2 Motor Protection Alstom.no Iet Logo
Transcript of 2 Motor Protection Alstom.no Iet Logo
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
1/72
Copyright of AREVA T&D UK Limited
This document is the exclusive property of Alstom Grid and shall not betransmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
GRID
Technical Institute
Motor Protect ion
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
2/72
2 > Motor Protection
In t roduct ion
Many different applications
Different motor characteristics
Difficult to standardise protection
Protection applied ranges from
FUSES to RELAYS
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
3/72
3 > Motor Protection
In t roduct ion
COST & EXTENT POTENTIAL
OF PROTECTION HAZARDS
SIZE OF MOTOR,TYPE & IMPORTANCE
OF THE LOAD
=
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
4/72
4 > Motor Protection
SYSTEM
Voltage Dips
Voltage Unbalance
Loss of supply
Faults
Motor Protect ion
MOTOR CIRCUIT
Insulation failure
Open circuits
Short circuits
Overheating
LOAD
Overload
Locked rotor
Coupling faults
Bearing faults
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
5/72
5 > Motor Protection
For Induc t ion motors
The main types to be considered :-
Overtemperature
Thermal overload
Stall / Locked rotor
Phase unbalance and single phasing
Short Circuit
Earth Fault
Undercurrent
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
6/72
6 > Motor Protection
Motor Protect ion Appl ication
Voltage Rating Switching ProtectionDevice
< 600V < 11kW Contactor (i) Fuses
(ii) Fuses + direct acting
thermal O/L + U/V
releases
< 600V 11 - 300kW Contactor Fuses+ Electronic O/L
3.3kV 100kW - 1.5MW Contactor + Time delayed E/F
Options :- Stalling
6.6kV 1MW - 3MW Contactor Undercurrent
6.6kV > 1MW Circuit
Breaker As above
+ Instantaneous O/C
11kV > 1MW Circuit + DifferentialBreaker
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
7/727 > Motor Protection
Protection must be able to :-
Operate for abnormal conditions
Protection must not :-
Affect normal motor operation
Considerations :-
Starting current
Starting time
Full load current
Stall withstand time (hot & cold)
Thermal withstand
In t roduct ion
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
8/728 > Motor Protection
Motor Currents
INDUCTION MOTOR
Define Slip, S, as the per unit difference in speed betweenthe stator and rotor fields
Slip S = f- fr
f
Speed of stator field relative to rotor
f - fr = sf
frStator
Field f
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
9/729 > Motor Protection
Motor Currents
INDUCTION MOTOR
Magnitude of induced volts :
Proportional to sf
Frequency of induced rotor current :
Equal to sf
R2
kVS
X2 = 2fL(STAND STILL)
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
10/7210 > Motor Protection
Rotor Equ ivalent Circui ts
STANDSTILL :
R2
kVS
X2 = 2fLROTOR
REACTANCE
AT
STANDSTILL
RUNNING :
R2
SkVS2sfL
= sX2
1/2
XS
R
kV
1/2XSR
skVCurrentRotor
22
22
2s
222
22
s
R2
SkVS X2
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
11/7211 > Motor Protection
Rotor Equ ivalent Circui ts
R2
SkVS2sfL
= sX2
1/2
XS
R
kV
1/2XSR
skV
CurrentRotor
2
2
222
s
222
22
s
R2
SkVS X2
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
12/7212 > Motor Protection
Motor Start ing Character ist ics
1/2
XS
R
kV
1/2XSR
skVphaseperCurrentRotor
22
222
s
22222
s
Time
Start
Time
CurrentFull Load Current
X2 >> R2Therefore R2 >> X2when s is small
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
13/7213 > Motor Protection
Abou t to Start
Phase Loss
Low Volts
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
14/7214 > Motor Protection
Reverse Phase Sequence Start ing
Protection required for lift motors, conveyors
Instantaneous I2 unit
Time delayed thermal trip
Separate phase sequence detector for low loadcurrent machines
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
15/72Copyright of AREVA T&D UK Limited
This document is the exclusive property of Alstom Grid and shall not betransmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
GRID
Technical Institute
Undervol tage
Protect ion
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
16/7216 > Motor Protection
Undervol tage
Causes low output torque
machine cannot reach rated speed
draws high stator current
Use time delayed undervoltage protection
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
17/7217 > Motor Protection
47 Three Phase Voltage Check
V2Start Low V Setting
Avoids excessive start times on DOL machines caused byinadequate voltage
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
18/7218 > Motor Protection
Undervo l tage Considerations
Reduced torque
Increased stator current
Reduced speed
Failure to run-up
Form of undervoltage condition :-
Slight but prolonged (regulation)
Large transient dip (fault clearance)
Undervoltage protection :-
Disconnects motor from failed supply
Disconnects motor after dip long enough to preventsuccessful re-acceleration
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
19/7219 > Motor Protection
Undervo l tage Tripp ing
Means of undervoltage tripping :-
AC holding coil for fused contactor
Undervoltage release
Undervoltage relay for shunt trip
Definite time
Inverse time
Considerations:-
U/V tripping should be delayed for essential motorsso that they may be given a chance to re-acceleratefollowing a short voltage dip (< 0.5s)
Delayed drop-out of fused contactor could bearranged by using a capacitor in parallel with the ACholding coil
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
20/72Copyright of AREVA T&D UK Limited
This document is the exclusive property of Alstom Grid and shall not betransmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
GRID
Technical Institute
Mechanical
Overload
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
21/7221 > Motor Protection
Mechanical Overload
OVERLOAD
HEATING
INSULATION
DETERIORATION
OVERLOAD PROTECTION
THERMAL REPLICAFUSES
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
22/7222 > Motor Protection
Motor Heating
HEAT STORED
INCREASES THEMOTOR TEMPERATURE
HEAT DISSIPATED AT A
RATE PROPORTIONAL TO
MOTOR TEMPERATURE
HEAT DEVELOPED AT A
CONSTANT RATE DUE TO
CURRENT FLOW
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
23/72
23 > Motor Protection
Moto r Heating
MOTOR TEMPERATURE
T = Tmax (1 - e-t/)
or as temp rise (current)2T = KI2max (1 - e-t/)
Rate of rise depend on motorthermal time constant
Time
TMAX
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
24/72
24 > Motor Protection
Motor Heating
Time
TMAX
T1T2
t2 t1
I2
I22I1
2
IR2
Time
Current
IR I1 I2
t1t2
Thermal Withstand
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
25/72
25 > Motor Protection
Motor Heating
-
-1nt
2eq
2
m2
eq2
22
22
1-K
a-K1nt
I2 - I2m = (I2eq - I2m) (1 - e-t/)
Rearranging this expression in terms of time
or alternatively
Time
I
2eq
I2
I2
m
tTRIP
Current2
M t C l i
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
26/72
26 > Motor Protection
Motor Cool ing
COOLING EQUATION :
I2m' = I2m e
-t/r
After time t equivalent motor current is reduced from Im to Im.
Time
Im
Current2
Im'
t0
M t H ti
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
27/72
27 > Motor Protection
Motor Heating
t1 = Motor restart not possible
t2 = Motor restart possible
Time
Tmax
t2t1
Trip
Temp
Cooling timeconstant r
T
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
28/72
Copyright of AREVA T&D UK Limited
This document is the exclusive property of Alstom Grid and shall not betransmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
GRIDTechnical Institute
Start / Stal l Pro tectio n
St l l i P t t i
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
29/72
29 > Motor Protection
Stal l ing Protect ion
Required for :-
Stalling on start-up (locked rotor)
Stalling during running
With normal 3 supply :-
ISTALL = ILOCKED ROTOR @ ISTART
Cannot distinguish between STALL and START by currentalone.
Most cases :- tSTART < tSTALL WITHSTAND
Sometimes :- tSTART > tSTALL WITHSTAND
L k d R t P t t i
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
30/72
30 > Motor Protection
Locked Rotor Protect ion
Start Time < Stal l Withs tand Time
Where Starting Time is less than Stall Withstand Time :
Use thermal protection characteristic
Use dedicated locked rotor protection
St l l P t t i
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
31/72
31 > Motor Protection
Stal l Protec t ion :-
tSTART< tSTALL
Thermal relay provides protection against 3 stall.
Thermal
StallWithstand
Start
t
tS
LtS
T
IFLISTISL
I
If St l l With t d I B l Th l C
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
32/72
32 > Motor Protection
If Stal l Withstand Is Below Thermal Curve
Separate stalling relay required :- Definite time O/C.
tSTART
Thermal
StallWithstand
tS
LtS
ISISTISL
Definite Time
Trip
(tS)T
O/C (IS)
tSL > tS > tSTART
Stal l Protect ion
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
33/72
33 > Motor Protection
Stal l Protect ion
Tstart < Tstall
Use of motor start contact and 2 stage definite time overcurrent relay.
Current
+ -
TD1MSD
TD1 O/C
TD2
TRIP
TD2
86
Time
TD1+TD2
starttime
TD1
tST
Cold Stall tSL (COLD)
TD2
Full loadCurrent
Io/c
Hot Stall tSL (HOT)
TD1 > tST (TD1 + TD2) < tSL(COLD)
TD2 < tSL(HOT)
Loc ked Rotor Protect ion
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
34/72
34 > Motor Protection
Motors with high inertia loads may often take longer to startthan the stall withstand time
However, the rotor is not being damaged because, as therotor turns the skin effect reduces, allowing the current to
occupy more of the rotor winding
This reduces the heat generated and dissipates the existingheat over a greater area
Detect start using tachometer input
Loc ked Rotor Protect ion
Start Time > Cold Stal l Withs tand Time
Stal l Protect ion
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
35/72
35 > Motor Protection
Stal l Protect ion
Tstart > Tstall
Use of tachoswitch and definite time overcurrent relay.
+ -
TDO/C
TD
TRIP
86
TACHOTime
StartTime
TD
Full loadCurrent
CurrentIo/c
Stall - Tstall
Tacho opens at
10% speedTD < Tstall
> Tacho opening
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
36/72
Copyright of AREVA T&D UK Limited
This document is the exclusive property of Alstom Grid and shall not betransmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
GRIDTechnical Institute
Unbalanced Supply Protect ion
Motor Currents
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
37/72
37 > Motor Protection
Motor Currents
NEGATIVE SEQUENCE CURRENT
Relative frequency of stator field = f + fr
But fr = (1-s)f
Therefore f + fr = (2-s)f
fr
Stator
Field f
Operat ion on Supply Unbalance
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
38/72
39 > Motor Protection
Operat ion on Supply Unbalance
At normal running speed
POSITIVE SEQ IMP STARTING CURRENT
NEGATIVE SEQ IMP NORMAL RUNNING CURRENT
Negative sequence impedance is much less than positivesequence impedance.
Small unbalance = relatively large negative sequence current.
Heating effect of negative sequence is greater than equivalentpositive sequence current because they are HIGHERFREQUENCY.
Equivalent Moto r Current
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
39/72
40 > Motor Protection
Equivalent Moto r Current
Heating from negative sequence current greater than positivesequence
take this into account in thermal calculation
Ieq = (I12 + nI2
2)
where : n = typically 6
small amount of I2 gives large increase in Ieq andhence calculated motor thermal state.
Loss of 1 Phase While Start ing
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
40/72
41 > Motor Protection
Loss of 1 Phase While Start ing
A
ANABA
ANA
x0.8662z
3V
2z
V'
openphase1With
z
V
currentstartingNormal
A2
A2
B2
A2
A1
ABA1
2
1
')a-(13
1)'a'(
3
1
21
'a)-(13
1)'a'(
3
1
STAR DELTA
normalx0.866
2z3xV
openPhase1
z
3VNormal
AB
AB
A
z
z
z
BC
A
B
C
1 winding carries twice
the current in the other 2.
Sing le Phase Stal l ing Protect io n
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
41/72
42 > Motor Protection
Sing le Phase Stal l ing Protectio n
Loss of phase on starting motor remains stationary
Start Current = 0.866 normal start I
Neg seq component = 0.5 normal start I
Clear condition using negative sequence element
Typical setting ~ 1/3 I2
i.e. 1/6 normal start currenti.e. Rated Current
Single Phasing Wh ile Runn ing
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
42/72
43 > Motor Protection
Single Phasing Wh ile Runn ing
Difficult to analyse in simple terms
Slip calculation complex
Additional I2 fed from parallel equipment
Results in :- I2 causes high rotor losses.
Heating considerably increased.
Motor output reduced.
May stall depending on load. Motor current increases.
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
43/72
Copyright of AREVA T&D UK Limited
This document is the exclusive property of Alstom Grid and shall not betransmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
GRIDTechnical Institute
Insu lat ion Failure
Insulat ion Failure
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
44/72
45 > Motor Protection
Insulat ion Failure
Results of prolonged or cyclic overheating
Instantaneous Earth Fault Protection
Instantaneous Overcurrent Protection
Differential Protection on some large machines
Stator Earth Fault Protect ion
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
45/72
46 > Motor Protection
Stator Earth Fault Protect ion
M
50
M
50
Rstab
(A) Residually connected CTs
(B) Core Balance (Toroidal)CT
Note: * In (A) CTs can also drive thermal protection
* In (B) protection can be more sensitive
and is stable
Typical Core-Balance CT Appl icat ion
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
46/72
47 > Motor Protection
Typical Core Balance CT Appl icat ion
50
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
47/72
48 > Motor Protection
50
Short Circui t
Due to the machine construction internal phase-phase faultsare almost impossible
Most phase-phase faults occur at the machine terminals oroccasionally in the cabling
Ideally the S/C protection should be set just above the maxIstart (I>>=1.25Istart), however, there is an initial start currentof up to 2.5Istart which rapidly reduces over 3 cycles
Increase I>> or delay tI>> in small increments accordingto start conditions
Use special I>> characteristic
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
48/72
Copyright of AREVA T&D UK Limited
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
GRIDTechnical Institute
Differen tial Protect ion
High-Impedance Wind ing Dif ferent ial Protect ion
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
49/72
50 > Motor Protection
High Impedance Wind ing Dif ferent ial Protect ion
A
B
C
87A
87B
87C
Note: Protection must be stable with starting current.
Self-Balance Winding Differential Protect ion
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
50/72
51 > Motor Protection
g
A
87A
B
C
87A
87B
87C
Ins tantaneous Earth Fault or Neg. Seq.
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
51/72
52 > Motor Protection
g q
Tr ipping is not Perm it ted w ith Contactors
TRIP
MPR
M
TIME
Ts
Is Icont CURRENT
FUSE
MPR
ELEMENT
Ts > Tfuse at Icont.
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
52/72
Copyright of AREVA T&D UK Limited
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
GRIDTechnical Institute
Bearings
Bearing Failure
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
53/72
54 > Motor Protection
g
Electrical Interference
Induced voltage
Results in circulating currents
May fuse the bearings
Remember to take precautions - earthing
Mechanical Failure
Increased Friction
Loss or Low Lubricant
Heating
Bearing Failure
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
54/72
55 > Motor Protection
g
Ball or Roller Bearings
Immediate standstill
Cannot protect bearing
Stall protection for machine
Sleeve Bearings
Failure rare
Temperature rise, vibration, increase in current
Temperature sensor in bearing
Thermal overload for motor - does not protect bearing
Use of RTDs
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
55/72
56 > Motor Protection
RTD sensors at known stator hotspots
Absolute temperature measurements to bias the relaythermal characteristic
Monitoring of motor / load bearing temperatures
Ambient air temperature measurement
49 Thermal pro tect ion
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
56/72
57 > Motor Protection
p
w ith ambient compensat ion
0%
25%
50%
75%
100%
125%
0C 20C 40C 60C 80C 100C
Temperature
Ith(%settin
g)
26 Stato r RTDs
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
57/72
58 > Motor Protection
RTDs cannot provide protection to the rotor
The protection provided during overloads is dependant upontheir positioning in the Stator windings and the insulationaround them.
In general current measurement is considered superiorunder large overload conditions
They do, however, respond to other conditions not present inthe current measurement (blocked cooling etc)
Undercurrent Protect ion
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
58/72
60 > Motor Protection
Detects loss of load
e.g. Pumps & Conveyors
Submersible down hole pump
Is cooled by pumped liquid
Motor overheats if it runs dry even though
current reduces
Setting current 40% IFL
37 Loss of load
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
59/72
61 > Motor Protection
In most applications it is desirable to stop the motor ifthe mechanical coupling is lost.
In addition a pump can be damaged if it becomesunprimed
No load current is normally about 50-60% ofIfl
On lightly loaded machines underpower provides betterdiscrimination between low load and load loss
No load power about 10%
May need to inhibit during start
Normal Shutdowns
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
60/72
62 > Motor Protection
On machines where the thermal element is limited duringstart, it is critical to ensure that restarts do not damagethe machine
Selectable thermal start inhibit
Jogging
Selectable number of hot starts, cold starts, period andinhibit time
Selectable time between 2 starts
49 Thermal start inh ibit
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
61/72
63 > Motor Protection
PROHIBIT START
Motor halt
Newrestart Prohibit START
Threshold
66 Lim ited starts/period
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
62/72
64 > Motor Protection
Cold start Hot start Hot start
Treference
2 hot starts
Information on StartProhibited
Tprohibit
66 Time between 2 starts
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
63/72
65 > Motor Protection
Tbetween 2 starts
Signal Minimum time between 2 restarts
Tbetween 2 starts Tbetween 2 starts
86 Lockout
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
64/72
66 > Motor Protection
Some trips require maintenance before the machine canbe restarted. A latched trip may be applied for thefollowing conditions
Short circuit
Earth faults
Loss of Phase
Emergency Restart
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
65/72
67 > Motor Protection
In certain applications, such as mine exhaust and shippumps, a machine restart is required knowing that itwill result in reduced life or even permanent damage.
All start up restrictions are inhibited
Thermal state limited to 90%
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
66/72
Copyright of AREVA T&D UK Limited
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the priorwritten consent of Alstom Grid Technical Institute. All rights reserved.
GRIDTechnical Institute
Synchronous Motors
Synchronous Machines
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
67/72
69 > Motor Protection
OUT OF STEP PROTECTION
Inadequate field or excessive load can cause the machineto fall out of step. This subjects the machine toovercurrent and pulsating torque leading to stalling
Field Current Method
Detect AC Cu rrent Induced In Field Circuit .
Power Factor Method
Detect Heavy Current A t Low Power Factor.
Synchronous Machines
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
68/72
70 > Motor Protection
LOSS OF SUPPLY
On loss of supply motor should be disconnected ifsupply could be restored automatically.
Avoids supply being restored out of phase.
Overvoltage & Underfrequency
Underpower & Reverse Power
Synchronous Machines
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
69/72
71 > Motor Protection
Overvoltage
> Busbar & motor unloaded:
Motor terminal voltage may rise instantaneously
to 20 - 30% on loss off supply due to open circuit
regulation of the motor
Synchronous Machines
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
70/72
72 > Motor Protection
Underfrequency
> Motor loaded:
Decelerate fairly quickly & frequency ofterminal voltage will fall.
Synchronous Machines
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
71/72
73 > Motor Protection
Underpower
Only applicable when power reversals do not occurunder normal operating conditions
Arranged to look into the machine; applicable whenthere is A possibility of no load connected on loss ofsupply.
Time delay required to overcome momentary powerreversals due to faults
Synchronous Machines
-
7/30/2019 2 Motor Protection Alstom.no Iet Logo
72/72
Reverse Power
Only Applicable When Power Reversals Do Not OccurUnder Normal Operating Conditions
Arranged To Look Away From The Machine; ApplicableWhere There Is Aways Load Connected.
Time Delay Required To Overcome Momentary Power
Reversals Due To Faults