Standard Sewer Drawings January
2019
1920 North Iris Lane Escondido, CA 92026
Phone (760) 7 45-5522 Facsimile (760) 7 45-4235 www.rinconwater.org
RINCON DEL DIABLO MUNICIPAL
WATER DISTRICT
STANDARD DRAWINGS
January 2019
RINCON DEL DIABLO MUNICIPAL WATER DISTRICT
1920 NORTH IRIS LANE ESCONDIDO, CALIFORNIA 92026
PHONE (760) 745-5522 FAX (760) 745-4235
Rincon del Diablo Municipal
Water District
Sewer Standard Drawings
CONTENTS
Part I. Sewer Construction Notes
Part II. Approved Materials List
Part Ill. Improvement Plan Signature Blocks and Certificate
Part IV. Standard Drawings - Sewer
RINCON DEL DIABLO MUNICIPAL WATER DISTRICT
PART I. Sewer Construction Notes
SEWER NOTES:
1. CONTRACTOR SHALL FURNISH AND INSTALL ALL FACILITIES IN ACCORDANCE WITH RINCON DEL DIABLO MUNICIPAL WATER DISTRICT (DISTRICT) WATER SYSTEM FACILITY REQUIREMENTS, STANDARD SPECIFICATIONS AND STANDARD DRAWINGS. RDDMWD STANDARD SPECIFICATIONS AND STANDARD DRAWINGS ARE AVAILABLE AT THE DISTRICT OFFICE. CONTRACTOR SHALL BE IN POSSESSION OF DISTRICT'S SPECIFICATIONS AND STANDARD DRAWINGS ON THE JOB SITE AT ALL TIMES.
2. ALL PERMITS REQUIRED BY LAW SHALL BE ACQUIRED BY THE APPLICANT OR THEIR CONTRACTOR AND ARE MADE PART OF THE SPECIFICATIONS.
3. THE DRAWINGS AND DATA HEREON ARE HEREBY MADE PART OF THE SPECIFICATIONS.
4. REVISIONS WILL NOT BE MADE TO THESE PLANS WITHOUT THE APPROVAL OF DISTRICT.
5. APPROVAL OF THESE PLANS BY DISTRICT DOES NOT CONSTITUTE A REPRESENTATION OF THE ACCURACY OF THE LOCATION OR EXISTENCE OR NON-EXISTENCE OF ANY UNDERGROUND UTILITY, PIPE OR STRUCTURE WITHIN THE LIMITS OF WORK.
6. CONTRACTOR SHALL NOTIFY THE RDDMWD ONE WEEK PRIOR TO STARTING CONSTRUCTION.
7. THE DISTRICT INSPECTOR SHALL BE FURNISHED TWO SETS OF PROJECT DRAWINGS.
8. THE CONTRACTOR SHALL CONFORM TO CURRENT CAL OSHA SAFETY REQUIREMENTS.
9. THE CONTRACTOR SHALL SUBMIT TO THE DISTRICT A SOILS REPORT BY A QUALIFIED GEOTECHNICAL ENGINEER WHICH CERTIFIES THAT ALL TRENCH BACKFILL WAS COMPACTED AS DIRECTED BY THE SOILS ENGINEER IN ACCORDANCE WITH PROJECT SPECIFICATIONS AND DISTRICT SPECIFICATIONS.
10. EACH LOT SHALL BE SERVICED WITH A FOUR (4)-INCH SEWER LATERAL SET AT A MINIMUM GRADE OF 2.0% WITH A MINIMUM INVERT DEPTH OF 5.0 FEET BELOW THE BOTTOM OF THE CURB AT THE PROPERTY LINE, UNLESS OTHERWISE APPROVED BY THE DISTRICT.
11. ALL LATERALS SHALL BE LOCATED AS SHOWN ON THE DRAWINGS, ADJUSTED UNDER DISTRICT INSPECTION TO CLEAR DRIVEWAYS AND OTHER IMPROVEMENTS. LATERALS SHALL BE FOUR (4)-INCH MINIMUM DIAMETER UNLESS OTHERWISE NOTED ON THE DRAWINGS. ALL LATERALS SHALL HAVE A CLEAN OUT IN ACCORDANCE WITH STANDARD DRAWINGS NO. S-9 AND S-30. LATERALS SHALL BE INSTALLED IN ACCORDANCE WITH DISTRICT STANDARD DRAWING NOS. S-4, S-5, S-6, AND S-7.
12. JOB-MIXING OF CONCRETE IS NOT PERMITTED.
13. ALL CONCRETE TESTING REQUIRED BY THE DISTRICT WILL BE AT THE EXPENSE OF THE CONTRACTOR.
14. THE CONTRACTOR SHALL SECURE APPROVAL FROM THE DISTRICT INSPECTOR PRIOR TO BACKFILLING OVER ANY SEWER PIPE OR WYE.
15. ALL SEWER LATERALS AND MAINS SHALL BE TESTED BY "AIR TEST METHOD" AFTER CONSTRUCTION AS SPECIFIED IN THE DISTRICT SPECIFICATIONS.
16. ALL ACCESS HOLES (MAN HOLES) SHALL BE TESTED BY "VACUUM TESTS" AS SPECIFIED IN THE DISTRICT STANDARD SPECIFICATIONS.
17. CONTRACTOR SHALL PROVIDE WRITTEN NOTIFICATION REQUESTING A SYSTEM SHUTDOWN FOR CONNECTIONS TO EXISTING SYSTEM. SAID NOTIFICATION SHALL BE OF THREE WEEKS PRIOR TO SAID SHUTDOWN TO THE DISTRICT ENGINEER.
18. CONTRACTOR SHALL DESIGNATE A QUALIFIED SUPERINTENDENT WITH FULL AUTHORITY TO ACT ON BEHALF OF THE CONTRACTOR. SAID SUPERINTENDENT SHALL BE ON THE JOB SITE AT ALL TIMES.
19. CONTRACTOR SHALL PERFORM ALL WORK UNDER SAN DIEGO COUNTY ROAD DEPARTMENT AND/OR CITY OF ESCONDIDO JURISDICTION IN ACCORDANCE WITH ALL REQUIREMENTS OF SAID DEPARTMENT INCLUDING TRAFFIC CONTROL, PAVEMENT REMOVAL, TEMPORARY PAVEMENT (INCLUDING BASE MATERIAL) AND TEMPORARY AND PERMANENT TRAFFIC STRIPPING.
20. ALL MATERIALS, TESTING, AND INSPECTION OF THE SEWER SHALL BE IN CONFORMITY WITH THE REQUIREMENTS OF THE DISTRICT, SAN DIEGO COUNTY AND/OR CITY OF ESCONDIDO STANDARDS. FAILURE TO MEET ANY REQUIREMENTS OF THE ABOVE REFERENCED AGENCIES WILL BE CAUSE FOR REJECTION.
21. SEWER SHALL BE ___ -INCH PVC (SOR 35) OR ___ -INCH PVC C900 OR C905 (REQUIRED FOR SEWER DEPTH>15-FEET) IN ACCORDANCE WITH DISTRICT SPECIFICATIONS AND STANDARDS.
22. FORCE MAINS SHALL BE ___ -INCH PVC IN ACCORDANCE WITH DISTRICT SPECIFICATIONS AND STANDARDS (PROVIDE FORCE MAIN DIAMETER, C900 OR C905, AND PIPE CLASS 200 OR GREATER).
23. STANDARD MANHOLES SHALL BE CONSTRUCTED IN ACCORDANCE WITH DISTRICT STANDARD DRAWING NO. S-12. TERMINUS TYPE MANHOLES SHALL BE CONSTRUCTED IN ACCORDANCE WITH DISTRICT STANDARD DRAWING NO. S-13.
24. STANDARD MANHOLE COVERS SHALL BE CONSTRUCTED IN ACCORDANCE WITH DISTRICT STANDARD DRAWING NO. S-14 ANDS-15. IN UPAVED AREAS LOCKING TYPE MANHOLE COVERS SHALL BE CONSTRUCTED IN ACCORDANCE WITH DISTRICT STANDARD DRAWING NO. S-17.
25. SEWER BEDDING, BACKFILL, CAPS, AND ENCASEMENT, CAPS SHALL BE IN ACCORDANCE WITH DISTRICT STANDARD DRAWING NO. S-1, S-2, AND S-3.
26. CONTRACTOR SHALL PROVIDE AND BEAR THE TOTAL COST OF CLOSED CIRCUIT VIDEO INSPECTION OF ALL NEW INSTALLED PIPELINES UNLESS OTHERWISE DIRECTED BY THE DISTRICT INSPECTOR.
27. PRIOR TO POURING OF MANHOLE BASE, CONTRACTOR SHALL INSTALL A MANHOLE ADAPTER MADE BY GPK PRODUCTS, INC FOR ALL INLET(S) AND OUTLET AT THE PROPER GRADE AND DIRECTION.
28. EACH MANHOLE SHALL BE VACUUM TESTED IMMEDIATELY AFTER ASSEMBLY AND PRIOR TO BACKFILLING BY THE CONTRACTOR. AFTER THE CONTRACTOR COMPLETES BACKFILLING AND PRIOR TO ACCEPTANCE BY THE DISTRICT, EACH MANHOLE SHALL BE RETESTED IN THE PRESENCE OF THE DISTRICT INSPECTOR.
29. NO GROUT SHALL BE PLACED IN THE HORIZONTAL JOINTS BEFORE TESTING.
30. A VACUUM OF 10 INCHES OF MERCURY SHALL BE DRAWN AND THE PUMP SHUT OFF. WITH ALL VALVES CLOSED, THE MANHOLE SHALL HOLD 10 INCHES OF MERCURY FOR 60 SECONDS.
31. IF THE MANHOLE FAILS THE INITIAL TEST, NECESSARY REPAIRS SHALL BE MADE WITH A NON-SHRINK GROUT TO THE OUTSIDE WHILE THE VACUUM IS STILL BEING DRAWN. RETESTING SHALL PROCEED UNTIL A SATISFACTORY TEST IS OBTAINED.
32. MANHOLE DIAMETERS SHALL BE 48-INCH FOR SEWER DIAMETER 24-INCH AND SMALLER, AND 60-INCH FOR SEWER PIPE DIAMETER 27-INCH AND LARGER AND FOR ALL MANHOLES WITH A DEPTH OF 12-FEET OR MORE. 36-INCH CONE SHALL BE USED WITH A 60-INCH MANHOLE.
33. FOR 1) ALL NEW MANHOLES ON SEWER DIAMETERS 15-INCHES OR GREATER 2) ALL NEW MANHOLES WHERE UPSTREAM SEWER SLOPE IS 5% OR GREATER 3) ALL MANHOLES WITHIN 1000 FEET OF A FORCEMAIN DISCHARGE AND 4) EXISTING MANHOLES WITH NEW CONNECTIONS SHALL BE PROVIDED WITH INTEGRALLY LOCKING PVC OR POLYURETHANE PROTECTIVE LINING SYSTEM PER SECTION 500-2 OF THE GREENBOOK.
RINCON DEL DIABLO MUNICIPAL WATER DISTRICT
PART II. Approved Materials List
Items
CASING, END SEAL
CASING, SP ACER
Description
1/4" Thick Styrene Butadiene Rubber Sheet End Seal. Use 1" Wide Stainless Steel Bands. Zippered End Seals with Stainless Steel Bands may also be used.
Polyethylene Casing Spacer Center Restrained Position Type with PVC Liner and Non-Metallic Anti- Friction Runners
DAMP-PROOFING Coating Systems used on the Exterior Surface of Manholes at and below Water Table
FLOWMETER Magnetic Flowmeter
LINER SYSTEM PVC T -Shaped Liner System for Lining of Precast Manholes and Concrete Sewer Pipe
MANHOLE, FRAME & COVER 24" Nominal Diameter Cast Iron frame and Covers per ASTM A48, Class 30, with Machined Seats.
MANHOLE, FRAME & COVER 36" Nominal Diameter Cast Iron frame and Covers per ASTM A48, Class 30, with Machined Seats.
MANHOLE, PIPE CONNECTOR Rubber O-Ring Type Gasket for Pipe to Manhole Connection for Cast-In-Place Manholes and Cemented-In-Place Connections (for existing manholes)
MANHOLE, PRECAST CON
MANHOLE, T-LOCK LINED PRECAST CONCRETE
PIPE, PVC
PIPE, PVC
SADDLE
Access Manholes for Sewer Mains ( Grade Rings, Cones, Risers, and Bases) designed for H-20 Highway Loading
PVC lined cones and riser for manholes
4" through 18" ASTM D 3034, SDR 35 Sewer Pipe
21" through 54" ASTM D-1784
4" and 6" Wye and Tee Connections for Sewer Line Installations
Manufacturer
Advance Products & Systems Cascade Water Works Calpico Powerseal Raychem
Advance Products & Systems,Inc (APS) Cascade Water Works Powerseal Pipeline Seal & Insulator, Inc. (PSI)
Kop-Coat, B itumastic Super Service Black
Sparling Tigermag Krohne Enviromag
Ameron
Alhambra Foundry A-1254
Alhambra Foundty A-1325
GPK Products, Inc.
B&W Precast Mar-Con Products Jens en Precast JR Concrete
B&W Precast Mar-Con Products
J ohns-Mansville Diamond Plastics Pacific Western pipe Ipex Vinyltech
Submittal Required
Certainteed Inserta Tee J&M Pipe
VAL VE, AIR RELEASE
VALVE, BACKWATER
WARNING/IDENTIFICATION TAPE
Pressure Air Release and Vacuum Valve, Designed for Sewer Use
4" Extendable ABS Valve
Warning/identification Tape 6" Wide, Colored Green, with Continuous Warning "CAUTION: SEWER LINE BURIED BELOW"
AR.I.
Clean Check, Inc.
Calpico Type 1 Line-Tee Type B Thor, Elast Tee
RINCON DEL DIABLO MUNICIPAL WATER DISTRICT
PART Ill. Improvement Plan Signature Blocks and Certificate
Rincon del Diablo Municipal Water District APPROVED FOR CONSTRUCTION:
General Manager Date
Engineering Date
SEWER SYSTEM CERT/FICA TION I certify that the design of the sewer system in ____________ is in Accordance with the sewer system requirements of the Rincon del Diablo Municipal Water District and that the District has programmed adequate capacity to treat the waste from the proposed project.
General Manager Date
RINCON DEL DIABLO MUNICIPAL WATER DISTRICT
PART IV. Standard Drawings - Sewer
Rincon del Diablo Municipal Water District
Standard Drawings - Sewer
TABLE OF CONTENTS
Description Pipe Zone Bedding & Trench Backfill Concrete Caps and Encasement Sewer Connection at Concrete Encasement Sewer Lateral Normal Cut Sewer Lateral Deep Cut Sewer Lateral VCP Saddle Connection Sewer Lateral Plastic Pipe Saddle Connection Connecting Dissimilar Sewer Pipes Residential Cleanout Sewer Chimney Lateral Sewer Tree Lateral & Cleanouts Pre-Cast Reinforced Eccentric Concrete Manhole Terminus Manhole with House Laterals Manhole Cover and Frame - Standard and Watertight Manhole Cover and Frame - Two Covers Paving Detail Around Manholes Manhole Cover and Frame - Locking Type Sewer Clean-Out 36" I.D. Sampling Manhole Drop Manhole NOT APPLICABLE NOT APPLICABLE Pipe Casing Sewer Main Sewer Main Crossing Existing Water Sand/or Oil Separator Sampling Box #1 (Industrial) Sampling Box #2 (Commercial) Grease Interceptor Typical Backflow Valve Assembly & Detail Standard Clean-Out Cover
Drawing Number S-1 S-2 S-3 S-4 S-5 S-6 S-7 S-8 S-9 S-10 S-11 S-12 S-13 S-14 S-15 S-16 S-17 S-18 S-19 S-20 S-21 S-22 S-23 S-24 S-25 S-26 S-27 S-28 S-29 S-30
UNSURFACED CONDITION (TYPICAL ALL PIPE TYPES)
RESURFACING-PER EXISTING (TYPICAL ALL PIPE TYPES)
BASE MA TERI AL CLASS 2 AB, 95% RELATIVE DENSITY
2" METAL LOCATOR TAPE 12" ABOVE SEWER FORCEMAIN
2" METAL LOCATER TAPE 12" ABOVE SEWER FORCEMAIN
(/) w ~ SUBGRADE-95% :;: RELATIVE DENSITY
= z N..-- ~
BACKFILL-90% RELATIVE DENSITY
AA----SELECT FILL 90% RELATIVE DENSITY ----,-
~ Cl
-.;t
ci' * ~77:n'7<::7T"t'----'-7"7:?'7".7'v":l"""""'-.:::---~·
BEDDING MA TERI AL CLASS C CLASS B
(/) w ~ <(
>
= z N..--~
"<;!
'* ,-.--'--T-,:;i'-Trd"..r:--'"'-f'"··-· --·r--__ ____._,Cl
(8" TO 15" UP (UP TO 20' * 4" MIN. TO 811
MAX. TO 15' COVER) ANY SIZE) BENEATH PIPE OR 1" MIN.
GREATER THAN 20' REQUIRES CONCRETE ENCASEMENT NO. 2, PER S-2
BELOW BELL, WHICHEVER IS GREATER
STANDARD INSTALLATION VCP PIPE
NOTES:
STANDARD INSTALLATION PVC PIPE
1. BEDDING MATERIAL SHALL CONSIST OF SAND, GRAVEL, CRUSHED AGGREGATE OR NATIVE FREE-DRAINING GRANULAR MATERIAL HAVING A SAND EQUIVALENT OF NOT LESS THAN 30 OR HAVING A PERMEABILITY GREATER THAN 35mm PER HOUR (1.4IN/HR), OR MATERIAL APPROVED BY THE ENGINEER.
2. BACKFILL MATERIAL MAY CONSIST OF NATIVE EXCAVATED SOIL PROVIDED THAT ALL ORGANIC MATERIAL, RUBBISH, DEBRIS AND OTHER OBJECTIONABLE MATERIALS ARE FIRST REMOVED. ROCKS GREATER THAN SIX (6) INCHES IN DIAMETER ARE NOT PERMITTED.
3. BACKFILL SHALL BE PLACED IN LIFTS NO GREATER THAN ONE (1) FEET THICK EXCEPT IN THE TOP ONE (1) FOOT OF TRENCH WHERE THE MAXIMUM LIFT THICKNESS IS SIX (6) INCHES.
4. BACKFILL AND BEDDING MATERIAL SHALL BE MECHANICALLY DENSIFIED WITH VIBRATORY EQUIPMENT TO A MINIMUM RELATIVE COMPACTION OF 90% PER ASTM 1557. WATER DENSIFICATION OF BACKFILL IS NOT ALLOWED (NO FLOODING) AND ROLLING EQUIPMENT SHALL NOT BE USED TO DENSIFY SOIL WITHIN 18 INCHES OF THE TOP OF PIPE.
5. IN PVC PIPE APPLICATIONS, C900 PVC PIPE SHALL BE USED WHEN TRENCH DEPTH EXCEEDS 15 FEET. THE MAXIMUM ALLOWABLE TRENCH DEPTH IS 20 FEET, UNLESS OTHERWISE APPROVED BY THE DISTRICT ENGINEER.
6. WHEN FIRM TRENCH BASE IS NOT ENCOUNTERED DUE TO SOFT, SPONGY OR OTHERWISE UNSUITABLE MATERIAL WITH LESS THEN 85% RELATIVE COMPACTION, UNSUITABLE MATERIAL SHALL BE REMOVED TO THE LIMITS DIRECTED BY THE DISTRICT, AND RESULTING EXCAVATION SHALL BE BACKFILLED WITH 3/4" CRUSHED ROCK UNTIL FIRM SUBGRADE IS FORMED.
REVISION DA1E BY DESCRIPTION 1-----1-----4---1-------------1 APPROVED -----
STANDARD DRAWINGS DWG. NO.
GENERAL MANAGER
DISlRICT ENGINEER
Rincon o'!:~~ Water~ , •
PIPE ZONE BEDDING & TRENCH BACKFILL S-1
DIMEN- PIPE I.D.
SIONS 6" 8" 10" 12" 14" 16"
"A" 6" 6" 6" 6" 6" 6"
HB" 6" 6" 6" 6" 6" 6"
18" 21" 24" 27"
6" 6" 6" 7"
6" 6" 6" 7"
30"
8" 3" MIN.
8"
t- D+12" MIN. -j
TRENCH WALL
STEEL="P" MIN.=0.4% CONT. AS SHOWN, C-C DIST.j'D"
D/4 (6" MIN.)
"B" MIN. "B" MIN. 3" MIN. D/2
3" CLEAR TYP.
CONCRETE
CONCRETE
"A" MIN.
12" LAP
--#4 TIES "B" MIN.
CLEAR TYP.
#5 CONT. AS SHOWN
EARTH
CONCRETE ENCASEMENT NO. 1
"B" MIN. "B" MIN.
t
D/8 (4" MIN.)
D/2
~~2~~~~~i~~~~;;~~~~~~~~~~~ ~ Ml~
REINFORCED CONCRETE CAP CLASS "AA"
AC PAVEMENT
#5 REBARS @
12" ON CENTER EACH WAY
2"CUSHION OF DG ~
TRENCH WALL
"A" MIN.
2 1/2" CLEAR
3" CLASS B CONCRETE SLAB
1'-0" INTO UNDISTURBED SOIL------'
SELECT BACKFILL COMPACTED
1- -71-TTT
1 /2" WELL GRADED CRUSHED ROCK
D/8 (4" MIN.)
CONCRETE ENCASEMENT NO. 2 NOTES: 1. CONCRETE ENCASEMENT AND CAPS SHALL BE INSTALLED AS REQUIRED
BY THE SPECIFICATIONS OR AS DIRECTED BY THE ENGINEER.
2. ALL CONCRETE SHALL BE CLASS 560-C-3250 CONCRETE
3. USE CONCRETE ENCASEMENT N0.2 UNLESS OTHERWISE APPROVED BY THE THE ENGINEER OR SHOWN ON THE CONTRACT DRAWINGS
4. BASED ON 1.25 FACTOR OF SAFETY REFER N.C.P.I. MANUAL, SOIL Wf. 130 LB/CU. FT DEPTHS OVER 30' MAY BE CALCULATED FROM MARSTON'S FORMULA. X DENOTES DISTANCE AT WHICH TRENCH WIDTH MAY BE INCREASE WITHOUT ADDING TO THE WEIGHT ON THE PIPE.
5. •p•=RATIO OF AREA OF STEEL TO AREA OF CONCRETE PER LINEAR FOOT (D/4 OR 4•x12• CONCRETE AREA.).
REVISION DAlE BY DESCRIPTION APPROVED -----1-----+-----+----------t
GENERAL MANAGER
DISlRICT ENGINEER
BOTTOM OF PIPE TO BE PROTECTED
CONCRETE CAP-CLASS "A"
6. CONCRETE CAN BE POURED AGAINST TRENCH WALL, (OPTIONAL)
7. BEDDING CONDITIONS ARE AS FOLLOWS:
A. BEDDING CLASS SHALL EQUAL OR EXCEED THAT GIVEN IN THE APPLICABLE TABLES PER STANDARD DRAWING S-1 .
B. CLASS •A• SHALL BE USED FOR SEWERS WHEREVER DEPTH OF COVER IS LESS THAN 4'.
C. CONSOLIDATED BACKFILL BEDDING BY FLOODING IS NOT PERMITTED D. DEPTHS OF COVER GREATER THAN 20' REQUIRE A SOIL INVESTIGA TlON AND
ANALYSIS BY THE ENGINEER.
8. TWO APPROVED FLEXIBLE COUPLINGS SHALL BE USED AT EACH END OF SEWER PIPE ENCASEMENTS PURSUANT TO STANDARD DRAWING S-3
Rincon 0~6
Water~ _. •
STANDARD DRAWINGS
CONCRETE CAPS AND ENCASEMENT
DWG. NO.
S-2
FLEXIBLE COUPLING
12" MAX.
w
IMMEDIATELY ADJACENT TO ~ CONCRETE ENCASEMENT
12" MAX.
FORMED ENDS CONCRETE ENCASEMENT PER S-2
FORMED ENDS
REVISION DAlE BY DESCRIPllON
1----+---+-+-----------1
NOTES:
1. TWO FLEXIBLE COUPLINGS AS SHOWN, 8O1H SIDES.
2. SUBMIT ROMAC, DRESSER, FORD OR EQUAL SEWER COUPLING WITH 316 SS HARDWARE FOR REVIEW AND APPROVAL COUPLING SHALL BE PROVIDED WITH EPOXY COATING AND SHALL BE INSTALLED WITH WAX TAPE WRAP.
APPROVED ----- STANDARD DRAWINGS
GENERAL MANAGER
Rincon D~~ Water~ , .. SEWER CONNECTION AT
CONCRETE ENCASEMENT DISlRICT ENGINEER
DWG. NO.
S-3
VARIABLE
STD. WYE, OR TEE
RINCON MAINT<? • I
VARIABLE
EXISTING OR PROPOSED WATER MAIN OR GAS MAIN
~ CUSTOMER MAINT.
NOTES: 1. SEWER LATERALS SHALL HAVE MINIMUM SLOPE OF
_ PROPERTY 2% EXCEPT AS OTHERWISE SPECIFICALL y NOTED ON THE PLANS.
I CLEANOUT SEE S g 2. PLUGS SHALL BE CEMENTED IN WITH CEMENT
- MORTAR, OR SHALL BE NEOPRENE STOPPER OR APPROVED EQUAL.
STD. PLUG
3. IN NO CASE SHALL A LATERAL CONNECT TO THE SEWER MAIN DIRECTLY ON TOP OF THE PIPE.
4. WHERE A STANDARD SADDLED TEE IS ADDED, IT SHALL BE SURROUNDED WITH 4" OF CLASS "A" PORTLAND CEMENT CONCRETE IN ACCORDANCE WITH STD. DWG. S-6 & S-7.
STD. "CUT IN" CONNECTION AS APPROVED
5. LATERALS SHALL END AT THE PROPERTY LINE, UNLESS OTHERWISE NOTED ON THE PLANS.
PLACE 2" X 4" (MIN.) MARKER AT END OF PLAN
1-1 /2" LETTER "S" MARKED IN FACE OF CURB
PROPERTY CLEANOUT SEE S-9
EACH LAT~TL
SURFACE OF STREET
4" MIN. TO 12' MAX. (SEE DWG S-5 WHERE HEIGHT IS OVER 12')
AL TERNA TE ELEVATION
~
EXISTING OR ~ I PROPOSED ~ WATER MAIN (PER OHS) OR GAS
REVISION DAlE BY DESCRIPTION
1---+---+--+----------1
ANGLE VARIABLE (MAX. 45")
ELEVATION
MIN. SLOPE UP 2% SEE NOTE 1
PIPE BEDDING OF 3/4" CRUSHED ROCK (1" BELOW BELL)
* WHERE UTILITY TRENCH IS PROPOSED BACK OF CURB SEWER LATERAL SHALL HAVE 5' -0" COVER BELOW CURB GRADE AT PROPERTY LINE.
lO I
t0
I( PROPERTY LINE
NOTES CONT.: 6. UNLESS WAIVED BY THE ENGINEER, 2" WIDE
METALLIC DETECTABLE LOCATOR TAPE SHALL BE PLACED WITH EACH LATERAL APPROX. 6 INCHES ABOVE THE PIPE, BUT NOT GREATER THAN 6 FEET DEEP.
7. WHERE SEWER LATERAL CROSSES ABOVE AN EXISTING OR PROPOSED WATER MAIN, USE D.I. PIPE (4" CL 51/ 4" CL 80) WITH HOT DIP BITUMINOUS COATING 10' EACH SIDE OF WATER MAIN.
8. MINIMUM 10'-0" SEPARATION BETWEEN SEWER LATERAL AND WATER SERVICE
9. MINIMUM 3'-6" SEPARATION BETWEEN SEWER LATERALS AT MAIN
MIN. SLOPE UP 2% SEE
APPROVED -----
GENERAL MANAGER
DISTRICT ENGINEER
NOTE J..
\_ BENDS AS REQUIRED TO SUIT FIELD CONDITIONS
STANDARD DRAWINGS
Rincon o~ ..
VARIABLE SEE DWG S-5 WHERE 12' OR HIGHER
DWG. NO.
Water~ ! SEWER LATERAL NORMAL CUT S-4
REVISION DAlE BY
SURFACE OF STREET ~
t .. . EXISTING OR PROPOSED WATER MAIN OR GAS MAIN (PER DHS)
SEWER MAIN
VARIABLE LENGTH
TRENC WIDTH
TRENCH WIDTH
PLAN
DESCRIPTION
z ~
io MIN.
2-45" BEND
THE VERTICAL PIPE SHALL BE BRACED WHILE BACKFILLING TRENCH
560-C-3250 CONCRETE BASE
STANDARD WYE, TEE, OR WYE SADDLE STANDARD CUT IN CONNECTION AS APPROVED.
APPROVED -----1----+---+---+----------t Rincon nt~~ Water~ ! GENERAL MANAGER
DISlRICT ENGINEER
,. .. ~ 0 z w w (/)
SLOPE 2%
VARIES, 12' MIN. OR AS DIRECTED BY DISTRICT. WHEN THIS DISTANCE IS 12' OR OVER USE DEEP CUT LATERAL CONNECTION AS SHOWN HEREON, UNLESS OTHERWISE SHOWN ON PLANS.
NOTES: 1. SEE DRAWING S-4 FOR DETAILS OF
SEWER LATERAL TO PROPERTY LINE.
2. USE CLASS 'C' CONCRETE WHERE SHOWN.
3. IN NO CASE SHALL A LATERAL CONNECT TO THE SEWER MAIN DIRECTLY ON TOP OF THE PIPE.
4. UNLESS WAIVED BY THE ENGINEER 2" WIDE METALLIC DETECTABLE LOCATOR TAPE SHALL BE PLACED WITH EACH LATERAL APPRXIM A TEL Y 6 • ABOVE THE PIPE.
5. MINIMUM 10' SEPERATION BETWEEN SEWER LATERAL AND WATER SERVICE. (PER DEPARTMENT OF HEALTH AND SAFETY)
6. WHERE UTILITY TRENCH IS PROPOSED BACK OF CURB SEWER LATERAL SHALL HAVE 5'-0" COVER BELOW CURB GRADE AT PROPERTY LINE.
STANDARD DRAWINGS
SEWER LATERAL DEEP CUT
DWG. NO.
S-5
SUBMIT V.C.P. COLLAR TEE SADDLE FOR APPROVAL, EPOXIED IN PLACE PRIOR TO ENCASING.
X 4: ~
b ! .,_
. ..-
• <I 4_ ·_s.,_·.4·· · . ... . i ·Z · ~- .. . · .
~. ·.,_v :iil · ... .i .: ., . . . . ..
WHERE A 1 /8 BEND IS NOT USED, A ONE FOOT PIECE OUT OF TEE IS REQUIRED .
560-C-3250 CONCRETE
SECTION - SEWER LATERAL
REVISION DAlE BY DESCRIPTION 1----1-+--+----------l APPROVED ----
GENERAL MANAGER
DISlRICT ENGINEER
Rincon ,i"::~~ Water~ !
STANDARD DRAWINGS
SEWER LATERAL VCP SADDLE CONNECTION
DWG. NO.
S- 6
REVISION DAlE BY DESCRIPTION
45· STREET ELBOW
TEE & WYE SADDLES PER MANUFACTURERS SPECIFICATIONS AND TO BE TIGHTENED WITH TWO STAINLESS STEEL BANDS AROUND PIPE AND SADDLE, WITH 316SS NUTS AND SOL TS.
~~~~- CUT HOLE WITH SABER SAW OR SHELL CUTTER
SECTION - SEWER LATERAL
i-------+-+-+-------~ APPROVED ___ _ STANDARD DRAWINGS
SEWER LATERAL PLASTIC PIPE
SADDLE CONNECTION
DWG. NO.
GENERAL MANAGER S-7 DISTRICT ENGINEER
REVISION DA1E BY DESCRIPTION
P.V.C. PIPE
COUPLING ---
NOTES:
FLEXIBLE COUPLING (NON-PRESSURE)
1. NO CONNECTION ALLOWABLE AT BELL END OF V.C.P. CUT BELL END OFF V.C.P. PRIOR TO MAKING CONNECTION.
2. SEWER TRANSITION COUPLING SHALL BE ROMAC WITH 316SS NUTS AND BOLTS, OR APPROVED EQUAL
3. COUPLINGS SHALL BE EPOXY COATED AND WRAPPED IN 10 MIL. POLYETHYLENE BAG.
APPROVED -----1------+----1--------------1 Rincon o~~~ Water~ , GENERAL MANAGER
• DISTRICT ENGINEER
VITRIFIED CLAY PIPE
STANDARD DRAWINGS
CONNECTING DISSIMILAR SEWER PIPES
DWG. NO.
S-8
0
THREADED CAP WITH SQUARE NUT
VARIES
4" OR 6" SEWER LATERAL PER RDDMWD STANDARDS
WYE PER UNIFORM BUILDING CODE
CAP AND PLUG AT fr.
z ~
b I
in
CURB AND GUTTER
ROAD SURFACE
TYPICAL SEWER SERVICE CONNECTION NO SCALE
NOTES: 1. PLACE CLEANOUT A MAXIMUM OF 1'-0"
FROM PROPERTY LINE WITHIN R/W
2. STANDARD CLEANOUT COVER PER S-30
3. INSPECTOR MAY REQUIRE VIDEO TAPING OF LATERAL TO MAIN TO ENSURE LATERAL IS CLEAR AND CONNECTED.
4. CLEANOUT IS REQUIRED FOR ALL RESIDENTIAL LATERALS.
5. ANTI-FLOOD DEVICES TO BE INSTALLED ON ALL LATERALS WHERE THE FINISH FLOOR ELEVATION IS LOWER THAN THAT OF THE FIRST DOWNSTREAM MANHOLE PER S-29
6. FOR PAVED AREAS CLEANOUT COVER SHALL BE INSTALLED IN CONCRETE COLLAR PER S-18
REVISION DA 1E BY DESCRIPTION APPROVED ____ _
.,___-+--__ --+-----------1 GENERAL MANAGER
DISlRICT ENGINEER
Rincon D~~ Water~ !
STANDARD DRAWINGS
RESIDENTIAL CLEANOUT
DWG. NO.
S-9
BRANCH IF REQUIRED
(3 MAX)
SAME MATERIAL AS MAIN
, ••• I 16" l -".11·-MIN.
I = .-
, ... . ., .i.·
560-C-3250 CONCRETE B B I' .
· . ., .d ••
,II
A ' ,' ,II 4 :
SECTION A-A ELEVATION
NOTES: 1. THE UPPER END OF THE CHIMNEY PIPE WILL BE 8
FEET BELOW THE GRADE OF THE LOWER CURB, UNLESS OTHERWISE SPECIFIED.
2. WHERE ONE OR TWO HOUSE CONNECTION(S) ARE TO BE JOINED TO THE CHIMNEY PIPE USE A SINGLE "Y' BRANCH; WHERE THREE HOUSE CONNECTIONS ARE TO BE JOINED USE DOUBLE "y" BRANCH.
3. WHERE THE CHIMNEY PIPE IS TO BE USED FOR A SINGLE HOUSE CONNECTION FACE "y" TOWARDS PROPERTY TO BE SERVED; WHERE USED FOR HOUSE CONNECTIONS ON BOTH SIDES OF SEWER, THE "'(' WILL FACE TOWARD THE RIGHT (LOOKING UPGRADE) AND THE HOUSE ON THAT SIDE WILL BE CONNECTED TO THE "'(' BRANCH BY A 6-INCH 45"-DEGREE BEND, AND THE HOUSE CONNECTION ON THE LEFT WILL BE CONNECTED TO THE UPPER END OF THE CHIMNEY BY A 6-INCH 45"-DEGREE BEND UNLESS OTHERWISE SPECIFIED.
4. THE SEWER MAIN WILL BE CONSTRUCTED OF THE MATERIAL SPECIFIED ON PLANS.
5. INSTALL 2" X 4" REDWOOD MARKER ABOVE UPPER END OF CHIMNEY FOR REPAIR AND CONNECTION LOCATING.
REVISION DAlE BY DESCRIPTION APPROVED -----1----+---+-+------------1
GENERAL MANAGER
DISTRICT ENGINEER
SEWER .·.,
MAIN 1
A
I --J 16" r _l__ ,-------,
4" MIN.
SEWER
MAIN
SECTION B-B PLAN
ELEVATION
DO NOT ENCASE BEYOND BELL
Rincon D~ 6
Water~ -:
STANDARD DRAWINGS
SEWER CHIMNEY LATERAL
DWG. NO.
S-10
6" LATERAL
PLAN
SEWER MAIN
CLEAN OUT
PROPERTY LINE ""I 1" FINGER HOLE
56O-C-325O CONCRETE
INSTALL REUSABLE EXPANSION DOLLAR PLUG FOR TESTING. LEAVE PLUG TO WATERPROOF CLEANOUT.
T/1//1//1//1//1//1/f
COVER
CASTING SHALL BE ALHAMBRA FOUNDRY NUMBER A-1241 OR EQUAL AS APPROVED BY THE DISTRICT
.... i~ .
NATURAL GROUND CLEANOUT
l-17" PROFILE
PROPOSED GUTTER
CLASS 'A' CONC.
b I
in
EXIST. OR PROPOSED~, 1 1' MIN WATER OR GAS MAIN t._J_ OR OTHER FACILITY
SEWER MAIN 6" x 6" DOUBLE WYE TO BE LAID HORIZONTAL ( 4" WHEN SPECIFIED)
NOTES:
NOTES: 1. MIN. SLOPE 0.02' RISE PER FOOT
UNLESS OTHERWISE SPECIFIED ON PLAN AND PROFILE.
REVISION DAlE BY DESCRIPTION
PROFILE
APPROVED -----1---+-----+----+-----------i
GENERAL MANAGER
DISTRICT ENGINEER
1. UNLESS WAIVED BY ENGINEER. A 2" WIDE METALLIC DETECTABLE LOCATOR TAPE SHALL BE PLACED WITH EACH LATERAL APPROXIMATELY 6" ABOVE THE PIPE, BUT NO GREATER THAN 6' DEEP.
2. SEWER TREES ARE NOT TO BE USED EXCEPT WITH SPECIAL WRITTEN APPROVAL BY THE DISTRICT ENGINEER.
Rincon D~~ Water~ !
STANDARD DRAWINGS
SEWER TREE LATERAL & CLEANOUTS
DWG. NO.
S-11
CONCRETE COLLAR PER S-14
CAST IRON MANHOLE FRAME AND COVER ALHAMBRA A-1254 OR APPROVED EQUAL. COVER
-:.. REINFORCED POLYPROPYLENE COATED STEPS PER ASTM D478
/
SHALL BE MARKED RINCON SEWER.
FINISHED GROUND SURFACE ,.
... SLOPE = •_":. 1" IN 12" · •··
CX)
" -.;;t I u
::E I-
z (/)
::E <(
re:: 0 w I
0..
"" 0 w u 48" OR 60" re:: 0 SEE NOTE 5 LL z w
2" ~ re:: .....
"D"
A-A NOTES: 1. PRECAST REINFORCED CONCRETE MANHOLES SHALL CONFORM TO
THE REQUIREMENTS OF ASTM C478, LA TEST, AND SHALL BE DESIGNED FOR H-20 LOADING.
2. ALL MANHOLE SECTIONS AND GRADE RINGS SHALL BE JOINED WITH 3/8" THICK CEMENT MORTAR NEATLY STRUCK AND POINTED.
3. VERTICAL WALL OF CONE SHALL BE ON UPSTREAM SIDE OF MANHOLES.
4. WHEN A CHANGE OF PIPE SIZE AT THE MANHOLE IS SPECIFIED, THE PIPES WILL BE PLACED SO THAT THE TOPS OF THE PIPES ARE ALIGNED.
5. MANHOLE DIAMETER SHALL BE 48" FOR SEWER PIPE DIAMETERS 24" AND SMALLER, AND 60" FOR SEWER PIPE DIAMETERS 27• AND LARGER, AND FOR ALL MANHOLES WITH A DEPTH OF 12' OR MORE. 60" DIAMETER MANHOLES SHALL BE USED WITH A 36" CONE.
6. WHEN MANHOLE IS IN A STREET TO BE PAVED, MANHOLE FRAME SHALL BE SET AFTER PAVEMENT HAS BEEN PLACED. TOP OF MANHOLE SHALL BE INSTALLED PER STD. DWG. S-14
7. MANHOLES SHALL BE SPACED AT 500 FEET MAXIMUM INTERVALS, UNLESS SPECIFIED OTHERWISE.
8. ALL NEW MANHOLES ON SEWERS 15-INCHES OR GREATER DIA., ALL NEW MANHOLES WHERE ENTERING PIPE SLOPE IS 5% OR GREATER, ALL EXISTING MANHOLES WITH NEW CONNECTIONS, AND ALL MANHOLES WITHIN 1,000 FEET OF RECEIVING A FORCE MAIN DISCHARGE: THE MANHOLES SHALL BE PROVIDED WITH INTEGRALLY LOCKING PVC OR POLYURETHANE PROTECTIVE LINING SYSTEM PER SECTION 500-2 OF THE GREENBOOK.
REVISION DA1E BY DESCRIPTION APPROVED -----1----+----+-----1------------t
GENERAL MANAGER
DISTRICT ENGINEER
;i. N
re:: 0
SECTION B-B
WELL COMPACTED MA TERI AL 90% MINIMUM
GPK MANHOLE ADAPTER
6" MAX.
B
----7
I I I I
12" MIN 1.5' "D" MAX. L __________ _J
CONCRETE INVERTS SHALL BE TRUE TO GRADE AND ALIGNMENT W/ A SMOOTH FINISH
STANDARD DRA~NGS
Rincon D~~ Water~ ! PRE-CAST REINFORCED
ECCENTRIC CONC MANHOLE
A
DWG. NO.
S-12
ALL LATERALS~ MUST BE PLAC~D "'-. UPSTREAM OF~ 't_ OF MANHOLE
-----7
LADDER
HOUSE LATERALS
CONCRETE GROUT
....
PLAN
----48"----_.::
I I I I
I MIN. DIA O.D. OF I 1-M.H. RINGS + 4"~
SECTION A-A
NOTES:
1. REFER TO STANDARD DRAWINGS OF MANHOLES FOR DETAILS PERTAINING TO MANHOLES ONLY.
2. THE TOP ½ DIAMETER OF THE PIPE IS TO BE BROKEN OUT TO A NEAT LINE. BROKEN EDGES SHALL BE PLASTERED SMOOTH WITH CEMENT MORTAR.
3. THE MAXIMUM NUMBER OF LATERALS INTO A TERMINUS MANHOLE SHALL BE LIMITED TO FOUR.
4. TERMINUS MANHOLES WITH HOUSE LATERALS ARE NOT TO BE USED EXCEPT WITH SPECIAL WRITTEN APPROVAL BY DISTRICT ENGINEER.
REVISION DAlE BY DESCRIPTION APPROVED -----
A
LOCATION OF MANHOLE COVER
STANDARD DRAWINGS 1----+----+--1------------1 Rincon o't!.
GENERAL MANAGER
DISlRICT ENGINEER
Water~ ! TERMINUS MANHOLE WITH HOUSE LATERALS
DWG. NO.
S-13
NOTES: ALHAMBRA FOUNDARY CO. A-1254, OR APPROVED EQUAL
3/4" X 1" PRY NOTCH
3/4" DIA. PICK HOLE
CONCRETE COLLAR FOR PAVED AREA USE 56O-C-325O CONCRETE
REVISION DAlE BY DESCRIPTION
18"
N
t--t----i----t----------
--- 27 1 /2" DIA. --r 26-1 /4"
24" DIA. 4" ·~:
----- 32" DIA. ____ __,
1-1/2" HIGH CASTED LETTERS TYP. PLACES
DIAMOND TREAD PATTERN
18" • ~ • : • ·II.
CONCRETE COLLAR FOR UNPAVED AREA USE 56O-C-325O CONCRETE
APPROVED ___ _ STANDARD DRAWINGS DWG. NO.
Rincon o~ ..
GENERAL MANAGER Water~, • DISlRICT ENGINEER
MANHOLE COVER & FRAME STANDARD & WATERTIGHT S-14
NOTES: ALHAMBRA FOUNDRY CO. A-1325, SOUTH BAY FOUNDRY 1325 OR APPROVED EQUAL
4"
REVISION DAlE BY
39 3/4" DIA.
36" DIA.
L36"DIA._J SECTION A-A
CONCRETE COLLAR FOR PAVED AREA USE 56O-C-325O CONCRETE
DESCRIPTION
COVER
APPROVED -----1---+---+---+-----------1
GENERAL MANAGER
DISlRICT ENGINEER
A
L
18" FRAME
CONCRETE COLLAR FOR UNPAVED AREA USE 56O-C-325O CONCRETE
3/4"
STANDARD DRAWINGS
Rincon D:.6 Water~ , •
MANHOLE COVER & FRAME TWO COVERS
A
J
DWG. NO.
S-15
PLACE 2" x 4" REDWOOD HEADER IF MORE THAN 5' TO EXISTING PAVEMENT OR AS REQUIRED BY ENGINEER
AREA TO ~E PAVED
MANHOLE FRAME
MANHOLE COVER
0 I
in
b I
0
I MEET EXIST. PAVEMENT ________ 5'-0" _J I- OR MIN. OF 5'-0"
NOTES:
MEET EXISTING GROUND OR PAVEMENT
SLOPE AWAY FROM MANHOLE SEE NOTE (1)
1. SLOPE WILL CONFORM WITH RIGHT OF WAY JURISDICTION AGENCY IMPROVEMENT STANDARDS AND SPECIFICATIONS, AS APPLICABLE, OR MEET EXISTING CONDITIONS AS DIRECTED BY ENGINEER.
2. ANY PAVEMENT AREAS THAT MAY COLLECT STORM WATER AROUND MANHOLE WILL REQUIRE A RAIN-STOPPER INSERT.
REVISION DAlE BY DESCRIPTION APPROVED -----1---+--+---+-----------1
GENERAL MANAGER
DISTRICT ENGINEER
Rincon D~~ Water~ , •
2"x4" REDWOOD HEADER OR AS DIRECTED
STANDARD DRAWINGS
PAVING DETAIL AROUND MANHOLES
DWG. NO.
S-16
27"
4-Xt
4
1" HIGH LETTERS IN A 6" X 9" BOX
PICK HOLES (2) TO BE PLUGGED WITH CORK STOPPER FURNISHED BY CONTRACTOR (IF REQUIRED)
l ,a .. · 1
18" ·. : 4 3-¾" CLEAR OPENING 24" 3-¾'.
"' · 4 , OVERALL BASE 31-¾"
SECTION CONCRETE COLLAR FOR PAVED AREA USE 56O-C-325O CONCRETE
NOTES: 1. MANHOLE COVER SHALL BE DESIGNED FOR A.A.S.H.O. H-20
LOADING.
2. CAST IRON SHALL HAVE MINIMUM TENSILE STRENGTH OF 30,000 LBS. PER SQ. INCH.
3. MANHOLE COVER SHALL BE "ALHAMBRA FOUNDRY CO." TYPE A1176 OR APPROVED EQUAL.
REVISION DAlE BY DESCRIPTION
~-------+-----------1 APPROVED -----
GENERAL MANAGER
DISlRICT ENGINEER
CONCRETE COLLAR FOR UNPAVED AREA USE 56O-C-325O CONCRETE
4. RAISE ALL UNIMPROVED AREA MANHOLES ABOVE GRADE AND USE BOLT DOWN COVERS. (INSTALL GAURDPOSTS).
5. RAINSTOPPERS TO BE INSTALLED WHERE STORM WATER COULD COLLECT OVER MANHOLE.
Rincon o!'~., Water~ , •
STANDARD DRAWINGS
MANHOLE COVER & FRAME LOCKING TYPE
DWG. NO.
S-17
EXPANSION COLLAR~ TEST PLUG TO REM~~~
AC
56O-C-325O CONCRETE
24"
12"
~
TOP
REVISION DAlE BY DESCRIPTION
VIEW
1----+----+----+-----------1
..
17"
1/8 SWEEP BEND OR 45· BEND
CONSOLIDATED TRENCH
BACKFILL
61
'&, ~I 1/8 SWEEP BEND OR 45· BEND
ALTERNATE MUST BE APPROVED BY DISTRICT ENGINEER PRIOR TO INSTALLATION.
ALTERNATE
ELEVATION
1" FINGER HOLE
~ TRENCH
WIDTH
._J
NOTES: 1. CLEAN-OUT IS TO BE USED FOR INDUSTRIAL OR COMMERCIAL
INSTALLATIONS ONLY.
2. CLEAN-OUT IS NOT TO BE SUBSTITUTED FOR MANHOLE.
3. CLEAN-OUTS ARE NOT TO BE PLACED ON LATERALS OVER 150' LONG.
4. CLEAN-OUT PIPE MUST BE SAME · DIAMETER AND MATERIALS AS MAIN LINE SEWER.
5. CASTING WILL BE ALHAMBRA FOUNDARY NO. A-1241, OR APPROVED EQUAL.
6. COVER FRAME AND CONCRETE PAD ARE TYPICAL FOR Bn I.D. MAIN LINE SEWERS.
7. PLUGS WILL BE CEMENTED IN PLACE WITH CEMENT MORTAR. NEOPRENE PLUGS OR APPROVED EQUALS MAY BE SUBSTITUED.
B. STATION OF WYE OR LOWER 1/B SWEEP BEND WILL CORRESPOND TO lHE CLEAN-OUT STATION SHOWN ON CONSTRUCTION DRAWINGS WITH CLEAN-OUT CONSTRUCTION EXTENDED BEYOND lHAT POINT AS NECESSARY.
9. USE ONLY 560-C-3250 CONCRETE FOR CONSTRUCTION.
APPROVED ----- STANDARD DRA¥.1NGS DWG. NO.
GENERAL MANAGER
DISlRICT ENGINEER
NON-RESIDENTIAL SEWER CLEAN-OUT S-18
Cf. STREET
6" Cf. SEWER MAIN
SURFACE OF STREET
SAMPLING MANHOLE
5'-0" MIN. COVER AT PROPERTY LINE 7 r 8" MAX.
TO JOINTS
_,.....,.._ ____ ..J....------.ri-r---~__,..,_ ___ A---¥--H-+-- 2% MIN. ---1
SEWER LATERAL MIN. SLOPE UP AT 2%
ELEVATION
/
ALHAMBRA FOUNDRY CO. 5" 24" DIA A-1264. PARKWAY LID OR
½_! __ ·1.---_,1_·---~· ~· .--I -, APPROVED EQUAL
-+---+---- !-
GPK MANHOLE ADAPTOR, OR APPROVED EQUAL.
-+-'=--::..~1:..-:..-:..--...s-""7"7 .. ::_~ ~~}/.~·::-~ ·\)/··:>/~/-_·r~ µ24" MAX.
~• MAX.
_.__ __ .....,,__
GPK MANHOLE ADAPTOR, OR APPROVED EQUAL.
NOTES:
36" DIA.
LONGITUDINAL VIEW OF SAMPLING MANHOLE
WELL COMPACTED MATERIAL 90% MINIMUM
4" MIN. I.D.
SECTIONAL VIEW OF SAMPLING MANHOLE
1. MANHOLE TO BE INSTALLED ON BUILDING SEWER AND LOCATED SUCH THAT THE MANHOLE WILL BE ACCESSIBLE AT ALL TIMES.
6. SEE DWG. NO. S-17 FOR DETAILS AND INSTALLATION OF MANHOLE COVER AND FRAME.
2. 35• MANHOLE TO BE AS CONSTRUCTED BY SOUTHWEST CONCRETE PROD. INLAND CONCRETE ENTERPRISES, OR EQUAL, AND MAY BE REINFORCED, OR NON-REINFORCED.
7. GRADE RINGS SHALL BE 24" I.D. EXCEPT AS OTHERWISE NOTED.
3. WHERE NO BUILDING SET-BACK IS AVAILABLE, SET MANHOLE IN PARKWAY AREA: WHERE MANHOLE MUST BE SET IN CONCRETE WALK, PLUG PICK HOLE FLUSH. LOCATE MANHOLE TO CLEAR OTHER UTILITIES.
4. CONCRETE BASE SHALL BE OF CLASS 560-C-3250 CONCRETE AND PLACED IN ONE OPERATION. CONCRETE INVERTS SHALL BE TRUE TO GRADE AND ALIGNMENT, AND FINISHED WITH A SMOOTH SURFACE. SPECIAL CARE SHALL BE USED IN FORMING ALL CHANNELS TO FACILITATE THE FLOW OF SEWAGE.
5. ALL MANHOLE TOPS SHALL BE INSTALLED WITH THE MANHOLE COVER OVER THE DOWNSTREAM INLET, EXCEPT AS OTHERWISE SPECIFIED.
REVISION DAlE BY DESCRIPTION
1-----+----4----------- APPROVED -----
GENERAL MANAGER
DISlRICT ENGINEER
8. JOINTS SHALL BE 3/8" THIKCNESS CEMENT MORTAR NEATLY STRUCK AND POINTED.
9. ALL SAMPLING MANHOLES MUST HAVE PROVISIONS FOR POWER AND COMPOSITE SAMPLER IN LOCKABLE CABINET.
Rincon o~ ..
Water~ --•
STANDARD DRAWINGS
36" I.D. SAMPLING MANHOLE
DWG. NO.
S-19
LAMP HOLE FRAME AND COVER ALHAMBRA FOUNDRY NO. A-1240 OR EQUAL
NOTES: 1. ALL MANHOLE TOPS WILL BE INSTALLED
WITH THE M.H. COVER AND STEPS OVER THE DOWNSTREAM OUTLET.
2. ALL PIPES AND FlTTlNGS SHALL BE CONSTRUCTED OF VITRIFIED CLAY OR POLY-VINYL CHLORIDE AND SHALL BE 8" MIN. DIA.
3. UPON APPROVAL FROM DISTRICT ENGINEER, DROP MANHOLE MAY BE INTERNAL TYPE BY RELINER, OR EQUAL.
CONCRETE SUPPORT 560-C-3250
REVISION DAlE BY DESCRIPTION
1-----1-------1-------1-------------, APPROVED ;...· -----
GENERAL MANAGER
DISlRICT ENGINEER
PLAN VIEW
ELEVATION
Rincon n~~ Water~ !
PRE-CAST ECCENTRIC CONCRETE MANHOLE PER STD. DWG. NO. S-12
OPTIONAL INTERNAL DROP MANHOLE, SEE NOTE 3.
STANDARD DRAWINGS
DROP MANHOLE
DWG. NO.
S-20
STEEL CASING OR OTHER APPROVED MATERIAL
REDWOOD SKIDS FULL LENGTH OF CASING
H
__..---=-6 '_' MAX.
PULL
H ~ ALL WOODEN SKIDS ~ TO BE SQUARE
NOTES:
1. ENDS OF THE CASING PIPE SHALL BE CLOSED AROUND THE CARRIER WITH A POURED-IN PLACE PLASTER-OF-PARIS OR CEMENT PLUG WITH A SMALL OPENING LEFT FOR DRAINAGE AT THE BOTTOM OF THE DOWNSTREAM SIDE ONLY (OR AS DIRECTED)
2. STEEL CASING SHALL BE INSTALLED BY MEANS OF JACKING OR DRY BORING, EXCEPT WHERE SPECIFlCALL Y NOTED ON THE PLANS TO BE INSTALLED BY OPEN TRENCH CONSTRUCTION.
3. CASING DIA. SHALL BE MINIMUM OF 4" GREATER THAN THE OUTSIDE BELL DIA., EXCEPT SEWER PIPE CASING SHALL NOT BE LESS THAN 30" IN DIA. WHEN CASING IS BORED, UNLESS SPECIFICALLY NOTED.
4. THE STEEL MIN. CASING THICKNESS SPECIFIED IN "TABLE A" IS REQUIRED FOR CASING IN PLACE AND DOES NOT ACCOUNT FOR CONSTRUCTION LOADS. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE STRUCTURAL SUFFICIENCY OF THE CASING DURING CONSTRUCTION, AND ALSO THE METHOD OF INSTALLATION.
PIPE COUPLING OR BELL
TABLE "A" (STEEL)
THICKNESS •r DIAMETER "D" STREETS & HWYS.
(INCHES} UP TO 150' OVER 150' RAILROADS
IN LENGTH IN LENGTH
4"-10" I.D. 1/4" 1/4" 4•-12· : 1/4"
12"-16" O.D. 3/8. 3/8" 4•-15• : 9/32· 5. GRAVITY SEM:R PIPELINES AND PRESSURE PIPELINES SHALL BE
SUPPORTED ON PIPE SKIDS SUBJECT TO THE APPROVAL OF THE ENGINEER. C.M.L &: C. PRESSURE PIPE MAY REST ON THE BOTTOM OF THE CASING, BUT SHALL NOT BE DRAGGED INTO POSl110N WITHOUT PIPE SKIDS.
18"-20· o.o. 3/8. 3/8" 18.:5/16" 20:11/32•
6. ALL SKIDS SHALL BE SQUARE IN CROSS SECTION AND MADE FROM REDWOOD.
7. SKIDS SHALL BE ATTACHED TO PIPE BY STRAPPING WITH A STANDARD STRAPPING MACHINE TO HOLD SKIDS IN PLACE DURING PULLING OPERATION. USE STAINLESS BAND, OR METHOD OF CLEA TING SKIDS TOGETHER.
8. FLEXIBLE PIPE (PVC, ETC.) SHALL HAVE SPACER GUIDE ALONG THE TOP TO PREVENT PIPE FROM FLOATING. FOR ENDS OF CASING PIPE, SEE NOTE (1). PIPE WITHIN CASING TO BE BONDED TOGETHER AT THE JOINTS FOR AN INTEGRAL UNIT PER MANUFACTURERS RECOMMENDATION. TWO APPROVED FLEXIBLE COUPLINGS SHALL BE USED AT EACH END OF CASING, PER S-8.
9. NOTICE AS REQUIRED BY THE DISTRICT SHALL BE GIVEN PRIOR TO CONSTRUCTION FOR DISTRICT INSPECTION OF CASING PIPE AND CARRIER PIPE INSTALLATION. THE AS-BUILT LOCATION AND GRADE OF CASING PIPE SHALL BE APPROVED BY THE DISTRICT PRIOR TO INSTALLATION OF THE CARRIER PIPE. DEPARTURES FROM PLANNED LOCATION OR GRADE OF THE CASING PIPE SHALL REQUIRE A FIELD SURVEY FOR CARRIER PIPE REDESIGN IF FEASIBLE, OR ABANDONMENT IN FAVOR OF A NEW INSTALLATION.
REVISION DAlE BY DESCRIPTION
1------1---------------1 APPROVED ------
GENERAL MANAGER
DISTRICT ENGINEER
22· 0.0.
24• O.D.
2s• O.D.
28• O.D.
30• O.D.
32" O.D.
34"-36" 0.0.
38" O.D.
40" O.D.
42" O.D.
4B"-6o" o.D.
s2• - 72" O.D.
Rincon D~~ Water~ , •
3/8. 3/e· 3/8"
3/e· 3/8. 13/32"
3/8" 3/8. 7/16"
3/8" 3/8. 15/32"
1/2" 112· 1/2"
1/2" 1/2" 1/2"
1/2" 1/2" 17/32"
112· 1/2" 9/16.
1/2" 3/4" 9/16"
1/2" 3/4" 9/16"
1/2" 3/4" AS REQUIRED
3/4" 3/4" AS REQUIRED
STANDARD DRAWINGS DWG. NO.
PIPE CASING SEWER MAIN S-23
PROPOSED SEWER, SEWER LATERAL, OR STORM DRAIN
[FINISH GROUND SURFACE
ZONE 'D' NO JOINTS IN SEWER WITHIN 4' OF EITHER SIDE OF WATER MAIN.
PROPOSED SEWER, SEWER LATERAL, OR STORM DRAIN
CROSSING (PERPENDICULAR) CONDITION
NOTES:
SPECIAL PERMISSION
g•
6' 3'
PARALLEL CONDITION
ZONE "A" NO SEWER SHALL BE CONSTRUCTED WITHOUT SPECIAL APPROVAL FROM STATE DEPARTMENT OF HEALTH SERVICES AND RINCON DEL DIABLO MWD
ZONE "B" SEWER SHALL BE CONSTRUCTED OF EXTRA STRENGTH VITRFIED CLAY PIPE WITH COMPRESSION JOINTS, POLYVINYL CHLORIDE PLASTIC PIPE WITH RUBBER RING JOINTS (PER ASTM D 3034), OR DUCTILE IRON PIPE WITH COMPRESSION JOINTS. REQUIRES APPROVAL FROM RINCON DEL DIABLO MWD.
ZONE "C" SEWER SHALL BE CONSTRUCTED OF DUCTILE IRON PIPE WITH & "D" APPROVED COATING AND MECHANICAL JOINTS OR CONTINUOUS
SECTION OF CLASS 200 (DR14 PER AWWA C-900) POLYVINYL CHLORIDE PLASTIC PIPE CENTERED OVER PIPE BEING CROSSED.
ZONE "p" NO SEWER LINE CONSTRUCTION ALLOWED.
REVISION DAlE BY
1. UPON APPROVAL FROM DISTRICT ENGINEER HOPE FUSION WELDED PIPE MAY BE USED AS A CASING WHEN MINIMUM JOINT DISTANCE CAN NOT BE MET.
DESCRIPTION 1--------+-----li------------1 APPROVED ----- Rincon n~ ..
GENERAL MANAGER Water~ --• DISTRICT ENGINEER
FINISH GROUND SURFACE
EXISTING WATER
STANDARD DRAWINGS
SEWER MAIN CROSSING EXISTING WATER
DWG. NO.
S-24
COVER ACCESS MUST BE PROVIDED AND BROUGHT TO FINISH GRADE.
INLET i.....---.f--,_, _i...---+----,,7 i.------+---,i 1--r=-~7~-CLE«ANOU~
REVISION DAlE BY
I II II I L ~ L _JL _JL _J PYRAMID PRECAST
CO. INC. PART NO. IW3 WITH SAMPLE BOX OR APPROVED EQUAL
PLAN 3 CHAMBERED INTERCEPTOR
EQUAL TO PIPE SIZE OR AS REQUIRED
STATIC WATER LEVEL
·: · • ·. :
... ·, .. ---~ .
~ 7n IJ \_PVC LINER} H
EACH HOLE :.· ..
.. ... .. ·. ~--·. ...·. ' . ···:., .: ·. ' ·.·. : ... ·.:. ·:: .· . . .
SECTION
NOTES: 1. LINK SEAL, OR EQUAL, REQUIRED ON
ALL PIPES WITH WALL PENETRATIONS.
DESCRIPTION
COVER SPECS: DISTRICT APPROVED GALVANIZED STEEL COVER WITH AASHTO H-20 TRAFFIC LOADING
....J <( w Cf)
a::: w I<(
:3:
12"
. . ~ . .
S-26 OR S-27 SAMPLE BOX
2" WITH 24" FEATHER EDGE INTO EXISTING GRADE
;. 24" ••. ... '•_J • -~ . . • 4! .. .. . :~-
l~fl_J ··. • ... :
TRAP AS REQUIRED BY PLUMBING CODE
CLEANOUT & VENT AS REQUIRED BY LOCAL PLUMBING CODE
1----------------1 APPROVED ---- Rincon o~ ..
STANDARD DRAWINGS
SAND/OIL SEPARATOR
(CONT'D)
DWG. NO.
GENERAL MANAGER Water~ , • S-25 DISlRICT ENGINEER
BOX TO BE SET 2" ABOVE FINISHED GRADE AND FEATHERED INTO FINISHED GRADE TO AVOID TRIP HAZARD
= N
A-LOK GASKET OR LINK-SEAL, TYP. ALL VAULT PENETRATIONS. __ _._EL-,
GAL VAN I ZED STEEL PLATE COVER: A NON-SKID SURFACE SUCH AS DIAMOND PLATE OR OTHER APPROVED SURFACE IS REQUIRED FOR THE COVER PLATE IF THE BOX IS LOCATED IN A PEDESTRIAN OR VEHICULAR TRAFFIC AREA, A 3/4" DIA. HOLE MUST BE DRILLED 6" FROM ANY EDGE OF COVER.
1 1/8" ANGLE IRON LIP
FLOW
PYRAMID PRECAST CO. INC. MODEL NO. SB-22 OR APPROVED EQUAL
'._· • • 4 .-_· • • • ~- • • • • • • .• . • .i . . :_ ~ : •·. ·: ·.· ·-.. : • ,
A
NOTES:
SECTION A-A
= ..-
32"
PLAN
1. AU. SURFACE WAlER SHALL DRAIN AWAY FROM THE SAMPLE BOX.
4"
2. LID AND ANGLE IRON THICKNESS WILL DEPEND ON TRAFFIC PATTERNS IN SAMPLE BOX AREA.
3. INSTALl.AllON IN ACCORDANCE WITH AU. LOCAL PLUMBING CODES.
4. AU. PIPE PENETRATIONS REQUIRE LINK-SEAL, OR EQUAL
l-!!RE~Vl~SION~D!!!AlE:::+-=::-BY-4-_ ___:D=ESCR=IP..a.:..:llON"-'-----, APPROVED -----
Rincon o~ ..
GENERAL MANAGER Water~ , • DISlRICT ENGINEER
52O-A-3OOO CONCRETE
A
J
STANDARD DRA\\1NGS
SAMPLE BOX #1 (INDUSTRIAL)
DWG. NO.
S-26
BOX TO BE SET 2" ABOVE FINISHED GRADE AND FEATHERED INTO FINISHED GRADE TO AVOID TRIP HAZARD
w a.. 3/8" PED.
GALVANIZED STEEL PLATE COVER: A NON-SKID SURFACE SUCH AS DIAMOND PLATE OR OTHER APPROVED SURFACE IS REQUIRED FOR THE COVER PLATE IF THE BOX IS LOCATED IN A PEDESTRIAN OR VEHICULAR TRAFFIC AREA. A 3/4" DIA. HOLE MUST BE DRILLED 6" FROM ANY EDGE OF COVER.
.....Jo:::
.....J 1 /2" TRAFFIC
1 1/8" ANGLE IRON LIP 3=f2
~:r: a.. 1-LLJ a.. Cl~
.....Jz
::io 0::::0 wz >w 0 a..
w Cl FLOW
~~:
. ..,. ___ _..;;;;2;;.._;4_" ___ ~ •·.~ · \.· .
;,,4 , •
~ >:~· .·.::>>~:_. :~. _:,Jl..------52O-A-30OO _.__ ________ ___, ___ .__........._ ________ --'--'---'-......,........_. CONCRETE
SIDE VIEW
32"
4 ,
END VIEW
NOTES:
1. ALL SURFACE WAlER SHALL DRAIN AWAY FROM THE SAMPLE BOX.
· .. ~ 1~ ... 4" · .. 4'
PYRAMID PRECAST CO. INC. MODEL NO. ESB-22-2 OR APPROVED EQUAL
TOP HALF OF PIPE REMOVED AFTER CONSTRUCTION
2. LID AND ANGLE IRON THICKNESS WILL DEPEND ON TRAFFIC IN SAMPLE BOX AREA
3. INSTALLATION IN ACCORDANCE WITH ALL LOCAL PLUMBING CODES.
4. A-LOK GASKETS REQUIRED 8" IMMEDIA lEL Y ADGACENT TO SAMPLE BOX.
5. ALL PIPE PENETRATIONS REQUIRE LINK-SEAL, OR EQUAL.
REVISION DAlE BY DESCRIPTION 1---~----1-----+--------~ APPROVED -----
GENERAL MANAGER
DISlRICT ENGINEER
Rincon o't:~~ Water~ !
STANDARD DRAWINGS
SAMPLE BOX #2 (COMMERCIAL)
DWG. NO.
S-27
CLEANOUT AS REQUIRED PER LOCAL PLUMBING CODE.
BUILDING 01/ COLLECTING
AREA
I \ RECEPTOR OR FLOOR DRAIN
INSTALL CLEAN OUT PER RDDMWD
STD. DWG. S-11 RESTROOM LINE
S-26 OR S-27 SAMPLE BOX REQUIRED
INTERCEPTOR REQUIREMENTS TO BE DETERMINED BY DISTRICT
w z :::J
a:::: w 3: w en
PYRAMID PRECAST TYPICAL INSTALLATION CO. INC. MODEL NO. IW2
WITH SAMPLE BOX
DISTRICT APPROVED GALVANIZED STEEL COVER WITH H-20 TRAFFIC LOADING
· : ~ ... . .... . . . ..
PVC LINER~
. . • : 4 . .. • . . ~ . . ·. . .. . . .
2 CHAMBER INTERCEPTOR
NOTES:
1. ALL INTERCEPTORS SHALL HAVE A MINIMUM LIQUID CAPACITY OF 750 GALLONS. PROVIDE SIZING CALCULATIONS.
2. ALL WASTEWATER EXCLUDING RESTROOMS, MUST PASS THROUGH THE INTERCEPTOR. KITCHEN DESIGN SHALL BE SUBMITED TO DISTRICT FOR REVIEW AND APPROVAL.
3. ALL SURFACE WATER SHALL DRAIN AWAY FROM THE INTERCEPTOR.
4. GREASE INTERCEPTOR SHALL BE IN ACCORDANCE W/ THE LATEST UNIFORM PLUMBING CODE (UPC) REQUIREMENTS, SECTION 1014.
5. LINK SEAL, OR EQUAL, REQUIRED ON ALL PIPES WITH WALL PENETRATIONS.
REVISION DAlE BY DESCRIPTION
OR APPROVED EQUAL
2" WITH 24" FEATHER EDGE INTO EXISTING GRADE
INSTALL CLEANOUT PER RDDMWD STD DWG. S-11
. .. . .•..
L S-26 OR S-27 SAMPLE BOX AS SPECIFIED
12" BY DISTRICT
.. .... .. ~
STANDARD DRAWINGS DWG. NO. APPROVED -----1---+---+---+---------1 Rincon o~ ..
GENERAL MANAGER Water~ ! GREASE INTERCEPTOR S-28 DISlRICT ENGINEER
REVISION DAlE BY
TYPICAL BACKFLOW VALVE ASSEMBLY LOCATION
BUILDING
NOTES:
MAINTAINED BY OWNER
I /PROPERTY LINE r I CLEANOUT PER S-9
SEE DETAIL "A" 2% MIN. SLOPE OR AS APPROVED BY LOCAL AGENCY
COVER LID~..-~------,
SEWAGE BACKWATER VALVE
DETAIL "A" SEWAGE BACKFLOW VALVE ASSEMBLY
1. BACKWATER VALVE REQUIRED FOR PAD ELEVAllONS BELOW RIM ELEVA llON OF UPSTREAM MANHOLE.
DESCRIPTION 1-------4--1---1-----------1 APPROVED ----
, Rincon n~ .,
Water~ -"
STANDARD DRA\\1NGS
GENERAL MANAGER
DISTRICT ENGINEER •
TYPICAL BACKFLOW VALVE ASSEMBLY & DETAIL
DWG. NO.
S-29
NOTES: ALHAMBRA FOUNDRY 1208, OR APPROVED EQUAL
A
1/2"
1"
REVISION DAlE BY
\
B
/ /
BOTTOM VIEW
'W
·x·
•z•
SECTION A-A
DESCRIPTION APPROVED ---
t-----1i----t---t-----------1
GENERAL MANAGER
DISlRICT ENGINEER
A
1/2"
SIZE ·w· 6"¢ PIPE 9-3/4"
8"¢ PIPE 11-3/4"
Rincon D~~~ Water~ !
1 /2" HIGH LETTERS, RAISED 1/8"
TOP VIEW
II 3/4"
SE
·x· •y•
4-3/4" 7-1/2"
6-3/4" 9-1/2"
STANDARD DRAWINGS
RESIDENTIAL CLEANOUT COVER
•z· 7-3/4"
9-3/4"
DWG. NO.
S-30