2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

19
OXFORD BROOKES UNIVERSITY P30401 – Building Physics & Thermal Comfort. Professor M. G. Hutchins Assignment 3 – Monday 8th December 2008 Andrea Luise Schrader

description

P30401 Building Physics & Thermal Comfort. Written report following the construction and run analysis of a working Excel Model calculating the heat/energy gains & losses of a building and the resultant annual heating load. Student: Andrea Luise Schrader. Oxford Brookes University.

Transcript of 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

Page 1: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

OXFORD BROOKES UNIVERSITY

P30401 – Building Physics & Thermal Comfort. Professor M. G. Hutchins

Assignment 3 – Monday 8th December 2008

Andrea Luise Schrader

Page 2: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

CalculationOfAnnualSpaceHeatingRequirement.Atwostoreydetatchedhouseis10mwide,8mdeepwiththelongfacadesfacingNorth/South. Theheight of each storey is 2.75mThe glazed areason theNorth, South, East&West facadesare10m2,15m2,4m2&4m2 respectively.Window framesoccupy15%ofthewindowarea,allwindowshavecleardoubleglazingandallwindowsareunshaded.Theheightoftheatticespaceis2.75mandtheridgeoftheroofarearunsEast/Westandis10mlong.Forallmonthsthereareanaverageof0.5airchangesperhour. Internalgainsamount to 15kWh/day, and the mean internal temperature is required to be 19 oC. A“medium”utilisationfactor(a=1.8)applies.TherespectiveU‐valuesoftheenvelopecomponentsare:WallU‐value=0.35W.m‐2oC‐1FloorU‐value=0.40W.m‐2oC‐1RoofU‐value=0.20W.m‐2oC‐1WindowU‐value=2.7W.m‐2oC‐1(frame&glazing)Windowtotalsolarenergytransmittance,g=0.76The monthly mean daily ambient temperatures and the monthly mean daily solarirradianceoneachverticalplanearegiveninTable1&Table2respectively:

Month JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DECMeanTemp0C

2.9

3.8

7.6

11.0

14.4

18.7

19.6

19.8

14.2

11.7

6.4

1.9

Table1.Monthlymeandailyambienttemperatures.

Month JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DECNorth 0.27 0.49 0.86 1.39 1.87 2.14 1.88 1.45 1.05 0.60 0.34 0.21South 1.24 1.87 1.69 2.23 2.77 2.73 2.78 2.98 2.59 2.33 1.57 1.10East 0.42 0.87 1.37 2.05 2.52 2.75 2.74 2.47 1.65 0.96 0.50 0.32West 0.47 0.87 1.42 2.37 3.03 3.04 3.01 2.78 1.99 1.36 0.72 0.40Table2.Estimatedmonthlymeansofdailyglobalradiationonverticalplanes(kWh/m2day)Additionaldata:No.ofsecondsinoneday=86400Specificheatcapacityofair=1050J/kg.oCDensityofair=1.25kgm‐2MeanDailyGroundTemperature=13oC

Page 3: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

FINDTHERESPECTIVEDAILYANDMONTHLY1. HEATLOSSinkWh;SOLARGAINinkWh;TOTALGAINinkWh2. GAIN/LOSSRATIOANDUTILISATIONFACTOR3. USEFULGAINinkWh4. FABRIC/VENTILATIONLOSS5. MONTHLY/ANNUALSPACEHEATINGREQUIREMENT(inkWhandin£)Assumethecost

ofakWhtobe£0.096. INVESTIGATE THE SENSITIVITY OF THE ANNUAL SPACE HEATING REQUIREMENT TO

REPLACINGTHEGLAZINGWITHAWINDOWWITH:

(i) g=0.75,U=1.6W/(m2C);(ii)g=0.34,U=1.1W/m2C7. FOR CASE i) INVESTIGATE THE SENSITIVITY OF THE ANNUAL SPACE HEATING

REQUIREMENTTOTHEWINDOWWALLRATIO.8. FORCASEi)ANDTHEDEFAULTGLAZINGAREASINVESTIGATETHESENSITIVITYOFTHE

ANNUAL SPACE HEATING REQUIREMENT TO THE AIR TIGHTNESS OF THE BUILDING.ASSUMINGANAIDIABETICINTERFACECALCULATEANDCOMPARETHEANNUALSPACEHEATINGREQUIREMENTFORASEMI‐DETATCHEDANDMID‐TERRACEBUILDING.

Page 4: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

TotalMonthlyHeatLosses(kWh)

MonthlyHeatLossesDividedBySource(kWh)

Page 5: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

TotalMonthlySolarGain.(kWh)

MonthlySolarGainsDividedBySourcingFaçade.(kWh)

Page 6: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

TotalMonthlyGain.(kWh)

Page 7: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

TotalLosses/TotalUsefulGains/TotalLossesGraphsTobeaddedasoverlayedgraph.

Page 8: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

TotalMonthlyGains&Losses.(kWh)

TheGainsToLossesRatio(GLR)&TheUtilisationFactor(UF)Compared.

Page 9: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

MonthlyUsefulHeatGain(kWh)

Page 10: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

MonthlyVentillationLosses(kWh)

Page 11: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

MonthlySpaceHeatingRequirement.(kWh)

AnnualSHR(kWh) 10825.6825

AnnualCost(£0.09) 974.3114251

Page 12: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

INVESTIGATE THE SENSITIVITY OF THE ANNUAL SPACE HEATING REQUIREMENT TOREPLACINGTHEGLAZINGWITHAWINDOWWITH:

(i) g=0.75,U=1.6W/(m2C);

AnnualSHR(kWh) 9597.516277

AnnualCost(£0.09) 863.7764649

(ii) g=0.34,U=1.1W/m2C

Page 13: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

AnnualSHR(kWh) 9046.125425

AnnualCost(£0.09) 814.1512882

Page 14: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

AComparisonOfTheMonthlySHROfOption(i),(ii)&Default.(kWh)

Page 15: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

TheaffectofairchangeontheASHRinadetatched,semidetatchedandmidterracehouse.(kWh)

DataForOption(i)Detatched AirChanges/n

AnnualSHR(kWh) Cost(£)

0.1 8026.88 542.420.2 6887.26 619.850.3 7771.00 699.390.4 8675.23 780.770.5 9597.52 863.780.6 10535.81 948.220.7 11488.38 1033.950.8 12453.75 1120.840.9 13430.62 1208.761.0 14417.89 1297.61

DataForOption(i)SemiDetatchedAirChanges/n

AnnualSHR(kWh) Cost(£)

0.1 4384.5 394.610.2 5189.77 467.080.3 6026.12 542.350.4 6889.24 620.030.5 7775.61 699.80.6 8682.31 781.410.7 9606.92 864.62

0.80 10547.41 949.270.90 11502.04 1035.181.00 12469.33 1122.24

DataForOption(i)Mid‐TerraceHouseAirChanges/n

AnnualSHR(kWh) Cost(£)

0.1 2595.75 233.620.2 3305.88 297.530.3 4062.51 365.630.4 4858.13 437.230.5 5686.76 511.810.6 5643.67 588.930.7 7424.95 668.250.8 8327.49 749.470.9 9248.65 832.381 10182.26 916.76

Page 16: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

g=0.85TOTALDAILYHEATLOSSES/GAINS/USEFULLGAINSinkWh

MONTHLYHEATLOSSES/GAINS/USEFULLGAINSinkWh

GAIN/LOSSRATIOANDUTILISATIONFACTOR

Page 17: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

g=0.75TOTALDAILYHEATLOSSES/GAINS/USEFULLGAINSinkWh

MONTHLYHEATLOSSES/GAINS/USEFULLGAINSinkWh

GAIN/LOSSRATIOANDUTILISATIONFACTOR

Page 18: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

g=0.34TOTALDAILYHEATLOSSES/GAINS/USEFULLGAINSinkWh

MONTHLYHEATLOSSES/GAINS/USEFULLGAINSinkWh

GAIN/LOSSRATIOANDUTILISATIONFACTOR

Page 19: 2007 Article - Space Heating Excel Model Calculated, Run & Analysed.

MONTHLYSPACEHEATINGREQUIREMENT(in£)costofakWh‐>£0.09