220kV SWITCHYARD AREA

16
Office Quarter Guard room Store room Control room Quarter -8 ;#4& 0'9 $*#4#6274 1.& *'6#7&# $75 %172.'4 2+ 2+ N ELECTRICAL LAYOUT PLAN 220kV SWITCHYARD AREA 132kV SWITCHYARD AREA 11kV Line Take off Tower/Beam 132kV Cable Termination Yard 132kV Cable Termination Yard 220/132 KV Tower NOT IN SCOPE 4--4 Office Guest House Canteen POST INSULATORS 24000 24000 400kV GIS LAYOUT OF HETAUDA SUBSTATION FOR TENDER PURPOSE ONLY DRAWING NO. NEA-HDI-H-E-LY-01 OF 01

Transcript of 220kV SWITCHYARD AREA

Page 1: 220kV SWITCHYARD AREA

Office

Quarter

Guard room

Store room

Control room

Quarter

N

ELECTRICAL LAYOUT PLAN

220kV

SW

ITC

HY

AR

D A

RE

A

132kV

SW

ITC

HY

AR

D A

RE

A

11kV

Lin

e T

ake o

ff Tow

er/B

eam

132kV

Cable

Term

inatio

n Y

ard

132kV

Cable

Term

inatio

n Y

ard

220/1

32 K

V T

ow

er

NO

T IN

SC

O

PE

4--4

OfficeGuest

House

Canteen

POST INSULATORS

24000

24000

400kV GIS LAYOUT OF HETAUDA SUBSTATION

FOR TENDER PURPOSE ONLY

DRAWING NO.

NEA-HDI-H-E-LY-01 OF 01

Page 2: 220kV SWITCHYARD AREA

ELECTRICAL LAYOUT PLAN

400kV GIS LAYOUT OF INARUWA SUBSTATION

FOR TENDER PURPOSE ONLY

DRAWING NO.

NEA-HDI-I-E-LY-01 OF 01

Page 3: 220kV SWITCHYARD AREA

SINGLE LINE DIAGRAM

HETAUDA 400/220KV GIS SUBSTATION SLD

FOR TENDER PURPOSE ONLY

DRAWING NO.

FROM DHALKEBAR NEPAL

400 KV D/C

QUAD MOOSE ACSR LINE

400 KV D/C

FUTURE LINE

400/220 KV

ICT BAY

FROM NAUBISE NEPAL

400 KV D/C

QUAD MOOSE ACSR LINE

400/220 KV

ICT BAY

Future

NEA-HDI-H-SLD-01 OF 01

Page 4: 220kV SWITCHYARD AREA

FROM DHALKEBAR NEPAL

400 KV D/C

QUAD MOOSE ACSR LINE

400 KV D/C

FUTURE LINE

400 KV D/C

FUTURE LINE

SINGLE LINE DIAGRAM

INARUWA 400/220KV GIS SUBSTATION SLD

DRAWING NO. NEA-HDI-I-SLD-01 OF 01

FOR TENDER PURPOSE ONLY

Page 5: 220kV SWITCHYARD AREA

'A'

DETAIL'A'

NEA-HDI-H/I -FEN-01 OF 01

FOR TENDER PURPOSE ONLY

REV DATE REV

STANDARD DETAIL FOR SWITCHYARD CHAINLINK FENCING

Page 6: 220kV SWITCHYARD AREA

13

400KV GIS HALL

1 2 3

SIDE WALL ELEVATION @ GL- L

3

2

1

F.G.L0.00 M. LVL.

F.F.L.+0.500 M. LVL.

750

12 MM THK. FINAL FINISHIN 1:4 CEMENT MORTAR

50 MM THK. P.C.C. IN 1:2:4

75MM THK. COMPACTED RUBBLE PACKING

WELL COMPACTED EARTH

FOR TENDER PURPOSE ONLY

REV DATE REV

GIS BUILDING GENRAL LAYOUT

DRAWING NO:

NOTES

1. THIS DRAWINGS SHOWS A TYPICAL LAYOUT OF 400/220 KVGIS SUBSTATION. THE BIDDER SHALL SUBMIT THE LAYOUT OFGIS BUILDING AS PER TECHNICAL SPECIFICATION AND THESAME WOULD BE FINALIZED AFTER THE APPROVAL OF OWNER.

2. ALL DIMENSION ARE IN MM AND ELEVATION IN METERS3. DRAWINGS IS NOT IN SCALE4. THE REQUIREMENT OF THE PRE-ENGINEERED BUILDING IS AS

PER TS AND BPS

NEA-HDI-H/I -PEB-01 OF 01

Page 7: 220kV SWITCHYARD AREA
Page 8: 220kV SWITCHYARD AREA

(M

IN

.)

75X6 M.S. FLAT

(TYP)

`E'

1100 (M

AX

.)

F.G.L.

`E'

F.G.L.

P.C.C. 1:4:8 (TYP)

SECTION 2-2

F.G.L. F.G.L.

50X50X6 CABLE

SUPPORT ANGLE

SECTION 4-4

P.C.C. 1:4:8 (TYP)

50X50X6 CLEAT

TO BE WELDED

EARTHING CONDUCTOR

`E'(50X6 M.S. FLAT)

L50X50X6

75X6 M.S FLAT INSERT

CABLE TRENCH WALL

50X6 FLAT TO

BE WELDED

TYPICAL CABLE SUPPORT

80

0 (M

AX

.)

F.G.L. F.G.L.

PLAN CABLE TRAY SUPPORT FOR

SECTION 2-2,2A-2A, 3-3 AND 4-4

SECTION 3-3

P.C.C. 1:4:8 (TYP)

NEA-HDI-H/I -CT-01 OF 05

75X6 M.S

FLAT INSERT

TYP.

50X50X6 CLEAT

ANGLE

TYP.

(M

IN

.)

1100 (M

AX

.)

F.G.L. F.G.L.

P.C.C. 1:4:8 (TYP)

SECTION 2A-2A

`E'

FOR TENDER PURPOSE ONLY

REV DATE REV

CABLE TRENCHESDETAIL OF CABLE TRENCH SECTIONS

Page 9: 220kV SWITCHYARD AREA

75x6

M.S. FLAT

8 M.S. ROD WELDED TO

M/S FLAT @ 750 C/C

TYPICAL DETIAL OF ANCHORING

75X6 M.S.FLAT

CABLE TRENCH WALL

10 M.S. ROD

DETAIL OF LIFTING HOOK

SIDE WALL OF CABEL TRENCH

C

L

OF LIFTING HOOK (TYP) TRENCH COVER SLAB

FOR SECTION (2-2,2A-2A)

DETAIL OF TRENCH COVER SLAB

FOR SECTION (3-3),(4-4)

DETAIL OF TRENCH COVER SLAB

SIDE WALL OF CABEL TRENCH

1050 FOR SECTION 3-3

600 FOR SECTION 4-4

OF LIFTING HOOK (TYP)C

L

HOOK (TYP)

OF LIFTING

C

L

HOOK (TYP)

OF LIFTING

C

L

SLEEVE (TYP.)

NEA-HDI-H/I -CT-02 OF 05

FOR TENDER PURPOSE ONLY

REV DATE REV

CABLE TRENCHESDETAIL OF CABLE TRENCH SECTIONS

Page 10: 220kV SWITCHYARD AREA

(DETAIL OF TRENCH COVER

FOR SECTION A-A)

PLAN

FOR SECTION B-B,C-C & D-D )

(DETAIL OF TRENCH COVER

SECTION X-X

SECTION 2-2

8 @ 175 C/C

8 @ 175 C/C

8 @ 200 C/C

F.G.L.

SECTION 3-3

F.G.L.

F.G.L.

SECTION 4-4

F.G.L.

F.G.L.

HOOK (TYP)

OF LIFTING

C

L

HOOK (TYP)

OF LIFTING

C

L

SECTION Y-Y

SECTION 2A-2A

8 @ 175 C/C

8 @ 175 C/C

8 @ 200 C/C

F.G.L.

NEA-HDI-H/I -CT-03 OF 05

FOR TENDER PURPOSE ONLY

REV DATE REV

CABLE TRENCHESDETAIL OF CABLE TRENCH SECTIONS

Page 11: 220kV SWITCHYARD AREA

C

L

OF

10 @170 C/C

X

10 @ 170 C/C

SECTION 3-3

10 @170 C/C

10 @170 C/C

250Ø HUME PIPE

AND SUMP PIT

5 NOS. PRECAST R.C.C.

COVER SLAB

PRECAST R.C.C.

COVER SLAB

975X400X50

3450X400X50 THK.

L 50X50X5

(TYP)

PRECAST R.C.C.

COVER SLAB

2475X400X50

FORMATION LEVEL

(±) 0.00M

TOP PLAN OF SUMP PIT

10 @170 C/C

(BOTH FACE BOTHWAYS)

10 170 C/C (TOP & BOTTOM) BOTH WAYS

6 NOS 16 LUGS

SECTION D-D

DETAIL OF LIFTING HOOK

TYPICAL DETAIL OF

SLAB SUPPORT

50x50x5 (TYP.)

8 3 NOS.

8 @250 C/C

D D

3 3

E

E

SECTION E-E

50x50x5 (TYP.)

LIFTING HOOK

8 3 NOS.

8 @250 C/C

10 M.S. ROD

SLEEVE (TYP.)

DETAIL 'X'

10 @170 C/C

(BOTH FACE

BOTH WAYS)

75 THK.

P.C.C. 1:4:8

CABLE

TRENCH WALL

TRENCH

COVER

NEA-HDI-H/I -CT-04 OF 05

FOR TENDER PURPOSE ONLY

REV DATE REV

CABLE TRENCHESGA AND RC DETAIL OF SUMP PIT

Page 12: 220kV SWITCHYARD AREA

CABLE TRENCH SECTION B-B CROSSING ROAD

G.L.G.L.

P.C.C. (1:2:4)P.C.C. (1:4:8:) (TYP)

150 THK P.C.C.

BRICK MASONARY IN 1:6

CEMENT SAND MORTAR

INVERT LVL.

LONGITUDUNAL SECTION THROUGH CABLE TRENCH CROSSING ROAD

CABLE TRENCH SECTION A-A CROSSING ROAD

G.L.G.L.

TOP OF ABUTMENT

TOP OF ROAD

EARTH FILLING

S

75 THK P.C.C.(1:4:8)

P.C.C. (1:2:4:)

150 O PVC PIPE FOR OFC

G.L.G.L.

TOP OF ABUTMENT

TOP OF ROAD

EARTH FILLING

S

75 THK P.C.C.(1:4:8)

P.C.C. (1:2:4:)

150 O PVC PIPE FOR CONTROL CABLE

CABLE TRENCH SECTION C-C CROSSING ROAD

G.L.G.L.

TOP OF ABUTMENT

TOP OF ROAD

EARTH FILLING

S

75 THK P.C.C.(1:4:8)

P.C.C. (1:2:4:)

150 O PVC PIPE

R.C.C. HUME PIPE

CLASS NP-3 (TYP)

R.C.C. HUME PIPE

CLASS NP-3 (TYP)

R.C.C. HUME PIPE

CLASS NP-3 (TYP)

NEA-HDI-H/I -CT-05 OF 05

FOR TENDER PURPOSE ONLY

REV DATE REV

CABLE TRENCHESDETAIL OF CABLE TRENCH CROSSINGS

Page 13: 220kV SWITCHYARD AREA
Page 14: 220kV SWITCHYARD AREA

FOR TENDER PURPOSE ONLY

REV DATE REV

RCC CONTROL BUILDING GENERAL LAYOUT

DRAWING NO:

Note:1.All dimension of building are tentative,final dimensionshall be decided by contractor and approved by employer.

NEA-HDI-H-CR-01 OF 01

Page 15: 220kV SWITCHYARD AREA

75

760

75

BRICK WORK

WITH CM 1:6

230 300 230

50

0 (M

AX

)

75

75MM THK. P.C.C 1:4:8

25MM THK. P.C.C 1:2:4

100MM THK. GRAVEL FILLING

75MM THK. P.C.C 1:5:10

F.G.L

SECTION A-A

(FOR DEPTH UP TO 600MM)

SCALE 1:10

12MM THK. CEMENT PLASTER

WITH NEAT CEMENT FINISH

ENTIRE INNER SURFACE

AND TOP OF DRAIN

X

X

2000 (TYP.)

25MM THK. P.C.C (1:2:4)

75MM THK. P.C.C (1:2:4)

SECTION X-X

(APPLICABLE FOR GRAVEL SIDE)

SCALE 1:10

2000 (TYP.)

25MM THK. P.C.C (1:2:4)

75MM THK. P.C.C (1:2:4)

SECTION X-X

(APPLICABLE FOR ROAD SIDE)

SCALE 1:10

250

LEVEL TO MATCH WITH

ROAD SHOULDER

10

0

125

12

5

75

25

MS FLAT

15X3(TYP.)

DETAIL A

SCALE 1:5

GENERAL NOTES

1. ALL DIMENSIONS ARE IN MM AND ELEVATIONS ARE IN METER

UNLESS NOTED OTHERWISE.

2. ALL DRAINS SHALL BE GIVEN A MINIMUM SLOPE OF 1:1000 IN

THE LONGITUDINAL DIRECTION.

3. MINIMUM DEPTH OF DRAIN SHALL BE 300MM BELOW FGL.

4. WHERE EVER TWO SECTIONS ARE MEETING A TRANSITION

ZONE SHALL BE CONSTRUCTED HAVING LENGTH 1000MM.

5. DEPTH OFF DRAIN IS TAKEN AS HEIGHT FROM TOP OF DRAIN TO

INVERT OF DRAIN.

6. IN CASE OF FILLING AREA, PROPER COMPACTION OF FILLED

SOIL SHALL BE CARRIED OUT AS PER TS PRIOR TO LAYING OF

DRAIN.

NEA-HDI-H/I -DR-01 OF 02

FOR TENDER PURPOSE ONLY

REV DATE REV

DETAIL FOR DRAIN SECTION

Page 16: 220kV SWITCHYARD AREA

75

1140

75

BRICK WORK

WITH CM 1:6

230 450 230

50

0

75

75MM THK. P.C.C 1:4:8

25MM THK. P.C.C 1:2:4

100MM THK. GRAVEL FILLING

75MM THK. P.C.C 1:5:10

F.G.L

SECTION B-B

(FOR DEPTH FROM 600 TO 900MM)

SCALE 1:10

12MM THK. CEMENT PLASTER

WITH NEAT CEMENT FINISH

ENTIRE INNER SURFACE AND

TOP OF DRAIN

300 (MAX.)

345

345

75

1520

75

BRICK WORK

WITH CM 1:6

230 600 230

50

0

75

75MM THK. P.C.C 1:4:8

25MM THK. P.C.C 1:2:4

100MM THK. GRAVEL FILLING

75MM THK. P.C.C 1:5:10

F.G.L

SECTION C-C

(FOR DEPTH FROM 900 TO 1200MM)

SCALE 1:10

12MM THK. CEMENT PLASTER

WITH NEAT CEMENT FINISH ENTIRE

INNER SURFACE AND TOP OF DRAIN

30

0

345

345

300 (MAX.)

460 460

75

1900

75

BRICK WORK

WITH CM 1:6

230 750 230

50

0

75

75MM THK. P.C.C 1:4:8

25MM THK. P.C.C 1:2:4

100MM THK. GRAVEL FILLING

75MM THK. P.C.C 1:5:10

F.G.L

SECTION D-D

(FOR DEPTH FROM 1200 TO 1500MM)

SCALE 1:10

12MM THK. CEMENT PLASTER

WITH NEAT CEMENT FINISH

ENTIRE INNER SURFACE AND

TOP OF DRAIN

30

0

345

345

30

0

300 (MAX.)

460

575

460

575

GENERAL NOTES

1. ALL DIMENSIONS ARE IN MM AND ELEVATIONS ARE IN METER

UNLESS NOTED OTHERWISE.

2. ALL DRAINS SHALL BE GIVEN A MINIMUM SLOPE OF 1:1000 IN

THE LONGITUDINAL DIRECTION.

3. MINIMUM DEPTH OF DRAIN SHALL BE 300MM BELOW FGL.

4. WHERE EVER TWO SECTIONS ARE MEETING A TRANSITION

ZONE SHALL BE CONSTRUCTED HAVING LENGTH 1000MM.

5. DEPTH OFF DRAIN IS TAKEN AS HEIGHT FROM TOP OF DRAIN TO

INVERT OF DRAIN

6. IN CASE OF FILLING AREA, PROPER COMPACTION OF FILLED

SOIL SHALL BE CARRIED OUT AS PER TS PRIOR TO LAYING OF

DRAIN.

NEA-HDI-H/I -DR-02 OF 02

FOR TENDER PURPOSE ONLY

REV DATE REV

DETAIL FOR DRAIN SECTION