1. GENERAL INFORMATION A. GOVERNING BUILDING CODE: 2009 INTERNATIONAL BUILDING CODE (IBC-2009). B. BUILDING CLASSIFICATION: THE BUILDING CLASSIFICATION ACCORDING TO IBC-2009 TABLE 1604.5 AND ASCE 7-05 TABLE 1-1 IS CATEGORY II. C. CONTRACT DOCUMENTS: THE CONTRACT DOCUMENTS CONSIST OF THE AGREEMENT BETWEEN THE OWNER AND CONTRACTOR, CONDITIONS OF THE CONTRACT, DRAWINGS, SPECIFICATIONS, ADDENDA ISSUED PRIOR TO EXECUTION OF THE CONTRACT, OTHER DOCUMENTS LISTED IN THE AGREEMENT AND MODIFICATIONS ISSUED AFTER EXECUTION OF THE CONTRACT. D. CORRELATION OF THE CONTRACT DOCUMENTS: THE CONTRACT DOCUMENTS ARE COMPLIMENTARY, AND WHAT IS REQUIRED BY ONE SHALL BE AS BINDING AS IF REQUIRED BY ALL. IF CONFLICTING REQUIREMENTS ARE FOUND BETWEEN THE DRAWINGS, SPECIFICATIONS AND/OR THESE GENERAL NOTES, THE MORE STRINGENT PROVISION SHALL CONTROL UNLESS DIRECTED OTHERWISE IN WRITING BY THE STRUCTURAL ENGINEER. E. ELEVATIONS: REFERENCE ELEVATION OF 100'-0" EQUALS FINISHED FLOOR ELEVATION FOR THE NEW BUILDING. 2. DESIGN LOADS A. DEAD LOAD: SELF WEIGHT OF MATERIALS, UNLESS NOTED OTHERWISE B. ROOF DEAD LOAD: 1) BUILT UP ROOF................................................6 PSF 2) INSULATION...................................................2 PSF 3) DECK.........................................................2 PSF 4) BEAMS, JOISTS & BRIDGING.....................................3 PSF 5) CEILING......................................................1 PSF 6) MISC (LIGHTING, DUCTWORK, PIPING, ETC.)......................2 PSF 7) TOTAL.......................................................16 PSF C. FLOOR DEAD LOAD: 1) 3½" CONC. OVER 0.6 NON-COMPOSITE METAL DECKING..............41 PSF 2) BEAMS, JOISTS, AND BRIDGING..................................5 PSF 3) CEILING......................................................1 PSF 4) MISC (LIGHTING, DUCTWORK, PIPING, ETC.) .....................3 PSF 5) TOTAL.......................................................50 PSF D. LIVE LOADS: 1) ROOF LIVE LOAD .............................................20 PSF 2) FLOOR LIVE LOAD A) LOBBIES.................................................100 PSF B) CORRIDORS................................................80 PSF C) OFFICES W/ PARTITION LOAD................................65 PSF E. WIND LOADS: 1) GOVERNING CODE:..........................................ASCE 7-05 2) IMPORTANCE FACTOR, Iw:........................................1.00 3) EXPOSURE CATEGORY:...............................................C 4) WIND VELOCITY, V:...........................................90 MPH F. SNOW LOADS: 1) GOVERNING CODE:..........................................ASCE 7-05 2) IMPORTANCE FACTOR, Is:........................................1.00 3) GROUND SNOW LOAD, Pg:.......................................10 PSF 4) EXPOSURE FACTOR, Ce:...........................................1.0 5) ROOF SLOPE FACTOR, Cs:.........................................1.0 6) CALCULATED FLAT ROOF SNOW LOAD, Pf:..........................7 PSF 7) MINIMUM FLAT ROOF SNOW LOAD, I*Pf:..........................10 PSF 8) RAIN ON SNOW SURCHARGE LOAD:.................................5 PSF 9) DRIFT LOADS:.............................................ASCE 7-05 G. SEISMIC DESIGN CRITERIA: 1) GOVERNING CODE:..........................................ASCE 7-05 2) IMPORTANCE FACTOR, Ie:........................................1.00 3) SOIL SITE CLASSIFICATION (ASSUMPTION MADE FROM ADJACENT PROPERTY VALUES):.........................................................D 4) 0.2 SEC. MAPPED SPECTRAL ACCELERATION, Ss:...................0.279 5) 1.0 SEC. MAPPED SPECTRAL ACCELERATION, S1:...................0.079 6) SITE COEFFICIENT, 0.2 SEC. PERIOD, Fa:........................1.58 7) SITE COEFFICIENT, 1.0 SEC. PERIOD, Fv:.........................2.4 8) 0.2 SEC. DESIGN SPECTRAL ACCELERATION, Sds:..................0.239 9) 1.0 SEC. DESIGN SPECTRAL ACCELERATION, Sd1:..................0.126 10) SEISMIC DESIGN CATEGORY:.........................................B 11) SEISMIC USE GROUP:..............................................II 12) SEISMIC PARAMETERS FOR ELEVATOR SHAFT: A) SEISMIC FORCE RESISTING SYSTEM: ORDINARY REINFORCED MASONRY SHEAR WALLS B) RESPONSE MODIFICATION COEFFICIENT, R:.....................2.00 C) SYSTEM OVERSTRENGTH FACTOR, O:............................2.50 D) DEFLECTION AMPLIFICATION FACTOR, Cd:......................1.75 E) ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE METHOD. F) SEISMIC RESPONSE COEFFICIENT, Cs:........................0.147 G) TOTAL LATERAL BASE SHEAR, V:............................1 KIPS 3. MATERIAL DESIGN VALUES A. CONCRETE (MINIMUM ULTIMATE COMPRESSIVE STRENGTH AT 28 DAYS, NORMAL WEIGHT U.N.O.): 1) FOUNDATIONS:.............................................4,000 PSI 2) CONCRETE SLAB-ON-GRADE:..................................4,000 PSI 3) ALL OTHER STRUCTURAL CONCRETE, U.N.O:....................4,000 PSI B. REINFORCED CONCRETE MASONRY (MINIMUM ULTIMATE COMPRESSIVE STRENGTH AT 28 DAYS): 1) PRISMS (ASTM C1314), f'm:................................1,500 PSI 2) MORTAR (ASTM C270).......................................1,800 PSI 3) CONCRETE MASONRY UNITS (ASTM C90)........................1,900 PSI 4) GROUT....................................................3,000 PSI C. CONCRETE AND MASONRY REINFORCEMENT (MINIMUM YIELD STRENGTH) 1) ALL PLAIN AND DEFORMED BARS (ASTM A615, GRADE 60)......FY = 60 KSI 2) WELDED WIRE FABRIC (ASTM A184) ........................FY = 60 KSI 3) WELDABLE REINFORCING BARS (ASTM A706) .................FY = 60 KSI D. STRUCTURAL STEEL (MINIMUM YIELD STRENGTH) 1) ALL WIDE FLANGE SHAPES (ASTM A992)....................FY = 50 KSI 2) STRUCTURAL TUBES (ASTM A500, GRADE B)..................FY = 46 KSI 3) PIPES (ASTM A53, GRADE B)..............................FY = 35 KSI 4) ANCHOR RODS (ASTM F1554, GRADE 55, WELDABLE) ..........FY = 55 KSI 5) DEFORMED BAR ANCHORS (ASTM A496).......................FY = 70 KSI 6) ALL OTHER SHAPES AND PLATES UNLESS NOTED (ASTM A36)....FY = 36 KSI E. COLD FORMED STEEL (MINIMUM YIELD STRENGTH) 1) ROOF DECK (ASTM A653, SS GRADE 33, G-60 GALVANIZED)....FY = 33 KSI 2) COMPOSITE FLOOR DECK (ASTM A653, SS GRADE 40, G-60 GALVANIZED)............................................FY = 40 KSI 3) COLD FORMED METAL STUDS (ASTM A1003/A, GRADE ST33H, G-60 GALVANIZED)............................................FY = 33 KSI 4) COLD FORMED METAL CLIPS (ASTM A653, SS GRADE 50,G-90 GALVANIZED)............................................FY = 50 KSI 4. DEMOLITION NOTES A. ALL DIMENSIONS FOR THE EXISTING STRUCTURE SHALL BE VERIFIED IN THE FIELD PRIOR TO PROCEEDING WITH ANY DEMOLITION OR NEW WORK. B. AS DEMOLITION OR NEW WORK PROGRESSES THE CONTRACTOR SHALL MAKE WRITTEN DOCUMENTATION IF INCONSISTENCIES OCCUR IN THE EXISTING STRUCTURE. THESE INCONSISTENCIES SHALL BE SUBMITTED TO THE OWNER'S REPRESENTATIVE FOR REVIEW. C. THE CONTRACTOR SHALL PROVIDE AND INSTALL ALL SHORING, PROPS, AND GUYS REQUIRED FOR THE TEMPORARY SUPPORT OF EXISTING PIPING, STRUCTURE, ETC. AS MAY BE NECESSARY TO COMPLETE THE REQUIRED DEMOLITION OR NEW WORK. D. THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING EXISTING UTILITIES, BOTH CHARTED AND UNCHARTED BEFORE COMMENCING WITH ANY EXCAVATION OR DEMOLITION WORK. DEPTH OF CONCRETE SAW SHALL BE SET SO AS NOT TO CUT ANY LOCAL UNDER FLOOR PIPING OR WIRING WHICH IS TO REMAIN. E. THE PROJECT AREA SHALL BE MAINTAINED AS CLEAN AS POSSIBLE WITH DUST BEING LIMITED AS MUCH AS PRACTICAL. DEMOLITION SHALL PROCEED AS DIRECTED BY THE OWNER'S REPRESENTATIVE. F. WHEN SAW CUTTING, SPECIAL CARE SHALL BE TAKEN TO NOT OVER CUT INTO AN EXISTING AREA OF STRUCTURE THAT WILL REMAIN. 5. FOUNDATION NOTES A. GEOTECHNICAL REPORT: A GEOTECHNICAL ENGINEERING SERVICES REPORT WAS NOT PROVIDED, THUS MINIMUM DESIGN VALUES WERE USED PER IBC 2009. B. BUILDING FOUNDATIONS 1) SHALLOW FOOTINGS: THE PROPOSED BUILDINGS SHALL BE SUPPORTED ON CONVENTIONAL SHALLOW SPREAD FOOTINGS FOUNDED ON EXISTING NON-EXPANSIVE SOIL OR PROPERLY COMPACTED ENGINEERED FILL. 2) FOOTING DESIGN PARAMETERS: SHALLOW SPREAD FOOTINGS FOR BUILDING COLUMNS AND CONTINUOUS FOOTINGS FOR BEARING WALLS HAVE BEEN DESIGNED FOR A TOTAL ALLOWABLE SOIL BEARING PRESSURE OF 1,500 POUNDS PER SQUARE FOOT, BEARING ON EXISTING SOIL OR PROPERLY COMPACTED ENGINEERED FILL. 3) PIPE PENETRATIONS: ALL HORIZONTAL PIPE OR SIMILAR PENETRATIONS OR SLEEVES THROUGH FOOTINGS SHALL PREFERABLY OCCUR WITHIN THE MIDDLE 1/3 OF THE FOOTING DEPTH. AT PENETRATIONS, PROVIDE (4) #5 DIAGONAL BARS AT EACH FOOTING FACE (3" CLEAR BETWEEN BAR AND PENETRATION AND 3" CLEAR FROM FOOTING BEARING). IF PENETRATION MUST OCCUR NEAR THE BOTTOM OF FOOTING, REFER TYPICAL DETAILS FOR STANDARD DETAIL TO TRANSITION & THICKEN FOOTING TO ACCOMMODATE PENETRATION. C. SLAB-ON-GRADE CONSTRUCTION 1) SLAB THICKNESS AND REINFORCING: SLABS-ON-GRADE SHALL BE 6" THICK CONCRETE REINFORCED WITH #4 BARS AT 18" ON CENTER EACH WAY. REINFORCING BARS SHALL BE PLACED 1½" CLEAR FROM TOP OF SLAB USING CHAIRS OR SLAB BOLSTERS COMPLYING WITH CRSI'S "MANUAL OF STANDARD PRACTICE". 2) SLAB SUBGRADE: THE FLOOR SLAB SHALL BE GRADE SUPPORTED ON EXISTING NON-EXPANSIVE SOILS. 3) AGGREGATE BASE COURSE: A 6-INCH THICK, FREE-DRAINING SAND BASE COURSE SHALL BE PLACED BENEATH THE FLOOR SLAB TO ENHANCE DRAINAGE AND PROVIDE INCREASED SUBGRADE STRENGTH. AT THE TIME OF THE SLAB PLACEMENT, THE GRANULAR BASE SHALL BE MOIST, BUT FREE OF ANY STANDING OR SELF-DRAINING WATER. 4) VAPOR RETARDER: A VAPOR RETARDER SHALL BE PLACED IMMEDIATELY BELOW THE CONCRETE SLAB. VAPOR RETARDER SHALL BE SEALED TO PREVIOUSLY PLACED CONCRETE AS RECOMMENDED BY VAPOR RETARDER MANUFACTURER. BEFORE PLACING CONCRETE, PATCH AND SEAL ANY RIPS, TEARS OR HOLES IN VAPOR RETARDER INCURRED DURING CONSTRUCTION. 5) SLAB MIX DESIGN: SLAB-ON-GRADE CONCRETE MIX SHALL BE DESIGNED FOR A 28-DAY COMPRESSIVE STRENGTH OF 4,000 PSI, A WATER-CEMENT RATIO OF 0.40 AND A MAXIMUM SLUMP OF 4-INCHES. 6) MOIST CURING OF SLAB: SLABS-ON-GRADE SHALL BE WATER CURED FOR A MINIMUM OF 7 DAYS BY PONDING, SPRAYING, SPRINKLING OR BY USE OF SATURATED COVERINGS. 7) ISOLATION JOINTS: PROVIDE SLAB ISOLATION AROUND COLUMNS PENETRATING THE SLAB-ON-GRADE. PROVIDE 30# FELT AROUND PERIMETER OF ISOLATION JOINTS. REFER TO TYPICAL DETAILS AND ADDITIONAL INFORMATION. 8) SLAB JOINTS: SLAB JOINTS SHALL BE PROVIDED AS SHOWN IN THE TYPICAL DETAILS. THE FOLLOWING JOINT TYPES ARE SHOWN ON THE DRAWINGS: A) CJ = CONSTRUCTION JOINT B) SJ = SAWED CONTRACTION JOINT C) EJ = EXPANSION JOINT D. MISCELLANEOUS 1) DRAINAGE CONSIDERATIONS: DUE TO ADVERSE EFFECT ON STRUCTURES, WATER SHALL NOT BE ALLOWED TO COLLECT IN THE FOUNDATION EXCAVATION OR ON PREPARED SUBGRADE OF THE CONSTRUCTION AREA EITHER DURING OR AFTER CONSTRUCTION. UNDERCUT OR EXCAVATED AREAS SHALL BE SLOPED TOWARD ONE CORNER TO FACILITATE REMOVAL OF ANY COLLECTED RAINWATER, OR POSITIVE RUNOFF SHALL BE PROVIDED. THE CONTRACTOR SHALL EXERCISE CARE IN CREATING DRAINAGE PATHS FOR WATER DURING THE CONSTRUCTION PHASE OF THE PROJECT. TO REDUCE INFILTRATION OF SURFACE WATER AROUND THE PERIMETER OF THE BUILDING AND BENEATH THE FLOOR SLABS, POSITIVE DRAINAGE SHALL BE PROVIDED DURING ALL PHASES OF CONSTRUCTION. 2) EXCAVATION AND TEMPORARY SLOPES: THE CONTRACTOR, DESIGNATED AS "RESPONSIBLE PERSON" IN OSHA CONSTRUCTION STANDARDS FOR EXCAVATIONS, 29 CFR PART 1926, IS SOLELY RESPONSIBLE FOR PLANNING AND IMPLEMENTING ALL SAFETY PROCEDURES. ALL EXCAVATION HEIGHT, SLOPE, AND DEPTH MUST ADHERE TO ALL SPECIFICATIONS OUTLINED IN LOCAL, STATE, AND FEDERAL SAFETY REGULATIONS. KFC ENGINEERING DOES NOT ASSUME ANY RESPONSIBILITY FOR CONSTRUCTION SITE SAFETY OR ANY PARTY'S, INCLUDING THE CONTRACTOR'S, COMPLIANCE WITH THE APPLICABLE LOCAL, STATE, AND FEDERAL SAFETY REGULATIONS OR ANY OTHER APPLICABLE REGULATIONS. 3) TRENCH BACKFILL: ALL REQUIRED TRENCH BACKFILL SHALL BE MECHANICALLY COMPACTED IN LAYERS TO AT LEAST 95% OF THE STANDARD PROCTOR MAXIMUM DRY DENSITY AS DETERMINED BY ASTM D 698. SOME SETTLEMENT OF THE BACKFILL MAY BE EXPECTED AND ANY UTILITIES WITHIN THE TRENCHES SHALL BE CONSTRUCTED TO ALLOW THESE DIFFERENTIAL MOVEMENTS. REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. 4) CONSTRUCTION MONITORING: MIDWEST ENGINEERING AND TESTING CORPORATION (METCO) SHALL BE RETAINED AS THE GEOTECHNICAL ENGINEER TO PROVIDE OBSERVATIONS AND TESTING OF SOILS EXPOSED DURING PROJECT CONSTRUCTION IN ORDER TO VERIFY THAT SOIL CONDITIONS ARE AS ANTICIPATED. CONSTRUCTION ACTIVITIES PERTAINING TO EARTHWORK, SLAB PLACEMENT, CONCRETE TESTING, AND OTHER RELATED ACTIVITIES SHALL ALSO BE OBSERVED BY PSI REPRESENTATIVES AS OUTLINED ABOVE. 6. CONCRETE CONSTRUCTION NOTES A. ALL DETAILING, FABRICATION, AND PLACING OF REINFORCING STEEL, UNLESS OTHERWISE NOTED, SHALL FOLLOW ALL SECTIONS OF THE ACI "DETAILING MANUAL-2004" (SP-66 04) AND THE ACI "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318-02). B. MIX DESIGNS SHALL BE PROPORTIONED IN ACCORDANCE WITH ACI 318, SECTION 5.3, "PROPORTIONING ON BASIS OF FIELD EXPERIENCE AND/OR TRIAL MIXTURES" AND MEET THE REQUIREMENTS OF THE SPECIFICATIONS AND ACI 211 AND 301. IF TRIAL BATCHES ARE USED, MIX DESIGN SHALL BE PREPARED BY AN INDEPENDENT TESTING LABORATORY AND ACHIEVE A COMPRESSIVE STRENGTH 1200 PSI HIGHER THAN SPECIFIED STRENGTH. C. UNLESS OTHERWISE NOTED, LAP SPLICES SHALL CONFORM TO ACI REQUIREMENTS FOR CLASS B TENSION SPLICES. REFER TO LAP LENGTH SCHEDULES FOR TYPICAL LAP REQUIREMENTS. D. PROVIDE CORNER BARS IN BOTH FACES OF ALL CONTINUOUS GRADE BEAMS, FOOTINGS AND WALLS. NUMBER, SIZE, AND SPACING OF CORNER BARS SHALL BE EQUAL TO NUMBER, SIZE AND SPACING OF HORIZONTAL REINFORCING WITH WHICH THEY LAP AND SHALL HAVE CLASS B TENSION LAP SPLICES IN EACH DIRECTION. REFER TO TYPICAL DETAILS FOR ADDITIONAL INFORMATION. E. UNLESS OTHERWISE NOTED, CONCRETE COVER OVER STEEL REINFORCING SHALL CONFORM TO MINIMUM REQUIRED BY ACI 318-08. F. AT INTERSECTING FOUNDATIONS, EXTEND ALL HORIZONTAL REINFORCING OF THE INTERSECTING MEMBERS BEYOND THE POINT OF INTERSECTION TO THE OPPOSITE FACE. BEND TO A STANDARD 90 DEGREE HOOK OR PROVIDE BENT DOWELS OF EQUAL SIZE AND SPACING AND LAP AS REQUIRED BY NOTE C (BUT NOT LESS THAN 12") IN EACH DIRECTION. REFER TO TYPICAL DETAILS FOR ADDITIONAL INFORMATION. G. PROVIDE CONCRETE EQUIPMENT PADS OF SIZE REQUIRED FOR EQUIPMENT FURNISHED. SEE MECHANICAL, PLUMBING, FIRE PROTECTION AND ELECTRICAL DRAWINGS FOR NUMBER, SIZE, AND LOCATION OF SUCH PADS. UNLESS OTHERWISE SHOWN, MINIMUM PAD THICKNESS SHALL BE 4" AND SHALL EXTEND A MINIMUM OF 6" BEYOND THE FACE OF THE EQUIPMENT. MINIMUM REINFORCING SHALL BE #4 BARS AT 12" O.C. EACH WAY. TOOLED OR CHAMFERED EDGES SHALL BE PROVIDED AT ALL EQUIPMENT PADS. ANCHORAGE TO SLAB SHALL BE MADE. H. THE SIZE AND LOCATION OF ALL FLOOR PITS, TRENCH DRAINS, AND OPENINGS FOR ALL DUCTS AND PIPES THROUGH WALLS, FLOORS, AND FOUNDATION WORK SHALL BE VERIFIED WITH THE MECHANICAL, PLUMBING, FIRE PROTECTION AND ELECTRICAL CONTRACTOR'S REQUIREMENTS PRIOR TO THE START OF ANY CONCRETE WORK. I. ALL CONSTRUCTION JOINTS (VERTICAL AND HORIZONTAL) IN PITS AND TRENCHES SHALL BE KEYED AND HAVE BENTONITE WATERSTOPS INSTALLED UNLESS NOTED OTHERWISE. ALL PITS AND TRENCHES SHALL BE WATERPROOFED, UNLESS NOTED OTHERWISE. J. UNLESS NOTED OTHERWISE ON ARCHITECTURAL DRAWINGS, PROVIDE 3/4" CHAMFER ON ALL EXPOSED CONCRETE EDGES. K. A SINGLE CONCRETE POUR SHALL NOT EXCEED 100' FOR CONTINUOUS SHALLOW FOOTINGS. L. ALL HORIZONTAL CONCRETE SURFACES SHALL HAVE A TROWEL FINISH (VERIFY WITH ARCHITECTURAL DRAWINGS). M. A SINGLE CONCRETE POUR FOR SLABS-ON-GRADE SHALL NOT EXTEND BEYOND THE CONSTRUCTION JOINTS (CJ'S) SHOWN ON THE FOUNDATION PLANS. REFER TO PLANS FOR SLAB JOINT PLACEMENT. N. ALL OPENINGS IN CONCRETE WALLS LARGER THAN 1'-0" IN SIZE SHALL HAVE A MINIMUM OF (2)#5 BARS PLACED AT ALL SIDES OF OPENING AND EXTENDED 2'-6" BEYOND EDGE OF OPENING. IN ADDITION, DIAGONAL CORNER BARS SHALL EXTEND 2'-6" EACH WAY BEYOND CORNER OF OPENING. REFER TYPICAL FOUNDATION DETAILS FOR MORE INFORMATION. O. FOR PLACEMENT OF CONCRETE SLABS ON UNSHORED METAL DECK, ANTICIPATE A 10% CONCRETE VOLUME INCREASE TO COMPENSATE FOR DEFLECTION OF THE METAL DECK UNDER THE WEIGHT OF WET CONCRETE. P. TO COMPENSATE FOR DEFLECTION OF METAL DECKS UNDER THE WEIGHT OF WET CONCRETE, SLABS ON METAL DECK SHALL BE LASER SCREEDED TO PROVIDE ELEVATION CONTROL DURING CONCRETE PLACEMENT OPERATIONS. 7. REINFORCED HOLLOW CMU NOTES A. REFER TO ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS RELEVANT TO ALL CMU CONSTRUCTION. B. ALL CMU SHALL BE 1 OR 2-CELL LIGHTWEIGHT CONCRETE BLOCK. C. UNLESS NOTED OTHERWISE, ALL CONCRETE MASONRY UNITS SHALL HAVE A MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 1900 PSI ON THE NET AREA (INDIVIDUAL STRENGTH PER ASTM C 90). D. CMU SHALL BE CONSTRUCTED WITH PORTLAND CEMENT/LIME, TYPE S MORTAR CONFORMING TO ASTM A C270 WITH AN MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 1800 PSI. E. CELLS WHICH CONTAIN REINFORCING STEEL SHALL BE FILLED SOLIDLY WITH 3000 PSI PEA-GRAVEL CONCRETE OR 3000 PSI GROUT. F. VERTICAL CELLS TO BE FILLED SHALL HAVE VERTICAL ALIGNMENT SUFFICIENT TO MAINTAIN A CLEAR UNOBSTRUCTED CONTINUOUS VERTICAL CELL NOT LESS THAN 2"x3" IN PLAN DIMENSION. G. SLAB DOWELS SHALL EXTEND 30 BAR DIAMETERS INTO THE CONCRETE OR WITH A STANDARD ACI 90 DEGREE BEND. LAP OR SPLICES OF REINFORCING STEEL IN MASONRY SHALL AS SHOWN IN THE CMU REINFORCING LAP SCHEDULE. THERE SHALL BE A SLAB DOWEL FOR EACH VERTICAL WALL REINFORCING BAR. AT CONTRACTOR'S OPTION DOWELS MAY BE DRILLED AND GROUTED WITH EPOXY MATERIAL TO DEVELOP THE TENSILE CAPACITY OF BAR. EPOXY MANUFACTURER INFORMATION SHALL BE SUBMITTED FOR REVIEW AND APPROVAL BY THE ARCHITECT-ENGINEER. H. MINIMUM HORIZONTAL AND VERTICAL REINFORCING IN CMU WALLS SHALL BE PROVIDED AS FOLLOWS: 1) VERTICAL: A) INTERIOR WALLS: 8" CMU #5 AT 32" O.C. CENTERED IN CELL B) ELEVATOR WALLS: 12" CMU #5 AT 16" O.C. CENTERED IN CELL 2) HORIZONTAL: BOND BEAMS SHALL BE PLACED AT 48" ON CENTER MAX (EVERY 6TH COURSE) OR AS REQUIRED FOR DETAILING AT LINTELS, WALL OPENINGS, ETC. BOND BEAMS SHALL BE REINFORCED WITH (2) #3 BARS. I. NORMAL VERTICAL WALL REINFORCING SHALL EXTEND CONTINUOUSLY FROM THE TOP OF FOUNDATION TO EMBED AT LEAST 6" INTO THE FLOOR OR ROOF DIAPHRAGM BOND BEAM. THE DIAPHRAGM BOND BEAM SHALL BE DEFINED AS THE BOND BEAM AT THE FLOOR OR ROOF LEVEL OR WHERE KICKER ANGLES OR CLIP ANGLES ARE PROVIDED TO PROVIDE LATERAL SUPPORT. J. AN ADDITIONAL VERTICAL BAR OF THE SAME SIZE AND LENGTH AS THE NORMAL REINFORCING BAR SHALL BE PLACED: 1) AT JAMBS OF WALL OPENINGS. 2) ON EACH SIDE OF CONTROL JOINTS OR EXPANSION JOINTS. 3) AT INTERSECTION OF EXTERIOR WALLS. 4) AT INTERSECTION OF INTERIOR WALLS WITH EXTERIOR WALLS. 5) AT INTERSECTION OF INTERIOR WALLS. K. BOND BEAM REINFORCING STEEL FOR INTERIOR AND EXTERIOR WALLS SHALL BE CONTINUOUS THROUGHOUT, EXCEPT AT CONTROL JOINTS. AT CONTROL JOINTS, INTERMEDIATE BOND BEAM REINFORCEMENT SHALL BE CUT, BUT SHALL BE CONTINUOUS AT DIAPHRAGM BOND BEAMS. REFER TO TYPICAL DETAILS AND LAP SCHEDULE FOR ADDITIONAL INFORMATION. L. LOCATION AND DETAILS OF CONTROL JOINTS SHALL BE AS DEFINED ON ARCHITECTURAL DRAWINGS. M. EXTEND REINFORCING BARS NOT LESS THAN THAT SPECIFIED ON LAP SCHEDULE. N. OPENINGS FOR ALL DUCTS AND PIPES PENETRATING MASONRY WALLS SHALL BE VERIFIED AND COORDINATED WITH MECHANICAL AND ELECTRICAL CONTRACTORS REQUIREMENTS. PENETRATIONS THROUGH WALLS SHALL HAVE ADDITIONAL REINFORCING AS SHOWN ON IN THE TYPICAL DETAILS. O. LINTELS SHALL BE PROVIDED WHERE REQUIRED ACCORDING TO TYPICAL LINTEL DETAILS AND SCHEDULE OR AS INDICATED ON PLAN SHEETS. P. UNLESS BRACED BY ATTACHMENT TO A STRUCTURAL SLAB OR METAL DECK, THE TOP OF MASONRY WALLS SHALL BE BRACED IN ACCORDANCE WITH THE TYPICAL DETAILS SHOWN IN THE DRAWINGS. 8. STEEL CONSTRUCTION NOTES A. ALL STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED, AND ERECTED IN ACCORDANCE WITH THE CURRENT EDITIONS OF THE AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES" AND THE AISC "LOAD AND RESISTANCE FACTOR DESIGN SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS", AND AS SUPPLEMENTED BY THESE GENERAL NOTES IN ADDITION TO THE PROJECT SPECIFICATIONS. B. THE CONTRACTOR SHALL DESIGN ALL CONNECTIONS AND SPLICE CONNECTIONS SHOWN, NOT SHOWN, OR ONLY PARTIALLY DETAILED ON THE DRAWINGS. THE CONTRACTOR SHALL RETAIN A REGISTERED, PROFESSIONAL ENGINEER WHO SHALL DESIGN ALL SPLICES AND CONNECTIONS SHOWN, NOT SHOWN, OR ONLY PARTIALLY DETAILED ON THE DRAWINGS. C. CONNECTIONS SHALL BE DESIGNED TO SUPPORT THE FACTORED END REACTIONS SHOWN ON THE DRAWINGS. WHERE END REACTIONS ARE NOT SHOWN OR OTHERWISE SPECIFIED, CONNECTIONS SHALL BE DESIGNED TO SUPPORT 50% OF THE TOTAL UNIFORM LOAD CAPACITY SHOWN IN THE MANUAL OF STEEL CONSTRUCTION FOR THE GIVEN SHAPE, SPAN AND THE SPECIFIED STEEL. D. ALL CONNECTION PLATES, STIFFENERS AND BOLTS SHOWN ON THE DRAWINGS ARE SCHEMATIC ONLY. CONTRACTOR SHALL DESIGN ALL CONNECTIONS, SPLICES, PLATES, GUSSET PLATES, STIFFENERS, BOLTS AND WELDS FOR FORCES INDICATED ON DRAWINGS IN ADDITION TO THE REQUIREMENTS OF THE AISC DESIGN SPECIFICATION. E. ALL STEEL CONNECTIONS, GUSSET AND WING PLATES SHALL BE DESIGNED AND PROVIDED TO DEVELOP FORCES INDICATED ON DRAWINGS. IN ALL CASES, A MINIMUM 3/8" PLATE AND A MINIMUM OF (2) 3/4" DIAMETER A325 BOLTS SHALL BE PROVIDED. PROVIDE STIFFENER PLATES FOR ALL WELDED CONNECTIONS OR WING PLATES CONNECTED TO WEB WHERE THE FORCE IS TRANSVERSE TO THE WEB OF THE MEMBER WITH THE WING PLATES. F. CONNECTIONS FOR FRAMING MEMBERS WITH BOTH GRAVITY LOADS (REACTIONS) AND AXIAL LOADS OR TRANSFER FORCES (TENSION OR COMPRESSION) SHALL BE DESIGNED FOR THE COMBINED EFFECT OF BOTH LOADS. G. CONNECTION DESIGN DRAWINGS AND CALCULATIONS MUST BE SUBMITTED FOR APPROVAL TO THE ARCHITECT AND SUBSEQUENTLY REVIEWED, APPROVED AND RETURNED BY THE ARCHITECT PRIOR TO THE SUBMITTAL OF SHOP DRAWINGS THAT INCORPORATE THESE DESIGNS. CONNECTION DESIGN SUBMITTAL REVIEW COMMENTS MADE BY THE ARCHITECT SHALL BE INCORPORATED INTO THE RELATED SHOP DRAWINGS PRIOR TO THEIR SUBMITTAL. SUBMITTALS IN NONCOMPLIANCE WILL BE RETURNED UNREVIEWED BY THE ARCHITECT. H. STEEL CONTRACTOR SHALL FURNISH ERECTION BOLTS AS REQUIRED FOR FIELD CONNECTIONS. I. ALL BEAMS THAT ARE REQUIRED TO HAVE CAMBER SHALL BE FABRICATED WITH CAMBER UPWARD. BEAMS WITHOUT SPECIFIED CAMBER SHALL BE FABRICATED SUCH THAT AFTER ERECTION, ANY NATURAL CAMBER DUE TO ROLLING OR SHOP FABRICATION IS UPWARD. J. UNLESS OTHERWISE INDICATED IN THE DRAWINGS, ALL ANCHOR RODS SHALL CONFORM TO ASTM F1554 GRADE 55-WELDABLE AND SHALL BE ¾" DIAMETER WITH A MINIMUM FOUNDATION EMBEDMENT OF 12". THE EMBEDDED END SHALL HAVE A HEAVY HEX NUT WITH THE THREADS SPOILED ABOVE AND BELOW THE NUT. K. PROVIDE TEMPORARY SHORES, GUYS, BRACES, AND OTHER SUPPORTS DURING ERECTION TO KEEP STRUCTURAL STEEL SECURE, PLUMB, AND IN ALIGNMENT AGAINST TEMPORARY CONSTRUCTION LOADS AND LOADS EQUAL IN INTENSITY TO DESIGN LOADS. THE TEMPORARY SUPPORTS SHALL BE SUFFICIENT TO SECURE THE BARE STRUCTURAL STEEL FRAMING OR ANY PORTION THEREOF AGAINST LOADS THAT ARE LIKELY TO BE ENCOUNTERED DURING ERECTION, INCLUDING THOSE DUE TO WIND AND THOSE THAT RESULT FROM ERECTION OPERATIONS. L. DO NOT REMOVE TEMPORARY SUPPORTS UNTIL THE INSTALLATION OF ALL STRUCTURAL ELEMENTS IS COMPLETE AND HAS BEEN ACCEPTED AS COMPLETE BY THE STRUCTURAL ENGINEER. FOR THE PURPOSES OF THIS PARAGRAPH, "ALL STRUCTURAL ELEMENTS" INCLUDES ANY OF THE FOLLOWING THAT ARE SHOWN IN THE STRUCTURAL DRAWINGS: FOUNDATIONS, TILT-UP CONCRETE PANELS AND THEIR CONNECTIONS TO FOUNDATIONS AND SLABS, LOAD-BEARING CMU WALLS, CMU SHEAR WALLS, STRUCTURAL STEEL, STEEL CONNECTIONS, PERMANENT BRACING, WELDED MOMENT CONNECTIONS, STEEL JOISTS, JOIST BRIDGING, ROOF DECK AND FLOOR DECK. M. ALL SHOP AND FIELD WELDS SHALL BE MADE IN ACCORDANCE WITH THE ANSI/AWS "D1.1-STRUCTURAL WELDING CODE - STEEL", LATEST EDITION. ALL WELDING SHALL USE LOW HYDROGEN PROCESSES. N. ALL BOLTS SHALL BE ASTM A325 WITH SUITABLE WASHERS AND NUTS. O. ALL ANGLE FRAMES, PLATES AND OTHER EMBEDDED ITEMS CAST INTO CONCRETE SHALL BE GALVANIZED. P. SUBSTITUTION OF EXPANSION ANCHORS FOR EMBEDDED ANCHORS SHOWN ON THE DRAWINGS WILL NOT BE PERMITTED. Q. CUTS, HOLES, COPING, ETC. REQUIRED FOR WORK OF OTHER TRADES SHALL BE SHOWN ON THE SHOP DRAWINGS AND MADE IN THE SHOP. CUTS OR BURNING OF HOLES IN STRUCTURAL STEEL MEMBERS IN THE FIELD WILL NOT BE PERMITTED. R. ALL EXTENSION BARS, RUN-OFF PLATES, AND BACKING BARS USED IN WELDED CONNECTIONS SHALL BE REMOVED AND THE JOINTS SHALL BE GROUND SMOOTH WHERE SUCH CONNECTION IS PERMANENTLY EXPOSED TO VIEW OR IS DESIGNATED AS ARCHITECTURALLY EXPOSED STEEL. S. ALL ROOF OPENINGS GREATER THAN 6" SHALL BE SUPPORTED BY AN ANGLE FRAME. IF SIZES ARE NOT PROVIDED, REFER TYPICAL DETAILS FOR ROOF OPENING FRAME DETAIL. T. ALL ELEVATED MECHANICAL EQUIPMENT SHALL BE SUPPORTED BY STEEL. IF SIZES ARE NOT PROVIDED, REFER TYPICAL DETAILS FOR ROOF OPENING FRAME DETAIL. U. GALVANIZED LOOSE LEDGE ANGLES SHALL BE PROVIDED OVER ALL MASONRY VENEER OPENINGS OR RECESSES DEEPER THAT 4". LINTELS SHALL HAVE 1" OF BEARING AT EACH END FOR EVERY FOOT OF SPAN, WITH A MINIMUM OF 4" AND SIZED AS FOLLOWS UNLESS SHOWN OTHERWISE IN THE DRAWINGS. 1) UP TO 4'-0".........................L3-1/2 x 3-1/2 x 3/8 2) 4'-1" to 5'-0"......................L4 x 3-1/2 x 3/8 (LLV) 3) 5'-1" to 6'-6"......................L5 x 3-1/2 x 3/8 (LLV) 4) 6'-7" to 8'-0"......................L6 x 3-1/2 x 3/8 (LLV) V. ALL VISIBLE STEEL EXPOSED TO EXTERIOR WEATHER OR AN UNCONTROLLED ENVIRONMENT SHALL BE BLAST CLEANED, PRIMED WITH A ZINC-RICH PRIMER AND FIELD PAINTED WITH A HIGH PERFORMANCE PAINT. NON-VISIBLE STEEL EXPOSED TO EXTERIOR WEATHER OR AN UNCONTROLLED ENVIRONMENT SHALL BE BLAST CLEANED AND RECEIVE A ZINC-RICH PRIMER. INTERIOR STEEL SHALL BE SHOP PRIMED AND FIELD PAINTED. W. ALL HEADED STUDS AND DEFORMED BAR ANCHORS SHALL BE INSTALLED USING AUTOMATIC END-WELDING EQUIPMENT RECOMMENDED BY THE STUD OR ANCHOR MANUFACTURER. MANUAL WELDING OF HEADED STUDS OR DEFORMED BAR ANCHORS WILL NOT BE ALLOWED. 525 Central Park Drive, Suite 202 Oklahoma City, OK 73105 Telephone: 405.528.4596 Fax: 405.528.4580 Kirkpatrick Forest Curtis PC Structural Engineering engineering OK CA #3888, EXP. 06/30/19

Transcript of 1PARTIAL FOUNDATION PLAN REV 5 CLIMAT… · 1.general information a.governing building code: 2009...

Page 1: 1PARTIAL FOUNDATION PLAN REV 5 CLIMAT… · 1.general information a.governing building code: 2009 international building code (ibc-2009). b.building classification: the building classification

1. GENERAL INFORMATION

A. GOVERNING BUILDING CODE: 2009 INTERNATIONAL BUILDING CODE (IBC-2009).

B. BUILDING CLASSIFICATION: THE BUILDING CLASSIFICATION ACCORDING TO IBC-2009TABLE 1604.5 AND ASCE 7-05 TABLE 1-1 IS CATEGORY II.

C. CONTRACT DOCUMENTS: THE CONTRACT DOCUMENTS CONSIST OF THE AGREEMENT BETWEENTHE OWNER AND CONTRACTOR, CONDITIONS OF THE CONTRACT, DRAWINGS,SPECIFICATIONS, ADDENDA ISSUED PRIOR TO EXECUTION OF THE CONTRACT, OTHERDOCUMENTS LISTED IN THE AGREEMENT AND MODIFICATIONS ISSUED AFTER EXECUTION OFTHE CONTRACT.

D. CORRELATION OF THE CONTRACT DOCUMENTS: THE CONTRACT DOCUMENTS ARECOMPLIMENTARY, AND WHAT IS REQUIRED BY ONE SHALL BE AS BINDING AS IF REQUIREDBY ALL. IF CONFLICTING REQUIREMENTS ARE FOUND BETWEEN THE DRAWINGS,SPECIFICATIONS AND/OR THESE GENERAL NOTES, THE MORE STRINGENT PROVISION SHALLCONTROL UNLESS DIRECTED OTHERWISE IN WRITING BY THE STRUCTURAL ENGINEER.

E. ELEVATIONS: REFERENCE ELEVATION OF 100'-0" EQUALS FINISHED FLOOR ELEVATION FORTHE NEW BUILDING.

2. DESIGN LOADS

A. DEAD LOAD: SELF WEIGHT OF MATERIALS, UNLESS NOTED OTHERWISE

B. ROOF DEAD LOAD:1) BUILT UP ROOF................................................6 PSF2) INSULATION...................................................2 PSF3) DECK.........................................................2 PSF4) BEAMS, JOISTS & BRIDGING.....................................3 PSF5) CEILING......................................................1 PSF6) MISC (LIGHTING, DUCTWORK, PIPING, ETC.)......................2 PSF7) TOTAL.......................................................16 PSF

C. FLOOR DEAD LOAD:1) 3½" CONC. OVER 0.6 NON-COMPOSITE METAL DECKING..............41 PSF2) BEAMS, JOISTS, AND BRIDGING..................................5 PSF3) CEILING......................................................1 PSF4) MISC (LIGHTING, DUCTWORK, PIPING, ETC.) .....................3 PSF5) TOTAL.......................................................50 PSF

D. LIVE LOADS:1) ROOF LIVE LOAD .............................................20 PSF2) FLOOR LIVE LOAD

A) LOBBIES.................................................100 PSFB) CORRIDORS................................................80 PSFC) OFFICES W/ PARTITION LOAD................................65 PSF

E. WIND LOADS:1) GOVERNING CODE:..........................................ASCE 7-052) IMPORTANCE FACTOR, Iw:........................................1.003) EXPOSURE CATEGORY:...............................................C4) WIND VELOCITY, V:...........................................90 MPH

F. SNOW LOADS:1) GOVERNING CODE:..........................................ASCE 7-052) IMPORTANCE FACTOR, Is:........................................1.003) GROUND SNOW LOAD, Pg:.......................................10 PSF4) EXPOSURE FACTOR, Ce:...........................................1.05) ROOF SLOPE FACTOR, Cs:.........................................1.06) CALCULATED FLAT ROOF SNOW LOAD, Pf:..........................7 PSF7) MINIMUM FLAT ROOF SNOW LOAD, I*Pf:..........................10 PSF8) RAIN ON SNOW SURCHARGE LOAD:.................................5 PSF9) DRIFT LOADS:.............................................ASCE 7-05

G. SEISMIC DESIGN CRITERIA:1) GOVERNING CODE:..........................................ASCE 7-052) IMPORTANCE FACTOR, Ie:........................................1.003) SOIL SITE CLASSIFICATION (ASSUMPTION MADE FROM ADJACENT PROPERTY

VALUES):.........................................................D4) 0.2 SEC. MAPPED SPECTRAL ACCELERATION, Ss:...................0.2795) 1.0 SEC. MAPPED SPECTRAL ACCELERATION, S1:...................0.0796) SITE COEFFICIENT, 0.2 SEC. PERIOD, Fa:........................1.587) SITE COEFFICIENT, 1.0 SEC. PERIOD, Fv:.........................2.48) 0.2 SEC. DESIGN SPECTRAL ACCELERATION, Sds:..................0.2399) 1.0 SEC. DESIGN SPECTRAL ACCELERATION, Sd1:..................0.12610)SEISMIC DESIGN CATEGORY:.........................................B11)SEISMIC USE GROUP:..............................................II12)SEISMIC PARAMETERS FOR ELEVATOR SHAFT:

A) SEISMIC FORCE RESISTING SYSTEM: ORDINARY REINFORCED MASONRY SHEAR WALLSB) RESPONSE MODIFICATION COEFFICIENT, R:.....................2.00C) SYSTEM OVERSTRENGTH FACTOR, O:............................2.50D) DEFLECTION AMPLIFICATION FACTOR, Cd:......................1.75E) ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE METHOD.F) SEISMIC RESPONSE COEFFICIENT, Cs:........................0.147G) TOTAL LATERAL BASE SHEAR, V:............................1 KIPS

3. MATERIAL DESIGN VALUES

A. CONCRETE (MINIMUM ULTIMATE COMPRESSIVE STRENGTH AT 28 DAYS, NORMAL WEIGHTU.N.O.):1) FOUNDATIONS:.............................................4,000 PSI2) CONCRETE SLAB-ON-GRADE:..................................4,000 PSI3) ALL OTHER STRUCTURAL CONCRETE, U.N.O:....................4,000 PSI

B. REINFORCED CONCRETE MASONRY (MINIMUM ULTIMATE COMPRESSIVE STRENGTH AT 28 DAYS):1) PRISMS (ASTM C1314), f'm:................................1,500 PSI2) MORTAR (ASTM C270).......................................1,800 PSI3) CONCRETE MASONRY UNITS (ASTM C90)........................1,900 PSI4) GROUT....................................................3,000 PSI

C. CONCRETE AND MASONRY REINFORCEMENT (MINIMUM YIELD STRENGTH)1) ALL PLAIN AND DEFORMED BARS (ASTM A615, GRADE 60)......FY = 60 KSI2) WELDED WIRE FABRIC (ASTM A184) ........................FY = 60 KSI3) WELDABLE REINFORCING BARS (ASTM A706) .................FY = 60 KSI

D. STRUCTURAL STEEL (MINIMUM YIELD STRENGTH)1) ALL WIDE FLANGE SHAPES (ASTM A992)....................FY = 50 KSI2) STRUCTURAL TUBES (ASTM A500, GRADE B)..................FY = 46 KSI3) PIPES (ASTM A53, GRADE B)..............................FY = 35 KSI4) ANCHOR RODS (ASTM F1554, GRADE 55, WELDABLE) ..........FY = 55 KSI5) DEFORMED BAR ANCHORS (ASTM A496).......................FY = 70 KSI6) ALL OTHER SHAPES AND PLATES UNLESS NOTED (ASTM A36)....FY = 36 KSI

E. COLD FORMED STEEL (MINIMUM YIELD STRENGTH)1) ROOF DECK (ASTM A653, SS GRADE 33, G-60 GALVANIZED)....FY = 33 KSI2) COMPOSITE FLOOR DECK (ASTM A653, SS GRADE 40, G-60

GALVANIZED)............................................FY = 40 KSI3) COLD FORMED METAL STUDS (ASTM A1003/A, GRADE ST33H, G-60

GALVANIZED)............................................FY = 33 KSI4) COLD FORMED METAL CLIPS (ASTM A653, SS GRADE 50,G-90

GALVANIZED)............................................FY = 50 KSI

4. DEMOLITION NOTES

A. ALL DIMENSIONS FOR THE EXISTING STRUCTURE SHALL BE VERIFIED IN THE FIELD PRIORTO PROCEEDING WITH ANY DEMOLITION OR NEW WORK.

B. AS DEMOLITION OR NEW WORK PROGRESSES THE CONTRACTOR SHALL MAKE WRITTENDOCUMENTATION IF INCONSISTENCIES OCCUR IN THE EXISTING STRUCTURE. THESEINCONSISTENCIES SHALL BE SUBMITTED TO THE OWNER'S REPRESENTATIVE FOR REVIEW.

C. THE CONTRACTOR SHALL PROVIDE AND INSTALL ALL SHORING, PROPS, AND GUYS REQUIREDFOR THE TEMPORARY SUPPORT OF EXISTING PIPING, STRUCTURE, ETC. AS MAY BENECESSARY TO COMPLETE THE REQUIRED DEMOLITION OR NEW WORK.

D. THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING EXISTING UTILITIES, BOTHCHARTED AND UNCHARTED BEFORE COMMENCING WITH ANY EXCAVATION OR DEMOLITION WORK.DEPTH OF CONCRETE SAW SHALL BE SET SO AS NOT TO CUT ANY LOCAL UNDER FLOORPIPING OR WIRING WHICH IS TO REMAIN.

E. THE PROJECT AREA SHALL BE MAINTAINED AS CLEAN AS POSSIBLE WITH DUST BEINGLIMITED AS MUCH AS PRACTICAL. DEMOLITION SHALL PROCEED AS DIRECTED BY THEOWNER'S REPRESENTATIVE.

F. WHEN SAW CUTTING, SPECIAL CARE SHALL BE TAKEN TO NOT OVER CUT INTO AN EXISTINGAREA OF STRUCTURE THAT WILL REMAIN.

5. FOUNDATION NOTES

A. GEOTECHNICAL REPORT: A GEOTECHNICAL ENGINEERING SERVICES REPORT WAS NOTPROVIDED, THUS MINIMUM DESIGN VALUES WERE USED PER IBC 2009.

B. BUILDING FOUNDATIONS

1) SHALLOW FOOTINGS: THE PROPOSED BUILDINGS SHALL BE SUPPORTED ON CONVENTIONALSHALLOW SPREAD FOOTINGS FOUNDED ON EXISTING NON-EXPANSIVE SOIL OR PROPERLYCOMPACTED ENGINEERED FILL.

2) FOOTING DESIGN PARAMETERS: SHALLOW SPREAD FOOTINGS FOR BUILDING COLUMNS ANDCONTINUOUS FOOTINGS FOR BEARING WALLS HAVE BEEN DESIGNED FOR A TOTALALLOWABLE SOIL BEARING PRESSURE OF 1,500 POUNDS PER SQUARE FOOT, BEARING ONEXISTING SOIL OR PROPERLY COMPACTED ENGINEERED FILL.

3) PIPE PENETRATIONS: ALL HORIZONTAL PIPE OR SIMILAR PENETRATIONS OR SLEEVESTHROUGH FOOTINGS SHALL PREFERABLY OCCUR WITHIN THE MIDDLE 1/3 OF THE FOOTINGDEPTH. AT PENETRATIONS, PROVIDE (4) #5 DIAGONAL BARS AT EACH FOOTING FACE(3" CLEAR BETWEEN BAR AND PENETRATION AND 3" CLEAR FROM FOOTING BEARING).IF PENETRATION MUST OCCUR NEAR THE BOTTOM OF FOOTING, REFER TYPICAL DETAILSFOR STANDARD DETAIL TO TRANSITION & THICKEN FOOTING TO ACCOMMODATEPENETRATION.

C. SLAB-ON-GRADE CONSTRUCTION

1) SLAB THICKNESS AND REINFORCING: SLABS-ON-GRADE SHALL BE 6" THICK CONCRETEREINFORCED WITH #4 BARS AT 18" ON CENTER EACH WAY. REINFORCING BARS SHALLBE PLACED 1½" CLEAR FROM TOP OF SLAB USING CHAIRS OR SLAB BOLSTERS COMPLYINGWITH CRSI'S "MANUAL OF STANDARD PRACTICE".

2) SLAB SUBGRADE: THE FLOOR SLAB SHALL BE GRADE SUPPORTED ON EXISTINGNON-EXPANSIVE SOILS.

3) AGGREGATE BASE COURSE: A 6-INCH THICK, FREE-DRAINING SAND BASE COURSE SHALLBE PLACED BENEATH THE FLOOR SLAB TO ENHANCE DRAINAGE AND PROVIDE INCREASEDSUBGRADE STRENGTH. AT THE TIME OF THE SLAB PLACEMENT, THE GRANULAR BASESHALL BE MOIST, BUT FREE OF ANY STANDING OR SELF-DRAINING WATER.

4) VAPOR RETARDER: A VAPOR RETARDER SHALL BE PLACED IMMEDIATELY BELOW THECONCRETE SLAB. VAPOR RETARDER SHALL BE SEALED TO PREVIOUSLY PLACED CONCRETEAS RECOMMENDED BY VAPOR RETARDER MANUFACTURER. BEFORE PLACING CONCRETE,PATCH AND SEAL ANY RIPS, TEARS OR HOLES IN VAPOR RETARDER INCURRED DURINGCONSTRUCTION.

5) SLAB MIX DESIGN: SLAB-ON-GRADE CONCRETE MIX SHALL BE DESIGNED FOR A 28-DAYCOMPRESSIVE STRENGTH OF 4,000 PSI, A WATER-CEMENT RATIO OF 0.40 AND AMAXIMUM SLUMP OF 4-INCHES.

6) MOIST CURING OF SLAB: SLABS-ON-GRADE SHALL BE WATER CURED FOR A MINIMUM OF7 DAYS BY PONDING, SPRAYING, SPRINKLING OR BY USE OF SATURATED COVERINGS.

7) ISOLATION JOINTS: PROVIDE SLAB ISOLATION AROUND COLUMNS PENETRATING THESLAB-ON-GRADE. PROVIDE 30# FELT AROUND PERIMETER OF ISOLATION JOINTS.REFER TO TYPICAL DETAILS AND ADDITIONAL INFORMATION.

8) SLAB JOINTS: SLAB JOINTS SHALL BE PROVIDED AS SHOWN IN THE TYPICAL DETAILS.THE FOLLOWING JOINT TYPES ARE SHOWN ON THE DRAWINGS:A) CJ = CONSTRUCTION JOINTB) SJ = SAWED CONTRACTION JOINTC) EJ = EXPANSION JOINT

D. MISCELLANEOUS

1) DRAINAGE CONSIDERATIONS: DUE TO ADVERSE EFFECT ON STRUCTURES, WATER SHALLNOT BE ALLOWED TO COLLECT IN THE FOUNDATION EXCAVATION OR ON PREPAREDSUBGRADE OF THE CONSTRUCTION AREA EITHER DURING OR AFTER CONSTRUCTION.UNDERCUT OR EXCAVATED AREAS SHALL BE SLOPED TOWARD ONE CORNER TO FACILITATEREMOVAL OF ANY COLLECTED RAINWATER, OR POSITIVE RUNOFF SHALL BE PROVIDED.THE CONTRACTOR SHALL EXERCISE CARE IN CREATING DRAINAGE PATHS FOR WATERDURING THE CONSTRUCTION PHASE OF THE PROJECT. TO REDUCE INFILTRATION OFSURFACE WATER AROUND THE PERIMETER OF THE BUILDING AND BENEATH THE FLOORSLABS, POSITIVE DRAINAGE SHALL BE PROVIDED DURING ALL PHASES OFCONSTRUCTION.

2) EXCAVATION AND TEMPORARY SLOPES: THE CONTRACTOR, DESIGNATED AS "RESPONSIBLEPERSON" IN OSHA CONSTRUCTION STANDARDS FOR EXCAVATIONS, 29 CFR PART 1926, ISSOLELY RESPONSIBLE FOR PLANNING AND IMPLEMENTING ALL SAFETY PROCEDURES. ALLEXCAVATION HEIGHT, SLOPE, AND DEPTH MUST ADHERE TO ALL SPECIFICATIONSOUTLINED IN LOCAL, STATE, AND FEDERAL SAFETY REGULATIONS. KFC ENGINEERINGDOES NOT ASSUME ANY RESPONSIBILITY FOR CONSTRUCTION SITE SAFETY OR ANYPARTY'S, INCLUDING THE CONTRACTOR'S, COMPLIANCE WITH THE APPLICABLE LOCAL,STATE, AND FEDERAL SAFETY REGULATIONS OR ANY OTHER APPLICABLE REGULATIONS.

3) TRENCH BACKFILL: ALL REQUIRED TRENCH BACKFILL SHALL BE MECHANICALLYCOMPACTED IN LAYERS TO AT LEAST 95% OF THE STANDARD PROCTOR MAXIMUM DRYDENSITY AS DETERMINED BY ASTM D 698. SOME SETTLEMENT OF THE BACKFILL MAY BEEXPECTED AND ANY UTILITIES WITHIN THE TRENCHES SHALL BE CONSTRUCTED TO ALLOWTHESE DIFFERENTIAL MOVEMENTS. REFER TO PROJECT SPECIFICATIONS FORADDITIONAL REQUIREMENTS.

4) CONSTRUCTION MONITORING: MIDWEST ENGINEERING AND TESTING CORPORATION (METCO)SHALL BE RETAINED AS THE GEOTECHNICAL ENGINEER TO PROVIDE OBSERVATIONS ANDTESTING OF SOILS EXPOSED DURING PROJECT CONSTRUCTION IN ORDER TO VERIFY THATSOIL CONDITIONS ARE AS ANTICIPATED. CONSTRUCTION ACTIVITIES PERTAINING TOEARTHWORK, SLAB PLACEMENT, CONCRETE TESTING, AND OTHER RELATED ACTIVITIESSHALL ALSO BE OBSERVED BY PSI REPRESENTATIVES AS OUTLINED ABOVE.

6. CONCRETE CONSTRUCTION NOTES

A. ALL DETAILING, FABRICATION, AND PLACING OF REINFORCING STEEL, UNLESS OTHERWISENOTED, SHALL FOLLOW ALL SECTIONS OF THE ACI "DETAILING MANUAL-2004" (SP-66 04)AND THE ACI "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318-02).

B. MIX DESIGNS SHALL BE PROPORTIONED IN ACCORDANCE WITH ACI 318, SECTION 5.3,"PROPORTIONING ON BASIS OF FIELD EXPERIENCE AND/OR TRIAL MIXTURES" AND MEET THEREQUIREMENTS OF THE SPECIFICATIONS AND ACI 211 AND 301. IF TRIAL BATCHES AREUSED, MIX DESIGN SHALL BE PREPARED BY AN INDEPENDENT TESTING LABORATORY ANDACHIEVE A COMPRESSIVE STRENGTH 1200 PSI HIGHER THAN SPECIFIED STRENGTH.

C. UNLESS OTHERWISE NOTED, LAP SPLICES SHALL CONFORM TO ACI REQUIREMENTS FOR CLASSB TENSION SPLICES. REFER TO LAP LENGTH SCHEDULES FOR TYPICAL LAP REQUIREMENTS.

D. PROVIDE CORNER BARS IN BOTH FACES OF ALL CONTINUOUS GRADE BEAMS, FOOTINGS ANDWALLS. NUMBER, SIZE, AND SPACING OF CORNER BARS SHALL BE EQUAL TO NUMBER, SIZEAND SPACING OF HORIZONTAL REINFORCING WITH WHICH THEY LAP AND SHALL HAVE CLASSB TENSION LAP SPLICES IN EACH DIRECTION. REFER TO TYPICAL DETAILS FORADDITIONAL INFORMATION.

E. UNLESS OTHERWISE NOTED, CONCRETE COVER OVER STEEL REINFORCING SHALL CONFORM TOMINIMUM REQUIRED BY ACI 318-08.

F. AT INTERSECTING FOUNDATIONS, EXTEND ALL HORIZONTAL REINFORCING OF THEINTERSECTING MEMBERS BEYOND THE POINT OF INTERSECTION TO THE OPPOSITE FACE.BEND TO A STANDARD 90 DEGREE HOOK OR PROVIDE BENT DOWELS OF EQUAL SIZE ANDSPACING AND LAP AS REQUIRED BY NOTE C (BUT NOT LESS THAN 12") IN EACHDIRECTION. REFER TO TYPICAL DETAILS FOR ADDITIONAL INFORMATION.

G. PROVIDE CONCRETE EQUIPMENT PADS OF SIZE REQUIRED FOR EQUIPMENT FURNISHED. SEEMECHANICAL, PLUMBING, FIRE PROTECTION AND ELECTRICAL DRAWINGS FOR NUMBER, SIZE,AND LOCATION OF SUCH PADS. UNLESS OTHERWISE SHOWN, MINIMUM PAD THICKNESS SHALLBE 4" AND SHALL EXTEND A MINIMUM OF 6" BEYOND THE FACE OF THE EQUIPMENT.MINIMUM REINFORCING SHALL BE #4 BARS AT 12" O.C. EACH WAY. TOOLED OR CHAMFEREDEDGES SHALL BE PROVIDED AT ALL EQUIPMENT PADS. ANCHORAGE TO SLAB SHALL BEMADE.

H. THE SIZE AND LOCATION OF ALL FLOOR PITS, TRENCH DRAINS, AND OPENINGS FOR ALLDUCTS AND PIPES THROUGH WALLS, FLOORS, AND FOUNDATION WORK SHALL BE VERIFIEDWITH THE MECHANICAL, PLUMBING, FIRE PROTECTION AND ELECTRICAL CONTRACTOR'SREQUIREMENTS PRIOR TO THE START OF ANY CONCRETE WORK.

I. ALL CONSTRUCTION JOINTS (VERTICAL AND HORIZONTAL) IN PITS AND TRENCHES SHALL BEKEYED AND HAVE BENTONITE WATERSTOPS INSTALLED UNLESS NOTED OTHERWISE. ALL PITSAND TRENCHES SHALL BE WATERPROOFED, UNLESS NOTED OTHERWISE.

J. UNLESS NOTED OTHERWISE ON ARCHITECTURAL DRAWINGS, PROVIDE 3/4" CHAMFER ON ALLEXPOSED CONCRETE EDGES.

K. A SINGLE CONCRETE POUR SHALL NOT EXCEED 100' FOR CONTINUOUS SHALLOW FOOTINGS.

L. ALL HORIZONTAL CONCRETE SURFACES SHALL HAVE A TROWEL FINISH (VERIFY WITHARCHITECTURAL DRAWINGS).

M. A SINGLE CONCRETE POUR FOR SLABS-ON-GRADE SHALL NOT EXTEND BEYOND THECONSTRUCTION JOINTS (CJ'S) SHOWN ON THE FOUNDATION PLANS. REFER TO PLANS FORSLAB JOINT PLACEMENT.

N. ALL OPENINGS IN CONCRETE WALLS LARGER THAN 1'-0" IN SIZE SHALL HAVE A MINIMUMOF (2)#5 BARS PLACED AT ALL SIDES OF OPENING AND EXTENDED 2'-6" BEYOND EDGE OFOPENING. IN ADDITION, DIAGONAL CORNER BARS SHALL EXTEND 2'-6" EACH WAY BEYONDCORNER OF OPENING. REFER TYPICAL FOUNDATION DETAILS FOR MORE INFORMATION.

O. FOR PLACEMENT OF CONCRETE SLABS ON UNSHORED METAL DECK, ANTICIPATE A 10%CONCRETE VOLUME INCREASE TO COMPENSATE FOR DEFLECTION OF THE METAL DECK UNDERTHE WEIGHT OF WET CONCRETE.

P. TO COMPENSATE FOR DEFLECTION OF METAL DECKS UNDER THE WEIGHT OF WET CONCRETE,SLABS ON METAL DECK SHALL BE LASER SCREEDED TO PROVIDE ELEVATION CONTROL DURINGCONCRETE PLACEMENT OPERATIONS.

7. REINFORCED HOLLOW CMU NOTES

A. REFER TO ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS RELEVANT TO ALL CMUCONSTRUCTION.

B. ALL CMU SHALL BE 1 OR 2-CELL LIGHTWEIGHT CONCRETE BLOCK.

C. UNLESS NOTED OTHERWISE, ALL CONCRETE MASONRY UNITS SHALL HAVE A MINIMUM 28-DAYCOMPRESSIVE STRENGTH OF 1900 PSI ON THE NET AREA (INDIVIDUAL STRENGTH PER ASTMC 90).

D. CMU SHALL BE CONSTRUCTED WITH PORTLAND CEMENT/LIME, TYPE S MORTAR CONFORMING TOASTM A C270 WITH AN MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 1800 PSI.

E. CELLS WHICH CONTAIN REINFORCING STEEL SHALL BE FILLED SOLIDLY WITH 3000 PSIPEA-GRAVEL CONCRETE OR 3000 PSI GROUT.

F. VERTICAL CELLS TO BE FILLED SHALL HAVE VERTICAL ALIGNMENT SUFFICIENT TOMAINTAIN A CLEAR UNOBSTRUCTED CONTINUOUS VERTICAL CELL NOT LESS THAN 2"x3" INPLAN DIMENSION.

G. SLAB DOWELS SHALL EXTEND 30 BAR DIAMETERS INTO THE CONCRETE OR WITH A STANDARDACI 90 DEGREE BEND. LAP OR SPLICES OF REINFORCING STEEL IN MASONRY SHALL ASSHOWN IN THE CMU REINFORCING LAP SCHEDULE. THERE SHALL BE A SLAB DOWEL FOREACH VERTICAL WALL REINFORCING BAR. AT CONTRACTOR'S OPTION DOWELS MAY BEDRILLED AND GROUTED WITH EPOXY MATERIAL TO DEVELOP THE TENSILE CAPACITY OF BAR.EPOXY MANUFACTURER INFORMATION SHALL BE SUBMITTED FOR REVIEW AND APPROVAL BYTHE ARCHITECT-ENGINEER.

H. MINIMUM HORIZONTAL AND VERTICAL REINFORCING IN CMU WALLS SHALL BE PROVIDED ASFOLLOWS:

1) VERTICAL:A) INTERIOR WALLS: 8" CMU #5 AT 32" O.C. CENTERED IN CELLB) ELEVATOR WALLS: 12" CMU #5 AT 16" O.C. CENTERED IN CELL

2) HORIZONTAL: BOND BEAMS SHALL BE PLACED AT 48" ON CENTER MAX (EVERY 6THCOURSE) OR AS REQUIRED FOR DETAILING AT LINTELS, WALL OPENINGS, ETC. BONDBEAMS SHALL BE REINFORCED WITH (2) #3 BARS.

I. NORMAL VERTICAL WALL REINFORCING SHALL EXTEND CONTINUOUSLY FROM THE TOP OFFOUNDATION TO EMBED AT LEAST 6" INTO THE FLOOR OR ROOF DIAPHRAGM BOND BEAM.THE DIAPHRAGM BOND BEAM SHALL BE DEFINED AS THE BOND BEAM AT THE FLOOR OR ROOFLEVEL OR WHERE KICKER ANGLES OR CLIP ANGLES ARE PROVIDED TO PROVIDE LATERALSUPPORT.

J. AN ADDITIONAL VERTICAL BAR OF THE SAME SIZE AND LENGTH AS THE NORMALREINFORCING BAR SHALL BE PLACED:

1) AT JAMBS OF WALL OPENINGS.2) ON EACH SIDE OF CONTROL JOINTS OR EXPANSION JOINTS.3) AT INTERSECTION OF EXTERIOR WALLS.4) AT INTERSECTION OF INTERIOR WALLS WITH EXTERIOR WALLS.5) AT INTERSECTION OF INTERIOR WALLS.

K. BOND BEAM REINFORCING STEEL FOR INTERIOR AND EXTERIOR WALLS SHALL BE CONTINUOUSTHROUGHOUT, EXCEPT AT CONTROL JOINTS. AT CONTROL JOINTS, INTERMEDIATE BONDBEAM REINFORCEMENT SHALL BE CUT, BUT SHALL BE CONTINUOUS AT DIAPHRAGM BONDBEAMS. REFER TO TYPICAL DETAILS AND LAP SCHEDULE FOR ADDITIONAL INFORMATION.

L. LOCATION AND DETAILS OF CONTROL JOINTS SHALL BE AS DEFINED ON ARCHITECTURALDRAWINGS.

M. EXTEND REINFORCING BARS NOT LESS THAN THAT SPECIFIED ON LAP SCHEDULE.

N. OPENINGS FOR ALL DUCTS AND PIPES PENETRATING MASONRY WALLS SHALL BE VERIFIEDAND COORDINATED WITH MECHANICAL AND ELECTRICAL CONTRACTORS REQUIREMENTS.PENETRATIONS THROUGH WALLS SHALL HAVE ADDITIONAL REINFORCING AS SHOWN ON IN THETYPICAL DETAILS.

O. LINTELS SHALL BE PROVIDED WHERE REQUIRED ACCORDING TO TYPICAL LINTEL DETAILSAND SCHEDULE OR AS INDICATED ON PLAN SHEETS.

P. UNLESS BRACED BY ATTACHMENT TO A STRUCTURAL SLAB OR METAL DECK, THE TOP OFMASONRY WALLS SHALL BE BRACED IN ACCORDANCE WITH THE TYPICAL DETAILS SHOWN INTHE DRAWINGS.

8. STEEL CONSTRUCTION NOTES

A. ALL STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED, AND ERECTED IN ACCORDANCEWITH THE CURRENT EDITIONS OF THE AISC "CODE OF STANDARD PRACTICE FOR STEELBUILDINGS AND BRIDGES" AND THE AISC "LOAD AND RESISTANCE FACTOR DESIGNSPECIFICATION FOR STRUCTURAL STEEL BUILDINGS", AND AS SUPPLEMENTED BY THESEGENERAL NOTES IN ADDITION TO THE PROJECT SPECIFICATIONS.

B. THE CONTRACTOR SHALL DESIGN ALL CONNECTIONS AND SPLICE CONNECTIONS SHOWN, NOTSHOWN, OR ONLY PARTIALLY DETAILED ON THE DRAWINGS. THE CONTRACTOR SHALL RETAINA REGISTERED, PROFESSIONAL ENGINEER WHO SHALL DESIGN ALL SPLICES ANDCONNECTIONS SHOWN, NOT SHOWN, OR ONLY PARTIALLY DETAILED ON THE DRAWINGS.

C. CONNECTIONS SHALL BE DESIGNED TO SUPPORT THE FACTORED END REACTIONS SHOWN ONTHE DRAWINGS. WHERE END REACTIONS ARE NOT SHOWN OR OTHERWISE SPECIFIED,CONNECTIONS SHALL BE DESIGNED TO SUPPORT 50% OF THE TOTAL UNIFORM LOAD CAPACITYSHOWN IN THE MANUAL OF STEEL CONSTRUCTION FOR THE GIVEN SHAPE, SPAN AND THESPECIFIED STEEL.

D. ALL CONNECTION PLATES, STIFFENERS AND BOLTS SHOWN ON THE DRAWINGS ARE SCHEMATICONLY. CONTRACTOR SHALL DESIGN ALL CONNECTIONS, SPLICES, PLATES, GUSSET PLATES,STIFFENERS, BOLTS AND WELDS FOR FORCES INDICATED ON DRAWINGS IN ADDITION TO THEREQUIREMENTS OF THE AISC DESIGN SPECIFICATION.

E. ALL STEEL CONNECTIONS, GUSSET AND WING PLATES SHALL BE DESIGNED AND PROVIDED TODEVELOP FORCES INDICATED ON DRAWINGS. IN ALL CASES, A MINIMUM 3/8" PLATE AND AMINIMUM OF (2) 3/4" DIAMETER A325 BOLTS SHALL BE PROVIDED. PROVIDE STIFFENERPLATES FOR ALL WELDED CONNECTIONS OR WING PLATES CONNECTED TO WEB WHERE THEFORCE IS TRANSVERSE TO THE WEB OF THE MEMBER WITH THE WING PLATES.

F. CONNECTIONS FOR FRAMING MEMBERS WITH BOTH GRAVITY LOADS (REACTIONS) AND AXIALLOADS OR TRANSFER FORCES (TENSION OR COMPRESSION) SHALL BE DESIGNED FOR THECOMBINED EFFECT OF BOTH LOADS.

G. CONNECTION DESIGN DRAWINGS AND CALCULATIONS MUST BE SUBMITTED FOR APPROVAL TOTHE ARCHITECT AND SUBSEQUENTLY REVIEWED, APPROVED AND RETURNED BY THE ARCHITECTPRIOR TO THE SUBMITTAL OF SHOP DRAWINGS THAT INCORPORATE THESE DESIGNS.CONNECTION DESIGN SUBMITTAL REVIEW COMMENTS MADE BY THE ARCHITECT SHALL BEINCORPORATED INTO THE RELATED SHOP DRAWINGS PRIOR TO THEIR SUBMITTAL.SUBMITTALS IN NONCOMPLIANCE WILL BE RETURNED UNREVIEWED BY THE ARCHITECT.

H. STEEL CONTRACTOR SHALL FURNISH ERECTION BOLTS AS REQUIRED FOR FIELDCONNECTIONS.

I. ALL BEAMS THAT ARE REQUIRED TO HAVE CAMBER SHALL BE FABRICATED WITH CAMBERUPWARD. BEAMS WITHOUT SPECIFIED CAMBER SHALL BE FABRICATED SUCH THAT AFTERERECTION, ANY NATURAL CAMBER DUE TO ROLLING OR SHOP FABRICATION IS UPWARD.

J. UNLESS OTHERWISE INDICATED IN THE DRAWINGS, ALL ANCHOR RODS SHALL CONFORM TOASTM F1554 GRADE 55-WELDABLE AND SHALL BE ¾" DIAMETER WITH A MINIMUM FOUNDATIONEMBEDMENT OF 12". THE EMBEDDED END SHALL HAVE A HEAVY HEX NUT WITH THE THREADSSPOILED ABOVE AND BELOW THE NUT.

K. PROVIDE TEMPORARY SHORES, GUYS, BRACES, AND OTHER SUPPORTS DURING ERECTION TOKEEP STRUCTURAL STEEL SECURE, PLUMB, AND IN ALIGNMENT AGAINST TEMPORARYCONSTRUCTION LOADS AND LOADS EQUAL IN INTENSITY TO DESIGN LOADS. THE TEMPORARYSUPPORTS SHALL BE SUFFICIENT TO SECURE THE BARE STRUCTURAL STEEL FRAMING OR ANYPORTION THEREOF AGAINST LOADS THAT ARE LIKELY TO BE ENCOUNTERED DURINGERECTION, INCLUDING THOSE DUE TO WIND AND THOSE THAT RESULT FROM ERECTIONOPERATIONS.

L. DO NOT REMOVE TEMPORARY SUPPORTS UNTIL THE INSTALLATION OF ALL STRUCTURALELEMENTS IS COMPLETE AND HAS BEEN ACCEPTED AS COMPLETE BY THE STRUCTURALENGINEER. FOR THE PURPOSES OF THIS PARAGRAPH, "ALL STRUCTURAL ELEMENTS"INCLUDES ANY OF THE FOLLOWING THAT ARE SHOWN IN THE STRUCTURAL DRAWINGS:FOUNDATIONS, TILT-UP CONCRETE PANELS AND THEIR CONNECTIONS TO FOUNDATIONS ANDSLABS, LOAD-BEARING CMU WALLS, CMU SHEAR WALLS, STRUCTURAL STEEL, STEELCONNECTIONS, PERMANENT BRACING, WELDED MOMENT CONNECTIONS, STEEL JOISTS, JOISTBRIDGING, ROOF DECK AND FLOOR DECK.

M. ALL SHOP AND FIELD WELDS SHALL BE MADE IN ACCORDANCE WITH THE ANSI/AWS"D1.1-STRUCTURAL WELDING CODE - STEEL", LATEST EDITION. ALL WELDING SHALL USELOW HYDROGEN PROCESSES.

N. ALL BOLTS SHALL BE ASTM A325 WITH SUITABLE WASHERS AND NUTS.

O. ALL ANGLE FRAMES, PLATES AND OTHER EMBEDDED ITEMS CAST INTO CONCRETE SHALL BEGALVANIZED.

P. SUBSTITUTION OF EXPANSION ANCHORS FOR EMBEDDED ANCHORS SHOWN ON THE DRAWINGSWILL NOT BE PERMITTED.

Q. CUTS, HOLES, COPING, ETC. REQUIRED FOR WORK OF OTHER TRADES SHALL BE SHOWN ONTHE SHOP DRAWINGS AND MADE IN THE SHOP. CUTS OR BURNING OF HOLES IN STRUCTURALSTEEL MEMBERS IN THE FIELD WILL NOT BE PERMITTED.

R. ALL EXTENSION BARS, RUN-OFF PLATES, AND BACKING BARS USED IN WELDED CONNECTIONSSHALL BE REMOVED AND THE JOINTS SHALL BE GROUND SMOOTH WHERE SUCH CONNECTION ISPERMANENTLY EXPOSED TO VIEW OR IS DESIGNATED AS ARCHITECTURALLY EXPOSED STEEL.

S. ALL ROOF OPENINGS GREATER THAN 6" SHALL BE SUPPORTED BY AN ANGLE FRAME. IFSIZES ARE NOT PROVIDED, REFER TYPICAL DETAILS FOR ROOF OPENING FRAME DETAIL.

T. ALL ELEVATED MECHANICAL EQUIPMENT SHALL BE SUPPORTED BY STEEL. IF SIZES ARENOT PROVIDED, REFER TYPICAL DETAILS FOR ROOF OPENING FRAME DETAIL.

U. GALVANIZED LOOSE LEDGE ANGLES SHALL BE PROVIDED OVER ALL MASONRY VENEEROPENINGS OR RECESSES DEEPER THAT 4". LINTELS SHALL HAVE 1" OF BEARING AT EACHEND FOR EVERY FOOT OF SPAN, WITH A MINIMUM OF 4" AND SIZED AS FOLLOWS UNLESSSHOWN OTHERWISE IN THE DRAWINGS.

1) UP TO 4'-0".........................L3-1/2 x 3-1/2 x 3/82) 4'-1" to 5'-0"......................L4 x 3-1/2 x 3/8 (LLV)3) 5'-1" to 6'-6"......................L5 x 3-1/2 x 3/8 (LLV)4) 6'-7" to 8'-0"......................L6 x 3-1/2 x 3/8 (LLV)

V. ALL VISIBLE STEEL EXPOSED TO EXTERIOR WEATHER OR AN UNCONTROLLED ENVIRONMENTSHALL BE BLAST CLEANED, PRIMED WITH A ZINC-RICH PRIMER AND FIELD PAINTED WITH AHIGH PERFORMANCE PAINT. NON-VISIBLE STEEL EXPOSED TO EXTERIOR WEATHER OR ANUNCONTROLLED ENVIRONMENT SHALL BE BLAST CLEANED AND RECEIVE A ZINC-RICH PRIMER.INTERIOR STEEL SHALL BE SHOP PRIMED AND FIELD PAINTED.

W. ALL HEADED STUDS AND DEFORMED BAR ANCHORS SHALL BE INSTALLED USING AUTOMATICEND-WELDING EQUIPMENT RECOMMENDED BY THE STUD OR ANCHOR MANUFACTURER. MANUALWELDING OF HEADED STUDS OR DEFORMED BAR ANCHORS WILL NOT BE ALLOWED.

10.

525 Central Park Drive, Suite 202Oklahoma City, OK 73105Telephone: 405.528.4596Fax: 405.528.4580

Kirkpatrick Forest Curtis PCStructural Engineering

engineering

OK CA #3888, EXP. 06/30/19

Page 2: 1PARTIAL FOUNDATION PLAN REV 5 CLIMAT… · 1.general information a.governing building code: 2009 international building code (ibc-2009). b.building classification: the building classification

X. SHOP PRIMER SHALL NOT BE APPLIED TO THE FOLLOWING AREAS:

1) SURFACES EMBEDDED IN CONCRETE OR MORTAR. EXTEND PRIMING OF PARTIALLYEMBEDDED MEMBERS TO A DEPTH OF 2 INCHES.

2) SURFACES TO BE FIELD WELDED.3) SURFACES TO BE HIGH-STRENGTH BOLTED WITH SLIP-CRITICAL CONNECTIONS.4) SURFACES TO RECEIVE SPRAYED FIRE-RESISTIVE MATERIALS.5) GALVANIZED SURFACES.

9. STEEL JOIST AND BRIDGING NOTES

A. AS A MINIMUM REQUIREMENT, THE JOIST MANUFACTURER SHALL DESIGN ALL JOISTS FORTHE DESIGN LOADS SPECIFIED IN THE STEEL JOIST INSTITUTE'S LOAD TABLES. INADDITION, JOISTS SHALL BE DESIGNED TO CARRY ANY OTHER LOADS INDICATED ON THEDRAWINGS.

B. JOISTS SHALL BE DESIGNED BY THE JOIST MANUFACTURER FOR A NET UPLIFT OF 10 PSFIN THE FIELD OF THE ROOF AND 15 PSF WITHIN 10 FEET OF ROOF EDGES.

C. PROVIDE FLAT BEARING SEATS FOR ALL JOISTS BY INCREASING THE DEPTH OF THE SEATAT THE HIGH END OF SLOPED JOISTS.

D. JOIST BRIDGING SHOWN IS GREATER THAN OR EQUAL TO THE MINIMUM REQUIRED BY THESTEEL JOIST INSTITUTE (SJI). JOIST MANUFACTURER CAN PROVIDE LARGER SIZE, IFREQUIRED.

E. ADDITIONAL BRIDGING LINES AT THE BOTTOM CHORD OUTSIDE PANEL POINT HAVE NOT BEENSHOWN FOR CLARITY BUT ARE REQUIRED. PROVIDE AS DESIGNED BY THE JOISTMANUFACTURER.

F. BETWEEN PANEL POINTS OF STEEL JOISTS THE CHORD MEMBERS SHALL BE DESIGNED TOSUPPORT 50 LBS. VERTICAL LOAD WITHOUT REINFORCEMENT OF THE CHORD. TYPICALLY,UNDERHUNG LOADS SHALL BE SUPPORTED AT PANEL POINTS. OFF PANEL POINT LOADING INEXCESS OF 50 POUNDS WILL REQUIRE JOIST REINFORCING. REFER TYPICAL DETAILS FORJOIST REINFORCING DETAIL. NO VERTICAL LOAD SHALL BE IMPOSED ON BRIDGING. NOLOAD APPLIED TO JOIST SHALL BE DONE IN A MANNER THAT EXCEEDS MOMENT OR SHEARCAPACITY OF THE JOIST.

G. ANY HANGERS SUPPORTED FROM JOISTS SHALL BE CONNECTED WITHOUT FIELD WELDING ORDRILLING TO THE JOIST.

H. BOTTOM CHORDS ON ALL JOISTS SHALL BE EXTENDED TO RECEIVE CEILING OR POTENTIALFUTURE CEILING.

I. IN STEEL FRAMES, WHERE COLUMNS ARE NOT FRAMED IN AT LEAST TWO DIRECTIONS WITHSTRUCTURAL STEEL MEMBERS, BEARING SEATS FOR JOISTS AT COLUMN LINES SHALL BEFABRICATED TO ALLOW FOR FIELD BOLTING.

J. ERECTION OF JOISTS SHALL FOLLOW THE STEEL JOIST INSTITUTE'S CODE OF STANDARDPRACTICE. JOISTS SHALL NOT BE FULLY LOADED UNTIL ALL BRIDGING LINES ARESECURED AND METAL DECKING IS IN PLACE. THE JOIST MANUFACTURER AND ERECTORSHALL PROVIDE ADDITIONAL BRIDGING DURING CONSTRUCTION SEQUENCING AS REQUIRED BYTHE CURRENT SJI SPECIFICATIONS AND OSHA REQUIREMENTS.

K. HORIZONTAL BRIDGING ANGLES FOR TOP AND BOTTOM CHORDS OF JOISTS ARE SHOWN ONFRAMING PLANS THUS: - - - - -

L. DIAGONAL BRIDGING IS SHOWN AS AN "X" ALONG A LINE OF HORIZONTAL BRIDGING.DIAGONAL BRIDGING SHALL BE PROVIDED WHERE SHOWN AND AT ANY DISCONTINUITIES INTHE ROW OF BRIDGING.

M. REFER TYPICAL DETAILS FOR JOIST BRIDGING DETAILS.

N. THE GENERAL CONTRACTOR SHALL CONFIRM OR REVISE MECHANICAL EQUIPMENT WEIGHTS ANDPROVIDE THE JOIST MANUFACTURER POINT LOADS FOR WHICH SPECIAL JOISTS ARE TO BEDESIGNED. PRELIMINARY ROOF TOP UNIT (RTU) WEIGHTS ARE SHOWN ON THE ROOF PLANS.SHOULD WEIGHTS EXCEED THOSE SHOWN, CONTRACTOR SHALL CONTACT ARCHITECT-ENGINEERFOR REVIEW.

10.METAL DECK NOTES:

A. ROOF DECK:

1) ROOF DECK SHALL BE 1½" DEEP, 22 GAGE, GALVANIZED WIDE RIB METAL DECK WITHSTRUCTURAL PROPERTIES MEETING OR EXCEEDING THE FOLLOWING:A) I = 0.183 IN4/FTB) Sp = 0.186 IN3/FTC) Sn = 0.192 IN3/FTD) Fy = 33 KSIE) SIDE LAPS: OVERLAPPED

2) ROOF DECK SHALL BE CONNECTED TO SUPPORTS WITH #12 MECHANICAL FASTENERS AT 6"O.C. (36/7 PATTERN).

3) ROOF DECK SIDE LAPS SHALL BE FASTENED WITH #10 SIDE LAP FASTENERS AT 6" ONCENTER.

B. SUBSTITUTION OF WELDING OR PINS FOR MECHANICAL SCREW ANCHORS WILL NOT BEPERMITTED.

C. SUPPORTS FOR DECKING ARE DEFINED AS MEMBERS PROVIDING DIRECT TRANSVERSE SUPPORTAS WELL AS CONTINUOUS PARALLEL EDGE SUPPORT.

D. ALL DECKING SHALL BE PLACED PERPENDICULAR TO SUPPORTING ROOF MEMBERS AND SHALLSPAN A MINIMUM OF 3 SPANS UNLESS SHOWN OTHERWISE IN STRUCTURAL DRAWINGS.

E. METAL DECKING SHALL NOT BE USED TO SUPPORT ANY HANGING LOADS INCLUDING, BUT NOTLIMITED TO, SUSPENDED MECHANICAL, ELECTRICAL, OR PLUMBING EQUIPMENT, CABLETRAYS OR RACEWAYS, CEILING FINISHES OR CEILING FRAMING.

F. ALL DECK OPENINGS GREATER THAN 6" SHALL BE SUPPORTED BY AN ANGLE FRAME. IFSIZES ARE NOT PROVIDED, REFER TYPICAL DETAILS FOR ROOF OPENING FRAME DETAIL.

G. METAL ROOF DECK SHALL BE LAPPED A MINIMUM OF 2" OVER SUPPORTS. FASTENERS SHALLPENETRATE BOTH PLIES OF DECKING INTO SUPPORTING SUBSTRATE OR 2 LINES OFFASTENERS SHALL BE PROVIDED.

525 Central Park Drive, Suite 202Oklahoma City, OK 73105Telephone: 405.528.4596Fax: 405.528.4580

Kirkpatrick Forest Curtis PCStructural Engineering

engineering

OK CA #3888, EXP. 06/30/19

Page 3: 1PARTIAL FOUNDATION PLAN REV 5 CLIMAT… · 1.general information a.governing building code: 2009 international building code (ibc-2009). b.building classification: the building classification

SCALE: 1/4"=1'-0"

PARTIAL FOUNDATION PLAN1

S2.0

1

S5.0

S5.0

3

1

1

1

1

KEY PLAN

1

SCALE: 1"=1'-0"

SECTION OPTIONAL

TYP. WALL FOOTING

2

S2.1

1

525 Central Park Drive, Suite 202Oklahoma City, OK 73105Telephone: 405.528.4596Fax: 405.528.4580

Kirkpatrick Forest Curtis PCStructural Engineering

engineering

OK CA #3888, EXP. 06/30/21

1

Page 4: 1PARTIAL FOUNDATION PLAN REV 5 CLIMAT… · 1.general information a.governing building code: 2009 international building code (ibc-2009). b.building classification: the building classification

SCALE: 1/4"=1'-0"

PARTIAL FOUNDATION PLAN1

S2.1

1

1

1

1

1

KEY PLAN

1

525 Central Park Drive, Suite 202Oklahoma City, OK 73105Telephone: 405.528.4596Fax: 405.528.4580

Kirkpatrick Forest Curtis PCStructural Engineering

engineering

OK CA #3888, EXP. 06/30/21

1

Page 5: 1PARTIAL FOUNDATION PLAN REV 5 CLIMAT… · 1.general information a.governing building code: 2009 international building code (ibc-2009). b.building classification: the building classification

SCALE: 1/4"=1'-0"

SECOND LEVEL FRAMING PLAN

PARTIAL

1

S3.0

1

S5.0

5

S5.0

5

S5.0

1

5

S5.0

1

1

1

1

KEY PLAN

525 Central Park Drive, Suite 202Oklahoma City, OK 73105Telephone: 405.528.4596Fax: 405.528.4580

Kirkpatrick Forest Curtis PCStructural Engineering

engineering

OK CA #3888, EXP. 06/30/21

1

1

Page 6: 1PARTIAL FOUNDATION PLAN REV 5 CLIMAT… · 1.general information a.governing building code: 2009 international building code (ibc-2009). b.building classification: the building classification

SCALE: 1/4"=1'-0"

SECOND LEVEL FRAMING PLAN

PARTIAL

1

S2.1

1

1

1

KEY PLAN

525 Central Park Drive, Suite 202Oklahoma City, OK 73105Telephone: 405.528.4596Fax: 405.528.4580

Kirkpatrick Forest Curtis PCStructural Engineering

engineering

OK CA #3888, EXP. 06/30/21

1

1

Page 7: 1PARTIAL FOUNDATION PLAN REV 5 CLIMAT… · 1.general information a.governing building code: 2009 international building code (ibc-2009). b.building classification: the building classification

SCALE: 1/4"=1'-0"

PARTIAL ROOF FRAMING PLAN1

S3.1

2

S5.0

1

S5.0

1

KEY PLAN

1

525 Central Park Drive, Suite 202Oklahoma City, OK 73105Telephone: 405.528.4596Fax: 405.528.4580

Kirkpatrick Forest Curtis PCStructural Engineering

engineering

OK CA #3888, EXP. 06/30/21

1

Page 8: 1PARTIAL FOUNDATION PLAN REV 5 CLIMAT… · 1.general information a.governing building code: 2009 international building code (ibc-2009). b.building classification: the building classification

SCALE: 1/4"=1'-0"

FRAMING ELEVATION3

S4.0 SCALE: 1/4"=1'-0"

FRAMING ELEVATION4

S4.0

SCALE: 1/16"=1'-0"

EXTERIOR FRAMING ELEVATION -WEST1

S4.0

S4.0

4

SCALE: 1/16"=1'-0"

ELEVATION -NORTH

FRAMING

2

S4.0

S4.0

3

1

525 Central Park Drive, Suite 202Oklahoma City, OK 73105Telephone: 405.528.4596Fax: 405.528.4580

Kirkpatrick Forest Curtis PCStructural Engineering

engineering

OK CA #3888, EXP. 06/30/21

1

Page 9: 1PARTIAL FOUNDATION PLAN REV 5 CLIMAT… · 1.general information a.governing building code: 2009 international building code (ibc-2009). b.building classification: the building classification

SCALE: 1/4"=1'-0"

MEZZANINE FRAMING PLAN1

SSK-01

2

SSK-01

SCALE: 1"=1'-0"

SECTION @ JST SUPPORT2

SSK-01

525 Central Park Drive, Suite 202Oklahoma City, OK 73105Telephone: 405.528.4596Fax: 405.528.4580

Kirkpatrick Forest Curtis PCStructural Engineering

engineering

OK CA #3888, EXP. 06/30/21

Page 10: 1PARTIAL FOUNDATION PLAN REV 5 CLIMAT… · 1.general information a.governing building code: 2009 international building code (ibc-2009). b.building classification: the building classification

SCALE: 1/4"=1'-0"

ENLARGED WALL PANEL ELEVATION2

S4.1

SCALE: 1/16"=1'-0"

EXTERIOR FRAMING ELEVATION -WEST1

S4.0

S4.1

2

KEY PLAN

1

S4.2

525 Central Park Drive, Suite 202Oklahoma City, OK 73105Telephone: 405.528.4596Fax: 405.528.4580

Kirkpatrick Forest Curtis PCStructural Engineering

engineering

OK CA #3888, EXP. 06/30/21

AutoCAD SHX Text
EXT. GRADE
AutoCAD SHX Text
NEW OPENING
AutoCAD SHX Text
7 " CONC. 14" CONC. TILTWALL PANEL
AutoCAD SHX Text
FIN. ROOF LINE
AutoCAD SHX Text
JOIST SEAT
AutoCAD SHX Text
JOIST EXTENSION EMBED (F.F.)
AutoCAD SHX Text
5 " REVEAL12" REVEAL
AutoCAD SHX Text
FIN. FLOOR ELEV.
AutoCAD SHX Text
NEW OPENING
AutoCAD SHX Text
3
AutoCAD SHX Text
2
AutoCAD SHX Text
INFILLED OPENING
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
20'-0"
AutoCAD SHX Text
40'-0"
AutoCAD SHX Text
PANEL A 02 03 a
AutoCAD SHX Text
PANEL A 02 03 b
AutoCAD SHX Text
A
AutoCAD SHX Text
H
AutoCAD SHX Text
1
AutoCAD SHX Text
16
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
DRAWING TITLE
AutoCAD SHX Text
DRAWING NUMBER
AutoCAD SHX Text
PROJECT NUMBER
AutoCAD SHX Text
DRAWING TITLE
AutoCAD SHX Text
CADD FILE NAME
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DATE
AutoCAD SHX Text
TRINITY
AutoCAD SHX Text
INTERIOR ARCHITECTURE
AutoCAD SHX Text
3030 N.W. EXPRESSWAY SUITE 1450
AutoCAD SHX Text
ARCHITECTS
AutoCAD SHX Text
GROUP
AutoCAD SHX Text
ARCHITECTURE
AutoCAD SHX Text
OKLAHOMA CITY, OK 73112
AutoCAD SHX Text
LAND PLANNING
AutoCAD SHX Text
405.947.7262
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
CD-18113.DWG
AutoCAD SHX Text
C
AutoCAD SHX Text
M
AutoCAD SHX Text
LIMATE ASTER,INC.
AutoCAD SHX Text
7300 SW 44th St
AutoCAD SHX Text
OKLAHOMA CITY, OK 73179
AutoCAD SHX Text
WALL PANEL ELEVATION
AutoCAD SHX Text
S4.1
AutoCAD SHX Text
JANUARY 20, 2020
Page 11: 1PARTIAL FOUNDATION PLAN REV 5 CLIMAT… · 1.general information a.governing building code: 2009 international building code (ibc-2009). b.building classification: the building classification

SCALE: 1/2"=1'-0"

SECTION AT ELEVATOR PIT1

S5.0 SCALE: 1/2"=1'-0"

ENLARGED PLAN AT ELEV. PIT3

S5.0

SCALE: 1"=1'-0"

SECTION AT ELEVATOR2

S5.0

SCALE: 3/4"=1'-0"

LINTEL TYPE4

S5.0

SCALE: 1"=1'-0"

SECTION5

S5.0525 Central Park Drive, Suite 202

Oklahoma City, OK 73105Telephone: 405.528.4596Fax: 405.528.4580

Kirkpatrick Forest Curtis PCStructural Engineering

engineering

OK CA #3888, EXP. 06/30/19