220 KV Substation

download 220 KV Substation

of 24

Transcript of 220 KV Substation

  • 8/12/2019 220 KV Substation

    1/24

    TRAINING AT 220KVSUBSTATION JAIPUR

  • 8/12/2019 220 KV Substation

    2/24

    SUBSTATION A station in the power transmission system at which elec

    power is transformed to a conveniently used form.

    The station may consist of transformers, switches, circbreakers and other auxiliary equipment.

    Its main function is to receive energy transmitted at hvoltage from the generating station, by either step-up or st

    down the voltage to a value appropriate for local use aprovide facilities for switching.

    Some substation, such as power plant switchyard are simswitching stations where different connections can be ma

    between various transmission lines.

  • 8/12/2019 220 KV Substation

    3/24

    TYPE OF SUBSTATION

    Step Up Substation

    Primary Grid Substation

    Secondary Grid Substation

    Distribution Substation Bulk Supply Substation

  • 8/12/2019 220 KV Substation

    4/24

    FEEDERS

    Incoming Feeders:

    Bassi(220 KV)

    Heerapura(220 KV)

    Outgoing Feeders:Sitapura(132 KV)

    Puranaghat(132 KV)

  • 8/12/2019 220 KV Substation

    5/24

    TYPICAL COMPONENTS OF APOWER PLANT SUBSTATION(SWITCHYARD)

    A - Busbar

    B - Disconnector

    C - Circuit Breaker

    D - Current Transformer

    E - Voltage Transformer

    F - Earthing Switch

    G - Surge Arrestor

    CONNECT

    CONNECT & DIS-CONNECT

    CONNECT, DIS-CONNECT & DETECT

    DETECT & TRANSFORM

    DETECT & TRANSFORM

    PROTECT & SAFETY

    PROTECT

  • 8/12/2019 220 KV Substation

    6/24

    BUSBAR

    This is a term we use for a mainbar or conductor carrying an electric

    current to which many connection

    may be made.

    Buses are merely convenient

    means of connecting switches andother equipment into various

    arrangements.

    Aluminum or copper conductorssupported on porcelain insulators,

    carry the electric energy from point

    to point.

  • 8/12/2019 220 KV Substation

    7/24

    DISCONNECTS

    This is an easily removed piece ofthe actual conductor of a circuit.

    The purpose of disconnects is toisolate equipment.

    A typical use of disconnects is toisolate a circuit breaker by installingone disconnect on either side of the

    circuit breaker (in series with the

    breaker).

    Disconnect Switch( moving contact rod (A)

    contacts with flexiblefingers (B) )

  • 8/12/2019 220 KV Substation

    8/24

    CIRCUIT BREAKER

    This is used to interrupt circuits whilecurrent is flowing through them.

    The operation of the breaker is very rapidwhen opening.

    Circuit breakers of this type are usuallyarranged for remote electrical control

    from a suitably located switchboard.

    Some recently developed circuit breakershave no oil, but put out the arc by a blast

    of compressed air these are called air

    circuit breakers.

    Circuit Bre( Connected in a

    phase circ

    Po

    Ind

  • 8/12/2019 220 KV Substation

    9/24

    CURRENT TRANSFORMER

    Current transformer are used withammeters, watt meters, power-factormeters, watt-hour meters, compensators,

    protective and regulating relays and the

    trip coil of circuit breakers.

    One current transformer can be used tooperate several instruments, provided

    that the combined burden does notexceed that for which the transformer is

    designed and compensated.

    The current transformer is connecteddirectly in series with the line.

  • 8/12/2019 220 KV Substation

    10/24

    VOLTAGE TRANSFORMER

    This is also know as potential transformer usedwith volt-meters, wattmeter's, watt-hour meters,power-factor meters, frequency meters,

    protective and regulating relays and the no-

    voltage and over-voltage trip coils of automatic

    circuit breakers.

    One transformer can be used for a number ofinstruments at the same time if the total current

    taken by the instrument does not exceed that for

    which the transformer is designed and

    compensated.

    The ordinary voltage transformer is connectedacross the line, and the magnetic flux in the core

    depends upon the primary voltage.

  • 8/12/2019 220 KV Substation

    11/24

    EARTHING SWITCH This is also known as ground disconnect, which used

    connects the equipment to a grid of electrical conducto

    buried in the earth on the station property.

    It is intended to protect people working on the groundequipment.

    It does this by completing a circuit path, thereby reducithe voltage difference between the equipment and

    surroundings.

  • 8/12/2019 220 KV Substation

    12/24

    SURGE ARRESTOR These are devices used to provide the

    necessary path to ground for such surges, yetprevent any power current from following the

    surge. An ideal arrester must therefore have the

    following properties:

    1. Ability to remove the surge energy from the line

    in a min. time.

    2. High resistive to flow of power current.

    3. A valve action automatically allowing surge to

    pass and then closing up so as not to permitpower current to flow to ground.

    4. Always ready to perform.

    5. Performance such that no system disturbances

    are introduced by its operation.

    6. Economically feasible

  • 8/12/2019 220 KV Substation

    13/24

    OVERHEAD GROUND WIRE

    This is a wire, generally of steel,supported from the top of transmission-

    line towers and solidly grounded at each

    tower.

    It is considered a preventive device, but itdoes not entirely prevent the formation of

    travelling waves on a line.

    Furthermore, those lines which are notequipped with ground wires will be

    subjected to disturbances which produce

    surges that must be allowed to escaped

    to ground

  • 8/12/2019 220 KV Substation

    14/24

    RELAYS

    Various types of relays used areoBuchloz Relay

    oOver Current Relay

    oEarth Fault Relay

    o

    Over Voltage RelayoDifferential Relay

    oBus Bar Relay

  • 8/12/2019 220 KV Substation

    15/24

    BUCHLOZ RELAY

    Used for protection of oil immersedtransformers, reactors, etc.

    Phenomenon of liberation of gas incase of fault generation is used to

    provide protection.

    Falling level of oil could be detected.

  • 8/12/2019 220 KV Substation

    16/24

    OVER CURRENT RELAY

    Protection from overload.

    Protection devices like fuse orcircuit breaker fitted with

    overload coils or series

    connected trip coils are used for

    over current protection.

  • 8/12/2019 220 KV Substation

    17/24

    EARTH FAULT RELAY

    The earth-fault relay is designed to beused for selective earth-fault protection,either primary or back-up protection, in

    solidly earthed or low-resistance earthed

    power systems.

    When an earth-fault occurs, the relaydelivers an alarm signal, trips the circuit

    breaker provide alarms, record fault data,

    etc., in accordance with the application

    and the configured relay functions.

  • 8/12/2019 220 KV Substation

    18/24

    OVER/UNDER VOLTAGE RELAY

    Relay is used for over voltageprotection and supervision in

    distribution systems.

    Relay is also used for over / undervoltage protection of generators,

    Motors and Transformers.

    They are generally used forincoming line protection.

  • 8/12/2019 220 KV Substation

    19/24

    DIFFERENTIAL RELAY

    Operates when the vectordifference of two or more

    quantities exceeds a

    predetermined value.

    The relay has ratio matchingtaps and incorporates a secondharmonic restraint function

    where large transformer

    magnetizing in rush is present.

  • 8/12/2019 220 KV Substation

    20/24

    BUS BAR RELAY

    The scheme of busbar protection, statesthat total electric current entering anelectrical node is exactly equal to total

    current leaving the node.

    But this scheme has also a maindisadvantage. This scheme of protection

    can not discriminate the faulty section of thebusbar.

    Very short tripping time (

  • 8/12/2019 220 KV Substation

    21/24

    OTHER DEPT. OF SUBSTATION

    CONTROL ROOM

    POWER LINE CARRIER COMMUNICATION ROOM

    BATTERY ROOM

  • 8/12/2019 220 KV Substation

    22/24

    CONTROL ROOM

    Contain meters, control switches andrecorders located in the control building

    Used to control the substationequipment to send power from one

    circuit to another or to open or to shut

    down circuits when needed.

    Annunciator is present which consist ofsounding alarm and an indicator which

    indicate nature of fault and zone where

    fault occurred.

  • 8/12/2019 220 KV Substation

    23/24

    POWER LINE CARRIER COMMUNICATIOROOM

    Used in case of largeinterconnected system where

    control leads dispatch station

    has to co-ordinate the working of

    various unit to see that thesystem is maintained

    most economic and reliablemethod of communication in

    power network

  • 8/12/2019 220 KV Substation

    24/24

    BATTERY ROOM

    Batteries used are lead acid typehaving solution of sulfuric and

    distilled.

    Room is kept maintainable so it isnota ccumulated with acid vapours

    to avoid risk of explosion.

    Batteries are kept at healthy stateat 2.1/2.2 V/cell.