Partial Discharge Measurements on Instrument Transformers
Dr. Michael Krüger (c) OMICRON
![Page 2: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/2.jpg)
Faults on Instrument Transformers
PAGE 2
![Page 3: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/3.jpg)
Faults on Instrument Transformers
PAGE 3
![Page 4: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/4.jpg)
Faults on Instrument Transformers
PAGE 4
![Page 5: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/5.jpg)
Faults on Instrument Transformers
PAGE 5
![Page 6: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/6.jpg)
Measurement Method Application Indicated by FRT*
Oil Diagnosis(Water Content, Breakdown Voltage , DGA ...)
Routine TestPeriodical Testse.g. every 7 years
FRT
Tan-Delta / PFInsulation Diagnosis, Ageing, Moisture
Karl-Fischer Titration, DGA FRT
Dielectric Response Insulation Diagnosis, Ageing, Moisture
Karl-Fischer Titration, DGA FRT
Partial Discharge Measurement
Insulation Diagnosis, Partial Discharges
DGA T
Ratio VT Accuracy After Outage, Oil Values FRTRatio CT Accuracy Wrong Current Readings FRTExcitation Current VT Core Faults, Shorted Turns After Outage, Oil Values FTExcitation Current CT Knee Point Voltage Malfunction of the Protection FRT*F=Fingerprint, R=Routine, T=Troubleshooting
Electrical Measurement Methods for Instrument Transformers
PAGE 6
![Page 7: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/7.jpg)
PD Circuit according to IEC60270
(IEC 60270)
PAGE 7
![Page 8: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/8.jpg)
PD Testing on Instrument Transformers
Example Ur = 10kV
1 min
28kV 7kV
< 20pC
PAGE 8
![Page 9: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/9.jpg)
Design of a MV Epoxy Type Voltage Transformer
Source: RITZ Technical Dictionary Instrument Transformers
![Page 10: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/10.jpg)
Faults on MV Epoxy Type Instrument Transformers
PAGE 10
![Page 11: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/11.jpg)
PAGE 11
Exploded 6.6kV Voltage Transformer
![Page 12: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/12.jpg)
HV Transformer with Coupling Capacitor, Quadripole and PD Instrument
PAGE 12
![Page 13: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/13.jpg)
Generation of the 150Hz Test Voltage with CPC100 + TR7
PAGE 13
![Page 14: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/14.jpg)
Good CT with PD < 10pC at 12kV
PAGE 14
![Page 15: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/15.jpg)
Conspicuous Voltage Transformer PD > 500pC at 8kV
PAGE 15
![Page 16: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/16.jpg)
Hazardous PD on a Voltage Transformer TE = 2nC at 2.5kV!
PAGE 16
![Page 17: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/17.jpg)
High Hydrogene on a 123kV VT-CT
PAGE 17
![Page 18: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/18.jpg)
PD Measurements on GIS Voltage Transformers
PAGE 18
![Page 19: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/19.jpg)
GIS Voltage Transformer
PAGE 19
![Page 20: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/20.jpg)
Technical Assessment
Test Voltage: 1.2 x Um / √3 = 1.2 x 242 / √3 = 170 kV
PAGE 20
![Page 21: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/21.jpg)
Technical Assessment
Calculation of the test current Voltage Transformer DataPrimary voltage UPrim 242 [kV]
Sekundary voltage USec 0,11 [kV]
Maximum operation voltage Um 245 [kV]Operation voltage U 230 [kV]
Calculation of the Capacitances Capacitance of the busbar -B3 CGIS 600 [pF]
Capacitance of the voltage transformer CTP 300 [pF]
Capacitance of the HV SF6 - outdoor bushing CTrav 400 [pF]
Cpacitance of the coupling capacitor 300 kV CCondo 300 [pF]
Total capacitance Ctot 1600 [pF]
Test DataTest voltage 1.2 * Um / V3 170 [kV]Test frequency f 60 [Hz]
Calculation of the Test CurrentPrimary current (245kV) IPrim 0,103 [A]
Secondary current (110V) ISec 226 [A]Needed test power = 75V * 226A S 17 [kVA]
PAGE 21
![Page 22: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/22.jpg)
Test Setup
> 01.31.13034 Omicron - Diag.-Woche - TE 220 kV Spgswandler
GIS Gas volume B4
GIS SF6 / outdoor
bushing
GIS Gas volume B3
Coupling capacitor 333pF / 300kV
Quadripole
PD instrument
MPD600
CPC100
CP TR8
CP CR6
CP CR6 CP CR6
CP CR6
PAGE 22
![Page 23: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/23.jpg)
110V Measurement Circuit
> 01.31.13034 Omicron - Diag.-Woche - TE 220 kV Spgswandler
ω
ω
PAGE 23
Resonance:
I = 226A
![Page 24: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/24.jpg)
Setup - 110V Side
CPC100 (Source)
Matching transformer and compensation reactors
Secondary terminals PAGE 24
![Page 25: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/25.jpg)
Setup 242kV Side Coupling Caoacitor 333pF 300kV with Quadripole and MDD600
PAGE 25
![Page 26: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/26.jpg)
PD Calibration with 100pC
PD Calibrator
PAGE 26
![Page 27: 20_KRUEGER_PD measurements on IT.pdf](https://reader033.fdocuments.net/reader033/viewer/2022050714/577ccd1a1a28ab9e788b804d/html5/thumbnails/27.jpg)
PD Level < 6pC at 170kV
PAGE 27