20120504 LISAT slides Dube
-
date post
18-Oct-2014 -
Category
Business
-
view
447 -
download
2
description
Transcript of 20120504 LISAT slides Dube
ARC FLASH MITIGATIONSTRATEGIES
forMETALCLADSWITCHGEAR
The Sign of Quality
PEDERSEN POWER PRODUCTS
Discussion Topics
Arc Flash Standards Arc Flash Prevention Arc Flash Protection Mitigation Techniques
Molten MetalDroplets
Copper Solid toVapor Expansion67,000 Times
Toxic Gases
PressureWave
IntenseLight Flash
Flying Objects& Shrapnel
SoundBlast
Arc Flash HazardsIntense Heat35,000F
ARC FLASHSTANDARDS
The Sign of Quality
PEDERSEN POWER PRODUCTS
IEEE Standard 1584
Contains calculations used to determinesafe boundary distances for unprotectedpersonnel and the incident energy at theworking distance for qualified personnelworking on energized equipment.
Incident Energy Calculation forArc Flash in a Cubic Box
E =1038.7D-1.4738 x T[0.0093F2-0.3453F+5.9675]E = Incident Energy in cal/cm2D = Distance to arcing pointT = Time to clear arcing faultF = Available bolted fault short circuit current
IEEE Standard 1584
NFPA-70E-2009
Utilizes IEEE 1584 methods forcalculating incident energy onspecific electrical equipment andprovides guidelines for the PPEclothing required based on theincident energy level.
Standard for Electrical Safetyin the Workplace
National Electric Code
Requires labeling of electrical equipmentto warn qualified personnel of the dangerof electric arc flash.Refers to NFPA-70E as a guide forquantifying the hazard.
Arc Flash Warning Label
Compliance with National Electric Code
Arc Flash Warning Label
OSHA 29 CFR Part 19101910.333 Selection and Use of Work PracticesSafety-related work practices to prevent injuries resultingfrom either direct or indirect electrical contact, whenwork is performed near or on equipment or circuits whichmay be energized.1910.335 Safeguards for Personal ProtectionPPE shall be used to protect employees fromelectrically related injuries while that employee isworking near exposed energized parts.
Subpart S, Appendix AReferences NFPA-70E forElectrical Safety Practices
ARC FLASHPREVENTION
The Sign of Quality
PEDERSEN POWER PRODUCTS
DONTWORK ON
ENERGIZEDELECTRICAL
EQUIPMENT!
Arc Flash Prevention
Causes of Electric Arc Flash Contact with Live Parts Unsafe Work Procedures Misoperation Insufficient Maintenance Overvoltages Insulation Failure Entry of Small Animals
Arc Flash Prevention Maintain Sound Safety Practices Prevent Entry of Critters Use IEEE Metalclad Standards Prevent Moisture Ingress Proper Insulation System Design Monitor for Partial Discharge Monitor Bus Temperatures
IEEE Standard C37.20.7
There is little likelihood of an internal arc inequipment meeting the requirements of IEEE StandardC37.20.1-2002 or IEEE Standard C37.20.3-2001. Thereis even less likelihood of an internal arc in equipmentthat has insulated bus, compartmentalization, barriers,and interlocks, such as those described in IEEEStandard C37.20.2-1999.
Metalclad Switchgear Design Standard
Uninsulated Bus
LoadTerminals
Ground bus
Load breakair switch
Fuse
LineTerminals
Everything in SameCompartment
ExposedLive Parts
withDoor Open
Metal Enclosed Switchgear
Metalclad SwitchgearRelay, Controls
andInstrumentation
BreakerCompartment
Loadbus
Main bus
Ground bus
CT
CT
Primary circuits,relays, meters,and controlsisolated in owngrounded metalcompartments
Primary buses andconnections coveredwith insulation
CT barrier
MovableShutters
Shutters coverPrimaries whenno breaker installed
Metalclad SwitchgearRelay, Controls
andInstrumentation
Loadbus
Main bus
Ground bus
CT
CTVacuumBreaker
Steel barrier
No primary circuitsexposed withbreaker installed
Arc Flash Prevention Maintain Good Safety Practices Prevent Vermin Entry Use IEEE Metalclad Standards Prevent Moisture Ingress Proper Insulation System Design Monitor for Partial Discharge Monitor Bus Temperatures
IEEE Tested Enclosure DesignMoisture Prevention
Use Extended Life Sealants Ventilate Cable Compartment Maintain Filters/Screens Use Dual Strip Heaters Monitor Strip Heaters Seal Unintentional Openings Apply Quality Protective Finish
IEEE C37.20.2 Section 6.2.10Test Criteria
7.1 gallons per minute flow rate 60psi min water pressure 10 ft. Min Distance from Joints Against 2 Surfaces at each Joint
Arc Flash Prevention Maintain Good Safety Practices Prevent Vermin Entry Use IEEE Metalclad Standards Prevent Moisture Ingress Proper Insulation System Design Monitor for Partial Discharge Monitor Bus Temperatures
Fluidized Bed Epoxy Bus Insulation
Insulation Materials
PVCInsert
Cycloaliphaticbus supports
95kV BIL Rated Insulators
Arc Flash Prevention Maintain Good Safety Practices Prevent Vermin Entry Use IEEE Metalclad Standards Prevent Moisture Ingress Proper Insulation System Design Monitor for Partial Discharge Monitor Bus Temperatures
Signalsent toInsulGardRelay
Partial Discharge Monitoring
RFCT #1 detects partialdischarges internal toswitchgear compartment.RFCT #2 detects partialdischarges in Customerscables up to 100 ft fromswitchgear
Partial Discharge Monitoring
Arc Flash Prevention Maintain Good Safety Practices Prevent Vermin Entry Use IEEE Metalclad Standards Prevent Moisture Ingress Proper Insulation System Design Monitor for Partial Discharge Monitor Bus Temperatures
Wireless Parasitically PoweredTemperature Detectors forMedium Voltage Switchgear(under development)
Temperature Monitoring
BusJoint
StraightBus
Protection system configurationTemperature input from sensorsCurrent Input from CTsCalculate and Predict a ProblemEmail/Alarm notification
Output Through Internet
ARC FLASHPROTECTION
The Sign of Quality
PEDERSEN POWER PRODUCTS
Train Personnel Wear Proper PPE Install Warning Labels Maintain Good Safety Practices Build Sturdy Enclosure Reduce the Human Interface Redirect the Blast Energy
Arc Flash Protection
De-Energize EquipmentUse Lockout/Tagout ProceduresLatch and Secure All PanelsLabel Line and Load Side Bus Isolate Potential BackfeedsOpen Tie Breaker/Redundant SourcesGround De-Energized Conductors
Safety Practices
First G&T Standard Established Formal G&T Tests BIL Withstand AC Hipot 1-minute Momentary For 10 Cycles Per
C37.20.2 K*I 2 Seconds Per C37.20.2 Interlocking (Upper & Lower) 500 Insertions and Removals
IEEE C37.20.6-2007Safety Practices
G&T TESTING STANDARD
Safety PracticesBall Type Ground & Test Device
Safety Practices
Ground Conductor Sizing31.5kA for 2 seconds
Requires three (3) 500mcmcables per phase
(total of 9 grounding cables)
Ground Conductor Sizing25kA for 2 seconds
Requires three (3) 350mcmcables per phase
(total of 9 grounding cables)
Safety Practices
Train Personnel Wear Proper PPE Install Warning Labels Maintain Good Safety Practices Build Sturdy Enclosure Reduce the Human Interface Redirect the Blast Energy
Arc Flash Protection
Use Only 11 Gauge Steel Weld Cubicles Two Walls Between Sections Heavy Duty Door Hinges Heavy Duty Door Latches
Sturdy Enclosure Design
Train Personnel Wear Proper PPE Install Warning Labels Maintain Good Safety Practices Build Sturdy Enclosure Reduce Human Interface Redirect the Blast Energy
Arc Flash Protection
Reduce Human InterfaceOpening & Closing Breaker Relocate control switch Use remote communications Use local HMI Use remote control station Use Remote Operator Use Time Delay Control Switch
RemoteControlStation
Remote Breaker ControlSmartReduce Human Interface
Remote Breaker ControlELECTROSWITCH
Reduce Human Interface
Remote BreakerRacking Motor
RemoteBreakerRackingMotor
Remote Breaker RackingReduce Human Interface
Remote Breaker RackingReduce Human Interface
Remote Breaker RackingReduce Human Interface
Train Personnel Wear Proper PPE Install Warning Labels Maintain Good Safety Practices Build Sturdy Enclosure Reduce the Human Interface Redirect the Blast Energy
Arc Flash Protection
IEEE Standard C37.20.7
IEEE Standard C37.20.7
NOT A DESIGN STANDARD
A procedure for testing and evaluatingthe performance of medium-voltagemetal-enclosed switchgear for internalarcing faults and identifying thecapabilities of the equipment relativeto specific zones of protection.
IEEE Standard C37.20.7
Equipment designed to withstandthe effects of an internal arcingfault as indicated by successfullymeeting the requirements of IEEEStandard C37.20.7-2007.
Arc-Resistant Definition:
IEEE Standard C37.20.7
Term Arc Resistant can be misleading.In the event of an internal arcing fault,the dangerous effects of the arc arevented away from the zone ofprotection for personnel.Term Arc Venting is more accurate
Arc Venting Switchgear
48 min
95
Duct can exit to theleft, right, or rear
Arc Venting Switchgear
Exhaust Vent Duct Design Tested on the switchgear Must vent to safe area Fire rated at wall opening No external air allowed in Prevent buildup of ice and snow Prevent critter ingress
Arc Venting Switchgear
IEEE Standard C37.20.7
Intended to provide an additional degree ofprotection to the personnel performing normaloperating duties in close proximity to the equipmentwhile equipment is operating under normalconditions
Not intended to provide this additional degree ofprotection to operating personnel who, in the normalperformance of their duties, would be required toopen enclosure doors or panels or otherwise alter theequipment from its normal operating conditions.
IEEE Standard C37.20.7
IEEE does not require that metalcladswitchgear to be manufactured topass the IEEE Standard C37.20.7Testing Procedures.
IEEE Standard C37.20.7
Zonesof
Protection
Zones of Protection
Switchgear with arc-resistant designs orfeatures at the freelyaccessible front of theequipment only.
Type 1
Zones of Protection
Switchgear with arc-resistant designs orfeatures at the freelyaccessible exterior(front, back and sides)of the equipment only.
Type 2
Zones of Protection
That arcing does notcause holes in the freelyaccessible front of theenclosure or in the wallsisolating the low-voltagecontrol or instrumentcompartments.
Type 1B
Zones of Protection
That arcing does notcause holes in the freelyaccessible front, sidesand rear of the enclosureor in the walls isolatingthe low-voltage control orinstrumentcompartments.
Type 2B
Zones of Protection
Adds isolation fromeffects of an internalarcing fault between alladjacent compartments
Type 1BC
Zones of Protection
Adds isolation fromeffects of an internalarcing fault between alladjacent compartments
Type 2BC
Arc Venting Switchgear
Initial cost (up to 25% more) Need breaker lift device Must design room accordingly Must seal all cable entries Low voltage wiring protection Loss of protection if door/panel open
Considerations
IEEE Standard C37.20.7
Protection against toxic gases Protection against excessive sound Arcing within components Protection from above or below
Testing Does Not Address
ARC FLASHMITIGATION
The Sign of Quality
PEDERSEN POWER PRODUCTS
Arc Flash Mitigation
Incident Energy CalculationE =1038.7D-1.4738 x T[0.0093F2-0.3453F+5.9675]E = Incident Energy in cal/cm2D = Distance to arcing pointT = Time to clear arcing faultF = Available short circuit current
Complete System Analysis High Speed Differential Relay Fast Bus Tripping Maintenance Relay Settings Arc Flash Detection Hi-Speed Arc Terminator 3 Cycle Breakers Current Limiting Fuses
Arc Flash Mitigation
Fast Bus Tripping
50/62
50 50 50 50 50T
Fast Bus Tripping
50/62
50 50 50 50 50
T
Complete System Analysis High Speed Bus Differential Relay Fast Bus Tripping Maintenance Relay Settings Arc Flash Detection Hi-Speed Arc Terminator 3 Cycle Breakers Current Limiting Fuses
Arc Flash Mitigation
Relay Group Settings Feature can be enabledby a contact input, communications or ARMsSelector Switch to enable Maintenance Modeprotective settings when maintenance is beingperformed on the equipment.Maintenance Mode Protective Group settingstypically establish lower instantaneous pick-ups that can be optimized to reduce trip delaysand increase sensitivity, but avoid nuisancetrips.Remote and/or Local Visual Indication can beprovided to confirm the Relay is in MaintenanceMode.
CI - 8
a b
ARMsSelectorSwitchTB2FP5000
Relay
CI - 7
Maintenance ModeIndicating Light
Maintenance Relay Settings
ARMs Selector SwitchFP5000 Postion A Position B
Relay SettingsGroup
Group 2Maintenance Mode
Group 1Normal Mode
Relay ContactInput CI-7 CI-8
Complete System Analysis High Speed Bus Differential Relay Fast Bus Tripping Maintenance Relay Settings Arc Flash Detection Hi-Speed Arc Terminator 3 Cycle Breakers Current Limiting Fuses
Arc Flash Mitigation
Microprocessor based high speed relaysends trip signal to breaker upon sensinga light flash with high speed light sensorsinstalled in theswitchgearcompartments.
Arc Flash Detection
Arc Flash DetectionSEL-751A Feeder Protection RelayInstantaneous OvercurrentTimed OvercurrentInstantaneous Neutral OvercurrentTimes Neutral OvercurrentUndervoltage (Bus Side)Overvoltage (Bus Side)Undervoltage (Line Side)Overvoltage (Line Side)Over FrequencyUnder FrequencySyncronism CheckAuto-ReclosingArc-Flash DetectionArc-Flash Overcurrent
Arc Flash DetectionTest Cell Without Arc Flash Detection
Arc Flash DetectionTest Cell With Arc Flash Detection
Arc Flash DetectionSwitchgear Without Arc Flash Detection
Arc Flash DetectionSwitchgear With Arc Flash Detection
Arc Flash DetectionTest Dummy Without Arc Flash Detection
Arc Flash DetectionTest Dummy With Arc Flash Detection
Complete System Analysis High Speed Bus Differential Relay Fast Bus Tripping Maintenance Relay Settings Arc Flash Detection Hi-Speed Arc Terminator 3 Cycle Breakers Current Limiting Fuses
Arc Flash Mitigation
Detects presence of an arc flash with highspeed photo sensors and closes a highspeed switch that shorts out the the mainbus in the first cycle to create a parallelpath to the arc and quickly extinguish aburning arc
Arc Terminator
Arc Terminator
Arc Terminator
Arc Terminator
Phase A
Phase B Phase C
Arc TerminatorArc
Confines Arc Effects at Initiation Point Extinguishes Arc < Cycle Prevents Pressure Buildup No Change to Relay Coordination Integrated Into Switchgear Lineup Indicates Where Flash was Detected. Limited to 40ka Symmetrical Faults
Arc Terminator
Complete System Analysis High Speed Bus Differential Relay Fast Bus Tripping Maintenance Relay Settings Arc Flash Detection Hi-Speed Arc Terminator 3 Cycle Breakers Current Limiting Fuses
Arc Flash Mitigation
Complete System Analysis High Speed Bus Differential Relay Fast Bus Tripping Maintenance Relay Settings Arc Flash Detection Hi-Speed Arc Terminator 3 Cycle Breakers Current Limiting Fuses
Arc Flash Mitigation
Current Limiting FusesCurrent Limiting Protector (CLiP)Up to 5,000A Continuous @15.5kvUp to 120,000A Interrupting
Current Limiting Fuses
10ka Trigger Elementlimits peak to 17ka vs48ka
Scheme Comparison
Protection SchemeArcingTime
PercentReduction
ArcingTime
PercentReduction
Normal Coordination 800ms 0% 767ms 0%Fast Bus Trip 170ms 137ms Maintenance Settings 120ms 87ms High Speed Differential 107ms 74ms Arc Flash Detection 86ms 53ms Arc Terminator 2.3ms 2.3ms
5 Cycle Breakers 3 Cycle Breakers
NFPAPersonalProtectiveEquipment
RequirementsThe Sign of Quality
PEDERSEN POWER PRODUCTS
IncidentEnergyPresent(cal/cm2)
PPERiskCat
RequiredMinimumPPE Rating(cal/cm2)
Protective Clothing Required to PreventOnset of a Second Degree Burn
E 1.2 0 N/A Untreated Cotton1.2 < E 4 1 4 FR Shirt + FR Pants4 < E 8 2 8 Cotton Undergarments + FR Shirt + FR Pants8 < E 25 3 25 Cotton Undergarments + FR Shirt + FR Pants
+ FR Coverall25 < E 40 4 40 Cotton Underwear + FR Shirt + Pants
+ Multi-Layer Flash Suit (minimum of 3 layers)E > 40 N/A N/A Too Dangerous to Work On
NFPA PPE Requirements
NFPA PPE RequirementsNO CALCULATION OF INCIDENT ENERGYNFPA Table 130.7(C)(9) 1Kv 38Kv Switchgear
Tasks Performed on Energized Equipment Risk CatInspections Outside Restricted Approach Boundary 3Operate Circuit Breaker with Door Closed 2Operate Circuit Breaker with Door Open 4Operate Meter Switch 0Work on Energized Electrical Conductors 4Work on Exposed Control Energized Circuits 120V 4Racking of Breakers with Door Open or Closed 4Application of Safety Grounds After Voltage Test 4Remove Covers to Expose Energized Conductors 4Open Hinged Covers to Expose Energized Conductors 3Open PT or SST Compartment 4
NFPA PPE RequirementsNO CALCULATION OF INCIDENT ENERGYNFPA Table 130.7(C)(9) 1Kv 38Kv SwitchgearIF ARC RESISTANT SWITCHGEAR UTILIZED
(for clearing times less than 500ms)
Tasks Performed on Energized EquipmentNon ARRisk Cat
AR SwgrRisk Cat
Operate Circuit Breaker with Door Closed 2 0Operate Circuit Breaker with Door Open 4 4Work on Energized Control Circuits 120V 4 4Racking of Breakers with Door Open 4 4Racking of Breakers with Door Closed 4 0Insert or Withdraw Potential Transformers 4 0
E (cal/cm2) versus Fault CurrentProtection Scheme 25ka 40ka 50ka 63kaNormal Coordination 13.30 29.70 50.50 89.30Fast Bus Trip 2.83 6.32 10.73 18.97Maintenance Settings 2.00 4.46 7.58 13.39High Speed Differential 1.78 3.98 6.76 11.94Arc Flash Detection 1.47 3.20 5.43 9.60
Protection Scheme 25ka 40ka 50ka 63kaNormal Coordination 12.75 28.5 48.40 85.60Fast Bus Trip 2.28 5.09 8.65 15.29Maintenance Settings 1.45 3.23 5.49 9.71High Speed Differential 1.23 2.75 4.67 8.26Arc Flash Detection 0.88 1.97 3.35 5.91
3 Cycle Breaker
5 Cycle Breaker
E(cal/cm2)
PPECat
1.2 04 18 225 340 4>40 N/A
0102030405060708090
100
0 6 12 18 24 30 36
FC = 25kaFC = 40kaFC = 50kaFC = 63ka
E (cal/cm2) versus DistanceNormal Coordination (5 cycle)
PPECat
1
E(cal/cm2)
PPECat
1.2 04 18 225 340 4>40 N/A
23
4
Distance to Arcing Point (inches)
Incide
nt En
ergy (
cal/c
m2)
E (cal/cm2) versus Distance
0
5
10
15
20
25
30
35
40
0 12 24 36 48 60 72 84 96 108 120 132 144 156 168 180 192 204 216
FC = 25kaFC = 40kaFC = 50kaFC = 63ka
Normal Coordination (5 cycle)
Incide
nt En
ergy (
cal/c
m2)
E(cal/cm2)
PPECat
1.2 04 18 225 340 4>40 N/A
PPECat
4
3
21
Distance to Arcing Point (inches)(216 = 18)
E (cal/cm2) versus Distance
0
5
10
15
20
25
30
35
40
0 6 12 18 24 30 36
FC = 25kaFC = 40kaFC = 50kaFC = 63ka
Bus Differential + Arc Flash (3 cycle)
E(cal/cm2)
PPECat
1.2 04 18 225 340 4>40 N/A
PPECat
12
3
0Distance to Arcing Point (inches)
4
Incide
nt En
ergy (
cal/c
m2)
Remote Racking/Control Advantages
E(cal/cm
2)PPECat
1.2 04 18 225 340 4>40 N/A
Bus Differential Protection (107ms interrupt)Standard 5 cycle Breakers
FaultCurrent
Operation at Frontof Cubicle Door
Operation at 20 Feetfrom Cubicle Door
25kA 1.78 cal/cm2 0.11 cal/cm240kA 3.98 cal/cm2 0.24 cal/cm250kA 6.76 cal/cm2 0.41 cal/cm263kA 11.94 cal/cm2 0.73 cal/cm2
Normal Coordination (800ms clearing time)Standard 5 cycle Breakers
FaultCurrent
Operation at Frontof Cubicle Door
Operation at 20 Feetfrom Cubicle Door
25kA 8.31 cal/cm2 0.51 cal/cm240kA 18.58 cal/cm2 1.13 cal/cm250kA 31.56 cal/cm2 1.93 cal/cm263kA 55.79 cal/cm2 3.40 cal/cm2
Transformer Differential ProtectionBus Differential Protection
Arc Flash Detection
Recommended Scheme
87B Zone
Arc FlashDetectionZones
To CTs atTransformer
87T Zone
ThinkPEDERSENThink
PEDERSEN
PPP