1/2 10K RF E SUS316L A2S
Page 5 of 26
TPC VINA PLASTIC AND CHEMICAL CORP.,LTDCONTROL VALVE SCHEDULE
PVC LINE 2 PROJECT
TAG NO.
Data from file : PV4 Instrument R29 Operating Condition SpecificationPVC-4 LIQ Press. Nor.Rate Max.Rate Vapor Input Cv Size
Rating
Port Mat'l Action Acces- LineTag no. Service No. Fluid STM Up P Temp. L:kg/h L:kg/h Density M.W. Signal Cal. (inch) Type (Note 2) sories Size M'F'R
Or Stream S:kg/h S:kg/h (kg/m3) Visc. Select Body (Note 1) Body (Note 3) (Note 4) Spec.
GAS G:Nm3/h G:Nm3/h (C.P.) Port Trim
(kg/cm2G) (OC)
(kg/cm2G)
PCV-804-2 GB-801 1 RVCM GAS 0 0.1 35 20 30 1.16 I/P 4.17 1 ANSI S A216WCB C B 1 INLET 10 1 150 RF E SUS316L A9A
TCV-301A/B-1 EA-303A/B 2 CW L 4 0.5 30 600,000 1000 1.0 I/P 10 JIS E 6 O B 10JACKET HEATER 8 10K RF 2 A1S
TCV-301A/B-2 EA-301A/B 2 CW L 4 0.5 30 462,000 1000 1.0 I/P 6 JIS E 6 O B 6INLET 6 10K RF 2 A5S
TCV-303A/B HCV-303A/B EA-303A/B 2 LS S 7 0.5 170 4,970 I/P 6 JIS E SCPH2 C B 6 M.SINLET 390 6 10K RF 2,5 Rx3 A2S-H
TCV-304 TCV-304 EA-302 1 CW L 4 0.5 30 61,000 1000 1.0 I/P 6 JIS E SCPH2 C B 5 M.SINLET 275 5 10K RF 2 A1S
TCV-401-1 EA-402 1 CWR L 4 0.5 30 50,000 1000 1.0 I/P 82.5 3 JIS S A216WCB O B 3OUTLET 125 3 10K RF E SUS316L A1S
TCV-401-2 FA-402 1 LS S 7 3 170 100 I/P 1.25 1 JIS S SCPH2 C B 1 INLET 4 10K RF E SUS316L A1S-H
Page 6 of 26
TPC VINA PLASTIC AND CHEMICAL CORP.,LTDCONTROL VALVE SCHEDULE
PVC LINE 2 PROJECT
TAG NO.
Data from file : PV4 Instrument R29 Operating Condition SpecificationPVC-4 LIQ Press. Nor.Rate Max.Rate Vapor Input Cv Size
Rating
Port Mat'l Action Acces- LineTag no. Service No. Fluid STM Up P Temp. L:kg/h L:kg/h Density M.W. Signal Cal. (inch) Type (Note 2) sories Size M'F'R
Or Stream S:kg/h S:kg/h (kg/m3) Visc. Select Body (Note 1) Body (Note 3) (Note 4) Spec.
GAS G:Nm3/h G:Nm3/h (C.P.) Port Trim
(kg/cm2G) (OC)
(kg/cm2G)TCV-502 EA-503 1 CWR L 4 0.5 30 150,000 175,000 1000 1.0 I/P 109.2 6 JIS S A216WCB C B 6 M.S
OUTLET 275 5 10K RF E SUS316L A1K
TCV-513 TCV-502 EA-505 1 LS S 7 0.5 170 830 4 I/P 2 1/2 JIS E SCPH2 C B.R 2 1/2 M.SINLET 81 2 1/2 10K RF 2,5 A1S-H
TCV-515 TCV-503 FA-505 1 LS S 7 5 170 40 4 I/P 1 JIS E 1 C 3/4 M.SINLET 1.5 1/4 10K RF 2,5 A3K-H
TCV-501 EA-501A/B 1 LS S 7 0.4 170 778 895 I/P 26.47 2 JIS S SCS13A C B 2INLET 50 2 10K RF E SUS316L A1K-H
TCV-702 TCV-701 FA-701 1 LS S 7 5 170 2,700 4 I/P 4 JIS E SCPH2 C B 4 M.SINLET 0 40 2 10K RF 2 A1S-H
TCV-801-1 EA-802 1 CWR L 4 0.5 30 10,000 1000 1.0 I/P 16.51 1 1/2 JIS S A216WCB O B 1 1/2 M.SOUTLET 30 1 1/2 10K RF E SUS316L A1S
TCV-801-2 TCV-801-2 FA-802 1 LS S 7 0.5 170 100 4 I/P 3/4 JIS E SCPH2 C B 1 M.SINLET 5.2 1/2 10K RF 2.5 A6S-H
HCV-303A/B DC-301A/B 2 RVCM GAS 3 0.2 75 24,104 27,719 9.2 0.012 I/P 441.1 8 ANSI S A216WCB C B 8TO FA-303 kg/hr kg/hr 700 8 150 RF E SUS316L A2S
HCV-503 GB-501 C 40SUCTION A2X
PCV-511 GB-503 C #1000SUCTION A2X-H
XSV-101 XSV-101 FA-111 1 PW L E/P 1 JIS B 12 C W(O).R 1 K.MINLET 1 10K RF 1,13 W(C) A1K
XSV-102 XSV-102 FA-111 1 CAT+ L E/P 1 JIS B 12 C W(O).R 1 K.MDISCHARGE PW 1 10K RF 1,13 W(C) A1K
XSV-103A/B XSV-103A/B GA-111 2 CAT+ L E/P 1 JIS B 12 C W(O).R 1 K.MDELIVERY PW 1 20K RF 1,13 W(C) B1K
XSV-105 XSV-105 GA-104 1 VCM L E/P 6 JIS B 12 C W(O).R 6 K.MDELIVERY 6 20K RF 12,14 W(C)H B1J
XSV-106 FSV-305 DC-301A/B 1 VCM L 5.3 0.5 34 13800 158700 884 0.21 E/P 6 JIS B 12 C W(O).R 6 K.MFEED 6 20K RF 12,14 W(C)A B1L
XSV-111 FA-111 1 AG2 L E/P 1 ANSI B CF8M F,RO W(O),R 1 AG- INLET 1 150 RF 316 SS W(C) A7K
XSV-301A/B XSV-301A/B DC-301A/B 2 DW L E/P 6 JIS B 12 C W(O)R 6 K.MFEED 6 20K RF 12,14 W(C)A A1K
Rx2XSV-302A/B XSV-302A/B DC-301A/B 2 VG G E/P 6 JIS B 12 C W(O)R 6 K.M
Page 7 of 26
TPC VINA PLASTIC AND CHEMICAL CORP.,LTDCONTROL VALVE SCHEDULE
PVC LINE 2 PROJECT
TAG NO.
Data from file : PV4 Instrument R29 Operating Condition SpecificationPVC-4 LIQ Press. Nor.Rate Max.Rate Vapor Input Cv Size
Rating
Port Mat'l Action Acces- LineTag no. Service No. Fluid STM Up P Temp. L:kg/h L:kg/h Density M.W. Signal Cal. (inch) Type (Note 2) sories Size M'F'R
Or Stream S:kg/h S:kg/h (kg/m3) Visc. Select Body (Note 1) Body (Note 3) (Note 4) Spec.
GAS G:Nm3/h G:Nm3/h (C.P.) Port Trim
(kg/cm2G) (OC)
(kg/cm2G)OUTLET 6 20K RF 12,14 W(C)A A1K
XSV-303A/B XSV-303A/B DC-301A/B 2 VCM L E/P 6 JIS B 12 C W(O)R 6 K.MFEED 6 20K RF 12,14 W(C)A B1L
XSV-304A/B XSV-304A/B DC-301A/B 2 AG19 L E/P 1 JIS B 1 C W(O)R 1 K.MFEED 1 20K RF 1,14 W(C)A A1K
XSV-305A/B XSV-305A/B DC-301A/B 2 AG-2 L E/P 1 JIS B 1 C W(O)R 1 1/2 K.MFEED 1 20K RF 1,14 W(C)A A1K
XSV-306A/B XSV-306A/B DC-301A/B 2 AG-3 L E/P 1 JIS B 1 C W(O)R 1 1/2 K.MFEED 1 20K RF 1,14 W(C)A A1K
XSV-307A/B XSV-307A/B DC-301A/B 2 AG-1 L E/P 1 JIS B 1 C W(O)R 1 1/2 K.MFEED 1 20K RF 1,14 W(C)A A1K
XSV-308A/B XSV-308A/B DC-301A/B 2 CAT L E/P 1 JIS B 1 C W(O)R 1 K.MFEED 1 20K RF 1,14 W(C)A B1K
XSV-309A/B DC2301A/B 2 AD-5 LIQ E/P 1 ANSI B CF8M F,RO W(O),R 1 FEED 1 300 RF 316 SS W(C) A7K-H
XSV-310A/B XSV-310A/B DC-301A/B 2 AD-3 L E/P 1 JIS B 1 C W(O)R 1 K.MFEED 1 20K RF 1,14 W(C)A A1K
XSV-311A/B XSV-311A/B DC-301A/B 2 R-VCM G E/P 8 JIS B 12 C W(O)R 1 K.MOUTLET 8 20K RF 12,14 W(C)H A2S
XSV-312A/B DC-301A/B 2 PW L E/P 2 ANSI B CF8M C W(O),R 2HEADER WASH 2 300 RF 316 SS W(C) A7K
XSV-313A/B DC-301A/B 2 PW L E/P 2 ANSI B CF8M C W(O),R 2HEADER WASH 2 150 RF 316 SS W(C) A7K
XSV-314A/B XSV-314A/B DC-301A/B 2 VCM G E/P 4 JIS B 12 C W(O)R 4 K.MEQ LINE 4 20K RF 12,14 W(C) B1L
XSV-315A/B XSV-315A/B DC-301A/B 2 AIR G E/P 3 JIS B 12 C W(O)R 3 K.MVENTILATION 3 20K RF 12,14 W(C) B1L
XSV-316A/B XSV-316A/B DC-301A/B 2 VG G E/P 6 JIS B 12 C W(O)R 6 K.MOUTLET 6 20K RF 12,14 W(C) B1L
XSV-317A/B XSV-317A/B AG-19 NOZZLE 2 PW L E/P 1 JIS B 1 C W(O)R 1 K.MFLUSHING 1 20K RF 1,14 W(C) B1L
XSV-318A/B XSV-318A/B DC-301A/B 2 PS.PW L E/P 10 JIS B 12 C W(O)R 8 K.MDISCHARGE 8 20K RF 1,13 W(C)H B1K
XSV-319A/B XSV-319A/B PRA-302A/B 2 VCM G E/P 1/2 JIS B 1 C W(O)R 1/2 K.MDETECT LINE 1/2 20K RF 1,14 W(C) B1L
XSV-320A/B DC-301A/B 2 WW LIQ E/P 8 ANSI B CF8M F,RO W(O),R 8DISCHARGE 8 300 RF 316 SS W(C) B1K
XSV-321A/B XSV-321A/B DC-301A/B 2 DW L E/P 1 JIS B 1 C W(O)R 1 K.MFLUSHING 1 20K RF 1,14 W(C) B1K
XSV-322A/B XSV-322A/B EA-303A/B 2 LS S E/P 6 JIS B SCPH C W(O)R 6 K.MINLET 6 10K RF 12,13 W(C) A2S-H
XSV-323A/B XSV-323A/B EA-301A/B 2 DW L E/P 1 JIS B 1 C W(O)R 1 K.MFEED 1 20K RF 1,14 W(C) B1K
XSV-324A/B XSV-324A/B EA-301A/B 2 R-VCM G E/P 1 JIS B 1 C W(O)R 1 K.MINERT 1 20K RF V W(C) A2S
Page 8 of 26
TPC VINA PLASTIC AND CHEMICAL CORP.,LTDCONTROL VALVE SCHEDULE
PVC LINE 2 PROJECT
TAG NO.
Data from file : PV4 Instrument R29 Operating Condition SpecificationPVC-4 LIQ Press. Nor.Rate Max.Rate Vapor Input Cv Size
Rating
Port Mat'l Action Acces- LineTag no. Service No. Fluid STM Up P Temp. L:kg/h L:kg/h Density M.W. Signal Cal. (inch) Type (Note 2) sories Size M'F'R
Or Stream S:kg/h S:kg/h (kg/m3) Visc. Select Body (Note 1) Body (Note 3) (Note 4) Spec.
GAS G:Nm3/h G:Nm3/h (C.P.) Port Trim
(kg/cm2G) (OC)
(kg/cm2G)
XSV-325A/B DC-301 2 DW L E/P 1 ANSI B CF8M F,RO W(O),R 1 DW MAIN 1 150 RF 316 SS W(C) B1K
XSV-326 FA-304 1 LS S E/P 3 ANSI B CF8M C W(O),R 33 150 RF 316 SS W(C) A6S-H
XSV-327 FA-304 1 PW L E/P 1 ANSI B CF8M C W(O),R 1 1 150 RF 316 SS W(C) A7K
XSV-328 FA-324 1 AFA L E/P 1 ANSI B CF8M C W(O),R 1 OUTLET 1 150 RF 316 SS W(C) A7K
XSV-329A/B CAT10 2 CAT10 LIQ E/P 3/4 ANSI B CF8M F,RO W(O),R 3/43/4 150 RF 316 SS W(C) A1A
XSV-330A/B CAT8 2 DW LIQ E/P 1/2 ANSI B CF8M F,RO W(O),R 1/21/2 300 RF 316 SS W(C) B6A
XSV-331A/B XSV-333A/B DC-301A/B 2 PS L E/P 8 JIS B 12 C W(O)R 8 K.MDISCHARGE AFA 8 20K RF 12,14 W(C) B1K
XSV-332A/B XSV-331A/B DC-301A/B 2 PS L E/P 8 JIS B 12 C W(O)R 8 K.MDISCHARGE 8 20K RF 12,14 W(C) B1K
XSV-333A/B XSV-332A/B DC-301A/B 2 PW L E/P 8 JIS B 12 C W(O)R 8 K.MRINSE WATER 8 20K RF 12,14 W(C) B1K
XSV-334A/B DC-301A/B 2 PW LIQ E/P 2 ANSI B CF8M F,RO W(O),R 22 150 RF 316 SS W(C) A7K
XSV-335 XSV-336 PW TO 1 PW L E/P 3 JIS B 12 C W(O)R 3 K.MDC-301A/B 3 20K RF 12,14 W(C) A1K
XSV-336 XSV-335 GA-308 1 PW L E/P 4 JIS B 12 C W(O)R 4 K.MDELIVERY 4 20K RF 12,14 W(C) A1K
XSV-337A/B DC-301A/B 2 CW L E/P 10 ANSI B CF8M C W(O),R 10JACKET 10 150 RF 316 SS W(C) A1S
XSV-339A/B DC-301A/B 2 VC GAS E/P 4 ANSI B CF8M C W(O),R 44 150 RF 316 SS W(C) A7K
XSV-343 FA-304 1 CAT-10 LIQ E/P 3/4 ANSI B CF8M C W(O),R 3/43/4 150 RF 316 SS W(C) A9A
XSV-341A/B-1 FA-302A/B 2 INH-3 LIQ E/P 1 ANSI B CF8M F,RO W(O),R 1 DELIVERY 1 150 RF 316 SS W(C) B2J-H
XSV-342A/B-1 DC-301A/B 2 INH-3 LIQ E/P 1 ANSI B CF8M F,RO W(O),R 1 TOP INLET 1 150 RF 316 SS W(C) B2J-H
XSV-343A/B-1 FA-302A/B 2 INH-3 LIQ E/P 3/4 ANSI B CF8M F,RO W(O),R 3/4PURGE 3/4 150 RF 316 SS W(C) B2J-H
XSV-341A/B-2 FA-302A/B 2 INH-3 LIQ E/P 1 ANSI B CF8M F,RO W(O),R 1 DELIVERY 1 300 RF 316 SS W(C) C1K
XSV-342A/B-2 DC-301A/B 2 INH-3 LIQ E/P 1 ANSI B CF8M F,RO W(O),R 1 TOP INLET 1 300 RF 316 SS W(C) C1K
XSV-343A/B-2 FA-302A/B 2 INH-3 LIQ E/P 3/4 ANSI B CF8M F,RO W(O),R 3/4PURGE 3/4 300 RF 316 SS W(C) C1K
XSV-349 EE-302 1 RCS-1 LIQ E/P 1 ANSI B CF8M C W(O),R 1 INLET 1 150 RF 316 SS W(C) A1K
Page 9 of 26
TPC VINA PLASTIC AND CHEMICAL CORP.,LTDCONTROL VALVE SCHEDULE
PVC LINE 2 PROJECT
TAG NO.
Data from file : PV4 Instrument R29 Operating Condition SpecificationPVC-4 LIQ Press. Nor.Rate Max.Rate Vapor Input Cv Size
Rating
Port Mat'l Action Acces- LineTag no. Service No. Fluid STM Up P Temp. L:kg/h L:kg/h Density M.W. Signal Cal. (inch) Type (Note 2) sories Size M'F'R
Or Stream S:kg/h S:kg/h (kg/m3) Visc. Select Body (Note 1) Body (Note 3) (Note 4) Spec.
GAS G:Nm3/h G:Nm3/h (C.P.) Port Trim
(kg/cm2G) (OC)
(kg/cm2G)XSV-350 INLET 1 MS STM E/P 1 1/2 ANSI B CF8M C W(O),R 1 1/2
FE-302 1 1/2 300 RF 316 SS W(C) B1S-H
XSV-348A/B EA-301A/B TOP 2 PW L E/P 2 ANSI B CF8M C W(O),R 2RINSE VALVE 2 300 RF 316 SS W(C) B1K
XSV-353A/B DC-301A/B SIDE 2 PW L E/P 2 ANSI B CF8M C W(O),R 2RINSE VALVE 2 300 RF 316 SS W(C) B1J
XSV-354A/B DC-301A/B SIDE 2 PW L E/P 2 ANSI B CF8M C W(O),R 2RINSE VALVE 2 300 RF 316 SS W(C) B1J
XSV-359A/B RCS-1 2 RCS-1 LIQ E/P 1 1/2 ANSI B CF8M C W(O),R 1 1/2TO DC-301A/B 1 1/2 300 RF 316 SS W(C) B1K-H
XSV-361 XSV-361 GB-301 1 VG G E/P 6 JIS B SCPH2 C W(O)R 6 K.MSUCTION 6 10K RF 12,13 W(C) A1S
XSV-362 XSV-362 EJECTOR 1 AIR G E/P 2 1/2 JIS B SCPH2 C W(O)R 2 1/2 K.M1SUCTION 2 1/2 10K RF 12,13 W(C) A1S
XSV-363 XSV-363 GB-301 1 IW G E/P 1 1/2 JIS B SCPH2 C W(O)R 1 1/2 K.MSEAL 1 1/2 10K RF 12,13 W(C) A1S
XSV-368A/B INLET 2 AFA L E/P 1 1/2 ANSI B CF8M C W(O),R 1 1/2DC-301A/B 1 1/2 300 RF 316 SS W(C) B1K-H
XSV-369A/B INLET 2 AFA L E/P 1 1/2 ANSI B CF8M C W(O),R 1 1/2DC-301A/B 1 1/2 300 RF 316 SS W(C) B1K-H
XSV-370A/B INLET 2 RCS-1 L E/P 1 1/2 ANSI B CF8M C W(O),R 1 1/2DC-301A/B 1 1/2 300 RF 316 SS W(C) B1K-H
XSV-371 XSV-371 FD-301 1 PW L E/P 3 JIS B 12 C W(O)R 3 K.MINLET 3 10K RF 12,13 W(C) A1K
XSV-372 XSV-372 GA-301 1 PW L E/P 1/2 JIS B SCH14 C W(O)R 1/2 K.MSEAL 1/2 10K RF SCS14,13 W(C) A1K
XSV-373 GA-301 1 PS SLUR E/P 6 ANSI B CF8M C W(O),R 6DISCHARGE RY 6 150 RF 316 SS W(C) A1K
XSV-374A/B DC-301A/B 2 DPW LIQ E/P 2 ANSI B CF8M C W(O),R 22 150 RF 316 SS W(C) A7K
XSV-375 FA-310 1 DPW L E/P 4 ANSI B CF8M C W(O),R 4INLET 4 150 RF 316 SS W(C) A7K
XSV-376 GA-301 1 PS SLUR E/P 6 ANSI B CF8M C W(O),R 6RY 6 150 RF 316 SS W(C) A7K
XSV-377 FA-310 1 PS SLURRY E/P 6 ANSI B CF8M C W(O),R 6INLET 6 150 RF 316 SS W(C) A9K
XSV-378 FA-310 1 EQ G E/P 4 ANSI B CF8M C W(O),R 44 150 RF 316 SS W(C) A9K
XSV-379 FA-304 1 LEQ GAS E/P 3 ANSI B CF8M F,RO W(O),R 33 150 RF 316 SS W(C) A9K
Rx2XSV-380 FA-304 1 LEQ GAS E/P 4 ANSI B CF8M F,RO W(O),R 4
4 150 RF 316 SS W(C) A9K
XSV-381 FA-304 1 PS SLUR E/P 6 ANSI B CF8M C W(O),R 6RY 6 150 RF 316 SS W(C) A7K
XSV-382 FA-304 1 RVCM GAS E/P 8 ANSI B CF8M C W(O),R 8
Page 10 of 26
TPC VINA PLASTIC AND CHEMICAL CORP.,LTDCONTROL VALVE SCHEDULE
PVC LINE 2 PROJECT
TAG NO.
Data from file : PV4 Instrument R29 Operating Condition SpecificationPVC-4 LIQ Press. Nor.Rate Max.Rate Vapor Input Cv Size
Rating
Port Mat'l Action Acces- LineTag no. Service No. Fluid STM Up P Temp. L:kg/h L:kg/h Density M.W. Signal Cal. (inch) Type (Note 2) sories Size M'F'R
Or Stream S:kg/h S:kg/h (kg/m3) Visc. Select Body (Note 1) Body (Note 3) (Note 4) Spec.
GAS G:Nm3/h G:Nm3/h (C.P.) Port Trim
(kg/cm2G) (OC)
(kg/cm2G)8 150 RF 316 SS W(C) A9K
XSV-383 RINSE 1 DPW LIQ E/P 2 ANSI B CF8M C W(O),R 2WATER 2 150 RF 316 SS W(C) A7K
XSV-384 FA-304 1 DW L E/P 1 ANSI B CF8M F,RO W(O),R 1 1 150 RF 316 SS W(C) B2J
XSV-385 FA-304 1 PS SLURRY E/P 8 ANSI B CF8M C W(O),R 8OUTLET 8 150 RF 316 SS W(C) A9K
XSV-386 FA-304 1 PW LIQ E/P 2 ANSI B 13 C W(O),R 22 150 RF CF8M W(C) A7K
316 SSXSV-387 FA-304 1 AD5 LIQ E/P 1 ANSI B CF8M C W(O),R 1
1 150 RF 316 SS W(C) A7K-H
XSV-388 FA-311 1 IA G E/P 1 ANSI B CF8M C W(O),R 1 1 150 RF 316 SS W(C) A5X
XSV-389 FA-311 1 IA G E/P 1 ANSI B CF8M C W(O),R 1 1 150 RF 316 SS W(C) A5X
XSV-390 FA-311 1 IA G E/P 1/2 ANSI B CF8M C W(O),R 1/2
1/2 150 RF 316 SS W(C) A5X
XSV-391A/B HCV-301A/B DC-301A/B 2 DW.VCM L P 8 JIS B 12 C W(O)H 8 K.MHEADER 8 20K RF 12,14 W(C) B1L
XSV-392A/B HCV-302A/B DC-301A/B 2 PW,VCM L P 8 JIS B 12 C W(O)H 8 K.MHEADER 8 20K RF 12,13 W(C) B1L
XSV-393 FA-310 1 PS SLURRY E/P 8 ANSI B CF8M F,RO W(O),R 8OUTLET 8 150 RF 316 SS W(C) A9K
XSV-394 GA-302 1 PS SLURRY E/P 8 ANSI B CF8M F,RO W(O),R 8INLET 8 150 RF 316 SS W(C) A9K
XSV-395 FD-302 1 PW L E/P 1 1/2 ANSI B CF8M C W(O),R 1 1/2INLET 1 1/2 150 RF 316 SS W(C) A7K
XSV-396 FD-302 1 VG G E/P 1 ANSI B CF8M C W(O),R 1 OUTLET 1 150 RF 316 SS W(C) A9A
XSV-397 FD-302 1 PS SLURRY E/P 6 ANSI B CF8M C W(O),R 6OUTLET 6 150 RF 316 SS W(C) A9K
XSV-398 GA-302 1 PW L E/P 1 ANSI B CF8M C W(O),R 1 SEAL WATER 1 150 RF 316 SS W(C) A7K
XSV-399 IA FROM 1 IA G E/P 1 ANSI B CF8M C W(O),R 1 FA-311 1 150 RF 316 SS W(C) A5K
XSV-401 XSV-401 EA-302 TO 1 RVCM G E/P 6 JIS B SCPH2 C W(O)R 6 K.MFA-403 6 10K RF 12,13 W(C) A2S
XSV-402 XSV-402 GB-402 1 RVCM G E/P 6 JIS B SCPH2 C W(O)R 6 K.MSUCTION 6 10K RF 12,13 W(C) A2S
XSV-403 XSV-403 GB-401 1 RVCM G E/P 6 JIS B SCPH2 C W(O)R 6 K.MSUCTION 6 10K RF 12,13 W(C) A2S
XSV-404 XSV-404 GB-402 1 RVCM G E/P 6 JIS B SCPH2 C W(O)R 6 K.MSUCTION 6 10K RF 12,13 W(C) A2S
XSV-415 GA-403A/B 1 RVCM L E/P 1 ANSI B CF8M F,RO W(O),R 1 DISCHARGE 1 300 RF 316 SS W(C) B1A
Page 11 of 26
TPC VINA PLASTIC AND CHEMICAL CORP.,LTDCONTROL VALVE SCHEDULE
PVC LINE 2 PROJECT
TAG NO.
Data from file : PV4 Instrument R29 Operating Condition SpecificationPVC-4 LIQ Press. Nor.Rate Max.Rate Vapor Input Cv Size
Rating
Port Mat'l Action Acces- LineTag no. Service No. Fluid STM Up P Temp. L:kg/h L:kg/h Density M.W. Signal Cal. (inch) Type (Note 2) sories Size M'F'R
Or Stream S:kg/h S:kg/h (kg/m3) Visc. Select Body (Note 1) Body (Note 3) (Note 4) Spec.
GAS G:Nm3/h G:Nm3/h (C.P.) Port Trim
(kg/cm2G) (OC)
(kg/cm2G)
XSV-416 EA-404 1 RVCM L E/P 1 ANSI B CF8M C W(O),R 1 1 150 RF 316 SS W(C) A9A
XSV-421 XSV-407 FA-407 1 INH-1 L E/P 1 JIS B SCPH2 C W(O)R 1 K.MINLET 1 10K RF 12,13 W(C) A2S
XSV-422 XSV-405 FA-407 1 INH-1 L E/P 1 JIS B SCPH2 C W(O)R 1 K.MINLET 1 10K RF 12,13 W(C) A7K
XSV-423 GA-403A/B 1 INH-1 L E/P 1 ANSI B CF8M C W(O),R 1 DISCHARGE 1 150 RF 316 SS W(C) A9A
XSV-424 FA-802 1 VG GAS E/P 1/2 ANSI B CF8M F,RO W(O),R 1/2INLET 1/2 150 RF 316 SS W(C) A7K
XSV-425 XSV-411 FA-403 1 RVCM GAS E/P 2 JIS B 6 C W(O).R 2 KITZBOTTOM 2 10K RF 1,15 W(C) A5S
XSV-426A/B/C XSV-408 DA-401A/B/C 3 RVCM GAS E/P 1 1/2 JIS B 6 C W(O).R 1 1/2 KITZXSV-409 1 1/2 10K RF 1,15 W(C) A2SXSV-410
XSV-427 XSV-413 DA-401A/B/C 1 PW LIQ E/P 1 ANSI B 6 C W(O).R 1 1/2 KITZBOTTOM 1 150 RF 1,15 W(C) A1S-H
XSV-430 VCM FROM 1 VCM L E/P 6 ANSI B CF8M C W(O),R 6GA-404A/B 6 300 RF 316 SS W(C) B1J-C
XSV-431 FA-404 1 VCS L E/P 2 ANSI B CF8M C W(O),R 2INLET 2 300 RF 316 SS W(C) B2J
XSV-433 GA-404A/B 1 VCS L E/P 2 ANSI B CF8M C W(O),R 2CIRCULATION 2 300 RF 316 SS W(C) B6A
XSV-501 FA-501B/C 1 PS SLURRY E/P 4 ANSI B CF8M F,RO W(O),R 44 150 RF 316 SS W(C) A3J
Rx2XSV-502 FA-501B/C 1 PS SLURRY E/P 4 ANSI B CF8M F,RO W(O),R 4
4 150 RF 316 SS W(C) A3JRx2
XSV-507A/B XSV-501A/B GF-501A/B 2 PS SLURRY E/P 2 1/2 JIS B 12 C W(O)R 3 K.MSUCTION 2 1/2 10K RF 1,13 W(C) A1K-P
XSV-509 FA-501B/C 1 PW LIQ E/P 1 ANSI B CF8M F,RO W(O),R 1 RETURN LINE 1 150 RF 316 SS W(C) A1K
XSV-511 EQ LINE 1 LEQ GAS E/P 3 ANSI B CF8M F,RO W(O),R 3TO FA-304 3 150 RF 316 SS W(C) A9K
XSV-513-1~4 LS INLET 4 LS STM E/P 1 ANSI B CF8M F,RO W(O),R 1 DA-501 1 150 RF 316 SS W(C) A3K-H
XSV-514 XSV-506 FD-505 TO 1 PW L E/P 1 JIS B 12 C W(O)R 1 K.MDA-501 1 10K RF 1,13 W(C) A7K
XSV-515B/C FA-501B/C 2 PW LIQ E/P 1 ANSI B CF8M F,RO W(O),R 1 AERATION RING 1 150 RF 316 SS W(C) A1K
XSV-516B/C FA-501B/C 2 AIR GAS E/P 4 ANSI B CF8M F,RO W(O),R 4AERATION RING 4 150 RF 316 SS W(C) A1K-P
XSV-517B/C FA-501B/C 2 LS STM E/P 2 ANSI B CF8M F,RO W(O),R 2AERATION RING 2 150 RF 316 SS W(C) A1K-H
XSV-518A FA-501A/B/C 1 PW LIQ E/P 2 ANSI B CF8M C W(O),R 22 150 RF 316 SS W(C) A7K
Page 12 of 26
TPC VINA PLASTIC AND CHEMICAL CORP.,LTDCONTROL VALVE SCHEDULE
PVC LINE 2 PROJECT
TAG NO.
Data from file : PV4 Instrument R29 Operating Condition SpecificationPVC-4 LIQ Press. Nor.Rate Max.Rate Vapor Input Cv Size
Rating
Port Mat'l Action Acces- LineTag no. Service No. Fluid STM Up P Temp. L:kg/h L:kg/h Density M.W. Signal Cal. (inch) Type (Note 2) sories Size M'F'R
Or Stream S:kg/h S:kg/h (kg/m3) Visc. Select Body (Note 1) Body (Note 3) (Note 4) Spec.
GAS G:Nm3/h G:Nm3/h (C.P.) Port Trim
(kg/cm2G) (OC)
(kg/cm2G)XSV-518B/C FA-501A/B/C 1 PW LIQ E/P 2 ANSI B CF8M C W(O),R 2
2 150 RF 316 SS W(C) A1K
XSV-520A/B XSV-507A/B GF-501A/B 2 PW L E/P 1 JIS B 12 C W(O)R 1 K.MSUCTION LINE 1 10K RF 1,13 W(C) A1K
XSV-521A/B GF-501A/B 2 PW LIQ E/P 1/2 ANSI B CF8M F,RO W(O),R 1/21/2 150 RF 316 SS W(C) A1K
XSV-524B/C XSV-502A/B FA-501B 1 PS SLURRY E/P 4 JIS B 12 C W(O)R 4 K.MBOTTOM 4 10K RF 1,13 W(C) A1K
XSV-525B/C XSV-503A/B FA-501A 1 PW L E/P 1 1/2 JIS B 12 C W(O)R 1 1/2 K.MBOTTOM LINE 1 1/2 10K RF 1,13 W(C) A1K
XSV-527 EA-501 1 PW LIQ E/P 2 ANSI B CF8M C W(O),R 22 150 RF 316 SS W(C) A7K
XSV-528 EA-501 1 PW LIQ E/P 2 ANSI B CF8M C W(O),R 22 150 RF 316 SS W(C) A7K
XSV-531 PW 1 PW LIQ E/P 1 ANSI B CF8M C W(O),R 1 FLUSHING 1 150 RF 316 SS W(C) A1K
XSV-808 XSV-801 GB-801 1 R-VCM GAS E/P 3 JIS B SCPH2 C W(O) R 3 K.MSUCTION 3 10K RF 1,13 W(C) A2S
XSV-801 FA-804 1 RVCM GAS E/P 1 ANSI B CF8M F,RO W(O),R 1 1 150 RF 316 SS W(C) A9A
XSV-802 BOTTOM 1 WW LIQ E/P 1 1/2 ANSI B CF8M F,RO W(O),R 1 1/2FA-804 1 1/2 150 RF 316 SS W(C) A5S
XSV-803 FA-802 1 RVCM GAS E/P 2 ANSI B CF8M F,RO W(O),R 2RVCM TO FA-403 2 150 RF 316 SS W(C) A9A
XSV-806 INLET 1 RVCM GAS E/P 3 ANSI B CF8M F,RO W(O),R 3GB-801 3 150 RF 316 SS W(C) A2S
EMV-102 XSV-104 FA-1105 1 VCM L E/P 8 JIS B 12 C W(O).R 8 K.MDIS CHARGE 8 10K RF 12,13 W(C)H A1L-C
PCV-910 LS 1 LS S 7 0.5 170 2.1 5.00 I/P 82.38 4 JIS S A216WCB C B 8MAIN Ton/hr Ton/hr 175 4 20K RF E SUS316L B1A-H
PCV-902 PCV-902 FF-501 1 LS S 7 5 176 100 4 1 JIS SCPH2 C 2TRACE 1 10K RF 2 A1S
HCV-504
Page 13 of 26
TPC VINA PLASTIC AND CHEMICAL CORP.,LTDCONTROL VALVE SCHEDULE
PVC LINE 2 PROJECT
TAG NO.
Data from file : PV4 Instrument R29 Operating Condition SpecificationPVC-4 LIQ Press. Nor.Rate Max.Rate Vapor Input Cv Size
Rating
Port Mat'l Action Acces- LineTag no. Service No. Fluid STM Up P Temp. L:kg/h L:kg/h Density M.W. Signal Cal. (inch) Type (Note 2) sories Size M'F'R
Or Stream S:kg/h S:kg/h (kg/m3) Visc. Select Body (Note 1) Body (Note 3) (Note 4) Spec.
GAS G:Nm3/h G:Nm3/h (C.P.) Port Trim
(kg/cm2G) (OC)
(kg/cm2G)
Page 14 of 26
References P&IDand/or balance
Remarks No.
D005,6CW Item 3,4
D010420
D012A###
D012A508
D013701
D012A526
D022Summary
D004###
D008405
D006A###
D016FA2308
D007###
D007###
D009407
D009410
D012A516
D018710
D019804
D019###
D019###
D022
PRESS. REGULATOR VALVE D001
PRESS. REGULATOR VALVE D002
Page 15 of 26
References P&IDand/or balance
Remarks No.
PRESS. REGULATOR VALVE D004A
D004###
D004###
D006A###
D006B###
PRESS. REGULATOR VALVE D006A
PRESS. REGULATOR VALVE D004A
D009412
D009414
SPLIT RANGE D010Data sheet
EA404SPLIT RANGE D010
416
D010EA2403
D012A526
D019803
D019###
SPLIT RANGE D019Copy from L-5
Page 16 of 26
References P&IDand/or balance
Remarks No.
SPLIT RANGE D019Copy from L-5
SPLIT RANGE D005,6EA230A/B
SPLIT RANGE D005,6EA2301A/B
D005,6EA2303A/B
D008EA2302
SPLIT RANGE D009EA2402
SPLIT RANGE D009FA2402
Page 17 of 26
References P&IDand/or balance
Remarks No.
D012AEA2503
D013EA2505
D014FD2502
D012EA2501A/B
D018FA2701
SPLIT RANGE D019EA2802
SPLIT RANGE D019FA2701
D005,6
D013
D013
D002
D002
D002
D003
D003106+422
D002
D005,6
D005,6
Page 18 of 26
References P&IDand/or balance
Remarks No.
D005,6
D005,6
D005,6
D005,6
D005,6
D005,6
D005,6
D005,6
D005,6
D005,6
D005,6
D005,6
D005,6
D005,6
5D2
D005,6
D005,6
D005,6
D005,6
D005,6
D005,6
D005,6
Page 19 of 26
References P&IDand/or balance
Remarks No.
D005,6
D006B
D006B
D004A
D005,6
D005,6
D005,6
D005,6
D005,6
D005,6
D007
D007
D005,6
D005,6
D006B
D005,6
D005,6
D005,6
D005,6
D005,6
D005,6
D004A
Page 20 of 26
References P&IDand/or balance
Remarks No.
D004A
D005,6
D005,6
D005,6
D004A
D015
D015
D015
D005,6
D005,6
D005,6
D006A
D006A
D006A
D005,6
D006B
D005,6
D006B
D006B
D006B
D006B
D006B
D006B
Page 21 of 26
References P&IDand/or balance
Remarks No.
D006B
D006B
D006B
D006B
D006B
D006A
D006A
D006A
D005,6
D005,6
D006B
D006B
D006B
D006B
D006B
D006B
D006A
D009
D009
D009
D009
D010
Page 22 of 26
References P&IDand/or balance
Remarks No.
D010
D009
D009
D010
D019
D010
D010
D010
D003
D010B
D010B
D012
D012
D012A
D012A
D011A
D012A
D012A
D012
D012
D012
D011A
Page 23 of 26
References P&IDand/or balance
Remarks No.
D012
D012A
D012A
D012
D012
D012A
D012A
D012
D019
D019
D019
D019
D019
D003
D001-1
SELF ACTUATED D001-1VALVE MODEL.481-S Copy from L-5
Page 24 of 26
References P&IDand/or balance
Remarks No.
VINA L-2 PVC-4 CAUSE NO. SIZE TYPE PRICE(THB)FCV-316A-1/2 FCV-316A-1/2 Obsolete 2 10 BUTTERFLY 500,000FCV-503 FCV-502 Open 92% 1 4 GLOBE 400,000FCV-506A/B HCV-501A/B Body leak 2 2 1/2 V-BALL 250,000LCV-803 LCV-803 Open > 100% 1 1 GLOBE 100,000PCV-404 TCV-402 Damage 1 8 GLOBE 800,000TCV-301A/B-1 TCV-301A/B-1 Obsolete 2 8 BUTTERFLY 450,000TCV-301A/B-2 TCV-301A/B-2 Obsolete 2 6 BUTTERFLY 450,000TCV-401-1 TCV-401-1 Damage 1 3 GLOBE 300,000TCV-401-2 TCV-401-2 Damage 1 1 GLOBE 100,000XSV-312A/B XSV-312A/B Expand pipe size 2 2 BALL 100,000XSV-313A/B XSV-313A/B Expand pipe size 2 2 BALL 100,000TCV-501 TCV-501 Open 95% 1 8 GLOBE 800,000FCV-511 FCV-504 Open > 100% 1 6 GLOBE 550,000
TOTAL 19
SpareXSV-111
XSV-309A/B
* รอ Update รายการซื้��อใหม่�ก บ ACK
AMOUNT1,000,000
400,000500,000100,000800,000900,000900,000300,000100,000200,000200,000800,000550,000
6,750,000